ZAZMAT POWER STATION

ELECTRICAL LOAD LIST

REFERENCE:

Main Contractor :

XXXX
XXXX

SINGLE LINE DIAGRAM (Existing)


SINGLE LINE DIAGRAM (Existing)

XXXX
XXXX
XXXX

KEY SINGLE LINE DIAGRAM


DETAILED SINGLE LINE DIAGRAM
ELECTRICAL LOAD LIST

Engineering Consultant:

CONTRACT No. XXXXX

TITLE

ZAZMAT POWER STATION


ELECTRICAL LOAD LIST
B

Re-issued for Construction

02.03.08

xxx

xxx

xxx

Approved for Construction

10.01.08

xxx

xxx

xxx

REV.

DESCRIPTION

DATE

DWN CHK

APPD

THIS IS AN EXCEL SHEET AND MUST NOT BE ALTERED MANUALLY


APPD

APPD

DWG

NO.

xxxx-xxxx

ORIG. SHEET SIZE: A3

SHT

EXCEL FILE:

01

OF

REV.

05
001

RESTARTING

NONESSENTIAL

ESSENTIAL

DESCRIPTION

VITAL

EQUIPMENT
NO.

PANEL

ITEM NO.

EQUIPMENT
ABSORBED
LOAD

kW

33-SB-3303 SWITCHBOARD (0.415kV) LOAD SUMMARY

1
2
3
4
5
6
7
8
9
10
11

MOTOR
RATING

LOAD FACTOR
(=A/B)

EFFICIENCY
at load
factor C

C IN DEC.
B IN DEC
D
kW B
DES
ACT.
C

D
D
B

POWER
FACTOR
at load
factor C
COS PHI

KW=A/D

CONSUMED LOAD( EXISTING+ADDITIONAL)

CONTINUOUS (Sum C)
kW
DES.

kvar
ACT.

DES.

kvar=kW*tg phi
STAND-BY (SumS)

INTERMITTENT AND SPARES (SumI)

E
ACT.

kW
DES.

kvar
ACT.

DES.

ACT.

kW
DES.

kvar
ACT.

DES.

33-DB-3303-02 Distribution Board DG Building (0.415kV)

5.5

3.5

1.2

0.7

0.1

0.0

33-DB-3303-01 Distribution Board Telemetry Building (0.415kV)

17.3

6.1

3.0

1.8

0.1

0.0

58.75

44.06

58.96

44.13

24 Volts DC Battery Charger - 1, (Duty Power Supply)

5.00

5.00

1.00

0.95

0.85

5.26

3.26

24 Volts DC Battery Charger - 2, (Standby Power Supply

5.00

5.00

1.00

0.95

0.85

5.26

3.26

110 Volts DC Battery Charger - 1, (Duty Power Supply)

1.65

1.65

1.00

0.95

0.85

1.74

1.08

110 Volts DC Battery Charger -2, (Standby Power Supply

1.65

1.65

1.00

0.95

0.85

1.74

1.08

PACU-01

47

47

1.00

0.8

0.80

58.75

44.06

0.53

0.33

PACU-02

47

47

1.00

0.8

0.80

PACU CONTROL PANEL

0.5

0.5

1.00

0.95

0.85

Outdoor Process Area Welding Socket Outlet

16

20

1.00

0.95

0.85

16.84

10.44

Transformer Yard Welding Socket Outlet

10

1.00

0.95

0.85

8.42

5.22

29.42

18.23

Total Plant Running Load (TPRL) :


(Est. X% SumC + Y% SumI)
(Existing+Additional)

Total Plant Peak Load (TPPL) :


(Est. X% SumC + Y% SumI + Z% SumS)
(Existing+Additional)

105

KW

X = 100 %

111

KW

X = 100 %

68

KVAR

kW + kvar

KVAR

kW + kvar

ACT.

CABLE DETAILS
P=PVC
X=XLPE OR EPR
RATING=SITE RATING
NO.
P/X SQ.MM RATING

REMARKS

Calculated Value
Calculated Value
Vendor Data
Vendor Data
Vendor Data
Vendor Data
Calculated Value
Calculated Value
Assumed Value
Calculated Value
Calculated Value

125 kVA
TOTAL KVA
(Existing+Additional)

Y = 30 %

73

MEASURED
CURRENT

3.0 CALCULATION SHEET

96.06

62.71

DES.

115

132 kVA

Y = 30 % Z = 10 %

Power factor without compensation (cos phi)


Power factor with compensation (cos phi)

kVA =

kW + kvar

35

74

required capacitor rating [=kW (tg phi - tg phi)]

0.
:

0.
:

kvar

ACT.

NOTES:

REV.

DESCRIPTION

DATE

DWN CHK

APPD

APPD
(FERNAS)

APPD (QP)

DWG

NO.

2436-4107

SHT

02

OF

05
001

ABSORBED
LOAD

DG Building Indoor Lighting

0.87

0.87

1.00

DG Building Outdoor Lighting

0.20

0.20

1.00

DG Building Emergency & Exit Lights

0.09

0.09

DG Socket Outlet

0.50

0.50

Power Supply of DG Control Panel

3.00

DG Room Exhaust Fan Control Panel

0.50

VITAL

kW

Total Plant Running Load (TPRL) :


(Est. X% SumC + Y% SumI)
(Existing)

Total Plant Peak Load (TPPL) :


(Est. X% SumC + Y% SumI + Z% SumS)
(Existing)

NOTES:

EFFICIENCY
at load
factor C

C IN DEC.
B IN DEC
D
kW B
DES
ACT.
C

33-DB-3303 Distribution Board DG Building (0.415kV)

1
2
3
4
5
6

LOAD FACTOR
MOTOR &
(=A/B)
NON-MOTOR
RATING

KW

X = 100 %

KW

X = 100 %

KVAR

KVAR

KW=A/D

CONSUMED LOAD( EXISTING+ADDITIONAL)

CONTINUOUS (Sum C)
kW

kvar

COS PHI

DES.

