2017-11-06 Guideline 36 Draft 3
2017-11-06 Guideline 36 Draft 3
The appearance of any technical data or editorial material in this public review document does not constitute
endorsement, warranty, or guaranty by ASHRAE of any product, service, process, procedure, or design, and ASHRAE
expressly disclaims such.
© 2017 ASHRAE. This draft is covered under ASHRAE copyright. Permission to reproduce or redistribute all or any
part of this document must be obtained from the ASHRAE Manager of Standards, 1791 Tullie Circle, NE, Atlanta, GA
30329. Phone: 404-636-8400, Ext. 1125. Fax: 404-321-5478. E-mail: [email protected].
1. PURPOSE ................................................................................................................................... 1
2. SCOPE ........................................................................................................................................ 1
3. SETPOINTS, DESIGN & FIELD DETERMINED ................................................................... 1
3.1 Information Provided by Designer ................................................................................... 1
3.2 Information Provided by (or in Conjunction with) the Test & Balance Contractor ...... 15
4. LIST OF HARDWIRED POINTS............................................................................................ 18
4.1 VAV Terminal Unit – Cooling Only ............................................................................. 19
4.2 VAV Terminal Unit with Reheat ................................................................................... 19
4.3 Fan Powered Terminal Unit (Series or Parallel, Constant or Variable Speed Fan) ....... 20
4.4 Dual Duct Terminal Unit with Inlet Sensors .................................................................. 20
4.5 Dual Duct Terminal Unit with Discharge Sensor .......................................................... 21
4.6 Multiple Zone VAV Air Handling Unit ......................................................................... 21
4.7 Dual Fan Dual Duct Heating VAV Air Handling Unit .................................................. 23
4.8 Single Zone VAV Air Handling Unit ............................................................................ 24
5. SEQUENCES OF OPERATIONS ........................................................................................... 25
5.1 General ........................................................................................................................... 25
5.2 Generic Ventilation Zones ............................................................................................. 43
5.3 Generic Thermal Zones .................................................................................................. 52
5.4 Zone Groups ................................................................................................................... 57
5.5 VAV Terminal Unit, Cooling Only ............................................................................... 61
5.6 VAV Terminal Unit with Reheat ................................................................................... 64
5.7 Parallel Fan-Powered Terminal Unit, Constant Volume Fan ........................................ 69
5.8 Parallel Fan-Powered Terminal Unit, Variable Volume Fan ......................................... 74
5.9 Series Fan-Powered Terminal Unit, Constant Volume Fan ........................................... 80
5.10 Series Fan-Powered Terminal Unit, Variable Volume Fan ........................................... 84
5.11 Dual Duct VAV Terminal Unit – Snap Acting Control ................................................. 88
5.12 Dual Duct VAV Terminal Unit – Mixing Control with Inlet Airflow Sensors ............. 94
5.13 Dual Duct VAV Terminal Unit – Mixing Control with Discharge Airflow Sensor ...... 99
5.14 Dual Duct VAV Terminal Unit – Cold Duct Minimum Control ................................. 104
5.15 Air Handling Unit System Modes ................................................................................ 108
5.16 Multiple Zone VAV Air Handling Unit ....................................................................... 109
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page iii
5.17 Dual Fan Dual Duct Heating VAV Air Handling Unit ................................................ 143
5.18 Single Zone VAV Air Handling Unit .......................................................................... 149
6. CONTROL DIAGRAMS (INFORMATIVE APPENDIX) ................................................... 171
6.1 VAV Terminal Unit, Cooling Only ............................................................................. 171
6.2 VAV Terminal Unit with Reheat ................................................................................. 171
6.3 Parallel Fan-Powered Terminal Unit, Constant Volume Fan ...................................... 172
6.4 Parallel Fan-Powered Terminal Unit, Variable Volume Fan ....................................... 172
6.5 Series Fan-Powered Terminal Unit, Constant Volume Fan ......................................... 173
6.6 Series Fan-Powered Terminal Unit, Variable Volume Fan ......................................... 173
6.7 Dual Duct Terminal Unit with Inlet Sensors ................................................................ 174
6.8 Dual Duct Terminal Unit with Discharge Sensor ........................................................ 174
6.9 Multiple Zone VAV Air Handling Unit with Return Fan and OA Measurement Station
...................................................................................................................................... 175
6.10 Multiple Zone VAV Air Handling Unit with Relief Fan & Differential Pressure OA
Measurement ................................................................................................................ 176
6.11 Dual Fan Dual Duct Heating VAV Air Handling Unit ................................................ 177
6.12 Single Zone VAV Air Handling Unit (Return Fan Option) ......................................... 178
(This foreword is not part of this guideline. It is merely informative and does not contain
requirements necessary for conformance to the guideline.)
FOREWORD
This guideline is intended to establish a set of standardized advanced sequences of operation for
common HVAC systems. Standardized advanced control sequences will provide the following
benefits:
• Reduce engineering time for design engineers. Rather than develop sequences themselves,
they can adapt standard sequences that have been proven to perform.
• Reduce programming and commissioning time for contractors.
• Reduce energy consumption by making systems less dependent on proper implementation
and commissioning of control sequences.
• Reduce energy consumption by ensuring that proven, cost effective strategies, including
those required by ASHRAE standards and building codes, are fully implemented.
• Improve indoor air quality by ensuring control sequences are in compliance with IAQ
standards and codes such as ASHRAE Standard 62.1.
• Reduce energy consumption and reduce system down-time by including diagnostic
software to detect and diagnose system faults and make operators aware of them before
they cause performance problems.
• Provide a common language of terms which will facilitate communication between
specifiers, contractors, and operators
The intended audience include HVAC designers, control contractors, commissioning agents, and
building owners, operators, and maintenance technicians.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page iv
This initial version of the guideline is limited to variable air volume (VAV) systems. But it is
expected that sequences for other HVAC systems will be added over time. It is also expected that
the sequences herein will also be adjusted, augmented, and possibly replaced over time based on
feedback from users. The guideline is a living document that will be under continuous
maintenance.
This style (bold) provides direction to the editor of these sequences so that they are properly
implemented, e.g., identifying mutually exclusive options.
This style (italics) is intended to provide guidance or additional information about specific
sequences.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 1
1. PURPOSE
The purpose of this guideline is to provide uniform sequences of operation for heating, ventilating, and air-
conditioning (HVAC) systems that are intended to maximize HVAC system energy efficiency and
performance, provide control stability, and allow for real-time fault detection and diagnostics.
2. SCOPE
2.1 This guideline provides detailed sequences of operation for HVAC systems.
2.2 This guideline describes functional tests that when performed will confirm implementation of the
sequences of operation.
The design setpoints listed in this section must be scheduled in design documents for each
zone and air handler by the design engineer.
3.1.1. General Thermal Zone Information
Zone temperature initial setpoints can be specified by the designer in a number of ways.
The most flexible is to include them for each zone in VAV box and single zone VAV
(SZVAV) AHU equipment schedules. They can also be generically listed by zone type,
such as this example:
1. Default setpoints shall be based on zone type:
Occupied Unoccupied
Zone Type
Heating Cooling Heating Cooling
21°C 24°C 16°C 32°C
VAV
(70°F) (75°F) (60°F) (90°F)
18°C 29°C 18°C 29°C
Mech./Elec Rooms
(65°F) (85°F) (65°F) (85°F)
18°C 24°C 18°C 24°C
Networking/Computer
(65°F) (75°F) (65°F) (75°F)
Ventilation setpoints can be specified by the designer in a number of ways. The most
flexible is to include them for each zone in VAV box and SZ equipment schedules.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 2
The engineer must select between ventilation logic options:
If the project is to comply with California Title 24 ventilation requirements, keep subsection
“2” and delete subsection “1.”
If the project is to comply with Standard 62.1 ventilation requirements, keep subsection “1”
and delete subsection “2.”
1. For projects complying with the Ventilation Rate Procedure of ASHRAE Standard
62.1-2016:
This is the zone floor area times the outdoor airflow rate per unit area, as given in
Table 6.2.2.1 of Standard 62.1-2016
i.e., Vbz-A = Az * Ra
This is the zone design population (without diversity) times the outdoor airflow rate
per occupant, as given in Table 6.2.2.1 of Standard 62.1-2016
i.e., Vbz-P = Pz * Rp
Zone Air Distribution Effectiveness depends on the relative locations of supply and
return in the space, per Table 6.2.2.2 of ASHRAE Standard 62.1-2016.
a. Vocc-min: Zone minimum outdoor airflow for occupants, per Title 24 prescribed
airflow-per-occupant requirements.
b. Varea-min: Zone minimum outdoor airflow for building area, per Title 24
prescribed airflow-per-area requirements.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 3
3.1.1.3. CO2 Setpoints
Space CO2 setpoints are used for demand controlled ventilation (DCV) and
monitoring/alarming as required by LEED and other green building standards.
The CO2 setpoints in the table below are from the Lawrence article. They assume an
ambient concentration of 400 ppm, in lieu of using an ambient CO2 sensor. These
sequences are based on not having an ambient sensor. This will be conservative in areas
with high ambient CO2 concentrations; few areas have lower concentrations. The
Lawrence article was based on Standard 62.1-2007, but the outdoor air rates on which
these are based have not changed in the 2016 Standard.
Setpoints vary by occupancy type, so the easiest way to include this info is by including
a column in VAV box and SZ unit schedules and entering the setpoint individually for
each zone.
CO2 Setpoint CO2 Setpoint
Occupancy Category Occupancy Category
(ppm) (ppm)
Correctional Facilities Office Buildings
Cell 965 Office Space 894
Dayroom 1,656 Reception Areas 1,656
Guard Stations 1,200 Telephone/Data Entry 1,872
Booking/Waiting 1,200 Main Entry/Lobbies 1,391
Educational Facilities Miscellaneous Spaces
Day Care (Through Age 4) 1,027 Bank Vaults/Safe Deposit 805
Day Care Sickroom 716 Computer (Not Printing) 738
Pharmacy (Preparation
Classrooms (Age 5 – 8) 864 820
Area)
Classrooms (Age 9+) 942 Photo Studios 983
Lecture Classroom 1,305 Transportation Waiting 1,305
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 4
CO2 Setpoint CO2 Setpoint
Occupancy Category Occupancy Category
(ppm) (ppm)
Lecture Hall (Fixed Seats) 1,305 Public Assembly Spaces
Art Classroom 837 Auditorium Seating Area 1,872
Place of Religious
Science Laboratories 894 1,872
Worship
University/College Lab 894 Courtrooms 1,872
Wood/Metal Shop 1,156 Legislative Chambers 1,872
Computer Lab 965 Libraries 805
Media Center 965 Lobbies 2,628
Music/Theater/Dance 1,620 Museums (Children’s) 1,391
Multiuse Assembly 1,778 Museum/Galleries 1,620
Food and Beverage Service Retail
Restaurant Dining Rooms 1,418 Sales (Except Below) 1,069
Cafeteria/Fast-Food Dining 1,536 Mall Common Areas 1,620
Bars, Cocktail Lounges 1,536 Barbershop 1,267
General Beauty and Nail Salons 723
Break Rooms 1,267 Pet Shops (Animal Areas) 709
Coffee Stations 1,185 Supermarket 1,116
Conference/Meeting 1,620 Coin-operated Laundries 1,322
Hotels, Motels, Resorts, Dormitories Sports and Entertainment
Bedroom/Living Area 910 Spectator Areas 1,778
Barracks Sleeping Areas 1,116 Disco/Dance Floors 1,440
Health Clubs/Aerobics
Laundry Rooms, Central 1,249 1,735
Room
Health Clubs/Weight
Laundry Within Dwelling 983 1,232
Room
Lobbies/Prefunction 1,494 Bowling Alley (Seating) 1,232
Multipurpose Assembly 2,250 Gambling Casinos 1,368
Game Arcades 894
Stages, Studios 1,391
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 5
California Title 24 CO2 Setpoint Guidance:
Title 24 stipulates the setpoint for all occupancies must be 600 ppm above ambient.
Ambient concentration may be assumed to be 400 ppm or an ambient sensor may be
provided. These sequences are currently based on not having an ambient sensor, so the
CO2 setpoint for all occupancy types is 1000 ppm.
3.1.2. VAV Box Design Information
For the terminal unit sequences, the engineer must provide the setpoint information
below, typically on VAV box schedules on drawings.
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-minimum, except for zones that have CO2 DCV for which Vmin should be equal
to Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
3.1.2.2. VAV Reheat Terminal Unit
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min, except for zones that have CO2 DCV for which Vmin should be equal to
Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
3. Zone maximum heating airflow setpoint (Vheat-max)
The design engineer should set Vheat-max such that the design heating load is met by
Vheat-max airflow at a discharge air temperature equal to MaxΔT plus the heating
setpoint. MaxΔT can be no higher than 11°C (20°F) above space temperature setpoint
per Standard 90.1-2016 (e.g., DAT no more than 32°C (90°F) at 21°C (70°F) space
temperature setpoint) for systems supplying air greater than 1.8m. (6 ft.) above floor,
e.g., ceiling supply systems. Zone air distribution effectiveness EzH, can be improved if
MaxΔT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm) supply air jet
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 6
reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2 of ASHRAE
Standard 62.1-2016.
