SANS 517:2009 Light Steel Frame Building
SANS 517:2009 Light Steel Frame Building
SANS 517:2009
Edition 1
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table of changes
Change No.
Date
Scope
Foreword
This South African standard was approved by National Committee SABS SC 59F, Construction
standards Steel and aluminium structures, in accordance with procedures of the SABS Standards
Division, in compliance with annex 3 of the WTO/TBT agreement.
This document was published in November 2009.
Reference is made in 4.1 and 6.1 to the "relevant national legislation". In South Africa this means
the National Building Regulations and Building Standards Act, 1977 (Act No. 103 of 1977).
Reference is made in 5.12.2 to the relevant national legislation. In South Africa this means the
Occupational Health and Safety Act, 1993 (Act No. 85 of 1993).
Reference is made in 8.2.1 to the relevant national body. In South Africa this means the
Engineering Council of South Africa (ECSA), or the South African Council for National Scientific
Professions (SACNASP).
Annexes A, B and C are for information only.
Introduction
The Southern African Light Steel Frame Building Association (SASFA) was formed as a division of
the SA Institute of Steel Construction by a group of interested companies to coordinate the
systematic development of this new industry and to ensure quality throughout the value chain. One
of the major tasks identified was to establish this standard for light steel frame building.
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Contents
Page
Foreword
Introduction
1 Scope ..................................................................................................................................
6
6
19
4 Materials ..............................................................................................................................
4.1 General .......................................................................................................................
4.2 Steel . ..........................................................................................................................
4.3 Fasteners ...................................................................................................................
4.4 Interior lining of walls and ceilings .............................................................................
4.5 Exterior cladding of walls (excluding masonry) ..........................................................
4.6 Masonry for exterior cladding of walls and foundation walls ......................................
4.7 Thermal and acoustic insulation ................................................................................
4.8 Damp proof courses ...................................................................................................
4.9 Wall ties and fixings ...................................................................................................
4.10 Sheathing to prevent racking .....................................................................................
4.11 Vapour permeable membranes .................................................................................
4.12 Reinforced concrete ...................................................................................................
4.13 Holding down devices ................................................................................................
4.14 Floors .........................................................................................................................
20
20
20
20
20
21
21
21
21
21
21
21
22
22
22
22
22
23
23
33
33
34
37
43
46
47
50
51
52
56
58
58
58
58
59
63
70
73
78
1
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Contents(concluded)
Page
7 Installation of services .........................................................................................................
7.1 Positioning of services in concrete floor slabs ...........................................................
7.2 Holes in members ......................................................................................................
7.3 Plumbing pipework and fittings ...................................................................................
7.4 Electrical cables and fittings .......................................................................................
80
80
80
81
82
8 Foundations ........................................................................................................................
8.1 General .......................................................................................................................
8.2 Site investigation ........................................................................................................
8.3 Selection of foundation type .......................................................................................
8.4 Standard designs .......................................................................................................
8.5 Design by engineering principles ...............................................................................
8.6 Site preparation and filling ..........................................................................................
8.7 Additional precautions ................................................................................................
82
82
83
85
91
96
98
101
104
107
109
Bibliography ...........................................................................................................................
112
2
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
1 Scope
This standard establishes rules and requirements for the design, fabrication and construction of
buildings with light steel frames, clad and insulated with appropriate materials, including the walls,
roofs, floors, and foundations of such buildings.
This standard applies to buildings which do not exceed the geometric limitations given in figure 1.
This standard does not cover doors, windows, services, finishes or other elements of buildings that
are either not peculiar to light steel frame buildings or do not have a direct interface with the steel
frame.
Dimensions in metres
W
L
=
=
width
length
3
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
2 Normative references
2.1 Standards
The following referenced documents are relevant for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies. Information on currently valid national
and international standards can be obtained from the SABS Standards Division.
AS 2870.1, Residential slabs and footings Construction.
ASTM D 7033, Standard practice for establishing design capacities for oriented strand board (OSB)
wood-based structural-use panels.
ASTM E 1677, Standard specification for an air retarder (AR) material or system for low-rise framed
building walls.
ISO 11997-2, Paints and varnishes Determination of resistance to cyclic corrosion conditions
Part 2: Wet (salt fog)/dry/humidity/UV light.
SANS 204-2, Energy efficiency in buildings Part 2: The application of the energy efficiency
requirements for buildings with natural environmental control.
SANS 227, Burnt clay masonry units.
SANS 248, Bituminous damp-proof courses.
SANS 266, Gypsum plasterboard.
SANS 457-2, Wooden poles, droppers, guardrail posts and spacer blocks Part 2: Softwood
species.
SANS 457-3 (SABS 457-3), Wooden poles, droppers, guardrail posts and spacer blocks Part 3:
Hardwood species.
SANS 675, Zinc-coated fencing wire.
SANS 803, Fibre-cement boards.
SANS 952 (SABS 952), Polyolefin film for damp-proofing and waterproofing in buildings.
SANS 1200 DM, Standardized specification for civil engineering construction Section DM:
Earthworks (roads, subgrade).
SANS 1200 M, Standardized specification for civil engineering construction Section M: Roads
(general).
SANS 1273 (SABS 1273), Fastness for roof and wall coverings in the form of sheeting.
SANS 1381-1, Materials for thermal insulation of buildings Part 1: Fibre thermal insulation mats.
SANS 1381-4, Materials for thermal insulation of buildings Part 4: Reflective foil laminates (rolls,
sheets and sections).
SANS 1381-6 (SABS 1381-6), Materials for thermal insulation of buildings Part 6: Cellulose loose
fill thermal insulation material.
4
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
SANS 1383, Rigid urethane and isocyanurate foams for use in thermal insulation.
SANS 1700 (all parts), Fasteners.
SANS 3575/ISO 3575, Continuous hot-dip zinc-coated carbon steel sheet of commercial and
drawing qualities.
SANS 4998/ISO 4998, Continuous hot-dip zinc-coated carbon steel sheet of structural quality.
SANS 7253/ISO 7253, Paints and varnishes Determination of resistance to neutral spray (fog).
SANS 9364 /ISO 9364, Continuous hot-dip aluminium/zinc-coated steel sheet of commercial,
drawing and structural qualities.
SANS 10005, The preservative treatment of timber.
SANS 10043, The installation of wood laminate flooring.
SANS 10100-1 (SABS 0100-1), The structural use of concrete Part 1: Design.
SANS 10100-2 (SABS 0100-2), The structural use of concrete Part 2: Materials and execution of
work.
SANS 10124, The application of soil insecticides for the protection of buildings.
SANS 10142-1, The wiring of premises Part 1: Low-voltage installations.
SANS 10106, The installation, maintenance, repairs and replacement of domestic solar water
heating systems.
SANS 10160 (SABS 0160), The general procedures and loadings to be adopted in the design of
buildings.
SANS 10161 (SABS 0161), The design of foundations for buildings.
SANS 10162-1, The structural use of steel Part 1: Limit-state design of hot-rolled steelwork.
SANS 10162-2 (SABS 0162-2), The structural use of steel Part 2: Limit-states design of coldformed steelwork.
SANS 10177-2, Fire testing of materials, components and elements used in buildings Part 2: Fire
resistance test for building elements.
SANS 10249, Masonry walling.
SANS 10252-1, Water supply and drainage for buildings Part 1: Water supply installations for
buildings.
SANS 10252-2 (SABS 0252-2), Water supply and drainage for buildings Part 2: Drainage
installations for buildings.
SANS 10254, The installation, maintenance, replacement and repair of fixed electric storage water
heating systems.
SANS 10400 (SABS 0400), The application of the National Building Regulations.
TRH 14, Guidelines for road construction materials.
5
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
2.2 Other publications
NHBRC (National Home Builders Registration Council, RSA), Home Building Manual, Parts 1 3.
Agrment Board of South Africa, Booklet B1, Performance criteria and minimum requirements for
the assessment of innovative methods of construction.
3.1 Definitions
3.1.1
acceptable
acceptable to the authority administering this standard, or to the parties concluding the purchase
contract, as relevant
3.1.2
acoustic insulation
insulation material installed to reduce the transmittance of sound from one side of the insulation to
the other
3.1.3
air infiltration
air movement through a material, component or an assembly into a building
3.1.4
balconies
external areas, at least one metre above ground level
3.1.5
beam
horizontal structural member that supports vertical loads and is subject to flexural stresses
3.1.6
bearer
sub-floor beam supporting the floor joists (see figures 2 and 7)
3.1.7
bottom wall plate
bottom plate
member running along the bottom of a wall frame and resting directly on a foundation wall,
foundation beam or floor slab (see figures 2 and 4)
3.1.8
bracing
diagonal members, or diaphragms, that resist lateral movement of members or racking forces (or
both), (see figures 2, 9 and 10)
3.1.9
brandering
member fixed to roof trusses or rafters to support the ceiling (see figure 3), and which does not
apply to suspended ceilings
6
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.1.10
brick veneer
single leaf non-load-bearing brick wall serving as exterior cladding
3.1.11
building envelope
exterior skin of a building, consisting of the floor, external walls, ceiling under roof overhangs, and
roof cladding
3.1.12
bulk insulation
mineral or synthetic fibre wool in rolls which are available in different densities and thicknesses
NOTE Referred to as bats when cut to length.
3.1.13
category 1 building
building which
a) is designated as being a class A3, A4, F2, G1, H2, H3 and H4 occupancy (see SANS 10400),
b) has no basements,
c) has a maximum length between intersecting walls or members providing lateral support of 6,0 m,
and
2
3.1.14
chord
top (rafter) or bottom member of a truss (see figures 2 and 3)
3.1.15
competent person
person who is qualified, by virtue of his education, training, experience and contextual knowledge,
to make a determination regarding the performance of a building or part thereof in relation to a
functional regulation
3.1.16
crawl space
gap between a suspended ground floor and the underlying ground, to allow for inspection and
maintenance of structural members supporting the floor
3.1.17
domestic dwelling
building used for residential purposes, consisting of one or more dwelling units
3.1.18
energy efficiency
measure of the minimisation of the need to use energy for heating and cooling of buildings
3.1.19
expansion joint
discontinuation between elements, such as wall panels, to allow for relative movement between
adjoining elements and to prevent stresses arising in the elements from such differential
movements
7
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.1.20
exterior wall
wall forming part of the building envelope, and which is normally load-bearing
3.1.21
external wall cladding
weather resistant external skin of a building, fixed to the light steel frame
NOTE External wall cladding may consist of a single leaf of brickwork (veneer), weather resistant boards or
reinforced plaster.
3.1.22
fibre cement board
composite material made of cement, sand and cellulose or synthetic fibres (or both)
3.1.23
fire rating
shortest period for which a building element or building component will comply with the
requirements for stability, integrity and insulation (see 4.1)
3.1.24
fire resistance
ability of a composite floor, wall or ceiling assembly to remain stable when exposed to heat
generated by fire
3.1.25
floor joist
beam that directly supports the flooring (see figures 2 and 7)
3.1.26
glass wool
material made from glass, spun into fibre-like structure
NOTE Available in different densities (kilogram per cubic metre) for use as insulation.
3.1.27
gypsum board
board with a gypsum plaster core with an envelope of two layers of paper
NOTE Gypsum board can be specified to be fire resistant or water resistant.
3.1.28
insulation
building fabric installed in wall and roof cavities, or attached to steel framing elements or cladding
materials, to provide resistance against heat or sound transfer (or both), between rooms or
dwellings
NOTE The insulation specified for category 1 buildings does not comply with the insulation requirement of
SANS 204-2. It was included to allow for low cost buildings.
3.1.29
internal lining
cladding of an internal wall, the inner face of an external wall or a ceiling that provides a neat finish,
fire resistance to the light steel structure and part of the insulation
3.1.30
jack stud
vertical member in a wall frame below or above a window or door opening (see figure 2)
8
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.1.31
jamb stud
stud located beside an opening in a wall frame such as a window or door opening (see figures 2, 5
and 6)
3.1.32
light steel frame building
buildings in which the load-bearing structure, comprising the wall framing, columns, beams, trusses,
panels or any combination of these, consists of assemblies of thin-walled cold-formed steel sections
3.1.33
lintel
horizontal member in a wall frame spanning over an opening (see figures 2, 5 and 6)
3.1.34
nogging
horizontal restraining member fixed between studs in a wall frame (see figures 2 and 4)
3.1.35
non-load-bearing walls
wall that is not required to carry gravity or wind loads (see figure 8)
3.1.36
notching
localised removal of material from a steel element that involves cutting away a flange of the element
or a portion thereof
3.1.37
open web joist
parallel-chord truss that supports concentrated or distributed loads, such as floor joists, rafters in a
roof and lintels (see figures 5 and 6)
3.1.38
purlin
member fixed to roof trusses or rafters to support roof sheeting (see figure 3)
3.1.39
racking
in-plane distortion of a framing module such as a wall or a roof, involving movement of the top
relative to the bottom, in the plane of the module
3.1.40
reflective insulation
material with a reflective surface such as a reflective foil laminate capable of reducing radiant heat
flow due to its high reflectivity and low emissivity
3.1.41
roof batten
member fixed to roof trusses or rafters to support roof tiles (see figure 3)
3.1.42
R-value
measure of resistance to heat flow of a material or composite element, including the effects of any
air spaces or reflective surfaces (or both)
NOTE The higher the R-value, the better the ability of the material or composite element to resist the flow of
heat through it. R-values are expressed using the units, m2K/W.
