EATON Digitrip 810
EATON Digitrip 810
Contents 6 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Description Page 6.1 Digitrip RMS Trip Assemblies. . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Type DS Low-Voltage AC Power Circuit Breakers. . . . . . . . . 27
Important Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.3 Type DS II Low-Voltage AC Power Circuit Breakers . . . . . . . 27
1 General Description - Digitrip RMS 810
Trip Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 6.4 Type SPB Systems Pow-R. . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.1 Basic Digitrip RMS 810 Trip Unit. . . . . . . . . . . . . . . . . . . . . . . 4 6.5 Series C® R-Frame Molded Case Circuit Breakers. . . . . . . . 27
1.1.1 Operational Status and Protection TRIP Indicators. . . . . . 5 6.6 Assemblies Electronic Monitors. . . . . . . . . . . . . . . . . . . . . . 27
1.1.2 General Over-Current Protection. . . . . . . . . . . . . . . . . . . . 6 6.7 INCOM® AND IMPACC® Communications. . . . . . . . . . . . . . 27
1.1.3 Discriminator (High Initial Current Release) APPENDIX A: Zone lnterlocking. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
(For Types LS and LSG Trip Units Only) . . . . . . . . . . . . . . . 9 APPENDIX B: Interpreting Display Codes after Circuit Breaker
1.1.4 OVERRIDE (Fixed Instantaneous). . . . . . . . . . . . . . . . . . 10 Trips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1.1.5 Zone Interlocking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Four Character Information Display Window. . . . . . . . . . . . . 10
1.2.1 Values Displayed During Normal Service . . . . . . . . . . . . 10
1.2.1.1 Instrumentation - Current Values. . . . . . . . . . . . . . . . . 10
1.2.1.2 Instrumentation - Power and Energy Values. . . . . . . . . 13
1.2.2 Messages Displayed After ALARM or TRIP . . . . . . . . . . 13
1.2.2.1 ROM Error ... See I.L. . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.3 Frame Rating, Sensor Rating (where applicable) and Rating
Plugs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.4 Power / Relay Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.5 Potential Transformer Module. . . . . . . . . . . . . . . . . . . . . . . . 16
1.6 Auxiliary Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2 UL Listed Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3 Protection Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 Long Delay Current Setting. . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Long Delay Time Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Short Delay Current Setting . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.5 Short Delay Time Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6 Instantaneous Current Setting. . . . . . . . . . . . . . . . . . . . . . . 18
3.7 No Instantaneous Current Setting . . . . . . . . . . . . . . . . . . . . 18
3.8 Ground Fault Current Setting . . . . . . . . . . . . . . . . . . . . . . . . 18
3.9 Ground Fault Time Delay Setting . . . . . . . . . . . . . . . . . . . . . 19
4 Test Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 When To Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Testing Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 Conducting Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4.1 Not Tripping the Breaker. . . . . . . . . . . . . . . . . . . . . . . . . 21
4.4.2 Tripping the Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.5 Testing the Back-up Battery (Inside the Rating Plug) . . . . . . 21
4.5.1 Back-up Battery Check. . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.5.2 Replacing the Back-up Battery. . . . . . . . . . . . . . . . . . . . 21
5 Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1 Trip Unit Address and Baud Rate . . . . . . . . . . . . . . . . . . . . . 22
5.2 Remote Master Computer. . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Assemblies Electronic Monitor (AEM-II) and Breaker
Interface Monitor (BIM). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4 Both Remote Master Computer and AEM / BIM. . . . . . . . . 24
5.5 INCOM® Network Interconnections. . . . . . . . . . . . . . . . . . . 24
5.6 Information Communicated by Digitrip RMS 810. . . . . . . . . 24
5.7 System Power Factor (Remote) . . . . . . . . . . . . . . . . . . . . . . 26
5.8 Remote Closing and Tripping of Circuit Breakers. . . . . . . . . 26
5.9 Remote Resetting of the Trip Unit . . . . . . . . . . . . . . . . . . . . 26
1. Phase currents;
2. Ground current or Neutral current (when supplied); and
3. Rating plug.
Keyed
Green LED's Receptacle
Light to Identify for Auxiliary
Which Value Is Power Module
Presently Being Connector (See
Displayed in Section 1.6)
Window
4-Character
Display Window
The Unit INCOM
Press and release "PEAK RESET"
Address
Push button to Reset Peak Demand
(Circuit Breaker
Reading to Zero
Location References)
Catalog Number
Press and release "STEP" Push button
to Display Value of Next Parameter in
Window
LED's light "Red"
DS Rating Plug
to indicate cause
of trip Press and Release "Test"
Push Button to Initiate
Time-Current curve for Self-Test (See Section 4)
Phase Protection
Press and Release "Trip
Time-Current
Reset" Push Button to
Curve for Ground
Reset Trip Unit
Protection
SPB Rating Plug R-Frame Rating Plug
Figure 1. Digitrip RMS 810 Trip Unit Type LSIG with Rating Plug.
