Manual Corredera
Manual Corredera
Manual Corredera
SAL T2
Manual
Article No. 702270 I1
Included options:
Section 17
:...................................
Section 18
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
SAL T2 Manual
2 (9)
Consilium
SAL T2 Manual
Table of Contents
Section
Description
1 Introduction
2 Technical Description
3 Technical Specification
4 Installation of Transducer and Bottom Parts
5 Installation of Electronics Unit
6 Log Processing Unit LPU2
7 SAL SD4 Serial Digital Display
8 Analogue Indicator SIA-2-8
9 SAL T2 system drawings
10 SAL T2+ system drawings
11 IEC 61162 / NMEA 0183, Users guide
12 SAL BTU (Bottom Track Unit) Menu System
13 SAL WTU (Water track Unit) Menu System
14 Harbour Acceptance test
15 Calibration and Sea acceptance tests
16
17
18
19 Ship Equipment Spec., test documents
20 Installation and service reports
3 (9)
Doc ID
702271
702273
702274
701618
702313
704531
704005
701402
703270
703280
700164
703258
702314
703254
703255
N/A
N/A
Consilium
1.
SAL T2 Manual
Introduction
The purpose of this manual is to fulfil the needs for normal installation, commissioning, everyday use and also to give enough guidance for ships crew and local service agents to pinpoint
faulty sub-unit.
We would appreciate all comments from readers and users that would help us to improve this
manual.
Consilium Marine & Safety AB
4 (9)
Consilium
SAL T2 Manual
5 (9)
Consilium
SAL T2 Manual
1. Block diagram
Typical block diagram for a SAL T2, 2-axis configuration:
6 (9)
Consilium
SAL T2 Manual
7 (9)
Consilium
SAL T2 Manual
Name of unit
SAL T2 ELC
SAL T2+ ELC
LPU2
TRU-2-2
MSSBSV
SD4-2
Description
Log main unit (ELC = Electronics Cabinet)
Log Processing Unit, second generation
Transducer w. 30m cable
Mounting Set Single Bottom w. Sea Valve
Serial Digital SOG/STW speed, total/trip distance.
Also used as a remote log control unit,
Speed Log Master Display
Name of unit
SD4-4
SD4-5
Description
Serial Digital General instrument
SD4, Serial Digital SOG/STW, Docking log Display
704080
704090
704110
704120
704130
701219E
71-21049-17
71-71091-00
704100
(71-22188-40)
71-22191-00
71-19839-xx
SD4 BMB
SD4SA
SD4EB
SD4ED
SDR2
SDP
SIA-2-8 AN.SPEED
EXT DIM TYPE SIA
TRU2-2
MSDBSV
Connecting Tube
8 (9)
Consilium
SAL T2 Log System Manual, U/N 702270 I
Consilium Marine & Safety AB
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Intentionally blank
Consilium
SAL T-series
Consilium
Technical
Description
Article No. 702273
Consilium
Contents:
1
PRINCIPLE OF OPERATION
2.1
Acoustic transmission/reception
2.2
Depth measurement
2.2.1 Seek mode
2.2.2 Lock mode
5
5
5
2.3
Speed measurement
2.3.1 Speckle pattern
2.3.2 Correlation technique
6
6
11
12
3.1
Acoustic transmission/reception
12
3.2
Signal processing
13
3.3
Correlation functions
3.3.1 Boundary layer and calibration
14
15
3.4
Sampling control
3.4.1 Transmit pulse
3.4.2 Echo time
3.4.3 Integration time
3.4.4 How to interpret the signals received
3.4.5 Digital filtering
16
16
17
17
17
18
3.5
Speed filtering
19
3.6
Distance calculation
19
3.7
Adverse conditions
19
3.8
20
3.9
Software
3.9.1 Power on / software update
3.9.2 Normal operation
3.9.3 Menu system
20
20
20
23
TRANSDUCER TRU-2-2
24
25
5.1
BTU-PCB
26
5.2
WTU-PCB
26
2 (26)
Consilium
5.3
Revisions:
Date
2003-04-24
2003-09-10
2003-10-15
Version
A0
A1
A2
Author
NE
RB
JKW/OM
2004-03-03
2004-09-24
2005-02-21
2007-09-18
B0
B1
C0
C1
HW
UH
JL
RB
2007-12-13
C2
HW
2008-02-08
2009-03-10
2010-04-29
C3
C4
C5
RB
OM
OM
26
Comment
Created from 703251A3
WTU/RSC PCB and connection diagram
Corrected some picture and added the SAL T3
ELC number
Changed to be general for all T-series
WTU card added in electrical connection dwg.
Changed for T-M motherboard.
Added NMEA messages on serial ports (chapter
5.3)
Terminal 102/103 VDVLW message removed
from table page 26
Updated picture on page 25
Correspond to IEC62288, SOG, STW
Company name changed, corrections
3 (26)
Consilium
Principle of operation
The SAL T-Series Log system (incl. SAL T1, SAL T2, SAL T2s, SAL T2+, SAL T3 ) is
actually two more or less independent log systems, one for sensing speed over ground (SOG),
Bottom Track Unit, (BTU), and the other for sensing speed through water (STW), Water
Track Unit (WTU).
Although both sensor systems are based on correlation technique, sharing many common
features, the principles are somewhat different. Accordingly, they are described in different
chapters.
Acoustic transmission/reception
The correlation speed log uses acoustic waves in water. The transducer is mounted flush with
the hull, see figure below. Waves are transmitted from the piezo-electric elements into the
water, down to the sea-bed. The sea-bed reflects the signal back to the piezo-electric elements,
which acts as receivers, when not used as transmitters. We use broad antenna lobes because we
are not sensitive to lobe widths, compared to a system using Doppler technique.
Transducer
Hull
Hull
S1
S2
Ahead
Piezo-electric elements
Acoustic beams from transmitting
piezo-electric elements
4 (26)
Consilium
The beam travels down to the sea bed with a velocity of close to 1500 m/s. This velocity is
almost constant for different frequencies. If we have a calibrated depth meter, we may have to
compensate for salinity, density and temperature differences. The SOG correlation speed logs
operate at 150 kHz, giving a wavelength of 10 mm.
2.2
Depth measurement
The depth measurement is divided into two phases: first we seek the depth by transmitting a
pulse and wait for the echo to return. Once the depth has been measured we use a locked loop
to adjust the depth to correct value.
2.2.1 Seek mode
In the six predefined seek modes the log transmits a pulse. The pulse length varies between 0.3
and 67 ms corresponding to seek ranges from minimum depth 1 to maximum depth 400 meters.
After the transmit pulse the receiver is sampled at regular intervals. The echo will have the
same length as the transmitted pulse. The log correlates the transmitted pulse with the echo to
form an echo function. The peak of this function corresponds to the time it takes for the pulse to
travel from the hull to the sea-bed and back. If a valid echo is found the log enters the depth
lock mode.
5 (26)
Consilium
3 4
6 7 8
9 1
Transmit pulse
Echo signal
Sampling
Depth lock
Speed measurement
If the edge comes too late, the pulse duration is lengthened, if it comes too early, the pulse
duration is shortened.
During cycle 5 and 6 a second pulse is transmitted. This pulse is equal to the time the signal
travels from the transducer to the sea-bed and back again. During cycle 7 and 8 the echo is used
for speed measurement.
2.3
Speed measurement
The receiving sensor elements will see a speckle pattern. First we discuss this pattern, and then
correlation technique to estimate the speed.
2.3.1 Speckle pattern
A coherent beam is transmitted towards the sea-bed. This means that the signal has both
intensity and phase information. When the signal is reflected back, the signal will be modulated
both in amplitude and phase. Each reflector will give a phase and amplitude modulation of the
signal. If the bottom has a depth variation larger than the wavelength (10 mm) it will give a
random phase modulation. All reflectors will sum up in one position depending on the distance
to that position, see figure below.
6 (26)
Consilium
Transducer
Hull
Hull
S1
S2
Ahead
Piezo-electric elements
Acoustic beams from reflecting
objects in bottom back to
piezo-electric elements
In some spots the reflectors will cancel each other, while in other spots they will support each
other. The same effect is used in holography, where also both phase and amplitude information
is used. Thus we get a "holographic pattern" on the hull of the ship with loud and silent spots. It
can be shown that the size of a loud spot is typically the same as the transmitter area.
The receivers measure the intensity as they travel over this pattern. One such computer
simulated pattern with only five reflectors can be seen in the figure below.
7 (26)
Consilium
sigbel
8 (26)
Consilium
This pattern may also be visualised as a map with valleys and mountains representing the
intensity at the position, see figure below.
sigbel
9 (26)
Consilium
When the transducer is moved across this pattern the elements measure the intensity along the
intersection of this map. Two sensors aligned with the motion may give the following result,
see figure below.
5
3
s1
s2
n
n
2
0
0
20
40
60
80
100
120
Figure: two identical signals with delay caused by displacement between sensors.
A complex sensor as the SAL TRU-2-2 will measure intensity along several intersections of the
map. The figure below shows the difference at 45 and a 90 relative to the motion. The
similarity decreases, and the signal time displacement decreases.
5
s1
n
3
s2
s3
s4
n
n
2
n
0
0
20
40
60
80
100
120
The ship moves the transducer during both transmit and receive. This will be seen as a doubled
speed of the speckle pattern during receive. The interference pattern will give signals with
100% modulation that are easy to detect. Side lobes give no false speed. The broad beam gives
10 (26)
Consilium
always some signal component back, compared to doppler using a narrow beam which may be
missed if the ship is rolling. The interference pattern is also unaffected by salinity, temperature
and density. A layer may give a signal component from that layer if it has time delay close to
the bottom echo, but as long as the main signal comes from the bottom, this will be the main
speed source.
2.3.2 Correlation technique
Correlation is a method of finding the similarity between signals. The definition we use is to
calculate at what time difference between signal pairs the similarity is maximised. This time
delay corresponds to the distance between the sensors. By dividing this distance by the time we
get the speed.
In the "interpolation mode", when the time delay is larger than the maximum pulse length, we
cannot calculate the speed directly. This limit is when the speed [in knots] multiplied with the
depth [in metres] is less than 41. In this case signal statistics is used to estimate the speed.
Accuracy is lower in this mode.
The two axis log (SAL T2, SAL T3) calculates the velocity in six different directions and then
weights them together to find the longitudinal and transversal component. The patented
transducer configuration with only five elements gives the possibility to measure speed in all
directions with a 30 resolution, see figure below.
SAL 860 transducer configuration
Longitudinal
s1
s3
s5
s2
Transversal
s4
Fig: SAL TRU-2-2, T2, T3 /860 transducer. Used measurement directions: 0 (s1s2), +30 (s2
s4), -30 (s5s4), +60 (s3s2), -60 (s1s3) and 90 (s5 - s2).
11 (26)
Consilium
Acoustic transmission/reception
The transducer will send two parallel signals into the water. The signal to the forward crystal
(TRU cable 1 and 2) will have a frequency of 3.8 MHz and to the astern crystal (TRU cable 4
and 5) 4.2 MHz. Output amplitude is approximately 25 V in 100 ohms, giving an electrical
output of 3 W. The theoretical lobe function is shown in figure below.
.01
.01
10
10
20
20
30
30
20 . log
Sb
m
10
40
20 . log
, 0
Sb ( m , 0 )
)
50
40
60
50
70
60
80
70
10
90
10
100
100
m
10
Figure: Lobe function for STW part of the TRU-2-2. Y-axis: dB, X-axis: degrees
relative to symmetry axis of transducer element.
The lobe function is very narrow, and no side lobe contributes significantly to the signal
content. It is thus fair to assume that the beam goes perpendicular to the surface of the crystal.
Only the main lobe is considered in the following discussion.
25 V
25 V
4.2 MHz
3.8 MHz
Hull
Hull
S1
S2
12 (26)
Consilium
Correlation technique is used to calculate the time delay between the signals. The operating
frequency, centred on 4 MHz, has been empirically optimised. It is a trade-off between signal
decay, lobe function and transducer design.
The signals from the transducer move out into the water. They are reflected by objects and
move back to the transducer. The effective speed for the pulses is thus half the speed of sound
in water. The time delay for signal echo is thus proportional to this speed multiplied with the
distance to the object. The transmit-pulse length gives a volume, which may give echo at a
given delay. Figure E shows the measurement water volume, which may give an echo for a
transmit-pulse. The STW-log makes an integration of the signal for a given time. This is
equivalent of the water volume moving outwards during this time at half the speed of sound.
Hull
S1
S2
Hull
Integration
time
Signal processing
The STW-log is used to measure relative speed in the boundary layer (see section on
calibration) using acoustic correlation technique. The signal is measured in a water volume at a
chosen distance below the hull. The echo signal is intensity modulated by the particles that
traverse the water volume below the sensors.
Correlation technique is used to calculate the time delay (t) between signal S1 and S2. This is
called temporal correlation. If the sensor is based on a one or two-dimensional array the
displacement calculation is called spatial correlation. A number of algorithms have been
developed to measure this delay / displacement. The extreme of the correlation function
maximises the similarity of the signals. This delay is called 0 (tau), see figure E.
13 (26)
Consilium
S1
S2
samples
Correlation functions
The correlation function is used to measure the displacement between the two channels. One
often-used correlation function is the cross correlation function (CCF). It is defined as:
ccf ( ) =
s1(i) * s2(i + )
i
where (D) is the distance between the sensors, and 0 is the displacement corresponding to
maximum correlation. The algorithm used in the STW-log is slightly different, and gives a
minimum for the maximum correlation coefficient, see figure below.
14 (26)
Consilium
Correlation function
9
8
7
6
5
4
3
2
1
0
-4 -3 -2 -1
0 1 2
3 4 5 6
7 8 9 10
Delay
Ships hull
Ships
Speed
0
Outside boundary layer
(Relative water speed = U)
15 (26)
Consilium
The positioning of the TRU is very important. The water flow below the TRU must not be
turbulent or affected by skew water flows. Turbulent flow gives no common signal between the
two channels.
Calibration is needed to compensate STW speed change. The calibration may be set in one
point, called single point calibration, or more than one point, called multiple point calibration.
3.4
Sampling control
Sampling is controlled by three timing factors: Transmit pulse length, Echo time and
Integration time:
SAL R1 sampling
Transmit pulse
Echo time
Integration time
Figure: Sampling
One sample-period starts when the transmit-pulse is emitted for the time T (i.e. Transmit pulse
length). As already described the signal is sent out into the water and reflected against particles.
Both crystals in the TRU transmit and receive simultaneously. The transmit pulse, echo and
integration times are possible to adjust in the STW-log. The sum of transmit pulse, echo and
integration time is software limited to 199.3 s.
Adjusting the STW-log sampling timing is intended only after discussions with Consilium
Navigation. It is included to give the possibility to fine tune installations, but may give the log
bad working conditions if used without experience. The calibration must be remade after
changing sampling timing, as the calibration factor differs at different positions within the
boundary layer.
Reasons for changing the parameters may include:
High-speed vessels may find better working conditions closer to the hull as the boundary
layer is thinner.
Slow-speed vessels (as submarines) may find better working conditions further away from
the hull as the boundary layer is thicker.
In very clear water with low particle content a longer integration time gives a better signal
to noise ratio. On the other hand, in waters with high-particle content a shorter integration
time is preferred.
3.4.1 Transmit pulse
The length of the transmit pulse has empirically been set to 10.7 s. Normally this value should
not be altered, unless the measurement conditions are too unfavourable for this setting.
16 (26)
Consilium
15
. * echotime
2
Time
17 (26)
Consilium
Signal
Time
Time
18 (26)
Consilium
Signal
Speed information
IIR
True signal
Frequence
Figure: Digital filtering
Digital filtering is used when the present AGC level is higher than background noise level plus
a certain offset. The offset can be adjusted in a menu.
3.5
Speed filtering
The inaccuracy of the speed value depends on the time constant. The correlation speed log
inaccuracy depends on the correlation coefficient and the measurement distance. A longer
measurement distance will give a more accurate value. The selected time constant is a
compromise between fast response and stable readings.
In lower speeds, the relative time-delay change is large when the speed changes. The relative
time delay change from 1 to 5 knots is thus equal to the change from 10 to 50 knots. In order to
keep the log from loosing track of the speed in the low speed range, the algorithm uses a
number of fix delays. The speed estimate is then interpolated.
3.6
Distance calculation
The speed value is integrated into distance. The distance information is sent to indicators as
serial NMEA message for synchronisation of the total speed through water distance data, DIST
WAT.
3.7
Adverse conditions
It is important to remember that what the STW-log measures is actually the speed of a discrete
number of reflectors moving in a small water volume under the hull. In order to interpret the
echoed signal it is anticipated that the particles are moving parallel to the vessel axis. If the
19 (26)
Consilium
transducer has been installed at a non-preference location of the hull the water flow might be
turbulent at the site of the transducer. Under these conditions there is no guarantee for the log to
work. See section on installation of bottom parts for correct transducer installation.
In the low speed range, the distance travelled per time interval is low yielding limited
information to the correlation function. This influences accuracy and may impose lost speed
track conditions.
The log may encounter problems to measure when the ship moves in water with high particle
content. This depends on that many particles give "foggy" reflections, which makes it difficult
to see the same pattern at the true delay.
3.8
The menu system in the WTU is accessed using the Speed Log Master Display.
Four green LEDs are also available on the WTU board. Tr1 and Tr2 are lit
when the transmitter of the WTU is active and working properly. Clearwater is
lit when in normal mode and darkened when in dirty water mode. Corr is lit
when the correlation coefficient is good or better.
3.9
Software
The STW-log software has different working modes. This chapter describes the STW-log
functions seen by the user.
3.9.1 Power on / software update
At power on the WTU runs a special program that tests if the WTU code is present. If the code
is found and correct, the WTU starts to execute in normal operation. Software program updates
are also possible to download into the WTU with this program. This program controls erase and
store of the update.
3.9.2 Normal operation
The STW-log has three processes that run in parallel: measurement, menu system and
evaluation of measurement data. It is thus possible to enter the menu system without stopping
the log from measuring. The only exception to this is test modes, where the log transmits a
simulated dummy speed. The test mode T3 may also be used by the program itself for testing
the transducer levels.
The measurement process can be divided into seek and lock modes. After power on the log
enters seek mode. It seeks for zero speed (mode SZ) and based on the result of the measurement
it may stay in zero speed mode, or enter speed seek modes. The speed seek modes are seek Low
speed (mode SL) for speeds below 4 knots, or seek High speed (mode SH) for speeds above 2
knots. The seek operation is repeated until a valid speed is found. The log then enters the
locked speed modes. There are two locked modes, one in the high speed range above 2 knots
(mode LH), and one for speeds below 2.5 knots (mode LL).
20 (26)
Consilium
There is an AGC (Automatic Gain Control) for each channel on the input of the STW-log. It
will check the strength of the signals on channel 1 and 2 respectively and compensate the input
so that the signals are at an optimum when the log starts to sample and correlate them. A low
AGC value (in mV) is equivalent to a high amplification of the signal, and vice versa. The
maximum AGC value is 2200 mV. A normal value is 1200 to 1400 mV, whilst in very clear
waters the value may approach the background noise level. To summarise; high value indicates
many particles and low value indicate few reflectors in the water. In water with high particle
content a digital filter is applied (field F) to improve signal conditions.
The Speed Log Master Display when remote connected to the WTU can show the working
condition, speed information and signal level. The readout uses the following field descriptors:
MM XX.XX YY.YY
FC=DDD ZZZZ:TTTT
If no valid speed is found the log enters search modes where XX.XX and S=DDDD share the
same position. The definition for the field descriptors is found in the table below.
Descriptor
Explanation
Working mode (SZ, SL, SH, LL, LZ)
MM
XX.XX
YY.YY / --.--
F
C=DDD
S=DDD
ZZZZ:TTTT
YY.YY
21 (26)
Consilium
FC=DDD ZZZZ:TTTT
3.9.2.3 Locked low speed mode
In "Locked-Low-Speed-mode" the log has a predefined sampling interval and calculates the
correlation function corresponding to a number of discrete speeds. Interpolation is used to give
better speed resolution. If the speed is below 0.2 knots, seek zero speed mode is entered. If the
speed is above 2.5 knots, lock high speed mode is entered. The readouts presents speed
information in the following format:
LL XX.XX YY.YY
FC=DDD ZZZZ:TTTT
3.9.2.4 Seek high mode
In "Seek-high-mode" the log searches for speed in the upper speed range. It has a predefined
sampling interval and calculates the correlation function corresponding to a number of discrete
speeds. The values for correlation coefficient (C) and signal quality (S) is presented:
SH S=DDD YY.YY
FC=DDD ZZZZ:TTTT
Settling is stopped after 10 seconds, and the log returns to normal operation. The readouts
presents normal test result as:
T3 TRU SIGNAL
LEVELS NORMAL
If signal levels are (too) low (and the transducer may be damaged or not connected) as:
T3 TRU SIGNAL
LEVELS LOW
22 (26)
Consilium
23 (26)
Consilium
Transducer TRU-2-2
The transducer is a highly refined product, containing piezoelectric sensor elements facing the
water and containing some matching circuits to achieve good matching to the cable (30 m of
cable is supplied as standard, option 40m).
207,51 mm
122,00 mm
As seen, the transducer elements are clearly divided into the five SOG elements and the two
STW elements in a separate casing.
Electrically, each sensor element is connected via a matching transformer to a separately
shielded twisted pair. For transmission with the low frequency SOG part, a separate transmit
cable pair is used, that connects the signal to the three transducer elements used for
transmission.
The positioning of the transducer is very important. The water flow below the transducer must
not be turbulent or affected by skew water flows. Turbulent flow gives no common signal
between the two STW channels.
24 (26)
Consilium
The Electronics Unit is from the functional point of view divided into two more or less
separated units: SOG unit (BTU; T2F, T2R and transmitter integrated on T-M board) and STW
unit (WTU). Block diagram is shown below:
T2F
Additional T2R
used in T3+ only
T2R
WTU
TP: +12V
TP: VCC
TP: -12V
TP: +5V
TP: -5V
TP: AGND
+5V
-5V
S0 Tmit -10dB
S1 Tmit -20dB
S2 MUX Enable
S3 Transmit
S4 AMP1 +20dB
S5 AMP2 +40dB
S6 LoopBackEn.
S7 Osc. synchr.
TR2
TR1
CLEAR WATER
CORR OK
S8 Overflow
J3
Test
connector
9P-DSUB
Service
connector
9P-DSUB
Service
connector
P3
Test
connector
FLAGS0
FLAG0
LED D
LED C
LED B
LED A
NMEA 4, Tx
NMEA 5, Rx
NMEA 2, Tx
NMEA 3 (6)
NMEA 0, Tx
NMEA 1, Rx
TMIT DIS.
Fuse:
F301: 2.5 A(SB), Backup power supply
F302: 2.5 A(SB), Backup power sypply
F303: 2.5 A(SB), Main power supply
F304: 2.5 A(SB), Main power supply
F305: 2.5 A(SB), Spare fuse
115VAC
MAIN
230VAC
MAIN
+12V
J8
9P-DSUB
Service
connector
Transducer WT
NMEA IN / OUT
Transmit Control
Transducer BT
25 (26)
OVDC
0VDC
OVDC
ALARM
shown
de-energised
230VAC Power supply, Main 2
(Option 115VAC)
DANGER
High voltage
Transducer BT
Earth screw
(Transducer)
Transducer cable
230VAC
BACKUP
BACKUP POWER SUPPLY
TO BE USED WHEN TWO
TRANSFORMERS ARE MOUNTED
NMEA 6 (TxWT)
115VAC
BACKUP
Consilium
5.1
BTU-PCB
The BTU-PCB unit consists of two boards T2F and T2R (one additional T2R in T3+), placed in
a rack on the T2-M motherboard which also includes a power supply and an amplifier section
for the transmit pulse.
T2F has the function to condition and amplify the signals received from the five piezo-electric
elements in the transducer, T2R is the main processor board in the BT unit. The amplifier
integrated on the T-M motherboard is used to amplify the transmit pulse which is generated by
T2R.
5.2
WTU-PCB
The WTU-PCB consists of one board placed on T-M motherboard in the same rack as the
BTU-PCBs. The WTU PCB is powered from a separate power supply also included on the T2M motherboard.
5.3
Data is sent and received from the log as serial NMEA messages on standard IEC 61162-1 /
NMEA (RS 422/485) output / input.
Serial NMEA messages used by the speed log are described in detail in Technical Document
700164, which is available from Consilium Navigation AB.
The following NMEA sentences are transmitted in a standard setup:
Serial port
NMEA0(TxBT)
Terminal 102/103
NMEA1(RxMain)
Terminal 105/106
NMEA2(TxMain)
Terminal 108/109
NMEA4(Tx)
Terminal 114/115
NMEA5(Rx)
Terminal 117/118
NMEA6(TxWT)
Terminal 120/121
Function
This output carries basic information. Can
be used by external users.
Main input.
VDVBW, VDDPT,
VDVLW, PSALS, PSALX
Not Used.