4. Zone maximum discharge air temperature above heating setpoint (MaxΔT)
Vheat-min is the minimum airflow required for reheat coil operation, as is often
required of electric resistance coils. It should be as low as possible for best efficiency.
For reheat coils with no minimum flow requirement, such as hot water coils, Vheat-min
should be zero.
3.1.2.3. Parallel Fan-Powered Terminal Unit, Constant Volume Fan
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min, except for zones that have CO2 DCV for which Vmin should be equal to
Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
3. Zone maximum discharge air temperature above heating setpoint (MaxΔT).
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min, except for zones that have CO2 DCV for which Vmin should be equal to
Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
3. Parallel fan maximum heating airflow setpoint (Pfan-htgmax)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 7
The design engineer should set Pfan-htgmax such that the design heating load is met by
the sum of Pfan-htgmax and Vmin at a discharge air temperature equal to MaxΔT plus
the heating setpoint. MaxΔT can be no higher than 11°C (20°F) above space
temperature setpoint per Standard 90.1-2016 (e.g., DAT no more than 32°C (90°F) at
21°C (70°F) space temperature setpoint) for systems supplying air greater than 1.8m.
(6 ft.) above floor, e.g., ceiling supply systems. Zone air distribution effectiveness EzH,
can be improved if MaxΔT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm)
supply air jet reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2
of ASHRAE Standard 62.1-2016. This can be done in most zones by setting Pfan-htgmax
to ensure these conditions are maintained.
4. Zone maximum discharge air temperature above heating setpoint (MaxΔT)
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min, except for zones that have CO2 DCV for which Vmin should be equal to
Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
Series Fan airflow is not a design variable because it is not controlled. It must be
designed and balanced to be equal to or greater than Vcool-max. Typically, the Series
Fan airflow is equal to Vcool-max but it may be higher if some blending is desired such
as on cold primary air systems. It may also be higher to improve zone air distribution
effectiveness as discussed in the next comment.
The design engineer should set the Series Fan airflow such that the design heating load
is met with a discharge air temperature equal to MaxΔT plus the heating setpoint.
MaxΔT can be no higher than 11°C (20°F) above space temperature setpoint per
Standard 90.1-2016 (e.g., DAT no more than 32°C (90°F) at 21°C (70°F) space
temperature setpoint) for systems supplying air greater than 1.8m. (6 ft.) above floor,
e.g., ceiling supply systems. Zone air distribution effectiveness EzH, can be improved if
MaxΔT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm) supply air jet
reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2 of ASHRAE
Standard 62.1-2016. This can be done in most zones by setting the Series Fan airflow
to ensure these conditions are maintained.
3. Zone maximum discharge air temperature above heating setpoint (MaxΔT)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 8
3.1.2.6. Series Fan-Powered Terminal Unit, Variable Volume Fan
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min, except for zones that have CO2 DCV for which Vmin should be equal to
Varea-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
The design engineer should set Sfan-htgmax such that the design heating load is met by
the sum of Sfan-htgmax and Vmin at a discharge air temperature equal to MaxΔT plus
the heating setpoint. MaxΔT can be no higher than 11°C (20°F) above space
temperature setpoint per Standard 90.1-2016 (e.g., DAT no more than 32°C (90°F) at
21°C (70°F) space temperature setpoint) for systems supplying air greater than 1.8m.
(6 ft.) above floor, e.g., ceiling supply systems. Zone air distribution effectiveness EzH,
can be improved if MaxΔT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm)
supply air jet reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2
of ASHRAE Standard 62.1-2016. This can be done in most zones by setting Sfan-htgmax
to ensure these conditions are maintained.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 9
For ASHRAE Standard 62.1 ventilation, select Vmin to prevent creating critical zones.
This may lead to Vmin being higher than code minimum ventilation for some zones. For
California Title 24 ventilation, Vmin should be selected as the larger of Varea-min and
Vocc-min. When selecting Vmin, do not consider the limitations of the VAV box
controller to measure and control airflow; that is addressed by the control sequences
themselves.
Zones must be assigned to Zone Groups such as by using a table (see example below)
either on drawings or in BAS specifications. Other formats may be used if they convey
the same information.
Example Zone Group Table:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 10
Guidance for zone group assignments:
• Each zone served by a single-zone air handler shall be its own Zone Group.
• Rooms occupied 24/7, such as computer rooms, networking closets,
mechanical, and electrical rooms served by the air handler shall be assigned to
a single Zone Group. These rooms do not apply to the zone group restrictions
below.
• A Zone Group shall not span floors (per Section 6.4.3.3.4 of ASHRAE 90.1
2016).
• A Zone Group shall not exceed 2,300 m2 (25,000 ft2) (per Section 6.4.3.3.4 of
ASHRAE 90.1 2016).
• If future occupancy patterns are known, a single Zone Group shall not include
spaces belonging to more than one tenant.
• A zone shall not be a member of more than one zone group.
AHU setpoints required by the designer are best conveyed in equipment schedules since
the setpoints vary for each AHU.
The Min_ClgSAT variable should be set no lower than the design coil leaving air
temperature to prevent excessive chilled water temperature reset requests which will
reduce chiller plant efficiency.
The Max_ClgSAT variable is typically 18°C (65°F) in mild and dry climates, 16°C
(60°F) or lower in humid climates. It should not typically be greater than 18°C (65°F)
since this may lead to excessive fan energy that can offset the mechanical cooling
savings from economizer operation.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 11
Occupied Mode supply air temperature setpoint reset logic uses a combination of reset
by outdoor air temperature (intended to reduce fan energy during warm weather) and
zone feedback (SAT needed to satisfy the zone requiring the coldest air to meet space
temperature setpoint). OAT_Min and OAT_Max define the range of outdoor air
temperatures used for the OAT reset logic. Typical values are OAT_Min = 16°C (60°F)
and OAT_Max = 21°C (70°F), selected to maximize economizer operation and minimize
reheat losses, offset partially by higher fan energy. A lower range, e.g., 18°C (65°F)
and 13°C (55°F) respectively, may improve net energy performance for some
applications, such as:
• The chiller plant operates continuously, so extended economizer operation
does not reduce plant runtime.
• The system has very little reheat inherently such as dual fan/dual duct
systems or fan-powered box systems with very low primary air minimums.
• The climate is warm or humid, limiting available economizer hours.
1. For projects complying with the Ventilation Rate Procedure of ASHRAE Standard
62.1:
a. DesVou, the uncorrected design outdoor air rate, including diversity where
applicable.
b. DesVot, design total outdoor air rate (Vou adjusted for ventilation efficiency)
DesVou and DesVot can be determined using the 62MZCalc spreadsheet provided
with the Standard 62.1 User’s Manual.
a. AbsMinOA, the design outdoor air rate when all zones with CO2 sensors or
occupancy sensors are unpopulated.
b. DesMinOA, the design minimum outdoor airflow with areas served by the system
are occupied at their design population, including diversity where applicable.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 12
3.1.4.3. Economizer High Limit
If the project is to comply with Standard 90.1 economizer high limit requirements, keep
subsection “1.” and delete subsection “0.”
If the project is to comply with California Title 24 economizer high limit requirements, keep
subsection “0.” and delete subsection “1.”
The control logic will automatically select the correct setpoints based on Thermal
Zone and high limit type selected. Note that points lists and schematics show herein
do not include enthalpy sensors; they must be added if the designer wishes to use
high limit logic that includes enthalpy.
a. Select ASHRAE Thermal Zone number and suffix in which air handling system is
located.
a. Indicate California Thermal Zone number in which air handling system is located.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 13
3.1.5. Dual Fan Dual Duct VAV Air Handler Design Information
1. Max_HtgSAT, highest heating supply air temperature, typically design heating coil
leaving air temperature
Max_HtgSAT can be no higher than 11°C (20°F) above space temperature setpoint per
Standard 90.1-2016 (e.g., no more than 32°C (90°F) at 21°C (70°F) space temperature
setpoint) for systems supplying air greater than 1.8m. (6 ft.) above floor, e.g., ceiling
supply systems. Zone air distribution effectiveness EzH, can be improved if
Max_HtgSAT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm) supply air
jet reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2 of
ASHRAE Standard 62.1-2016.
3.1.6.1. Setpoints
Cool_SAT is typically the design coil leaving air temperature. Heat_SAT is typically
the design coil leaving air temperature, no more than 20ºF above the active heating
setpoint.
3. MaxΔT, maximum reheat coil discharge air temperature above heating setpoint
MaxΔT can be no higher than 11°C (20°F) above space temperature setpoint per
Standard 90.1-2016 (e.g., DAT no more than 32°C (90°F) at 21°C (70°F) space
temperature setpoint) for systems supplying air greater than 1.8m. (6 ft.) above floor,
e.g., ceiling supply systems. Zone air distribution effectiveness EzH, can be improved if
MaxΔT is less than 8°C (15°F), provided that the 0.8 m/s (150 fpm) supply air jet
reaches to within 1.4m. (4.5 ft.) of floor level as indicated in Table 6.2.2.2 of ASHRAE
Standard 62.1-2016.
4. MaxDPT, maximum supply air dewpoint temperature
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 14
MaxDPT is used to limit supply air temperature to ensure supply air is not too humid
resulting in high space humidity. This is typically only needed in humid type “A”
climates, A typical value is 17°C (62°F). For mild and dry climates, a high setpoint
(e.g. 24°C (75°F)) should be entered for maximum efficiency.
3.1.6.2. Economizer High Limit
If the project is to comply with Standard 90.1 economizer high limit requirements, keep
subsection “1.” and delete subsection “2.”
If the project is to comply with California Title 24 economizer high limit requirements, keep
subsection “2.” and delete subsection “1.”
The control logic will automatically select the correct setpoints based on Thermal Zone
and high limit type selected. Note that points lists and schematics show herein do not
include enthalpy sensors; they must be added if the designer wishes to use high limit
logic that includes enthalpy.
1. ASHRAE 90.1 Economizer High Limit
a. Select ASHRAE Thermal Zone number and suffix in which air handling system is
located.
a. Indicate California Thermal Zone number in which air handling system is located.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 15
While not listed as such in Title 24, it is possible to use both fixed and differential
dry bulb high limits.
3.2 Information Provided by (or in Conjunction with) the Test & Balance Contractor
a. Supply Fan
b. Return Fan
c. Relief Fan
3.2.1.3. Ventilation plenum pressures (for Minimum Outdoor Air Control with separate outdoor
air damper and differential pressure control – see 5.16.4)
1. For projects complying with the Ventilation Rate Procedure of ASHRAE Standard
62.1:
a. DesMinDP, the design minimum outdoor air damper differential pressure that
provides the design minimum outdoor airflow, DesVot.
a. AbsMinDP, the absolute minimum outdoor air damper differential pressure that
provides an outdoor airflow equal to the absolute minimum outdoor airflow,
AbsMinOA.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 16
b. DesMinDP, the design minimum outdoor air damper differential pressure that
provides the design minimum outdoor airflow, DesMinOA.
Instructions for establishing MinDP are given in the Test and Balance
Specification. For example:
1) Open the minimum outdoor air damper and return air damper fully; close
the economizer outdoor air damper.
2) Measure outdoor airflow.
3) If outdoor airflow rate is above design minimum (DesVot for ASHRAE
Standard 62.1 or DesMinOA for California Title 24, adjust damper linkage
on minimum outdoor air damper so that intake is at design minimum with
damper fully stroked.
4) If outdoor airflow rate is below design minimum, temporarily adjust return
air damper position via the BAS until design outdoor airflow is achieved.
This position shall be used for testing only and shall not limit the return air
damper position during normal operation.
5) Note differential pressure across the outdoor air damper. This value
becomes the design minimum outdoor air differential pressure setpoint
(DesMinDP) in the BAS. Convey this setpoint to BAS installer and note on
air balance report.
6) With the system at the minimum outdoor air position, reduce supply air fan
speed until the outdoor airflow is equal to the absolute minimum outdoor
airflow setpoint (AbsMinOA for California Title 24) on AHU schedule.
7) Note differential pressure across the outdoor air damper. This value
becomes the absolute minimum outdoor air differential pressure setpoint
(AbsMinDP for California Title 24) in the BAS. Convey this setpoint to BAS
installer and note on air balance report.
3.2.1.4. Return fan discharge static pressure setpoints (for Return Fan Direct Building Pressure
Control – see 5.16.10)
1. RFDSPmin: That required to deliver the design return air volume across the return air
damper when the supply air fan is at design airflow and on minimum outdoor air.
This setpoint shall be no less than 2.4 Pa (0.01 inches) to ensure outdoor air is not
drawn backwards thru the relief damper.
