2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
Contents
1 2 Scope Applicable Standards 2.1 2.2 2.3 3 Electrical Standards ....................................................................................................................... 3 Mechanical Standards ................................................................................................................... 4 Communication Standards............................................................................................................ 4
General Meter/System Requirements 3.1 3.2 3.3 Auxiliary Power Supply ................................................................................................................. 4 Rated Electrical Parameter ........................................................................................................... 5 Climatic Conditions ....................................................................................................................... 6
Measured Parameters 4.1 Instantaneous Parameters ............................................................................................................ 6 Instantaneous Parameters .................................................................................................... 6 Average RMS voltage ............................................................................................................ 6 Average Frequency ............................................................................................................... 6 Net Power Factor .................................................................................................................. 7 RTC: ....................................................................................................................................... 7
Energy Parameters ........................................................................................................................ 7 Active Energy......................................................................................................................... 7 Reactive Energy ..................................................................................................................... 7 Apparent Energy ................................................................................................................... 7
Demand Parameters ..................................................................................................................... 8 Maximum Demand ............................................................................................................... 8 Cumulative Demand.............................................................................................................. 8 Rising Demand ...................................................................................................................... 8
Stored Parameters 5.1 5.2 5.3 Time of Use (ToD/ToU) Parameters .............................................................................................. 8 Billing Parameters ......................................................................................................................... 9 Load Survey Parameters ............................................................................................................... 9
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
5.4
5.4.1
5.5 ........................................................................................................................................................... 11 6 Display Parameters 6.1 6.2 6.3 7 8 LCD Details .................................................................................................................................. 12 6.2 Display on Meter ................................................................................................................... 12 Display Parameters ..................................................................................................................... 13
Communication & BCS Software: CONSTRUCTION OF THE METER 8.1 8.2 8.3 SEALING OF THE METER:............................................................................................................. 16 TERMINAL BLOCK COVER: ........................................................................................................... 16 CONNECTION DIAGRAM & TERMINAL MARKING:- .................................................................... 17
Accessories
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
1 Scope
The Technical Specification shall cover the design, engineering, manufacture, assembly, inspection & testing at manufacturers works before supply and delivery at site / FOR destination of class 0.2s accuracy static HT tri vector availability based tariff meters. The offered meters shall be suitable for commercial/tariff metering for bulk, inter utility power flows as well open access consumer for ABT application. The said meters will be installed on various EHV/HV lines as a self-contained device for measurement of average frequency and active energy for each successive 15 minute blocks as per relevant national/international standards. The meter shall be capable of other tariff applications like Time of Day (TOD) metering. The offered metering system shall be projection type. The meters shall be 3 phase 4 wire type suitable for connection to 3 phase 4 wire systems. The meter shall be capable to record and display Active, Reactive and Apparent energy and maximum demand(kW/kVA) for 3 phase 4 wire AC balanced/ unbalanced loads for a power factor range of zero (lagging), unity and zero (leading) for both export and import. In other words, the meter shall be capable of measuring and recording in all the four quadrants. The meters shall have two test outputs (for Active and Reactive) in the form of blinking LEDs for testing the meters accuracy. Testing shall also be possible through optical port accessible from the front and can be monitored with Meter Reading Instrument having high-resolution display.
2 Applicable Standards
The offered meters shall conform to the following Indian/International Standards and all related Indian/International Standards, which are to be read with up to date and latest amendments/revisions thereof:
CBIP Technical Report 304 with Specification for AC static electrical latest amendments energy meters IEC 62053-22 with latest AC static Watt-hour meters for active
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
energy class 0.2S and 0.5S. latest Basic environmental testing procedures for electronic and electrical items.
2.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
2.
Current
3. 4. 5.
50Hz Zero(lag)-Unity-Zero(Lead) Voltage Circuit The power consumption shall not be greater than 1.5watts & 10VA in reference operating conditions. Current Circuit It shall not be greater than 1VA in reference Operating Conditions.
6.
Accuracy
0.2S
The meters shall withstand the fluctuations arising during line faults. Specifically, 115% of rated VT secondary voltage applied continuously; 190% of rated VT secondary voltage applied for 3 seconds; 120% of rated CT secondary current applied continuously; or 20 times of maximum current applied for 0.5 seconds-- shall not cause any damage to or the mal -functioning of the meter.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
4 Measured Parameters
The meter shall measure and compute Energy, Demand and other Electrical parameters on Real Time Basis.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
4.1.4 Net Power Factor The meter shall compute the Net Power Factor that is the ratio of Active Power to Apparent Power. Net Power Factor = (kW) / (kVA) 4.1.5 RTC: The meter shall have a built in calendar in clock, having an accuracy of 3 minutes per year or better. The calendar and clock shall be correctly set at manufacturers works. Clock adjustment shall be possible at site using the common meter reading instrument (CMRI). A separate internal Lithium battery back-up shall be provided for continuous operation of meter RTC for at least two years under meter un-powered conditions. The offered meters shall be supplied duly fitted with the long life battery of at least 10 years as long as total PT failure does not exceed two years.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
In Import Mode [kVAh (Import)+ = (kWh import) 2 + (kVArh lag import + kVArh lead import) 2 In Export Mode *kVAh (Export)+ = (kWh Export) 2 + (kVArh lag Export + kVArh lead Export) 2
5 Stored Parameters
The meter shall have a non-volatile memory to store the measured parameters as specified in Technical Specification. The meter shall store load survey data for at least 75days which shall be updated on FIFO basis. The non-volatile memory shall retain the data for a period not less than 10 years under unpowered condition; battery backup memory shall not be considered as NVM. The Stored data shall be available through communication ports while down loading the meter using Hand Held Units for Billing/Analysis/Report Generation purpose at Base Computer Station.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