26 (26)
Consilium
SAL T-series
Consilium
Technical
Specification
Article No. 702274
Consilium
Abstract: Performance, environmental conditions and power requirements for the SAL TSeries log system
Contents:
1
GENERAL
PERFORMANCE
4
4
4
2.2 Inaccuracy
2.2.1
STW
2.2.2
SOG
2.2.3
Distance Trough Water Inaccuracy
2.2.4
Distance Over Ground Inaccuracy
2.2.5
Echo sounder depths (SAL T1 and SAL T3)
4
4
4
5
5
5
5
5
5
5
ENVIRONMENTAL CONDITIONS
OUTPUT SIGNALS
6
6
6
6
6
CALIBRATION
POWER REQUIREMENTS
LIABILITY
2 (8)
Consilium
Revisions:
Date
2002-04-04
2004-03-12
2004-09-24
2005-08-04
2007-12-19
2009-03-10
2010-04-29
Version
A1
A2
A3
A4
C0
C1
C2
Author
SFS
HW
RB/HW
OM
OM/RB
OM
OM
Comment
Created from 703252 and 702274A0
Tex changed from T2 to T-Series. Echo sounder added
Editorial changes, WTU PCB,
Added SD4 and Echo sounder alarm
Changed LPU to LPU2, deleted SD1 and SD2, NMEA rev
Correspond to IEC62288, SOG, STW
Corrections
3 (8)
Consilium
General
The technical specification in this section deals with the SAL T-Series system, including the
Transducer, Electronics unit, Optional LPU and connected Display units. Operating
performance limits like inaccuracies or certain measurement criteria are set by the speed
sensors, i. e. the combination Transducer/Electronics unit.
Performance
The performance limits defined here are met when the log system is operating within the
environmental conditions described in this section and if calibration is correctly done.
2.1
Principle of operation
Acoustic correlation using vertical beams. The log system uses two different sensors,
measuring speed trough water (STW) and speed over ground (SOG) simultaneously and
independently.
2.1.1 STW (speed through water = relative speed)
Frequencies:
3.8 and 4.2 MHz
Speed is measured at a distance of 130 mm from the surface of the transducer.
Depth range:
> 3 m.
Speed range:
Speed range:
2.2
Inaccuracy
The SOG measurement system operates in two different modes, resulting in different
precision of the measurement. The "Normal mode" gives better accuracy but is only active
when the speed and depth product (meters and knots, respectively) is above 41. When this
condition is not met, the "Interpolation mode" is active, producing a somewhat degraded
performance.
2.2.1 STW
Speed accuracy relative to sensed water flow: 0.1 knot or 0.5%, whichever is greater.
2.2.2 SOG
Normal mode:
4 (8)
Consilium
Inaccuracy
0.2%
0.1%
0.05%
2.3
Function limits
5 (8)
Consilium
Environmental conditions
All units of the system meet the environmental conditions specified in IEC 60945.
Unit
Transducer/Bottom parts
Electronics Unit
Log Processing Unit
Echo Souder display
SD4 indicators
SD4 indicators w SD4 SA or bulkhead mount box
Protected
Exposed
X
X
X
X
Submerged
X
X1
X
1)
Output signals
4.1
Serial outputs
All serial outputs are based on IEC 61162-1 :2007(E) (NMEA 0183 standard rev 3.01).
Output drivers are utilised using RS 485 or RS422 components. For a closer definition of
NMEA messages used in SAL logs, please refer to Technical Document 700164, which is
available from Consilium Navigation AB.
4.1.1 ELC - Electronics Unit
One NMEA output channel, carrying $VDVBW, $VDVLW and $VDDPT messages, also
carrying internal priority PSAL messages.
One additional NMEA output channel from the STW-part is used to achieve full redundancy
between the STW- and SOG part of the log. This redundancy output channel is mandatory in
SAL T1 / T3 / T3+ combined speed log & echo sounder systems and when connecting the
ELC to a LPU2.
One NMEA input channel, used for remote control such as calibration and service.
4.1.2 LPU2 Log Processing Unit
23 serial outputs fed from 13 separately buffered NMEA drivers. The LPU2 has various
options to perform message conversion and calculations and has also variety of inputs for
taking data from other units. Please consult LPU2 section for this.
4.2
4
4
8
The LPU2 has two analogue outputs that can be individually programmed to carry speed and
depth information.
Please consult LPU2 section for more information about this.
6 (8)
Consilium
Calibration
The SAL T-series log has built-in functions to calibrate speed measurement correction factors
and transducer alignment via the Speed Log Master Display, both for the SOG and STW unit.
STW: Calibration range -50.00% to +50.00% of measured value in 0.01% steps.
SOG: Calibration range -50.00% to +50.00% of measured speed in 0.01% steps.
SOG angle: Calibration range -180.0 to +180.0 in 0.1 steps.
The STW-log needs correction calibration in all ships due to water flow around hull, while
SOG-log angle calibration is only needed when correct transducer alignment is impossible to
reach. The SOG-log seldom needs calibration and requires extremely accurate reference data.
7 (8)
Consilium
Power requirements
ELC
Voltage:
Frequency:
Power consumption:
LPU2
Voltage:
Frequency:
Power consumption
ESD2
Voltage:
Power consumption
Powered from the LPU2.
18 - 36 V DC
typical 25W peak 35W.
SD4
Voltage
10 - 32 V DC
Current:
150 mA maximum, 100 mA typically.
Powered from the LPU2 normally. An optional AC power supply unit SDP for 115/230 V AC
operation is available, see sections SD4.
Liability
All equipment described in this manual was designed for use on board ships to fulfil
requirements specified in various IMO documents.
However, equipment may sometimes fail or work outside its performance specification due to
component malfunction or depending on other factors.
Consilium Marine & Safety AB will not take any responsibility if this equipment is used in
such a way that its normal or abnormal function causes damage or creates situations that can
be dangerous.
8 (8)
Consilium
Consilium
SAL T-series
Installation of
transducer and
bottom parts
Article No. 701618
Consilium
Contents
1.
General
2.
3.
4.
5.
6.
7.
Transducer installation
Revisions
Date
92-02-09
97-12-18
99-05-20
02-04-23
2002-07-11
2002-10-16
2002-11-20
2005-05-11
2007-11-20
2008-10-21
2009-02-10
2009-03-10
2009-06-07
2010-05-24
Ver.
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
Ab
AC
Ad
Name
PGM
Aj
Aj/STE
JXA
STE
STE
HW
HW
HW
RB
RB/OM
OM
HW
OM
Comment
Created
Dimension drawing of valve, updated figures
Typographical changes, TRU location
New first page and headers/footers
Transducer cable clarifications
Added T2 descriptions
Transducer location clarifications
Installation heights clarified
Transducer location requirements
Added MSSB and productnumber in fig 2.5+2.7
Added unpacking of Bottom Flange + editorial
Correspond to IEC 62288, SOG, STW
Change P/N for SAL TRU T-2-2
Company name changed
2 (34)
Consilium
General
This part is intended to explain the various factors to be considered when selecting a position
for the transducer. The siting of the SAL TRU-2-2 transducer is an important factor in
determining the accuracy and efficiency of the overall system.
The transducer is designed to be fitted flush with the hull, along the longitudinal axis of the
hull. It measures the SOG (true speed) of the ship relative to the sea bed and the STW
(relative speed) will be measured in the water mass approximately 130 mm below the ships
hull. This makes it suitable to be installed on ships of all sizes.
NOTE: The transducer is tested with the cable as one unit. Do not cut or modify the
transducer cable. The relative speed measurement operates at a frequency where cable length
may affect performance. Consilium Marine & Safety AB takes no responsibility in case of
cable modification.
Transducer "Profile"
30 m (standard)
Water tracking
transducer elements
3
1
210
Transducer direction
145
180
5
Bottom tracking elements
122
Bottom Parts
The bottom parts of the system are shown in Figs. 2.5 and 2.8. A steel bottom flange is
welded to the ships hull surface. The bottom flange including the guide ring, holds the
transducer flush with the underside of the hull. The valve cover of the sea valve makes it
possible to change the transducer without dry-docking the vessel.
When using the MSSB arrangement without sea valve, maintenance of the transduser has to
be done dry-docking the vessel.
3 (34)
Consilium
The connecting tube holds the transducer fixed in its position with a tube bracket assembly
and has a watertight cable seal in its top end.
Bottom Sea Valve (MSSBSV)
Flat faces towards starboard
2.
1. To achieve the best performance of the log, special care must be taken to find the best area
in respect of water streaming under the transducer head. The transducer location MUST
BE APPROVED BY CONSILIUM MARINE & SAFETY AB in terms of the hydro
dynamical conditions, otherwise the guarantee for the log system will not be valid. Early
discussions on transducer location with drawings are always recommended. The hydro
dynamical approval given by Consilium concerns only the above requirement and not the
inside design, such as installation height, access to closing valve or any inside obstacles
that might occur and jeopardise the function or maintenance. For more detailed
installation advises please read the full manual.
2. The transducer should be installed in the foremost part of the vessel as close as possible to
the keel line.
3. The bottom valve should always be installed perpendicular to the ships horizontal plane.
4. The sea valve arrangement and transducer cable are not intended for submerged mounting
in a water filled tank. If no other alternative is available a separate watertight (W.T.)
compartment must be arranged housing the sea valve/transducer assembly. The cable must
be run in a watertight pipe conduit, connecting directly from the W.T. compartment to
free/dry space where the log electronics unit (ELC) is normally installed.
5. The compartment in which the transducer is installed may be sealed by a manhole or hatch
but the compartment must always be accessible for service.
6. The transducer cable must not be permanently installed in case of service or replacement
of defective transducer. Extra cable shall be coiled.
Do not cut the cable! Warranty is void if cable is cut.
4 (34)
Consilium
7. Sufficient headroom must be available at the transducer position to allow for its fitting and
removal (see drawings for appropriate bottom parts).
8. On tankers the transducer location is not to be within the EXarea. The transducer must
never come in contact with cargo.
9. The transducer cable shall run directly to the T-series ELC and must never be cut off,
shortened, extended or by any other mean passes a junction!
10. The SAL T speed log operates with ultra-sonic frequencies of 145 - 155 kHz, and 3.8
MHz / 4.2 MHz. The transducer location must be at least 2 m from any echo sounder
transmitters or other similar devices generating the same type of frequencies.
11. In the vicinity of the transducer location, the outside of the vessel must be free from
sudden projections, welding joints, steps and sharp edges. Special care must be taken that
no obstacle occurs before the transducers. These conditions will cause water turbulence,
which may give unreliable speed-readings from the log system.
12. Water inlets and outlets may disturb the water flow. Therefore, the transducer should be at
least 2 m forward of such openings.
13. The transducer (sensor-elements) must always remain submerged, even with a minimum
of cargo in heavy seas.
Boundary Layer
A moving ships hull tends to drag a layer of water with it, causing a boundary region around
the hull. The water speed at the hull is almost the same as the ships speed, so that the relative
water speed is almost zero. With successive water layers, the relative water speed increases
until, at the boundary edge, the relative water speed becomes equal to the ships speed. The
thickness of this boundary layer is not uniform around the ship, and can range from a few
millimetres near the bow to over a meter at the stern on a large ship.
The relative speed of successive water layers is not proportional to distance from the hull, but
follows a curve as shown below:
Ships hull
Ships
Speed
0
Outside boundary layer
(Relative water speed = U)
5 (34)
Consilium
3.
Detailed instructions for installing the different bottom parts are given in the sections that
follow. Refer to the section covering your particular application.
The bottom flange, which is to be welded into the ships hull, is the same size whether it is for
the single or double bottom parts. The bottom flange dimensions are shown in Fig. 2.4 and
2.7.
6 (34)
Consilium
4.
The mounting set single bottom sea valve assembly is suitable for single bottom ships, where
the transducer can be removed without taking the ship out of the water.
Before starting assembly check the contents of the kit against the packing list. Fig. 2.5 shows
how components fit together. The component assembly with its overall dimensions is shown
in Fig. 2.4.
Cut a circular hole (diameter 250mm +10/ 0 mm) at the selected transducer position.
2.
Weld the bottom flange into the hole; ensure that it is positioned so that the sea valve
may be fitted without obstruction.
Notes:
1.
Welding work should be carried out by qualified personnel as required by the
applicable classification society.
2.
IT IS IMPORTANT that the outer (bottom) surface of the flange is flush with
the hull and exactly vertical. The welded joint must be ground smooth and
flush with the hull. There must be no sharp edges to interfere with the water
flow around the transducer.
7 (34)
Consilium
Ships Hull
30
2.5
249
Ships Hull
Ships Hull
8 (34)
Consilium
3.
Fit the zinc ring and the guide ring into the base of the bottom flange and secure with
six FS10 x 30 screws.
Bottom flange
Ships Hull
Zinc ring
Guide ring
Screw M10
4.
Screw eight PS16 x 60 studs into the top of the bottom flange.
Stud
Ships Hull
9 (34)
Consilium
5.
Place seal 1 on the flange surface. Fit the sea valve over the eight PS16 x 60 studs,
align it with the flange and secure it with the eight M6 M16 nuts and eight M6 M16
locknuts.
Seal 1
Seal 1
Ships Hull
Sea valve
Nuts
Ships Hull
10 (34)
Consilium
6.
Apply seal 2 and place it on top of the sea valve, and install the transducer assembly
(see text under chapter, transducer installation). After the transducer assembly are
install in the valve cover, fit it align with the sea valve and secure the valve cover in
the sea valve by using the eight M6S 16x60 screws and eight M6 M16 nuts and eight
M6 M16 locknuts.
Seal 2
Seal 2
Ships Hull
11 (34)
Consilium
Transducer assembly
Valve cover
Screw
Nut
Ships Hull
12 (34)
Consilium
5.
Before starting the assembling, check the contents of the kit against the packing list. To
complete the assembly, the Intermediate Tube and Blanking Plate MUST BE
MANUFACTURED BY THE SHIPYARD and welded to the valve flange and the bottom
flange.
Figure 2.8 shows the component assembly with its principal dimensions, and Fig. 2.7 shows
how the components fitted together.
Intermediate
Tube Length
(mm)
Part No.
1300
1500
1700
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
71-19839-08
71-19839-10
71-19839-12
71-19839-14
71-19839-16
71-19839-18
71-19839-20
71-19839-22
71-19839-24
71-19839-26
71-19839-28
71-19839-30
71-19839-32
71-19839-34
71-19839-36
71-19839-38
71-19839-40
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
13 (34)
Consilium
Make the intermediate tube according to the dimensions shown in Fig. 2.1. The
material used should be steel, type ISO S355JR or equivalent.
Fig. 2.1
160
0
149.8-0.3
10
10
132
45
20
2 0
132
10
10
45
0
149.8-0.3
160
2.
Use Table 2.1 to choose the required intermediate tube length, the part number and the
length of the transducer connecting tube.
3.
Make the blanking plate according to the dimensions shown in Fig. 2.2. The material
used should be steel, type ISO S355JR or equivalent.
Fig. 2.2
14 (34)
Consilium
350
60 +
5
350
-0
Cut a circular hole (diameter 200mm) in the tank top, vertically above the transducer
position (see fig. 2.7).
Tank top
200
15 (34)
Consilium
5.
Apply the prefabricated blanking plate over the hole in tank top. Do not weld yet!
Insert the prefabricated intermediate tube, with the upper valve flange DB welded on
top, into the blanking plate and tank top down into the double bottom to coincide with
the bottom hull flange.
Upper flange DB
Weld
Blanking plate
Tank top
Intermediate tube
Bottom flange DB
Ships Hull
16 (34)
Consilium
6.
Align the intermediate tube vertically and complete welding to the bottom hull flange,
tank top/blanking plate and blanking plate/intermediate tube.
Upper flange DB
Weld
Blanking plate
Tank top
Intermediate tube
Weld
Bottom flange DB
Ships Hull
17 (34)
Consilium
7.
Fit the zinc ring and the guide ring into the base of the bottom flange and secure with
six FS10 x 30 screws.
8.
Screw eight PS16 x 60 studs into the top of the bottom flange for the sea valve.
Mounting the sea valve on the valve flange is identical with the procedures to mount the sea
valve on the single bottom flange, see section 3 for these steps!
Stud
Upper flange DB
Blanking plate
Tank top
Intermediate tube
Bottom flange DB
Ships Hull
Zinc ring
Guide ring
Screw M10
18 (34)
Consilium
6.
The mounting set single bottom is a compact version of the MSSBSV without the Sea Valve.
This mounting set is intended for installations with limited space or other circumstances
where an installation without a Sea Valve is the only alternative.
Maintenance or exchange of the transducer when using the MSSB must be done dry-docking
the vessel or when afloat sealed off by diver.
Before starting assembly check the contents of the kit against the packing list. Fig. 2.9 shows
how components fit together. The component assembly with its overall dimensions is shown
in Fig. 2.8.
Seal 1
Ships Hull
19 (34)
Consilium
Transducer assembly
Valve cover
Nuts
Ships Hull
20 (34)
Consilium
7.
Transducer Installation
The transducer assembly consists of the transducer with cable, which should be fitted to the
connecting tube supplied to fit the sea valve installation.
Assemble the transducer as follows:
1.
The valve cover should be removed from the closed sea valve.
Valve cover
Blanking plate
2.
Tank top
Connecting tube
Mounting direction
3.
Assemble the nut, locking washer, washer and O-ring onto the connecting tube in the
order shown in Fig. 2.11.
21 (34)
Consilium
Valve cover
Connecting tube
O-ring
Washer
Locking washer
Nut
4.
Assemble the tube bracket in the double fork (on valve cover) and then the cable gland
on top of the connecting tube.
Double fork
Connecting tube
Cable gland
Tube bracket
22 (34)
Consilium
5.
Push the transducer cable through the connecting tube and remove the transducer
protection.
Note: from this point and forward in the instruction, the transducer must be
handled with extra care so it will not be damaged.
6.
Assemble the connecting tube and transducer, checking carefully that the slot in the
connecting tube is engaged correctly in the transducer.
Mounting direction
Connecting tube
Cable gland
Cable end
Slot
7.
8. Secure the cable outlet at the upper end of the connecting tube and tighten the cable gland
around the cable.
Connecting tube
23 (34)
Consilium
9.
Push the transducer assembly completely into the valve cover. Secure the transducer
temporarily by tightening the tube bracket.
Valve cover
Connecting tube
Tube bracket
24 (34)
Consilium
10.
Lower the valve top and transducer assembly carefully onto the sea valve. ENSURE
that the transducer does not touch the valve body or the valve side.
Connecting tube
Screw
Valve cover
Seal 2
Transducer head
Nuts
Sea valve
Blanking plate
Tank top
11.
Fit the valve cover to the sea valve using the eight M6S 16x60 screws and eight M6
M16 nuts and eight M6 M16 locknuts.
12.
Open the sea valve, loosen the tube bracket and carefully push the transducer assembly
down until resistance is felt (caused by the chamfered guide ring). ENSURE that the
transducer is correctly seated at its lowest possible position, and VERIFY this by
checking the transducer installation from outside the ships hull.
25 (34)
Consilium
Tube bracket
Connecting tube
Double fork
Blanking plate
Tank top
Ships Hull
13.
FULLY TIGHTEN the tube bracket to the connecting tube and the wing nuts in the
double fork.
14.
Loosen the double fork clamp around the valve cover and turn the top assembly so that
the flat section on the connecting tube faces to starboard and is parallel within 1 to
the keel line. Use a straight guide bar held against the flat section to facilitate this (see
fig 2.3). Tighten the double fork clamp at this position.
26 (34)
Consilium
15.
16.
When steps 1-13 are carried out, installation of transducer is completed, but to be
absolutely sure that the transducer is correctly seated and FLUSH WITH THE
HULL, this must be verified from outside the ship. If necessary, this must be
realigned.
The transducer cable must not be permanently installed in case of service or
replacement of defective transducer. Extra cable shall be coiled. Do not cut the cable!
Warranty is void if cable is cut.
Fore
Guide bar
(held against flat
on connecting tube)
Connecting tube
(viewed from top)
"SB"
Starboard
side
Stern
27 (34)
Consilium
740
Min 1250 mm
575
Ships Hull
249
28 (34)
55
200
511
450
Consilium
SAL T MSSBSV
29 (34)
PART NUMBER
71-22190-00
Consilium
252
Min L+1100 mm
575
Min50 55
200
450
Blanking plate
Ships Hull
249
30 (34)
55
L+80
Tank top
Consilium
Blanking plate
Tank top
Intermediate tube
"Shipyard supply"
Bottom flange DB SAL T
71-22184-00
Zinc ring SAL T
71-22182-00
Ships Hull
31 (34)
PART NUMBER
71-22191-00
Consilium
Ships Hull
249
32 (34)
55
315
740
Min 865 mm
Consilium
SAL T MSSB
33 (34)
PART NUMBER
71-22192-00
Consilium
Locking washer/circlip
71-19834-00
Washer
71-19835-00
O-Ring 34.52x3.53
00-00730-87
Transducer SAL TRU-2-2
704400 (30m cable)
704401 (40m cable)
Transducer view from the fore of the ship
34 (34)
Consilium
Consilium
SAL T-series
Installation of
Electronics Unit
Article No. 702313
Consilium
Table of Contents
1.
2.
3.
General............................................................................................................................................................ 3
Wiring ............................................................................................................................................................. 3
Installation of ELC .......................................................................................................................................... 3
3.1.
Selecting location................................................................................................................................. 3
3.2.
Mechanical mounting........................................................................................................................... 5
4. Downloading of new Water Track Unit software............................................................................................ 8
5. Downloading new Bottom Track Unit software.............................................................................................. 8
Revisions:
Date
2003-04-24
2003-09-11
Version
A0
A1
Author
NE
RB
2003-10-15
A2
JKW/OM
2004-03-01
A3
OM
2004-09-24
2005-02-21
2005-11-10
A4
B0
B1
UH
JL
UH
2008-01-11
2010-05-21
2010-10-29
D0
D1
D2
OM/RB
OM
OM
Comment
Created from 703253A5
ELC dimension, electrical connections, Software update
refer to 706080
Change from 8mm bolts to 6mm bolts.
Added terminals number for main NMEA input.
Added terminal number for redundancy in T1 / T3 echo
sounder systems
WTU card added in electrical connection dwg.
Adapted to new T-M motherboard.
Mechanical dimensions corrected (drill hole distance).
Transducer shield instructions.
Adapted to LPU2
Company name updated
Added SAL T2+ ELC version
2 (8)
Consilium
1.
General
The purpose of this section is to provide enough information to have a good and reliable
installation of the Electronics Unit (ELC, T1 U/N 703400, T2 U/N 702200,
T2+ U/N 702200-01, T3 U/N 703300 or T3+ U/N 703500) in the SAL T-series Log system.
WARNING
This unit contains electrostatic sensitive devices.
Observe precautions for handling.
Note that this is only one of the manual sections needed for installation. A special and
completely stand-alone section prior to this describes the important issue of installing the
bottom parts and transducer. It should be noted that a good transducer installation is of
primary importance for achieving good performance of the log system. Selecting correct
transducer location shall be done in cooperation with Consilium Marine & Safety AB and
Consilium Marine & Safety AB must approve the selected location!
2.
Wiring
Depending on how the order was placed, a ship's specific wiring diagram may be delivered
with this manual. If not, a typical wiring diagram is included.
In general, it is sufficient to fulfil some simple rules for having good electrical connections
within the system.
The ELC shall be firmly grounded to the ship's structure.
All wires shall be electrically shielded and all signal wiring shall be twisted pairs.
3.
Installation of ELC
The location should be protected from weather and should offer a stable temperature not
outside the range 0 - 55C.
The location should not expose the unit for excessive vibration levels.
3 (8)
Consilium
The location should be far from electrical installations giving excessive electric and/or
magnetic fields, such as powerful electrical motors for ventilation, bow thrusters etc.
There must be a reasonably good way of laying the 30 m cable to the transducer in such a
way that it is possible to replace for transducer replacement.
The drawing below defines the mechanical dimensions. There must be a flat surface for
mounting and it must also be possible to fit the four bolts. Note also that there must be
enough room (400 mm free space in front of the unit) for opening the doors to access the
electronics inside and that there is room for cables below the cabinet.
Dimensions:
H: 480 mm
W: 360 mm
D: 240 mm
4 (8)
Consilium
Drilling:
Horr: 301 mm
Vert: 421 mm
6 mm steel bolts shall be used for mounting. Use fibre or Teflon sealing to maintain water
tightness.
5 (8)
Consilium
3.3
Electrical connections
The electrical connection to the ELC is fairly simple in a normal installation, since the number
of cables to be connected in a standard installation is small. All connections to the ELC and
to optional LPU2 shall be made with screened cables!
FLAGS0
FLAG0
LED D
LED C
LED B
LED A
NMEA 4, Tx
NMEA 5, Rx
NMEA 2, Tx
NMEA 3 (6)
NMEA 0, Tx
NMEA 1, Rx
TMIT DIS.