9
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.1.43
sheathing
rigid board fastened directly to the wall studs to provide support for exterior cladding material, to
lend structural support to the light steel frame members or to enhance the insulation of exterior
walls
3.1.44
sheet insulation
insulation materials in (rigid) sheet form
NOTE Sheet insulation is available in different densities and thicknesses, with or without reflective surfaces.
3.1.45
sound insulation
measures taken to reduce the transfer of sound through a composite wall or floor assembly
(see 3.1.2)
3.1.46
spacing
unless otherwise specified, the centre-to-centre distance between studs, joists, bearers, trusses,
battens, purlins or other elements
3.1.47
span
unless otherwise specified, the centre-to-centre distance between the supports of a beam, truss,
joist, purlin, batten, rafter or roof
3.1.48
stone wool
material made from stone or slag, spun into fibre-like structure
NOTE Available in different densities (expressed using the units, kg/m3) for use as insulation.
3.1.49
structural steel
all steel which forms part of the structure, including the roof construction, wall frame construction,
floor and ceiling supports
3.1.50
studs
vertical members of the light steel wall frame
NOTE Studs could be load-bearing, or not (see figures 2 and 4).
3.1.51
subfloor
lower layer of timber, concrete or fibre cement flooring to which the bottom wall plate and wearing
surface is attached
3.1.52
suspended floor
floor supported by beams or columns
3.1.53
tenancy-separating wall/floor
wall or floor that separates one residential unit from another
10
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.1.54
thermal break
air gap or layer of insulating material between two building components to reduce the transfer of
heat by conduction
3.1 55
thermal efficiency
ability of a composite building component or assembly (floor, wall, ceiling or roof) to resist heat
transfer
3.1.56
top wall plate
member running along the top of a wall frame (see figures 2 and 4)
3.1.57
TRH
technical recommendations for highways
3.1.58
truss
latticed frame supporting the roof and ceiling over the full width of the domestic dwelling (see
figures 2 and 3)
3.1.59
uncontrolled air flow
unintended movement of air into or through a room or a building
3.1.60
vapour permeable membrane
membrane installed to prevent or minimise the ingress of moisture and uncontrolled air flow, and
allow the passage of vapour
3.1.61
wall tie
bracket or wire connecting brick veneer cladding to the steel frame
3.1.62
weatherproofing
measures taken to prevent the ingress of moisture and to minimise uncontrolled air flow
3.1.63
web member
element of a truss or open web joist other than the top and bottom chord (see figures 2 and 3)
11
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
12
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
13
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Stud height
Floor joist
spacing
Stud height
Upper or single
storey common stud
Upper or single
Storey top plate
Lower storey
Rafter / Truss
spacing
Nogging
Upper or single
storey bottom plate
Lower storey
top plate
Lower storey
common stud
Stud spacing
Lower storey
bottom plate
Drg.740g
14
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
15
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Floor joist
spacing
Lintel
Jamb stud
Sill trimmer
n
spa
el
t
n
Li
Drg.740i
16
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Load-bearing or
non-load-bearing wall
parallel to floor joist
Load-bearing or
non-load-bearing wall
perpendicular to
floor joist
Drg.740k
17
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Roof bracing
Drg.740l
Double diagonal
metal strap brace
Sheet brace
(FC sheet,
hardboard, plywood
or steel)
'K' brace
Drg.740m
18
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
3.2 Symbols
A
cp
cpe
cpi
cr
height
span or length
qk
Qk
qp
spacing of elements
vb
wind pressure
wind load
Wr
Ww
W(down)
W(up)
roof slope
deflection
air density
19
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
4 Materials
4.1 General
Materials that have been proven to meet the requirements of the relevant national legislation (see
foreword), if used appropriately in combination with other materials, and installed to an acceptable
quality of workmanship, are listed as being acceptable in this section. Other materials and
combinations of materials may be used if information derived from authoritative sources can be
provided to demonstrate that the requirements of the relevant national legislation (see foreword) are
met in all respects.
A building element or building component shall comply with the requirements for stability, integrity
and insulation when tested in accordance with the relevant provisions of SANS 10177-2.
4.2 Steel
Steel, either hot rolled or cold formed, used for the structures of light steel frame buildings, shall
comply with the requirements of an internationally recognised standard and shall have a coating at
least equivalent in corrosion resistance and robustness to 200 g/m2 galvanising (Z200) or a
150 g/m2 aluminium-zinc coating (AZ150).
Light structural steel members shall be manufactured using the prescribed steel strength grade (for
example, 300 MPa or 550 MPa minimum yield strength) in accordance with the design specification.
The material shall comply with the requirements of SANS 3575 or SANS 4998 (or both), or
SANS 9364.
All steel used shall have sufficient formability to allow the cold forming of profiles without any
cracking of the steel substrate.
Steel elements shall comply with the dimensional and straightness tolerances given in 5.13.1.
4.3 Fasteners
Fasteners, connectors and fixing methods for the steel structure shall comply with
a) SANS 1700 (all parts) for bolts, nuts and screws (self drilling or self tapping (or both)), as
relevant,
b) the manufacturers recommendations, supported by international standards,
c) specifications for clinching or other mechanical means of fastening as recommended by the
manufacturer, supported by international standards or specifications.
Carbon steel fasteners shall be coated with a zinc or inorganic coating (or both) to provide corrosion
protection similar, under the prevailing conditions, to the metallic coated steel sheet used for the
light steel cold-formed sections (for example coating designation Z275). (See 5.14.)
20
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
4.5 Exterior cladding of walls (excluding masonry)
The materials shall comply with
a) SANS 803 for fibre cement board, and
b) SANS 3575 or SANS 4998 for galvanised steel sheet.
21
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
4.12 Reinforced concrete
The material shall comply with SANS 10100-2 for reinforced concrete.
4.14 Floors
The materials shall comply with
a) SANS 803 for fibre cement boards,
b) ASTM D 7033 for OSB board (structural), and
c) SANS 10100-2 for structural concrete.
5 Steel structure
5.1 Basis for design
5.1.1 General
The structure shall resist all the loads the building will be subjected to, including loads deriving from
its own mass. However, the lateral support provided to steel elements by the non-structural
elements of the building, such as the wall or roof cladding or the ceilings, may be taken into account
in the design of these elements, provided that it can be demonstrated that the non-structural
elements have adequate strength for lending such support, and that the steel structure will not be
subjected to loads its elements cannot resist without such lateral support while the non-structural
elements are, for whatever reason, not in position.
A clear path shall be discernable for every force, from where the force acts to the foundations, and
all members and connections along this path shall have adequate strength and stiffness to resist
the forces generated in them without failure, or deflections that exceed the maximum deflections
specified in this standard.
The system effect as described in annex B may be taken into account in the design of systems of
beams or other bending elements with crossing members that can distribute load between the
beams.
5.1.2 Durability
The design criteria are based on the assumption that the materials used and their installation and
maintenance will ensure that components fulfil their intended structural function for the intended life
of the structure. (See 5.14.)
22
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.2 Resistances of structural elements and connections
5.2.1 Design standard
Cold-formed steel components shall be designed to meet the requirements of SANS 10162-2,
except where expressly specified differently in this standard. Hot-rolled steelwork shall be designed
to comply with the requirements of SANS 10162-1.
23
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.3.2 Imposed loads for domestic dwellings
For the design of domestic dwellings as defined in 3.1.17, the following characteristic imposed loads
may be used, with the uniformly distributed load and the concentrated load not necessarily
occurring simultaneously:
a) For roofs, not accessible except for normal maintenance:
Uniformly distributed load (qk): 0,5 kPa for contributory areas < 3 m2;
0,25 kPa for contributory areas >15 m2; interpolate in-between;
Concentrated load (Qk): 1,0 kN applied anywhere.
b) For general floor areas:
Uniformly distributed load (qk): 1,5 kPa, but if the area A supported by a single column, wall,
beam or girder exceeds 20 m2;
3,1
qk = 0,3 +
1,5 0,75 kPa
A
The wind loads used in the design of buildings meeting the geometric limitations of figure 1 may be
calculated in accordance with 5.3.3.2 and 5.3.3.3.
5.3.3.2 Peak wind speed pressure
The peak wind speed pressure qp, expressed in kilopascals shall be determined using equation (1).
qp
1
2 000
. (1, 4 cr v b,0 )
24
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
(1)
SANS 517:2009
Edition 1
where
NOTE The recommended values of density as a function of altitude above sea level are given
in table 1.
cr
0,71 for a structure within a built-up suburb which does not rise significantly above
the structures and objects on all sides of it;
cr =
cr =
1,09 for an exposed structure located less than 3 km from the coastline;
vb,0 is the fundamental value of the basic wind speed corresponding to the specific
geographical location, which shall be taken from figure 11.
Table 1 Air density as a function of site altitude
1
Air density p
kg/m
1,20
500
1,12
1 000
1,06
1 500
1,00
2 000
0,94
25
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
Latitude Degrees
SANS 517:2009
Edition 1
Longitude Degrees
Figure 11 Geographic regions related to wind speeds
26
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.3.3.3 Wind pressure on surfaces
5.3.3.3.1 General
Wind load on structures and structural elements shall be determined taking into account the
simultaneous action of external and internal wind pressures.
The net pressure on a wall, roof or other element is the difference between the pressures on the
opposite surfaces taking due account of their signs. Pressure directed towards the surface is taken
as positive, and suction, directed away from the surface, is taken as negative.
5.3.3.3.2 Internal wind pressure
For a building without a wall with a dominant opening, the internal pressure coefficient cpi shall be
taken as +0,2 or 0,3, whichever causes the more severe loading in combination with the
appropriate external wind pressure.
For a building with a dominant opening in the windward wall, the internal pressure coefficient cpi
shall be taken as +0,75. If this dominant opening can be assumed to be closed during storm
conditions, the internal pressure coefficient cpi may be taken as +0,6.
A wall shall be regarded as containing a dominant opening if the area of its openings is at least
twice the sum of the area of openings and leakages in the remaining exterior walls of the building.
The wind pressure, w (expressed in kilopascals), on walls and ceilings in the building shall be
determined using equation (2) and the appropriate internal pressure coefficient cpi, as defined
above.
w = qpcpi
(2)
where
qp is the peak wind speed pressure, in accordance with 5.3.3.2;
cpi is the pressure coefficient for the internal pressure.
5.3.3.3.3 External wind pressure on walls
The external pressure coefficients cpe for buildings and parts of buildings depend on the size of the
loaded area A, which is the tributary area of the structure that produces the wind action effect in the
structural component to be calculated. The external pressure coefficients are given for loaded areas
of 1 m2 and 10 m2 in the tables for the appropriate building configurations as cpe,1, for local
coefficients, and cpe,10, for overall coefficients, respectively.
Values for cpe,1 are intended for the design of small elements and fixings with an area per element
of 1 m2 or less, such as cladding or roofing elements. Values for cpe,10 may be used for the design of
the overall load bearing structure of buildings.
The external pressure coefficients cpe for the walls of a building with a rectangular plan shall be
obtained from figure 12. The definition of the zones on the walls of the building is given in figure 12.
The external wind pressure we (measured in kilopascal) on the vertical walls of the building shall be
determined using equation (3) and the appropriate external pressure coefficients as defined in
figure 12.
we = qpcpe
(3)
27
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
where
qp
b
d
e
h
=
=
=
=
Zone
Coefficient
cpe
cpe,1
1,4
1,1
+1,0
0,5
cpe,10
1,2
0,8
+0,8
0,5
The resultant wind pressure w on walls or roofs is the sum of the internal and external wind
pressures, and shall be calculated using equation (4) and the appropriate internal and external
pressure coefficients as defined figure 12.
W = qp (Cpe + Cpi)
where qp, cpi and cpe are as defined for equations (2) and (3).
28
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
(4)
SANS 517:2009
Edition 1
5.3.3.3.5 Wind pressure on roof overhangs
The pressure on the underside of the roof overhang is equal to the pressure for the zone of the
vertical wall directly connected to the overhang; the pressure at the top side of the roof overhang is
equal to the pressure of the zone, defined for the roof (see figure 13).
The roof, including protruding parts, shall be divided into zones as shown in figure 14, with b always
the across wind plan dimension of the building.
b
d
e
h
=
=
=
=
Side view
Side view
29
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
The external wind pressure coefficient for mono-pitched roofs shall be obtained from table 2.
