VNC Function Operation Instruction
VNC Function Operation Instruction
Various client-sides
Kinco does not provide the VNC software. Users could download from the internet:
VNC software for PC: VNC Viewer
Browser: IE, Firefox
VNC software for mobile terminal: most mobile system support VNC software, for example: VNC/RDP.
1. JAVA plugin tool is required by browser access. Generally, PC has the JAVA
plugin. Please refer to Java.com to install if there is no JAVA plugin on PC.
2. You can open multiple VNC Viewer clients to access to multiple HMI at the
same time.
Example 1Remote control MT4414TE by PC. MT4414TE works as server, while PC as client.
1. Only the HMI models with Ethernet port support VNC function for the VNC
function is realized via Ethernet.
+86-755-26585555
www.kinco.cn
Kinco
2)
Function
LB9290
LB9291
LB9292
LB9293
LW10146~LW10147
Operation password
LW10148~LW10149
Inquiry password
+86-755-26585555
www.kinco.cn
Kinco
4) Parameter setting on PC
Input IP of the target HMI:
Monitoring on PC:
+86-755-26585555
www.kinco.cn
Kinco
Changes on HMI is displayed on PC simultaneously, meanwhile, user could control HMI by operating on PC.
1. If input inquiry password on PC side, then users only could check HMI
information, but cannot operate.
2. If input operation password on PC side, then users could check HMI
information and operate HMI on PC, but cannot operate.
3. If there is no password set on HMI, then no passwords required for
monitoring or operating HMI.
Example 2Remote control MT4414TE by an android mobile. MT4414TE works as server, while the
android mobile as client.
1) Tools required for mobile
+86-755-26585555
www.kinco.cn
Kinco
1. Input IP in the Address box.
2. The default port is 5900, please do not change it, otherwise, may not get
connection.
3. Nickname and User name can be omitted.
4. Input operation password or inquiry password.
Monitoring on mobile:
Changes on HMI is displayed on mobile simultaneously, meanwhile, user could control HMI by operating on
[email protected]
+86-755-26585555
www.kinco.cn
Kinco
mobile.
Monitoring by browser:
+86-755-26585555
www.kinco.cn
Kinco
Changes on HMI is displayed by browser simultaneously, meanwhile, users could control HMI by operating on
browser.
1. The remote control by browser is realized by a JAVA plugin running on the
website. Please make sure that JAVA software has been installed on PC.
2. Default port for browser access is 5800. Please do not change it, otherwise
may not get connection.
3. Only after updated kernel and Rootfs by this version software or above, the
HMI can support the remote control by browser.
+86-755-26585555
www.kinco.cn
Kinco
1) Port mapping:Choose menuForwarding->Virtual Servers,click the Add Newbutton
3) Assumed that the WAN IP of the local network where the HMI located is 192.168.100.14, then, users
need to input IP 192.168.100.14 into VNC Viewer and mobiles of external network to remote control
HMI. Choose menu Network->WAN
For remote access by browser via WAN, users need to map the HMI IP to port number 5800.
Example 5 The IP of the remote HMI is: 192.168.4.39
1. Port mapping: Choose menuForwarding->Virtual Servers,click the Add Newbutton
+86-755-26585555
www.kinco.cn
Kinco
2.
3. Assumed that the WAN IP of the local network where the HMI located is 192.168.100.14, then, use the
browser of the external network to visit website: http://192.168.100.14:5800 to remote control HMI.
1. The Gateway must been set in the same network segment for access via WAN.
2. The firewall and antivirus software are suggested to be closed, for it may affect
the VNC function.
Simple router mapping method: If the DMZ host is opened on PC, then users could remote control HMI by
VNC without port mapping.
Example 6 The IP of the remote HMI is: 192.168.4.39
1) Router mappingChoose menu Forwarding->DMZ
+86-755-26585555
www.kinco.cn
Kinco
Example 7IP of remote HMI1 is 192.168.100.35 IP of remote HMI2 is 192.168.100.36.
1)
Port setting of router: add two new items in [transfer rule]-[Virtual server]
1. For access by VNC Viewer, the internal port must be set to 5900 by router, and
serve port can be set as casual value. Input IP and internal port for access by
VNC Viewer via WAN.
2. For access by browser, the internal port must be set to 5800 by router, and
serve port can be set as casual value. Input IP and internal port for access by
browser via WAN.
2) Parameter setting of HMI:
HMI1:
HMI2:
+86-755-26585555
www.kinco.cn
Kinco
3)
Assumed that the WAN IP of the local network where the HMI located is 203.110.174.214, then, users
need to input 203.110.174.214:5900 and 203.110.174.214:5901 into PCs and mobiles of external
network to remote control HMI.
1. The firewall and antivirus software are suggested to be closed, for it may affect
the VNC function.