3516 516de4a 50HZ 6300
3516 516de4a 50HZ 6300
FEATURES
FUEL/EMISSIONS STRATEGY Low Fuel consumption DESIGN CRITERIA The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response. FULL RANGE OF ATTACHMENTS Wide range of bolt-on system expansion attachments, factory designed and tested Flexible packaging options for easy and cost effective installation SINGLE-SOURCE SUPPLIER Fully prototype tested with certified torsional vibration analysis available WORLDWIDE PRODUCT SUPPORT Cat dealers provide extensive post sale support including maintenance and repair agreements Cat dealers have over 1,600 dealer branch stores operating in 200 countries The Cat SOSSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products CAT 3516 TA DIESEL ENGINE Reliable, rugged, durable design Field-proven in thousands of applications worldwide Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight CAT SR5 GENERATOR Matched to the performance and output characteristics of Cat engines Industry leading mechanical and electrical design Industry leading motor starting capabilities High Efficiency CAT EMCP 3 SERIES CONTROL PANELS Simple user friendly interface and navigation Scalable system to meet a wide range of customer needs Integrated Control System and Communications Gateway
Exhaust
Fuel
Power Termination
Generators
[ ] Load share governor [ ] EMCP 3.2 ... [ ] EMCP 3.3 [ ] Option for right or left mount UIP [ ] Local & remote annunciator modules [ ] Digital I/O Module [ ] Generator temperature monitoring & protection [ ] Remote monitoring software [ ] Oil level regulator [ ] Deep sump oil pan [ ] Electric & air prelube pumps [ ] Manual prelube with sump pump [ ] Duplex oil filter [ ] Isolator removal [ ] Spring-type vibration isolator(shipped loose) [ ] Battery chargers (10& 20 Amp) [ ] 45 amp charging alternator [ ] Oversize batteries [ ] Ether starting aids [ ] Heavy duty starting motors [ ] Barring device (manual) [ ] Air starting motor with control & silencer [ ] Front stub shaft [ ] CSA certification [ ] CE Certificate of Conformance * Not included with packages without radiators
Lube
Mounting Starting/Charging
Lubricating oil Gear type lube oil pump Oil filter, filler and dipstick Oil drain lines and valve Fume disposal Rails - Engine / generator / radiator mounting Rubber anti-vibration mounts (shipped loose) 24 volt starting motor(s) Batteries with rack and cables Battery disconnect switch
General
Right hand service Paint - Caterpillar Yellow (with high gloss black rails & radiator) SAE standard rotation Flywheel and flywheel housing - SAE No. 00
SPECIFICATIONS
CAT GENERATOR
Caterpillar HV Generator Frame size....................................................................... 2750 Excitation................................................ Permanent Magnet Pitch.............................................................................. 0.6670 Number of poles...................................................................4 Number of bearings......................................................... 002 Number of Leads.............................................................. 006 Alignment.....................................................Closed Coupled Overspeed capability - % of rated................................... 125 Wave Form...................................................................002.00 Paralleling kit/Droop Transformer......................... Standard Voltage regulator..................3 Phase sensing with volts/Hz Voltage regulation............Less than +/- 1/2% (steady state) Less than +/- 1% (no load to full load) Telephone Influence Factor.............................. Less than 50 Harmonic distortion......................................... Less than 5% Insulation......Class F with tropicalization and antiabrasion
TECHNICAL DATA
Open Generator Set - - 1500 rpm/50 Hz/6600 Volts Low Fuel Consumption Generator Set Package Performance Genset Power rating @ 0.8 pf Genset Power rating with fan Coolant to aftercooler Coolant to aftercooler temp max Fuel Consumption 100% load with fan 75% load with fan 50% load with fan Cooling System1 Air flow restriction (system) Air flow (max @ rated speed for radiator arrangement) Engine Coolant capacity with radiator/exp. tank Engine coolant capacity Radiator coolant capacity Inlet Air Combustion air inlet flow rate Exhaust System Exhaust stack gas temperature Exhaust gas flow rate Exhaust flange size (internal diameter) Exhaust system backpressure (maximum allowable) Heat Rejection Heat rejection to coolant (total) Heat rejection to exhaust (total) Heat rejection to aftercooler Heat rejection to atmosphere from engine Heat rejection to atmosphere from generator Alternator2 Motor starting capability @ 30% voltage dip Frame Temperature Rise Lube System Sump refill with filter
3
DM7962
1825 kVA 1460 ekW 82 C 382.7 L/hr 292.0 L/hr 209.2 L/hr 0.12 kPa 1543 m/min 398.0 L 233.0 L 165.0 L 115.7 m/min 477.6 C 304.2 m/min 203.2 mm 6.7 kPa 961 kW 1380 kW 191 kW 159 kW 57.7 kW 2843 skVA 2750 105 C 401.3 L 180 F 101.1 Gal/hr 77.1 Gal/hr 55.3 Gal/hr 0.48 in. water 54491 cfm 105.1 gal 61.6 gal 43.6 gal 4085.9 cfm 891.7 F 10742.7 cfm 8.0 in 26.9 in. water 54652 Btu/min 78480 Btu/min 10862 Btu/min 9042 Btu/min 3281.4 Btu/min
Emissions (Nominal) NOx mg/nm3 7168.2 mg/nm CO mg/nm3 328.6 mg/nm HC mg/nm3 95.7 mg/nm PM mg/nm3 34.7 mg/nm 1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory. 2 UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40 degree C ambient per NEMA MG1-32. 3 Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel with 35 API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
DIMENSIONS
Package Dimensions
Length Width Height Weight 6233.2 mm 2286.0 mm 2342.0 mm 17 909 kg 245.4 in 90 in 92.2 in 39,483 lb
NOTE: For reference only - do not use for installation design. Please contact your local dealer for exact weight and dimensions. (General Dimension Drawing #2748728).
Performance No.: DM7962 Feature Code: 516DE4A Gen. Arr. Number: 2524226 Source: U.S. Sourced August 30 2010 16288811
www.CAT-ElectricPower.com 2010 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, SAFETY.CAT.COM their respective logos, "Caterpillar Yellow," and the POWER EDGE trade dress, as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. 6