620.9100 Huba Control
620.9100 Huba Control
Overpressure and
vacuum switch
625
Huba Control
FOR FINE PRESSURE AND FLOW MEASUREMENT
Technical overview Pressure ranges
See order code selection table Pressure connections
With their finely tuned range increments and Type 620
long-term switching point stability, overpressure Connection pipe 6 mm, inside thread M5,
and vacuum switches of type 620/25 are suita- Maximum overpressure thread M12x1 with counternut
ble for monitoring liquids and gases in Maximum overpressure and test pressure see
industrial equipment manufacturing applications setting ranges Type 625
in general, in process technology or in food Thread G 1/8, G 1/4, M12x1 with counternut.
automation.
Setting ranges See order code selection table. Other threads on
The rugged mechanics are the assurance of high
See graphic on the back request
operating reliability, even in the presence of
percussions or vibrations. A range of switches with
many standard versions and ideal price /perfor-
mance ratio, even in the case of small quantities. Lowest turn-on pressure Diaphragm
2 mbar A NBR-based C FPM
Switching point and switching difference E EPDM F Silicon
adjustable
Parts coming into contact with the medium, to
Smallest switching difference: 1 mbar base and diaphragm. Polyacetal and stainless
steel 1.4301 with vacuum switch version.
Repeatability
5% of the switching point of type A, F dia- Electrical connections
phragm material, but as a minimum 0.3 mbar Screw terminals (option), AMP tab connectors
6.3 mm, cable gland PG 11 with cover
10% of the switching point of type C, E dia-
phragm material, but as a minimum 0.6 mbar
Contact system
Changeover contact
Temperature range
Medium temperature with diaphragm type 625:
NBR-based 0 + 80 C Contact material / Loading
FPM - 10 + 80 C Nominal voltage,
EPDM - 10 + 80 C type of current 250 VAC 250 VAC
Q (Silicon) - 40 + 80 C Nominal current for
resistive loading 1A 6A
Ambient temperature T 65 Nominal voltage for
Legend to cross-section drawing motor loading 0.5 A 3A
Type 620 see order code selection table Contact material AgCdO AgCdO
1 Switching point setting
2 AMP tab connectors
3 Switching difference setting Case construction Type of protection
4 Compression spring Type series 620/25: Switch case fiberglass- Without cover IP 00
5 Changeover contact reinforced With cover (for installation arrangement
6 Contact element electrical connections upward) IP 54
7 Diaphragm Type series 620: Base ABS or PA
Plastic cover with Pg 11 on side Screw terminals Mounting bracket Type 620 with pressure case Type 625 with pressure case
AMP connector set ABS / PA alu/brass
Pressure 9
Vacuum 6
p max pt 2 Switching capacity 250 V
Pressure ranges1 (mbar) 2 8 30 50 1A 0
6 75 300 500 1A 1
12.5 80 300 500 6A 2
12.5 200 300 500 1A 3
25 220 300 500 6A 4
80 2000 6000 10 000 1A 5
120 2200 6000 10 000 6A 6
1000 6000 6000 10 000 6A 7
Accessories
25 220 mbar 80 2000 mbar 120 2200 mbar 1000 6000 mbar
A A A A
B B B B
A Upper switching point (mbar) B Distance between contacts 100 900 mbar
A
B
Type 620 Type 625
L
X X L
G 1/4 16
G 1/8 16
M 12 x 1 14 1 Common
2 NC contact
3 NO contact
For vacuum:
terminal 3 break contact
Technical data subject to change.