Influent pumping facilities shall be capable of pumping the Peak Influent Rate (PIR) with the
largest pump out of service, unless a flow equalization basin is installed. Include here the wet
well calculations for the pumping station - 7.601.
6-23
Pretreatment devices:
Trash trap: Yes _____________ No ____________ Capacity ___________ gal.
Comminutor with bar screen bypass: Yes _____________
No ____________
Other _________________________________________________________________________
Design capacity of comminutor _____________ gal./min.
Method of flow division where parallel aeration unit arrangements are planned. Describe:
_______________________________________________________________________________
_______________________________________________________________________________
Aeration chamber volume: (based on 80 cu. ft./lb. BOD5)
___________ lb. BOD5/day x 80 cu. ft. x 7.48 gal./cu. ft. = __________ gal.
______________ gallons supplied
Aeration detention time:
Chamber volume
gal. x 24 hours
_____________________________ = ______________ hours
ADDF ___________ gal./day
Are the dimensions and proportions of the aeration tanks such as to maintain effective mixture and utilization
of air, to prevent unaerated sections and noticeable channeling, and to maintain velocities sufficient to
prevent deposition of solids?
Yes __________ No ___________
Are inlets and outlets for each aeration tank provided with valves, gates, stop-planks, weirs, or other
devices to permit flexibility in controlling the flow to any unit to maintain a reasonable constant water level
and to permit cleaning of individual units?
Yes __________ No ___________
Are the aeration plates, tubes, or jets used for the introduction of air to mixed liquor removable for
inspection, maintenance, and replacement without de-watering the tank?
Yes _________ No ___________ N/A ___________
If mechanical aerators are to be used, the oxygen required will be:
____________ lbs.BOD5/day x 2 = ______________lbs. 02/day
NOTE:
Calculations and data should be included to verify the 02 transfer rate used to compute the
supplied amount of 02/day.
Non-mechanical hoppered tanks only may include the upper 1/3 (by height) of the hopper(s)
in computing detention time.
If the Influent Pumping Rate (IPR) exceeds the peak Influent Flow Rate (PIR), then it should be
substituted in the above equation for (PIR).
If the Influent Pumping Rate (IPR) exceeds the Peak Influent Flow Rate (PIR), then it should
be substituted in the above equation for (PIR).
6-25
Note: A minimum storage volume of 1,000 gallons will be required for plants with a design flow of less
than 10,000 gal. day.
If aerobic digestion of sludge is to be utilized, the volume of the tank(s) will be: (based on three cubic feet
per population equivalent)
Design BOD5 loading lbs./day x 3 x 7.48
_____________________________________ = _____________ gal. (minimum)
0.167 lbs. BOD5/population equivalent
_____________ gallons supplied
a. Air supply: (based on 20 cu. ft./min. per 100 cu. ft. of volume)
gallons supplied x 20 cu. ft./min.
_____________________________________ = _____________ cu. ft./min.
7.48 gal./cu. ft. x 1,000 cu. ft.
Air supplied: ____________ cu. ft./min. (with largest blower our of service)
6-26
If anaerobic digestion of sludge is to be utilized, the volume of the tank(s) will be:
______________ gal.
NOTE: Basis of design and calculations must be submitted for the above volume.
If sludge drying beds are to be installed, the area provided shall be: (based on one square foot per
population equivalent)
NOTE:
Where phosphate removal or other chemical treatment processes are to be utilized, design of
sludge handling facilities must take into account possible increased sludge production.
Check which of the following modes of advanced treatment of effluent disposal are to be installed:
___________ Surface slow sand filter
___________ Rapid sand gravity filter
___________ Microstrainers
___________ Lagoons
___________ Other:
If surface slow sand filters are to be installed, the area provided shall be: (Based on 11.5 gallons per square
foot per day)
ADDF
gal./day
_____________________________________ = _____________ sq. ft
11.5 gal./sq. ft./day
_____________square feet provided _______________ number of beds
a. Capacity of dosing chamber shall be: _____________ gallons
b. Size of dosing pumps: _____________ gal./min. (with largest pump out of service)
NOTE:
Dosing chamber and pumps must be sized to dose half of the total filter to depth of three (3)
inches within 10 to 15 minutes.
6-27
*NOTE: The peak flow rate shall be equal to the maximum rate of the pumping facilities preceding
filtering.
a. Clearwell capacity: _____________ gallons
b. Rate of backwash: _____________ gpm/sq. ft.
c. Duration of backwash: ____________ minutes
d. Number of backwash pumps: ____________ @ _____________ gal./min.
e. Mudwell capacity: ____________ gallons
NOTE:
Please refer to Part II of Ohio EPA's "Recommended Engineering Procedures and Design
Guidelines Relative to Advanced Wastewater Treatment" in designing rapid sand gravity filters.
If microstrainers are to be installed, the net submerged effective area of the microstrainer fabric shall be:
(based on 3.33 gpm/sq. ft. at the peak flow rate).
The peak flow rate shall be equal to the maximum rate of the pumping facilities preceding the
microstrainers.
6-28
a.
b.
NOTE:
Please refer to Part II of Ohio EPA's "Recommended Engineering Procedures and Design
Guidelines Relative to Advanced Wastewater Treatment" in designing microstrainers.
If lagoons are to be utilized, their total volume will be: (based on five (5) days detention)
Design hydraulic flow _____________ gal./day x 5 = ________ gal.
________ gallons supplied
Average design flow depth: ____________ feet
Number of cells: _______________
Minimum freeboard of _____________ feet will be provided.
The embankments of the lagoons shall have a minimum slope of ________________ vertical to
__________________ horizontal.
Does the overflow structure provide flexible water depth control and operation of facilities?
Yes ____________ No ____________
NOTE:
Prior to designing tertiary lagoons, contact the Division of Waste Management and Engineering
in the appropriate District Office for information relative to the acceptability of the proposal.
Are the tank(s) baffled or so constructed as to reduce short circuiting of flow to a minimum?
Yes ____________ No ______________
Describe provisions for cleaning tank(s) and for maintaining adequate disinfection during cleaning operations:
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
6-30
What provisions, if any, will be made to provide standby power for electrical equipment?
Describe: _________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
Should include capacity.