Fuse:
F301: 2.5 A(SB), Backup power supply
F302: 2.5 A(SB), Backup power sypply
F303: 2.5 A(SB), Main power supply
F304: 2.5 A(SB), Main power supply
F305: 2.5 A(SB), Spare fuse
115VAC
MAIN
230VAC
MAIN
J8
9P-DSUB
Service
connector
115VAC
BACKUP
NMEA
1 (Rx
Main)
NMEA
2 (Tx
Main)
NMEA
5 (RxSG1)
NMEA
4 (TxSG1)
NMEA 0 (Tx BT) NMEA 6 (TxWT)
230VAC
BACKUP
BACKUP POWER SUPPLY
TO BE USED WHEN TWO
TRANSFORMERS ARE MOUNTED
de-energised
Transducer BT
ALARM
shown
NMEA IN / OUT
OVDC
OVDC
0VDC
Transducer WT
A
Transmit Control
Transducer BT
230VAC 230VAC
Power supply,
PowerMain
supply,
1 Main 2
(Option 115VAC)
(Option 115VAC)
DANGER
High voltage
Earth screw
(Transducer)
Transducer cable
An extremely solid connection is to be made between the metal structure of the hull and
the grounding screw on the outside of the case. The cable area of this connection shall be
at least 10 mm, preferably using copper braid.
The AC power intake cable shall be brought to the 230 V AC terminals at the MAIN_1
intake located in the lower left end corner of the ELC. Connect to L1, L2 and GND.
The transducer cable shall be connected to terminal numbers 1 - 5 and 37 - 54. Do not cut
the cable. If the cable is cut the warranty will not be valid.
Connect terminals 1 5 to the WT connector numbered 1-5.
Connect terminals 37 54 to the BT connectors numbered 37 54.
Connect the two shield wires (red and blue) to the ground bolt (M5) in the ELC.
Connect the shield in the cable gland.
6 (8)
Consilium
The NMEA output cables and any other signal outputs/input should be brought through
appropriate cable glands to other users.
Main NMEA output is found on terminals 108 (A) and 109 (B).
Main NMEA input is found on terminals 105 (A) and 106 (B).
One additional NMEA out (Redundant WT) shall be connected from terminals 120 (A)
and 121 (B) to the redundancy NMEA input 5 in the LPU2, described in the SAL T-series
system drawing chapter if applicable.
When the ELC is a part of a SAL T1 or SAL T3 system, the following additional connections
shall be made to increase redundancy between Echo sounder / STW / SOG speed log parts of
the ELC. This additional connection shall also be made on the SAL T2+ version to separate
power between the STW and SOG part of the ELC.
One separately fused additional AC power intake shall be brought to the 230 V AC
terminals at the MAIN_2 (BACKUP) intake located just below the MAIN_1 intake.
Connect to L1, L2 and GND.
The cable shields for the NMEA output/input cables should be connected firmly in the LPU2
and not in the ELC.
All supplied cable glands are designed to terminate the cable shield directly to the outer
enclosure in the cable gland. This is necessary precaution to maintain the EMC protection
performance as verified in type approval testing. If more cable glands than those supplied are
needed, types designed for cable screen termination must be used!
Correct mounting of cable gland on Transducer cable:
1.
2.
3.
4.
5.
Remove the protecting cover to expose the outer shield and outer insulation of the
cable.
Push the parts over the cable in the order shown.
Push down the screen over the top of part B
Push Cable/B part firmly into the fixed part of the cable gland.
Tighten nut A firmly.
7 (8)
Consilium
4.
The Water Track Unit WTU or RSC860B in the ELC is delivered with the software
installed in a flash memory. If, however, an update of software would become necessary,
please refer to utility program WinFlash, 706080, available from Consilium Marine & Safety
when required.
5.
The Bottom Track Unit, T2R circuit board, in the ELC is delivered with the software installed
in a flash memory. If, however, an update of software would become necessary Please refer to
utility program WinFlash, 706080, available from Consilium Marine & Safety when required.
8 (8)
Consilium
Consilium
LPU2
LPU2
Technical Manual
Incl. installation, setting up and
maintenance guidelines
Document No. 704531
1 (52)
Consilium
Revisions
2006-09-14
2007-09-18
2008-02-12
2008-02-15
2008-07-01
A0
B0
B1
B2
B3
RB
RB
RB
AF
AF
2008-10-08 B4
2009-06-16 B5
AF
OM
2009-11-16 B6
2011-02-13 B7
RB
OM
2011-03-24 B8
OM
LPU2
Created
Document changed from Technical manual to Manual outline
Changed back to Technical Manual. First sharp edition.
Menu_O: BTR, relay+opto out MAIN and REDUN.
T- menues, Distances TRU2, Error codes in Alert-menus. System types
menu S1. GPS. System test. Opto Inputs.
Opto input functions not implemented. Service clarified. RS232 clarified.
SW ver 704580A4. Deleted filters be edited, No 38400 Baud NMEA out 223, USB FILL UP=default, IEC62288 SOG STW, Web-interface, CHECKSUMCORR->CHECKSUMTEST, Dip 1-6 defaults, K1-K4 no pulse, Logic for relay
WT- BT- DEPTH INVALID, LED code, Troubleshooting, Alert list updated.
Added tolerances to mechanical installation picture.
Added terminal 58, BT/WT->SOG/STW, indicator->display, NMEA filter and
PSALW handling corresponds to 704580A6 or later
Clarified DIP, LED S1-S4 and factory reset.
2 (52)
Consilium
LPU2
Contents
1 Introduction .......................................................................................................................... 4
1.1
1.2
1.3
1.4
2
3
3.1
3.2
3.3
3.4
4
General.............................................................................................................................9
Cabinet interior ..............................................................................................................10
List of connections.........................................................................................................10
LPU2 Table of connections by numbers summary.....................................................19
5.1
5.2
5.3
5.4
6
7
8
Dimensions ......................................................................................................................8
Cabinet location ...............................................................................................................8
Cable inlet with EMC protection and cable support........................................................9
Grounding bolt .................................................................................................................9
4.1
4.2
4.3
4.4
5
General.............................................................................................................................4
Definitions and abbreviations ..........................................................................................4
Principle of operation.......................................................................................................4
Block Diagram .................................................................................................................6
NMEA filtering.................................................................................................................... 38
Testing Procedure ............................................................................................................. 40
Service and maintenance .................................................................................................. 41
8.1
8.2
8.3
8.4
8.5
8.6
Annex 1 .................................................................................................................................... 47
9 Web-interface .................................................................................................................... 47
9.1
9.2
9.3
Annex 2 .................................................................................................................................... 50
10 Wiring principles ................................................................................................................ 50
3 (52)
Consilium
LPU2
1 Introduction
1.1 General
This document describes the LPU2 (2nd generation Log Processing Unit), which serves as an
interconnection device between SAL speed logs, SD4-x displays, indicators and other users,
such as ARPA, auto-pilots etc.
IEC61162/NMEA serial signals and how to connect cables carrying IEC61162-signals is
described in document 700164
Description
Serial Display family, e.g. SD1-x, SD2-x, SD4-x
Serial Display 4 generation, e.g. SD4-1, SD4-2, SD4-5
IEC61162-1 ed2 serial interface standard
Speed Trough the Water.
This is equivalent to Water Track (WT) speed (relative)
Water Track resulting speed or distance (relative)
Water Track Longitudinal and may refer to both
speed and distance
Water Track Transverse and may refer to both
speed or distance
Speed Over the Ground.
This is equivalent to Bottom Track (BT) speed (true)
Bottom Track resulting speed or distance (true)
Bottom Track Longitudinal and may refer to both
speed and distance
Bottom Track Transverse speed or distance
Trip distance counter
Total distance counter
Combined SOG and STW log
Electrical cabinet (SAL R1a, T1, T2, T2s, T2+, T3, T3+)
Echo sounder display, first generation
Echo sounder display, 2nd generation
Consilium
LPU2
However, a default configuration is active on delivery and shall be used whenever possible.
The unit is equipped with a power supply, able to provide power to SD4 displays as well as to
an SAL Echo Sounder Display.
The LPU2 is also used for docking log calculations. The output from a Rate Of Turn gyro can
be connected to the LPU2 via serial (NMEA) or analogue input. From this input and the
received SOG from the SAL speed log, the LPU2 calculates transversal speeds of both ends of
the ship, which can be fed to SD4-5 docking-log displays.
The SD4 Log Remote Control is used to access the menu system in the LPU2 as well as in
connected speed logs. This SD4 shall be labeled as a Speed Log Master Display according to
instructions in the SD4 chapter.
The LPU2 is equipped with an Ethernet connection (RJ45) to access the LPU2 web-interface.
This web-interface can be used to access the LPU2 menu system, display in/out going NMEA
messages, display alert lists, and for other service purposes.
The LPU2 software is contained in Flash-memory, which can be updated on board from a USB
memory stick or using the serial D-sub.
Note 1: The SAL T1 or T2s system does not calculate transversal speed over ground and will
therefore not be used in docking log systems.
Note 2: When the LPU2 is used together with a SAL R1a (speed trough water log system),
please disregard from all information referring to BT/SOG, transverse speed or docking log
functionality.
5 (52)
Consilium
LPU2
NMEA0183 data
ROT -gyro
In do cking -lo g
System s o nl y
Analog (option)
NMEA/R S 422
N MEA/ RS 422
E cho S ou nd er D ispla y
(E S D2)
In T3 /T1 system s on ly
DC Power
NMEA0183 data
NMEA 0183
DC Power
Redundant Power
N MEA0183 dat a
DC Power
S D4- 2 di spla y
S TW/SO G disp lay
NMEA0183 data
D C Power
SD 4-5 Displ ay
Docki ng lo g d ispl ay
SA L T- seri es
or
SA L R 1a
spe ed log
(1 NM EA ou t)
N MEA 0183
D C Power
N MEA0183 redundant
A na log ue Sp ee d
Ind icato r SIA -2- 8
N MEA0183 data
NME A Co nsu me r
200p/ NM
This block diagram shows the general layout of the system. Data is received from the SAL
T-series speed log and the Rate Of Turn gyro, alternatively a SAL R1a speed log can be used if
only speed through water is required. Processing is done in the LPU2, which also serves as data
distribution/interfacing unit. The exact wiring depends on each installation, depending on
which displays are needed, what turn-rate gyro is used etc.
6 (52)
Consilium
LPU2
2 Technical Specification
Mechanical specification
Height:
Width:
Depth:
Weight:
Electrical specification
Power intake:
1
Power
consumption:
SD display power
9
output terminals:
ESD power output: 1
Serial inputs:
Analogue inputs:
Opto inputs:
Serial output
terminals:
Serial terminal:
Analogue outputs:
Switching relay
outputs:
Closing relay
outputs:
Opto outputs:
Ethernet
connection
USB Device
USB Host
Service D-sub
Environmental specification
Enclosure material:
Enclosure protection:
EMC:
Heat dissipation (max)
Colour:
Recommended operating
temperature
Extreme operating temperature:
Extreme operating Humidity:
Steel plate
IP22, splash proof
IEC 60945, protected class
= Power consumption
RAL 7035
0C to +40 C
-15C to +55 C
Less than 93 % RH (non condensing) at 40C
7 (52)
Consilium
LPU2
3 Mechanical installation
The LPU2 is mounted in an
IP22 drip-proof cabinet. All
cables are brought into the case
via cable glands in the bottom
plate. Steel bolts in the
dimension M8 shall be used for
mounting. To assure that the
cabinet is drip-proof, nylon
washers must be used to seal
the fixing holes.
3.1 Dimensions
LPU2 ELC:
NOTE: When mounting, reserve a space of at least 150 mm under the cabinet for cable routing.
The LPU2 cabinet shall be vertically mounted in a location where necessary cabling
from bridge equipment can be brought to the unit, preferably on the bridge or a space
close to the bridge.
The location must have space enough to give sufficient space and accessibility for
service of the unit.
The location shall be protected from weather and shall offer a stable temperature.
The location shall not expose the unit to excessive vibration levels.
The location shall be far from electrical installations giving excessive electric and/or
magnetic fields.
The cabinet bottom shall be placed approximately 1.2 m from the floor where practical.
Compass safe distance 2 meters.
8 (52)
Consilium
LPU2
4 Electrical installation
4.1 General
To simplify the reading of this instruction, IEC61162/NMEA serial signals are named just
NMEA.
Closer information about IEC61162/NMEA serial signals and how to connect cables carrying
IEC61162.signals is described in document 700164.
Also see Appendix 2 (Wiring Principles) below.
All cables shall be brought into the case via the provided cable inlet tubes in the bottom plate
and all screens shall be properly terminated in the inlet tube clamp plate.
The cable screens between the SAL Speed log ELC and the LPU2 should only be connected to
the LPU2 and not to the SAL ELC. Use a shielded cable with twisted pairs to connect the SAL
Speed Log ELC to the LPU2.
The connection terminals are positioned on the IO-PCB and the PSU-PCB. Terminals that are
stacked on top of each other have the same number with an extra letter or mark, indicating
column. For example NMEA in 1 has terminal numbers 1A, 1B and 1C, Opto out 1 has
terminal numbers 28+ and 28-.
The terminals are designed for cable areas with a cross-section from 0,5mm to maximum 2,5
mm terminated without end caps.
9 (52)
Consilium
LPU2
The transformer and three Printed Circuit Boards are mounted on a plate inside the cabinet. The
top PCB (CPU-PCB) is covered with a protection plate, in which holes are made for USB,
Ethernet and RS232 connectors as well as the red 2 x LED digits. Also the Reboot pushbutton
and the DIP switches are accessible without removing the front plate. All connection terminals
are found on the two uncovered boards (IO- and PSU- PCB).
Term#
71
72
73
74
Function
230 V AC
115 V AC
N Neutral
Protective ground
Note
L1
(L1 if not 71 is connected)
L2
GND
Only one of the terminals 71 or 72 shall be connected. When powered from 230VAC, terminal
71-73-74 shall be used and the transformer connector shall be plugged into the 230 VAC
contact.
If powered from 115 VAC, terminal 72-73-74 shall be used and the transformer connector shall
be plugged into the 115 VAC contact.
10 (52)
Consilium
LPU2
The main fuses are positioned next to the main power terminals.
NOTE: There is no main switch. To switch the LPU2 AC power off, remove the fuses.
Connections to Log 1 ELC
Term#
1A
1B
42A
42B
Function
NMEA in 1
NMEA in 1
NMEA out 7
NMEA out 7
Note
Connect to T-Series speed Log NMEA "A" output
Connect to T-Series speed Log NMEA "B" output
Connect to Log control NMEA "A" input
Connect to Log control NMEA "B" input
The NMEA in 1 connects to the NMEA out terminal 108 and 109 on the SAL T-Series speed
log ELC.
4.3.1 NOTE! NMEA in 1 is not to be used if Log 1 is a SAL R1a!
NMEA in 1 is supervised by the LPU2: if there is no NMEA the relay K1 will drop.
NMEA out 7 (terminal 42) connects to the NMEA in terminal on the SAL Speed log ELC,
SAL T-series and R1a.
Term# Function
5A
NMEA in 5
5B
NMEA in 5
Note
Connect to Log NMEA "A" output (redundancy)
Connect to Log NMEA "B" output (redundancy)
SAL T-series: NMEA in 5 connects to the redundancy NMEA output (Redundant STW) in
Log 1 terminal 120 and 121. This will improve the redundancy of the system. Even if the LPU2
and/or the speed over ground log are malfunctioning, at least speed trough water will still be
presented on the redundancy outputs.
SAL R1a: NMEA in 5 connects to the NMEA output on the SAL R1a ELC.
NMEA in 5 is supervised by the LPU2 if there is no NMEA the relay K2 will drop.
Also refer to typical Connection diagrams in the system drawing section.
This connection (Redundant STW) has to be made when a SAL T1 or T3 system is installed to
ensure the redundancy between the speed log part and the echo sounder part of the combined
SAL T1 / T3 Speed log / Echo sounder system.
Connections to Log 2 ELC (option)
Term#
2A
2B
43A
43B
Function
NMEA in 2
NMEA in 2
NMEA out 8
NMEA out 8
Note
Connect to Log NMEA "A" output
Connect to Log NMEA "B" output
Connect to Log control NMEA "A" input
Connect to Log control NMEA "B" input
A second SAL Speed Log can be connected to the LPU2. The NMEA in 2 and NMEA out 8
shall be connected to the NMEA connections of the Log 2 ELC via a twisted pair cable.
Connection to gyro (if docking-log option is used)
11 (52)
Consilium
Term# Function
3A
NMEA in 3
3B
NMEA in 3
LPU2
Note
Connect to NMEA "A" output terminal from gyro
Connect to NMEA "B" output terminal from gyro
Instead of a serial NMEA interface an analogue signal can be used to obtain rate of turn
information from the gyro.
Term#
Function
Note
17 Sign.
Analogue in
Connect to analogue output signal from gyro
17 0VDC Analogue in
Connect to signal ground from gyro
Note! The gyro output impedance may not exceed 150 when using the analogue input.
Connections to ESD2
In SAL T1, T3 and T3+ systems an ESD2, Echo Sounder Display 2nd, is used to present a
graphical view of the depth, handle depth alarms, store historical depth data and such. The
ESD2 is connected to the LPU2 over an NMEA / 422 interface.
NMEA interface (1st option for ESD2 connection) and power to ESD
Term#
4A
4B
36A
36B
47+
Function
NMEA in 4
NMEA in 4
NMEA out 1
NMEA out 1
+18 to 32 VDC
Note
Connect to NMEA "A" output from ESD2 (COM4, D9 #2)
Connect to NMEA "B" output from ESD2 (COM4, D9 #7)
Connect to NMEA "A" input to ESD2 (COM 4, D9 #8)
Connect to NMEA "B" input to ESD2 (COM 4, D9 #3)
Connect to DC power input of ESD with a separate DC power
cable. Fuse F304
470 VDC
Connect to DC power input of ESD with a separate DC power
cable.
The DC power cable shall have a cross section of at least 1.5 mm2
NMEA out 1 will be directly connected, via redundancy relays, to NMEA in 1 (the main input
from speed log1) in case of loss of power or a failure in the LPU2.
Term# Function
48+
+18 to 32 VDC
48-
0 VDC
49+
+18 to 32 VDC
49-
0 VDC
Note
Connect to DC power input of ESD with a separate DC power
cable. Spare terminal, Fuse F304
Connect to DC power input of ESD with a separate DC power
cable. Spare terminal.
Connect to DC power input of ESD with a separate DC power
cable. Spare terminal. Fuse F304
Connect to DC power input of ESD with a separate DC power
cable. Spare terminal.
Term# Function
Note
10
RS232 In (Rx)
Connect to pin 3 in 9-pole D-sub on ESD display
11
RS232 GND
Connect to pin 5 in 9-pole D-sub on ESD display
12
RS232 Out (Tx)
Connect to pin 2 in 9-pole D-sub on ESD display
Terminal 12 has same function as NMEA out 1.
Terminal 10 and terminal 4 has same function and can therefore not be used simultaneously.
12 (52)
Consilium
LPU2
SD4 Log remote control Speed Log Master Display and redundancy displays
Term#
37A
37B
6A
6B
50+
50-
Function
NMEA out 2
NMEA out 2
NMEA in 6
NMEA in 6
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to SD4 NMEA "A" output
Connect to SD4 NMEA "B" output
Connect to DC power input of display. Fuse F301
Connect to DC power input of display
The speed logs and the LPU2 menu system can be remotely accessed for calibration and setup
of parameters from an SD4 display such as SD4-2.
The NMEA out 2 and NMEA in 6 shall be connected to the NMEA in and out connections of
the SD4 via a twisted pair cable. It is recommended to use a shielded cable with four twisted
pairs to connect the SD4 to the LPU2, two pairs for NMEA, one pair for power and one pair as
spare. NMEA out 2 will be directly connected, via redundancy relays, to NMEA in 5 (the
redundancy output of speed log1) in case of loss of power or a failure in the LPU2.
2nd SD4 Log remote control
Term#
44A
44B
7A
7B
51+
51
Function
NMEA out 9
NMEA out 9
NMEA in 7
NMEA in 7
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to SD4 NMEA "A" output
Connect to SD4 NMEA "B" output
Connect to DC power input of display. Fuse F301
Connect to DC power input of display
A 2nd SD4 remote control can be connected to the system. It will have the same remote control
functionality as the Speed log master display.
GPS input
Term# Function
8A
NMEA in 8
8B
NMEA in 8
Note
Connect to GPS NMEA "A" output
Connect to GPS NMEA "B" output
GPS info received is only used for diagnostic purpose. This is an optional but recommended
connection with the intention to simplify troubleshooting of the speed log system.
Alarm Acknowledge input
Term# Function
Note
9A
NMEA in 9
Connect to bridge alarm panel
9B
NMEA in 9
Connect to bridge alarm panel
If an NMEA alarm ($xxALR,,,A,V,) is sent out from the LPU2 to the bridge alarm panel, the
alarm can be acknowledged using NMEA in 9.
E.g. to acknowledge an ESD alarm such as: $SDALR,,150,A,V,Shallow alarm, a
corresponding: $SDACK,,150 shall be sent to this input from the central alarm panel.
13 (52)
Consilium
LPU2
Term# Function
Note
13+
OPTO in1
Mute external ESD alarm, relay K4
13OPTO in1
When Opto in 1 is activated, external ESD alarm relay K4 is energized (mute).
Only valid in SAL T1 or T3 systems.
Term# Function
Note
14+
OPTO in2
LOG 1 SOG silent mode
14OPTO in2
When Opto in 2 is activated, the acoustic transmission from the SOG part of log 1 stops, if
applicable.
Term# Function
Note
15+
OPTO in3
Echo sounder 2 MAIN
15OPTO in3
When Opto in 3 is activated ES 2 (LOG 2) becomes the active Echo Sounder.
Term# Function
Note
16+
OPTO in4
LOG 2 MAIN
16OPTO in4
When activated LOG 2 becomes the active log
Input choices:
ALARM MUTE
LOG 2 MAIN
ES 2 MAIN
LOG 1 SOG MUTE
LOG 2 SOG MUTE
These electrical inputs are galvanic separated from the LPU2 by opto couplers. The OPTO
inputs can detect an input voltage above 3,5VDC. Maximum input voltage is 40VDC.
NMEA out 10 15, connections to NMEA slave displays SD4/SD1/SD2
Provisions are made to connect NMEA output and DC power to SD4 or SD1/SD2 slave
displays. In total, including the Speed log master display, a maximum of 9 (nine)
SD4/SD1/SD2 displays can be powered from the LPU2.
Term#
45A
45B
52+
52-
Function
NMEA out 10
NMEA out 10
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse F301
Connect to DC power input of display
Term#
46A
46B
53+
Function
NMEA out 11
NMEA out 11
+12 to 28 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse 302
14 (52)
Consilium
LPU2
Term# Function
530 VDC
Note
Connect to DC power input of display
Term#
59A
59B
54+
54-
Function
NMEA out 12
NMEA out 12
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse F302
Connect to DC power input of display
Term#
60A
60B
55+
55-
Function
NMEA out 13
NMEA out 13
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse F302
Connect to DC power input of display
Term#
61A
61B
56+
56-
Function
NMEA out 14
NMEA out 14
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse F303
Connect to DC power input of display
Term#
62A
62B
57+
57-
Function
NMEA out 15
NMEA out 15
+12 to 28 VDC
0 VDC
Note
Connect to SD4 NMEA "A" input
Connect to SD4 NMEA "B" input
Connect to DC power input of display. Fuse F303
Connect to DC power input of display
Term# Function
58+
+12 to 28 VDC
580 VDC
Note
Connect to DC power input of display
Connect to DC power input of display. Spare terminal. Fuse F303
The NMEA out A and B shall be connected to the NMEA in connections of the SD4 displays
via a twisted pair cable. It is recommended to use a shielded cable with two twisted pairs to
connect the slave SD displays to the LPU2, one pair for NMEA and one pair for power.
NMEA out 3 6 and 16 23, connections to external NMEA listeners
12 external NMEA listeners can be connected to the LPU2. Out 3 6 share driver and will be
directly connected to NMEA in 5 (the redundancy output of speed log1) in case of loss of
power or a failure in the LPU2.
Term# Function
38A
NMEA out 3
38B
NMEA out 3
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
39A
NMEA out 4
39B
NMEA out 4
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
15 (52)
Consilium
LPU2
Term# Function
40A
NMEA out 5
40B
NMEA out 5
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
41A
NMEA out 6
41B
NMEA out 6
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
63A
NMEA out 16
63B
NMEA out 16
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
64A
NMEA out 17
64B
NMEA out 17
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
65A
NMEA out 18
65B
NMEA out 18
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
66A
NMEA out 19
66B
NMEA out 19
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
67A
NMEA out 20
67B
NMEA out 20
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
68A
NMEA out 21
68B
NMEA out 21
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
69A
NMEA out 22
69B
NMEA out 22
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
Term# Function
70A
NMEA out 23
70B
NMEA out 23
Note
Connect to external NMEA listener, NMEA "A" input
Connect to external NMEA listener, NMEA "B" input
16 (52)
Consilium
LPU2
There are 16 outputs of this kind: 4 switching relays, 4 closing relays and 8 opto couplers. The
function of each relay/opto output can be programmed into the LPU2, using the commands and
procedures defined in section 5, "Setting up Procedure".
Note! The switching relays K1-K4 are not intended for distance pulse function. First choice for
pulse function is opto O1-O8, second K5-K8. Warranty can not be claimed if K1, K2, K3 or K4
are used for distance pulse function.