Figure 2. RMS Digitrip 810 Trip Unit - Block Diagram. 1.1.2 General Over-Current Protection
The Digitrip RMS 810 Trip Unit is completely self-contained and
In the event that control power is lost, the back-up battery in the when the circuit breaker is closed, requires no external control
Rating Plug (see Section 1.3 and Figures 1 and 9) continues to power to operate its protection systems. It operates from current
supply power to the LEDs. To check the status of the battery, see signal levels and control power derived through current sensors inte-
Section 4.5. grally mounted in the circuit breaker.
NNote: The Digitrip RMS 810 performs all of its protection functions regardless The Digitrip RMS 810 Trip Unit is available in six different types.
of the status of the battery. The battery serves only to maintain the indication Each Trip Unit may be equipped with a maximum of five phase and
of the reason for automatic trip. two ground (time-current) settings (see Section 3) to meet specific
Press and release the "TRIP RESET" push-button shown in Figure 1, application requirements. The protection available for each type is
to turn "Off" the LEDs following a trip operation. summarized in Table 1, and illustrated in Figures 3 through 8:
NNote: *RMS Digitrip Type LI, LS and LSI Trip Units can be applied on 3-pole or
4-pole circuit breakers for protection of the neutral circuit, IF the circuit break-
er is wired and MARKED for NEUTRAL PROTECTION. Refer to the National
Electric Code for appropriate application of 4-pole breakers.
Figure 3. Digitrip RMS 810 Type LI. Figure 5. Digitrip RMS 810 Type LSI.
Figure 4. Digitrip RMS 810 Type LS. Figure 6. Digitrip RMS 810 Type LIG.
notice
AFTER EACH TRIP OPERATION (WHETHER DUE TO OVERCURRENT
PROTECTION OR REMOTE CONTROL) THE AUTOMATIC LOCKOUT-AFTER-
TRIP FEATURE OF THE DIGITRIP RMS 810 TRIP UNIT MAINTAINS THE
CIRCUIT BREAKER IN A "TRIP-FREE" CONDITION, PROVIDED 120 VAC
CONTROL POWER REMAINS AVAILABLE TO THE POWER / RELAY MODULE.
THE TRiP UNIT MUST BE RESET BEFORE THE CIRCUIT BREAKER CAN BE
CLOSED AGAIN. THE RESET CAN BE ACCOMPLISHED EITHER LOCALLY BY
PRESSING AND RELEASING THE "TRiP RESET' PUSH BUTTON (SEE FIGURE
1),OR REMOTELY BY THE IMPACC SYSTEM (SEE SECTION 5.9).
or
Control power is not available, or wrong potential applied.
Trip unit not "ON" 1.4
NNote:
In the case of a high-level fault condition, the Trip Unit will operate verRlDe (Fixed Instantaneous) Trip is for type LS and LSG Trip Units
O
whenever a complete RMS current value exceeds the trip level. For (no Instantaneous element), on circuit breakers whose Short-Circuit
this reason, the displayed value may be less than the actual RMS fault current interrupting capability exceeds their Short- Time Current with-
current. stand capability (see Section 1.1.4).
In the case of a very high fault current, the message "ORNG" (indicating he values of the currents displayed after a TRIP event, are the values
T
over range) appears because the Trip Unit cannot display the actual at the time the TRIP operation was initiated. Although the magnitude
value of the fault current. of a fault current, for example, can continue to increase after the TRIP
operation is initiated, those values of current occurring after the TRIP
operation is initiated, are not displayed.
Range- 0 to 9.999 MW NNote: After a trip condition, RECORD all Values of interest and note which
"RED" LEDs are lighted. Correct the cause of the overload or fault BEFORE
Assumes - 5% < Current < 175% of the Plug Rating In YOU RESET the Trip Unit to avoid repeated tripping.
Sampling Window- 15 min. for Peak Demand, 1 sec. for The LOCKOUT after trip feature requires the Trip Unit to be reset
Present Demand before the breaker can be closed again.
Accuracy- ± 4% of (Frame Rating x 600 V) for Series C® For examples of how to interpret the display after an overload and
R-Frame or Type SPB circuit breakers, after a short-circuit, see Appendix B.
or ± 4% of (Current Sensor Rating x 600 V) for Type
DS circuit breakers. 1.2.1.1 ROM Error ... See I.L.