2. RFDSPmax: That required to exhaust enough air to maintain building static pressure
at setpoint 12 Pa (0.05 inches) when the supply air fan is at design airflow and on
100% outdoor air.
3.2.1.5. Return fan airflow differential (Return Fan Airflow Tracking Control – see 5.16.11)
1. S-R-DIFF. The airflow differential between supply air and return air fans required to
maintain building pressure at desired pressure (e.g., 12 Pa (0.05”)), using a handheld
sensor if a permanent sensor is not provided. All exhaust fans that normally operate
with the air handler should be on.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 17
3.2.2. Single Zone Air Handler Information
1. MinSpeed. The speed that provides supply airflow equal to DesOA (see 3.2.2.2) with
the economizer outdoor air damper fully open.
2. MaxHeatSpeed. The speed that provides supply airflow equal to the design heating
airflow scheduled on plans. If no heating airflow is provided on plans, default to half
of the maximum cooling speed.
3. MaxCoolSpeed. The speed that provides supply airflow equal to the design cooling
airflow scheduled on plans.
The engineer must select between options for determining the outdoor airflow setpoint.
If instead the project is to comply with Standard 62.1 ventilation requirements, delete
subsection “b” and use subsection “a.” If instead the project is to comply with California
Title 24, delete subsection “a” and use subsection “b.”
1. For projects complying with the Ventilation Rate Procedure of ASHRAE Standard
62.1, for purposes of determining Outdoor Air Damper Positions below.
4. MinPosMax: the outdoor air damper position required to provide MinOA when the
supply fan is at MaxCoolSpeed.
5. DesPosMin: the outdoor air damper position required to provide DesOA when the
supply fan is at MinSpeed.
6. DesPosMax: the outdoor air damper position required to provide DesOA when the
supply fan is at MaxCoolSpeed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 18
3.2.2.3. Relief damper positions (if non-powered relief)
3.2.2.4. Return fan speed differential (if return fan is used), S-R-DIFF. The speed differential
between supply air and return air fans required to maintain building pressure at desired
pressure (e.g., 12 Pa (0.05”)), using a handheld sensor if a permanent sensor is not
provided. All exhaust fans that normally operate with the air handler should be on.
Point Types:
AO = Analog Output
DO = Digital Output (aka BO = Binary Output)
AI = Analog Input
DI = Digital Input (aka BI = Binary Input)
Note that terminal unit discharge air sensors are actively used for control and therefore must be
reasonably accurate. If a single point probe type sensor is used, it should be located at least five
duct diameters downstream of the coil due to stratification off of the heating coil, particularly at
low loads. However, this is seldom practical in practice. If an averaging type sensor is used, it
should be located at least 12” downstream of the coil if possible, 6” minimum. But averaging
sensors are costlier and also may have installation issues especially if installed after ductwork
is fully installed which is typically the case. Reasonable results can be obtained by using a single
point probe sensor mounted as far from the coil as possible but upstream of the first diffuser with
the probe located as near as possible the center of the duct both vertically and horizontally.
Occupancy sensors are listed as an optional hardwired point. This point is also commonly a
software point mapped from a networked lighting control system or security system.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 19
4.1 VAV Terminal Unit – Cooling Only
Re-
quired Description Type Device
?
AO Modulating actuator
R VAV Box Damper Position OR OR
two DOs Floating actuator
Differential pressure transducer
R Discharge Airflow AI
connected to flow sensor
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
A Zone CO2 Level (if applicable) AI Room CO2 sensor
Re-
quired Description Type Device
?
AO Modulating actuator
R VAV Box Damper Position OR OR
two DOs Floating actuator
Modulating valve
AO OR
Heating Signal
R OR Floating actuator
two DOs OR
Modulating electric heating coil
Differential pressure transducer
R Discharge Airflow AI
connected to flow sensor
Duct temperature sensor (probe or
R Discharge Air Temperature AI
averaging at designer’s discretion)
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
A Zone CO2 Level (if applicable) AI Room CO2 sensor
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 20
4.3 Fan Powered Terminal Unit (Series or Parallel, Constant or Variable Speed Fan)
Re-
quired Description Type Device
?
Fan Speed Command (if Connect to electronically commutated
A AO
applicable) motor (ECM)
Fan Start/Stop (if separate from
R DO Connect to ECM
fan speed point)
Fan Status DI Connect to current switch
O OR OR OR
Fan Speed Feedback AI Connect to ECM
AO Modulating actuator
R VAV Box Damper Position OR OR
two DOs Floating actuator
Modulating valve
AO OR
R Heating Signal OR Floating actuator
two DOs OR
Modulating electric heating coil
Differential pressure transducer
R Primary Airflow AI
connected to flow sensor
Duct temperature sensor (probe or
R Discharge Air Temperature AI
averaging at designer’s discretion)
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
A Zone CO2 Level (if applicable) AI Room CO2 sensor
Re-
quired Description Type Device
?
AO Modulating actuator
R Cooling Damper Position OR OR
two DOs Floating actuator
AO Modulating actuator
R Heating Damper Position OR OR
two DOs Floating actuator
Differential pressure transducer
R Cooling Airflow AI
connected to flow sensor
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 21
Re-
quired Description Type Device
?
Differential pressure transducer
R Heating Airflow AI
connected to flow sensor
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
Zone CO2 Level (if applicable,
A AI Room CO2 sensor
cold duct minimum control only)
Re-
quired Description Type Device
?
AO Modulating actuator
R Cooling Damper Position OR OR
two DOs Floating actuator
AO Modulating actuator
R Heating Damper Position OR OR
two DOs Floating actuator
Differential pressure transducer
R Discharge Airflow AI
connected to flow sensor
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
Zone CO2 Level (if applicable,
A AI Room CO2 sensor
mixing control only)
Re-
quired Description Type Device
?
R Supply Fan Start/Stop DO Connect to VFD Run
Supply Fan High Static Alarm
Dry contact to 120V or 24V control
A Reset (optional – see control DO
circuit
schematic)
R Supply Fan Speed AO Connect to VFD Speed
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 22
Re-
quired Description Type Device
?
O Supply Fan Status DI Connect to VFD Status
Duct temperature sensor (probe or
R Supply Air Temperature AI
averaging at designer’s discretion)
Differential pressure transducer down
R Duct Static Pressure AI
duct
Differential pressure transducer across
O Filter Pressure Drop AI
filter
Heating coil supply air
O AI Averaging temperature sensor
temperature
R Economizer Outdoor Air Damper AO Modulating actuator
R Return Air Damper AO Modulating actuator
R Outdoor Air Temperature AI Temperature sensor at outdoor air intake
O Mixed Air Temperature AI Averaging temperature sensor
A Return Air Temperature AI Duct temperature sensor
R Cooling Signal AO Modulating CHW valve
Modulating HW valve
A Heating Signal AO OR
Modulating electric heating coil
For units with a common economizer/minimum OA damper, include the following points
A Outdoor Airflow AI Airflow measurement station (AFMS)
For units with a separate minimum outdoor air damper and DP sensor, include the following points
Minimum Outdoor Air Damper
A DO Two position actuator
Open/Close
Minimum Outdoor Air Damper
Differential pressure transducer
A Differential Pressure AI
For units with a separate minimum outdoor air damper and AFMS, include the following points
A Minimum Outdoor Air Damper AO Modulating actuator
A Minimum Outdoor Airflow AI Airflow measurement station
For units with actuated relief dampers but no relief fan, include the following points
A Relief Damper Open/Close AO Modulating actuator
Differential pressure transducer between
A Building Static Pressure AI
representative space and outdoors
For units with a relief fan, include the following points
A Relief Fan Start/Stop DO Connect to VFD Run
O Relief Fan Status DI Connect to VFD Status
A Relief Fan Speed AO Connect to VFD Speed
A Relief Damper Open/Close DO Two position actuator
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 23
Re-
quired Description Type Device
?
Building Static Pressure (if direct Differential pressure transducer between
A AI
building pressure logic is used) representative space and outdoors
For units with a return fan, include the following points
A Return Fan Start/Stop DO Connect to VFD Run
O Return Fan Status DI Connect to VFD Status
Return Fan High Static Alarm
Dry contact to 120V or 24V control
A Reset (optional – see control DO
circuit
schematic)
A Return Fan Speed AO Connect to VFD Speed
Supply Airflow (if airflow Airflow measurement station at supply
A AI
tracking logic used) fan (or sum of VAV zones)
Return Airflow (if airflow tracking Airflow measurement station at return
A AI
logic used) fan
Return Fan Discharge Static
A Pressure (if direct building AI Differential pressure transducer at fan
pressure logic is used)
A Exhaust Damper AO Modulating actuator
Building Static Pressure (if direct Differential pressure transducer between
A AI
building pressure logic is used) representative space and outdoors
4.7 Dual Fan Dual Duct Heating VAV Air Handling Unit
Re-
quired Description Type Device
?
R Supply Fan Start/Stop DO Connect to VFD Run
Supply Fan High Static Alarm
Dry contact to 120V or 24V control
A Reset (optional – see control DO
circuit
schematic)
R Supply Fan Speed AO Connect to VFD Speed
Supply Fan Status DI Connect to VFD Status
Duct temperature sensor (probe or
R Supply Air Temperature AI
averaging at designer’s discretion)
Modulating HW valve
R Heating Signal AO OR
Modulating electric heating coil
Differential pressure transducer down
R Duct Static Pressure AI
duct
Differential pressure transducer across
O Filter Pressure Drop AI
filter
O Return Air Temperature AI Duct temperature sensor
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 24
4.8 Single Zone VAV Air Handling Unit
Re-
quired Description Type Device
?
R Supply Fan Start/Stop DO Connect to VFD Run
R Supply Fan Speed AO Connect to VFD Speed
O Supply Fan Status DI Connect to VFD Status
Duct temperature sensor (probe or
R Supply Air Temperature AI
averaging at designer’s discretion)
R Outdoor/Return Air Damper AO Modulating actuators
R Outdoor Air Temperature AI Temperature sensor at outdoor air intake
O Mixed Air Temperature AI Averaging temperature sensor
O Return Air Temperature AI Duct temperature sensor
Modulating CHW valve
R Cooling Signal AO OR
Variable-capacity compressor
Modulating HW valve
A Heating Signal AO OR
Modulating electric heating coil
R Zone Temperature AI Room temperature sensor
A Local Override (if applicable) DI Zone thermostat override switch
A Occupancy Sensor (if applicable) DI Occupancy sensor
A Window Switch (if applicable) DI Window switch
Zone Temperature Setpoint
A AI Zone thermostat adjustment
Adjustment (if applicable)
A Zone CO2 Level (if applicable) AI Room CO2 sensor
For units with actuated relief dampers but no relief fan, include the following points
A Relief Damper AO Modulating actuator
For units with a relief fan, include the following points
A Relief Fan Start/Stop DO Connect to VFD Run
O Relief Fan Status DI Connect to VFD Status
A Relief Fan Speed AO Connect to VFD Speed
A Relief Damper Open/Close DO Two position actuator
Differential pressure transducer between
A Building Static Pressure AI
representative space and outdoors
For units with a return fan, include the following points
A Return Fan Start/Stop DO Connect to VFD Run
O Return Fan Status DI Current switch
A Return Fan Speed AO Connect to VFD Speed
Exhaust Air Damper (if applicable
A DO Two position actuator
– damper may be barometric)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 25
5. SEQUENCES OF OPERATIONS
5.1 General
5.1.1. These sequences are intended to be performance based. Implementations that provide the
same functional result using different underlying detailed logic will be acceptable.
The intention of these sequences is to specify the functional result of the programming
logic. While all sequences are described using specific programming logic as a way
to clearly document the resulting functionality, implementations using alternative logic
that result in the same functional performance are acceptable. Verification of
conformance to these sequences will eventually be through functional performance
tests (FPTs) that demonstrate that the sequences were properly implemented, rather
than verification of the detailed logic. FPTs for RP-1455 sequences are currently under
development through RP-1746; they will be adapted to Guideline 36 sequences and
issued as an appendix in a future addendum.
5.1.2. Unless otherwise indicated, control loops shall be enabled and disabled based on the status
of the system being controlled to prevent windup.
5.1.3. When a control loop is enabled or re-enabled, it and all its constituents (such as the
proportional and integral terms) shall be set initially to a Neutral value.
5.1.4. A control loop in Neutral shall correspond to a condition that applies the minimum control
effect, i.e., valves/dampers closed, VFDs at minimum speed, etc.
5.1.5. When there are multiple outdoor air temperature sensors, the system shall use the valid
sensor that most accurately represents the outdoor air conditions at the equipment being
controlled.
5.1.5.1. Outdoor air temperature sensors at air handler outdoor air intakes shall be considered
valid only when the supply fan is proven on and unit is in Occupied Mode or in any
other Mode with the economizer enabled.