Switching relays (NC=normally closed contact, CM=common, NO=normally open contact)
Relay# Term#
Default signal
K1
20:NC 20:CM 20:NO No NMEA Log 1 Main = de-energized
K2
21:NC 21:CM 21:NO No NMEA Log 1 Redundancy = de-energized
K3
22:NC 22:CM 22:NO STW Astern = energized
K4
23:NC 23:CM 23:NO ESD Alarm = de-energized
When energized, the corresponding LED will be lit and CM-NO will be electrically connected.
In case of power fail of the LPU2, position NC-CM for the relays K1-K4 is valid.
The relays K1 and K2 supervise the NMEA in 1 and 5. The relays will be de-energized for no
NMEA activity.
Relay K3 will be energised when STW indicates astern speed.
Relay K4 will be de-energized when an Echo sounder alarm occurs ($SDALR,,,A,V,) until
acknowledged ($SDALR,,,A,A,).
Relay K4 can therefore be used as a contact for an external ESD buzzer.
If Opto in 1 is activated, K4 will be energized (external ESD buzzer mute).
If no SAL ESD is connected to the LPU2 the relay is de-energized.
Closing relays (NO=normally open contact, CM=common)
Relay# Term#
Default signal
K5
24:CM 24:NO
Speed through water longitudinal 200p/nm, STW
K6
25:CM 25:NO
Speed through water longitudinal 200p/nm, STW
K7
26:CM 26:NO
Speed over ground resulting 200p/nm, BTR
K8
27:CM 27:NO
Speed over ground resulting 200p/nm, BTR
If no transversal SOG (BTT) is available such as in SAL T2s and T1 systems, all BTR outputs
will be calculated as if BTT=0, thus BTR outputs will be equal to BTL. This is applicable for
analogue out, pulse relays and opto-couplers.
17 (52)
Consilium
LPU2
Opto-couplers
Opto#
O1
O2
O3
O4
O5
O6
O7
O8
Term#
28+ 2829+ 2930+ 3031+ 3132+ 3233+ 3334+ 3435+ 35-
Default signal
Speed through water longitudinal 200 p/nm, WTL
Speed through water longitudinal 200 p/nm, WTL
Speed through water longitudinal 200 p/nm, WTL
Speed through water longitudinal 200 p/nm, WTL
Speed over ground resulting 200 p/nm, BTR
Speed over ground resulting 200 p/nm, BTR
Speed over ground resulting 200 p/nm, BTR
Speed over ground resulting 200 p/nm, BTR
Analogue outputs
Output
Ana out 1
Ana out 2
Term#
18:Sign 18:0VDC
19:Sign 19:0VDC
Default signal
Speed through water longitudinal 0.1 V/knot, WTL
Speed over ground resulting 0.1 V/knot, BTR
18 (52)
Consilium
LPU2
Terminal
1A
1B
1C
2A
2B
2C
3A
3B
3C
4A
4B
4C
5A
5B
6A
6B
Name
In 1 A
In 1 B
Function
Default use
NMEA in 1
Not to be used
In 2 A
In 2 B
NMEA in 2
Speed log 2
Not to be used
In 3 A
In 3 B
NMEA in 3
Gyro (ROT)
Not to be used
In 4 A
In 4 B
NMEA in 4
ESD2
Not to be used
In 5 A
In 5 B
In 6 A
In 6 B
NMEA in 5
NMEA in 6
19 (52)
Consilium
Terminal
7A
7B
8A
8B
9A
9B
10
11
12
13 +
13 14 +
14 15 +
15 16 +
16 17 Sign
17 0VDC
18 Sign
18 0VDC
19 Sign
19 0VDC
20 NC
20 CM
20 NO
21 NC
21 CM
21 NO
22 NC
22 CM
22 NO
23 NC
23 CM
23 NO
24 CM
24 NO
25 CM
25 NO
26 CM
26 NO
27 CM
27 NO
28 +
28 29 +
29 30 +
30 31 +
31 -
Name
In 7 A
In 7 B
In 8 A
In 8 B
In 9 A
In 9 B
In (Rx)
GND
Out(Tx)
LPU2
Function
Default use
NMEA in 7
NMEA in 8
NMEA in 9
Alarm Ack.
RS232 In
RS232 GND
RS232 Out
Opto in1
Opto in2
Opto in3
Opto in4
LOG 2 MAIN
Analogue in
Ana out 1
Ana out 2
K1
K2
K3
K4
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
STW Astern
K5
K6
K7
K8
Opto 1
Opto 2
Opto 3
Opto 4
20 (52)
Consilium
Terminal
32 +
32 33 +
33 34 +
34 35 +
35 36 A
36 B
36 C
37 A
37 B
38 A
38 B
Name
LPU2
Function
Default use
Opto 5
Opto 6
Opto 7
Opto 8
Out 1 A
Out 1 B
ESD2
(Channel 0)
Out 2 A
Out 2 B
Out 3 A
Out 3 B
39 A
39 B
Out 4 A
Out 4 B
40 A
40 B
Out 5 A
Out 5 B
41 A
41 B
Out 6 A
Out 6 B
42 A
42 B
Out 7 A
Out 7 B
NMEA out 7
Log 1
(Channel 3)
43 A
43 B
Out 8 A
Out 8 B
NMEA out 8
Log 2
(Channel 4)
44 A
44 B
Out 9 A
Out 9 B
NMEA out 9
45 A
45 B
Out 10 A
Out 10 B
NMEA out 10
(Out 10-11 share driver)
SD display
(Channel 6)
46 A
46 B
Out 11 A
Out 11 B
NMEA out 11
(Out 10-11 share driver)
SD display
(Channel 6)
47 +
47 48 +
48 49 +
49 50 +
50 51 +
51 52 +
52 53 +
53 54 +
54 -
18-32 VDC
18-32 VDC
18-32 VDC
12-28 VDC
12-28 VDC
12-28 VDC
12-28 VDC
12-28 VDC
21 (52)
Consilium
Name
12-28 VDC
LPU2
Function
Terminal
55 +
55 56 +
56 57 +
57 58 +
58 59 A
59 B
Default use
Out 12 A
Out 12 B
NMEA out 12
(Out 12-13 share driver)
SD display
(Channel 6)
60 A
60 B
Out 13 A
Out 13 B
NMEA out 13
(Out 12-13 share driver)
SD display
(Channel 6)
61 A
61 B
Out 14 A
Out 14 B
NMEA out 14
(Out 14-15 share driver)
SD display
(Channel 6)
62 A
62 B
Out 15 A
Out 15 B
NMEA out 15
(Out 14-15 share driver)
SD display
(Channel 6)
63 A
63 B
Out 16 A
Out 16 B
NMEA out 16
(Out 16-17 share driver)
64 A
64 B
Out 17 A
Out 17 B
NMEA out 17
(Out 16-17 share driver)
65 A
65 B
Out 18 A
Out 18 B
NMEA out 18
(Out 18-19 share driver)
66 A
66 B
Out 19 A
Out 19 B
NMEA out 19
(Out 18-19 share driver)
67 A
67 B
Out 20 A
Out 20 B
NMEA out 20
(Out 20-21 share driver)
68 A
68 B
Out 21 A
Out 21 B
NMEA out 21
(Out 20-21 share driver)
69 A
69 B
Out 22 A
Out 22 B
NMEA out 22
(Out 22-23 share driver)
70 A
70 B
Out 23 A
Out 23 B
NMEA out 23
(Out 22-23 share driver)
12-28 VDC
12-28 VDC
12-28 VDC
22 (52)
Consilium
LPU2
Terminal
71
72
73
74
Name
230 VAC
115 VAC
N
GND
Function
230 VAC Power supply (L1)
115 VAC Power supply (L1 Option)
Neutral (L2)
Ground
Note
Fuse F101
Fuse F102
Fuse F103
5 Setting up procedure
The LPU2 has an internal menu system that can be accessed via a remote SD4 Speed Log
Master Display or via the web-interface. At setup the menu system is used for:
1) changing the default setup of input- and output channels. See Menu I, N and O.
2) enter speed log transducer (TRU) position to enable docking log calculations. See Menu
S on page 30.
3) enter system type: T-Series, R1a or Dual Log. See Menu S on page 30.
4) access the internal alert list for troubleshooting. See Menu A on page 26.
The settings are stored in non-volatile memory and will therefore also be active after a reboot
or power shut-down. After the setting up is finished and the system is tested, no further actions
are required during normal operation.
Consilium
LPU2
The Menu Mode is reached by pressing the Mode button for minimum 5 sec. The Mode
Window will show the text PRESS ENTER FOR MENU. Then press the Enter button (4th
button from left) within 5 seconds.
The Mode Window will now show the start menu in the SD4. The six buttons under the Mode
Window have now got alternative functions. The alternative functions are lit in red text below
relevant button.
The buttons now have the following functions:
Mode: 1st button from left. Will inform which remote device is connected in remote mode.
Esc:
2nd button from left. The Escape function is used in the Remote Device menu to
escape from the menu system in a remotely connected unit (E.g. the LPU2 menu
system) and step back to the local menu system in the SD4 unit.
Menu: 3rd button from left. Is used alone, or together with the Minus (-) button, or together
with the Enter button, to move in the menus as described below.
Menu button alone, will display next menu i.e. step forward on same menu level.
Menu button and Minus (-) buttons pressed simultaneously will display previous
menu, i.e. step back on the same menu level.
Menu button and Enter buttons pressed simultaneously will move up one menu level,
except when leaving the Remote Device menu. (see Esc-button)
Enter:
4th button from left is used to store changed values or to move to sub-menus.
- +
Minus button and Plus button are used to change values or status (E.g. write
access OFF/ON) and /or to change device values.
Note: The Menu System will exit automatically if no button has been pressed for 5 minutes
when being in the local SD4 Menu System, when connected to a remote device there is no
timeout and the Escape button must be used to exit from a remotely connected device.
5.1.2 SD4 in Menu Mode
The Menu Mode in the SD4 has three Local Menus and one Remote Device menu:
SD4 LOCAL. This is the start menu when entering the Menu Mode. If one or more
other displays are remotely dimmed from the display, this menu shows a second text
line were the remote dimming function can easily be turned ON/OFF.
LP0 PROPERTIES. This menu contains sub menus for local setting up of the display.
Note: Do not turn write access ON without special training.
LS0 REMOTE SETUP. This menu contains sub menus for setting up when the display
is used as a Speed log Master Display /Remote Device for other units and displays.
Note: Do not turn write access ON without special training
R0 REMOTE DEV. On designated Speed Log Master Displays this menu provides
access to a remote device, e.g. the WTU-unit, BTU-unit or the LPU2 menu structure.
Note: Verify that the setting in SD4 menu LS7 is R0 REMOTE ENABLED [ON]
to be able to connect to remote devices.
To connect to the menu system in the LPU2:
24 (52)
Consilium
LPU2
When in SD4 LOCAL (the start menu) step to R0 REMOTE DEV menu by pressing the
MENU button three times.
When pressing ENTER in the R0 menu the SD4 will establish communication with all
connected equipment and display them in a list of menu choices.
Press the MENU button until the LPU is displayed and press ENTER to start communicating
with the LPU2.
ESC is used to step back.
Example of a menu walk in the R0 REMOTE DEV menu:
R0 REMOTE DEV CONNECT
press[Enter]
SYNCHRONISING
(counting down from 5)
wait 3 seconds
R1 DEVICE 1 OF 3
BTU 1
(T2A)
press[MENU]
R2 DEVICE 2 OF 3
LPU 1
(LP1)
press[ENTER]
W+XX.X DXXX.X
BL+XX.X T+X.XX
press[ESC or MENU+ENTER]
R0 REMOTE DEV
CONNECT
25 (52)
Consilium
LPU2
+ = ahead, - =astern
Sign as above.
+ = starboard, - = port.
This is the "default" menu, which is shown during normal operation. If left in any other menu,
the system will return to this menu after 2 minutes of idling.
5.2.2 Menu A, Alert list
When pressing the MENU button in the Main menu, A0 ALERT LIST is displayed.
A0 ALERT LIST
0 ACTIVE
This menu displays the number of active SAL speed log system alerts if any (PSALW)
including LPU2 alerts (400-499).
The menu will also display external alarms ($xxALR). Note! Echo Sounder alarms ($SDALR)
are NOT displayed.
Press the ENTER button for sub menu A1. Menu A1 contains a list of active alerts. Use the +, or MENU button to toggle between all active alerts/alarms if any.
For a list of LPU2 alert numbers, see Table 6 Alert list on page 42.
5.2.3 Menu I, Inputs
When pressing the MENU button in the Alert list MENU, I0 INPUTS is displayed.
I0 INPUTS
WRITE ACCESS OFF
Settings concerning NMEA- and OPTO- inputs are set under this menu.
NMEA talkers:
I1 NMEA IN1
LOG 1 MAIN
to
I9 NMEA IN9
ALARM MUTE
Which type of NMEA talkers that are connected to the LPU2 can be set in menu I1 to I9. These
settings control which type of NMEA messages that will be let through on each input. Menu I1
to I9 can also be set to correct and let through incoming NMEA with missing or corrupt
checksum. Each NMEA talker is filtered according to the filter-file in use, see 6 NMEA
filtering on page 38.
NOTE! Each of the four default input functions: LOG 1 MAIN, LOG 1 REDUNDANCY,
GYRO or ESD shall never be set to more than one NMEA input.
26 (52)
Consilium
LPU2
OPTO inputs:
I10 OPTO IN 1
ALARM MUTE
to
I13 OPTO IN 4
LOG 2 MAIN
The LPU2 is equipped with four opto-isolated inputs that can be used to control the system.
Each input can be set according to the following list:
OPTO inputs
ALARM MUTE
Mute an ESD Alarm
ES 2 MAIN
ES 2 (LOG 2) becomes the active Echo Sounder
LOG 2 MAIN
LOG 2 becomes the active log
LOG 1 BT MUTE
Mutes the BT / SOG transmitter of LOG 1
LOG 2 BT MUTE
Mutes the BT / SOG transmitter of LOG 2
Table 1 OPTO input list
Example of settings:
- Restore to default menu settings
- CPU Reboot
- Display SoftWare REVISION
- Display FirmWare REVISION
- Display HardWare REVISION
- ACCESS LEVEL
See table Menu function summary For a complete MENU list.
5.2.5 Menu N, NMEA out
When pressing the MENU button in the M0 MISC menu, N0 NMEA OUT is displayed.
NO NMEA OUT
WRITE ACCESS OFF
to
N8 NMEA O 16-23
SPEED+DEPTH
Which type of NMEA listeners that are connected to the LPU2 can be set in menu N1 to N8.
These settings control which NMEA messages are transmitted on each output. Each NMEA
output is filtered according to the filter-file in use, see 6 NMEA filtering on page 38.
27 (52)
Consilium
LPU2
Setting concerning analogue, relay and opto outputs are set under this menu.
Analogue outputs:
O1 ANALOG OUT 1
WTL
to
O18 OPTO 8
PULSE F BTR 200P
Program a threshold value for relay and / or OPTO outputs:
Example to set OPTO out 1 to a threshold value of WTL higher than 8kn:
Use the MENU button to go to menu O11
O11 OPTO 1
PULSE A WTL 200P
Press the ENTER button once more to reach sub menu O11.1
O11.1 OPTO 1
WTL HIGH THAN 0
Function
Consilium
LPU2
Function
WTT PORT
WT INVALID
BTL ASTERN
BTT PORT
BT INVALID
BT DEPTH INVALID
WTL HIGH.THAN XX
WTT HIGH.THAN XX
WTR HIGH.THAN XX
BTL HIGH.THAN XX
BTT HIGH.THAN XX
BTR HIGH.THAN XX
WTL LOW.THAN XX
WTT LOW.THAN XX
WTR LOW.THAN XX
BTL LOW.THAN XX
BTT LOW.THAN XX
BTR LOW.THAN XX
29 (52)
Consilium
LPU2
Setting concerning docking-log, NMEA syntax, NMEA delay, BT speed (SOG) input, pulse
timers, speed averaging, USB handling and network IP-address can be accessed under this
menu.
The system can automatically detect connected SAL speed logs and set-up the system
accordingly. When the menu is set to AUTO SENSE it will make a new scan of the inputs and
choose a new system setup. The decision is made 5 seconds after the first valid NMEA input on
LOG1 Main, LOG1 Redundancy or LOG2. The chosen system type is displayed when the
menu S1 is entered again. Alternatively, this menu can be used to manually set the type of
system according to following table.
SYSTEM TYPE
Function
AUTO SENSE
T SERIES
R1a
DUAL LOG
The rate of turn signal from the gyro can be fed to the LPU2, either via a serial NMEA
interface or an analogue DC voltage. If ANALOGUE is chosen, an additional menu S2.2 will
be used to set the scale factor of the analogue input.
S3 DL GEO BOW
0 M
Consilium
LPU2
Specifies in which format the docking-log information is transmitted over the serial NMEA
interface. Can be set to VDVBW, PSALL or PSALL/VBW STERN
VDVBW: This is the standard Velocity Doppler log format, which includes two fields for
transversal speed. The first field shows transversal speed in the bow and the second field shows
transversal speed in the stern of the ship. If no docking-log calculation takes place, only the
first transversal field is used, indicating transversal transducer speed.
PSALL: This is a propriety message containing the docking-log information. The VDVBW
message is transmitted simultaneously, with only the first transversal field used indicating
transducer speed.
PSALL/VBW STER: The PSALL message and the VDVBW message are both transmitted.
The PSALL message containing the docking-log information, and the VDVBW message, using
the first transversal field for transducer speed and the second transversal field for speed in the
stern.
IEC 61162-1 edition 2 adds docking-log information fields to the VDVBW message for stern
transversal speed. Some older listeners might not support those new fields in the message.
Setting this menu to SHORT, forces the LPU2 to output the VDVBW message in the shorter
format without stern transversal speed.
Note if SHORT version of the VDVBW message is used menu S5 must be set to PSALL for
the docking-log info to be transmitted to the listeners, e.g. SD4-5.
This menu controls the interval between serial data messages. The delay can be used to lower
data rate for slow receiver devices unable to handle messages back to back. The value is
adjustable in 10 ms steps from 0 up to 60-70 ms (default delay is 0 ms). For maximum
31 (52)
Consilium
LPU2
throughput the value shall be set as low as possible. When using the MFD5 we recommend
setting this value to 60-70ms.
Currently not implemented, but will extend the use of the LPU2 to also calculate docking-log
information from other speed sources.
to
S14 PULSE F
BTR 200 P / NM
There are 6 different pulse timers (A-F) used to generate speed pulses that can be chosen for
relay and opto outputs. Following listed speeds can be set under Menu S9 S14.
Pulse timer settings Function
WTL 100P
Longitudinal STW 100 pulses / NM
WTL 200P
Longitudinal STW 200 pulses / NM (Default for Pulse timer A)
WTL 400P
Longitudinal STW 400 pulses / NM
WTL 500P
Longitudinal STW 500 pulses / NM
WTT 100P
Transversal STW 100 pulses / NM
WTT 200P
Transversal STW 200 pulses / NM (Default for Pulse timer B)
WTT 400P
Transversal STW 400 pulses / NM
WTT 500P
Transversal STW 500 pulses / NM
WTR 100P
Resulting STW 100 pulses / NM
WTR 200P
Resulting STW 200 pulses / NM (Default for Pulse timer C)
WTR 400P
Resulting STW 400 pulses / NM
WTR 500P
Resulting STW 500 pulses / NM
BTL 100P
Longitudinal SOG 100 pulses / NM
BTL 200P
Longitudinal SOG 200 pulses / NM (Default for Pulse timer D)
BTL 400P
Longitudinal SOG 400 pulses / NM
BTL 500P
Longitudinal SOG 500 pulses / NM
BTT 100P
Transversal SOG 100 pulses / NM
BTT 200P
Transversal SOG 200 pulses / NM (Default for Pulse timer E)
BTT 400P
Transversal SOG 400 pulses / NM
BTT 500P
Transversal SOG 500 pulses / NM
BTR 100P
Resulting SOG 100 pulses / NM
BTR 200P
Resulting SOG 200 pulses / NM (Default for Pulse timer F)
BTR 400P
Resulting SOG 400 pulses / NM
BTR 500P
Resulting SOG 500 pulses / NM
Table 3 Pulse timer settings
Consilium
LPU2
This menu will affect analogue and pulse outputs as well as those NMEA outputs programmed
for NMEA listeners SPD AVERAGE +DPT. Rapid changes of speed will be slowed down
by the set value in this menu. If, for example, this menu is set to 5 sec, it will take 5 seconds for
a speed change to be fully indicated on the output. When choosing this setting on an NMEA
output, speed is filtered according to the time setting but transmitted DPT is unchanged
An USB memory stick can be used to store all received and transmitted NMEA messages in the
LPU2. This menu enables activation or deactivation of the NMEA storage. Please reboot the
LPU2 before inserting USB memory stick. Average storage on USB memory stick is approx.
300 MB/24h. Menu can be set to FILL UP or OFF.
5.2.7.9 S17, USB Erase
S17 USB ERASE
DISABLED
This menu gives the possibility to completely erase and format an USB memory. However, it
might fail depending on LPU2 load and the type of USB memory.
Specifies which IP address the LPU2 will respond to when accessed from a service tool. Last
digit is default set to 17 and should normally not be changed. As authorized it may be set
from 1 to 50. If set outside this range, it will use 1 or 50.
S19 SERVICE PC
IP 192.168.5.56
Specifies which IP address the LPU2 shall connect to when accessing a service tool.
Not changeable.
5.2.8 Menu T, Test
When pressing the MENU button in the S0 SETTINGS menu, T0 TEST is displayed.
T0 TEST
WRITE ACCESS OFF
NMEA input signals are simulated internally by the LPU2 with the following setting:
Log1Main:
WTL = 20.10, BTL = 21.10, BTT = 1.10, Depth = 99.1
Log1Redundancy: WTL = 24.50, BTL = 25.50, BTT = 1.50, Depth = 99.5
GYRO_ROT:
ROT = 5.30
33 (52)
Consilium
LPU2
NOTE echo sounder depth is not simulated, $SDDPT, only speed log depth $VDDPT.
If the setting in menu S1 is R1A, the LPU2 simulates incoming NMEA as below:
T1 TEST NMEA
R1A
NMEA input signals are simulated internally in the LPU2 with the following setting:
Log1Redundancy: WTL = 24.50
If the setting in menu S1 is DUAL_LOG, the LPU2 simulates incoming NMEA as below:
T1 TEST NMEA
DUAL LOG
NMEA input signals are simulated internally in the LPU2 with the following setting:
Log1Main:
WTL = 20.10, BTL = 21.10, BTT = 1.10, Depth = 99.1
Log1Redundancy: WTL = 24.50, BTL = 25.50, BTT = 1.50, Depth = 99.5
Log2Main:
WTL = 22.20, BTL = 23.20, BTT = 1.20, Depth = 99.2
GYRO_ROT:
ROT = 5.30
If the setting in menu S1 is AUTO SENSE this information is shown:
T1 TEST NMEA
CAN NOT SIMULATE AUTO
The LPU2 web interface appears where all settings can be made. For further assistance see
separate annex on page 47.