The Energy parameter is the summation of the average power over If the message, "ROM Error. . . See I.L.", scrolls across the display
time and it is expressed in megawatt-hours (MWh). The value is window, it means that a non-fatal error has been detected some-
updated approximately once a second. The value cannot be reset where in the Trip Unit's non-volatile memory. The Trip Unit will still
locally. After the maximum value is reached, the display automati- function to protect the circuit, but the calibration may be degraded
cally rolls over to zero. by a few percent. The Time-Current Curve tolerances may be exceed-
ed in some cases by as much as 12%.It is not necessary to trip and
The range and accuracy parameters for energy demand values dis- lockout the breaker. There may also be errors in values of current,
played are: energy, and power displayed and they could even be greater than
Range- 0 to 999.9 MWh if In ≤ 1000 A 12%. The scrolling message will not remain in the window constant-
ly but is repeated periodically to remind you to replace the Trip Unit.
0 to 9999 MWh if In > 1000 A
Assumes- 5% < Current < 175% of the Plug Rating In 1.3 Frame Rating, Sensor Rating (Where Applicable) and
Accuracy- ± 5% of (Frame Rating x 600 V x time) for Series Rating Plugs
C® R-Frame or Type SPB circuit breakers. The Frame Rating of a circuit breaker is the maximum RMS cur-
or ± 5% of (Current Sensor Rating x 600 V x time) rent it can carry continuously. The maximum Short-Circuit Current
for Type DS circuit breakers. Ratings of the circuit breaker are usually related to the Frame Rating
as well.
It is often times desirable to be able to choose a current value (In),
less than the full frame rating, to be the basis for the circuit break-
er's protection functions, without affecting its short-circuit current
capability. For the Digitrip RMS 810 Trip Unit the maximum continu-
ous current (In) is set by the Rating Plug (and/or Current Sensors,
Polarity
- +
Polarity
Rating Plug Battery "OK" Marks Battery
Identification if LED Lights Hinged
"Battery "GREEN" when Cover
Check" "Battery Check"
Push Button is
button Pushed
notice
THE POWER / RELAY MODULE HAS 120 V 50/60 HZ AC INPUT AS STANDARD
FOR ALL BREAKER TYPES. THERE IS AVAILABLE FOR CERTAIN BREAKER
TYPES A 230 V 50/60 INPUT VOLTAGE RATING. BEFORE ENERGIZING
THIS CONTROL VOLTAGE, PLEASE VERIFY CORRECT VOLTAGE RATING IS
EMPLOYED. THE DISPLAY, COMMUNICATION, OR TRIP RELAY ALARMS
MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED.
caution
APPLYING VOLTAGES GREATER THEN 600 VAC TO THE PRIMARY
CONDUCTORS OF THE CIRCUIT BREAKER, SUCH AS FOR DIELECTRIC
WITHSTAND TESTING, CAN POSSIBLY DAMAGE THE PTM OR THE TRiP
UNIT. FOLLOW THE INSTRUCTIONS GIVEN IN SECTION 4.1 FOR REMOVING
THE VOLTAGE DISCONNECT PLUG TO ISOLATE THE TRiP UNIT BEFORE
PERFORMING DIELECTRIC TESTS ON THE CIRCUIT BREAKER. SEE ALSO
THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT
BREAKER INSTRUCTION LEAFLET, LISTED IN SECTION 6.
NNote: " Ir" is also the basis for the Short-Delay Current Setting (see
Section 3.4).
6 x Ir
, Short Delay
Time
Available Settings
A.
.----- 2
I t Shape
200
250
50
63
60
75
70
88
80
100
100
125
120
150
150
188
200
250
“*” In Viewing Window I
Indicates 300 75 90 105 120 150 180 225 300
2
I t Shape
8 x Ir 400 100 120 140 160 200 240 300 400
Installed Rating Plug (Amperes) In
Figure 16. Short Delay time Settings. 600 150 180 210 240 300 360 450 600
630 158 189 221 252 315 378 473 630
3.6 Instantaneous Current Setting 800 200 240 280 320 400 480 600 800
There are eight (8) available lnstantaneous Current Settings, as illus- 1000 250 300 350 400 500 600 750 1000
trated in Figure 17. Six settings are in the range from 2 to 6 times 1200 300 360 420 480 600 720 900 1200
the rating plug value (In), and the other two settings are "M1" and
1250 312 375 438 500 625 750 938 1200
"M2" times (In). The values that "M1" and "M2" have depend upon
the type of circuit breaker, and are specified both on the rating plug 1600 400 480 560 640 800 960 1200 1200
label (see Figure 9), and on the applicable (I) Time-Current Curve ref- 2000 500 600 700 800 1000 1200 1200 1200
erenced in Section 6.
