3 REB500 Transverse Currents

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

REB500 Protection System

How to avoid blocking of busbar


protection function due to
Transverse Currents

ABB Switzerland
CHPAU / NSS-2 / Milltown/ F1 / 01-05-17 /Jan Schutter

ABB

Substation Lay Out : Milltown, Ireland

ABB Switzerland
CHPAU / NSS-2 / Milltown/ F2 / 01-05-17 /Jan Schutter

ABB

Problem : BBP can block due to Transverse Currents


Short circuit at bus
Infeed Short Circuit

Isolators parallel
ABB Switzerland
CHPAU / NSS-2 / Milltown/ F3 / 01-05-17 /Jan Schutter

Directional criterion may block BBP

ABB

Solution : extended blocking function for bus tie breakers

Activate extended blocking


function for bus tie breakers
ABB Switzerland
CHPAU / NSS-2 / Milltown/ F4 / 01-05-17 /Jan Schutter

ABB

Solution : extended blocking function for bus tie breakers


Activate extended blocking function for bus tie breakers

(REBCON only)

ABB Switzerland
CHPAU / NSS-2 / Milltown/ F5 / 01-05-17 /Jan Schutter

ABB

Constraint : Less Selective

Not selective for these zones


ABB Switzerland
CHPAU / NSS-2 / Milltown/ F6 / 01-05-17 /Jan Schutter

ABB

Summary

Directional Criterion BBP does not block in


case of transverse current.

Substation is protected less selective


during Isolator parallel.

ABB Switzerland
CHPAU / NSS-2 / Milltown/ F7 / 01-05-17 /Jan Schutter

ABB