The wind pressure, w (expressed in kilopascals), on the mono-pitched roof of the building shall be
determined using equation (4) and the appropriate external and internal pressure coefficients as
defined in table 2.
Table 2 External pressure coefficient cpe for mono-pitched roofs
1
Local coefficient
6
Overall coefficient
Cpe,1
Roof pitch
Cpe,10
Wind direction
0 or 180
90
0 or 180
90
Zone
degrees
E (edge)
G (edge)
E (edge)
G (edge)
2,0
1,2
2,0
1,3
0,8
1,8
0,0
0,0
0,0
0,0
15
2,0
1,2
1,3
0,9
0,2
0,2
0,2
0,2
30
1,5
0,8
2,0
0,8
1,0
0,7
0,4
2,0
0,7
1,0
0,7
0,6
or
or
0,7
0,4
45
0,7
0,5
0,7
0,6
or
or
a
2,5
1,9
1,5
1,4
At wind direction of = 0 the pressure changes rapidly between positive and negative
values around a pitch angle of , accordingly both positive and negative values are
given. For such roofs, two cases should be considered: one with all positive values, and
one with all negative values. Positive and negative values cannot act in combination on
the same face.
The roof, including protruding parts, shall be divided into zones as shown in figure 15.
The external wind pressure coefficients for the duo-pitched roofs shall be obtained from table 3.
30
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
b
d
e
h
=
=
=
=
31
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 3 External pressure coefficients cpe for duo-pitched roofs
1
10
Local coefficient
Overall coefficient
Cpe,1
Cpe,10
Roof pitch
11
Wind direction
0 or 180
90
0 or 180
90
Zone
degrees
2,0
1,2
0,6
0,0
0,0
0,2
15
1,5
0,3
1,5
0,2
0,2
0,0
30
1,5
0,2
0,5
0,7
0,4
0,0
or
or
or
45
0,0
0,0
0,3
0,7
0,6
0,0
or
a
G (edge)
K (edge)
2,0
2,0
2,0
2,0
L
1,2
1,2
1,2
1,2
G (edge)
1,2
0,6
0,6
0,0
0,0
0,2
0,8
0,3
1,0
0,2
0,2
0,0
0,5
0,2
0,5
0,7
0,4
0,0
0,0
0,0
0,3
0,7
0,6
0,0
K (edge)
1,3
0,7
1,3
0,6
1,4
0,8
1,4
0,9
For the across wind situation the pressure changes rapidly between positive and negative values on
the windward face depending on the roof pitch , accordingly both positive and negative values are
given. For such roofs, four loading cases shall be considered, where the largest or smallest values of
all areas G and H are combined with the largest or smallest value in area J. Positive and negative
values cannot act in combination on the same face.
The wind pressure w (expressed in kilopascals), on the duo-pitched roof building shall be
determined using equation (4) in 5.3.3.3.4 and the appropriate external and internal pressure
coefficients as defined in 5.3.3.3.2 and 5.3.3.3.7.
5.3.3.3.8 Local wind pressure at corners of roofs
The local external pressure coefficient for the square extending for 2 m in both directions
horizontally from the corners of a roof shall be taken as 2,9. This pressure coefficient shall be used
in conjunction with the pressure on the underside of the roof for the design of purlins, battens and
sheeting and their fixings in this area.
32
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
e) Loads on roofs during construction:
uniformly distributed load (qk): 0,50 kPa for contributory areas < 3,0 m2, or 0,25 kPa for
contributory areas > 15 m2, with linear interpolation in-between;
Concentrated load (Qk): 1,0 kN.
5.4.2 Serviceability
The design criteria for serviceability shall be taken from, but not limited to, the criteria given in
sections 5.6 to 5.8 (inclusive).
NOTE The design criteria have been determined on the basis of experience. The serviceability limits are
intended to provide satisfactory service for typical situations. SANS 10160 provides further guidelines for other
situations.
5.5.2 Calculations
Calculations shall be based on appropriate structural models for the ultimate or serviceability limit
states under consideration. The method of structural analysis shall take into account equilibrium,
stability and geometric compatibility. The combinations of loads shall include all appropriate
combinations outlined in this document. The design properties for steel shall be in accordance
with 5.2.2. The design capacities of steel elements shall be determined in accordance with
SANS 10162-1 or SANS 10162-2.
33
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.5.3 Testing
Only prototype testing of full size members or sub-assemblies in accordance with section 5.11 shall
be used in assessment.
The combinations used for the determination of the design load effects for strength are:
1,2 Gk + 1,6 Qk
1,2 Gk + 1,6 qk
0,9 Gk + 1,3 Wk(up)
1,2 Gk + 1,3 Wk(down)
where
Gk
are the permanent loads including the weight of roofing, purlins or battens and
insulation;
Wk
is the wind load derived from w in 5.3, taking both the external and internal wind
pressures into account;
Qk and qk
are the imposed load as in section 5.3. For inaccessible roofs, it may be assumed
that the concentrated load Qk is shared equally between two adjacent battens
provided their spacing does not exceed 400 mm.
For satisfactory performance under each issue of concern, the calculated value of the serviceability
parameter under the nominated load(s), shall be kept within the limiting value of the response, as
shown in table 4.
34
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 4 Serviceability response limits roof battens and purlins
1
Issue of
concern
Serviceability
parameter
Factored
load
Limit of
response
Application
Visual sagging
Mid-span deflection ()
Deflection under
imposed load
Mid-span deflection ()
1,1 Gk
Cantilever deflection ()
L/300
L/150
L/150
Cantilever deflection ()
1,0 Qk
or 1,0 qk
Deflection under
wind load
Mid-span deflection ()
0,6 Wk
L/150
Cantilever deflection ()
Batten
or
purlin
L/75
L/75
The combinations used for the determination of the design load effects for strength are:
1,2 Gk + 1,6 qk
1,2 Gk + 1,6 Qk
0,9 Gk + 1,3 Wk(up)
1,2 Gk + 1,3 Wk(down)
where
Gk
are the permanent loads of the complete roofing system including the weight of
roofing, purlins or battens, insulation, ceilings, brandering, trusses or of services as
appropriate;
Wk
is the wind load derived from w in section 5.3.3, taking both the external and
internal wind pressures into account;
Qk and qk
The concentrated load Qk need not be applied to the web members of trusses.
5.6.3.2 Design for serviceability
For satisfactory performance under each issue of concern, the calculated value of each parameter
in table 5 shall be kept within the limiting value of the response, under the action of the appropriate
load.
35
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 5 Serviceability response limits Trusses and rafters
1
Issue of concern
Serviceability
parameter
Factored
load
Limit of
response
Application
Visual sagging
Mid-span deflection ()
1,1 Gk
L/300
Cracking of ceiling
Mid-span deflection ()
Qk
d/250
Deflection under
imposed load
Mid-span deflection ()
1,0 Qk or
1,0 qk
d/200 or
Truss or rafter
L/250, whichever
is less
Deflection under
wind load
Mid-span deflection ()
0,6 Wk
L/150
Truss or rafter
Undulation of roof
Differential mid-span
deflection ()
1,1 Gk
s/150
(< 4 mm)
Differential deflection
between adjacent
trusses or rafters
The load combinations used for the determination of the design load effects for strength are:
0,9 Gk + 1,3 Wk(up)
1,2 Gk + 1,3 Wk(down)
where
Gk
Wk
NOTE Brandering need not be designed to resist imposed loads, on the assumption that nobody will be
allowed to stand on the brandering.
For satisfactory performance under each issue of concern, the calculated value of the parameter
under the nominated load shall be kept within the limiting value of the response, as shown in
table 6.
36
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 6 Serviceability response limits Brandering
1
Issue of concern
Serviceability
parameter
Factored load
Limit of
response
Application
Sag or ripple
Mid-span deflection ()
1,1 Gk
L/300
All ceilings
Cracking of ceiling
Mid-span deflection ()
Gk + 0,6 Wk
L/200
Gk and Wk = as in 5.6.4.1
37
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.7.2 Load-bearing wall studs
5.7.2.1 General
The load combinations for the determination of the design load effects for the strength of wall studs
are:
1,2 Gk + 1,6 qk
1,2 Gk + 1,6 Qk
1,2 Gk + 1,3 (Wkw + Wkr(down))
0,9 Gk + 1,3 (Wkw + Wkr(up))
where
Gk
is the self weight of the roof, including roof structure, roof cladding, roof battens,
ceiling battens, ceiling, services and roof insulation if appropriate;
qk and Qk
Wkw
Wkr
NOTE Wall studs may also be subject to additional axial forces if they are part of the bracing system
resisting racking forces.
NOTE Guidance for the determination of weights can be found in annex A.
38
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.7.2.2.2 Design for serviceability
For satisfactory performance under each issue of concern, the calculated value of the parameter
under the nominated load shall be kept within the limiting value of the response in table 7.
Table 7 Serviceability response limits External walls, single or upper storey
1
Issue of concern
Serviceability
parameter
Load
Limit of
response
Application
H/150
(< 20 mm)
Face loading
Impact
H/200
(< 12 mm)
Wkw
Mid-height deflection () Q
= 0,7 kN
5.7.2.3 External load-bearing wall studs for the lower storey of a two storey construction
5.7.2.3.1 Design for strength
The load combinations used for the determination of the design load effects for the strength of wall
studs are:
1,2 Gk + 1,6 Qk
1,2 Gk + 1,6 qk
1,2 Gk + 1,3 (Wkw + Wkr(down))
0,9 Gk + 1,3 (Wkw + Wkr(up))
where
Gk
is the self weight, of the roof, including the roof structure, roof cladding, roof
battens, ceiling battens, ceiling, upper storey walls, upper storey floor, services and
roof insulation, if appropriate;
qk and Qk
are the imposed loads on the roof and upper storey floor;
Wkw
Wkr
For satisfactory performance under each issue of concern, the calculated value of the parameter
under the nominated load shall be kept within the limiting value of the response in table 8.
39
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 8 Serviceability response limits External walls, lower of two storeys
1
Issue of concern
Serviceability
parameter
Load
Limit of
response
Application
Mid-height deflection ()
= 0,7 kN
0,6 W
H/150
(< 20 mm)
Face loading
H/200
(< 12 mm)
NOTE Jamb studs may warrant specific serviceability criteria to counteract the closing and slamming
of doors. Brittle lining materials, such as ceramic tiles, may require special consideration for
serviceability. Brick veneer should not be considered as a brittle cladding material under this definition.
Design criteria for internal load-bearing wall studs are similar in principle to external load-bearing
wall studs. Wind load normal to the wall is limited to differential pressure between the wall faces and
may be taken as 0,3 qp where qp is obtained from 5.3.3.2.
Non-load-bearing studs are defined here as wall studs that are not required to carry gravity loads,
other than their own self-weight. These studs are, however, expected to carry any lateral loads such
as wind loads, impact loads or internal pressures they may be subjected to and shall be designed
accordingly.
The top wall plate of a non load-bearing wall shall be laterally supported.
Joints shall be made in non-load-bearing walls where they cross movement joints in the main
structure.
Care shall be taken to ensure that non-load-bearing studs do not become load-bearing because of
deflection of a floor above it. This can be achieved by measures similar in concept to those depicted
in figure 16. The finishes shall be detailed so as not to be damaged by the resulting movements.
40
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Channel fixed to
structure over top
wall plate
Top wall plate not
attached to channel
Drg.740v
New load-bearing studs have to resist wind loads and shall be designed in the following way:
a) External non-load-bearing studs shall be designed for the full wind load normal to the wall.
b) Internal non-load-bearing studs shall be designed for the differential pressure between the sides
of the wall, which may be taken as 0,3 qp, where qp is obtained from 5.3.3.2.
5.7.3.3 Design for serviceability
The serviceability requirements for non-load-bearing studs are the same as those for load-bearing
studs (see 5.7.2).
5.7.4 Noggings
Noggings shall be designed to provide lateral and torsional restraints to the studs. In addition,
noggings shall be designed to support an imposed concentrated vertical gravity load of 1,0 kN
placed anywhere on its span to produce the maximum load effects during construction.
Noggings are not normally required for non-load-bearing walls, except where required for the fixing
of cladding in accordance with recommendations of the manufacturers of the cladding material.
Load-bearing wall plates are designed to transfer vertical loads only. Wall plates are generally not
designed to transfer horizontal loads laterally to support walls, as ceiling and floor diaphragms are
designed to resist horizontal loads and give lateral support to walls.
Load-bearing wall plates shall be designed to resist the vertical loads exerted by the elements
resting on them, except where such loads are transferred directly into the supporting structural
elements below the wall plate, aligned with the supported elements.
Wall plates may also have to resist longitudinal forces resulting from wall bracing (see 5.10.3).
41
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.7.5.2 Lintels
A lintel shall be provided to any opening in a load-bearing wall where one or more studs are cut or
displaced to form the opening. A lintel is not required where an opening falls between studs.
