Ibc 2003
Ibc 2003
mineral wool
ERRATA TO THE
2003 INTERNATIONAL BUILDING CODE
Errata to the 3rd Printing
April 2004
*302.3.2: Exception, line 4 now reads ...the fire-resistance ratings in Table 302.3.2...
*Table 302.3.2: Note d now reads ...See Section 406.1.4.
*Table 307.7(1): Note n added in title.
*Table 307.7(1): Note e now reads ...e.Maximum allowable quantities shall be increased 100 percent
when stored in approved storage cabinets, gas cabinets, exhausted enclosures or safety cans as
specified in the International Fire Code. Where Note d also applies, the increase for both notes shall be
applied accumulatively.
*Table 307.7(1): Note m now reads ...m.For gallons of liquids, divide the amount in pounds by 10 in
accordance with Section 2703.1.2 of the International Fire Code.
*Table 307.7(1): Note n now reads ...n.For storage and display quantities in Group M and storage quantities
in Group S occupancies complying with Section 414.2.4, see Table 414.2.4.
*402.7.3: Exception, last line now reads ...complying with Section 705.
*410.3.1: Exception 1, last line now reads ...with Section 410.3.4.
*Section 414.1.2.2 now reads 414.1.2.1 Aerosols and 414.1.2.2 deleted.
*Table 414.2.4: Note i now reads ...i.The permitted quantities shall not be limited in a building equipped
throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
*LIQUID STORAGE ROOM, last line now reads ...liquids in a closed condition.
*Table 503: Group I-3, Type IIB now reads ...10,000
*Table 721.2.3(2): Title now reads ...COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR
ROOF SLABS (inches)
*907.2.13: Line 4 now reads ...be activated in accordance with Section 907.6.
1007.1: Exception 3, last line now reads ...in Section 1024.8.
1008.1.2: Exception 6 now reads ...Power-operated doors in accordance with Section 1008.1.3.2.
1016.4: now reads ...Air movement in corridors. Exit access corridors shall not serve as supply, return,
exhaust, relief or ventilation air ducts.
1021.3: Line 3 now reads ...smoke detector installed in accordance with Section 907.10.
1405.9.1 has been deleted.
1405.9.1.1: now reads ...1405.9.1 Interior adhered masonry veneers. Interior adhered masonry veneers
shall have a maximum weight of 20 psf (0.958 kg/m 2 ) and shall be installed in accordance with Section
1405.9. Where the interior adhered masonry veneer is supported by wood construction, the supporting
members shall be designed to limit deflection to 1/600 of the span of the supporting members.
*2110.1.1: Exception 1, line 4 now reads ...715 in fire barriers and fire partitions that have a...
*Table 2111.1: Row 2, column 3 now reads ...4-inch minimum thickness for hearth, 2-inch minimum
thickness for hearth extension.
*2211.1: Paragraph 2, line 2 now reads...A, B and C, in accordance with Section 1616, shall be ...
2211.2.2: Item 8, last line now reads ...by Table 2211.2(1).
Table 2211.2(2): Title now reads ...NOMINAL SHEAR VALUES FOR WIND AND SEISMIC FORCES IN
POUNDS PER FOOT FOR SHEAR WALLS FRAMED WITH COLD-FORMED STEEL STUDS AND
FACED WITH GYPSUM BOARD a,b
Table 2211.3: Table notes now read ...a. See Section 2211.3.2, item 2. b. See Section 2211.3.2, item 1.
2211.3.2: Line 3 now reads ...multiplied by the sum of the widths (3Li ) of the Type II shear...
2211.3.3: Line 1 now reads ...Anchorage and load path. Design of Type II shear wall...
2211.3.3.3: Line 3 now reads ...Section 2211.3.3.1, Type II shear wall bottom plates...
2211.3.3.4: Line 2 now reads ...each end of each Type II shear wall segment shall be...
*Table 2306.3.2: Note a, line 2 now reads ...above for nail size of actual grade, and (3) Multiply value by
the following adjustment factor = [1 - (0.5 - SG)], where SG = Specific gravity of the framing lumber.
*Table 2902.1: Title now reads ...MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES a
ERRATA TO THE
2003 INTERNATIONAL BUILDING CODE
(Errata Item added 8-12-04)
Figure 1609.6.2.2. Add legend to figure for Interior Zones, End Zones and Corner Zones as follows:
Page 1 of 1
909.5.2: Last 2 lines now read . . . Door openings shall be protected by fire door assemblies complying with
Section 715.3.3.
909.5.2: Exception 1, last line now reads . . . in accordance with Section 907.10.
909.20.2.1: Line 5 now reads . . . in accordance with Section 715.3.7.
909.20.3.1: Last line now reads . . . in accordance with Section 715.3.
909.20.3.2: Section references now read . . . Section 715.3.
909.20.4.1: Section references now read . . . Section 715.3.
Table 1004.1.2: Column 2, row 6 now reads . . . See Section 1004.7
1021.3: Last line now reads . . . with Section 907.10.
1203.1: Section reference now reads . . . Section 1203.4
1203.4.3: Section reference now reads . . . Section 1206
Table 1507.2: Column 2, row 10, line 2 now reads . . . (0.105 inch)
1604.6: Section reference now reads . . . Section 1713
1615.1.4: Equation 16-43, section reference in notation T now reads . . . (see Section 9.5.5.3 of ASCE 7).
1617.2.2.2: Reference to r in notation rmax now reads . . . ?
1617.6.1.1: Item 3, last line now reads . . . factor of 4.
1617.6.1: Add new subsection as follows:
1617.6.1.3 ASCE 7, Section 9.5.2.2.4.3 Modify Section 9.5.2.2.4.3 by changing exception to read
as follows:
Exception: Reinforced concrete frame members not designed as part of the seismic-forceresisting system and slabs shall comply with Section 21.11 of Ref. 9.9-1.
1622.1.3: ASCE 7, Section changed to 9.14.7.9 and section reference in 5th line now reads 9.1.3
1704.5: Last line of Section and Exception 1 now read . . . Table 1604.5 and Section 1617.2).
1704.5.2: Last line now reads . . . Table 1604.5 and Section 1617.2).
Table 1704.5.3: Column 5, row 12 now reads . . . Sec. 1.2.2(e), 2.1.4, 3.1.6
1805.9: paragraph 2, line 2 and last line of exception 2 now reads . . . provisions of ACI 318, Sections
21.10.1 to 21.10.3
1808.2.23.2: Line 6 now reads . . . Provisions of ACI 318, Section 21.10.4; Exception 2, last line now reads
. . .Section 21.10.4; Exception 3 now reads . . . Section 21.10.4.4(a) of ACI 318...
1910.4.1: Last line now reads . . . as modified by Section 1908.1.7.