5.4.1.1 Potential Miss Meter shall have provision to detect the PT miss Phase wise.
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
5.4.1.2 Voltage Unbalance Meter shall have provision to detect the voltage unbalance when the difference between Vmax and Vmin is more than a threshold value. 5.4.1.3 Current Reversal Meter shall have provision to detect the Current reversal in CT Phase wise. 5.4.1.4 Current Unbalance Meter shall have provision to detect the Current unbalance when difference between Imax and Imin is more than the threshold value. 5.4.1.5 CT Open Meter shall detect the CT open as per the threshold values. 5.4.1.6 CT Bypass Meter shall have provision to detect the event of Current Bypass as per thresholds. 5.4.1.7 Neutral Disturbance Injection of Spurious Signals/DC injection through Diode affecting the meter functionality shall be detected. 5.4.1.8 Magnetic Influence Meter shall be accurate under Magnetic Influence as per CBIP report No.304. Meter shall record Energy at Vref, Imax & UPF in magnetic influence.
10
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
S.NO
TAMPER TYPE
OCCURANCE THRESHOLDS
RESTORE THRESHOLDS
CONDITION
Link Miss
First compartment
Meter Under Influence Ix > 5 % Ibasic Vx >40% Vref Direction ve Net PF > 0.1
Magnetic Meter Not Under Magnetic Third Influence compartment Ix > 10 % Ibasic Vx >40% Vref Direction +ve Net PF > 0.1 Vx>25% Vref and Other 2 phases<72Volt
5.5
Second compartment
Neutral Disturbance
Vx<25% Vref and Other 2 phases>125% Vref (Imax Imin) > 30% of Ib and Average current>20mA Bypass Current>20% Ib
Third Compartment
CT Open
Voltage Unbalance
Vmax-Vmin>10% of max Vmax-Vmin<10% of max First voltage of 3-phase voltages voltage of 3-phase voltages compartment All Voltages>60% Vref All Voltages>60% Vref
11
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
6 Display Parameters
The meter shall have provision to display the measured parameters on an LCD as detailed below.
12
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
13
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
PUSH MODE Push All segment check Real Time Real Date Meter ID(Meter Serial No.) Bill KWH import Bill KWH export Bill KVAH import Bill KVAH export Bill MD KVA import Bill MD KVA export Bill PF import Bill PF export Bill Reactive High lag import when V>103% Vref Bill Reactive High lag export when V>103% Vref Bill Reactive High lead import when V>103% Vref Bill Reactive High lead export when V>103% Vref Bill Reactive low lag import when V<97% Vref Bill Reactive low lag export when V<97% Vref Bill Reactive low lead import when V<97% Vref Bill Reactive low lead export Vref Power on hours Md reset count last IP block active energy import last IP block active energy export Average Frequency of previous Block Average Percentage voltage Reactive High lag import when V>103% Vref Reactive High lag export when V>103% Vref Reactive High lead import when V>103% Vref Reactive High lead export Vref when V>103% when V<97%
Reactive low lag import when V<97% Vref Reactive low lag export when V<97% Vref Reactive low lead import when V<97% Vref Reactive Hlow lead export Vref Active Energy Import Active Energy Export when V<97%
14
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
Cumulative Reactive Lag during KWh import Cumulative Reactive Lag during KWh Export Cumulative Reactive Lead during KWh import Cumulative Reactive Lead during KWh Export Apparent Energy during KWh Import Apparent Energy during KWh Export Instantaneous power factor cumulative MD KVA import cumulative MD kva export Instantaneous R phase voltage Instantaneous Y phase voltage Instantaneous B phase voltage Instantaneous R phase current Instantaneous Y phase current Instantaneous B phase current Line frequency in Hz Phase sequence Active Power( KW) Reactive Power( KVAR) Apparent Power(KVA)
MD Kw import MD Kw export MD KVA import MD KVA export R/Y/B Phase voltage miss Voltage Unbalance Neutral disturbance R/Y/B Phase current reverse Load bypass R/Y/B/CT open Current unbalance magnet tamper Last Tamper Occur Last Tamper Occur Date Last Tamper Occur Time Last Tamper Restore Last Tamper Restore Date Last Tamper Restore Time Cumulative Tamper Count
15
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
16
TECHNICAL SPECIFICATIONS FOR 0.2S ACCURACY CLASS AC STATIC TRIVECTOR ENERGY METERS, SUITABLE FOR AVAILABILITY BASED TARIFF APPLICATION.
the terminal cover when energy meter is mounted on the meter board.
8.3 CONNECTION DIAGRAM & TERMINAL MARKING:The connection diagram of the meter shall be clearly shown on inside portion of terminal cover and should not fade with time. Meter terminals shall also be marked and should appear in the above diagram. Meter shall have a name plate clearly visible, secured against removal & indelibly and distinctly marked with all the essential particulars as per relevant standards i.e. a. Manufacturers name and trademark b. Serial number c. Type designation d. Rated current, voltage ,frequency, PT ratio e. Relevant IS/IEC No. along with ISI certificate mark, wherever available. f. Meter constant shall invariably be indicated. g. Name of the owner, purchase order no. & date and month/year of manufacturing shall be printed. h. Guarantee Period i. Principal units of measurement. j. Number of phases and wires k. Class index of meter
9 Accessories
The Meter shall be supplied with BCS/CMRI software CDs, one copy at each Division/sub-Division or as per requirement. Communication Cable (Meter to CMRI) shall be supplied with each meter. Each Meter shall have user manual with Display Parameter, Tamper Threshold & connection Diagram details.
17