2400 600 720 840 960 1200 1200 1200 1200
2500 625 750 875 1000 1200 1200 1200 1200
Available Settings
3000/3150 750 900 1050 1200 1200 1200 1200 1200
3200 800 960 1120 1200 1200 1200 1200 1200
2, 2.5, 3, 4,
5, 6, M1, M 2 4000 1000 1200 1200 1200 1200 1200 1200 1200
Setting Inst. :----- 5000 1200 1200 1200 1200 1200 1200 1200 1200
6 X In In Multiples of
Rating Plug Tolerances on settings are ± 10% of values shown.
Amperes (In) Refer to Type DS, Type SPB, or Series C R-Frame supplemental instruction leaflets
given in Section 6 for list of available rating plugs for each type circuit breaker.
M1 and M 2 Values are Specified on Rating Plug
caution
Available Settings
TESTING A CIRCUIT BREAKER UNDER "TRIP CONDITIONS" WHILE IT IS IN
.1, .2, .3, .4, .5 SERVICE AND CARRYING LOAD CURRENT, WHETHER DONE BY LOCALLY OR
BY REMOTE MEANS, IS NOT RECOMMENDED.
I I .- - - - - - - - Seconds w i t h
5 Communications 4. To decrement the address, press and release the (Black) "STEP"
push button (see Figure 1). The address will decrease by one
One of the most important functions of the Digitrip RMS 810 unit each time you press the (Black) "STEP" push button. If you
Trip Unit is its ability to communicate both information and con- press-and-hold the (Black) "STEP" push button, the address will
trol signals via the Eaton proprietary INtegrated COMmunications decrease continuously, slowly at first, and then faster as you con-
(INCOM®) Local Area Network (LAN). INCOM® interconnects tinue to hold the button in. (You do need to continue to hold-in
microprocessor based (and other) electrical distribution and control the "TRIP RESET" push button while you do this.)
products, with personal computers into a comprehensive information
and control communications network (see Section 5.5). The Digitrip 5. The letter "H" refers to the High 9600 Baud rate; and the letter "L"
RMS 810 Trip Unit already has INCOM® capability for external com- refers to the Low 1200 Baud Rate. An " X in the Baud Rate field
munications built into its microprocessor chip (see Figures 2, 21, 22, indicates that neither "H"igh nor "L”ow Baud Rate has been select-
23, and the specific wiring diagrams for your circuit breaker listed in ed. Press and release the (Black) "TEST" push button to change
Section 6). The receiving terminal(s) can be: the baud rate. (You do need to continue-to hold-in the "TRIP
RESET" push button.) Suggestion: Before you press and release
• An Assemblies Electronic Monitor (AEM) or Breaker Interface the (Black) "TEST" push button, set the "TEST AMPS" switch to "1
Module (BIM) for local or remote monitoring (see Figure 22 and ", to minimize the effect of an "unintended test", which can occur,
references in Section 6). if your other finger would happen to come off the "TRIP RESET
• A remote master personal computer (PC) - IBM® compatible (see push button.
Figure 21 and references in Section 6). NNote: For correct communications, be sure to use the terminating resistor at
• Both an AEM or BIM (for local monitoring) and a PC for remote the end of the twisted pair (last element in the INCOM® chain) (see Figures
monitoring and control (see Figure 23 and references in 21, 22, and 23, and refer to the IMPACC® Wiring Specification listed in
Section 6). Section 6).
6. When the address and baud rate code in the display window are
5.1 Trip Unit Address and Baud Rate correct, release the "TRIP RESET" push button to save the values
To enable the INCOM® communications system to identify each cir- into the Trip Unit's non-volatile memory, and the kA, MW or MWh
cuit breaker individually, the Digitrip RMS 810 Trip Unit has a unique value will return to the display window. If control power is lost,
3-digit "ADDRESS", which INCOM® uses to identify the Trip Unit and the Trip Unit will still know its (new) address and baud rate.
the circuit breaker it controls. NNote: If control power is lost while you are changing the address or baud rate,
i.e.: while you are still holding-in the "TRIP RESET" push button, the display
will go blank and when the control power is restored, the Trip Unit will still
notice retain the previous address and baud rate values, as if you had not been trying
NEW DIGITRIP MODEL 810 TRIP UNITS, AND TRIP UNITS PROVIDED AS A to change them.
