HV/LV distribution transformers

Minera

ground-mounted, mineral oil-immersed transformers


from 50 to 2500 kVA
insulation voltage 24 kV EN 50464-1, losses B0 Bk (High efficiency)
standards

These transformers comply with standards:


EN 50464-1
EN 60076-1 to 10
Products assembled using new components, PCB-free
guaranted

standard fittings

one 3 or 5 positions off-circuit tap changer

on the cover, with padlocking

3 HV plug-in bushings (250 A / 24 kV)

on the cover

4 LV flat-bars (from 250 kVA)

description

Mineral oil-immersed, 50 Hz, three-phase


distribution transformers with the following
characteristics:
hermetically sealed with integral filling
cover bolted to the tank
ONAN-type natural cooling
Indoor/outdoor use
(depending on selected fittings and options)

anti-corrosion surface treatment :

corrositivity category C3, Medium


durability (according to ISO 12944-2)
final colour grey RAL 7033
protection index IP00 (coverless version)

4 LV porcelain bushings (from 50 to 160 kVA)


4 bi-directional flat rollers
2 lifting and untanking lugs
2 pulling eyelets on the frame
2 earthing terminals on the cover
(M12 studs)

1 filling plug
1 draining device (according to EN 50216-4)
1 aluminium rating plate

3 mobile connectors for plug-in

optional fittings

liquid retention container

bushings straight or elbow

(cable characteristics must be specified)

protection relays (DMCR or DGPT2)

on the filling plug


1 free, thermometer pocket
control device in the thermometer pocket

Load losses performance


No-load losses performance
Minera oil-immersed transformers Minera oil-immersed transformers
according to EN 50464-1
according to EN 50464-1
Optimum efficiency

(pointer thermometer with 0 or 2 contacts max,


2-contact thermostat, etc.)

liquid dielectric

A0

3 HV, 250 A porcelain bushings


4 LV porcelain bushings (from 250 kVA)
LV, sealable cover, rated IP21 or IP54

new insulating mineral oil


tested in accordance with IEC 60296
compatible with all the transformers

C0

rated power (kVA)

50
100
160
250
315
400
500 630
630
primary 15 and/or 20 kV
rated voltage
secondary at no-load 400 to 433 V between phases, 231 to 250 V phase to neutral
primary 17,5 kV for 15 kV
rated insulation level (1)
24 kV for 20 kV
MV tapping range (off-circuit)
2,5 % and/or 5 %
Yzn 11 (50 kVA version only)
vector group
Dyn 11

kV eff, 50 Hz - 1 mn
kV choc, 1,2/50 s

(kV)

800

1000

1250 1600

2000 2500

180
1475

260
360
2000 2750

440
3250

520
3850

610
4600

730
5400

680
5600

800
7000

940 1150 1450 1800 2150


9000 11000 14000 18000 22000

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

B0Bk

4
1
10
0,2
1,81
3,57
98,07
97,60
98,42
98,03
42
33

4
1
9
0,3
1,54
3,43
98,37
97,97
98,67
98,35
44
35

4
0,8
9
0,3
1,32
3,31
98,61
98,27
98,86
98,58
47
37

4
0,8
8
0,3
1,17
3,22
98,77
98,47
98,99
98,74
50
40

4
0,8
8
0,3
1,11
3,17
98,84
98,56
99,05
98,81
52
42

4
0,8
8
0,3
1,04
3,13
98,92
98,65
99,11
98,89
53
42

4
0,8
8
0,3
1,00
3,10
98,97
98,71
99,15
98,95
54
43

4
0,7
8
0,35
0,93
3,06
99,04
98,80
99,21
99,01
55
44

6
0,7
8
0,35
,093
3,06
99,04
98,80
99,21
99,01
55
44

6
0,7
6,5
0,4
1,05
4,35
99,03
98,80
99,22
99,02
56
45

6
0,7
6,5
0,45
1,08
4,37
99,02
98,77
99,21
99,01
58
47

6
0,7
6,5
0,45
1,06
4,35
99,04
98,80
99,22
99,03
59
48

6
0,7
6,5
0,45
1,05
4,35
99,04
98,81
99,23
99,04
61
49

6
0,7
6,5
0,45
1,08
4,37
99,02
98,78
99,21
99,02
63
51

6
0,7
6,5
0,45
1,06
4,35
99,04
98,81
99,23
99,04
66
54

7,2

12

17,5

24

20
60

28
75

38
95

50
125

(2) measurements according to IEC 60076-10

Dk
Standard efficiency

110
875

(1) reminder of insuation levels:


rated insulation level

Ck

Standard efficiency

electrical characteristics

Bk

Bk

E0

(with or without lock)

no-load
due to load at 75C
combination of losses
according to EN 50464
rated impedance voltage (%)
no-load current (%)
Ie/In peak value
switching current
time constant
voltage drop
P.F. = 1
at full load (%)
P.F. = 0,8
P.F. = 1
100 %
load
P.F. = 0,8
efficiency (%)
P.F. = 1
75 %
load
P.F.= 0,8
acoustic power LWA
noise level
dB(A)(2) acoustic pressure LPA at 1 m

Ak

D0

locking device for plug-in bushings

losses (W)

B0

B0

(only with plug-in bushings on the HV side)

components

Optimum efficiency

HV/LV distribution transformers

Minera

ground-mounted, mineral oil-immersed transformers


from 50 to 2500 kVA
insulation voltage 24 kV EN 50464-1, losses B0 Bk (High efficiency)
dimensions and weights

HV side
F

lifting lug

earthing
terminal

1W

tap changer
earthing
terminal

1V

Note : Bushings are marked according


to the IEC 60616 standard.

D(3)

1U

(4)

2N 2W 2V 2U

free,
thermometer
pocket

D : Height over LV cable box (optional


accessory, compatible with HV plug-in
bushings only).

(3)

80 mm for the 50 kVA version.

Dimensions and weights are for


guidance only, and are provided for a
single-voltage transformer with the
following electrical characteristics: 20
kV (HV) / 400 V (LV) 3-position tap
changer, 2.5%
(5)

filling plug

rating plate

H H

40

A
corrugated panels in the corners
according to cooling needs

125(4)

J
B

38

LV side

rated power (kVA)


dimensions(5) (mm)

50

100

160

250

315

400

500

630

630

800

1000

1250

1600

2000

2500

1050

1100

1300

1200

1300

1450

1500

1700

1700

1700

1800

1950

1900

1900

2200

C
D

840

1120

880

1160

925

1205

1055

1395

1155

1495

1300

1640

1300

1640

1400

1740

1400

1740

1450

1790

1500

1840

1450

1855

1450

1855

1475

1975

1650

2150

80

80

75

150

150

150

150

150

150

150

150

170

170

170

170

650

700

265

F
J

265

total

800

265

900

265

900

265

265

1000

265

265

1300

1600

1850

2250

2250

2600

2900

3150

3600

3600

5000

1250

1250

1250

1250

1250

1250

1250

1600

2500

2500

3150

5000

255

340

350

450

450

105
540

85

590

85

670

820

265

900

105

820

1200

205

790

105

670

265

1300

180

600

105

670

265

1200

125

500

105

670

265

1200

105

105

670

265

1000

520
105

670

265

1000

520
105

670

265

1000

520
105

670

950

520
105

K
weights(5) (kg)
dielectric (mineral oil)

800

85

680

820

820

85

85

725

825

connections
maximum intensity (A)
LV flat-bars
LV porcelain bushings

250

250

250

630

630

630

1000

1000

1000

LV connections

12

50
50

18

50
18

3150 A

2500 A

70

20

10
M 12
165

250A

M 20
178

630A

60

26

60

14
263

1000A

17
26
M 30

100

50

100

14
340

25
20
40

15
120

M 42

2000A

3150

4500

60

14
372

120

200

150

255

290
locking
device

250 A porcelain bushings (option)


40

40
30

20
40

150

M 12

70
18
450

40
M 55

385

M 48

3150A

locking
device

87

(mobile connectors not supplied)

5000 A

porcelain bushings according to EN 50386 (standard from 50 to 160 kVA optional for other powers)

15

3150

50

135

35

20

25

310

120

45

14,5
11

2000

250 A plug-in bushings (standard)

45

31,5

50

120
50

250

12

250

31,5

1600 A

1250 A

31,5

52

11

14,5

100

106,5

31,5

97,5

31,5

31,5

12

221

31,5

52

14,5

12
155

11

31,5

52

31,5
31,5

63

63

2000

HV connectors according to EN 50180

flat-bars according to EN 50387 (standard from 250 kVA)


31,5

2000

4500A

250 A

Routine fittings such as bar and cable supports, flexible connectors, etc. will be supplied by the contractor, who will ensure that the transformer bushings are not subject to
mechanical stresses.

Schneider Electric SAS

Address :
france transfo
PO Box 10140
F-57281 Maizires-les-Metz cedex
France
tl : 33 (0)3 87 70 57 57 / fax : 33 (0)3 87 51 10 16
RCS Metz B 357801 109

Due to the evolution of standards and materials, the present document will
bind us only after confirmation from the technical department.

GEen 02 M EN-50464-1/BoBk Rev a

07/2010

You might also like