2-8 Loop Fire Alarm Control Panel: Features
2-8 Loop Fire Alarm Control Panel: Features
Features
Robust, removable equipment
chassis with plug-in connectors for
simple fixing and cable termination.
Advanced graphical LCD user
interface with up to 1000 fire zones
as standard, allowing full EN54
compliance without additional
hardware or LED indication.
2 x 5 Amp power supply and charger
to EN54 part 4.
Dedicated RS232 serial port for
direct PC or modem connection.
Key Features
Fully Expandable
Fully Networkable
Multiple Languages
Dual microprocessor
Flash memory
Global Compliance
3 Year warranty
Specification
Base technology
Dual Flash based Processors with Real Time Clock, trace diagnostics, pulse communications & programmable
languages
Display
LED Indicators
3 red (2 x Fire, 1 x Alarm), 1 green (Power) & 12 amber (Fault & System)
Controls
Alpha numeric keypad, navigation keys & system keys for Reset, Mute, Silence/Resound & Evacuate
Protocols
Apollo (S90,XP95, Xplorer and Discovery), Hochiki ESP, Nittan Evolution & Argus Vega
1000
Number of loops
Loop Current
500mA
8 x 1 Amp programmable
On Board Relays
Auxiliary Supply
1 x 24v 500mA
8 x programmable
Mains supply
Battery Capacity
Charger Current
Serial ports
Programming
Event Log
Networking
Printer (Optional)
Enclosure / Colour
Cable Entry
Size H x W x D mm
950 x 450 x 188 / 23Kg. Back box only (when recessing) 950 x 450 x 173
Metalwork Options
Approvals
Mx-4807*:
Mx-4808*:
* Add /N:
* Add /V:
* Add /FT: