This document discusses reverse power protection for a turbine generator unit. It describes two settings for a reverse power relay (#1 and #2). For setting #1, the trip level is set to 0.3 times the no load loss of the turbine generator unit to prevent overspeeding during a turbine failure. The trip delay is set to 1 second. For setting #2, the trip level is set to 0.5 times the no load loss to protect against generator motoring. The trip delay is longer at 15 seconds to allow more time for motoring.
This document discusses reverse power protection for a turbine generator unit. It describes two settings for a reverse power relay (#1 and #2). For setting #1, the trip level is set to 0.3 times the no load loss of the turbine generator unit to prevent overspeeding during a turbine failure. The trip delay is set to 1 second. For setting #2, the trip level is set to 0.5 times the no load loss to protect against generator motoring. The trip delay is longer at 15 seconds to allow more time for motoring.
This document discusses reverse power protection for a turbine generator unit. It describes two settings for a reverse power relay (#1 and #2). For setting #1, the trip level is set to 0.3 times the no load loss of the turbine generator unit to prevent overspeeding during a turbine failure. The trip delay is set to 1 second. For setting #2, the trip level is set to 0.5 times the no load loss to protect against generator motoring. The trip delay is longer at 15 seconds to allow more time for motoring.
This document discusses reverse power protection for a turbine generator unit. It describes two settings for a reverse power relay (#1 and #2). For setting #1, the trip level is set to 0.3 times the no load loss of the turbine generator unit to prevent overspeeding during a turbine failure. The trip delay is set to 1 second. For setting #2, the trip level is set to 0.5 times the no load loss to protect against generator motoring. The trip delay is longer at 15 seconds to allow more time for motoring.
In case of Turbine Failure, the Turbine is tripped and then the Generator is tripped by operation of reverse power relay to prevent overspending of the Turbine generator unit.
2- Protection against generator motoring 32G (#2).
-Generator motoring protection is designed for the prime mover or the system, rather than for the generator.
- With steam turbines, Turbines will overheat on low steam
flow, motoring results from a low input To the Ac Generator, - When This I/P cant meet all the losses, the deficiency is supplied by absorbing real power from the system.
- since field excitation should remain the same , the same
reactive power would flow as before motoring , thus, on motoring the real power will be into the generator, while the reactive power may be either flowing out or into the generator
Setting of Reverse Power Relays
Data for setting calculations -Rated Capacity of Generator -------- 440,000 KVA -No Load Loss of Generator --------- 1,785 KW -No Load Loss of Turbine ---------- 1,350 KW -No Load Loss of TG unit ---------- 3,135 KW -Permissible Motoring Time ------- 60 Sec. -Relay Constant ------------------- 1 P.U. = Generator KVA
Setting Of Reveres Power Relay 32G ( #1 )
1- Reverse Power Trip Level Trip Level < No load loss of TG unit * 0.3 = 3,135 * 0.3 = 940.5 KW Pick up = Trip level / relay constant = 941 / 440,000 = 0.0021 P.U. Setting = - 0.002 P.U. ( 880KW )