PART OF NEW CIRCUIT BREAKERS, WILL ALREADY CONTAIN A FACTORY-
SET BAUD RATE AND ADDRESS, WHICH IN GENERAL WiLL NOT APPLY
TO YOUR NETWORK. FOR PROPER COMMUNICATIONS, EACH TRIP UNIT
ADDRESS AND BAUD RATE MUST BE SET TO THE VALUES APPLICABLE
notice
FOR YOUR NETWORK. SIMILARLY, PRIOR TO THE INSTALLATION OF A AS SHOWN IN FIGURE 1, TO THE LEFT AND BELOW THE DISPLAY WINDOW,
TRIP UNIT INTO ITS CIRCUIT BREAKER, OR PRIOR TO INSTALLATION OF IS A SPACE TO RECORD THE INCOM® ADDRESS. BECAUSE TRIP UNITS
A CIRCUIT BREAKER INTO ITS COMPARTMENT (AFTER MAINTENANCE AND CIRCUIT BREAKERS OF THE SAME RATING ARE INTERCHANGEABLE,
FOR EXAMPLE), THE USER SHOULD VERIFY THAT THE BAUD RATE AND IF MORE THAN ONE HAS BEEN WITHDRAWN FOR MAINTENANCE AT ONE
ADDRESS ARE CORRECT. FAILURE TO USE THE CORRECT BAUD RATE TIME, IT IS CRITICAL THAT THE EACH UNIT BE RETURNED TO ITS CORRECT
OR ADDRESS CAN CONFUSE THE COMMUNICATIONS SYSTEM. IT IS CELL LOCATION SO THAT THE CIRCUIT HAS THE CORRECT ADDRESS.
RECOMMENDED THAT THE APPROPRIATE BAUD RATE, ADDRESS, AND FOR EXAMPLE, IF TWO IDENTICAL BREAKERS (ONE WHOSE TRIP UNIT
CIRCUIT BREAKER CELL LOCATION OR BUS OR CIRCUIT REFERENCE BE ADDRESS IS "001" AND THE OTHER WHOSE TRIP UNIT ADDRESS IS
RECORDED IN THE SPACES PROVIDED ON THE TRIP UNIT DISPLAY PANEL, "100") WERE SWITCHED, THE INCOM® COMMUNICATIONS SYSTEM WILL
FOR FUTURE REFERENCE (SEE FIGURE 1). RESPOND PER THE INFORMATION FROM EACH TRIP UNIT'S ADDRESS
NUMBER AND NOT THE NEW CELL POSITION.
The User can view the present address and assign a new 3-digit
address by the following procedure. 5.2 Remote Master Computer
NNote: The breaker need not be open and may be carrying current. To communicate with a remote master (IBM® compatible) personal
computer, install a Eaton Computer Operated Network Interface
1. Press-and-continue-to-hold-in the "TRIP RESET" push-button (see (CONI) card or Master INCOM Network Translator (MINT) into the
Figures 1 and 20). computer frame (chassis). The connections in the network are then
made by twisted pairs of wires as shown in Figure 21.
2. Watch the display window, and after about 5 seconds the param-
eter value will disappear, and either the letter "H" or "L" (baud rate
code), followed by the 3-Digit address (between "001" and "999",
there is no "000") will appear. (You do need to continue to hold-in
the "TRIP RESET" push button.)
3. To increment the address, press and release the (Black)
"DEMAND RESET push button near the display window (see
Figure 1). The address will increase by one unit each time you
press the (Black) "DEMAND RESET push button. If you press-
and-hold the (Black) "DEMAND RESET" push button, the address
will increase continuously, slowly at first, and then faster as you
continue to hold the button in. (You do need to continue-to-hold-
in the "TRIP RESET" push-button while you do this.)
Twisted Pair.
No. 18 AWG, (See Section 5.5
-----
Cut-off Shield at last
CONI Card Device Do Not Ground
Breaker
with
RMS 810
Trip Unit
3
View A
Refer t o circuit breaker connection diagrams referenced i n Section 6 for actual connections.
Modular telephone connector, Type RJ11 supplied by user.
Ground shielding at computer only as shown. Where devices are daisy-chained, interconnect shielding, but do not ground
the connection.
1 / 2 w a t t carbon resistor required at last breaker. See T.D. 17-513.
Figure 21. INCOM with Remote Master Computer.
Breaker
Interface Twisted Pair.
OR Monitor
(BIM)
Cut-off Shield at
Device Do N o t Ground
Circuit
Breaker
RMS 800
See Section
810
Trip Unit
Note: OK t o m i x Models 700, 800, and 810 Trip Units i f Baud Rate L = 1200 is used.
Refer t o circuit breaker connection diagrams referenced i n Section 6 for actual connections.
Ground shielding at AEM/BIM only as shown. Where devices are daisy-chained,
interconnect shielding, but d o not ground the connection.
1/2 watt carbon resistor required at last breaker. See T.D. 17-513.
Assemblies Breaker
Typical IBM (or IBM Electronic or Interface
Monitor Monitor
(AEM) (BIM)
Twisted Pair.