34 (52)
Consilium
LPU2
Name
MAIN
MENU
A0
W+XX.XX DXXX.X
BL+XX.X T+X.XX
ALERT LIST
A1
ACTIVE ALERTS
INPUTS
NMEA IN1
NMEA IN1
NMEA IN1
LOG 1 MAIN
CHECKSUMTEST ON
BAUDRATE 4800
I3.01
I3.02
NMEA
NMEA
NMEA
NMEA
NMEA
NMEA
IN2
IN2
IN2
IN3
IN3
IN3
LOG 2 MAIN
CHECKSUMTEST ON
BAUDRATE 4800
GYRO (ROT)
CHECKSUMTEST ON
BAUDRATE 4800
I4.01
I4.02
NMEA IN4
NMEA IN4
NMEA IN4
ESD
CHECKSUMTEST ON
BAUDRATE 4800
NMEA IN5
NMEA IN5
NMEA IN6
LOG 1 REDUNDANCY
CHECKSUMTEST ON
SD4
NMEA IN6
NMEA IN7
NMEA IN7
NMEA IN8
NMEA IN8
NMEA IN9
NMEA IN9
OPTO IN 1
OPTO IN 2
OPTO IN 3
OPTO IN 4
ANALOG IN
MISCELLANEOUS
MENU DEFAULTS
MENU FROM USB
MENU TO USB
CONF DEFAULTS
CONF FROM USB
CONF TO USB
CHECKSUMTEST ON
SD4
CHECKSUMTEST ON
GPS
CHECKSUMTEST ON
ALARM MUTE
CHECKSUMTEST ON
ALARM MUTE
LOG 1 BT MUTE
ES 2 MAIN
LOG 2 MAIN
GYRO (ROT)
I0
I1
I1.01
I1.02
I2
I2.01
I2.02
I3
I4
I5
I5.01
I6
I6.01
I7
I7.01
I8
I8.01
I9
I9.01
I10
I11
I12
I13
I14
M0
M1
M2
M3
M4
M5
M6
Default setting
Function
DISABLED
DISABLED
DISABLED
DISABLED
DISABLED
DISABLED
35 (52)
*
OFF or ON
*
4800 or 38400
*
OFF or ON
4800 or 38400
*
OFF or ON
4800 or 38400
*
*
OFF or ON
*
4800 or 38400
*
*
OFF or ON
*
Speed Log Master
Display
*
OFF or ON
*
OFF or ON
Diagnostic function
OFF or ON
OFF or ON
Mutes the SOG function
*
*
*
*
*
*
*
Consilium
LPU2
No
M7
M8
M9
M10
M11
M12
M13
N0
N1
N1.01
Name
USB UPDATES
BACKUP TO USB
CPU REBOOT
SW REVISION
FW REVISION
HW REVISION
ACCESS LEVEL
NMEA OUT
NMEA OUT 1
NMEA O 1
Default setting
DISABLED
DISABLED
DISABLED
704519xx
704517xx
704510xx
ALL USER
N2
N3
N4
N5
N6
N7
N8
O0
O1
O1.01
O2
O2.01
O3
O4
O5
O6
O7
O8
O9
O10
O11
O12
O13
O14
O15
O16
O17
O18
S0
S1
NMEA OUT 2
NMEA OUT 3-6
NMEA OUT 7
NMEA OUT 8
NMEA OUT 9
NMEA OUT 10-15
NMEA OUT 16-23
OUTPUTS
ANALOG OUT 1
ANALOG OUT 1
ANALOG OUT 2
ANALOG OUT 2
RELAY K1
RELAY K2
RELAY K3
RELAY K4
RELAY K5
RELAY K6
RELAY K7
RELAY K8
OPTO 1
OPTO 2
OPTO 3
OPTO 4
OPTO 5
OPTO 6
OPTO 7
OPTO 8
SETTINGS
SYSTEM TYPE
SD4 MASTER
SPEED+DEPTH
LOG 1
LOG 2
SD4 MASTER
SD4
SPEED+DEPTH
DL GYRO INPUT
DL GYRO INPUT
DL AIN SCALE
NMEA
ANA +180/MIN=10V
+180/MIN = +10V
S2
S2
S2.01
Function
*
*
xx = actual revision
xx = actual revision
xx = actual revision
ESD
BAUDRATE 4800
WTL
0.1 V/KNOTS
BTR
0.1 V/KNOTS
Fail Log 1
Fail Log 1
WTL ASTERN
ESD ALARM
PULSE A WTL
PULSE A WTL
PULSE F BTR
PULSE F BTR
PULSE A WTL
PULSE A WTL
PULSE A WTL
PULSE A WTL
PULSE F BTR
PULSE F BTR
PULSE F BTR
PULSE F BTR
200P
200P
200P
200P
200P
200P
200P
200P
200P
200P
200P
200P
AUTO SENSE
36 (52)
*
4800 or 38400
*
*
Consilium
No
S3
LPU2
Name
DL GEO BOW
Default setting
0 M
S4
DL GEO STERN
0 M
S5
DL NMEA
VDVBW
S6
S7
S8
S9
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
VDVBW FORMAT
TX DELAY
BT SPEED INP
PULSE A
PULSE B
PULSE C
PULSE D
PULSE E
PULSE F
SPD AVERAGE
USB STORAGE
USB ERASE
LPU2 ADDRESS
SERVICE PC
TEST
TEST NMEA
EXTENDED
0 MS
LOG
WTL 200 P / NM
WTT 200 P / NM
WTR 200 P / NM
BTL 200 P / NM
BTT 200 P / NM
BTR 200 P / NM
0 SEC
FILL UP
DISABLED
IP 192.168.5.17
IP 192.168.5.56
WRITE ACCESS OFF
T-SERIES
T0
T1
Function
Distance from transducer
1 to the bow of the ship
[0-999m]
Distance from transducer
1 to the stern of the ship
[0-999m]
VDVBW, PSALL or
PSALL/VBW STERN *
SHORT/EXTENDED *
0-63ms (6bits)
*
(For future use)
*
*
*
*
*
*
*
0 to 255s
*
FILL_UP or OFF
Formats and erase
17 can be set from 1-50 *
192.168.5 56 is fixed *
T-SERIES, R1a or
DUAL-LOG
Note!
*) Not changeable.
Grey fields indicates not visible menus.
These settings shall never be changed and are only changeable when M13 is changed and
only for development purposes.
37 (52)
Consilium
LPU2
6 NMEA filtering
Inputs are filtered according to a filter-file. The table below describes input filtering when
filter-file NMEAfilterT_rev.txt is in use. The question mark ? is used as a wildcard and
can be replaced by any character.
NMEA talkers
Not filtered messages are starting with:
LOG 1 MAIN
VD; PSAL
LOG 1 REDUNDANCY VD; PSALS; PSALD; PSALW
LOG 2
VD; PSAL;
GYRO (ROT)
??ROT
ES
SDDPT
ESD
SD; VDTXT; PSALC
SD4
PSALS,0; PSALS,1; PSALS,2; PSALS,3; PSALS,4;
PSALR; PSALC; VDTXT; ??ACK
ALARM MUTE
??ACK
GPS
G??
GYRO (HDT)
??HDT
GYRO (ROT+HDT)
??HDT; ??ROT
OTHER
Not yet implemented
Table 4 NMEA talker list
This table is stored in a filter-file that is specific for the system type chosen in menu S1.
The filter-files also contain NMEA output filtering according to NMEA listners table below.
There are totally three default filter-files in the LPU2 application: NMEAfilterT_rev.txt,
NMEAfilterR1a_rev.txt and NMEAfilterDual_rev.txt. Example: a T-series system
will use the file NMEAfilterT_rev.txt.
Note! The filter-files shall never be changed and are only changeable when M13 is changed
and only for development purposes.
The filter-file type in use can be imported / exported to an USB memory stick. Using the menu
M6 CONF TO USB the LPU2 will create a folder on the USB memory stick named
LPU2store_restore and export (copy) the filter-file in use from the LPU2 into the
LPU2store_restore folder on the USB memory stick.
A filter-file can be imported into the LPU2 using menu M5 CONF. FROM USB. The USB
memory stick has to have a folder named LPU2store_restore on the root where the filterfile is placed.
38 (52)
Consilium
LPU2
The NMEA messages are routed according to the following default NMEA talkers list if the
NMEAfilterT_rev.txt filter-file is in use. (? Is used as a wildcard and can be replaced by
any character)
NMEA listeners
Transmitted messages are starting with
SPEED + DEPTH
VDVBW; VDVLW; ##DPT; ??ALR; PSALL
SPD AVERAGE +DPT @@VBW; VDVLW; ##DPT; ??ALR; @@ALL
SD4 DUAL LOG
VDVBW; PSALS,5; PSALS,6; PSALS,9; PSALc; PSALR,,;
PSALU,1
SD4 MASTER
VDVBW; VDVLW; ??DPT; VDALR; PSALS,5; PSALS,6;
PSALS,9; ??ROT; PSALL; PSALR,,, PSALW
SD4
VDVBW; VDVLW; ##DPT; ??ROT; PSALL; PSALR
LOG 1
PSALS,0; PSALS,1,; PSALS,1?,; PSALS,10; PSALC; VDACK
LOG 2
PSALS,0; PSALS,1,; PSALS,1?,; PSALS,10; PSALC; VDACK
ESD
VDDPT; SDACK; PSALX; VDVBW; PSALW
VDR
VDVBW; VDVLW; ##DPT; ??ALR; PSALc;
MFD
VD; ??ROT; PSALL
GPS
G??
OTHER
Not yet implemented
Table 5 NMEA listeners
##DPT:
@@VBW; @@ALL:
39 (52)
Consilium
LPU2
7 Testing Procedure
Connected equipment may be tested in two ways:
1) using ordinary input from the SAL Log ELC and the ROT gyro (optional). Either during
normal operation or using internal test modes to produce a known SAL Log ELC output. For
setting these test modes, please consult the operating/installation manuals for the SAL speed
log and ROT gyro.
2) using simulated NMEA input, self-generated by the LPU2. For setting these modes, please
see Menu T. Only equipment connected to the output can be tested.
40 (52)
Consilium
LPU2
Alert
Text
Description
400
405
07
407
08
408
09
409
10
410
31
32
33
431
432
433
34
35
36
37
434
435
436
437
38
438
40
440
4X
44X
NORMAL OPERATION
SYSTEM MISMATCH
NMEA input mismatch. Check System Type
(Menu S1)
POWER FAIL SOG 1
NMEA from SOG log 1 missing.
Check IN1 / System Type
POWER FAIL STW 1
NMEA from STW log 1 missing.
Check IN5 (always supervised)
POWER FAIL LOG 2
NMEA from speed log 2 missing.
Check IN2 / System Type
ROT MISSING
NMEA from Gyro missing
(Docking: Menu S3 and S4 > 0)
OVERFLOW OUT 1
NMEA overflow on Out_1, terminal 36 (channel 0)
OVERFLOW OUT 2
NMEA overflow on Out_2, terminal 37 (channel 1)
OVERFLOW OUT 3-6
NMEA overflow on Out_3-6, terminal 38-41
(channel 2)
OVERFLOW OUT 7
NMEA overflow on Out_7, terminal 42 (channel 3)
OVERFLOW OUT 8
NMEA overflow on Out_8, terminal 43 (channel 4)
OVERFLOW OUT 9
NMEA overflow on Out_9, terminal 44 (channel 5)
OVERFLOW O 10-15
NMEA overflow on Out_10-15,
terminal 45-46, 59-62 (channel 6)
OVERFLOW O 16-23
NMEA overflow on Out_16-23,
terminal 63-70 (channel 7)
NMEA OVERFLOW
NMEA inputs overflow. Too high total serial data
load
CORRUPT / BAUD IN
NMEA corrupt or wrong baud rate IN_X
X
(X = Input 1..9)
41 (52)
Consilium
LPU2
LED
code
5X
Alert
Text
Description
45X
POL/ BAUD IN X
6X
71
46X
471
CHECKSUM ERR IN X
HW ERR OUT 1
72
472
HW ERR OUT 2
73
473
74
474
HW ERR OUT 7
75
475
HW ERR OUT 8
76
476
HW ERR OUT 9
77
477
78
478
84
88
484
488
489
490
491
492
493
494
495
496
497
498
499
E0
The actual revision of the loaded software can be checked in the LPU2 Menu System M10 and
M11.
42 (52)
Consilium
LPU2
ON
8 7 6 5 4 3 2 1
OFF
ON
8 7 6 5 4 3 2 1
OFF
ON
8 7 6 5 4 3 2 1
OFF
ON
The mode is selected by first setting DIP switch 7 and 8 as follows and then press and release
the Reboot button on the CPU-board.
During the first seconds after a reboot both S1 and S2 are off, before the start-up procedure
enters the selected boot mode. Then each mode is indicated by the two red LEDs S1 and S2 on
the CPU board.
During normal operation, Mode 0, LED S1, S3 and S4 are lit and LED S2 flickers.
Regular software updates are performed using the flashing utility software WinFlash, 706080.
DIP switches shall be in default setting, i.e. DIP 7 and 8 Mode 0. The image file for LPU2 is
named 704580Rr.lpu, where Rr is the revision number. When performing this update,
connect a serial cable to the service RS232 D-sub located in the upper left corner of the LPU2
and to a PC. Menu settings will not be overwritten when updating the software using Winflash.
Press and release the Reboot button on the CPU-board and within a few seconds click Start
in WinFlash. If not succeeded try once more.
43 (52)
Consilium
LPU2
The LPU2 may be updated with smaller modifications from an USB memory stick. The
following softwares are supported for updates from USB:
704517, LPU2 PCB Firmware
704519, LPU2 PCB Software
First, prepare a USB memory stick by placing the software update(s) in a directory called
LPU2updates at the top directory level. It is important to use capital letters for LPU and
small letters for updates. Then, place the USB stick in either one of the two USB
connections.
Set DIP to Mode 1, DIP switch 8=off and 7=on. Press and release the Reboot button and the
following process begin:
1: LED S1 and S2 = OFF (a few seconds)
2: LED S1 = ON and LED S2 = OFF
3: As a safety procedure, all previous files in the update directory on the LPU2 are
backed up to the USB stick top level directory LPU2backup.
4: The updates are copied from the USB stick. All files in the LPU2updates directory
on the USB stick are copied to the lpu2.
5: To indicate that the update procedure is finished, LED S1 goes OFF.
LED S1 and S2 also indicate if something went wrong, by flashing repeatedly. Please check
USB stick and try again. Information about the installation progress is shown in a hyper
terminal if connected to the service RS232 D-sub (115k 8N1).
When the software update procedure is finished, take out the USB Memory stick and set the
DIP switch back to normal operation, Mode 0, and press and release the Reboot button.
MODE 0: Normal operation
Set dipswitch 8=off and 7=off. Press and release the Reboot button and the following process
begin:
1: S1 = off and S2 = off
2: Executes software upgrade if available, otherwise default software is executed.
3: S1, S2, S3 and S4 are now under the LPU2 software control. S1, S3 and S4 are lit, S2
flickers.
Consilium
LPU2
Set dipswitch to Mode 2 (from default move DIP 8=ON). Press and release the Reboot button
and the following process begin:
1: LED S2 = OFF (only a few seconds)
2: LED S2 = ON
3: Previous updates will be erased
4: The EPROM will be reset with the factory default menu settings and config.
5: To indicate that the factory reset procedure is finished, LED S2 goes OFF.
The factory reset takes totally about 1 minute and 30 seconds.
The LEDs (S1 and S2) may also indicate if something went wrong, by flashing repeatedly.
Press the Reboot button to try once more. Information about the factory-reset progress is sent to
a Hyper Terminal if connected to the service RS232 D-sub (115k 8N1).
When factory reset is finished, set the DIP switch back to Mode 0 (back to default, move DIP
8=off), normal operation and press and release the Reboot button. After about 45 seconds the
system is up and running.
8.5 USB
Either one of the two USB connections can be used, but not simultaneously.
8.5.1 USB memory stick requirements
o The USB memory stick must be formatted with a file system of type FAT32.
Menu S17 can be used to erase and format an inserted USB memory sticks. However, it might
fail depending on LPU2 load and the type of USB memory. If Menu S17 fails, us a PC to
format the USB memory to FAT 32.
o
8.5.2 Recording NMEA to a USB memory stick
It is possible to store all incoming and outgoing NMEA messages to a USB Memory stick. This
enables long time monitoring of system functionality. The USB memory stick can later be sent
for analysis. All incoming and outgoing NMEA messages are stored in a folder named
LPU2recordings on the USB memory stick.
1: Insert an empty USB memory stick.
2: Reboot the LPU2 using the Reboot button or menu M9.
3: Start the NMEA recording by enabling menu S16. This menu is by default enabled.
If already enabled, the recording will start by itself. The USB memory stick is updated once
every minute. The recording will not overwrite any data when USB memory stick is full.
8.6 Troubleshooting
The LPU2 is equipped with several functions for easy troubleshooting.
Fuses
3 pcs 5x20mm 2,5A SB (F101 230V, F102 115V, F103 Common, N)
located at the PSU board. These fuses power the LPU2.
4 pcs 5x20mm 1,6A SB supplying DC out, located at the IO board.
Each of these fuses supplies 3 terminals, i.e. the upper fuse supply terminals 4745 (52)
Consilium
LPU2
49, the second fuse supply terminals 50-52 etc. Each fuse has a green control
LED to the right of the fuse. At normal operation these four LEDs shall be lit.
Green LEDs
8 green LEDs for internal voltage supervision are located at the upper edge of
the CPU board. In normal operation these 8 LEDs shall be lit.
4 red LEDs
4 red LEDs are controlled by the software, LED S1, S2, S3 and S4.
In normal operation, S1, S3 and S4 are lit, S2 flickers.
Red 2 x LED digits
Red 2 x LED digits display for alert status. Code 00 shall be displayed during
normal operation, see 8.1 Supervision and alert numbers.
DIP 1-8
A set of 8 DIP switches are located on the CPU-board close to the upper right
corner. In normal operation these DIPs shall be set to: 1 and 5 = ON, the rest =
OFF. Note! ON = down.
NMEA inputs
Each NMEA input is supervised by a control LED. Whenever NMEA telegrams
are received the corresponding LED shall flicker.
NMEA outputs
Each NMEA output is supervised by a control LED. Whenever NMEA
telegrams are transmitted the corresponding LED shall flicker.
Opto and relay terminals
Each Opto and relay terminal is supervised by a control LED that is turned on
when the output is active.
Web interface
The built-in Web interface has several functions for trouble shooting such as an
NMEA display function where all incoming and outgoing NMEA traffic can be
watched. The Web interface can read the alert history file where all alerts are
time stamped.
USB interface
USB connection can be used to save incoming/outgoing NMEA traffic on a USB
memory stick. Saved data on the stick can be analyzed by Consilium for service
purpose.
46 (52)
Consilium
LPU2
Annex 1
9 Web-interface
The built-in web-interface can be used to setup the LPU2s menu system and for different
service purposes such as display incoming/outgoing NMEA, list time stamped alerts. Below
follows some examples from the web-interface.
47 (52)
Consilium
LPU2
2. The LPU2 internal system clock. The time stamps are relative this clock. The clock is
set from factory and is not related to, e.g., the GPS time. The time can not be set in SW
704519B0 or earlier.
2
1
48 (52)
Consilium
LPU2
49 (52)
Consilium
LPU2
Annex 2
10 Wiring principles
Cable Dimensions and Standards
Make sure that the all cables are approved for marine environment usage.
Signal Cables
All cables used for signal interconnection of the SAL Speed-log system units shall
have a cross section of at least 0.5 mm2 with a voltage rating of at least 60 volts and be
screened, either an aluminium foil screen with an inlaid, blank, stranded conductor, or
tinned copper braid should be used.
If the specifications state twisted pair, such cable should be used.
It is recommended to use a cable with numbered conductors. This makes identification much
easier, and minimizes the risk of miss-connections.
DC Power Cables
All cables specified to be DC power cables in the Speed-log system shall have a cross
section of at least 1.5 mm2 with a voltage rating of at least 120 volts. Using any other
cable type will void warranty.
The installation directions may specify a heavier cross section.
It is recommended to increase the cross section at longer runs of cable (e.g. exceeding 10
meter) to avoid problems with voltage drops.
It is also recommended to use cable with coloured conductors, preferable one red part for the
positive voltage and one black part for negative return.
AC Power Cable
All cables used for supplying AC power in the Speed-log system shall have a cross
section of at least 1.5 mm2 with a voltage rating of at least 500 volts.
The cable must be UL registered, for the environment in which it is used. Failing to use
UL registered cable will void warranty.
The cable must have three conductors, coloured blue, brown and yellow-green. The
yellow-green part is to be used for grounding only.
Follow established electrical safety regulations when selecting and using high voltage cabling.
Comments to signal cabling
Noise
All cables with two or more parts are twisted (stranded) for manufacturing reasons. This does
not mean any two-conductor cable is a Twisted Pair.
Twisted pair means two separated and isolated wires, twisted together in a special
noise-cancelling configuration.
Two twisted pairs means two separate sets of such two wires, twisted together, not
four wires twisted together.
The twisted pair is a unit that by its twist protects itself from the environment, and protects the
environment (such as, the pair next to it) from itself. The pitch of the twist is carefully
calculated to maximize the noise-cancelling properties, which is not the case with ordinary
50 (52)
Consilium
LPU2
multi-pole cable. Thus, when using Two twisted pairs make sure using the two wires twisted
together and not one wire from each twisted pair.
Do not use twisted quads or ordinary multi-pole cable, which also has somewhat twisted parts.
In a twisted quad the signals in one pair will cross-couple to the other pair, because they are so
close, and because one pair has no means of protecting itself from the other pair. In an ordinary
multi-pole cable, the noise-cancelling properties are random or unknown i.e. cross-coupling
between the individual wires is bound to occur.
EMI
Electromagnetic Interference (EMI) is everywhere. It is the unwanted signal component that
disrupts a system, creates unwanted noise in the audio channels, or causes the system to go
down at irregular intervals. If EMI is not counter-acted at installation time, it will be very
costly to troubleshoot and change the system later. Intermittent faults with an EMI background
can be impossible to find.
The Speed-log units has been designed and tested with EMI protection in mind, but defective
wiring may destroy that protection.
Termination of Signal Cables
To reduce the risk of
EMI induction
Excessive noise on audio channels
Short circuits
Intermittent faults
Entanglement
Mix-ups
and to ease re-dressing of cabling and re-connections after service
All signal cables must be connected carefully and by using described method depending
on type of connection block terminal.
1. Where the connection block terminals are of press-type we recommend to use bare
wires
2. Where the connection block terminals are of screw-type we recommend to press
end-caps on the bare wire ends as described below
Same principles can be used on power cables.
The free ends should be as short as possible. This tends to make connecting more difficult, but
greatly reduces the risk of EMI induction.
The end caps must be crimped with the proper tool to attain a proper connection. Never use
pliers or crimp-tools intended for anything else than end caps.
51 (52)
Intentionally blank
Consilium
Technical
Description
Serial Display
SAL SD4
Article No. 704005
Consilium
Contents
1.
2.
3.
Background ....................................................................................... 4
Definitions and abbreviations ............................................................ 4
Design, general ................................................................................. 5
4.
5.
6.
Set-up of SD4.................................................................................. 13
7.
8.
9.
10.
11.
12.
13.
14.
3.1.
3.2.
3.3.
4.1.
4.2.
4.3.
4.4.
4.5.
4.6.
4.7.
4.8.
4.9.
5.1.
5.2.
5.3.
5.4.
5.5.
6.1.
6.2.
6.3.
6.4.
6.5.
9.1.
9.2.
9.3.
Display windows............................................................................................... 5
Direction arrows, status indications and backlight ........................................... 5
Pushbuttons ..................................................................................................... 5
Mounting ........................................................................................................ 21
Downloading of new software ........................................................................ 22
Testing ........................................................................................................... 22
10.1.
10.2.
10.3.
10.4.
General .......................................................................................................... 23
Positioning of the Speed Log Master Display ................................................ 23
Electrical connection ...................................................................................... 23
Positioning of the labels ................................................................................. 24
14.1.
Consilium
14.2.
14.3.
14.4.
14.5.
14.6.
Revisions
2005-01-24
2005-04-12
A0
A1
2005-04-12
2005-10-12
A2
A3
2005-12-09
A4
2008-09-23
A5
2009-09-02
A6
2010-01-19
B0
2011-01-13
B1
RB
RB
Created
Timeout from menu system 3min, IP66, Menu R0 changed,
editorial changes, SD4-BMB drawing, testing
RB Added U/N, more accessories, wider panel cut-out
RB Valid from sw rev A3. Added Master Display info, clarified
200p/NM pulse output, added REMOTE DIM [EXT]
description, reduced maximum current consumption, compass
safe distance.
RB SD4SDR2 connections updated, SD4-5 bow/stern, Default
settings SD4-4, Dimmer switch corrected.
RB Alert Mode, Depth offset, Suspend function, Dual log added.
Valid from SW revision 704021B2 and 704024B1.
AF VLW sync at resulting distance, menu LPc. Default setting in
Menu function summary. No TOTAL BTL,BTT,WTL,WTT.
Added STANDBY STW mode. WT->STW, BT->SOG, added
IMO standard at chapter 2. Alert mode no label, service
warning only. Alert info and improved explanations of modes
in table 6.5
RB/OM Adapted to new front panels, (SOG and STW) and functions,
instrument and indicator=Display
Update Menu function summary to sw 704021C0
OM
Implemented Alert Mode LP2.21 PSALW, updated company
name,
3 (35)
Consilium
1.
Background
The SAL SD4 is a versatile display used primarily as a display to indicate speed,
distance and depth. It can also be used to remotely control such equipment, which is not
easily accessible or has no user interface, for example a speed log or an interface
cabinet.
The SD4 Display is intended as a successor to the SD1 and SD2 Displays. The different
Display versions of the SD4 series are utilised using the same main body, 704000.
2.
Description
Serial Display family
Serial Display 4
IEC61162-1 ed2 serial interface standard
Speed Trough the Water.
This is equivalent to Water Track (WT) speed (relative)
Speed Trough the Water Longitudinal
Speed Trough the Water Transversal
Water - refer to resulting distance (relative)
Water - refer to distance,
Longitudinal, Transversal
Speed Over the Ground.
This is equivalent to Bottom Track (BT) speed (true)
Speed Over the Ground Longitudinal
Speed Over the Ground Transversal
Ground refer to resulting distance (true)
Ground refer to distance,
Longitudinal, Transversal
Trip distance counter, resettable
Total distance counter
Rate Of Turn
Echo sounder display
4 (35)
Consilium
3.
Design, general
3.3. Pushbuttons
To operate the SD4, there are 6 push buttons positioned below the MODE WINDOW.
4.
Function, general
All SD4 versions will decode all defined messages and display all possible information
if available. Generally, all SD4 Displays can enter all requested modes.
5 (35)
Consilium
6 (35)
Consilium
7 (35)
Consilium
5.
kn
SOG
kn
SAL
SD4-1
Mode
Test
Press
2 sec
Mode
Esc
Trip /
DIST
Reset
Trip
Menu
Enter
+
DIM
U/N 704041
Consilium
SPEED WINDOW 1
STW (longitudinal) [88.8]. Arrows indicate forward or aft.
SPEED WINDOW 2
SOG (longitudinal) [88.8]. Arrows indicate forward or aft.