0.95

0.95

0.92

0.30

0.95

0.95

0.21

0.07

1.00

0.95

0.95

1.00

0.85

0.85

3.00

1.00

0.80

0.80

3.75

2.81

0.50

1.00

0.85

0.85

0.59

kW + kvar

kW + kvar

ACT.

DES.

kvar=kW*tg phi
STAND-BY (SumS)

INTERMITTENT AND SPARES (SumI)

E
ACT.

kW
DES.

kvar
ACT.

DES.

0.59

0.36

0.36

0.59

0.36

5.46

3.55

1.18

0.73

DES.

ACT.

kW
DES.

kvar
ACT.

DES.

0.09

0.03

0.09

0.03

G
ACT.

CABLE DETAILS
P=PVC
X=XLPE OR EPR
RATING=SITE RATING
NO.
P/X SQ.MM RATING

REMARKS

Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value

7 kVA
TOTAL

Y = 30 %

Y = 30 % Z = 10 %

D
D
B

POWER
FACTOR
at load
factor C

MEASURED
CURRENT

RESTARTING

NONESSENTIAL

DESCRIPTION

ESSENTIAL

EQUIPMENT
NO.

PANEL

ITEM NO.

EQUIPMENT

7 kVA

Power factor without compensation (cos phi)


Power factor with compensation (cos phi)

kVA =

kW + kvar

ACT.

required capacitor rating [=kW (tg phi - tg phi)]

0.
:

0.
:

kvar

ABS
MOTOR &
ORB NON-MOTOR
ED
RATING
LOA
B
A
D

kW

kW

33-DB-3303 Distribution Board Telemetry Building (0.415kV)

1
2
3
4
5
6
7
8
9
10
11
12

LOAD FACTOR
(=A/B)

EFFICIENCY
at load
factor C

C IN DEC.
B IN DEC
D
kW B
DES
ACT.
C

D
D
B

POWER
FACTOR
at load
factor C

KW=A/D

CONSUMED LOAD

CONTINUOUS (Sum C)
kW

COS PHI

DES.

ACT.

DES.

13.20

13.20

1.00

1.00

0.95

13.20

4.34

Telemetry Bldg. Outdoor Lighting

0.60

0.60

1.00

1.00

0.95

0.60

0.20

Telemetry Bldg. Indoor Lighting

2.12

2.12

1.00

1.00

0.95

2.12

0.70

Telemetry Bldg. Exit and Emergency Lighting

0.12

0.12

1.00

1.00

0.95

Telemetry Bldg. Indoor Socket Outlet

2.00

2.00

1.00

1.00

0.85

Outdoor Process Area Socket Outlet

0.18

0.18

1.00

1.00

0.85

Telecom Cabinet Power Supply Unit

0.80

0.80

1.00

1.00

0.85

0.80

0.50

Power Supply of Batt. Rm Exhaust Fan Contol Pnl

0.50

0.50

1.00

1.00

0.85

0.50

0.31

Telecom Cabinet Cubicle Lighting

0.10

0.10

1.00

1.00

0.85

0.10

0.06

RMU Space Heater

0.20

0.20

1.00

1.00

24 Volts DC UPS Space Heater

0.30

0.30

1.00

110 Volts DC UPS Space Heater

0.30

0.30

1.00

(Est. X% SumC + Y% SumI)


(Existing)

Total Plant Peak Load (TPPL) :


(Est. X% SumC + Y% SumI + Z% SumS)
(Existing)

18

KW

X = 100 %

KVAR

kW + kvar

kvar=kW*tg phi
STAND-BY (SumS)

INTERMITTENT AND SPARES (SumI)

kvar

Outdoor Process Area Lighting

Total Plant Running Load (TPRL) :

NOTES:

MOTOR
RATING

ACT.

kW
DES.

kvar
ACT.

DES.

2.00

1.24

0.18

0.11

0.85

0.20

0.12

1.00

0.85

0.30

0.19

1.00

0.85

0.30

0.19

2.98

1.85

ACT.

kW
DES.

kvar
ACT.

DES.

0.12

0.04

0.12

0.04

G
ACT.

MEASURED
CURRENT

RESTARTING

NONESSENTIAL

VITAL

PANEL

DESCRIPTION

ESSENTIAL

EQUIPMENT
EQ
UIP
ME
NT
NO.

CABLE DETAILS
P=PVC
X=XLPE OR EPR
RATING=SITE RATING
NO.
P/X SQ.MM RATING

REMARKS

Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value
Calculated Value
Assumed Value
Assumed Value
Assumed Value
Assumed Value

19.39
TOTAL

Y = 30 %

17.32

6.10

Power factor without compensation (cos phi)

0.

(carried forward to sheet -1/4)

18

KW

X = 100 %

KVAR

Y = 30 % Z = 10 %

kW + kvar

19 kVA

Power factor with compensation (cos phi)


kVA =

kW + kvar

DES.
ACT.

18

required capacitor rating [=kW (tg phi - tg phi)]

0.
:

kvar