5.1.5.2. The outdoor air temperature used for optimum start, plant lockout, and other global
sequences shall be the average of all valid sensor readings. If there are four or more
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 26
valid outdoor air temperature sensors, discard the highest and lowest temperature
readings.
5.1.6. The term “proven” (i.e., “proven on”/ “proven off”) shall mean that the equipment’s DI
status point (where provided, e.g., current switch, DP switch, or VFD status) matches the
state set by the equipment’s DO command point.
5.1.7. The term “software point” shall mean an analog variable, and “software switch” shall mean
a digital (binary) variable, that are not associated with real I/O points. They shall be
read/write capable (e.g., BACnet analog variable and binary variable).
5.1.8. The term “control loop” or “loop” is used generically for all control loops. These will
typically be PID loops, but proportional plus integral plus derivative gains are not required
on all loops. Unless specifically indicated otherwise, the following guidelines shall be
followed:
5.1.8.1. Use proportional only (P-only) loops for limiting loops (such as zone CO2 control loops,
etc.).
Use of proportional-only on limiting loops prevents integral windup from causing the
controlled sensor from overshooting setpoint due to the sensor generally being far from
setpoint.
5.1.8.2. Do not use the derivative term on any loops unless field tuning is not possible without
it.
Derivative terms make loop tuning difficult in practice. It can make loops unstable since
it increases as the rate of change of the error increases, amplifying the error signal. It
is used in industrial process controls and systems that have to react quickly, but is rarely
if ever needed in HVAC system.
5.1.9. To avoid abrupt changes in equipment operation, the output of every control loop shall
be capable of being limited by a user adjustable maximum rate of change, with a
default of 25% per minute.
5.1.10. All setpoints, timers, deadbands, PID gains, etc., listed in sequences shall be adjustable by
the user with appropriate access level whether indicated as adjustable in sequences or not.
Software points shall be used for these variables. Fixed scalar numbers shall not be
embedded in programs except for physical constants and conversion factors.
5.1.11. Values for all points, including real (hardware) points used in control sequences shall
be capable of being overridden by the user with appropriate access level (e.g., for
testing and commissioning). If hardware design prevents this for hardware points, they
shall be equated to a software point, and the software point shall be used in all
sequences. Exceptions shall be made for machine or life safety.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 27
All hardware points, not just inputs, should be capable of being overridden for
purposes of testing and commissioning. For example, the commissioning agent should
be able to command damper positions, valve positions, fan speeds, etc., directly
through Building Automation System (BAS) overrides.
The requirement to equate hardware points to software points is necessary for systems
that do not allow overriding real input points.
5.1.12. Alarms
Defining the operator’s interface is outside of the scope of Guideline 36, but effective
use of alarms by building personnel requires an effective user interface. We recommend
including at least the following requirements in the specification for the BAS graphical
user interface:
• All alarms shall include a Time/Date Stamp using the standalone control module
time and date.
• Each alarm can be configured in terms of level, latching (Requires
Acknowledgement of a Return to Normal/Does Not Require Acknowledgement of a
Return to Normal), entry delay, exit deadband, and post suppression period.
• An operator shall be able to sort alarms based on level, time/date, and current
status.
Alarms should be reported with the following information:
Date and time of the alarm
Level of the alarm
Description of the alarm
Equipment tags for the units in alarm
Possible causes of the alarm, if provided by the fault detection routines
The Source per 5.1.19 that serves the equipment in alarm.
5.1.12.2. Maintenance Mode: Operators shall have the ability to put any device (e.g., AHU) in/out
of maintenance mode.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 28
5.1.12.3. Entry Delays – All alarms shall have an adjustable delay time such that the alarm is not
triggered unless the alarm condition is true for the delay time. Default entry delays:
1. Each alarm shall have an adjustable time-based hysteresis (default: 5 seconds) to exit
the alarm. Once set, the alarm does not return to normal until the alarm conditions
have ceased for the duration of the hysteresis.
If a low pressure alarm is triggered at 0.5” and has exit hysteresis of 20% for 10
seconds, the alarm will remain active until the alarmed pressure rises above 0.6”
(0.5” plus 20%) continuously for 10 seconds.
5.1.12.5. Latching – Any alarm can be configured as latching or non-latching. A latching alarm
requires acknowledgement from the operators before it can return to normal even if the
exit deadband has been met. A non-latching alarm does not require acknowledgement.
Default latching status:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 29
5.1.12.6. Post Exit Suppression period – To limit alarms, any alarm may have an adjustable
suppression period such that a particular instance of that alarm may not re-occur until
the alarm has been cleared for the suppression period. Default suppression periods:
5.1.12.7. For both latching and non-latching alarms, the operators may acknowledge the alarm.
Acknowledging an alarm clears the alarm, the exit deadband, and suppression period.
A device can go right back into alarm as soon as the entry delay elapses.
To avoid operator confusion, the speed command point (and speed feedback point, if
used) for VFDs should be configured so that a speed of 0% corresponds to 0 Hz and
100% corresponds to maximum speed set in the VFD, not necessarily 60 Hz. The
maximum speed may be limited below 60 Hz to protect equipment or it may be above
60 Hz for direct drive equipment. Drives are often configured such that a 0% speed
signal corresponds to the minimum speed programmed into the VFD, but that causes
the speed AO value and the actual speed to deviate from one another.
5.1.13.1. The speed analog output sent to VFDs shall be configured such that 0% speed
corresponds to 0 Hz and 100% speed corresponds to maximum speed configured in the
VFD.
It is desirable that the minimum speed reside in the VFD to avoid problems when the
VFD is manually controlled at the drive. But minimums can also be adjusted
inadvertently in the VFD to a setpoint that is not equal to the minimum used in software.
The following prevents separate, potentially conflicting minimum speed setpoints from
existing in the BAS software and the drive firmware.
5.1.13.2. For each piece of equipment, the minimum speed shall be stored in a single software
point. This value shall be written to the VFD’s minimum speed setpoint every 15
minutes via the drive’s network interface; in the case of a hard-wired VFD interface, the
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 30
minimum speed shall be the lowest speed command sent to the drive by the BAS. See
3.2.1.2 for minimum speed setpoints.
Trim & Respond logic resets a setpoint for pressure, temperature, or other variables
at an air handler or plant. It reduces the setpoint at a fixed rate, until a downstream
zone is no longer satisfied and generates a request. When a sufficient number of
requests are present, the setpoint is increased in response. The importance of each
zone’s requests can be adjusted to ensure that critical zones are always satisfied. When
a sufficient number of requests no longer exist, the setpoint resumes decreasing at its
fixed rate. A running total of the requests generated by each zone is kept to identify
zones that are driving the reset logic.
Trim and Respond logic is optimal for controlling a single variable that is subject to
the requirements of multiple downstream zones (such as the static pressure setpoint for
a VAV air handler). In this application, it is easier to tune than a conventional control
loop and provides for fast response without high frequency chatter or loss of control of
the downstream devices. It typically does generate low frequency cyclic hunting, but
this behavior is slow enough to be non-disruptive.
See the end of this section for an example of T&R implementation.
5.1.14.1. Trim & Respond setpoint reset logic and zone/system reset Requests where referenced
in sequences shall be implemented as described below.
1. For each downstream zone or system, and for each type of setpoint reset Request
listed for the zone/system, provide the following software points:
c. System Run-Hours Total. This is the number of hours the zone/system has been
operating in any Mode other than Unoccupied Mode.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 31
Request-Hours accumulates the integral of requests (prior to adjustment of
Importance Multiplier) to help identify zones/systems that are driving the
reset logic. Rogue zone identification is particularly critical in this context,
since a single rogue zone can keep the Trim & Response loop at maximum,
and prevent it from saving any energy.
e. The Request-Hours Accumulator and System Run-Hours Total are reset to zero as
follows:
2. See zone and air handling system control sequences for logic to generate Requests.
3. Multiply the number of Requests determined from zone/system logic times the
Importance Multiplier and send to the system/plant that serves the zone/system. See
system/plant logic to see how Requests are used in Trim & Respond logic.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 32
5.1.14.3. For each upstream system or plant setpoint being controlled by a T&R loop, define the
following variables. Initial values are defined in system/plant sequences below. Values
for trim, respond, time step, etc., shall be tuned to provide stable control.
Variable Definition
Device Associated device (e.g., fan, pump)
SP0 Initial setpoint
SPmin Minimum setpoint
SPmax Maximum setpoint
Td Delay timer
T Time step
I Number of Ignored Requests
R Number of Requests from
zones/systems
SPtrim Trim amount
SPres Respond amount (must be opposite
in sign to SPtrim)
SPres-max Maximum response per time
interval (must be same sign as SPres)
Note that it is recommended that | SPres | > | SPtrim | so that the reset logic
does not get stuck at a value, as can happen if SPres and SPtrim are equal
in absolute value.
The number of Ignored Requests (I) should be set to zero for critical zones
or air handlers.
5.1.14.4. Trim & Respond logic shall reset setpoint within the range SPmin to SPmax. When the
associated device is off, the setpoint shall be SP0. The reset logic shall be active while
the associated device is proven on, starting Td after initial device start command. When
active, every time step T, trim the setpoint by SPtrim. If there are more than I Requests,
respond by changing the setpoint by SPres * (R-I), (i.e., the number of Requests minus
the number of Ignored Requests), but no more than SPres-max. In other words, every time
step T:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 33
The following is an example of a sequence that uses Trim & Respond to control the static pressure
setpoint of a VAV AHU serving multiple downstream zones:
Variable Definition
Device Supply Fan
SP0 120 Pa.
(0.5”)
SPmin 37 Pa.
(0.15”)
SPmax 370 Pa.
(1.50”)
Td 5
T 2
I 2
SPtrim -10 Pa.
(-0.04”)
SPres 15 Pa.
(0.06”)
SPres-max 37 Pa.
(0.15”)
Example:
System starts at 11:55. Initial setpoint is 120 Pa. (0.5”). At 12:00 (Td after start time), the reset
begins.
At 12:02 (i.e., 1*T after reset begins), there is one request (i.e., R=1). Trim component reduces
setpoint by SPtrim which is 10 Pa. (0.04”); since R-I < 0, there is no response component. Net
result: Setpoint is 110 Pa. (0.46”).
At 12:04 (i.e., 2*T), there are two requests (i.e., R=2): Trim component reduces setpoint by 10 Pa.
(0.04”); since R – I = 0, there is no response component. Net result: Setpoint is 100 Pa. (0.42”).
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 34
At 12:06 (i.e., 3*T), there are three requests (i.e., R=3): Trim component reduces setpoint by 10
Pa. (0.04”); since R – I = 1, response component increases setpoint by 15 PA. (0.06”) (i.e., 1 *
SPres). Net result: Setpoint is 105 Pa. (0.44”) (i.e., +5.0 Pa. (+0.02”) net change).
At 12:08 (i.e., 4*T), there are four requests (i.e., R=4): Trim component reduces setpoint by 10
Pa. (0.04”); since R – I = 2, response component increases setpoint by 30 Pa. (0.12”) (i.e., 2 *
SPres). Net result: Setpoint is 125 Pa. (0.52”) (i.e., +20 Pa. (+0.08”) net change).
At 12:10 (i.e., 5*T), there are six requests (i.e., R=6): Trim component reduces setpoint by 10 Pa.
(0.04”); since R – I = 4 but SPres- max =37 Pa. (0.15”), response component increases setpoint by
the maximum of 37 Pa. (0.15”) (i.e., not 4 * SPres = 60 Pa. (0.24”). Net result: Setpoint is 152 Pa.
(0.63”) (i.e., 27 Pa. (+0.11”) net change).
At 12:12 (i.e., 6*T), there are three requests (i.e., R=3): Trim component reduces setpoint by 10
Pa. (0.04”); since R – I = 1, response component increases setpoint by 15 Pa. (0.06”) (i.e., 1 *
SPres). Net result: Setpoint is 157 Pa. (0.65”).
At 12:14 (i.e., 7*T), there are zero requests (i.e., R=0): Trim component reduces setpoint by 10
Pa. (0.04”); since R – I < 0, there is no response component. Net result: Setpoint is 147 Pa.
(0.61”).
This is a trend graph of the example above, continued for a period of an hour:
#R > #I = setpoint rises Static Setpoint
0.70
R = 5 SPres-max= 37 Pa (0.15”)
0.60
0.40
0.20
5
Number of Requests
2 IGNORED REQUESTS
The system will tend towards minimum static pressure (thus saving energy) but respond rapidly to
increasing demand from the terminal units. A cyclic pattern is characteristic of a robust Trim &
Respond loop – the setpoint is not expected to remain static except at its minimum and maximum
values. Note that this diagram was created for purposes of illustrating how requests are used to
reset the setpoint and does not necessarily represent the expected behavior of an actual Trim &
Respond loop, although the long, slow cycling of the setpoint value is typical of T&R control.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 35
5.1.15. Equipment Staging and Rotation
Sequences for automatic lead/lag equipment staging and rotation will be added in a
later version of Guideline 36.
5.1.15.1. Operators with appropriate access level shall be able to manually command staging
order via software points, but not overriding the In Alarm or Hand Operation logic
below.
5.1.15.2. In Alarm: If the lead device has a fault condition or has been manually switched off, a
Level 2 alarm shall be generated and the device shall be set to the last stage position in
the staging order until alarm is reset by operator. A device in alarm can only
automatically move up in the staging order if another device goes into alarm.
This sequence does not lock out a device that is in alarm. It moves all devices in
alarm to the end of the rotation sequence such that they will be the last devices
called to run. The sequence will only call for these devices in alarm if all of the
devices not in alarm are already enabled and there is a call for a stage-up. A device
in alarm will respond if called to run, only if it is capable of doing so (e.g., not
locked out on internal safety, locked out on an HOA switch at the starter, or
otherwise disabled). It is important to note that this staging does not override the
devices internal safeties so it will not damage equipment.
Note some alarm conditions could be triggered when the underlying equipment is
fully operable. For example, a status point not matching the on/off command could
be triggered by a faulty status signal. The same is true for a supervised HOA at a
control panel, the operator might have been testing the equipment and simply forgot
to turn the HOA back to AUTO.
1) Status point not matching its on/off point for 3 seconds after a time delay of 15
seconds while the device is commanded on.
Current scope of these sequences only include Variable Speed Fans.
Pumps, chillers, and boilers are currently beyond the scope of Guideline
36. They will be incorporated into this logic as a part of RP-1711, which
addresses sequences for central heating and cooling plants.
2. Hand Operation: If a device is on in Hand (e.g., via an HOA switch or local control
of VFD), the device shall be set to the lead device and a Level 4 alarm shall be
generated. The device will remain as lead until the alarm is reset by the operator.
Hand operation is determined by:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 36
Any condition in which a device appears to continue to run after being commanded
off is considered a case of “hand operation;” in practice, this condition may arise
due to other circumstances (e.g., a bad current transducer).
1) Status point not matching its on/off point for 15 seconds while the device is
commanded off.
Current scope of these sequences only include Variable Speed Fans.
Pumps, chillers, and boilers are currently beyond the scope of Guideline
36. They will be incorporated into this logic as a part of RP-1711, which
addresses sequences for central heating and cooling plants.
5.1.16.1. This section is used to determine the lowest possible VAV box airflow setpoint (other
than zero) allowed by the controls (Vm) used in VAV box control sequences. The
minimums shall be stored as software points.
5.1.16.2. Option 1: If the VAV box controls simply stop moving the damper when the airflow
reading becomes too low to register and then re-enables the damper when the airflow
reading rises above that threshold, Vm shall be equal to zero.
VAV box controllers that stop moving the damper when they are unable to read an
airflow signal avoid the need to determine a minimum. When given a setpoint below
controllable minimum, the controller will control as low as it can, which is the desired
behavior.
1. Determine the velocity pressure sensor reading VPm in inches H2O that will give a
reliable flow indication. If this information is not provided by the sensor
manufacturer, determine the velocity pressure that will result in a digital reading from
the transducer and A/D converter of 12 bits or counts (assuming a 10-bit A/D
converter). This is considered sufficient resolution for stable control.
2. Determine the minimum velocity vm for each VAV box size and model. If the VAV
box manufacturer provides an amplification factor F for the flow pickup, calculate the
minimum velocity vm as
VPm
vm = 4005
F
Where F is not known, it can be calculated from the measured airflow at
250 Pa (1 inch w.c.) signal from the VP sensor
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 37
2
4005 A
F =
CFM
@ 1"
3. Calculate the minimum airflow setpoint allowed by the controls (Vm) for each VAV
box size as
Vm = vm A
5.1.17. Air Economizer High Limits
5.1.17.1. Economizer shall be disabled whenever the outdoor air conditions exceed the
economizer high limit setpoint as specified by local code. Setpoints shall be
automatically determined by the control sequences (to ensure they are correct and meet
code) based on energy standard, climate zone, and economizer high limit control device
type selected by the design engineer in 3.1.4.3 or 3.1.6.2. Setpoints listed below are for
current ASHRAE and California Energy Standards.
The engineer must specify the code basis of the economizer high limit and, optionally, the
high limit control device being used.
For jobs in California, delete “5.1.17.2” and keep “5.1.17.3.” For jobs elsewhere, delete
“5.1.17.3” and keep “5.1.17.2.”
Within the section that remains, the engineer can specify the high limit control device (e.g.,
differential dry bulb) if the same method is to be used for all equipment. Alternatively, the
engineer may retain the entirety of the selected table, but must then specify the high limit
device for each air handling unit later in the sequences.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 38
5.1.17.2. ASHRAE 90.1-2016:
5.1.18.1. Knowledge of damper and valve position are required for proper generation of Trim &
Respond reset requests.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 39
2. Floating actuator. Provide either
The engineer may choose to disallow the following option, which is less accurate than the
other options for determining damper position. But doing so may limit controller
manufacturer since not all manufacturers offer the other options.
Note that this logic is intended to suppress alarm visual and audible displays,
notifications (e.g., email or SMS text), listing in primary alarm logs, and other actions
that can distract the operator or make it more difficult to diagnose and respond to
alarms. The alarm may still be generated and recorded to a database.
5.1.19.1. For each piece of equipment or space controlled by the BAS, define its relationship (if
any) to other equipment in terms of “source,” “load,” or “system.”
For equipment that participates in a Trim & Response loop, the equipment
generating the requests will always be the load component, and the equipment
receiving and responding to the requests will be a source component.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 40
1. A component is a “source” if it provides resources to a downstream component, such
as a chiller providing chilled water to an AHU.
3. The same component may be both a load (receiving resources from an upstream
source) and a source (providing resources to a downstream load).
1) If the pumps are in a one-to-one relationship with equipment they serve, the
pumps shall be treated as part of the system to which they are associated (i.e.,
they are not considered loads) since a pump failure will necessarily disable its
associated equipment.
2) If the pumps are headered to the equipment they serve, then the pumps may be
treated as a system, which is a load relative to the upstream equipment (e.g.,
chillers) and a source relative to downstream equipment (e.g., air handlers).
Example: Consider a building with four cooling tower cells, each with its own
pump, two chillers with two CHW pumps in a headered arrangement, three air
handlers, and 10 VAV boxes on each AHU, with each VAV box serving multiple
rooms.
• The cooling towers together constitute a system, which is a source to the
chillers.
• The chillers together constitute a system, which is a load to the cooling tower
system and a source to the CHW pump system.
• The CHW pumps together constitute a system, which is a load to the chillers
and a source to the air handlers.
• Each air handler constitutes its own separate system because they do not
share a load in common. Each AHU is a load to the CHW pump system, and
a source to its own VAV boxes.
• Each VAV box constitutes its own system because they do not share a load in
common. Each VAV box is a load to its AHU (only; no relationship to the
other AHUs), and a source to the rooms that it serves.
• Each interior space is a load to its associated VAV box.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 41
5.1.19.2. For each system as defined above, there shall be a SystemOK flag, which is either true
or false.
5.1.19.3. SystemOK shall be true when all of the following are true:
2. The system is achieving its temperature and/or pressure setpoint(s) for at least five
minutes
5.1.19.4. SystemOK shall be false while the system is starting up (i.e., before reaching setpoint)
or when enough of the system’s components are unavailable (in alarm, disabled, or
turned off) to disrupt the ability of the system to serve its load. This threshold shall be
defined by the design engineer for each system.
2. The operator shall have the ability to individually determine which component
alarms may or may not inhibit SystemOK.
Examples:
If a boiler system consists of a pair of boilers sized for 100% of the design
load, in a lead-standby relationship, then SystemOK is true if at least one
boiler is operational and achieving setpoint.
If a chiller system consists of three chillers each sized for 50% of the design
load, then SystemOK is true if at least two chillers are available to run. If only
one chiller is available to run, then SystemOK will be false (even though the
one remaining chiller may be sufficient to serve off-peak loads).
5.1.19.5. The BAS shall selectively suppress (i.e., fail to announce; alarms may still be logged to
a database) alarms for load components if SystemOK is false for the source system that
serves that load.
1. If SystemOK is false for a cooling water system (i.e., chiller, cooling tower, or
associated pump), then only high temperature alarms from the loads shall be
suppressed.
2. If SystemOK is false for a heating water system (i.e., boiler or associated pump), then
only low temperature alarms from the loads shall be suppressed.
3. If SystemOK is false for an airside system (air handler, fan coil, VAV box, etc.), then
all alarms from the loads shall be suppressed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 42
5.1.19.6. This hierarchical suppression shall cascade through multiple levels of load-source
relationship, such that alarms at downstream loads shall also be suppressed.
Example:
A building has a cooling tower system (towers and CDW pumps), a chiller
system (chillers and CHW pumps), and a boiler system (boilers and HW
pumps). These systems serve several air handlers (each considered its own
system), and each air handler serves a series of VAV boxes (each also
considered its own system).
If SystemOK is false for the cooling tower system, then high temperature
alarms are suppressed for the chillers, the air handlers, the VAV boxes and
zones, but not for the boilers. Low temperature alarms are not suppressed.
(Note that in actuality, the hard-wired interlock between cooling tower and
chiller would inhibit chiller operation if the cooling towers are off or locked
out. The example is retained for illustrative purposes.)
If SystemOK is false for the chiller system, then high temperature alarms are
suppressed for the air handlers and the VAV boxes, but not for the cooling
towers or boilers. Low temperature alarms are not suppressed.
If SystemOK is false for the boiler system, then low temperature alarms are
suppressed for the air handlers and the VAV boxes, but not for the cooling
towers or chillers. High temperature alarms are not suppressed.
If SystemOK is false for one of the air handlers, then all alarms (low
temperature, high temperature, and airflow) are suppressed for all VAV boxes
served by that air handler only. Alarms are not suppressed for the cooling
towers, chillers, boilers, or the other AHU or its VAV boxes.
If one VAV box is in alarm, then all alarms (e.g., zone temperature, CO2) are
suppressed for the zone served by that VAV box only. No other alarms are
suppressed.
5.1.19.7. The following types of alarms will never be suppressed by this logic:
2. Failure-to-start alarms (i.e., equipment is commanded on, but status point shows
equipment to be off)
3. Failure-to-stop/hand alarms (i.e., equipment is commanded off, but status point shows
equipment to be on)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 43
5.1.20. Time-Based Suppression
5.1.20.1. Calculate a time delay period after any change in setpoint based on the difference
between the controlled variable (e.g., zone temperature) at the time of the change and
the new setpoint. The default time delay period shall be:
For example, if setpoint changes from 20°C (68°F) to 21°C (70°F) and the
zone temperature is 20°C (68.5°F) at the time of the change, inhibit alarm for
15 minutes (0.8°C (1.5°F) * 10 minutes/°F) after the change.
2. For thermal zone temperature cooling requests: 5 minutes per °F of difference, but
no longer than 30 minutes
3. For thermal zone temperature heating requests: 5 minutes per °F of difference, but
no longer than 30 minutes
5.2.1.1. For every zone that requires mechanical ventilation, the zone minimum outdoor airflows
and setpoints shall be calculated depending on the governing standard or code for
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 44
outdoor air requirements. Zones that do not require mechanical ventilation may
disregard this section.
The following subsection “5.2.1.3” should be used for ventilation logic that complies with
ASHRAE Standard 62.1. If instead the project is to comply with California Title 24
ventilation requirements, delete subsection “5.2.1.3” and use subsection “5.2.1.4,” below.
5.2.1.3. For compliance with the Ventilation Rate Procedure of ASHRAE Standard 62.1-2016,
outdoor air and zone minimum setpoints shall be calculated as follows:
a. If the discharge air temperature at the terminal unit is less than or equal to zone
space temperature, Ez shall be equal to EzC (default to 1.0 if no value is scheduled).
b. If the discharge air temperature at the terminal unit is greater than zone space
temperature, Ez shall be equal to EzH (default to 0.8 if no value is scheduled).
3. Vbz-P* is the population component of the required breathing zone outdoor airflow.
The normal value of Vbz-P* shall be Vbz-P.
4. The occupied minimum airflow Vmin* shall be equal to Vmin except as noted below:
5. The required zone outdoor airflow Voz shall be calculated as Voz = (Vbz-A + Vbz-P*) /
Ez, where the normal values of Vbz-A and Vbz-P* are modified if any of the following
conditions are met, in order from higher to lower priority:
a. If the zone is in any mode other than Occupied Mode and for zones that have
window switches and the window is open: Vbz-P* = 0, Vbz-A = 0, and Vmin* = 0.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 45
1) See 3.1.1.3 for CO2 setpoints.
2) During Occupied Mode, a P-only loop shall maintain CO2 concentration at
setpoint; reset from 0% at (setpoint minus 200 PPM) and to 100% at setpoint.
3) Loop is disabled and output set to zero when the zone is not in Occupied Mode.
CO2 DCV is not yet well defined for Standard 62.1. RP-1747 is under
way and should provide a detailed procedure. In the meantime,
sequences have been included at the zone level, matching California’s
DCV approach as a first step. Because outdoor air rates at the AHU
level dynamically calculate outdoor air rates using the Standard 62.1
multiple spaces procedure, compliance with the standard is assured.
Doing no DCV at all is not an option because it is required by Standard
90.1-2016.
4) For cooling-only VAV terminal units, reheat VAV terminal units, constant
volume series fan powered terminal units, dual duct VAV terminal units with
mixing control and inlet airflow sensors, dual duct VAV terminal units with
mixing control and a discharge airflow sensor, or dual duct VAV terminal units
with cold duct minimum control:
(a) The CO2 control loop output shall reset both the occupied minimum airflow
setpoint (Vmin*) and the population component of the required breathing
zone outdoor airflow (Vbz-P*) in parallel. Vmin* shall be reset from the
zone minimum airflow setpoint Vmin at 0% loop output up to maximum
cooling airflow setpoint Vcool-max at 100% loop output. Vbz-P* shall be
reset from 0 cfm at 0% loop output up to the Vbz-P at 100% loop output.
Vcool-max
Vbz-P
Vmin*
Vmin*
Vbz-P*
Vbz-P*
Vmin
0
0% 50% 100%
CO2 Control Loop
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 46
The CO2 control loop graph above is provided as a visual
representation of the reset logic and is not representative of
magnitude of Vbz-P* in relation to Vbz-A or Vmin*.
5) For parallel fan powered terminal units:
(a) Determine VCO2-max as follows:
(1) When the zone state is cooling, VCO2-max is equal to the maximum
cooling airflow setpoint Vcool-max.
(2) When the zone state is heating or deadband, VCO2-max is equal to
Vcool-max minus the parallel fan airflow
This logic prevents the total supply airflow from exceeding Vcool-max,
which could create diffuser noise problems.
(b) The CO2 control loop output shall reset both the occupied minimum airflow
setpoint (Vmin*) and the population component of the required breathing
zone outdoor airflow (Vbz-P*) in parallel. Vmin* shall be reset from the
zone minimum airflow setpoint Vmin at 0% loop output up to maximum
cooling airflow setpoint VCO2-max at 100% loop output. Vbz-P* shall be
reset from 0 cfm at 0% loop output up to the Vbz-P at 100% loop output.
VCO2-max
Vbz-P
Vmin*
Vmin*
Vbz-P*
Vbz-P*
Vmin
0
0% 50% 100%
CO2 Control Loop
The CO2 control loop graph above is provided as a visual
representation of the reset logic and is not representative of
magnitude of Vbz-P* in relation to Vbz-A or Vmin*.
6) For single zone VAV air handling units:
(a) The minimum outdoor air setpoint MinOAsp is equal to Voz. The CO2
control loop output shall reset the population component of the required
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 47
breathing zone outdoor airflow Vbz-P* from 0 cfm at 0% loop output up to
Vbz-P at 100% loop output.
Vbz-P
Vbz-P*
Vbz-P*
0
0% 50% 100%
CO2 Control Loop
The following subsection “5.2.1.4” should be used for ventilation logic that complies with
California Title 24. If instead the project is to comply with Standard 62.1 ventilation
requirements, delete subsection “5.2.1.4”and use subsection “5.2.1.3.”
5.2.1.4. For compliance with California Title 24, outdoor air setpoints shall be calculated as
follows:
2. Determine the zone minimum outdoor air setpoints Zone-Abs-OA-min and Zone-
Des-OA-min.
Zone-Abs-OA-min is used in terminal unit sequences and air handler sequences. Zone-
Des-OA-min is used in air handler sequences only.
1) Zero if the zone has a window switch and the window is open
2) 25% of Varea-min if the zone has an occupancy sensor and is unpopulated
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 48
The term “populated” is used instead of “occupied” to mean that a zone
occupancy sensor senses the presence of people because the term
“occupied” is used elsewhere to mean “scheduled to be occupied”.
a. If the zone has an occupancy sensor, Vmin* shall be equal to 25% of Varea-min
when the room is unpopulated.
b. If the zone has a window switch, Vmin* shall be zero when the window is open.
b. During Occupied Mode, a P-only loop shall maintain CO2 concentration at setpoint;
reset from 0% at (setpoint minus 200 PPM) and to 100% at setpoint.
c. Loop is disabled and output set to zero when the zone is not in Occupied Mode.
d. For cooling-only VAV terminal units, reheat VAV terminal units, constant volume
series fan powered terminal units, dual duct VAV terminal units with mixing
control and inlet airflow sensors, dual duct VAV terminal units with mixing control
and a discharge airflow sensor, or dual duct VAV terminal units with cold duct
minimum control:
1) The CO2 control loop output shall reset the occupied minimum airflow setpoint
(Vmin*) from the zone minimum airflow setpoint Vmin at 0% up to maximum
cooling airflow setpoint Vcool-max at 50%, as shown below. The loop output
from 50% to 100% will be used at the system level to reset outdoor air minimum;
see AHU controls.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 49
Vcool
-max
Vmin*
Vmin
0% 50% 100%
CO2 Control Loop
e. For parallel fan powered terminal units:
This logic prevents the total supply airflow from exceeding Vcool-max,
which could create diffuser noise problems.
2) The CO2 control loop output shall reset the occupied minimum airflow setpoint
(Vmin*) from the zone minimum airflow setpoint Vmin at 0% up to maximum
cooling airflow setpoint VCO2-max at 50%, as shown below. The loop output
from 50% to 100% will be used at the system level to reset outdoor air minimum;
see AHU controls.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 50
VCO2
-max
Vmin*
Vmin
0% 50% 100%
CO2 Control Loop
f. For single zone VAV air handling units:
1) The minimum outdoor air setpoint MinOAsp shall be reset based on the zone
CO2 control loop signal from Zone-Abs-OA-min at 0% signal to Zone-Des-OA-
min at 100% signal.
Zone-Des-
OA-min
MinOAsp
Zone-Abs-
OA-min
0% 50% 100%
CO2 Control Loop
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 51
This concludes the section where the ventilation logic is selected.
When the sequences are complete, only one of subsection “5.2.1.3” and subsection “5.2.1.4”
above should remain. The other subsection should be deleted, along with these flag notes.
5.2.2. Time-Averaged Ventilation (TAV)
ASHRAE Standard 62.1 and Title 24 allow for ventilation to be provided based on
average conditions over a specific period of time. This time-averaging method allows
for zone airflows to effectively be controlled to values below the VAV box controllable
minimum value, which may reduce energy use and the risk of overcooling when the zone
ventilation requirement is less than the VAV box controllable minimum.
5.2.2.1. When the active airflow setpoint (Vspt) is non-zero and is less than the lowest possible
airflow setpoint allowed by the controls (Vm), the airflow setpoint shall be pulse width
modulated as follows:
3. Open period: During the open period, the TAV airflow setpoint (Vspt*) shall be equal
to Vm for a period of time, OP, which is the larger of:
a. 1.5 minutes or
4. Closed Period: During the closed period, Vspt* shall be set to 0 for a period of time,
CP, where CP = TCT – OP. The VAV damper control loop shall be disabled with
output set equal to 0 during the closed period. At the end of each closed period, the
VAV damper shall be commanded to the last position from the previous open period
prior to re-enabling the control loop.
5. During TAV mode, each cycle shall consist of an open and closed period which
alternate until Vspt is greater than Vm.
The following logic ensures that multiple zones do not enter TAV mode at the same time,
avoiding the synchronized opening and closing of VAV dampers
6. When first entering TAV mode, start with an initial open period of duration
RNDM*OP, where RNDM is a random number between 0.0 and 1.0
5.2.2.2. The VAV damper shall be modulated by a control loop to maintain the measured airflow
at the active setpoint of Vspt* when in TAV Mode, or otherwise Vspt.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 52
5.3 Generic Thermal Zones
5.3.1. This section applies to all single zone systems and sub-zones of air handling systems, such
as VAV boxes, fan-powered boxes, etc.
5.3.2. Setpoints
5.3.2.1. Each zone shall have separate occupied and unoccupied heating and cooling setpoints.
5.3.2.2. The active setpoints shall be determined by the Operating Mode of the Zone Group [see
5.4.6].
1. The setpoints shall be the occupied setpoints during Occupied Mode, Warm up Mode,
and Cool-down Mode.
2. The setpoints shall be the unoccupied setpoints during Unoccupied Mode, Setback
Mode, and Setup Mode.
1. The heating setpoint from exceeding the cooling setpoint minus 0.5°C (1°F) (i.e., the
minimum difference between heating and cooling setpoints shall be 0.5°C (1°F)).
2. The unoccupied heating setpoint from exceeding the occupied heating setpoint; and
3. The unoccupied cooling setpoint from being less than the occupied cooling setpoint.
1. The setpoint adjustment offsets established by the occupant shall be software points
that are persistent (e.g., not reset daily), but the actual offset used in control logic shall
be adjusted based on limits and modes as describe below.
a. As a default, the active occupied cooling setpoint shall be limited between 22°C
(72°F) and 27°C (80°F).
b. As a default, the active occupied heating setpoint shall be limited between 18°C
(65°F) and 22°C (72°F).
3. The active heating and cooling setpoints shall be independently adjustable, respecting
the limits and anti-overlap logic described above. If zone thermostat provides only a
single setpoint adjustment, then the adjustment shall move both the active heating and
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 53
cooling setpoints upwards or downwards by the same amount, within the limits
described above.
4. The adjustment shall only affect occupied setpoints in Occupied Mode, Warmup
Mode, and Cool-down Mode and shall have no impact on setpoints in all other modes.
5. At the onset of demand limiting, the local setpoint adjustment value shall be frozen.
Further adjustment of the setpoint by local controls shall be suspended for the duration
of the demand limit event.
Demand limits can be triggered for different reasons, including: initiating utility
demand shed events; exceeding a predefined threshold; or to prevent excessive rates in
a ratchet schedule. Additional logic (not provided here) is needed to define the Demand
Limit Levels.
For example:
• Sliding Window: The demand control function shall utilize a sliding window
method selectable in increments of one minute, up to 60 minutes, 15-minute
default.
• Demand Limit Levels: Demand time periods shall be set up as per utility rate
schedule. For each On-Peak or Partial-Peak period, three demand limits can
be defined. When the measured demand exceeds the limit, the Demand Limit
Level switch for that level shall be set; when demand is less than 10% below
the limit for a minimum of 15 minutes, and the time is no longer within the On-
Peak or Partial-Peak window, the switch shall be reset. These levels are used
at the zone level (see Zone Control sequences) to shed demand.
An override for critical zones like data centers or equipment rooms should be provided
through the GUI. This override feature should require some level of supervision so that
all zones do not declare themselves “critical.”
Demand limits can also be simultaneously applied to lighting for systems with
daylighting/dimming capability and that are integrated with the HVAC BAS.
5.3.2.5. Cooling Demand Limit Setpoint Adjustment: The active cooling setpoints for all zones
shall be increased when a demand limit is imposed on the associated Zone Group. The
operator shall have the ability to exempt individual zones from this adjustment through
the normal BAS user interface. Changes due to demand limits are not cumulative.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 54
5.3.2.6. Heating Demand Limit Setpoint Adjustment: The active heating setpoints for all zones
shall be decreased when a demand limit is imposed on the associated Zone Group. The
operator shall have the ability to exempt individual zones from this adjustment through
the normal BAS user interface. Changes due to demand limits are not cumulative.
Heating Demand Limits may be desirable in buildings with electric heat or heat pumps,
or in regions with limited gas distribution infrastructure.
5.3.2.7. Window switches. For zones that have operable windows with indicator switches, when
the window switch indicates the window is open, the heating setpoint shall be
temporarily set to 4°C (40°F) and the cooling setpoint shall be temporarily set to 49°C
(120°F). When the window switch indicates that the window is open during other than
Occupied Mode, a Level 4 alarm shall be generated.
1. When the switch indicates that the space has been unpopulated for 5 minutes
continuously during the Occupied Mode, the active heating setpoint shall be
decreased by 0.5°C (1°F) and the cooling setpoint shall be increased by 0.5°C (1°F).
2. When the switch indicates that the space has been populated for one minute
continuously, the active heating and cooling setpoints shall be restored to their
previous values.
Occupancy sensors are often provided as part of the lighting control system due
to Standard 90.1 and Title 24 requirements. The point can be tied into the HVAC
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 55
BAS in several ways to avoid the cost of an additional occupancy sensor,
including:
• If the occupancy sensor is an addressable point and the lighting controls
have BACnet or other interface capability, the point can be mapped to the
BAS via this interface.
• Some occupancy sensors include auxiliary dry contacts that can be wired to
a digital input at the zone controller.