MODE WINDOW
Pre-set display modes:
DIST WAT
Trip WAT
Trip GND
Depth sensor (from ESD)
Alert
8 (35)
Consilium
Longitudinal
kn
STW
SAL
SD4-2
SOG
Transverse
kn
Mode
Test
Press
2 sec
Mode
STW
Trip /
DIST
Reset
Trip
Esc
Menu
Enter
+
DIM
U/N 704042
Consilium
SPEED WINDOW 1
STW or SOG (longitudinal) [88.8]. Arrows indicate forward or aft.
SPEED WINDOW 2
Transverse SOG [88.8]. Arrows indicate port or starboard. If the SD4-2 is set to display
STW and no transverse STW is available, this window and its indication arrows will be
unlit.
MODE WINDOW
Pre-set display modes:
DIST WAT
Trip WAT
Trip GND
Alert
9 (35)
Consilium
STW
kn
SAL
SD4-3
Mode
Test
Press
2 sec
Mode
Esc
Trip /
DIST
Reset
Trip
Menu
Enter
+
DIM
U/N 704043
Consilium
SPEED WINDOW 1
STW (longitudinal) [88.8]. Arrows indicate forward or aft.
SPEED WINDOW 2
Covered by front foil
MODE WINDOW
Pre-set display modes:
DIST WAT
Trip WAT
Alert
10 (35)
Consilium
SAL
SD4-4
NMEA A in
NMEA B in
NMEA A out
NMEA B out
Pulse output
SDR2
SDR2 / Ext Dim SDR2 / Ext Dim +
0 VDC
10..32 VDC
(12 or 24 VDC nominal)
Test
Mode
Esc
Menu
Enter
+
DIM
1
2
3
4
5
6
7
8
9
10
U/N 704044
Consilium
MODE WINDOW
Pre-set display modes:
STW-L (longitudinal)
11 (35)
Consilium
1
2
3
4
5
6
7
8
9
10
SAL
SD4-5
Test
STW
SOG
knots
m/s
+
DIM
Consilium
SPEED WINDOW 1
Transverse SOG or STW in bow [88.8]. Arrows indicate port or starboard.
SPEED WINDOW 2
Longitudinal STW or SOG [88.8]. Arrows indicate forward or aft.
MODE WINDOW
The MODE WINDOW is partly covered by the front foil, an opening in the same size as
the SPEED WINDOWS is left to display transverse STW or SOG in stern [88.8].
Arrows indicate port or starboard.
In the SD4-5 the ID used for remote dimming is set to number 5, there is no MENU
system available in the SD4-5 and therefore this fixed ID can not be changed.
12 (35)
Consilium
6.
Set-up of SD4
13 (35)
Consilium
6.2.2.
Local Properties MENU (LP0 PROPERTIES):
When pressing the MENU button in the BASIC MENU, LP0 PROPERTIES is
displayed. Setting of local properties is done under this menu.
For example:
SD4 type
Select options to display in the MODE WINDOW
Startup DIM
External inputs / outputs
See chapter 6.5.
Menu function summary, for a complete list of MENU choices
6.2.3.
Remote Setup MENU (LS0 REMOTE SETUP):
When pressing the MENU button in the LP0 Local Properties MENU, LS0 REMOTE
SETUP is displayed. Setting of remote properties is done under this menu.
For example:
SD4 id
DIM offset
Remote dim id
See chapter 6.5.
Menu function summary, for a complete list of MENU choices
6.2.4.
REMOTE DEV (MENU R0):
Remote User interface to other equipment.
When MENU R0 is entered the SD4 will establish communication with all connected
equipment and display them in a list of menu choices. When a choice is made the
communication starts with that equipment. ESC is used to step back to select another
equipment.
Example of a menu walk in the R0 menu:
R0 REMOTE DEV
CONNECT
[Enter]
SYNCHRONISING
(counting down from 3)
wait 3 seconds
R1 DEVICE 1 OF 2
BTU 1
(T2A)
[MENU]
R2 DEVICE 2 OF 2
WTU 1
(R1A)
[ENTER]
LH
7.89 7.91
RC=495 1055:1055
Access to the menu system in the WT unit. To exit back to
local mode the ESC button must be used. The ESC button
will always step out of the remotely controlled menu
14 (35)
Consilium
menu system.
MENU+ENTER is used to step back within the remotely
controlled menu system.
[ESC]
R2 DEVICE 2 OF 2
WTU 1
(R1A)
[ESC or MENU+ENTER]
R0 REMOTE DEV
CONNECT
If the MODE button is pressed when inside the MENU system, help text will be
displayed. For example when connected as a remote user interface and the mode button
is pressed, information will be displayed about the controlled equipment. If inside the
menu system to the BT unit the following text will be displayed as long as the MODE
button is pressed down.
REMOTE: T2A
When set to EXT this SD4 Display will not send out any remote dim messages when
the pushbuttons on the display are used for dimming but when the external input is
used remote dim messages will be sent out. (See 6.4.2. External DIM set-up
(Terminal 7 + 8) for explanation of external dim input.)
15 (35)
Consilium
IN1 SDR2
IN2 ext DIM / SDR2
IN3 ext DIM / SDR2
16 (35)
Consilium
Name
LP0
LP1
LP2
SD4- LOCAL
PROPERTIES
SD4 TYPE
SD4- [ ]
MODE WINDOW
LP2.01
DIST WATER
LP2.02
TRIP WAT-L
LP2.03
TRIP WAT-T
LP2.04
TRIP WATER
LP2.05
DIST GROUND
LP2.06
TRIP GND-L
LP2.07
TRIP GND-T
LP2.08
TRIP GROUND
LP2.09
DIST+TRP WAT
LP2.10
DIST+TRP GND
LP2.11
TRIP WAT+GND
LP2.12
LP2.13
LP2.14
LP2.15
LP2.16
LP2.17
LP2.18
LP2.19
SPEED SOG-L
SPEED SOG-T
SPEED SOG
SPEED STW-L
SPEED STW-T
SPEED STW
DEPTH (ESD)
SENSOR: No offset
KEEL: Negative offset
SURF: Positive offset
DEPTH (LOG)
LP2.20
ROT
Default setting
Function
SD4 SD4 SD4 SD4
-1
-2
-3
-4
BASIC MENU
Select properties menu
1
2
3
4
Sets type of SD4 display,
SD4-1.. SD4-4 (factory setting)
List of information to be displayed
in the MODE WINDOW:
OFF Total distance counter of STW
ON
ON
ON
(resulting)
OFF OFF OFF OFF Trip distance counter of STW
longitudinal
OFF OFF OFF OFF Trip distance counter of STW
transversal
OFF Trip distance counter of STW
ON
ON
ON
(resulting)
OFF OFF OFF OFF Total distance counter of SOG
(resulting)
OFF OFF OFF OFF Trip distance counter of SOG
longitudinal
OFF OFF OFF OFF Trip distance counter of SOG
transversal
OFF OFF Trip distance counter of SOG
ON
ON
(resulting)
OFF OFF OFF OFF DIST WAT and TRIP WAT
are displayed simultaneously
OFF OFF OFF OFF DIST GND and TRIP GND
are displayed simultaneously
OFF OFF OFF OFF TRIP WAT and TRIP GND
are displayed simultaneously
OFF OFF OFF OFF SOG longitudinal
OFF OFF OFF OFF SOG transversal
OFF OFF OFF OFF SOG (resulting)
OFF OFF OFF ON
STW longitudinal
OFF OFF OFF OFF STW transversal
OFF OFF OFF OFF STW (resulting)
OFF OFF OFF Depth from Echosounder display
ON
with offset according to $SDDPT
message.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
17 (35)
Consilium
No
Name
LP2.21
LP2.22
LP2.23
LP3
ALERT
DUALLOG
STANDBY STW
STARTUP DIM
[50%]
NEG SPD USE
[OFF]
Default setting
Function
SD4 SD4 SD4 SD4
-1
-2
-3
-4
OFF Display alert messages (PSALW)
ON
ON
ON
OFF OFF OFF OFF DISABLED (For future use.)
OFF OFF OFF OFF Deactivates valid STW NMEA to
invalid STW NMEA
50% 50% 50% 50% Default brightness after a reset
OFF
OFF
OFF
OFF
DIM
DIM
DIM
DIM
STWL
STWL
STWL
STWL
LP7
NMEA GATE
THROUGH [OFF]
OFF
OFF
OFF
OFF
LP8
NMEABAUDRATE
[4800]
SW REVISION
704021xx
RESET TOTAL
LOCAL DISTANCE
RESET TOT
CONFIRM [NO]
NO
NO
NO
NO
NO
NO
NO
NO
LP4
LP5
LP6
LP9
LPA
LPA.01
LPB
LPB.01
LS0
LS1
LS2
LS3
LS3.01
SET DEFAULT
MENU PARAMETERS
RESET MEN
CONFIRM [NO]
REMOTE SETUP
SD4 ID
[4]
DIM OFFSET
[0 %]
REMOTE DIM
ID
REMOTE DIM
Consilium
No
Name
LS3.02
LS3.03
LS3.04
LS4
LS5
LS6
LS7
R0
ID [ ]
REMOTE DIM
ID [ ]
REMOTE DIM
ID
[]
REMOTE DIM
ID
[]
HEARTBEAT
TIMEOUT [30]S
MENU ACKN
TIMEOUT [3]S
SD2 REMOTE
DIM [OFF]
R0 REMOTE
ACCESS [ENABLED]
Default setting
Function
SD4 SD4 SD4 SD4
-1
-2
-3
-4
entered
The second SD4 ID can be entered
The third SD4 ID can be entered
The fourth SD4 ID can be entered
30
30
30
30
OFF
OFF
OFF
OFF
EN
EN
EN
EN
REMOTE DEV
CONNECT
R1
DEVICE 1 OF x )
<NAME> (<ID>)
R2
DEVICE 2 OF x )
<NAME> (<ID>)
R3
19 (35)
Consilium
7.
8.
Technical data
Powering
Input voltage
Current
Environmental conditions
As required by IEC 60945 4th edition. If panel mounted on a watertight flat surface or in
a SD4 BMB box according to exposed category, otherwise protected.
Watertight as required by IEC 529 category IP66 if mounted in SD4 BMB, SD4SA or
panel mounted on a flat surface.
Compass safe distance: 0.3m
Nominal viewing distance
Serial:
Connections of power, inputs and output are done via a 10-pole plug-in terminal,
maximum cable area 1.5 mm.
Dimensions
20 (35)
Consilium
9.
9.1. Mounting
The four attaching holes in the SD4 are threaded with an M6 thread making it possible
to mount the SD4 either with four M6 screws from the back or with four M5 screws
from the front using nuts on the backside. When the SD4 is mounted on a flat surface
using M5 screws with nylon washers from the front and the provided neoprene gasket is
used, a protection of IP66 is achieved.
Mechanical dimensions and panel cut-out:
21 (35)
Consilium
9.3. Testing
If the SD4 is programmed to type SD4-0 a test sequence is performed.
(Not valid for SD4-5)
1. Diode test:
A number of test patterns are displayed to ensure that all LEDs are OK. Press any
button to step to the next pattern
2. Input test:
IN1, IN2 and IN3 is displayed together with status information. Press both DIM
buttons simultaneously to step to the next test.
3. Output test:
The output is pulsed with a frequency of 1 Hz. Press both DIM buttons
simultaneously to step to the next test.
4. Buttons test:
When a button is pressed a button number is displayed. Press both DIM buttons
simultaneously to end the test and jump to menu LP1 SD4 TYPE where the actual
SD4 Display type is entered, such as SD4-1, SD4-2, SD4-3 or SD4-4.
22 (35)
Consilium
23 (35)
Consilium
Longitudinal
kn
STW
SAL
SD4-2
SOG
Transverse
kn
Mode
Test
Press
2 sec
Mode
STW
Trip /
DIST
Reset
Trip
Esc
Menu
Enter
+
DIM
U/N 704042
Consilium
24 (35)
Consilium
Longitudinal
kn
STW
SAL
SD4-2
SOG
Transverse
kn
Mode
Test
Press
2 sec
Alert LED
Mode
STW
Trip /
DIST
Reset
Trip
Esc
Menu
Enter
+
DIM
U/N 704042
Consilium
The Alert message is displayed in the Mode window with the following field
descriptors:
ALERT XXX
YYY
TEXT
XXX: Alert number.
YYY: Input in LPU2 if applicable.
TEXT: 16 characters alert description text.
When an Alert message is received the Mode window will switch to ALERT mode and
display the message.
Example of STW simulation Alert from the STW Speed log:
ALERT 301 LPUIN5
STW SIMULATION
The text LPUIN5 is refering to that the Alert message is received on an LPU2 input
no 5 and is only showing when the SD4 is connected to an LPU2.
25 (35)
Consilium
If more than one Alert message is sent to the SD4 Display, the Alerts are stored in a list
in the sequence they were received. To view next Alert message press the MODE
button.
The SD4 has a capacity of storing a maximum of 10 Alerts.
If more than 10 different Alerts are received, Alert nr 11 and further the Mode window
show:
ALERT 999 -------- OVERFLOW --An Alert is treated as inactive when indicated in the received NMEA message or after a
timeout of one minute if no more Alert messages are received with the corresponding
Alert number.
If no Alerts are received, the Alert mode on the Mode window will show:
ALERT ---
26 (35)
Consilium
27 (35)
Consilium
28 (35)
Consilium
14. Accessories
The SD Display family can be equipped with a number of accessories, including a
mounting box for situations where the SD4 cannot be mounted in panel and an AC
power supply for 115/230 V AC powering.
29 (35)
Consilium
30 (35)
Consilium
The SD4-BMB can be used to mount the SD4 on any flat surface. Mounting is done
either from the front using the supplied mounting brackets or from the back with M5
screws. The cable intake is supplied with a cable gland for IP66 protection for cable
diameters in the range 9 - 13 mm.
The bulkhead mounting box assure that the SD4 is watertight according to IP66. The
SD4 unit itself is also watertight when mounted onto flat panel surface.
31 (35)
Consilium
The SD4SA can be used to mount the SD4 standing or hanging. The cable intake is
supplied with a cable gland for IP66 protection for cable diameters in the range 5 - 9
mm.
The SD4SA assure that the SD4 is watertight according to IP66. The SD4 itself is also
watertight when mounted onto flat panel surface.
32 (35)
Consilium
30,48
66,04
1 2 3 4
The SD4 Extension Board is equipped with two relays, which can be used to obtain
200p/NM speed pulses or for other use in special installation. Parameter LP6 is used to
choose function of the output. (See chapter 6.
Set-up of SD4)
14.4.1. Installation
The board is installed directly on the back of the SD4. Unplug the 10-pole terminal from
the SD4, plug in the SD4EB in its place and plug in the 10-pole terminal in the top
contact of the SD4EB. The two relay contacts can now be accessed via terminal block
#1-4 on the SD4EB.
SD4EB
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Note
Relay 1 normally open, max load 30V/30mA or 15V/100mA
Relay 2 normally open, max load 30V/30mA or 15V/100mA
33 (35)
Consilium
144 113
Consilium
SD4 DIMMER
U/N 704120
24
26
48
28,5
The SD4 External Dimmer is used to DIM one SD4 from a remote position.
Parameter LP5 EXTERNAL INPUTS shall be set to [DIM] for the dimmer to function
correctly (See chapter 6.
Set-up of SD4).
More SD4 Displays can be connected to the same dimmer if they are powered from the
same source. All connected SD4 Displays will be dimmed but the intensity level on
different SD4 Displays will not be the same. We therefore recommend using serial
Remote DIM message when more SD4 Displays shall be dimmed to the same intensity.
(See chapter 4.8.
Remote DIM message)
14.5.1. Installation
SD4
Terminal 7
Terminal 8
Terminal 9
SD4ED
Terminal 1
Terminal 3
Terminal 2
Function
Dim down
Dim up
0 VDC
34 (35)
Consilium
Test
Press
2 sec
48
Mode
WT
Trip/
Total
Reset
Trip
24
DIM
Consilium
U/N 704130
113
144
The SD4 Remote control is used to access the SD4 buttons from a remote position.
Parameter LP5 EXTERNAL INPUTS shall be set to [SDR2] for the remote control to
function correctly (See chapter 6. Set-up of SD4).
Note! The SDR2 is not intended for e.g. calibration
14.6.1. Installation
SD4
Terminal 6
Terminal 7
Terminal 8
Terminal 9
Terminal 10
SD4SDR2
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
Function
In 1
In 2
In 3
Not used
0 VDC
10..32 VDC
35 (35)
Intentionally blank
Consilium
Analogue Speed
Indicator
Doc No. 701402A3
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Intentionally blank
2 (3)
U. Hermansson
S. Gullbert
2002.10.02
701393 A0
2002.10.02
Consilium
Doc.: 701402A3
3 (3)
U. Hermansson
S. Gullbert
2002.10.02
701399A0
SIA-2-8
Analogue Indicator
U/N: 71-21049-17
2002.10.02
Consilium
Doc.: 701402A3
Intentionally blank
Consilium
Consilium
1 (2)
Consilium
Contents
1.
Introduction
Appendix:
Example of a SAL T2 cable diagram, 703266A2
Example of a SAL T2 cable connection diagram, 703267A2
Revisions
2008-04-08
2008-06-30
2010-10-01
A0
A1
A2
RB
AF
OM
Created
Revision appendix 703266A1 and 703267A1
703266->A2, 703267->A2
1.
Introduction
This section is to fulfil the needs for a normal electrical installation of a SAL T2 system and
contains examples of cable diagram and connection diagram.
2 (2)
Consilium
Consilium
1 (2)
Consilium
Contents
1.
Introduction
Appendix:
Example of a SAL T2+ cable diagram, 703286A1
Example of a SAL T2+ cable connection diagram, 703287A1
Revisions
2010-10-29
2011-01-26
A0
A1
OM
OM
Created
Clarified, at least two SD4 displays, one with external power
1.
Introduction
This section is to fulfil the needs for a normal electrical installation of a SAL T2+ system and
contains examples of cable diagram and connection diagram.
2 (2)
Intentionally blank
Intentionally blank
Consilium
IEC 61162/
NMEA 0183
User Guide
Document No. 700164
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
Revisions
Date
2007-08-09
2007-09-19
2008-09-12
2010-05-21
2010-10-05
A0
A1
A2
A3
A4
RB
RB
RB
OM
RB
Table of Contents
1.
Introduction .........................................................................................3
2.
Hardware.............................................................................................4
3.
1.1.
1.2.
1.3.
General.............................................................................................................3
References .......................................................................................................3
Background ......................................................................................................3
2.1.
3.1.
Standard IEC 61162-1 3rd ed/NMEA 0183 version 3.01 messages..................7
3.1.1.
Alarm Acknowledge (--ACK) .......................................................................7
3.1.2.
Alarm (--ALR)..............................................................................................7
3.1.3.
Depth (--DPT) .............................................................................................8
3.1.4.
Rate of turn (--ROT)....................................................................................8
3.1.5.
Text Transmission (--TXT)..........................................................................8
3.1.6.
Dual Doppler Velocities (--VBW) ................................................................9
3.1.7.
Distance travelled through the water and over the ground (--VLW)..........10
3.2.
Proprietary Consilium Messages ....................................................................11
3.2.1.
Log control messages (PSALC) ...............................................................11
3.2.2.
Log status messages (PSALc) .................................................................12
3.2.3.
SAL Docking log (PSALL).........................................................................14
3.2.4.
Remote dimming message (PSALR)........................................................14
3.2.5.
Remote control message (PSALS)...........................................................15
3.2.6.
Multiple Units message (PSALU) .............................................................16
2 (17)
Consilium
1.
Introduction
1.1. General
The purpose of this document is to define the most common serial messages that are used by
Consilium Marine & Safety speed logs, voyage data recorders and interface units as well as
specify the hardware used for serial communication.
The document is intended to be used as a sub-document to operator manuals.
1.2. References
1.3. Background
The National Marine Electronics Association (NMEA) has developed a specification that
defines the interface between marine electronic equipments called NMEA 0183. This standard
is closely aligned with the standard IEC 61162-1 from International Electrotechnical
Commission (IEC) which is specified by International Maritime Organization (IMO) to meet
the International convention for the Safety of Life at Sea (SOLAS) regulations.
In this document, as well as in all Consilium Marine & Safety documents, we refer to this
standard as IEC 61162-1/NMEA or IEC 61162-2/NMEA for the high speed version of the
same standard.
The idea of IEC 61162/NMEA is to send a line of data called a sentence that is self contained
and independent from other sentences. There are standard sentences for each device category
and a capability exist to define own / proprietary sentences for use by manufacturers.
3 (17)
Consilium
2.
Hardware
The IEC 61162-1/NMEA and IEC 61162-2/NMEA standard specifies serial data links with
one talker and multiple listeners, using for each talker a separate signal pair with all listeners
opto-isolated.
Both standards, IEC 61162-1 and IEC 61162-2, use the same serial data message definition
but the hardware has some differences on the receiving side. IEC 61162-2 uses a more
complex receiver stage as it is designed for a higher speed, 38400 b/s (bit per second)
compared to 4800 b/s used in IEC 61162-1.
Complying with IEC 61162-1 and IEC 61162-2 standard, all Consilium Marine & Safety
designed NMEA driver uses RS485 compatible driver circuits, using differential outputs
swinging in the range 0 to +5 Volts. The polarities of the signals are defined by "A" and "B".
In the idling state the "A" terminal carries 0 Volt and the "B" terminal +5 Volts. Maximum
load on each driver circuits is 100 ohm which is equal to ten IEC 61162-1/NMEA inputs in
parallel.
All Consilium Marine & Safety designed IEC 61162-1/NMEA inputs use opto-couplers to
assure isolation between the talker and the listener according to the IEC standard.
IEC 61162-2/NMEA inputs uses opto-isolated RS485 receivers with a DC power supply
which is isolated from case ground as well as from the DC power in the receiving unit.
We do not recommend any other technical solution, than those mentioned above, for
connecting equipment to NMEA networks were Consilium Marine & Safety products are
connected as talkers or listeners. Some early proposals for the IEC 1162-1 permitted also the
use of RS422 receivers, having a DC path between case ground and the receiver circuit. We
strongly discourage such use and recommend the use of a separate, opto-isolated buffer unit if
it is necessary to feed such devices.
The interface speed for IEC 61162-1/NMEA is 4800 b/s with 8 bits of data, no parity, and one
stop bit. At 4800 b/s you can only send 480 characters in one second. Since an NMEA
sentence can be as long as 82 characters you can be limited to less than 6 different sentences
per second. The actual limit is determined by the specific sentences used, but this shows that
it is easy to overrun the capacity of the interface.
4 (17)
Consilium
IEC 61162-2/NMEA uses three wires, two wires in one pair connected as signal "A" and "B"
and a third wire from a separate pair connected as "C" (ground connection between the
transmitting unit and the isolated input stage).
5 (17)
Consilium
3.
Field Type
Status
Variable
length
floating
Variable
length
integer
Fixed hex
Symbol
A
x.x
Definition
Single character field: A=data valid, V=data invalid.
Normal definition of a floating format variable. The integer version
separated into a new definition.
i.
hh-
Variable text
Fixed alpha
Fixed
number
Fixed text
cc
aaxx-
cc-
6 (17)
Consilium
3.1. Standard IEC 61162-1 3rd ed/NMEA 0183 version 3.01 messages
The intention of Consilium Marine & Safety is to implement the standard messages as defined
in the IEC 61162-1, 3rd edition. This corresponds to the NMEA 0183 version 3.01. All outputs
will, whenever possible, refer only to messages defined in these documents.
The first two characters after the $ sign define the talker identifier. Consilium Marine &
Safety uses the following identifiers:
IN
SD
TI
VD
VR
Integrated Navigation
Sounder, depth
Turn rate indicator
Velocity sensors: Doppler, other/general
Voyage data recorder
Field Type
Name
Definition
Alarm acknowledge
2
3
xxx
hh
Note
VD = Log, VR = VDR,
SD = Depth Sounder
Field Type
Name
Definition
Alarm
hhmmss.ss
xxx
4
5
6
7
A
A
cc
hh
Alarm condition
Acknowledge condition
Alarms description text
Check sum
7 (17)
Note
VD = Log, VR = VDR,
SD = Depth Sounder
UTC (Coordinated Universal
Time)
100 .. 199 ESD, 200 .. 299 SOGunit, 300 .. 399 STW-unit, 400 ..
499 LPU2
A = alarm, V = no alarm
A = Acknowledged, V = not
Consilium
Field Type
Name
x.x
x.x
Definition
Depth
Depth below transducer [m]
Depth between transducer and
keel or water line[m]
4
5
x.x
hh
Note
VD = Log, SD = Depth sounder
Null field indicates out of range
This figure is unknown to the log
system, so a null field is
transmitted here.
