Professional Documents
Culture Documents
Qcs 2010 Section 15 Part 2 Building Insulation PDF
Qcs 2010 Section 15 Part 2 Building Insulation PDF
Section 15
Part 2
Building Insulation
Page 1
2.
BUILDING INSULATION................................................................................ 2
2.1
GENERAL ...................................................................................................... 2
2.1.1
2.1.2
Scope
References
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.2.7
2.2.8
2.2.9
General
External Thermal Insulation Composite System (ETICS)
Cavity Wall Insulation
Perimeter Insulation
Exterior Framing or Furring Insulation
Rigid Insulation
Masonry Fill Insulation
Adhesive
Tape
2.3
INSTALLATION ............................................................................................. 4
2.3.1
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7
2.4
2.4.1
2.4.2
General
Quality and Requirements
QCS 2010
2
2
2
3
3
3
3
3
3
4
4
4
4
4
5
5
6
6
6
6
QCS 2010
Section 15
Part 2
Building Insulation
2.
BUILDING INSULATION
2.1
GENERAL
2.1.1
Scope
This Part specifies the type, quality and application of exterior wall insulation.
General
Roof Insulation
Section 5
Section 13
Section 18
Concrete
Masonry
Carpentry, Joinery and Ironmongery
2.1.2
References
Page 2
2.2
2.2.1
General
Various types of insulation may be specified for varying conditions or wall construction. The
BS classification system is to be used for insulation material.
The Contractor shall use only one type of insulation in any particular area where more than
one type is optional unless approved other wise by the Engineer.
Where insulation is used at exterior walls, roof surfaces, or below grade, the requirements
for condensation control shall be to BS 5250 and BS 5803.
QCS 2010
QCS 2010
Section 15
Part 2
Building Insulation
Page 3
2.2.2
If specified the external thermal insulation composite system (ETICS) shall be bonded
system and tested in accordance with ETAG-004 (European organization for technical
approvals):-
The external thermal insulation system shall compose of the following components:(a)
Adhesive layer
(b)
(c)
(d)
(e)
Fibremesh reinforcement
(f)
(g)
2.2.3
Mineral Fibre Board shall comply with the relevant provisions of BS 1142 and be faced with a
vapour retarder having a perm rating of not more than 0.5.
Polyurethane or polyisocyanurate board shall comply with the relevant provisions of BS 4841
and be faced with a vapour retarder having a perm rating of not more than 0.5.
Foam system insulation used in cavity walls shall be to BS 5617 and BS 5618.
Unless otherwise stated on the drawings cavity wall insulation shall be extruded polystyrene
board of minimum density 25 kg/m3 to the thickness detailed.
2.2.4
Perimeter Insulation
Polystyrene board where used for exterior perimeter insulation below ground and in contact
with soil shall comply with the relevant provisions of BS 3837 and BS 8216.
Where sprayed lightweight mineral coatings are used, they shall be to BS 8216.
2.2.5
On approval by the Engineer, batt or blanket type insulation can be used for exterior wall
insulation provided that proper protection, as designated in the Project Documentation, is
present.
2.2.6
Rigid Insulation
Rigid insulation shall be applied to the inside face of exterior walls, spandrel beams, floors
and where indicated in the Project Documentation.
Mineral fibre board shall comply with the relevant provisions of BS 6676 Part 1 and Part 2.
2.2.7
QCS 2010
QCS 2010
2
Section 15
Part 2
Building Insulation
Page 4
staples or nails complying with the relevant provisions of BS 1202, zinc-coated, size
and type best suited for purpose.
screws complying with the relevant provisions of BS 1210 and BS 3692, with washer
not less than 50 mm in diameter.
steel impaling pins with heads not less than 50 mm in diameter with adhesive for
anchorage to substrata; the impaling pins shall be of sufficient length to extend
beyond the insulation and retail cap washer when a washer is placed on the pin.
2.2.8
Adhesive
2.2.9
Tape
Tape used to seal cuts, tears or unlapped joints of insulation shall have pressure sensitive
adhesive on one face.
The perm rating of the tape shall not be more than 0.50.
2.3
INSTALLATION
2.3.1
Insulation shall be installed with the vapour barrier facing the heated side, unless specified
otherwise.
Rigid insulating units shall be installed with joints close and flush, in regular courses and with
cross-joints broken.
Batt or blanket insulation shall be installed with tight joints and filling framing void completely.
Seal cuts, tears, and unlapped joints with tape.
Insulation shall be fitted tight against adjoining construction and penetrations, unless
specified otherwise.
2.3.2
Insulation shall be mounted on exterior faces of inner leaves of masonry cavity walls and
brick faced concrete walls. Fill joints with the same material used for bonding.
Polystyrene board shall be bonded to surfaces with adhesive or Portland cement mortar
mixed and applied in accordance with recommendations of insulation manufacturer.
2.3.3
Perimeter Insulation
(a)
fill joints of insulation with the same material as used for bonding
(b)
bond polystyrene board to surfaces with adhesive or Portland cement mortar mixed
and applied in accordance with recommendations of the insulation manufacturer.
When applying horizontal perimeter insulation under concrete floor slabs the Contractor
shall:
(a)
lay insulation boards and blocks horizontally on level, compacted and drained fill
QCS 2010
QCS 2010
(b)
Section 15
Part 2
Building Insulation
Page 5
extend insulation from foundation walls towards the centre of the building.
2.3.4
The insulation shall be packed around door frames and windows and in building expansion
joints, door soffits and other voids. Open voids are not permitted. The insulation shall be held
in place with pressure sensitive tape.
Vapour retarder flanges shall be lapped together over the face of the framing for a
continuous surface. Seal all penetrations through the insulation.
The blanket insulation shall be fastened between metal studs or framing and exterior wall
furring by continuous pressure sensitive tape along flanged edges.
The blanket insulation between wood studs or framing shall be fastened with nails or staples
through the flanged edges on the face of the stud. Fastenings shall be spaced the not more
than 150 mm apart.
For roof rafter insulation or floor joist insulation, mineral fibre blankets shall be placed
between the framing to provide not less than a two 50 mm space between the insulation and
the roof sheathing or sub-floor.
(c)
at wood framing, blanket insulation shall be fastened between the wood framing or
joist with nails or staples through flanged edges of insulation.
at metal framing or ceiling suspension systems, blanket insulation shall be installed
above suspended ceilings or metal framing at right angles to the main runners or
framing; the insulation shall be taped tightly together so no gaps occur and metal the
framing members are covered by insulation.
in areas where suspended ceilings adjoin areas without suspended ceilings, either
blanket, batt, or mineral fibreboard insulation shall be installed; the insulation shall
extend from the suspended ceiling to underside of deck or slab above; the insulation
shall be secured in place to prevent collapse or separation of the insulation and
maintain it in a vertical position; blanket or batt insulation shall be secured to the
structure above with continuous cleats.
2.3.5
Rigid Insulation
Rigid insulation shall be securely fixed to the interior face of exterior walls of solid masonry,
or to concrete walls, beams, beam soffits, underside of floors, and to the face of studs where
shown on the Project Drawings for interior walls unless otherwise approved by the Engineer.
The insulation shall be bonded to solid vertical surfaces with adhesive as recommended by
insulation manufacturer. Joints shall be filled with adhesive cement.
Impaling pins shall be used for attachment of the insulation to the underside of horizontal
surfaces. Fastenings shall be spaced as necessary to hold insulation in place and prevent
sagging.
insulation shall be bond to concrete floors in attics by coating surfaces with hot asphalt
applied at rate of not less than 35 kg per 10 m2, and firmly bed the insulation.
QCS 2010
QCS 2010
Section 15
Part 2
Building Insulation
Page 6
(b)
when applied in more than one layer, bed succeeding layers in hot asphalt applied at
the rate to equal a total of not less than 35 kg per 10 m2 when completed.
(c)
2.3.6
Fill insulation shall be poured into cavity voids of masonry units from the tops of walls, or
from a sill where windows or other openings occur.
The fill insulation shall be poured in lifts of not more than 6 metres.
2.3.7
The wall insulation is to be mounted on the outside face of the external concrete walls,
behind the marble cladding panels. After ensuring that the surface is even and free from dirt,
grease, oil, concrete nibs etc an approved primer is to be applied.
The insulation slabs are to be fixed with an approved adhesive in accordance with the
manufacturers instructions. Both sides of the insulation are to be covered building paper.
The external face of the insulation is to be finished mat black.
2.4
2.4.1
General
2.4.2
Insulation and related vapour barriers or weather proofing are to be as shown on the Project
Drawings and as specified in the manufacturers literature, shop drawings and any other
relevant supporting documentation.
Thermal requirements will at minimum meet specifications as stated in this Part 2 of this
Section for standard wall construction unless stated otherwise in the Project Documentation.
Curtain wall or glass clad wall systems are also to meet the thermal requirements of this
Section. Refer to Section 25 for additional requirements.
END OF PART
QCS 2010