Preventive Maintenance: 5.1 Regular Checks
Preventive Maintenance: 5.1 Regular Checks
Chapter 5
Preventive Maintenance
However, in order to assure that all is well, then the following procedure shall be carried
out two or three times a year, (the engine must be STOPPED, and START BLOCKED
during this test):-
4) Check that the links between the EGS Actuator and the fuel
pumps have no sign of backlash. If a backlash in excess of 0,3
mm exists, the connection rods should be adjusted.
5) Open the EGS2000 Power Unit. Visually check that all cables
are sited properly. Close the Power Unit door.
960.200.561
EGS2000 version 4 - User Manual 5-2 of 2
5. Preventive Maintenance 2001.05.14
To carry out these tacho checks, the engine must be RUNNING , the vessel in SEA
CONDITION and the ACCESS code for either Privileged User or Lyngs Marine
technician inserted.
For details of MENU and ACCESS operations, see sections 3.3.3.1 and 4.1.3 in this
manual.
960.200.561