Product Overview

Salient Features
The Calix series was designed to provide compact, reliable switching
& protection solutions for MV distribution network. With over 50,000
VCB's in operation globally, this time tested product is in service from
1986. Needless to mention, the product had several design upgrades
& comply to the quality standards as per IEC 62271 - 100, 200.
The Calix truck is of same pedigree for the entire range that ensures
standardisation & ease for operator. The performance & reliability of
the VCB has increased many folds with the compliance of M2 Class -
extended mechanical endurance. The aesthetically designed &
compact product guarantees maximum operator safety, with a
combination of mechanical & electrical interlocks.
Vacuum Contactor
When the application demands for frequent switching operation,
Vacuum contactors are used in place of VCB Truck. These can be
used for protection & control of Motor feeders & Capacitor bank.

4Floor rolling type breaker with horizontal isolation & horizontal
draw-out.
4Inaccessible live parts & rack in/out with door closed condition
ensures operator safety.
Indoor Circuit Breaker
4Compartmentalized Panel with built in base frame & ramp.
4CG make highly reliable vacuum interrupters & protection relays.
4Type tested for extended mechanical endurance of M2 class as
per IEC 62271 100, ensuring 10,000 operating sequences.
4Stringent Electrical parameter compliance (E2 & C2) can be
provided on demand.
4Tested for rapid auto reclosing duty with SCADA compatible
control system.
4The optional features like draw-out type PT, Powerpack, Integral
earth switch, series trip arrangement for unmanned substation
(without auxiliary supply) can be provided.
4Internal arc tested as per IEC 62271-200.
4Fully type tested product at renowned testing laboratories like
KEMA - Netherlands, KERI Korea, CPRI / ERDA - India.
Earthing Device
The following variants are available:
4Integral Earth Switch
4Portable earthing truck
Characteristics Units VCB
Rated Voltage kV Upto 12 (Calix)*
Rated Current Amp Upto 800 Upto 1250 Upto 2000 Upto 2500 Upto 3150 Upto 4000
No of poles nos 3
Frequency Hz 50/60
Symmetrical Breaking Capacity kA rms for 3sec 13.1 20 26.3 31.5 40 50
Making Capacity kApk 32.75 50 65.75 78.75 100 125
Power Frequency Withstand Voltage kV rms 28 (std) / 35 (optional)
Impulse Withstand kVpk 75 (std) / 95 (optional)
Operating Duty cycles O-0.3sec-CO-3min-CO (Rapid Autoreclosing Duty)
Total Break Time cycles 3 3.5
Make Time cycles 3
DC Component % < 50%
Degree of protection IP 4X (std) / IP 5X (optional)
Applicable Standard IS 13118, IEC 62271-100 / 200
* Rated Voltage : 15 / 17.5 kV avaliable for export market
Technical Data
VCB Panel
Calix Truck
12 kV Vacuum Circuit Breaker
Technical data for Vacuum Contactor
Parameters Value
Rated Voltage kV Upto 7.2 12
Rated Current A 400 400
Short Time Current kA * 9 9
Rated P.F withstand Voltage 20 28
Impulse Withstand 60 75
* For higher kA level suitable HT HRC Fuses can be provided
Dimensions
CB Type Variant W x D x H (mm)
Fault Level: upto 26.3 kA,
Rated Current : upto 1250 A 705 x 1805 x 1830
BIL: 28/75 kV/kVp
Fault Level: 26.3 to 31.5 kA,
Calix Rated Current : upto 1250 A 650 x 2060 x 2220
BIL: 35/95 kV/kVp
Fault Level: Upto 50 kA
Rated Current : 1600 to 4000 A 800 x 2060 x 2220
Ordering Information
Please furnish the following details while making an enquiry / order
Parameters Value
Application Feeder / Transformer / Motor / Capacitor / Generator Protection
Site Conditions Altitude / Pollution / Reference ambient temperature
Rated Voltage (Range: 3.6 to 12 kV)
Symmetrical Breaking Capacity (Range: 13.1 to 50 kA)
Rated current (Range: 400 to 4000 A)
Frequency 50/60 Hz
System Earthing Effectively Earthed/ Unearthed/ Non effectively Earthed
Bus bar Type Copper / Aluminium
CT Details Ratio / Burden / Class Accuracy
PT Details Ratio / Burden / Class Accuracy / Fixed or Draw-out type
Protection Relay Function - Provide ANSI code
Electromechanical / Numerical
If Communicable, please provide protocol
Meters A / V / F / PF / kWH / TVM etc.
Control Supply Voltage 24/30/48/110/220 V or Power Pack
Note: All other accessories shall be provided as per our standard. Please specify for any specific accessory requirement.
General Arrangement Drawing
W
H
D
B Y R
VCB
TRUCK
CT
VT
CABLE
GLAND EARTHING
BUSBAR
BUSHING
PANEL
PLATE
VCB
SWING
SPOUT
POWER
SIDE VIEW FRONT VIEW
Indoor Circuit Breaker 12 kV Vacuum Circuit Breaker