Strong Room Specifications
Strong Room Specifications
The specifications for strong room for branches are detailed hereunder:
I. THE SPECIFICATIONS FOR THE STRONG ROOM ARE AS FOLLOWS:
FLOOR:
CEILING - R C C 1:2:4
Reserve Bank of India has specified ceilings fortification only in cases where it
is not feasible to provide RCC slab of specified thickness.
If it is not possible to provide the strong room with the ceiling of prescribed
thickness of 30 cms (12) or provide fabrication with MS grills, RBI would be
prepared to consider relaxation of the existing specification on merits of
individual cases, provided the floor space directly above the strong room is also
in the possession and occupation of the Bank.
12 mm dia mild Steel/tor steel @ 6c/c both ways and on both faces of the wall
(a formation of reinforcement matt of about 6x 6) on either face of the wall
to be obtained.
The above reinforcements are only the minimum and depending on the
structural requirements, the structural consultants for the work, should design
and detail out actual reinforcements required but these shall not be less than
what are specified above.
Two columns of 10"x10" size with 6 nos of 12 mm dia TOR Steel main rods and
6 mm dia binder rods are to be done only after fixing the door and ascertaining
the plumb line.
When the strong room is divided into 2 portions for cash and lockers, two
ventilators for both the rooms are to be provided. The Air ventilator/s should
not be fixed on the exterior / outer walls.