No. 18 AWG. (See Section 5.5
for cable specifications.)
----
Cut-off Shield at
CONI Card Device - D o Not Ground
See Section
Refer to circuit breaker connection diagrams referenced in Section 6 for actual connections.
Modular telephone connector, Type RJ11, supplied by User.
Grounded shielding at computer and AEM / BIM (cable to P1 only) as shown. Where devices are daisy-chained, interconnect shielding,
but do not ground the connection.
1/2 watt carbon resistor required at last breaker. See T.D. 17-513.
Figure 23. INCOM Network with Remote Master Computer and AEM / BIM.
Suffix Number 81 82 83 84 85 86
Instruction Leaflet No. I.L. 29-888
Remote Information X X X X X X 5.6
via INCOM / IMPACC:
View Breaker Status
Open / Closed / Tripped X X X X X X 5.6
Address Register & Baud Rate X X X X X X 5.1
View Trip Event Values
Trip Event Time r r r r r r 5.6
Trip Event Counter r r r r r r 5.6
View Protection Settings
Long-Time Delay Protection
Current Setting (Pick-up) X X X X X X 3.2
Time Delay Setting X X X X X X 3.3
Short-Time Delay
Current Setting (Pick-up) X X X X 3.4
Time Delay Setting X X X X 3.5
Opt. “I Squared T” Curve X X X X 3.5
Instantaneous
Current Setting (Pick-up) X X X X 3.6
DISCriminator (11 x) IN or OUT X X 1.1.3
Ground Fault
Current Setting (Pick-up) X X X 3.8
Time Delay Setting X X X 3.9
Opt. “I Squared T” Curve Shape X X X 3.9
View Current Values
Phase A Current [IA] (kA) X X X X X X 1.2.1.1
Phase B Current [IB] (kA) X X X X X X I
Phase C Current [IC] (kA) X X X X X X I
Ground Current [IG] (kA) X X X I
Neutral Current [ID] (kA) n n n 1.2.1.1
View Power / Energy Values
Peak Power Demand (MW) X X X X X X 1.2.1.2
Present Power Demand (MW) X X X X X X I
Reverse Power Flow X X X X X X I
Energy Consumption (MWh) X X X X X X I
Reverse Energy Consumption X X X X X X 1.2.1.2.
View Power Factor Value r r r r r r 5.7
View Remote Messages
DISC = DISCriminator X X Table 3
EXTT = EXTernal Trip X X X X X X Table 3
GNDT = GrouND Trip X X X Table 3
HILD = HIgh LoaD Alarm X X X X X X Table 3
INST = INStantaneous Trip X X X X Table 3
LDPU = Long-Time Delay Pick-up X X X X X X Table 3
LDT = Long-Time Delay X X X X X X Table 3
NORM = NORMal r r r r r r Table 3
NPOW = Negative POWer Flow X X X X X X Table 3
ORID = OverRIDe Trip 1 1 1 1 1 1
ORNG = OverRaNGe X X X X X X Table 3
PLUG = Rating Plug Problem X X X X X X Table 3
SDT = Short-time Delay Trip X X X X Table 3
NRES = Communications Failure r r r r r r Table 3
TEMP = OverTEMPerature Trip X X X X X X Table 3
TEST = TEST ready to Begin X X X X X X Table 3
Remote Control via INCOM / IMPACC X X X X X X
TRIP (OPEN) Circuit Breaker Command X X X X X X 5.8
CLOSE Circuit Breaker Command * * * * * * 5.8
RESET TRIP UNIT Command X X X X X X 5.9
RESET DEmand, Energy, Trip Event X X X X X X 5.9
LEGEND x = Function included.
n = Circuit Breaker must be equipped for Natural Protection.
r = This information can be viewed only REMOTELY by INCOM / IMPACC, but NOT LOCALLY at Trip Unit Display Window.
1 = n/a for Type DS Breakers.
* = Requires purchase of optional Electrical Operator or Spring Release Option with Circuit Breaker, and the Trip Unit may have to be RESET before the breaker
can close.
warning
UNEXPECTED SIGNALS TO "CLOSE' OR "TRIP' A CIRCUIT BREAKER FROM
A REMOTE LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE
PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE
IMMEDIATE VICINITY OF THE CIRCUIT BREAKER. PROVIDE PERMISSIVE
CONTROL SWITCHES, OR OTHER MEANS, LOCALLY AT THE CIRCUIT
BREAKER FOR MAINTENANCE PERSONNEL TO USE IN CONTROLLING
REMOTE "CLOSE" OR "TRIP" SIGNALS. FOR DETAILED INFORMATION
CONCERNING THE BREAKER CONTROL CIRCUITS NECESSARY TO
IMPLEMENT PERMISSIVE CONTROL LOCALLY, REFER TO THE CIRCUIT
BREAKER CONNECTION DIAGRAMS LISTED IN SECTION 6.