Lintels are designed to transfer the vertical loads applied over the opening, to the jamb studs on the
sides of the opening.
Lintels in single or upper storey walls are designed to support rafters, trusses or any other load
carrying members that are located over the opening (see figure 5).
Lintels in the lower storey walls of a two-storey construction are designed to support the loads from
the wall above including the roof loads and the floor loads from the storey above (see figure 6).
A lintel can be designed as part of a system that includes top wall plates and other structural
components located directly above an opening and connected to the lintel.
Elements at the level of the top wall plate are not normally designed to carry the wind load normal to
the wall arising from the opening. Elements at the level of a ledger (see figure 2) shall be able to
span horizontally between the jamb studs when the wall is subjected to wind loads.
5.7.5.3 Design for strength
The load combinations for the determination of the design load effects for wall plates and lintels are:
a) Single or upper storey
1,2 Gk + 1,6 qk
1,2 Gk + 1,6 Qk
0,9 Gk + 1,3 Wkr(up)
1,2 Gk + 1,3 Wkr(down)
1,2 Gk + 1,3 (Wkw + Wkr(down))
where
Gk
Wkw
b) Lower storey
1,2 Gk + 1,6 qk
1,2 Gk + 1,6 Qk
0,9 Gk + 1,3 Wkr(up)
1,2 Gk + 1,3 Wkr(down)
1,2 Gk + 1,3 (Wkw + Wkr(down))
42
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
where
Gk
is the weight of the complete roof, upper storey walls and floor, including the
ceiling;
qk and Qk are the imposed loads on the roof and upper storey floor;
Wkr
Wkw
For satisfactory performance under each issue of concern, the calculated value of the parameter
under the nominated load shall be kept within the relevant limiting value of the response, as shown
in table 9.
Table 9 Serviceability response limits for wall plates and lintels
1
Issue of concern
Serviceability
parameter
Load
Limit of
response
Application
Wall plates
Sagging or wind uplift Mid-span deflection ()
Gk
or
0,9G + 0,6 Wkr(up)
L/200
(< 3 mm)
Gk
L/300
Lintels
Sagging
Mid-span deflection ()
(< 10 mm)
Wind uplift
Mid-span deflection ()
L/200
Floor joists are designed mainly to support floor loads. Floor bearers are designed to support the
floor joists (see figure 7).
43
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Floor joists or bearers may also be required to support ceilings (of the storey below), and loadbearing and non-load-bearing walls which may run either parallel or perpendicular to the direction of
the joists or bearers (see figure 8).
Floor joists or bearers shall be fixed to supporting wall plates and channel bearing stiffeners as
shown in figure 17. Alternatively, bridging as shown in figure 20, or similar elements, shall be
provided to prevent rolling.
Drg.740w
The flanges of joists or bearers may not be notched unless it is specified in the design.
Except where adequate strengthening is provided around a hole through the web of a joist or
bearer, the rules in 5.7.1 governing penetrations through studs shall also be observed for floor joists
and bearers.
Where joists overlap on a load-bearing intermediate wall as shown in figure 18, they should be fixed
together with bolts or screws situated near the ends of the overlapping parts to prevent the floor
decking being pushed up or the ceiling being cracked when the cantilevered parts of the joist move
upward. The length of the overlap shall be a minimum of 150 mm.
Flanges of joists or bearers may not be notched to accommodate services, unless expressly
specified in the design. The rules provided in 5.7.1(a) to 5.7.1(e) shall be observed with respect to
penetrations through webs, and the design shall allow for such penetrations to be made.
44
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Drg.740x
The combinations of loads used for the determination of the design load effects for floor joists or
bearers are:
1,2 Gk + 1,6 qk
1,2 Gk + 1,6 Qk
where
Gk
Qk and qk
Where a joist or bearer is subjected to a point load deriving from a stud standing on it, it shall be
designed to resist the load resulting from that combination of loading that causes the load to be a
maximum.
5.8.2.3 Design for serviceability
For satisfactory performance under each issue of concern, the calculated value of each parameter
under the nominated load shall be kept within the appropriate limiting value of the response as
shown in table 10.
45
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 10 Serviceability response limits Floors
1
Issue of
concern
Noticeable sag
2
Serviceability
parameter
Mid-span deflection ()
Load
Limit of response
Application
qk
Gk + qk
L/450
L/350
15 mm
Vibration
Mid-span deflection ()
Gk + 0,2qk
5 mm
Span
1,0 kN
Load shared among 2 to
m
mm
3 joists for chipboard or
3,5
1,7
plywood floor, and 3 to
3,8
1,6
5 joists for concrete or
4,2
1,5
built-up acoustic floor
4,6
1,4
5,3
1,3
6,2
1,2
NOTE 1 Alternatively, a dynamic analysis can be performed with a loading of G + 0,2qk
response limit is that the frequency should exceed 8 Hz.
NOTE 2 Mid-span deflection refers to the total floor system deflection.
NOTE 3 Limit of response for a cantilever may be taken as half of the values given above.
Normal floor
system
Dynamic
performance
of floor
5.9 Connections
5.9.1 General
Connection elements include connection components (frame anchors, brackets, straps, plates,
parts of members to be connected) and connectors (welds, bolts, screws, rivets, clinches, nails,
structural adhesives).
46
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.10 Bracing
5.10.1 General
This section describes the requirements for the design of bracing. These include roof bracing, wall
bracing, and floor and sub-floor bracing.
NOTE Temporary bracing may be required during construction.
All roof members including roof battens or purlins, roof trusses or rafters, brandering and bracing
shall be designed to act together as a structural unit to transfer all the loads imposed on the roof to
appropriate supports. For lateral restraints, it is generally assumed that the roof battens or purlins
will provide the lateral support for the top chords of the trusses and the ceiling brandering will
provide the lateral support for the bottom chords of the trusses. These assumptions require
additional actions to ensure their validity, including:
a) provision of additional bracing such as cross braces to ensure that the assumptions are valid;
and
b) computation to verify the adequacy of the roof battens or purlins, and ceiling battens and their
connections to the trusses to act as lateral restraint members.
The roof structure shall form a diaphragm to provide lateral support to the walls and to ensure that
the shape in plan of the building is maintained under all loading conditions. The roof structure,
including battens, purlins, ties and bracing shall be designed to ensure that it can perform this
function, and transmit the forces to the wall bracing system. A planar ceiling consisting of panels
that are screwed to brandering may be considered to form a diaphragm of adequate strength for
this purpose, provided that the ceiling is firmly attached to both external and internal walls through
the structure.
5.10.2.2 Truss bracing
5.10.2.2.1 Top chord bracing (see figure 9)
The requirement for a top chord bracing system is to transfer the forces generated in the top chord
restraints (usually by battens or purlins) back to the supporting structures. The loads to be
considered are those required to restrain the top chord against buckling, which may be taken as
equal to 0,02 times the maximum compressive force in the top chord, in addition to the wind load
perpendicular to the span of the trusses, including the wind load on walls supported at the top chord
level. For bracing intended to support more than one truss the value 0,02 shall be replaced by
0,02 + 0,01(n 1) 0,08
where n is the number of trusses supported.
Diagonal bracing shall be installed at an angle of between 30 and 60 to the truss top chord or
rafter, and it shall not sag more than 1/500 of the distance between supports. Where tension
devices are used to remove excessive sag, care shall be taken not to over-tension the braces.
5.10.2.2.2 Bottom chord bracing
Bottom chord bracing is required to restrain bottom chords against lateral buckling under wind uplift.
It shall be fixed to each truss and to the wall in the same manner as for top chord bracing.
47
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
The loads to be considered are those required to restrain the bottom chord against buckling, which
may be taken as equal to 0,02 times the maximum compressive force in the bottom chord, as well
as wind load on walls supported at the bottom chord level.
A planar ceiling consisting of panels screwed to brandering, which is in turn screwed to the bottom
chords of the trusses, may be regarded as providing adequate bracing to these chords.
5.10.2.2.3 Web bracing
Where the truss design requires bracing of the web members, acceptable bracing, properly
supported and connected, shall be provided.
Wall bracing is required to transfer all horizontal forces from the roof, walls and floors to the
appropriate suspended floor diaphragms and to the foundations. Typical wall bracing is shown in
figure 10. Portal frames made of hot-rolled steel may also be used for bracing. Alternatively, the
building may be tied to a strong and rigid vertical structure such as a concrete wall.
Metal strap bracing shall be fixed to each stud it crosses, only after the structure has been squared
up and plumbed and the bracing has been finally tensioned.
5.10.3.2 Design for strength
The design of the wall bracing shall conform to the following criteria:
a) The magnitudes of the forces shall be determined in accordance with 5.3 or SANS 10160.
b) Bracing shall be provided in two orthogonal directions and shall be distributed evenly so that no
torsional weakness is created (see figure 19).
c) If the strength of non-structural cladding is to be taken into account for the bracing of the building,
the design shall be based on full scale tests in accordance with 5.11 and the values in table 12,
and not more than 50 % of the bracing force may be assumed to be resisted by such cladding.
d) The angle of any metal strap bracing element shall be between 30 and 60 to the horizontal.
e) Sheet bracing elements shall not have an aspect ratio (height/width) greater than 3.
f) Appropriate anchoring of the braced panels shall be provided. Anchors in a concrete foundation
shall have a sufficient edge distance to ensure that the strength of the anchorage will be
adequate, and such anchors may only be installed into or attached to beams and slabs with
sufficient strength to resist the forces exerted by the anchors.
g) A combination of different systems for wall bracing may be used only if it can be established that
the systems have similar bracing stiffness or the performance is established by testing of a full
size prototype. Otherwise, the strength of the bracing shall be taken as that of only one of the
systems.
h) If a portal frame is used for bracing, the members and connections of the frame shall have
adequate strength to resist the moments and forces in the frame, and the lateral deflection of the
frame under full serviceability wind loads may not exceed h/200, where h is the height of the
portal frame.
48
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
i) The racking strength of the system shall be established by either full size prototype testing or by
a rational analysis. Connection details shall be designed to resist the forces specified in 5.3 or
SANS 10160.
j) The braced panels shall be effectively attached to the roof and floor structures.
Suspended floors shall be designed to form a rigid plate that can provide lateral support to the walls
and ensure that the shape in the plan of the building is maintained under all loading conditions. If
the strength of the flooring is not adequate for resisting the forces acting on it and transmitting the
forces to the wall or sub-floor bracing, or the rigidity is not sufficient for resisting deformation,
bracing in the plane of the floor shall be provided.
5.10.4.2 Floor joists or bearers
Floor joists rely on the floor decking to provide lateral restraint. Similarly, bearers rely on floor joists
to provide lateral restraint.
If the span of floor joists or bearers consisting of lipped channels or -shaped channels exceeds
4 m, the joists should be secured against rolling at points along their length not further than 3 m
apart by bridging as shown in figure 20, or by another effective method.
All joists and bearers shall be secured against toppling or rolling at all supports.
49
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.11 Testing
5.11.1 General
Tests of steel and steel elements or assemblies shall be carried out as specified in SANS 10162-2.
The design resistance of an element, connection or assembly may alternatively be determined by
testing. Only full size prototypes of an element, connection or assembly shall be used in tests.
k f + km
Unless a comprehensive test program used to establish ksc shows otherwise, the value of ksc shall
be not less than the following:
a) member strength:
10 %;
b) connection strength: 20 %;
c) assembly strength:
20 %;
d) member stiffness:
5 %;
e) assembly stiffness:
10 %.
50
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.11.3 Establishment of design values for a specific product using prototype testing
5.11.3.1 General
When the design resistance Rd, for a specific product is established by prototype testing of that
product the following conditions shall be satisfied:
a) the minimum number of tests shall be 3;
b) the design value Rd shall satisfy:
Rd (Rmin. /kt)
where
Rmin. is the minimum value of the test results;
kt
NOTE The condition of the product under test should be the same as the condition of the product in use.
Number of
test units
ksc
5%
10 %
15 %
20 %
25 %
30 %
1,15
1,33
1,56
1,83
2,16
2,56
1,15
1,30
1,50
1,74
2,03
2,37
1,13
1,28
1,46
1,67
1,93
2,23
10
1,10
1,21
1,34
1,49
1,66
1,85
100
1,00
1,00
1,00
1,00
1,00
1,00
When prototype testing is conducted for a range of a specific parameter (for example span), to
establish design values for a specific product in accordance with 5.11.3.1, it is permissible to
interpolate the obtained results for that parameter provided that there is no change in structural
behaviour (for example no change in collapse mode) within the interpolating range.
No extrapolation of test values is permitted.
51
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.12.2 Factors to be considered during construction
The following factors shall be considered:
a) The partially complete structure may be subjected to a variety of loadings (see 5.3.4).
b) Regulatory safety requirements for workers in accordance with the relevant national legislation
(see foreword).
c) Provision of scaffolding and barriers, particularly those that rely on the building frame for support.
d) Temporary bracing and tie-down during the installation of permanent bracing and tie-down.