(Fix set to 400 m for SAL T2)
Example: Data from SAL T1 and SAL T2 speed log (depth measured to 30.0 m):
$VDDPT,30.0,,400*
$SDDPT,30.0,,400*
3.1.4. Rate of turn (--ROT)
1
2
3 4
$--ROT,x.x,A*hh<CR><LF>
Field #
1
2
3
4
Field Type
Definition
Note
Name
Rate of turn
TIROT, HEROT, INROT
x.x
Rate of turn [degrees / minute]
"-" is bow turns to port
A
Status
A = data valid, V = data invalid
hh
Checksum
Example: Data from rate of turn gyro (30 degrees / minute clockwise):
$TIROT,30.0,*
Field Type
Definition
Name
Alarm acknowledge
xx
Total number of sentences
xx
Sentence number
xx
Text identifier
c-c
Text message
hh
Check sum
Example: Text message from SD2-16.
VRTXT,01,01,01,START BACKUP*
8 (17)
Note
VD = Log, VR = VDR
Consilium
Field Type
Name
2
3
4
5
6
7
8
9
x.x
x.x
A
x.x
x.x
A
x.x
A
A
B
x.x
A
hh
Definition
Water-referenced and groundreferenced speed data
Longitudinal water speed
Transversal water speed
Status water speed
Longitudinal ground speed
Transversal ground speed
Status ground speed
Stern Transversal water speed
Status stern transversal water
speed
Stern Transversal ground speed
Status stern transversal ground
speed
Check sum
Note
VDVBW
knots
knots
A = data valid, V = data invalid
knots
knots
A = data valid, V = data invalid
knots
A = data valid, V = data invalid
knots
A = data valid, V = data invalid
SAL R1
SAL R1a
SAL T1
SAL T2s
SAL T2
SAL T3
$VDVBW,10.05,,A,,,V,,V,,V*
$VDVBW,10.05,,A,11.02,,A,,V,,V*
$VDVBW,10.05,,A,11.02,-0.05,A,,V,,V*
9 (17)
Consilium
3.1.7. Distance travelled through the water and over the ground (--VLW)
Note that this sentence was extended. Older systems might still transmit the shorter version of
the sentence with only the first five fields plus the checksum field.
1
2
3 4
5 6
7 8
9 A
$--VLW,x.x,T,x.x,T,x.x,T,x.x,T *hh<CR><LF>
Field #
1
2
3
4
5
6
7
8
9
A
Field Type
Name
x.x
Definition
Note
Distance through water
VDVLW
Total water distance [nautical
minimum range 9999.9
miles]
T
Type
N = Nautical mile
x.x
Trip water distance [nautical
miles]
T
Type
N = Nautical mile
x.x
Total ground distance [nautical
minimum range 9999.9
miles]
T
Type
N = Nautical mile
x.x
Trip ground distance [nautical
miles]
T
Type
N = Nautical mile
hh
Checksum
Example: Data from SAL R1 (total distance 100 nautical miles, trip 3.50 nautical miles):
$VDVLW,100.00,N,3.50,N,,N,,N*
10 (17)
Consilium
Field Type
Name
i.
i.
Definition
Proprietary SAL Control
Control message type
Bottom track transmission
Note
PSALC
2: SAL T2 BT control
0: Set transmit mode off
1: Set transmit mode on
hh
Check sum
Example: Force acoustic transmitter off:
$PSALC,2,0*
3.2.1.2.
Field #
1
2
3
4
Field Type
Definition
Name
Serial control message
i.
Control message type
c
Transmission status
hh
Checksum
Example: Turn off NMEA transmission:
$PSALC,3,S*
11 (17)
Note
PSALC
3: Transmit status
'A'=Active, 'S'=Silent
Consilium
3.2.1.3.
Field #
1
2
3
Field Type
Name
i.
ccc
Definition
Proprietary SAL Control
Control message type
Activate WT speed unit
ccc
3.2.1.4.
Note
PSALC
4: Active speed control
VD1: Log 1
VD2: Log 2
VD9: Simulated Log
VD1: Log 1
VD2: Log 2
GP1: GPS
VD9: Simulated Log
hh
Check sum
Example: Activate WT speed from Log1 and BT speed from Log 2:
$PSALC,4,VD1,VD2*
Log control message 5: Active depth unit
1
2 3
4
$PSALC,5,ccc*hh<CR><LF>
Field #
1
2
3
Field Type
Name
i.
ccc
Definition
Proprietary SAL Control
Control message type
Activate depth unit
Note
PSALC
5: Active depth control
VD1: Log 1
VD2: Log 2
SD1: External echosounder
VD9: Simulated Log
hh
Check sum
Example: Activate Log2 as depth unit:
$PSALC,5,VD2*
Field #
1
2
3
5
Field Type
Name
i.
i.
Definition
Proprietary SAL status
Control message type
Bottom track transmission
hh
Check sum
Example: Status is acoustic transmitter on:
$PSALc,2,1*
12 (17)
Note
PSALc
2: SAL T2 BT status
0: Transmit mode is off
1: Transmit mode is on
Consilium
3.2.2.2.
Field #
1
2
3
Field Type
Name
i.
ccc
Definition
Proprietary SAL status
Control message type
Activated WT speed unit
ccc
3.2.2.3.
Note
PSALc
4: Activated speed
VD1: Log 1
VD2: Log 2
VD9: Simulated Log
VD1: Log 1
VD2: Log 2
GP1: GPS
VD9: Simulated Log
hh
Check sum
Example: Log1 is the activated WT speed unit and Log 2 is the activated BT speed unit:
$PSALc,4,VD1,VD2*
Log status message 5: Activated depth unit
1
2 3
4
$PSALc,5,ccc*hh<CR><LF>
Field #
1
2
3
Field Type
Name
i.
ccc
Definition
Proprietary SAL status
Control message type
Activated depth unit
hh
Check sum
Example: Log2 is the activated depth unit:
$PSALc,5,VD2*
13 (17)
Note
PSALc
5: Activated depth unit
VD1: Log 1
VD2: Log 2
SD1: External echosounder
VD9: Simulated Log
Consilium
Field Type
Name
x.x
x.x
x.x
c
Definition
SAL docking Log
Longitudinal ground speed
Transversal ground speed of bow
Transversal ground speed of stern
Log status character
Note
PSALL?
knots
knots
knots
'B'=valid bottom track,
'W'=valid water track (only long)
'L'=valid bottom track, unvalid
rate of turn information. Field 3
contains transversal speed from
log, ?field 4 is invalid?
'E'=log error
hh
Checksum
Example: longitudinal speed 1.32 knots, bow -1.11 knots, stern +0.44 knots:
$PSALL,1.32,-1.11,0.44,B*
Field Type
Name
c
Definition
Remote dimming
Dimmer direction
Note
PSALR?
"+" = increase light,
"-" = decrease light
A Z
0% 100%
c-c
ID of instruments to be dimmed
i.
Dim value
hh
Checksum
This message is intended for using the NMEA network to control groups of indicators.
Whenever a $PSALR message is received by any indicator it adjusts the light level
accordingly. $PSALR messages are generated by SD indicators having remote dimmer
controls. (SD1 and SD2 indicators only uses field 2).
Example:
Increase light on SD1/SD2:
$PSALR,+,,*
Set a light level of 70% on instruments with id E:
$PSALR,,E,70*
14 (17)
Consilium
Field Type
Name
i.
cc
cc
hh
Example: Heartbeat
Definition
Signal data
Signal number
Identity (for receiver)
String data
Checksum
Note
PSALS
*
** Information coded as ASCII
Information coded as ASCII
$PSALS,1,R1A,1234*
* Field 2, signal number:
Signals with number 0 through 49 are used for signals from indicator to log. Signals with
number 50 through 99 are used for signals from log to indicator. Identity is a character field.
Status is the content of the LCD or equivalent presentation unit.
Number
Name
Content
0
Identify
MasterID, informative text
1
Heartbeat
ID, any test data
2
SDataLog request ID, port
3-9
Reserved
10-19
RemoteCmd
ID
20-45
Reserved
46
Activate
ID
47
Deactivate
ID
48
ResumeCmd
ID
49
SuspendCmd
ID
50
Identity
SlaveID, informative text
51
HeartAck
ID, any test data
52
SDataLog acknowl ID, port
53-59
Reserved
60-69
RemoteAck
ID, status
70-95
Reserved
96
Activate ackn.
ID
97
Deactivate ackn. ID
98
StatusInfo
ID, Status (23 char LCD) info
99
SignalUnknown
ID, signal number
100Reserved
15 (17)
Consilium
** Field 3, identity:
Identity
Comment
IN#
Indicator #, # = A to Z, (INA INZ corresponds to ID 1
- 26)
IND
Indicator 4 (# = D), master of the system
LPU
Log Processing Unit
R1A
First WT unit in the system
R1B
Second WT unit in the system
R1C
Third WT unit in the system
T2A
First BT unit in the system
T2B
Second BT unit in the system
T2C
Third BT unit in the system
T2D
Fourth BT unit in the system
LP1
First LPU in the system
LP2
Second LPU in the system
Field #
1
2
3
4
5
6
7
Field Type
Name
i.
ccc
Definition
Multiple units message
Message type
Unit ID
Note
PSALU?
1: Speed data
VD1: Log 1
VD2: Log 2
GP1: GPS
VD9: Simulated Log
Null field indicates no valid data
Null field indicates no valid data
Null field indicates no valid data
x.x
Longitudinal water speed WTL
x.x
Longitudinal ground speed BTL
x.x
Transversal ground speed BTT
hh
Checksum
Example: From log 2, WTL = 20.06, BTL = 21.07, BTT = null:
$PSALU,1,VD2,20.06,21.07,*
16 (17)
Consilium
3.2.6.2.
Field #
1
2
3
Field Type
Name
i.
ccc
4
5
x.x
x.x
6
7
Definition
Multiple units message
Message type
Unit ID
17 (17)
Note
PSALU?
2: Depth data
VD1: Log 1
VD2: Log 2
SD1: External echosounder
VD9: Simulated Log
Null field indicates out of range
Consilium
SAL T-series
Menu System
Article No. 703258
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
Revisions
Date
2001-11-23
2002-04-04
2002-04-10
2002-09-06
2002-10-16
Version
A00
A01
A02
B0
B1
2003-04-22
2004-05-26
2004-10-13
2008-02-13
2008-09-12
B2
B3
B4
C0
C1
1.
Author
STE
STE
STE
STE
STE/RB
Comment
Created from TP00050
Update
Menu corrections
Menu for max depth and T1 added
SAL T1 option clarified, unused menus removed/
Changed name to SAL T-series
STE/JKW
Updated menus for T2/860T software release A4
JKW
Updated menus for T2/T3 software release A5
OM
Corrections
AF/RB/STE Menus A-, F-, S3, T4, V- and Alert messages added.
OM/STE
Corrections, update for software release B2
Background
This document gives a brief overview of the SAL T-series menu system
and use. The menus correspond to software release 702275 Rev: B2.
2.
Jumper settings
2 (23)
Consilium
3.
4.
Menu system
The menu system, controlled via a remote indicator i.e. the Speed Log
Master Display SD4-x, enables controls and user interaction of the SAL
T-series log. The communication commands are described below. Keys
available are MENU, ENTER, + and -.
Explanation
Sensed longitudinal speed in knots from transducer.
Field is --.-- if no valid speed is available.
Sensed transversal speed in knots from transducer.
Field is --.-- if no valid speed is available.
Sensed depth below transducer.
Field is --.-- if no valid depth is available.
Sensed signal strength in dB from transducer.
Field is --.-- if no valid signal is available.
3 (23)
Consilium
4.2.1.
KEY combination
Explanation
MENU
MENU +
Same as MENU
MENU -
MENU ENTER
ENTER
+
Menu walk
The keys above can change the current position in the menu tree. Pressing
"Menu" steps to the next menu on the same level. Pressing "Enter" goes
down one level, or if at the lowest level saves current value in nonvolatile memory. Pressing "plus" or "minus" changes the content for the
current menu.
Example to go from Normal operation to menu M2:
press MENU five times followed by ENTER once, then MENU once more.
ENTER
MENU
MENU
ENTER
MENU-
Normal
A0
C0
D0
F0
M0
P0
S0
T0
V0
A1
C1
D1
F1
M1
P1
S1
T1
V1
4 (23)
Consilium
Access
Level
MM
A0
Name
(NORMAL
OPERATION)
All Users
Default
Range / info
Function
speed info
presented
ALERT LIST
5 (23)
Consilium
A210
All Users
BT: Phase
Roll
A220
All Users
BT: Sig
Balance
A230
All Users
BT:
Transmitter
A201
All Users
BT: Alert
Test
C0
C1
All Users
All Users
CALIBRATION
BT Speed Cal
+0.00%
(-50% to
+50%)
C2
All Users
BT angle Cal
+0.0deg
(180.0 to
+180.0deg)
D0
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
DEBUG
D1
D2
D4
F0
F1
Data Logging
NORMAL COND/
UNACKED ALR/
ACKNOWL ALR
NORMAL COND/
UNACKED ALR/
ACKNOWL ALR
NORMAL COND/
UNACKED ALR/
ACKNOWL ALR
NORMAL COND/
UNACKED ALR/
ACKNOWL ALR
Disabled
Watersampling Disabled
BT86Corr
BT corr method
Magnit.
Force Testing
Force Alert
Disabled
M1
Authorised
Expert
All Users
All Users
Disabled ForceTrack,
SeekRange =
0..5
Force Ph-Roll Disabled
MISCELLANEOUS
EepromRestore Disabled (Not stored)
M2
All Users
CPU Reset
M4
M5
M6
All Users
All Users
All Users
M7
All Users
Access Level
P0
Authorised
Expert
Authorised
Expert
PARAMETERS
F2
F3
M0
P1
Force Depth
Transmitter
power
All
Users
0..3
6 (23)
Consilium
P2
Authorised
Expert
Receiver gain 0
0..5
P3
Depth seek
corr limit
0.955
0 .. 1.000
DepthSeek
gradient
5.01e-5
Depth track
prop const
300
Depth track
deriv const
75
DepthTrack
StepCorr StepCorr
DepthTrack function
Depth track
timout
0.0
BT s/n ratio
+14.0dB
S0
S1
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
Authorised
Expert
All Users
All Users
S2
All Users
P4
P5
P6
P7
P8
P9
PA
PB
PC
PD
PE
PF
PG
PH
PI
PJ
PK
BTT2AlgoLimit 0.95
Bottomtrack
filter
2.00s
Corraverage
Dist=
10.00m
Zero speed
threshold
0.0800
2-dim
adaptation
100
2-dim
threshold
300
2-dim algo
Echo noise
limit
+3.0dB
86x feedback
150
2-Dim Thres
AccThres
3000
Max Depth
Limit
400m
SETTINGS
PSALX
telegram
PSALw
Enabled
Disabled
7 (23)
Consilium
S3
All Users
S4
All Users
S6
All Users
S7
S9
All Users
All Users
Sa
All Users
T0
T1
All Users
All Users
T2
All Users
T3
All Users
T4
All Users
V0
V1
All Users
All Users
V2
All Users
V3
All Users
V4
All Users
V5
All Users
V6
All Users
V7
All Users
V8
All Users
V9
All Users
VA
All Users
VB
All Users
VC
All Users
VD
All Users
VE
All Users
telegram
ALERT telegrm Enabled
8 (23)
Consilium
VF
All Users
SER-3
ERRORS
VG
All Users
DPT-TRK Fails
VH
All Users
T2T
VI
All Users
PHA
0x00000000 0xFFFFFFFF
0x00000000 0xFFFFFFFF
0x00000000 0xFFFFFFFF
-99.9 to
99.9
Failures
9 (23)
Consilium
4.2.5.4.
Menu A201 BT: Alert Test
This menu shows status of the test alert (activated from menu F1: forced
alert test). If the alert is unacknowledged it can be acknowledged by
pressing ENTER.
A201 NORMAL COND
BT: ALERT TEST
4.2.6. Menu C0 Calibration
The calibration menus are used to change calibration parameters for SAL
T-series log. Ordinary users may use all menus. Press "+" or "-" to select
write access on or off, ENTER to go into calibration sub menus.
C0 CALIBRATION
WRITE ACCESS OFF
4.2.6.1.
Menu C1 BT speed calibration
The bottomtrack transducer speed (magnitude) calibration is set with this
menu. Press "+" or "-" to change the calibration value to correspond to the
result of the mile run. Save value by pressing ENTER.
C1 BT Speed
Calibrat:RR.RR%
4.2.6.2.
Menu C2 BT angular calibration
The bottomtrack transducer angular calibration is set with this menu.
Press "+" or "-" to change the calibration value to correspond to the result
of the mile run. Save value by pressing ENTER.
C2 BT Angular
Calibrat:RRR.R
4.2.7. Menu D0 DEBUG menus
Only authorised service personnel are allowed to use these menus. The
menus change internals in the SAL T-series log. Press "+" or "-" to select
write or read-only access, ENTER to go into settings sub menus.
D0 DEBUG
WRITE ACCESS OFF
4.2.7.1.
Menu D1 Data Logging
The debug data logging messages may be activated by this menu. Press
"+" or "-" to select. Save selected value by pressing ENTER.
D1 Data Logging
Disabled
4.2.7.2.
Menu D2 Water Sampling
Extra signal sampling for diagnostics purpose may be set with this menu.
Press "+" or "-" to select. Save selected value by pressing ENTER.
10 (23)
Consilium
D2 WATERSAMPLING
Disabled
4.2.7.3.
Menu D4 BT86Corr
The BT correlation algorithm may be set with this menu. Press "+" or "-"
to change the value. Save selected value by pressing ENTER.
D4 BT86Corr
Magnitude
4.2.8. Menu F0 Forced testing menus
Only instructed service personnel are allowed to use these menus. Some
menus forces test mode where no normal speed is calculated in the SAL
T-series log. Press "+" or "-" to select write or read-only access, ENTER
to go into settings sub menus.
F0 FORCE TESTING
WRITE ACCESS OFF
4.2.8.1.
Menu F1 Force Alert
This menu is used to activate the test alert message:
$VDALR,,201,A,V,BT: Alert Test*11 on main serial output.
NOTE: Press "+" and ENTER to enable the alert, "-" and ENTER to
disable.
F1 FORCE ALERT
DISABLED
4.2.8.2.
Menu F2 Force Depth
WARNING: the log stops to operate when this mode is active. This menu
forces the SAL T-series log to an unconditional depth track or depth seek
mode where the depth range can be set from 0 to 5.
F2 FORCE Depth
DISABLED
Press + or - to select simulated tracking or seek modes shown in the
examples below. Enter the mode by pressing ENTER. Exit this mode by
pressing MENU, MENU +, MENU - or MENU+ENTER.
F2 FORCE Depth
SIMULATETRACKING
Press ENTER to activate the forced simulated depth tracking. The display
will show fields corresponding to normal depth tracking with the
difference that the first two characters are F2
The depth range can be chosen from 0 to 5 corresponding to the
predefined seek ranges.
F2 FORCE Depth
RANGE=0
11 (23)
Consilium
Press ENTER to activate the chosen selection. Each depth range will be
displayed by sub menu F2.0 to F2.5 respectively with the following field
descriptors:
F2.n Axy Qqq.qq
DS ddd.ddSsss.s
The definition for the field descriptors is found in the table below.
Descriptor
Explanation
Depth range 0 to 5
TAS (Transmitter Amplification): 4 to 7
Echo quality
Used for testing purposes only and not available in all
modes.
Sensed depth below transducer.
Field is --.-- if no echo is available.
Sensed signal strength in dB from transducer.
Field is --.-- if no valid signal is available.
qq.qq / --.--
4.2.8.3.
Menu F3 Force Phase Roll Test
WARNING: the log stops to operate when in this mode. This menu sets
the SAL T-series log to a repeated phase roll measurement, where the
phase roll measurement between transmitter and receiver for all five
channels can be inspected. NOTE: A TXT sentence is transmitted on the
serial output port with the total and incremental phase roll values.
Testing starts when the + followed by ENTER is pressed.
NOTE: Once enabled this mode continues until leaving menu F3. The log
shall be forced into reset after testing to ensure normal conditions again.
F3 Force PH-Roll
Disabled
The result of the test is displayed at regular updates. NOTE: Only values
below 100 Hz are shown. Values beyond 100 Hz are indicated as ++.+,
and --.- respectively.
F3 PHA
x.x
x.x
x.x
x.x
x.x
12 (23)
Consilium
4.2.9.1.
Menu M1 Restore EEPROM to default values
This menu restores the settings for all parameters of the EEPROM to
default values. WARNING: activating this menu erases all calibration
data and user specific settings. Press + to enable.
M1 EEPROMRestore
Disabled
Press ENTER to activate:
M1 EEPROMRestore
Enabled
Successful restore is presented as:
M1 EEPROMRestore
SETTINGSRESTORED
and unsuccessful restore is presented as:
M1 EEPROMRestore
ERROR IN RESTORE
4.2.9.2.
Menu M2 CPU RESET
By activating this menu the retriggering of the watchdog circuitry is
inhibited, and thus a timeout forces the SAL T-series log to reset.
M2 CPU Reset
Disabled
Press + to enable.
M2 CPU Reset
Enabled
Press ENTER to activate. As the menu system is only seen on a remote
display, communication is lost.
4.2.9.3.
Menu M4 BT Total distance
This menu shows the total (BTR) distance for bottom track log. Press "+"
or "-" to change the distance value. Save value by pressing ENTER.
M4 BT TOTAL DIST
DIST=RRRRR.RRNM
4.2.9.4.
Menu M5 BT Trip distance
This menu shows the total distance for bottom track log. Press ENTER to
reset the distance to zero.
M4 BT TRIP DIST
DIST=RRRRR.RRNM
13 (23)
Consilium
4.2.9.5.
Menu M6 SW Revision
See the software revision of the application code.
M4 SW revision
Rev 702275XX
4.2.9.6.
Menu M7 Access Level
Change access level for some first level menus. First step to the menu by
pressing "Menu". Press "+" or "-" to select access level. Save value by
pressing ENTER.
M5 Access Level
All Users
NOTE: For All Users some first level menus are locked.
Or
M5 Access Level
AuthorisedExpert
NOTE: For Authorised Expert no menus are locked. The Authorised
Expert access level shall only be used by instructed service personnel.
4.2.10.
14 (23)
Consilium
15 (23)
Consilium
16 (23)
Consilium
PE 2-Dimensional
Adapt= NNN
4.2.10.15. Menu Pf 2-dim threshold
The 2-dimensional LMS filter adaptation threshold for slower adaptation
is set with this menu. First step to the menu by pressing "MENU". Press
"+" or "-" to change the value. Save value by pressing ENTER.
PF 2-Dimensional
DualThres=NNNN
4.2.10.16. Menu Pg 2-dim algorithm mode
The 2-dimensional algorithm mode is set with this menu. First step to the
menu by pressing "MENU". Press "+" or "-" to change the value. Save
value by pressing ENTER. Value "0" is normal operation. Other values is
for test only.
PG 2-D Algorithm
Mode=NN
4.2.10.17. Menu Ph Echo noise limit
The echo check noise limit is set with this menu. First step to the menu by
pressing "MENU". Press "+" or "-" to change the value. Save value by
pressing ENTER.
PH Echo noise
Limit=RR.R dB
4.2.10.18. Menu Pi 86x feedback gain
The 86x feedback gain is set with this menu. First step to the menu by
pressing "MENU". Press "+" or "-" to change the value. Save value by
pressing ENTER.
PI 86x feedback
Gain=NNN
4.2.10.19. Menu Pj 2-Dimensional Accor Threshold
The 2-dimensional accor threshold is set with this menu. First step to the
menu by pressing "MENU". Press "+" or "-" to change the value. Save
value by pressing ENTER.
PJ 2-Dimensional
AccThres=NNNN
4.2.10.20. Menu Pk Maximum depth
The maximum depth is set with this menu. First step to the menu by
pressing "MENU". Press "+" or "-" to change the value. Save value by
pressing ENTER.
PK Maximum Depth
Limit=NNNN m
17 (23)
Consilium
4.2.11.
18 (23)
Consilium
19 (23)
Consilium
Press "+" or "-" to adjust the speed momentarily, ENTER to save current
simulated speed value.
T2 Simulation
BTTrans=RR.RRKN
4.2.12.3. Menu T3 Depth simulation
WARNING: the log stops to operate when in this mode. This menu sets
SAL T-series log in speed and depth simulation mode and the output
stream contains NMEA messages with the depth set to the value on the
display. NOTE: Simulation starts when the menu is accessed. Press "+" or
"-" to adjust the depth momentarily, ENTER to save current simulated
depth value.
T3 Simulation
Depth=RRR.RR m
4.2.12.4. Menu T4 Simulation with invalid status
WARNING: the log stops to operate when in this mode. This menu sets
SAL T-series log in speed and depth simulation mode and the output
stream contains NMEA messages with the depth and speed set to invalid..
T4 Simulation
D=-- BT=-4.2.13.
20 (23)
Consilium
21 (23)
Consilium
22 (23)
Consilium
23 (23)
Consilium
SAL WTU
Operating Menus
Article No. 702314
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
Contents:
1
Revisions:
Date
2003-04-24
2003-10-15
2004-05-26
Version
A0
A1
A2
Author
STE
JKW/OM
JKW
2005-01-19
B0
JKW
2005-05-24
B1
JKW
2005-10-26
B2
JL
2007-04-26
B3
JL
2007-08-13
2009-01-22
B4
B5
JL
JL
2009-02-05
B6
JL
Comment
Created from 701860D0
Update according to 701860D1
Updated to fit sw 700210b1, approved: JL, OM;
SGU
Correspond to software 700210C0 and later.