6.1 Digitrip RMS Trip Assemblies I.L. 29-801 lnstruction for the Systems Pow-R Breaker and
Drawout Mechanism
I.L. 29-885 lnstructions for Digitrip RMS 510 Trip Unit
I.L. 29-849 Supplementary lnstructions for the Systems
I.L. 29-886 lnstructions for Digitrip RMS 610 Trip Unit Pow-R Breaker used with the Digitrip RMS Trip
I.L. 29-888 lnstructions for Digitrip RMS 810 Trip Unit Units
I.L. 29-889 lnstructions for Digitrip RMS 910 Trip Unit AD 29-863 Typical Time-Current Characteristic Curves for
Type SPB Systems Pow-R Breaker
6.2 Type DS Low-Voltage AC Power Circuit Breakers SC-5623 lnstantaneous (I)
I.B. 33-790-1 lnstructions for Low Voltage Power Circuit SC-5624 Long Delay and Short Delay (LS)
Breakers Types DS and DSL
SC-5625 Ground (G)
Supplement B Digitrip RMS 510, 610, and 910 Trip Units with
I.S. 15545 SPB Master Connection Diagram
to I.B. 32-790-1 Types DS and DSL Low Voltage Power Circuit
Breakers 6.5 Series C R-Frame Molded Case Circuit Breakers
®
Zone
Fault 2 3
The feeder breaker trip unit will initiate the trip in 0.03 s to clear Figure A.1 Typical Zone Interlocking (Ground Fault Protection).
the fault; and Z2 will send an interlocking signal to the Z1 trip unit.
NNotes: A1: Wiring to be twisted pair of AWG No. 14 to AWG No. 20. Route
Z1 trip unit will begin to time out, and in the event that the feeder
Zone lnterlocking wiring separate from power conductors. DO
breaker Z2 would not clear the fault, the main breaker Z1 will clear NOT GROUND any Zone Interlock Wiring.
the fault in 0.5 s (as above). A2: The maximum distance between first and last zone is 250 feet
Fault 1 (110 m).
A3: A Maximum of 20 breakers may be connected in parallel in one
There are no interlocking signals. The main breaker trip unit will initi- Zone.
ate the trip in 0.03 s.
Figure A.2 presents a Zone Selective lnterlocking connection dia-
Legend
gram for a system with two main breakers from incoming sources
and a bus tie breaker. Note the blocking diode D1 is needed so that
=Common (Ungrounded)
the feeder breakers can send interlocking signals to both the main
and tie breakers, without having the tie breaker send itself an inter- =Short Delay Output Signal
locking signal. to Higher Level Zone
= Short Delay Input Signal
from Lower Level Zone
=Ground Output Signal
to Higher Level Zone
=Ground lnput Signal
from Lower Level Zone
= Fault at Location 2
M2
C C
-
SO
-
SO
SI
SO
SI
1N4004
0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec 0.1 Sec
APPENDIX B: Interpreting Display Codes • The "HILD" message would begin to flash in the window when
the overload condition had exceeded 0.85 x Ir for 40 seconds
After Circuit Breaker Trips or longer. To clear the "HILD" message and to view the present
Given a 1600 A frame circuit breaker with an In = 1000 A rating magnitudes of the currents, press and release the (Black) "STEP"
plug installed. push button on the display panel. Remember to push the "STEP"
button several times to be sure you see values of currents in all
CASE 1: Overload Trip Operation and High Load Condition phases, and ground/neutral as applicable.
Long Delay Current (Pick-up) Setting = 1.0, Ir = 1000 A • The "High-Load" Relay in the Power / Relay Module (see Figures
Assume a prolonged 1500 A overload condition which results in an 2, 10, and Section 1.4) would have been picked up (after a 40-sec-
automatic breaker trip operation. The following will occur: ond delay), to close the remote High Load Alarm Contact. Press
and release the "TRIP RESET" push-button to reset the High Load
• The Long Delay Trip LED will turn "On" (see Figure 1). Relay Contact, or reset the Trip unit remotely by INCOM® (see
• The coded message "LDT will appear in the Display Window (see Section 5.9).
Figure 1). • The Long Delay LED (Figure 1) begins to flash "On" and "Off".
• The Long Delay Relay in the Power / Relay Module (see Figures • The message "LDPU" begins to flash in the display window when
2 and 10) will operate to close the remote Long Delay Trip Alarm the current value exceeds Ir.