Particular care should be taken to provide adequate temporary bracing for the lower storey of
multi-storey construction where racking loads are significantly higher than those in single storey
buildings.
5.13 Tolerances
5.13.1 Manufacturing and assembly tolerances
5.13.1.1 Sections
The tolerances for cold-formed sections shall be determined such that the relevant actual sectional
properties differ by not more than 5 % from the design section properties.
5.13.1.2 Length
The length of a component shall not deviate from its specified length by more than 2 mm.
5.13.1.3 Straightness
A component that is specified to be straight, shall not deviate about any axis from a straight line
drawn between the end points by more than L/1000 or 6,0 mm, whichever is less.
5.13.1.4 Assembly
Assembled wall panels shall each not deviate from the specified dimension by more than:
Length: +2, 4 mm;
Height:
2 mm.
The height of assembled roof trusses may not deviate by more than 10 mm from the specified
dimension.
For load-bearing walls (including shear panels), gaps between the bottom plate and the concrete
slab greater than 3 mm shall be packed with load-bearing shims under each stud. For non-loadbearing walls, gaps greater than 3 mm shall be packed with load-bearing shims or grouted at jamb
studs and points where the bottom plate is fastened to the slab. Where the gap under the bottom
plate exceeds 10 mm the space between the bottom plate and the slab shall be filled with grout
after installation of the shims.
For the attachment of floor joists, bearers, trusses and rafters to walls, where the gap exceeds
3 mm, the gap shall be packed with load-bearing shims.
52
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.13.2.2 Walls
5.13.2.2.1 General
The following tolerances are applicable to all vertical members including walls, posts, and stumps.
5.13.2.2.2 Position
Walls and studs shall not deviate from the vertical by more than h/600 or 3 mm, whichever is
greater (see figure 21).
3,0 m
5 mm max.
Walls, specified as straight, shall not deviate from a straight line by more than 5 mm over a
3 m length as shown in figure 22. Where wall panels join to form a continuous wall, the critical face
or faces of the panel may not deviate by more than 2 mm at the joint.
Drg.740sb
53
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.13.2.2.5 Flatness of walls for installation of linings
The flatness of an individual wall that is to be lined shall be such that when a 1,8 m long straight
edge is placed parallel to the wall face, the maximum deviation from the straight edge does not
exceed 3 mm over 90 % of the area, and does not exceed 4 mm over the remaining area.
5.13.2.3 Trusses, rafters, ceiling joists and floor members
5.13.2.3.1 Position
Trusses, rafters, ceiling joists and floor members shall be positioned within 20 mm from their
specified position.
5.13.2.3.2 Straightness
Trusses, rafters, ceiling joists and floor members shall be installed so that they will not deviate from
a straight line by more than L/500 where L is the length of the member (see figure 23).
The difference in the level of points on adjacent members that are intended to be on the same level
shall not exceed 1/150 of the spacing of the members or 6 mm, whichever is less.
L =
length of member
Out of plumb at any point along the length of the truss from top to bottom, shall not exceed h/100
unless the trusses are specifically designed to be installed out of plumb (see figure 24).
54
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
The flatness of the floor surface shall be within 10 mm over the entire room, but not exceeding
5 mm over any 3 m length, unless specifically designed with a slope. Abutting floors between
rooms shall be aligned, unless specifically designed otherwise.
5.13.2.4 Vertical alignment of members
When members such as joists, rafter trusses and structural wall studs (above or below a wall plate)
are designed to be vertically aligned, the centre lines of the members shall not be more than 20 mm
apart, as shown in figure 25.
55
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
5.14.2 Fasteners
5.14.2.1 The minimum specification for corrosion protection of fasteners is supplied in table 12.
56
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 12 Corrosion protection requirements for fasteners
1
Application
Location in building
Ease of
a
access
Atmosphere
External cladding
wet rooms'
all other rooms
Roofing
5
b
Coating
c
class
min.
Difficult
Inland
C2
Difficult
Aggressive
C2
Easy
Inland
C2
Easy
Aggressive
C3
Difficult
Inland
C2
Difficult
Aggressive
C3
Difficult
Inland
C2
Difficult
Aggressive
C2
Difficult
Inland
C2
Difficult
Aggressive
C2
Easy
Inland
C2
Easy
Aggressive
C3
Easy
Internal Regular
condensation
C2
Easy
Internal Dry
C1
Easy
Inland
C2
Easy
Aggressive
C3
d
d
5.14.2.2 Test for compliance with coating class requirements: Screws shall be driven into a
galvanized sheet of at least 15 mm thickness, then removed and mounted on an inert material for
testing. The significant surface (i.e. head and un-driven shank) shall be evaluated. Salt fog tests
shall be made in accordance with SANS 7253, with an additional 240 hours of UV exposure before
this for fasteners with organic coatings. The UV requirements shall be in accordance with
ISO 11997-2, as follows:
57
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 13 Corrosion protection requirements for fasteners
1
Coating class
Coating type
Minimum coating
thickness
m
C1
C2
Electroplated zinc
Electroplated zinc
12
17
a
Electroplated zinc
C3
30
a
12
40
25
30
5.14.2.4 Fasteners not inside the building envelope and not washed by rain (for example under
overhangs) in marine and industrial environments, require additional protection against corrosion,
such as organic coatings.
5.14.2.5 Fasteners or the packaging (or both) should be acceptably marked to show compliance.
5.14.2.6 Manufacturers of rivets should provide evidence that rivets, once installed, have durability
required by the design, i.e. life expectancy equivalent to that of the materials being connected and
compatibility with those materials.
5.16 Earthing
The steel frame shall be properly electrically earthed to comply with SANS 10142-1.
58
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.2 General requirements
6.2.1 Damp and weatherproofing
Roofs, floors and external walls shall prevent the ingress of moisture from outside the building
envelope that can affect the health or comfort of occupants.
6.2.2 Durability
The building shall, with appropriate maintenance, be able to survive for its design life.
The building shall facilitate, through its thermal performance, the efficient use of energy for artificial
heating or cooling, while providing an acceptable indoor environment for its occupants or the
processes conducted in the building.
A number of factors impact on the thermal efficiency of a building, such as roof colour, orientation of
the building, area and type of glazing, shading for windows, sealing against uncontrolled air flow
and insulation of walls, ceilings and floors (see SANS 204-2). Only the limitation of uncontrolled air
flow and insulation are addressed in this standard.
South Africa has been divided into six climate zones (see figure 26). The recommended R-values
below are based on the climatic conditions in each zone.
6.2.3.2 External walls
In order to meet the requirement of 6.2.3.1, the external walls of a domestic dwelling shall meet the
thermal insulation requirements in table 14. Where a garage is attached to a domestic dwelling,
either the outer wall of the garage, or the wall separating the garage from the domestic dwelling,
shall meet the requirements in table 14.
59
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Climate zone
Building
1, 4 or 6
2, 3 or 5
Required R-value
(m2K/W)
Category 1 buildings
0,32
1,14
2,20
1,90
The combination of roof and ceiling insulation of a domestic dwelling shall meet the thermal
insulation requirements in table 15.
60
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 15 Minimum required R-value (m2K/W) of thermal
insulation for roofs and ceilings of domestic dwellings
1
Climate zone
4
Upwards Upwards
Up- and
downwards
Upwards Downwards
Upwards
Required R-value
2
m K/W
Category 1 buildings
2,22
1,92
1,62
2,22
1,62
2,10
Other buildings
3,70
3,20
2,70
3,70
2,70
3,50
NOTE 1 The climate zones for South Africa are defined in figure 26.
NOTE 2 The required R-values and the direction of heat flow assume that a domestic dwelling will
have a greater degree of occupancy during the night than during the day.
6.2.3.4 Floors
6.2.3.4.1 With the exception of climate zone 5, a concrete slab-on-ground shall have insulation
installed around the vertical edge of its perimeter which shall
a) for climate zones 1 and 2, with a partially or completely unenclosed exterior perimeter, which
shall achieve a R-value of 1,5,
b) for climate zones 3, 4 and 6, with a partially or completely unenclosed exterior perimeter, which
shall achieve a R-value of 1,0.
c) with an in-slab heating system, around the vertical edge of its perimeter and underneath the slab,
having a R-value of not less than 1,0.
d) The insulation shall be water resistant in order to retain its thermal insulation properties.
61
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.2.4 Acoustic insulation
The acoustic insulation in a building shall ensure that its occupants can use it for its normal
purposes without being unduly disturbed by noise coming from adjacent rooms or from outside, or
being concerned that they may cause disturbance to people not in the same room.
The requirements for acoustic insulation for the walls of a domestic dwelling are contained in
table 16.
Table 16 Minimum acoustic insulation values for walls in domestic dwellings
1
2
Required sound insulation
Position of wall
dB
50
With discontinuous construction
45
40
25
The acoustic insulation for floors between habitable rooms in domestic dwellings shall meet the
requirements in table 17.
Table 17 Minimum acoustic insulation values for floors in domestic dwellings
1
Position of floor
2
Required sound insulation
dB
45
50
62
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 18 Minimum required fire resistance of elements in domestic dwellings
1
Element
Required fire
resistance
min.
30
Non-load-bearing walls
20
30
30
30
6.2.7 Robustness
The fabric of the building shall be robust enough to survive deliberate or accidental impact of a
magnitude that could reasonably be expected, caused by human agents, animals or the weather,
with no or minimal damage.
The stud spacing may also be affected by the requirement to align with load-bearing members to be
supported by the studs.
6.3.1.2 A strip of polyolefin or similar membrane with minimum thickness of 250 m shall be
installed underneath all bottom wall plates of exterior walls to prevent moisture from the slab from
getting in contact with the bottom wall plate.
6.3.1.3 A vapour permeable membrane shall be applied on the outside of the steel studs to
minimize water penetration and uncontrolled air flow which reduces the effectiveness of thermal
insulation and may result in condensation on the steel structure inside the building envelope. It shall
however permit vapour inside the wall cavity to escape.
6.3.1.4 Special measures shall be taken for insulation of buildings in the Southern Cape
condensation belt to minimize condensation within the wall cavity and on inside wall surfaces (see
6.3.5).
6.3.1.5 All joints in exterior cladding shall be sealed against moisture ingress in accordance with
the manufacturers recommendations. Butt joints of cladding panels shall be made against steel
studs or noggings.
63
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.3.1.6 Expansion joints shall be allowed in exterior board cladding to allow for expansion and
contraction of the cladding material, in accordance with the manufacturers recommendations. Such
joints shall be sealed with a durable elastic sealant.
6.3.1.7 A thermal break between exterior cladding and wall studs shall be effected by installation of
suitable insulation material (see 6.3.3.3) except in the case of brick veneer cladding, where an air
gap of at least 25 mm shall be maintained.
6.3.1.8 External and interior cladding materials shall be able to withstand both the soft and hard
impact tests when fixed to the steel structure, as prescribed by the Agrment Board of South Africa
in Booklet B1.
The typical construction details in 6.3.2.1 to 6.3.2.3 (inclusive), are deemed to satisfy the
requirements of 6.2, however, proof of compliance should be supplied by the material
manufacturers. Other methods and materials may be used, subject to proof of compliance with the
requirements of 6.2. The table with each figure shows the additional insulation to be provided by
means of bulk insulation or additional material, including material with reflective surfaces (see
tables 19 to 21). See 6.3.3.1 for the R-values of some commonly used insulation materials.
6.3.2.2 Weatherboard (fibre cement or timber planks) external cladding
The R-value of basic elements of wall (excluding added insulation) is 0,47 m2K/W, (see figure 27).
The fire resistance exceeds 30 min.
64
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 19 Minimum required R-value (m2K/W) of added insulation
1
3
a
Climate zone
Building
1, 4 or 6
2, 3 or 5
Required Rvalue
2
(m K/W)
Category 1 buildings
0,85
0,67
1,73
1,43
The R-value of basic elements of wall (excluding added insulation) is 0,41 m2K/W (see figure 28).
The fire resistance exceeds 30 min.
65
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 20 Minimum required R-value (m2K/W) of added insulation
1
3
a
Climate zone
Building
1, 4 or 6
2, 3 or5
Required Rvalue
2
(m K/W)
Category 1 buildings
0,91
0,73
1,79
1,49
The R-value of basic elements of wall (excluding added insulation) is 0,55 m2K/W (see figure 29).
The fire resistance exceeds 30 min.
66
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 21 Minimum required R-value (m2K/W) of added insulation
1
3
a
Climate zone
Building
1, 4 or 6
2, 3 or5
Required Rvalue
2
(m K/W)
Category 1 buildings
0,77
0,59
1,65
1,35
The Rvalues of commonly used materials for providing insulation to outer walls are given in
table 22. Where more than one insulating layer is used, the Rvalues of the layers may be added
together. The combined R-value so achieved may be added to the R-value of the basic elements of
the wall, and this sum shall be at least equal the required R-value in table 14 for the relevant
climatic zone.