5.3.2.9. Hierarchy of Setpoint Adjustments: The following adjustment restrictions shall prevail
in order from highest to lowest priority:
3. Window switches
4. Demand limit
b. Local setpoint adjustment: Any changes to setpoint by local adjustment are frozen
at the onset of the demand limiting event and remain fixed for the duration of the
event. Additional local adjustments are ignored for the duration of the demand
limiting event.
5.3.3. Local override: When thermostat override buttons are depressed, the call for Occupied
Mode operation shall be sent up to the Zone Group control for 60 minutes.
Local overrides will cause all zones in the Zone Group to operate in Occupied Mode
to ensure that the system has adequate load to operate stably.
5.3.4.1. Two separate control loops shall operate to maintain space temperature at setpoint, the
Cooling Loop and the Heating Loop.
1. The Heating Loop shall be enabled whenever the space temperature is below the
current zone heating setpoint temperature, and disabled when space temperature is
above the current zone heating setpoint temperature and the Loop output is zero for
30 seconds. The Loop may remain active at all times if provisions are made to
minimize integral windup.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 56
2. The Cooling Loop shall be enabled whenever the space temperature is above the
current zone cooling setpoint temperature, and disabled when space temperature is
below the current zone cooling setpoint temperature and the Loop output is zero for
30 seconds. The Loop may remain active at all times if provisions are made to
minimize integral windup.
5.3.4.2. The Cooling Loop shall maintain the space temperature at the active cooling setpoint.
The output of the loop shall be a software point ranging from 0% (no cooling) to 100%
(full cooling).
5.3.4.3. The Heating Loop shall maintain the space temperature at the active heating setpoint.
The output of the loop shall be a software point ranging from 0% (no heating) to 100%
(full heating).
5.3.4.4. Loops shall use proportional + integral logic or other technology with similar
performance. Proportional-only control is not acceptable, although the integral gain
shall be small relative to the proportional gain. P and I gains shall be adjustable by the
operator.
5.3.4.5. See other sections for how the outputs from these loops are used.
5.3.5.1. Heating: when the output of the space heating control loop is nonzero and the output of
the cooling loop is equal to zero.
5.3.5.2. Cooling: when the output of the space cooling control loop is nonzero and the output of
the heating loop is equal to zero.
a. If the zone is 2°C (3°F) above cooling setpoint for 10 minutes, generate Level 3
alarm.
b. If the zone is 3°C (5°F) above cooling setpoint for 10 minutes, generate Level 2
alarm.
a. If the zone is 2°C (3°F) below heating setpoint for 10 minutes, generate Level 3
alarm.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 57
b. If the zone is 3°C (5°F) below heating setpoint for 10 minutes, generate Level 2
alarm.
Default time delay for zone temperature alarm (10 minutes) is intentionally long, to
minimize nuisance alarms. For critical zones such as IT closets, consider reducing time
delay or setting delay to zero.
Zone alarms are not suppressed in Setup, Setback, or Unoccupied Modes so that you detect heating
or cooling equipment or control failures that could result in excessive pull down or pick up loads
and even freezing of pipes if left undetected. See Paragraph 5.4.6 for description of Zone Group
Operating Modes.
1. CO2 sensors: If the CO2 concentration is less than 300 ppm, or the zone is in
Unoccupied Mode for more than 2 hours and zone CO2 concentration exceeds 600
ppm, generate a Level 3 alarm. The alarm text shall identify the sensor and indicate
that it may be out of calibration.
2. If the CO2 concentration exceeds setpoint plus 10% for more than 10 minutes,
generate a Level 3 alarm.
Zone Scheduling Groups, or Zone Groups, are sets of zones served by a single air handler
that operate together for ease of scheduling and/or in order to ensure sufficient load to
maintain stable operation in the upstream equipment. A Zone Group is equivalent to an
Isolation Area as defined in Section 6.4.3.3.4 of ASHRAE 90.1 2016. (We chose to use a
different term because “Isolation Area” seemed to cause confusion, or suggest isolation
e.g., as one would find in a hospital setting.)
5.4.1. Each system shall be broken into separate Zone Groups composed of a collection of one
or more zones served by a single air handler. See 3.1.3 for zone group assignments.
5.4.2. Each Zone Group shall be capable of having separate occupancy schedules and Operating
Modes from other Zone Groups.
Note that, from the user’s point of view, schedules can be set for individual zones, or
they can be set for an entire Zone Group, depending on how the user interface is
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 58
implemented. From the point of view of the BAS, individual zone schedules are
superimposed to create a Zone Group schedule, which then drives system behavior.
The schedule may govern operation of other integrated systems such as lights,
daylighting, or others, in addition to the HVAC system.
5.4.3. All zones in each Zone Group shall be in the same Zone Group Operating Mode as defined
in Paragraph 5.4.6. If one zone in a Zone Group is placed in any Zone Group Operating
Mode other than Unoccupied Mode (due to override, sequence logic, or scheduled
occupancy) all zones in that Zone Group shall enter that mode.
5.4.4. A Zone Group may be in only one mode at any given time.
5.4.5. For each Zone Group, provide a set of testing/commissioning software switches that
override all zones served by the Zone Group. Provide a separate software switch for each
of the zone-level override switches listed under “Testing and Commissioning Overrides”
in terminal unit sequences. When the value of a Zone Group’s override switch is changed,
the corresponding override switch for every zone in the Zone Group shall change to the
same value. Subsequently, the zone-level override switch may be changed to a different
value. The value of the zone-level switch has no effect on the value of the Zone Group
switch, and the value of the Zone Group switch only affects the zone-level switches when
the Zone Group switch is changed.
The Testing and Commissioning Overrides will be specified for each type of terminal
unit and system in subsequent sequences. These overrides allow a commissioning agent
to e.g., force a zone into cooling, or drive a valve all the way open or closed.
Zone Group override switches allow a commissioning agent to apply a zone-level
override to all zones in a Zone Group simultaneously. This greatly accelerates the
testing and commissioning process.
5.4.6. Zone Group Operating Modes: Each Zone Group shall have the following modes:
The modes presented in this section are to enable different setpoints and ventilation
requirements to be applied to Zone Groups based on their operating schedule,
occupancy status, and deviation from current setpoint.
See ASHRAE Guideline 13 for best practices in locating zone group operating mode
programming logic based on network architecture.
5.4.6.1. Occupied Mode: A Zone Group is in the Occupied Mode when any of the following is
true:
1. The time of day is between the Zone Group’s scheduled occupied start and stop times.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 59
2. The schedules have been overridden by the Occupant Override System.
3. Any zone local override timer (initiated by local override button) is nonzero.
5.4.6.2. Warmup Mode: For each zone, the BAS shall calculate the required warm up time
based on the zone’s occupied heating setpoint, the current zone temperature, the outdoor
air temperature, and a mass/capacity factor for each zone. Zones where the window
switch indicates that a window is open shall be ignored. The mass factor shall be
manually adjusted or self-tuned by the BAS. If automatic, the tuning process shall be
turned on or off by a software switch, to allow tuning to be stopped after the system has
been trained. Warmup Mode shall start based on the zone with the longest calculated
warm up time requirement, but no earlier than 3 hours before the start of the scheduled
occupied period, and shall end at the scheduled Occupied start hour.
5.4.6.3. Cool-Down Mode: For each zone, the BAS shall calculate the required cool down time
based on the zone’s occupied cooling setpoint, the current zone temperature, the outdoor
air temperature, and a mass/capacity factor for each zone. Zones where the window
switch indicates that a window is open shall be ignored. The mass factor shall be
manually adjusted or self-tuned by the BAS. If automatic, the tuning process shall be
turned on or off by a software switch, to allow tuning to be stopped after the system has
been trained. Cool-down Mode shall start based on the zone with the longest calculated
cool-down time requirement, but no earlier than 3 hours before the start of the scheduled
occupied period, and shall end at the scheduled Occupied start hour.
Warmup and Cool-Down Modes are used to bring the Zone Groups up to temperature
based on their scheduled occupancy period. The algorithms used in these modes (often
referred to as “Optimal Start”) predict the shortest time to achieve occupied setpoint
to reduce the central system energy use based on past performance.
We recommend using a global outdoor air temperature, not associated with any AHU,
to determine Warmup start time. This is because unit-mounted OA sensors, which are
usually placed in the outdoor air intake stream, are often inaccurate (reading high)
when the unit is off due to air leakage from the space through the OA damper.
5.4.6.4. Setback Mode: During Unoccupied Mode, if any 5 zones (or all zones, if fewer than 5)
in the Zone Group fall below their unoccupied heating setpoints or if the average zone
temperature of the Zone Group falls below the average unoccupied heating setpoint, the
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 60
Zone Group shall enter Setback Mode until all spaces in the Zone Group are 1°C (2°F)
above their unoccupied setpoints.
5.4.6.5. Freeze Protection Setback Mode: During Unoccupied Mode, if any single zone falls
below 4°C (40°F), the Zone Group shall enter Setback Mode until all zones are above
7°C (45°F), and a Level 3 alarm shall be set.
5.4.6.6. Setup Mode: During Unoccupied Mode, if any 5 zones (or all zones, if fewer than 5) in
the Zone rise above their unoccupied cooling setpoints or if the average zone
temperature of the Zone Group rises above the average unoccupied cooling setpoint, the
Zone Group shall enter Setup Mode until all spaces in the Zone Group are 1°C (2°F)
below their unoccupied setpoints. Zones where the window switch indicates that a
window is open shall be ignored.
Setback and Setup Modes are used to keep zone temperatures (and mass) from getting
excessively far from occupied setpoints so that the Cool-Down and Warmup Modes can
achieve setpoint when initiated. The minimum number of zones (set at 5 here) are to
ensure that the central systems (fans, pumps, heating sources, or cooling sources) can
operate stably. Obviously, the size of the zones and the characteristics of the central
systems are a factor in choosing the correct number of zones in each group.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 61
5.4.6.7. Unoccupied Mode: When the Zone Group is not in any other mode.
5.5.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.5.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
CO2 DCV for cooling-only zones can lead to over-cooling due to the faster rise in
CO2 levels from people in the room vs. the increase in cooling loads from people.
Including heat in all zones with CO2 DCV is therefore recommended.
5.5.3. See 3.1.2.1 for zone minimum airflow setpoint Vmin and zone cooling maximum design
airflow setpoint Vcool-max.
If the minimum ventilation rate is more than 25% or so of the cooling maximum, or demand
control ventilation is used, a reheat box is recommended to avoid overcooling. Demand
control ventilation logic is not provided for cooling-only boxes because doing so results in
periods of overcooling since the CO2 levels due to occupants rises much faster than the
cooling load due to occupants because of thermal mass.
5.5.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
Heating
Vmin* 0 0 0 0 0
maximum
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 62
5.5.5. Control logic is depicted schematically in the figure below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
Cooling
Maximum
Active Airflow
Setpoint, Vspt
Vmin*
5.5.5.1. When the Zone State is Cooling, the Cooling Loop output shall be mapped to the active
airflow setpoint from the minimum to the cooling maximum airflow setpoints.
1. If supply air temperature from the air handler is greater than room temperature,
cooling supply airflow setpoint shall be no higher than the minimum.
5.5.5.2. When the Zone State is Deadband or Heating, the active airflow setpoint shall be the
minimum airflow setpoint.
5.5.6. The VAV damper shall be modulated by a control loop to maintain the measured airflow
at the active setpoint.
5.5.7. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 63
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
5.5.7.2. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.5.7.3. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the zone
is proven on, generate a Level 4 alarm.
5.5.8.5. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
5.5.9. System Requests
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 64
5.5.9.2. Static Pressure Reset Requests
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the damper position is greater than 95%, send 1 Request until the damper
position is less than 85%,
If the minimum ventilation rate is more than 25% or so of the cooling maximum, or demand
controlled ventilation is used, a reheat box is recommended to avoid overcooling.
5.6.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.6.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.6.3. See 3.1.2.23.1.2.2.5 for zone minimum airflow setpoints Vmin, zone maximum
cooling airflow setpoint Vcool-max, zone maximum heating design airflow setpoint
Vheat-max, and the maximum discharge air temperature rise above heating setpoint,
MaxΔT.
5.6.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Cooling
Vmin* 0 0 0 0 0
minimum
Minimum Vmin* 0 0 0 0 0
Heating Max(Vheat-
Vheat-min 0 Vheat-max Vheat-max 0
minimum min, Vmin*)
Heating Max(Vheat-
Vheat-max 0 Vcool-max Vcool-max 0
maximum max, Vmin*)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 65
These sequences use different maximum airflow setpoints for heating and cooling. This
“dual max” logic allows the minimum airflow setpoint to be lower than in a
conventional sequence where the minimum airflow equals the heating airflow.
Heating is non-zero in Cool-down to allow for individual zones within a Zone Group
that may need heating while the Zone Group is in Cool-down.
