Fault Current Calculation
Fault Current Calculation
Fault MVA at 3.3kV Bus at MCC M3SA MVA values Upstream (in Series) Utility MVA Cable 1 MVA Combined Series MVA MVA values in Series downstream Motor 1 MVA Cable 1 MVA Combined Series MVA - Motor 1 Motor 2 MVA Cable 2 MVA Combined Series MVA - Motor 2 Motor 3 MVA Cable 3 MVA Combined Series MVA - Motor 3 Motor 4 MVA Cable 4 MVA Combined Series MVA - Motor 4 Motor 5 MVA Cable 5 MVA Combined Series MVA - Motor 5 MVA values in Parellel Sum of Parellel MVA in the bus (Sum of all motor MVA) Hence, Fault MVA at 3.3kV Bus at MCC M3SB A+B = = 207.827 MVA 36.35926 kA B = 24.75893 MVA = = = = = = = = = = = = = = = 3.36 645.2491 3.338348 MVA 4.46 645.2491 4.429889 MVA 4.65 645.2491 4.613148 MVA 4.65 645.2491 4.613148 MVA 7.96 314.7556 7.764399 MVA A = = = 250 683.7841 183.068 MVA
Fault MVA at 415V Bus - A at MCC NEW MCC MVA values in Series Upstream Transformer 1 MVA Combined MVA at Source (3.3kV Swgr) Combined Series MVA - Upstream C = = = 15.00 207.827 13.99025 MVA