Table 22 R-values of commonly-used insulation materials
1
Product
R-value (m2K/W)/
100 mm thickness
Sheet insulation
Extruded polystyrene
15 kg/m3
2,60
20 kg/m3
2,80
2,90
30 kg/m
2,00
2,50
2,68
2,76
2,56
67
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.3.3.3 Thermal break
If the external cladding consists of weatherboard, fibre cement sheeting or metal sheeting, a
thermal break with an R-value of at least 0,2 shall be installed between the steel frame and the
cladding. Expanded polystyrene of not less than 12 mm or timber of not less than 19 mm thickness
may be deemed to have an R-value of at least 0,2. Care shall be taken to ensure that the in-plane
shear strength of the wall panel assembly meets the design requirements.
Buildings in the Southern Cape condensation belt are prone to condensation due to topographical
factors, as well as the fact that it lies in the winter rainfall area of South Africa (see figure 31).
6.3.5.2 Especially in these areas, sufficient insulation shall be installed on the outside of the steel
structure to prevent the surface temperature of the light steel frame from dropping below the dew
point.
6.3.5.3 In addition, condensation is prevalent in the coastal areas of KwaZulu-Natal during the
summer months due to the high humidity levels. As air conditioning of residential buildings in this
area is not uncommon it is recommended that a thermal break (R = 0,2) be installed on the inside of
the steel frame to prevent the steel temperature dropping below dew point.
68
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
69
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.3.6 Robustness
The external walls shall be able to perform satisfactorily under both the soft body and hard body
impact tests as prescribed by the Board of Agrment South Africa in Booklet B1.
70
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.4.2 Typical construction details
6.4.2.1 General
The typical construction details in 6.4.2.2 to 6.4.2.4 (inclusive) are deemed to satisfy the
requirements given in 6.2. Other methods and materials may be used, subject to proof of
compliance with the requirements of 6.2.
6.4.2.2 Standard internal walls
Drg.741l
=
=
48 dB
30 min
Tenancy-separating walls have to extend to the underside of the roof cladding to prevent the spread
of fire, and to ensure the acoustic performance of the separation.
Electrical outlet boxes in tenancy-separating walls should not be installed back-to-back, as it will
impact negatively on the sound insulation of the wall. Sound insulation in the wall cavity shall extend
horizontally to meet the insulation of the external walls, to prevent noise transfer (referred to as
flanking).
For tenancy-separating walls with staggered studs, see figure 33. For tenancy-separating walls with
double wall frames, see figure 34.
71
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
=
=
50 dB
60 min
=
=
52 dB
60 min
72
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.4.2.4 Bathroom and scullery walls
The elements of bathroom and scullery walls are shown in figure 35.
=
=
48 dB
30 min
6.4.4 Robustness
When fixed to the steel structure cladding materials shall be able to withstand both the soft and hard
impact tests as prescribed by the Board of Agrment South Africa in Booklet B1.
73
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.5.2 Deemed- to-satisfy thermal insulation requirements
Table 15 shows the minimum insulation requirements for roof-and-ceiling system for the various
climate zones in South Africa.
In regions 3 and 5 the required R-value of the thermal insulation may be reduced by 0,5 if the roof
surface is light in colour, i.e. ranging from dull grey (weathered galvanised sheet) to cream and
white.
Emittance
of added
reflective
insulation
Direction
of
heat flow
Nonventilated
roof space
5
Flat roof
(slope
o
10 ) with
horizontal
ceiling
0,2 outer
0,05 inner
Downwards
1,21
1,08
1,28
0,96
0,86
0,66
0,2 outer
0,05 inner
Upwards
0,59
0,75
0,68
0,72
0,74
0,77
0,9 outer
0,05 inner
Downwards
1,01
0,92
1,06
0,74
0,64
0,44
0,9 outer
0,05 inner
Upwards
0,40
0,55
0,49
0,51
0,52
0,53
The typical construction details in 6.5.4.1 to 6.5.4.4 (inclusive), are deemed to satisfy the
requirements given in 6.2, however, proof of compliance should be supplied by the material
manufacturers. Other methods and materials may be used, subject to proof of compliance with the
requirements of 6.2.
NOTE The climate zones for South Africa are defined in figure 26.
The R-value of roof and ceiling materials attached to the underside of rafters is as follows:
Metal cladding = 0,35 m2K/W;
Cement/clay tiles = 0,37 m2K/W.
The fire rating is 30 min.
74
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
The ceiling lining attached to the underside of rafters is shown in figure 36, and the ceiling lining
attached to the underside of battens or purlins is shown in figure 37.
75
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 24 Required R-value (m2K/W) of added insulation
1
5
a
Climate zone
Building
1 and 4
3 and 5
Required R-value
2
(m K/W)
Category 1 buildings
2,00
1,70
1,40
1,88
3,34
2,85
2,35
3,15
The R-value of roofing materials for ventilated roof spaces (see figure 38) is as follows:
Cement/clay tiles = 0,22 m2K/W;
Steel roof cladding = 0,20 m2K/W;
The fire rating is 30 min.
76
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 25 Required R-value (m2K/W) of added insulation
1
5
a
Climate zone
Building
1 and 4
3 and 5
Required R-value
2
(m K/W)
Category 1 buildings
2,10
1,80
1,50
1,98
3,50
3,00
2,50
3,30
The R-value of roofing materials for unventilated roof spaces (see figure 39) is as follows:
Metal cladding = 0,38 m2K/W;
Clay/concrete tiles (with underlay) = 0,40 m2K/W.
The fire rating is 30 min.
77
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 26 Required R-value (m2K/W) of added insulation
1
5
a
Climate zone
Building
1 and 4
3 and 5
Required R-value
2
(m K/W)
Category 1 buildings
2,03
1,73
1,43
1,91
3,38
2,88
2,38
3,18
The following typical construction details are deemed to satisfy the requirements given in 6.2. Other
methods and materials may be used, subject to proof of compliance with the requirements of 6.2.
Tables 17 and 18, and 6.2.3.4 provide the minimum required acoustic insulation and fire rating
values of each assembly, and where applicable the required R-value of the floor assembly as well
as the required R-value of additional insulation to be provided.
See table 22 for the R-values of some commonly used insulation materials.
6.6.2.2 Suspended ground floor
A suspended ground floor with ventilated crawl space is shown in figure 40.
78
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
0,8 m2K/W
A suspended floor between levels in the same dwelling is shown in figure 41.
13 mm to 22 mm chipboard (or
similar) to give 15 kg/m 2
=
=
45 dB
30 min
79
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
6.6.2.4 Suspended tenancy-separating floor
Brandering on 400 mm
maximum spacing
15 mm minimum thickness
fire resistant gypsum board
Drg.741v
=
=
50 dB
30 min
7 Installation of services
7.1 Positioning of services in concrete floor slabs
Due to the accuracy of wall positioning characteristic of light steel frame building, care shall be
taken to accurately position water access and drainage pipes before casting the concrete floor.
80
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
f) All holes shall be positioned along the centreline of the steel section.
If any of these requirements cannot be met, the responsible engineers advice and approval shall be
obtained.
Copper or
plastic pipe
Plumbing
grommet
Drg.741w
81
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8 Foundations
8.1 General
The wall loads exerted by light steel frame buildings are generally significantly lower than those
exerted by conventional masonry structures. For structures with fibre cement cladding, the wall
loads vary from 20 %, of those exerted by a conventional brick structure for steel sheeted roofs, to
40 % for tiled roofs. These figures apply to both single and double storey structures and include the
imposed loads and the weight of the suspended floor where applicable. For single skin brick
cladding, the wall loads are approximately 50 % of the loads exerted by a conventional structure for
steel sheeted roofs and 70 % for cement tiled roofs.
Guidance on the design of foundations for buildings is given in SANS 10161, SANS 10400 and the
NHBRC Home Building Manual. The information contained in these documents is typically based on
the requirements for conventional brick structures. This section of the standard extends the
guidance given in the above documents for use in the design of light steel frame buildings.
All sites shall be classified in accordance with 8.2.3. Foundations shall either be designed in
accordance with engineering principles in accordance with 8.5 or typical foundation types may be
selected in accordance with 8.3, and constructed using the standard details given in 8.4. The ability
of the foundations to resist uplift due to wind loading shall, in all instances, be checked by
calculation in accordance with engineering principles.
82
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
All foundations shall be designed and constructed in accordance with the provisions of SANS 10400
and SANS 10161, unless specified to the contrary in this standard.
83
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.2.3.2 The classifications, C, H, R and S are not intended for dolomitic areas unless specific
investigations are carried out to assess the stability (risk of sinkholes and doline formation) of the
dolomites. Where the risk is found to be acceptable, the site shall be designated in accordance with
the provisions of the NHBRC Home Building Manual.
8.2.3.3 Site classes are based on the assumption that differential movements, experienced by
single-storey residential structures, expressed as a percentage of the total soil movements are
approximately equal to 50 % for soils that exhibit expansive or compressive characteristics and
75 % for soils that exhibit both compressible and collapse characteristics. Where this assumption is
incorrect or inappropriate, the total soil movements shall be adjusted so that the resultant differential
movement implied by table 27 is equal to that which is expected in the field.
8.2.3.4 In some instances, it may be more appropriate to use a composite description to describe a
site more fully for example, C1/H2 or S1 or H2 (or both). Composite site classes may lead to higher
differential movements and result in design solutions appropriate to a higher range of differential
movement for example, a class R/S1 may be described as a class S2 site. Alternatively, a further
site investigation may be necessary as the final design solution may depend on the location of the
housing unit on a particular site.
8.2.3.5 Where it is not possible to provide a single site designation and a composite description is
inappropriate, sites may be given multiple descriptions to indicate the range of possible conditions,
for example, H-H1-H2 or C1-C2.
8.2.3.6 Soft silts and clays usually exhibit high consolidation and low bearing characteristics.
Structures founded on these horizons may experience high settlements and such sites should be
designated as class S1 or S2, as relevant and appropriate.
8.2.3.7 Sites containing contaminated soils include those associated with reclaimed mine land, land
down slope of mine tailings and old land fills.
8.2.3.8 Where a site is classified as being P, full particulars relating to the founding conditions on
the site shall be provided.
8.2.3.9 Where a site is designated as being P, the reason for such classification shall be placed in
brackets immediately after the suffix, i.e. P (contaminated soils). Under certain circumstances
composite description may be appropriate.
8.2.3.10 Certain fills may contain contaminants, which present a health risk. The nature of such fills
should be evaluated and should be clearly demarcated as such.
84
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 27 Site class designations (to NHBRC Home Building Manual)
1
Characteristics of
founding material
Expected range
of total soil
movements
Assumed
differential
movement
Site class
Negligible
< 7,5 mm
7,5 15 mm
15 30 mm
>30 mm
50 %
50 %
50 %
50 %
H
H1
H2
H3
< 5 mm
5 10 mm
>10 mm
75 %
75 %
75 %
C
C1
C2
< 10 mm
10 20 mm
>20 mm
50 %
50 %
50 %
S
S1
S2
Stable
Heaving soils
Compressible and
potentially collapsible
soils
Variable
Variable
85
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 28 Typical foundation types
1
Foundation
type
Variations
Typical application
Strip footings
Site class
Reference
Stable soils
R, H, C, S
Figure 45a
Modified normal
H1, C1, S1
8.7.5.1
C1, S1
Figure 45a
Figure 48a
Soil raft
H1 H3, C1,
C2, S1, S2
Figure 45a
Figure 48b
Slab-on-ground Conventional
foundation
Modified normal
Stiffened raft
R, H, C, S
Figure 46
H1, C1, S1
8.7.5.1
Soil Raft
H1 H3, C1,
C2, S1, S2
Figure 46
Figure 48b
Conventional reinforced
concrete raft
Heaving, collapsible or
compressible soils
Figure 47a
Figure 47b
Waffle raft
Pad and pier
Brick piers
Timber or concrete
stumps
Stable soils or
collapsible/compressible/heaving
soils of limited thickness
R, H, C, S,
H1 H3, C1,
C2, S1, S2
86
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
Figure 45b
B
=
D
=
DPC =
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
Dimensions in millimetres
SANS 517:2009
Edition 1
87
DPC =
damp-proof course
Dimensions in millimetres
SANS 517:2009
Edition 1
88
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
b) Waffle raft
Dimensions in millimetres
SANS 517:2009
Edition 1
89
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Dimensions in millimetres
90
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table 29 Appropriate foundation types for various site class designations
1
Foundation type
R
H (< 7,5 mm)
C (< 5 mm)
S (< 10 mm)
C1 (5 mm to 10 mm)
S1 (10 mm to 20 mm)
H2
C2
S2
H3
(15 mm to 30 mm)
(> 10 mm)
(> 20 mm)
(> 30 mm)
Additional requirements
Normal construction
Strip footings or slab-on- Soil raft with normal construction. Soil raft should
ground
remove sufficient expansive material to limit total
heave movements to < 7,5 mm
Deep pad and pier
Stiffened raft
Soil raft
11 m;
4 m;
91
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Span of suspended first floor
Maximum height
6 m;
8,5 m.
b) Where the allowable bearing capacity of the in situ soil below foundations or load-bearing slabs
is less than 50 kPa. This situation could arise where the site is underlain by very loose granular
soils or by soft or very soft clays (see SANS 10161, for a definition of soil consistencies). Such
soils would generally lead to a C2 or S2 site classification.
c) Where there is a danger of subsidence due to dolomitic ground, undermining or landslip.
d) Where the site is underlain by fill material other than that placed under controlled conditions
during the course of construction.
e) Where the gradient is such that the maximum height of the foundation walls above surrounding
ground level exceeds 700 mm for a 220 mm brick wall or the overall depth of the edge beam for
a slab-on-ground foundation exceeds 750 mm.