Contact.
Operator Actions: CASE 2: lnstantaneous Trip Operation
1. Observe the mode of trip LED and coded message in the Display lnstantaneous Current (Pick-up) Setting = 8 x In = 8000 A
Window. Assume a 12 kA fault occurs.
2. Press and release "STEP" push-button (see Figure 1). This will Following the TRIP operation, the following will occur:
clear the coded cause of trip message in the Display Window. • The lnstantaneous Trip LED will turn "On" (see Figure 1).
3. View values of phase currents in Display Window (see • The coded message "INST will appear in the Display Window (see
Figure 1), e.g.: 1.50 kA.
Figure 1).
NNote: The phase current shown will be that identified by the "green" LED (see • The Short-Circuit Relay in the Power / Relay Module (see Figures
Figure 1) that is turned "On", assume "IA". (It may not be the faulted phase.) 2, 10, and Section 1.4) will operate to close the Remote Short-
Circuit Trip Alarm contact.
4. Press and release the "STEP" push-button to view current values
similar to "IA", "IB", "IC", "IG" and "ID". Each value of phase current Operator Actions:
kA appearing in the Display Window is the value at the time of 1. Observe the mode of trip LED and the "INST" message in the
the trip operation. Display Window.
5. RECORD all Values of interest; note which "RED" LEDs are light- 2. Press and release the "STEP" push-button to view current
ed BEFORE resetting the Trip Unit. values "IA", "IB", "IC", and "IG" or "ID" in the display window.
6. Reset the Trip Unit by pressing and releasing the "Trip Reset" NNote: The phase current value displayed will be that identified by the "green"
push-button (lower right corner of Trip Unit, see Figure 1). All LED (see Figure 1) that is turned "On". (But, the first value you see may not
coded messages and/or current values in the display window and be for the faulted phase.) Each value of phase current appearing in the Display
the cause of trip LED will turn "Off", and the Remote Alarm con- Window, is the value at the time the trip operation was initiated.
tacts in the Power / Relay Module will be reset (open).
3. RECORD all Values of interest; note which "RED" LEDs are
lighted BEFORE resetting the Trip Unit.
notice 4. The value of one phase current in display window (see Figure 1)
FOLLOWING LDT TRIP OPERATIONS, IT IS ESSENTIAL THAT ANY CAUSE will have been the 12.0 kA fault level.
OF OVERLOAD TRIP BE CORRECTED PRIOR TO RECLOSING THE CIRCUIT
BREAKER. SHOULD IT NOT BE CORRECTED AND THE CIRCUIT BREAKER BE NNote: Had the level of the fault current been more than 28 x In (or 28 kA in
RE-CLOSED TOO QUICKLY, THEN BECAUSE OF THE INHERENT LONG TIME this example) when the reason for trip message would be cleared (by push-
ing the "STEP" button), instead of the numerical value of current in kA, the
MEMORY FUNCTION (SEE NOTE IN SECTION 3.3), THE LONG DELAY TRIP "ORNG" code is displayed to show the current level exceeded maximum
ELEMENT WILL OPERATE FASTER THAN THE RELATED TIME-CURRENT range of current sensor accuracy.
CURVE INDICATES.
5. After making sure you have a record of all pertinent information
THE AMOUNT OF TIME REQUIRED TO CLEAR THE LTM MEMORY CIRCUIT stored in the Trip Unit memory, reset the Trip Unit by pressing
IS A FUNCTION OF THE LONG DELAY TIME SETTING (SEE FIGURE 5). THE and releasing the "Trip Reset" push-button (lower right corner of
LONGER THE DELAY SETTING, THE LONGER THE TiME REQUIRED TO the Trip Unit, see Figure 1). All coded messages, values of cur-
RESET THE MEMORY. TOTAL MEMORY CLEARING TIME COULD BE UP TO rent in the display window memory, and cause of trip LEDs will
TWELVE (12) MINUTES. THE LTM CAN BE RESET QUICKLY AS DESCRIBED IN turn "OFF", while the Remote Alarm Contacts of the signal relay
SECTION 4.4 (3). in the Power / Relay Module will reset (open).
6. Following any corrective actions and/or inspections of the circuit
The LTM memory function, simulates the conventional thermal type breaker and related equipment, re-close the circuit breaker to
(bi-metal) circuit breaker Trip Unit, and serves a useful function by restore power to the load circuit.
allowing the load conductors to cool down after an overload condition.
7. After correcting the cause of the overload trip (LDT), allow for the
LTM memory circuit to reset and reclose the circuit breaker to
restore power to the load circuit.
NNote: As the current approached the overload condition, prior to the overload
trip operation, the following Trip Unit indications would have been visible.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com