Leaflet HRD2
Leaflet HRD2
Leaflet HRD2
EFFICIENCY
UP TO
+
86 %
Air quality is
the quality of life
The exhaust air is a precious source of energy available for free.
The HRD2 heat recovery unit uses this energy and turns it
into an interesting energy saving opportunity.
02.03
High efficiency, given for free
Exhaust air is a valuable source of energy, available at no cost.
Not using it means wasting important opportunities for energy
savings.Thanks to an innovative heat recovery system, HRD2 allows
you to extract the energy contained in the exhaust air and re-use it
to condition or heat the renewal air.
The new heat recovery unit is in line with the requirements of the
Eco-design legislation no. 1253/2014, and it features efficiency
levels that are always higher than those set by the laws.
Alternatively, the air flow can be dynamically modulated thanks to the CO2 probe:
according to the environmental requirements, HRD2 adjusts the fan speed in order
to handle the exact required flow, with great advantages in terms of energy
consumption reduction.
Construction details
The self-supporting HRD2 structure is characterized by top quality - Removable inspection openings and panels for easy access
features and details that ensure durability and easy maintenance: to internal components;
- Supporting feet for vertical versions;
- Self-supporting steel structure with 25mm double panels made - Longitudinal mounting brackets for horizontal versions;
of galvanized sheet metal internally and painted sheet externally; - Compact air filters made of synthetic material (outer layer),
- Thermal and acoustic insulation made of non-flammable mineral fiberglass (inner layer) and a galvanized steel frame. The filters
wool and additional insulation for the parts close to the heat are type F7 with a very low pressure drop on the external air
exchanger in order to avoid condensation even with extreme intake, and type M5 on the ambient air intake. Access to filters
outdoor temperature conditions; is facilitated by removable panels.
04.05
By-pass system with motorized damper
The by-pass system with motorized damper enables the use of the heating or cooling capacity (free cooling or free-heating) contained
in the outside air to ensure a further reduction of energy consumption. All of this for free, just by taking advantage of the favorable
conditions of the outside temperature.
considered. Here the heat recovery unit works from 8am to 8pm, -10
Results 80
The air-to-air heat recovery system of HRD2 shows an increase
Efficiency [%]
an air temperature of 18°C (air flow 600 m³/h). Air flow 600 m3/h Air flow 1230 m3/h Air flow 1600 m3/h
2
clear in the winter period when the efficiency of the solution with 1,5
only recovery reaches a value equal to 3.4*, three times higher than 1
Heat recovery system + electric heater Heat recovery system + battery Heat recovery unit only
HRD2
Heat recovery unit
from 430 to 3700 m3/h
PLATE CONTROLLER
VERSIONS
OR Horizontal installation, right air supply VR Vertical installation, right air supply
OL Horizontal installation, left air supply VL Vertical installation, left air supply
CONFIGURATIONS
- With pre-heating function
- With post-heating function
- With filter pressure switch
- With differential pressure sensor
Control
The control system consists of an electrical panel mounted on-board and a remote control with display
for the management of all functional parameters. Thanks to four probes installed on the four sides of the unit,
the ventilation is easily regulated according to the desired requirements.
06.07
Technical data
HRD2 050 090 140 210 300 410
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 400/3+N/50 400/3+N/50
Overall power input Nominal W 327 339 904 930 1841 1910
Overall power input Max W 340 340 920 930 2000 2000
Overall current input Nominal A 2,7 2,9 5,9 6 3,3 3,4
Overall current input Max A 2,8 2,9 6,0 6,0 3,4 3,5
Fan speed control V 0-10 0-10 0-10 0-10 0-10 0-10
PERFORMANCE
Air flow rate m3/h 426 776 1230 1843 2720 3685
Air flow rate m3/s 0,118 0,216 0,342 0,512 0,756 1,024
External static pressure (1) Pa 218 153 265 172 194 200
Return sound pressure level (2) dB(A) 53 52 53 60 62 60
Supply sound pressure level (2) dB(A) 61 60 61 68 70 68
Recovery efficiency (3) % 86,2 86,9 83,7 85,3 84,8 85,0
Recovery capacity (3) W 3684 6768 10333 15777 23157 31435
Supply temperature (3) °C 16,3 16,5 15,6 16,0 15,9 16,0
COMPLIANCE WITH (UE 1253/2014)
Recovery efficiency (4) % 79,2 76,1 76,5 76,6 76,1 76,0
Efficiency bonus W/m3/s 366 273 285 288 273 270
Filter correction factor - 0 0 0 0 0 0
SFP internal limit W/m3/s 1548 1441 1434 1411 1360 1316
Total internal air pressure drop (4) Pa 722 753 684 658 728 775
Overall fan static efficiency (5) % 46,7 55,8 47,8 47,1 57,5 58,9
SFP internal W/m3/s 1545 1350 1431 1396 1266 1315
SIZE AND WEIGHT
A (6) mm 1350 1470 1850 1850 2150 2150
B (6) mm 680 820 1030 1460 1460 1840
H (6) mm 330 370 455 455 590 590
Operating weight (6) kg 85 105 175 230 290 360
Notes:
1 Fresh air/supply air circuit
2 Sound pressure level in free field on a reflective surface, 1 m from fan front and 1 m from the ground
Non-binding value obtained fron sound power level H
3 Size valued in the following hypothesis at wet conditions: outside air temp. -7 °C 80% RH; room air temperature 20 °C; 55% RH
4 Size valued in the following hypothesis at dry conditions: outside air temperature 5 °C; room air temperature 25 °C
5 Including motor&speed controller efficiency
6 Unit in standard configuration/execution, without optional accessories A
B
Accessories
Head Office: Via Sarson 57/c - 36061 Bassano del Grappa (VI) - Italy
Tel (+39) 0424 509 500 - Fax (+39) 0424 509 509
www.climaveneta.com
www.melcohit.com