These standard designs shall be used in conjunction with the precautions specified in 8.7.
All foundations shall extend to the founding horizon or minimum founding depth given in the site
investigation. Unless a foundation is placed on solid rock, the bottom of the foundation shall be at
least 300 mm below the level of the surrounding ground in the case of C, H or S sites and 400 mm
for all other sites.
The base of all excavations in ground other than rock shall be horizontal or at a slope of not more
than 1:10. Where necessary, the foundation shall be stepped in accordance with one of the
methods shown in figure 49. Where a foundation is placed on solid rock, the bearing area shall be
cleaned and, where necessary, stepped or dowelled so as to prevent lateral movement of the
foundation.
All loosened or disturbed material or soils that have softened due to flooding of the foundation
trenches shall be densified by compaction or removed from the base of the foundation trenches as
appropriate.
8.4.2.2 Foundation dimensions
The minimum width and thickness of foundations shall be as given in table 30.
92
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Founding
material
Exterior
cladding
Ground floor
No. of
storeys
Minimum
Reinforcement
Maximum dimensions
(except on
wall load
(B D)
R,C,H or S sites)
mm mm
Sound
rock
Brick veneer
or FC board
Suspended or
concrete surface
bed
Single or
double
40 kN/m
250 125
All soils
excluding
soft clay
and very
loose sand
Fibre cement
board
Concrete
surface bed
Single or
double
20 kN/m
400 150
2 Y10
Fibre cement
board
Suspended
Single
15 kN/m
400 150
2 Y10
Double
25 kN/m
500 200
3 Y10
Brick veneer
Concrete
surface bed
Single
15 kN/m
400 150
2 Y10
Double
35 kN/m
700 250
3 Y12
Brick veneer
Suspended
Single
20 kN/m
400 150
2 Y10
Brick veneer
or FC board
Suspended or
concrete surface
bed
Soil Raft
Double
40 kN/m
800 250
3 Y12
Single or
double
40 kN/m
400 150
2 Y10
NOTE 1 Table 30 is based on allowable bearing pressure of >200 kPa for rock, 100 kPa for soil raft
and 50 kPa for in situ soils.
NOTE 2 Minimum width of footing taken as 250 mm on rock and 400 mm for soil or soil raft.
NOTE 3 Table 30 is based on roof covering with a maximum self weight of 80 kg/m2.
NOTE 4 Exterior FC cladding taken as 9 mm fibre cement board. Brick veneer cladding comprises a
single skin of brickwork. Interior lining taken as 15 mm gypsum board.
93
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.4.2.3 Concrete and reinforcement
Foundation walls supporting load-bearing walls shall be at least 220 mm thick when constructed of
masonry or unreinforced concrete (min. 10 MPa) and at least 150 mm thick, when constructed of
reinforced concrete, provided that the foundation walls are designed in accordance with
SANS 10161.
Foundation walls shall be designed as retaining walls where the height difference in the ground or
fill (or both) elevations on opposite sides of the wall, exceeds 700 mm.
Foundations and foundation walls shall be designed to resist uplift due to wind in accordance
with 8.5.4.
The layout of the supports (stumps or piers) shall be determined taking into consideration the
support required by floor joists, the structural strength of the joists, the spacing of the wall studs and
the deflection of the joists between supports. The spacing of supports under bearers parallel to
walls shall not exceed 1,8 m.
Where pad and pier foundations are installed on sites where the upper portions of the soil profile
are collapsible, compressible or expansive, the depth of the piers shall be such that the expected
movement of the foundations is compatible with the movement tolerance of the superstructure.
8.4.3.2 Footings
The pad footings below the piers shall be designed for the maximum allowable bearing pressure
shown in table 31.
Table 31 Maximum allowable bearing pressures below pad footings
1
Site class
2
Allowable bearing pressure
a
kPa
200
C, H, H1 and S
100
C1, S1 and S2
50
94
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.4.3.3 Load
The lateral load capacity and uplift capacity of piers for resisting wind loading shall be determined
by rational design using engineering principles, (see 8.5.4).
8.4.3.4 Masonry or concrete piers
The cross-sectional area of masonry or concrete piers for external walls and for post construction
and beam construction shall be at least 230 mm 230 mm, and for sleeper piers approximately
36 000 mm2 (190 mm 190 mm). No pier may extend above the ground level by more than four
times its smallest dimension. The design of the pier and the connections between the pier and the
footing below and the bearer above shall be capable of resisting the uplift and horizontal loads
exerted by the superstructure.
8.4.3.5 Timber posts
Timber posts shall comply with SANS 457-2 or SANS 457-3, and shall have a cross-sectional area
of at least 9 500 mm2 (110 mm dia.) where they support a floor and load-bearing walls, and at least
7 500 mm2 (100 mm dia.) where they support a floor and non-load-bearing walls. The post shall be
designed as a column where the height above ground level of a post exceeds 1 m. The design of
the post and the connections between the post and the footing below and the bearer above shall be
capable of resisting the uplift and horizontal loads exerted by the superstructure.
The poles shall be pressure treated, or dip treated, against insect infestation, termites and fungal
attack in accordance with SANS 10005. The application of preservatives by brushing is not effective
and should not be practiced. Holes drilled for bolts shall also be treated, in this case by surface
treatment.
The posts of timber foundations shall be cut to the exact length before use and freshly-cut surfaces
preservative treated. Under no circumstances shall an end of a pole on which notching or cutting
has been carried out, be put into the ground before it is brush treated with a preservative and
sealed.
Care shall be taken when working with timber on site to ensure that material such as sawdust or
timber off-cuts, which could provide a source of nourishment for fungi, termites and borers, are not
left on the site or beneath suspended floors.
8.4.3.6 Fibre-reinforced cement stub columns
Fibre-reinforced cement stub columns shall have a minimum diameter of 200 mm where they
support a floor and load-bearing walls. Where the height of a fibre-reinforced cement pipe exceeds
1,0 m above ground level, the pipe shall be designed as a column with suitable reinforcing and
concrete fill. The design of the stub column and the connections between the stub column and the
footing below and the bearer above shall be capable of resisting the uplift and horizontal loads
exerted by the superstructure.
95
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.4.5 Stiffened raft foundations
Stiffened raft foundations shall be designed by engineering principles in accordance with 8.5.
The level tolerance on the finished surface of the raft shall be in accordance with 5.13.
96
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.5.4 Resistance to uplift and horizontal loads
8.5.4.1 General
The foundations shall be designed to resist the horizontal loads and uplift forces due to wind or
other loading conditions causing horizontal or uplift loads. This is particularly important in the case
of light-weight wall and roof systems. Checks shall include uplift resistance, horizontal stability and
overturning both of the structure as a whole and of individual parts of the structure or foundations.
8.5.4.2 Loading
The distribution of load on the foundations shall be determined by rational analysis taking into
account of the distribution of loads applied to the superstructure (see 5.3), the geometry of the
structure and the stiffness of the various load-bearing elements.
The foundations below all walls or other structural elements shall be capable of resisting the vertical
loads (both upwards and downwards) applied to such elements.
Foundations below shear walls shall be designed for the above loading plus the additional loads
induced by horizontal actions on the shear walls (push-pull effects and horizontal loading).
8.5.4.3 Resistance of foundations
The resistance of the foundation to uplift forces shall be equal to the weight of the foundation wall,
the weight of the foundation itself and any fill above the foundation plus such proportion of the
weight of the floor as may be expected to resist upward movement of the foundation. Where the
floor is isolated from the foundations by a movement joint, the contribution of the floor shall be
ignored.
8.5.4.4 Anchoring straps and holding-down bolts
All load-bearing elements of the structure shall be anchored to the substructure in a manner
capable of transmitting the loads from the superstructure to the foundations. In particular, the
adequacy of the anchoring of the structure shall be checked under uplift and shear loading.
In the case of strip footings, anchor straps shall pass through the foundation wall and be firmly
anchored in the concrete foundation below. For raft or slab-on-ground foundations, holding down
bolts should extend sufficiently far into the concrete to resist break-out under uplift forces. Holdingdown bolts shall not be anchored in masonry. Holding-down bolts shall be of sufficient length to be
anchored to the main pour of the concrete and not to the surface screed and shall be installed in
accordance with the manufacturers recommendations with respect to, for example, hole diameter,
edge distances and required torque.
Anchors straps shall be placed immediately adjacent to studs and shall be fixed to the stud with
fasteners capable of mobilising the required uplift resistance. Anchor straps shall be steel,
galvanized in accordance with SANS 3575 or SANS 4998. A galvanized strap of approximately a
50 mm portion, on either side of the point of emergence from the foundation masonry or concrete,
shall be coated with epoxy-tar paint.
Non-load-bearing elements shall be fastened to the substructure in a manner capable of resisting
displacement of the element.
97
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
of a temporary nature, damage category 2 may be accepted provided this is clearly indicated on the
drawings and unambiguously stated in the construction contract.
The permissible deformation of foundations to meet the above requirement shall be determined by
the designer but shall not exceed the values given in table 32.
Table 32 Maximum permissible differential movement of foundations
1
Type of construction
Maximum differential
movement as a function
of span
Maximum differential
movement
Clad frame
L/500
25
L/600
20
Brick veneer
L/1000
12
mm
These limits may be increased by 50 % on C1, C2, S1 and S2 sites where movements are nonreversible provided provision is made for maintenance of the structure and damage category 2 is
acceptable before repair.
Overall tilt of the structure shall not exceed 1:200.
98
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
Dimensions in millimetres
SANS 517:2009
Edition 1
99
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.6.2 Storm water and ground water
Where storm water drains towards the building, provision shall be made for intercepting such run-off
by means of surface drains or catch pits leading to a buried stormwater drainage system and for
discharging this water on the down-slope side of the building in a responsible manner. The site shall
be shaped so that no water ponds within 1,5 m of the structure.
Subsoil drainage shall be provided in areas where the soil is waterlogged or the presence of an
impermeable layer at shallow depth creates the possibility of a perched water table developing in
the rainy season. The extent of such drainage, whether around the full perimeter of the domestic
dwelling, below the domestic dwelling itself or merely along the upslope side will depend on the
severity of the problem, the source of the water and the slope on the site. Advice should be sought
from a geotechnical practitioner where necessary. Decay of timber stumps below buildings can be
minimised if the moisture content is kept below 20 %.
Ground water can interfere with soil-poisoning operations. If the soil is very wet, the poison will not
be absorbed properly and will be carried away with the surface run-off water. The ground shall
always be sprayed when dry enough to absorb the chemical and the site should be kept well
drained. The surface shall not be disturbed once it has been treated.
8.6.4 Fill
8.6.4.1 Controlled fill
Controlled fill is stable fill material that will provide adequate support for non-load-bearing slabs. The
thickness of controlled fill below structures shall not exceed 400 mm. Engineered fill (see 8.6.4.2)
shall be used where the fill thickness exceeds 400 mm or the fill is required to support foundations.
In technical terms, controlled fill shall consist of a G10 or better material in accordance with TRH 14
(CBR at 90 % mod AASHTO > 3, CBR swell at 100 % mod AASHTO < 1,5 %). It shall be placed
and compacted in layers at a moisture content of between 2 % below to 2 % above optimum
moisture content to a density of 90 % mod AASHTO maximum dry density throughout the full
thickness of each layer. Layer thickness will vary from 75 mm to 200 mm depending on the type of
compaction equipment used. In the case of a sand as defined in SANS 1200 M, the material shall
be compacted to 100 % mod AASHTO maximum dry density.
On site, where the size of the project does not warrant laboratory testing and field control testing of
fill materials, the following guidelines may be used:
a) Material: Controlled fill material should consist predominantly of sandy soils or mixtures of sand,
silt and gravel. Materials containing gravels larger than two-thirds of the compacted layer
thickness or materials containing predominantly clay or silt should not be used.
b) Moisture content: The material should be moistened or dried to the point that the material is firm
and just sticks together when squeezed in the hand but shows no signs of free moisture. The
moisture should be evenly distributed through the layer.