Some of the menu is hidden for a normal user.
Updated chapter 3.3.5.3 Menu C3 Multiple
point Calibration to fit the software 700210C0
and later
Added new menu C5 Calibr. RESET for sw
700210D3 and later.
Applies for software 700210D6 and later.
Added new menus M7 and M8 for firmware and
hardware revision. Access level menu is now
M9.
Updated with V-menus in software 700210D7
Updated description to conform to software
700210E1 menus. Editorial changes.
Menu S7, S8 and Sb removed to conform to
actual software.
2 (19)
Consilium
1 Menu system
The menu system is controlled through a serial interface connected to a remote display. The
information is presented as two lines with 16 characters. All settings, calibration etc. is
changed through the menu system. Seven key combinations are used:
These keys are used to go to the next menu within the menu
level. Each time the key is pressed, the displayed menu
number is incremented and the next menu is presented.
This key is used to go to the previous menu within the menu
MENU
level. Each time the key is pressed, the menu number
displayed is decreased and the previous menu is presented.
MENU ENTER: This key is used to go up one menu level.
This key is used to step down one level in the menu system.
ENTER:
It is also used to accept and save the setting(s) on the lowest
menu level.
This key is used to increment the chosen value or setting.
+ (Plus)
This key is used to decrement the chosen value or setting.
(Minus)
MENU
MENU +
Please note that both the plus and minus keys can be used to toggle between ON and OFF in
some menus.
If no keys are pressed within 30 seconds, the menu system times out to the normal operation
menu. The only exceptions to this are the test menus and menus Pm, Pn, Pu & Pv.
3 User interface
The log starts up and measures speed on its own. The log enters the menu system when a
remote login is made through the serial interface. The information readout depends on mode,
and is described below.
3.1 Initialisation
In the initialisation sequence the software verifies the checksum of the code. This can be seen
on the serial output from the WTU. Timers and hardware is then set-up for normal operation.
The software version can be seen on the serial output from the WTU.
3 (19)
Consilium
3.2
Normal operation
The log in normal operation calculates the speed from the sensor signals. The log also
measures signal level from the transducer. The remote display readout uses the following field
descriptors:
MMHXX.XX YY.YY
FC=DDD ZZZZ:TTTT
If no valid speed is found the log enters search modes where XX.XX and S=DDDD share the
same position.
The definition for the field descriptors is found in the table below.
Descriptor
Explanation
MM
H
Working mode
Hardware mode
C = Clear water
D = Dirty water
Q = Extra dirty water
Sensed (raw) speed from transducer
Output speed including calibration and time constant averaging.
Field is . if no valid speed is available.
Digital Filter setting. 'F' equals digital filter pre-processing of sample
data, 'R' equals raw sampling, 'L' equals limiter + digital filter.
Normalised correlation coefficient between 0..999, higher coefficient
is better
Normalised signal quality value between 0..999, higher value is
better
first/second channel AGC level [mV]
first/second channel ADConvert levels [bits], see menus D4 & T6
XX.XX
YY.YY / --.-F
C=DDD
S=DDD
ZZZZ:TTTT
UUuu-VVvv
4 (19)
Consilium
5 (19)
Consilium
When using the menu system the following keys are available:
KEY combination
Explanation
MENU
MENU+
Same as MENU
MENU-
MENU ENTER
ENTER
+
EN T ER
M EN U
EN TE R
M EN U -
N o rm a l
C0
D0
M0
P0
S0
T0
V0
C1
D1
M1
P1
S1
T1
V1
6 (19)
Consilium
Default
MM
FE
C0
C1
(NORMAL
OPERATION)
FATAL ERROR
CALIBRATION
Draught Cond
C2
C3
C4
C5
M0
M2
M4
M5
M6
M7
M8
M9
Draught Cal
MultiPointCal
TRU Calibrat
TRU Calibrat
MISCELLANEOUS
CPU Reset
Total Distance
Trip Distance
SW revision
FW revision
HW revision
Access level
S0
S1
S2
S3
S4
S5
S6
S9
Sa
SETTINGS
Average Low
Thres Low-Hi
Average High
Max Ahead
Max Astern
Lock Timeout
VBW format
VHW Telegram
Function
7 (19)
Consilium
No Name
Default
Sc
Analog Speed
Ahead +
Astern
T0
T1
TEST
Simulation
T3
T4
Ta
V0
V1
V2
TRU Passive
TRU Active
LogFail Alarm
VIEW
System Uptime
Speed/no speed
measuring time
Mode
Transitions
Mode dependent
correlation
Speed dependent
correlation
V3
V4
V5
8.00
Function
8 (19)
Consilium
C2 Draught Cal
Ballast1 RR.RR%
9 (19)
Consilium
10 (19)
Consilium
11 (19)
Consilium
12 (19)
Consilium
13 (19)
Consilium
14 (19)
Consilium
If signal levels are (too) low (and the transducer may be damaged or not connected) as:
T3 TRU SIGNAL
LEVELS LOW
15 (19)
Consilium
V1 C-Mode Uptime
00d:00h:00m:00s
V1 D-Mode Uptime
00d:00h:00m:00s
V1 Q-Mode Uptime
00d:00h:00m:00s
16 (19)
Consilium
17 (19)
Consilium
V5 CORR AT SPEED
0
9-12
V5 CORR AT SPEED
0
12-15
V5 CORR AT SPEED
0
15-18
V5 CORR AT SPEED
0
18-21
V5 CORR AT SPEED
0
21-24
V5 CORR AT SPEED
0
24-27
V5 CORR AT SPEED
0
27-30
V5 CORR AT SPEED
0
30-33
V5 CORR AT SPEED
0
33-36
V5 CORR AT SPEED
0
36 +
18 (19)
Consilium
4 Fatal errors
If the log encounters a fatal error condition, it stops normal execution, send a $VDTXT serial
message and displays a fatal error on the display. The second line is reserved for the error
description. The log will enter reset within a two-second timeout.
FE FATAL ERROR
ERRORCODE-------
Explanation
NMEALIB Err
SERIO? Error
Serial io error
Overrun Error
Serial io error
SAMPLING OVERRUN
EEPROM FAIL
19 (19)
Consilium
SAL
T-Series
Harbour Acceptance
Test
Article No. 703254
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
Scope
2.
Equipment needed
3.
4.
5.
6.
7.
Final inspection
8.
Protocol
Revisions:
Date
2002-04-04
2002-07-10
2002-10-31
2004-01-16
2005-10-31
2008-02-12
2010-05-21
Ver
A0
A1
A2
A3
B0
D0
D1
Iss by
JXA
STE
HW
OM
OM
RB
OM
Description
Created from 702906A1
Updated BT test
Cable to be checked for damages
Change from 860 to T-series
Change to T2M with internal BT transmitter
Adapted to LPU2
Company name, deleted LCD on WTU, BT/WTSTW/SOG
2 (10)
Consilium
1.
Scope
This document describes the Harbour Acceptance Test (HAT) for SAL T-series speed
log. The HAT for SAL T-series tests the electronics unit (ELC), the transducer (TRU),
the optional Log Processing Unit (LPU2) and their interaction. The ELC contains a
Water Track SAL WTU PCB unit (which measures speed through the water) and a SAL
T2 BTU Bottom Track PCB unit (which measures speed over the ground). This
document contains a list of equipment needed, test procedures and a prepared test
protocol.
2.
Equipment needed
In addition to the ELC and TRU under test, the following equipment is needed:
Calibrated DMM for measurement of VAC, VDC, ohm and frequency.
This HAT instruction, including an additional copy of the protocol pages.
NMEA test equipment for monitoring the serial NMEA 0183 communication (such
as terminal-emulating PC).
Technical Document 700164 for NMEA message description.
3.
4.
Consilium
Test the EEPROM by entering a new value in the speed simulation menu. Press
MENU six times until LCD presents "T0 TEST WRITE ACCESS OFF". Press "+" to
have "T0 TEST WRITE ACCESS ON". Press "ENTER" to enter dummy speed
simulation. Press "+" once to get "T1 Simulation Speed = +8.01 KN". Press
"ENTER" to store value and wait for "SAVE OK" on second LCD line. Press "-"
once to get "T1 Simulation Speed = +8.00 KN". Press "ENTER" to restore default
value and wait for "SAVE OK" on second LCD line. Exit simulation mode by
simultaneously pressing "MENU" and "ENTER" twice.
5.
The test is divided into the following tests: first the Power Supply Unit (PSU) is tested,
then the PCB unit, and finally the whole Bottom Track system.
Refer to protocol on page 9!
Verify the serial number and revision of the SAL T-serie ELC unit.
Verify the serial number and revision of the T2M pcb.
Verify main transformer primary connection according to ships power supply,
230VAC or 115VAC
Verify backup transformer primary connection if the ELC is equipped with two
transformers.
Check mains supply voltage and if applicable the backup supply.
Check mains supply frequency and if applicable the backup supply.
Connect terminal emulating software to the NMEA output.
Check T2F regulated voltages.
Connect mains supply voltage.
If the ELC is equipped with two transformers, connect backup power supply.
Watch the serial messages of the T2R during the start-up sequence and verify the SW
version.
6.
Consilium
Set the SOG part of the speed log in speed simulation (menu T1
BTLONG=+08.0KN, menu T2 BTTRANS = +0.08KN and menu T3 DEPTH=
80.0M. Check that the correct values are displayed in the start menu of the LPU2.
Check that the NMEA-message has correct value and sign and corresponds with the
NMEA standard $VDVBW message as defined in Technical Document 700164.
Verify that all SD4 indicators and external users of LPU2 information receive the
simulated speed and depth (NMEA, pulse and analogue users).
Restore the SOG speed log to normal operation. If the depth below the hull is at least
2 metres, the SOG log shall lock to the depth. The STW log will start its ``scanning
sequence to search for a valid speed.
7.
Final inspection
When the ELC and TRU have passed all tests the protocol is signed with signature
and date on the summary page 6. One copy of the completed protocol (pp 610) shall
be returned to Consilium Marine & Safety for reference purpose.
5 (10)
Consilium
8.
Protocol
Order#:
Comment
S/N:
S/N:
S/N:
S/N:
S/N:
S/N:
S/N:
S/N:
S/N:
S/N:
Status:
Comments: ____________________________________________________________
____________________________________________________________
Passed
/ Failed
Date:
______________________
Sign: ________________________
(Consilium)
Date:
______________________
Sign: ________________________
(Customer, if applicable)
6 (10)
Consilium
Order#:
Comment
[ohm]
1=>2
4=>5
1=>3
4=>3
1=>4
Bottom track DC test
Resistance [ohm]
38=>39:
41=>42:
44=>45:
47=>48:
50=>51:
53=>54:
Cable check:
Status:
1.82.6 ohms
1.82.6 ohms
> 20 Mohms
> 20 Mohms
> 20 Mohms
Resistance to GND (Red)
[ohm]
37:
40:
43:
46:
49:
52:
GND (Blue):
Damages, Yes
38:
41:
44:
47:
50:
53:
7 (10)
/No
Cut, Yes
/No
Consilium
Order#:
U/N:
Boot:
Test result
Comment
S/N:
Flash:
SAVE OK
8 (10)
Consilium
Order#:
Comment
U/N:
S/N:
115VAC or 230VAC
L1-L2:
L1-L2:
Tol 47 .. 63 Hz
115VAC or 230VAC
L1-L2:
L1-L2:
Tol 47 .. 63 Hz
U/N:
P5-P10:
P4-P10:
P6-P10:
P8-P10:
P9-P10:
U/N:
S/N:
Tol: 4.85 .. 5.25VDC
Tol: 11.6 .. 12.4 VDC
Tol: -11.6 .. -12.4 VDC
Tol: 4.85 .. 5.25VDC
Tol: -4.85 .. -5.25VDC
S/N:
U/N:
S/N:
9 (10)
Consilium
10 (10)
Comment
S/N:
S/N:
S/N:
S/N:
Menu M8
Menu M9
According to user demand
Correct speed and depth on
LPU2 start menu
According to 700164
All users receive correct
values?
Consilium
SAL
T-series
Calibration and Sea
Acceptance Test
Article No. 703255
Consilium Marine & Safety AB P.O. Box 5021 SE-131 05 NACKA SWEDEN
Phone +46-(0)8-563 051 00 Fax +46-(0)8-563 051 99 E-mail: [email protected]
Consilium
SAL T-Series
Calibration and Sea Acceptance test. Main Electronics Unit (ELC), Transducer
(TRU) and optional Log Processing Unit 2nd generation (LPU2)
Contents
1.
Scope
2.
Equipment needed
3.
3.1.
3.4.
3.5.
4.
12
5.
Final inspection
12
6.
SAT protocol
13
7.
15
8.
16
2 (16)
Consilium
Revisions:
Date
2002-04-04
2002-08-19
2004-01-19
2005-05-18
Ver
A0
A1
A2
B0
Iss by
JXA
STE
OM
JKW
2008-02-12
2008-08-05
2010-05-21
D0
D1
D2
RB
OM
OM
Description
Created from 702907C3
updated BT procedure and protocols
Update to T-Series
Update to fit new input of calibration points for
WTU rev C0 or greater.
Deleted LPU and adapted to LPU2
T3+, set parameters in second T2R
BT/WT-SOG/STW, Company name
3 (16)
Consilium
1.
Scope
This document describes the Calibration procedures and also serves as a Sea Acceptance test (SAT)
for SAL T-Series speed log systems such as, SAL T2 and SAL T3 systems. The SAT for SAL TSeries is used to verify that the system works, and to calibrate the log. The document contains a list of
equipment needed, how to perform the test and a test protocol.
To aid future customer support, it is necessary that two sets of the protocol pages are filled-in. One set
should be returned to Consilium Marine & Safety AB, Navigation division, After Sales Department
and the other set should be left in the reference manual on board the ship.
2.
Equipment needed
3.
Ensure that the bottom track log locks on bottom within measurement range and indicate speed.
Consilium
To align the transducer represents an even harder problem in finding accurate enough reference
systems. In some installations, where two axis speed is fed to an integrated navigation system together
with accurate gyro data, the two-dimensional dead reckoning performed by the navigation computer
can be directly compared with other position data and the angular error produced by the log can be
calculated directly or indirectly.
For most installations. however, this is not possible, and the following procedure is proposed:
a) Place the ship on a straight course directly against current and wind so that the true transversal
motion of the ship is zero.
b) Read the transversal speed output of the log as the same time as the transducer is accessible (the
transversal speed can for instance be read on an NMEA output of the Log Electronics Unit).
c) Trim the transducer angle until the transversal speed reading fluctuations are centred around zero.
(this is described in the section Installation of transducer and bottom parts.)
Where it is necessary to perform a software calibration of the transducer angle, some reference system
to establish the desired correction angle must be used. The accuracy of this system must be verified.
The following formula can be used:
NEW = OLD + measured - reference ,
where reference is the direction of movement (referenced to the keel line) obtained from the reference
system and measured is the same direction obtained from the log during the trial run. The angular
values for both reference system and log output can be found using the relationship:
= arctan (Dt / Dl),
where Dt is the transversal distance (or speed) component and Dl is the longitudinal component.
The angular correction entered on the thumbwheel switches are represented in 0.1 steps, using
menu C2 in SAL T2.
Consilium
6 (16)
Consilium
Ships hull
Ships
Speed
0
Outside boundary layer
(Relative water speed = U)
TRU calibration - a fix calibration factor (marked on the TRU and the TRU-cable)
compensating small differences in characteristics of individual transducers. To be set at the
speed log set-up at installation and when changing TRU only.
Draught calibration a single point calibration factor compensating differences in indicated
speed, due to load and trim of the ship. Three different preset draught conditions can be
programmed. They are named: FULL LOAD, BALLAST 1 and BALLAST 2.
Speed depending calibration - multiple point calibration factors compensating differences in
indicated speed over the whole speed range. Factors can be preset for up to ten different
speeds. Speeds between the calibrated points are interpolated automatically.
7 (16)
Consilium
Note: The minimum necessary calibrations to be set are the TRU-calibration plus at least one of the
draught calibrations. If so, after setting the TRU-calibration, chose e.g. FULL LOAD and compensate
for the normal cruising speed used at normal load conditions (se below)
Draught Calibration and Speed Depending Calibration shall normally not be used at the same time.
3.5.1.
TRU Calibration
Change the value by using the +/- buttons and then save the value by pressing Enter.
Leave the WTU menu and the Menu System and return to the normal Trip/Total mode by pressing
ESC three times.
3.5.2.
This type of calibration is meant for merchant vessels where the water flow around the hull is
changing due to different draughts and trims. Three calibrations can be performed for cruising speeds
relevant to each of three decided draught/load conditions (FULL LOAD or BALLAST 1 or BALLAST
2). These calibrations are compensating with the same calibration percentage, respectively, over the
whole speed register.
Changing between the three draught/load calibration types can then be done later in menu R0-C1 by
pressing plus (+) or minus (-) without changing the write access in menu C0. However the change
must be saved by pressing the ENTER button.
Before the calibration runs, make sure:
that correct TRU-calibration factor is set (see above)
that the desired draught condition is chosen and set to 0% (Menus RO- C1 /C2)
the Multi Point Calibration is DISABLED (Menu RO- C3)
8 (16)
Consilium
The system is calibrated by sailing a true, known distance in calm waters. To eliminate variations
caused by tide, current and wind, the ship should run the same route in both directions. For each
separate run, carefully observe beginning and end of the true sailed distance and corresponding
measured distance on log display. Then, for each speed, do following calculation to find the
calibration factor CF:
CF=[(expected dist.1 + expected dist.2 ) / (measured dist.1 + measured dist.2)]
Normally the true distance is based on optical observations, but it is also possible to use other
reference systems like DGPS or similar. If the calibration factor is based on a very long (several hours
or days) comparison with GPS observations, make sure that it has not been affected by wind and
current.
Use the menu system to enter the calibration factor in menu RO- C2. Note that the correlation shall be
expressed in percentage. A calculated value of e.g. 1.234 shall be entered as 23.40%.
Procedure: (see 4.4 above for how to move in the menu system)
1. Go in to the Menu System, step to R0 REMOTE DEV and then down to WTU sub menu C0
C0 CALIBRATION
WRITE ACCESS OFF
2. chose WRITE ACCESS ON (+)
3. move down to menu C1 and check that desired alternative is chosen (see above)
C1 DRAUGHT COND
FULL LOAD 0,00%
4. move to C2 and press Enter
5. use + and to change to calculated value from the calibration runs (e.g. 23.40%)
C2 DRAUGHT CAL
FULL LOAD +23,40%
6. save by pressing enter
7. leave the WTU menu and the Menu System and return to the normal Trip/Total mode by
pressing ESC three times
Repeat the procedure (2-6) for each draught condition if desired.
9 (16)
Consilium
3.5.3.
This type of calibration is meant for vessels needing varying speed compensation in the whole speed
register. Up to ten different speeds can be calibrated for, spread to speeds both ahead and astern.
Speeds between the calibration points are interpolated automatically, except the area nearest zero,
which uses its nearest calibration factor down (up) to speed zero.
The Multiple Point Calibration can be ENABLED and DISABLED in menu R0-C3 without changing
the write access rights in Menu C0. However the change must be stored by pressing the ENTER
button.
Make the calibration runs and calculations as described above for Single Point Calibration, but now
repeat the procedure for each speed desired.
Before the calibration runs, make sure
that correct TRU-calibration factor is set (see above)
that the chosen draught condition (e.g. BALLAST 1) is set to 0% (Menus R0- C1 and C2)
that the Multi Point Calibration is DISABLED (Menu R0-C3)
Due to the interpolation between the compensation factors the Multi Point Calibration must be
DISABLED during all calibration runs, also when making a later run for an extra calibration point.
Procedure to set new multiple points: (see 4.4 above for how to move in the menu system)
1. Go in to the Menu System, step to R0 REMOTE DEV and then down to WTU sub menu C0
C0 CALIBRATION
WRITE ACCESS OFF
2. chose WRITE ACCESS ON (+)
3. move to menu C3 and change to ENABLED (+)
C3 MULTI-P CAL
ENABLED
4. move down (with Enter) to C3.01.
C3,01 MULTI-P 1
UNUSED POINT
C3.01 MULTI-P 1
10,0 KN 23,45 %
10 (16)
Consilium
7. use + and to set which speed to be calibrated for (expected) at that point (i.e. the speed used
at the calibration run).
C3.01 MULTI-P
EXPECTED 0.00 KN
8. save by pressing Enter
9. use + and to change the calculated calibration factor for that speed
C3.01 MULTI-P 1
10,0 KN 0,00 %
10. save by pressing Enter
11. change to next point by pressing Menu and repeat from 6.
12. leave the WTU menu and the Menu System and return to the normal Trip/Total mode by
pressing ESC three times
Repeat the procedure (2-6) for each draught condition if desired.
Procedure to delete multiple points: (see 4.4 above for how to move in the menu system)
1. Go in to the Menu System, step to R0 REMOTE DEV and then down to WTU sub menu C0
C0 CALIBRATION
WRITE ACCESS OFF
2. chose WRITE ACCESS ON (+)
3. move to menu C3 and change to DISABLED (-)
C3 MULTI-P CAL
DISABLED
4. move down (with Enter) to C3.01.
C3.01 MULTI-P 1
10,0 KN 23,45 %
5. if needed change to next point by pressing Menu
6. press Enter
C3,01 MULTI-P 1
DELETE POINT
7. press Enter for deleting point. Averaging speed constants
Note: These settings must not normally be changed. We recommend contacting Consilium Marine &
Safety AB, navigation division, for advices before changing default values.
11 (16)
Consilium
4.
It should also be noted that there are numerous settings to be done on the LPU2 in order to configure
outputs etc. This is described in the LPU2 manual section of this manual.
5.
Final inspection
When the system have passed all tests the protocol is signed with signature and date. One copy is
returned to Consilium Marine & Safety AB, navigation division, for reference purposes.
12 (16)
Consilium
6.
SAT protocol
Comment
LPU2 S/N:
S/N:
S/N:
(single point calibrations)
%
degrees
(BALLAST 1 ??.??)
(BALLAST 2 ??.??)
(FULL LOAD ??.??)
(TC=???)
Result:
Passed
/ Failed
Date:
______________________
Sign: ________________________
(Consilium)
Date:
______________________
Sign: ________________________
(Customer, if applicable)
13 (16)
Consilium
Comment
LPU2 S/N:
S/N:
S/N:
(single point calibrations)
%
degrees
(BALLAST 1 ??.??)
(BALLAST 2 ??.??)
(FULL LOAD ??.??)
(TC=???)
Result:
Passed
/ Failed
Date:
______________________
Sign: ________________________
(Consilium)
Date:
______________________
Sign: ________________________
(Customer, if applicable)
14 (16)
Consilium
7.
Sea Acceptance Test for SAL T-Series Multiple point calibration part
Order#:
SAL T-Series SAT
Comment
Owner:
Yard:
Ship:
Type:
TRU S/N:
ELC S/N:
LPU2 S/N:
Gyro S/N:
Indicators:
S/N:
S/N:
S/N:
S/N:
S/N:
Calibration
(Multi point calibrations)
BT magnitude calibr
%
BT Angle calibration
degrees
WT C3.01 Speed
% (??.??KN ?.??%)
WT C3.02 Speed
% (??.??KN ?.??%)
WT C3.03 Speed
% (??.??KN ?.??%)
WT C3.04 Speed
% (??.??KN ?.??%)
WT C3.05 Speed
% (??.??KN ?.??%)
WT C3.06 Speed
% (??.??KN ?.??%)
WT C3.07 Speed
% (??.??KN ?.??%)
WT C3.08 Speed
% (??.??KN ?.??%)
WT C3.09 Speed
% (??.??KN ?.??%)
WT C3.10 Speed
% (??.??KN ?.??%)
Result:
Passed
/ Failed
Date:
______________________
Sign: ________________________
(Consilium)
Date:
______________________
Sign: ________________________
(Customer, if applicable)
15 (16)
Consilium
8.
Sea Acceptance Test for SAL T-Series Multiple point calibration part
Order#:
SAL T-Series SAT
Comment
Owner:
Yard:
Ship:
Type:
TRU S/N:
ELC S/N:
LPU2 S/N:
Gyro S/N:
Indicators:
S/N:
S/N:
S/N:
S/N:
S/N:
Calibration
(Multi point calibrations)
BT magnitude calibr
%
BT Angle calibration
degrees
WT C3.01 Speed
% (??.??KN ?.??%)
WT C3.02 Speed
% (??.??KN ?.??%)
WT C3.03 Speed
% (??.??KN ?.??%)
WT C3.04 Speed
% (??.??KN ?.??%)
WT C3.05 Speed
% (??.??KN ?.??%)
WT C3.06 Speed
% (??.??KN ?.??%)
WT C3.07 Speed
% (??.??KN ?.??%)
WT C3.08 Speed
% (??.??KN ?.??%)
WT C3.09 Speed
% (??.??KN ?.??%)
WT C3.10 Speed
% (??.??KN ?.??%)
Result:
Passed
/ Failed
Date:
______________________
Sign: ________________________
(Consilium)
Date:
______________________
Sign: ________________________
(Customer, if applicable)
16 (16)