100
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
c) Compaction: Materials compacted with hand tampers or vibrating plate compactors should be
placed in layers of 75 mm uncompacted thickness. Where walk-behind vibratory rollers are used,
the layer thickness can be increased to 100 mm or 150 mm depending on the size of the roller.
Typically 6 to 8 passes of the compaction equipment will be required on a well graded fill at the
correct moisture content. Compaction can be checked by means of a hand-operated dynamic
cone penetrometer (see the NHBRC Home Building Manual) where a penetration consistently
less than 30 mm per blow is an indication of adequate compaction. Note that the dynamic cone
penetrometer may provide misleading results in materials containing gravel.
8.6.4.2 Engineered fill
Engineered fill is selected fill material placed and compacted at a specified moisture content to a
defined density under the control of a competent person. Engineered fill shall be used where the
thickness of fill below structures exceeds 400 mm or where load-bearing elements of the structure
are to be founded on the fill.
Engineered fill shall consist of a G8 or better material in accordance with TRH 14 (CBR at 90 %
mod AASHTO > 10, CBR swell at 100 % mod AASHTO < 1,5 %). The material shall be placed in
layers not exceeding 200 mm compacted thickness at a moisture content ranging from 2 % below to
2 % above optimum moisture content and compacted to a density of 93 % mod AASHTO maximum
dry density. In the case of a sand as defined in SANS 1200 M, the material shall be compacted to
100 % mod AASHTO maximum dry density. The layer thickness shall be reduced where light
compaction equipment such as a walk-behind roller is used to ensure compaction throughout the
full thickness of each layer.
Verification of the quality of the fill material and compaction control shall be carried out in
accordance with the requirements of SANS 1200 DM. At least one set of classification tests
(grading, indicator, mod AASHTO maximum dry density and CBR) shall be undertaken on each
source of material used.
8.6.4.3 In situ compaction
Compaction of the in situ material shall be carried out below all controlled or engineered fills. Before
commencement of compaction, the site shall be cleared as described in 8.6.1 and any unsuitable
material removed from site.
In the case of controlled fills, the in situ material should be moistened (where required) and
compacted by hand tamping or with four passes of a pedestrian roller or vibrating plate compactor.
In the case of engineered fills, the moisture content of the material over the upper 100 mm below
the ground surface shall be adjusted to within 2 % of the optimum moisture content and the material
compacted to 90 % mod AASHTO maximum dry density to a depth of at least 100 mm.
101
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
8.7.2 Damp proofing
Polyolefin under-floor membranes with a minimum thickness of 250 m shall be provided below all
floor slabs laid on the ground, slab-on-ground foundations and raft foundations. The membrane may
be omitted in semi-arid or arid conditions where the likelihood of moisture ingress below the slab
from surrounding areas or due to capillary action is small. In the case of raft foundations or slab-onground foundations, the membrane should extend a minimum of 300 mm down the face of the
beam below the floor slab but need not be continuous below the remainder of the beam.
A damp-proof course (DPC) shall be provided at the level of the top of the floor slab below all
external and internal walls. The DPC below internal walls may be omitted where the waterproof
membrane below the slab is continuous. Where screeds are laid after the wall has been
constructed, a turn-up shall be provided between the wall and the screed.
Up to 8
8 to 15
Over 15
0,5
0,7
1,5
0,5
1,5
3,0
0,5
1,0
2,0
On site classes H1 to H3, no trees shall be planted within the minimum distances shown in figure 51
from any foundation.
102
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
The aim of modified normal construction is to enable the superstructure to deflect in sympathy with
foundation movements without undue distress.
Modified normal construction shall include:
a) Reinforcement of all footings as shown in table 30.
b) Brickforce in every third course of foundation walls and brick veneer and in each of the
uppermost three courses of foundation brickwork.
c) Light reinforcement of floor slabs (mesh ref 193 or ref 245 for structures > 125 m2).
d) Articulation joints at all external doors and internal doors in all straight walls longer than 6 m or
running the full width of length of the structure.
Foundations and foundation brickwork should be continuous below joints in the superstructure.
Brickforce should not pass through movement joints in the brick veneer.
NOTE These requirements fall short of those for split construction which include movement joints in wall
panels, movement joints at the intersection of internal and external walls and the strengthening of panels
between joints.
8.7.5.2 Plumbing
All plumbing entering or leaving the structure should be capable of accommodating the expected
differential movements without suffering damage. Brittle pipes or pipe couplings and piping subject
to corrosion should not be used on expansive or collapsible soil profiles.
103
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Annex A
(informative)
2
Self-weight
kN/m
a
0,18
0,28
0,35
Timber flooring up to 22 mm thick plus ceramic or terracotta floor covering and ceilings
a
104
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
0,45
SANS 517:2009
Edition 1
Component
Timber Strip flooring
Particleboard flooring
Plywood flooring
Self-weight
kN/m2
12 mm softwood
0,06
19 mm softwood
0,10
12 mm hardwood
0,10
19 mm hardwood
0,15
19 mm
0,13
22 mm
0,15
25 mm
0,18
15 mm
0,08
17 mm
0,09
19 mm
0,11
15 mm
0,28
18 mm
0,33
24 mm
0,44
0,01 to 0,06
0,10 to 0,40
2
Self-weight
2
kN/m
Steel sheet roofing 0,50 m thick and 0,58 mm thick roof battens at 900 mm spacing
0,06
Steel sheet roofing 0,50 mm thick, 0,58 mm thick steel roof battens at 900 mm spacing,
10 mm plaster ceiling and 0,58 mm thick steel ceiling battens at 450 mm spacing, sarking
and lightweight insulation
0,15
Concrete or terracotta roof tiles and 0,58 mm thick steel roof battens at 330 mm spacing,
sarking and lightweight insulation
0,61
Concrete or terracotta roof tiles and 0,58 mm thick steel roof battens at 330 mm spacing,
10 mm plaster ceiling and 0,58 mm thick steel ceiling battens at 450 mm spacing, sarking
and lightweight insulation
0,70
105
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Component
Material
Material
thickness
Spacing
Self-weight
mm
mm
kN/m
Steel sheet
0,50
0,58
0,053
0,061
Aluminium sheet
1,2
0,050
Terracotta tiles
Concrete tiles
Metal sheet tiles
0,580
0,540
0,075
Plasterboard
10
13
0,075
0,100
12
19
0,065
0,105
Plywood
12
8
0,065
0,050
4,8
5,5
0,050
0,055
50
50
0,100
0,200
4,5
6,0
0,070
0,090
Lightweight insulation
plus sarking
Heavyweight insulation
0,010
0,05 to 0,15
Z or C section
100 mm 1,5 mm
Z or C section
150 mm 1,5 mm
1 200
0,021
1 200
0,029
Z or C section
200 mm 1,9 mm
Z or C section
250 mm 2,4 mm
1 500
0,038
1 500
0,053
Z or C section
300 mm 3,0 mm
Z or C section
350 mm 3,0 mm
1 800
0,070
1 800
0,083
450
600
0,010
0,007
0,020
0,007
1 200
1 200
0,010
0,022
Roofing
Ceiling
softwood
hardwood
Hardboard
Fibreboard
low density
high density
Battens or
purlins
106
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Annex B
(informative)
System effect
B.1 Introduction
The interaction between structural elements and other elements of the construction system is
reflected in the design criteria. This is known as the system effect. Some of the elements of the
system effect can be established by calculation; others can be assessed by testing.
Once a particular system effect is quantified either by calculation or testing, it can be incorporated
into the design calculation. It is important to recognize that the system effect may change with
changes in materials and method of construction, especially if the effects have been established by
testing.
The system effect may be calculated as in B.2 or B.3, if applicable.
(0,2 ks 1,0)
where
kb
kc
Eb,Ec
are the modulus of elasticity of the member and the crossing members, respectively;
Ib, Ic
are the second moment of area of the member and a crossing member, respectively;
107
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
kc
Eb,Ec
are the modulus of elasticity of the member and the crossing members, respectively;
Ib, Ic
are the second moment of area of the member and a crossing member,
respectively;
This ks value is valid only when the distributed loads lie within the middle half of the beam.
Table B.1 Key values
1
Length
3
Value
k1
k2
0,20
0,95
0,15
0,75
108
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Annex C
(informative)
Classification of damage
The classification of damage is given in tables C.1 to C.2.
Table C.1 Classification of damage with reference to walls
(NHBRC Home Builders Manual and AS 2870.1)
1
Description of damage in terms of ease of repair
and typical effects
2
Approximate maximum
crack width in walls
mm
3
Category and degree
of expected damage
< 0,25
0
Negligible
1
Very slight
<5
2
Slight
3
Moderate
4
Severe
5
Very severe
109
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table C.2 Classification of damage with reference to concrete floors
(NHBRC Home Builders Manual and AS 2870.1)
1
Description of typical damage
2
Appropriate
maximum crack
width in floor
Maximum deviation of
any joint from a 3 m Category and degree
straight edge
of expected damage
mm
mm
< 0,3
<5
0
Negligible
< 1,0
<8
1
Very slight
< 10
2
Slight
2 to 4
10 to 20
3
Moderate
>4
> 20
4 to 5
Severe to very severe
NOTE 1 Crack width is only one factor in assessing damage and should not be used on its own as a direct
measure of damage. In assessing the degree of severity of damage, the location in the building where it
occurs, and also of the function of the building, will be relevant.
NOTE 2 This classification is based on the ease of repair which may be considered under three headings
representing a progression in difficulty of repair, namely, redecoration due to wear and tear, remedial work to
reinstate functional efficiency and structural repair. The former two categories relate to minor damage
(categories 0 to 2).
NOTE 3 Where cracking occurs in easily repairable plasterboard or similar clad-framed structures, the
crack width limits in each category may be increased by 50 %.
NOTE 4 In most instances, minor damage (categories 0 to 2) represent aesthetic damage as opposed to
serviceability damage (categories 3 and 4) and stability damage (category 5).
NOTE 5 Where cracks of less than 1 mm are widespread throughout the building, the damage may be
regarded as being category 2.
NOTE 6 The descriptions contained in column 1 relate to single storey construction. In multi-storey
construction, these descriptions will require modification for a particular category of expected damage.
NOTE 7 Local deviation of slope, from the horizontal or vertical, of more than 1/100 will normally be clearly
visible. Overall deviations in excess of 1/150 are undesirable.
110
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Table C.3 Classification of damage caused by ground floor slab settlement
(NHBRC Home Builders Manual)
1
Description of typical damage
Appropriate
crack width in
floor
Approximate
gap
mm
mm
4
Category
and degree
of expected
damage
Up to 1
0
Negligible
Up to 5
1
Very slight
Up to 1
Up to 15
2
Slight
Up to 5
Up to 20
3
Moderate
5 to 15
Up to 25
4
Severe
Usually greater
than 15 but
depends on the
number of
cracks
Greater than 25
5
Very severe
NOTE Gap refers to the space, usually between the skirting and finished floor, caused by settlement after
making appropriate allowance for discrepancy in, for example, building, shrinkage, and normal bedding
down.
111
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
SANS 517:2009
Edition 1
Bibliography
SANS 298, Mastic asphalt for damp-proof courses and tanking.
SANS 629 (SABS 629), Softwood flooring boards.
SANS 717-1/ISO 717-1, Acoustics Rating of sound insulation in buildings and of building
elements Part 1: Airborne sound insulation.
SANS 717-2/ISO 717-2, Acoustics Rating of sound insulation in buildings and of building
elements Part 2: Impact sound insulation.
SANS 929, Plywood and composite board.
SANS 1077, Sealing compounds for the building and construction industry, two-component,
polyurethane-base.
SANS 1090, Aggregates from natural sources Fine aggregates for plaster and mortar.
SANS 1381-2, Materials for thermal insulation of buildings Part 2: Loose fill thermal insulation
material.
SANS 1431, Weldable structural steels.
SANS 1508, Expanded polystyrene thermal insulation boards.
SANS 9933, Products in fibre-reinforced cement Long corrugated or asymmetrical section sheets
and fittings for roofing and cladding.
SANS 10021, The waterproofing of buildings (including damp-proofing and vapour barrier
installation).
SANS 10082, Timber frame buildings.
SANS 10109-1 Concrete floors Part 1: Bases to concrete floors.
SANS 10109-2, Concrete floors Part 2: Finishes to concrete floors.
SANS 10237 (SABS 0237), Roof and side cladding.
SANS 10244-2, Steel wire and wire products Non-ferrous metallic coatings on steel wire Part 2:
Zinc and zinc alloy coatings.
SABS
112
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.
Copyright protected. This standard was downloaded on 2011-04-04 10:20 by Mr. John Anderson (Private).
Single-user license only; copying and networking prohibited.