The Warmup and Setback minimum setpoint is set to zero to ensure spaces that do not
want heat during these modes receive no air; since the supply air temperature can be
warm in these modes if the AHU has a heating coil, any minimum could cause
overheating. The heating minimum is set to Vheat-max and the heating maximum is
set to Vcool-max to provide faster response. This also ensures non-zero flow for the
first half of the heating loop, avoiding instabilities.
5.6.5. Control logic is depicted schematically in the figure below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
Cooling Maximum
Airflow
Max
DAT
5.6.5.1. When the Zone State is Cooling, the Cooling Loop output shall be mapped to the airflow
setpoint from the cooling minimum to the cooling maximum airflow setpoints. Heating
coil is disabled unless the discharge air temperature is below the minimum setpoint [see
5.6.5.4 below].
1. If supply air temperature from the air handler is greater than room temperature,
cooling supply airflow setpoint shall be no higher than the minimum.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 66
5.6.5.2. When the Zone State is Deadband, the active airflow setpoint shall be the minimum
airflow setpoint. Heating coil is disabled unless the discharge air temperature is below
the minimum setpoint [see 5.6.5.4 below].
5.6.5.3. When the Zone State is Heating, the Heating Loop shall maintain space temperature at
the heating setpoint as follows:
The purpose of the following heating sequence is to minimize the reheat energy
consumption by first increasing the SAT while maintaining minimum flow, and only
increasing the total airflow if needed to satisfy the zone.
1. From 0-50%, the Heating Loop output shall reset the discharge temperature setpoint
from the current AHU SAT setpoint to a maximum of MaxΔT above space
temperature setpoint. The airflow setpoint shall be the heating minimum.
2. From 51%-100%, if the discharge air temperature is greater than room temperature
plus 3°C (5°F), the Heating Loop output shall reset the airflow setpoint from the
heating minimum airflow setpoint to the heating maximum airflow setpoint.
3. The heating coil shall be modulated to maintain the discharge temperature at setpoint.
(Directly controlling heating off the zone temperature control loop is not acceptable).
a. When the airflow setpoint is pulse width modulated per 5.2.2, the heating coil and
PID loop shall be disabled with output set to 0 during closed periods.
5.6.5.4. In Occupied Mode, the heating coil shall be modulated to maintain a discharge air
temperature no lower than 10°C (50°F).
This prevents excessively cold discharge air temperatures if the AHU is providing high
outdoor airflows and does not have a heating coil.
5.6.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 67
5.6.6.2. Low discharge air temperature
1. If heating hot water plant is proven on and the discharge air temperature is 8°C (15°F)
less than setpoint for 10 minutes, generate a Level 3 alarm.
2. If heating hot water plant is proven on and the discharge air temperature is 17°C
(30°F) less than setpoint for 10 minutes, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its Hot Water reset
Trim & Respond control loop, low discharge air temperature alarms shall be
suppressed for that zone.
5.6.6.3. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.6.6.4. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the zone
is proven on, generate a Level 4 alarm.
5.6.6.5. Leaking valve. If the valve position is 0% for 15 minutes, discharge air temperature is
above AHU SAT by 3°C (5°F), and the fan serving the zone is proven on, generate a
Level 4 alarm.
5.6.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 68
Per 5.1.10, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the damper position is greater than 95%, send 1 Request until the damper
position is less than 85%,
1. If the discharge air temperature is 17°C (30°F) less than setpoint for 5 minutes, send
3 Requests,
2. Else if the discharge air temperature is 8°C (15°F) less than setpoint for 5 minutes,
send 2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 69
5.6.8.4. If there is a hot water coil and a heating hot water plant, Heating Hot Water Plant
Requests. Send the heating hot water plant that serves the zone a Heating Hot Water
Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
5.7.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.7.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.7.3. See 3.1.2.2.5 for zone minimum airflow setpoint Vmin, and zone maximum cooling airflow
setpoint Vcool-max, and the maximum discharge air temperature rise above heating
setpoint, MaxΔT..
5.7.4. Active maximum and minimum primary air setpoints shall vary depending on the Mode of
the Zone Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 70
5.7.5. Control logic is depicted schematically in the figure below and described in the following
sections. In the charts below, OA-min is Voz (if using ASHRAE Standard 62.1 ventilation
logic) or Zone-Abs-OA-min (if using Title 24 ventilation logic).
OA-min
Minimum
Primary
Airflow
Setpoint
Minimum
Primary
Airflow
Setpoint
OA-min
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 71
5.7.5.1. When the Zone State is Cooling
1. The Cooling Loop output shall be mapped to the primary airflow setpoint from the
minimum to the cooling maximum airflow setpoints.
a. If supply air temperature from the air handler is greater than room temperature,
cooling supply airflow setpoint shall be no higher than the minimum.
1. As the Heating Loop output increases from 0 to 100%, it shall reset the discharge
temperature from the current AHU SAT setpoint to a maximum of MaxΔT above
space temperature setpoint.
Standard 90.1-2016 limits overhead supply air to 11°C (20°F) above space
temperature (e.g., 32°C (90°F) at 21°C (70°F) space temperature setpoint) to
minimize stratification.
2. The heating coil shall be modulated to maintain the discharge temperature at setpoint.
(Directly controlling heat off zone temperature control loop is not acceptable).
5.7.5.4. The VAV damper shall be modulated to maintain the measured primary airflow at
setpoint.
3. If ventilation is according to California Title 24, fan shall run in Deadband and
Cooling when the primary air volume is less than Zone-Abs-OA-min for one minute,
and shall shut off when primary air volume is above Zone-Abs-OA-min by 10% for
3 minutes.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 72
The designer must ensure that the sum of the indirect ventilation provided by the
fan plus the ventilation provided by the primary air at minimum setpoint meet
Standard 62.1 requirements.
5.7.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
1. If heating hot water plant is proven on and the discharge air temperature is 8°C (15°F)
less than setpoint for 10 minutes, generate a Level 3 alarm.
2. If heating hot water plant is proven on and the discharge air temperature is 17°C
(30°F) less than setpoint for 10 minutes, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its Hot Water reset
Trim & Respond control loop, low discharge air temperature alarms shall be
suppressed for that zone.
5.7.6.3. Fan alarm is indicated by the status input being different from the output command after
a period of 15 seconds after a change in output status.
5.7.6.4. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.7.6.5. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the zone
is proven on, generate a Level 4 alarm.
5.7.6.6. Leaking valve. If the valve position is 0% for 15 minutes, discharge air temperature is
above AHU SAT by 3°C (5°F), and the fan serving the zone is proven on, generate a
Level 4 alarm.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 73
5.7.7. Testing/Commissioning Overrides: Provide software switches that interlock to a system
level point to
5.7.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below)
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 74
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the discharge air temperature is 17°C (30°F) less than setpoint for 5 minutes, send
3 Requests,
2. Else if the discharge air temperature is 8.3°C (15°F) less than setpoint for 5 minutes,
send 2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
5.7.8.4. If there is a hot water coil and a heating hot water plant, Heating Hot Water Plant
Requests. Send the heating hot water plant that serves the zone a Heating Hot Water
Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
5.8.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.8.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.8.3. See 3.1.2.4 for zone minimum airflow setpoint Vmin, zone maximum cooling airflow
setpoint Vcool-max, the parallel fan maximum heating airflow setpoint Pfan-htgmax, and
the maximum discharge air temperature rise above heating setpoint, MaxΔT.
5.8.4. Pfan-z is the lowest rate the fan will operate at when it is turned on but has the lowest
possible speed signal from the BAS.
5.8.5. Active maximum and minimum primary air setpoints shall vary depending on the Mode of
the Zone Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 75
Control logic is depicted schematically in the figure below and described in the
following sections. Relative levels of various setpoints are depicted for Occupied
Mode operation. In the chart below, OA-min is Voz (if using ASHRAE Standard 62.1
ventilation logic) or Zone-Abs-OA-min (if using Title 24 ventilation logic).
In the heating zone state, the logic keeps the fan airflow rate low while supply air
temperature is increased as the first heating stage. This presumes that the temperature
of the air the fan is supplying is neutral or below the space temperature, as it would be
if the fan draws air directly from the space and as it might be if the fan draws air from
a return air plenum that is cooled by roof and wall heat losses. In the past, return air
plenums were warmed by recessed light fixtures, but pendent lights are more and more
common, so the potential for “free” heating from the plenum is smaller than it once
was. Since there is the potential that the plenum is colder than the space due to
envelope loads, the logic leads with the supply air temperature rather than with an
increase in fan speed. If the designer is confident that the plenum will always be
warmer, the logic can be reversed.
Cooling Maximum
Discharge Air
Temperature
Setpoint
Total CFM
(not directly controlled)
Pfan-htgmax
OA-min
Parallel Fan
Airflow Setpoint
Active Primary
Minimum Airflow
Airflow Setpoint, Vspt
Setpoint
Pfan-z
1. The Cooling Loop output shall be mapped to the airflow setpoint from the minimum
to the cooling maximum airflow setpoints.
a. If supply air temperature from the air handler is greater than room temperature,
cooling supply airflow setpoint shall be no higher than the minimum.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 76
2. Heating coil is off.
4. If ventilation is according to California Title 24: In Occupied Mode only, parallel fan
starts when primary airflow drops below Zone-Abs-OA-min minus one half of Pfan-
z and shuts off when primary airflow rises above Zone-Abs-OA-min. Fan airflow
rate setpoint is equal to Zone-Abs-OA-min minus the current primary airflow
setpoint.
The designer must ensure that the sum of the indirect ventilation provided by the
fan plus the ventilation provided by the primary air at minimum setpoint meet
Standard 62.1 requirements.
4. If ventilation is according to California Title 24: In Occupied Mode only, parallel fan
runs if primary airflow setpoint is below Zone-Abs-OA-min. Fan airflow rate setpoint
is equal to Zone-Abs-OA-min minus the current primary airflow setpoint.
The designer must ensure that the sum of the indirect ventilation provided by the
fan plus the ventilation provided by the primary air at minimum setpoint meet
Standard 62.1 requirements.
For systems with electric reheat, ensure that the minimum airflow provided by the
parallel fan at minimum speed exceeds the minimum required airflow for the
electric heater.
2. From 0-50%, the Heating Loop output shall reset the discharge temperature from the
current AHU SAT setpoint to a maximum of MaxΔT above space temperature
setpoint.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 77
Standard 90.1-2016 limits overhead supply air to 11°C (20°F) above space
temperature (e.g., 32°C (90°F) at 21°C (70°F) space temperature setpoint) to
minimize stratification.
3. From 50%-100%, the Heating Loop output shall reset the parallel fan airflow setpoint
from the airflow setpoint required in Deadband (see above; this is Pfan-z if Deadband
setpoint is less than Pfan-z) proportionally up to the maximum heating fan airflow
setpoint (Pfan-htgmax).
5.8.5.4. The heating coil shall be modulated to maintain the discharge temperature at setpoint.
(Directly controlling heating off zone temperature control loop is not acceptable).
5.8.5.5. The VAV damper shall be modulated to maintain the measured primary airflow at the
primary airflow setpoint.
5.8.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
1. If heating hot water plant is proven on and the discharge air temperature is 8.3°C
(15°F) less than setpoint for 10 minutes, generate a Level 3 alarm.
2. If heating hot water plant is proven on and the discharge air temperature is 17°C
(30°F) less than setpoint for 10 minutes, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its Hot Water reset
Trim & Respond control loop, low discharge air temperature alarms shall be
suppressed for that zone.
5.8.6.3. Fan alarm is indicated by the status input being different from the output command after
a period of 15 seconds after a change in output status.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 78
5.8.6.4. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.8.6.5. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while fan serving the zone is
proven on, generate a Level 4 alarm.
5.8.6.6. Leaking valve. If the valve position is 0% for 15 minutes and discharge air temperature
is above AHU SAT by 3°C (5°F), generate a Level 4 alarm.
5.8.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 79
4. Else if the Cooling Loop is less than 95%, send 0 Requests
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the discharge air temperature is 17°C (30°F) less than setpoint for 5 minutes, send
3 Requests,
2. Else if the discharge air temperature is 8.3°C (15°F) less than setpoint for 5 minutes,
send 2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
5.8.8.4. If there is a hot water coil and a heating hot water plant, Heating Hot Water Plant
Requests. Send the heating hot water plant that serves the zone a Heating Hot Water
Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 80
5.9 Series Fan-Powered Terminal Unit, Constant Volume Fan
5.9.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.9.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.9.3. See 3.1.2.5 for zone minimum airflow setpoints Vmin, zone maximum cooling airflow
setpoint Vcool-max, and the maximum discharge air temperature rise above heating
setpoint, MaxΔT.
5.9.4. Active maximum and minimum primary air setpoints shall vary depending on the Mode of
the Zone Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
5.9.5. Control logic is depicted schematically in the figure below and described in the following
sections.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 81
5.9.5.1. When the Zone State is Cooling
1. The Cooling Loop output shall be mapped to the primary airflow setpoint from the
minimum to the cooling maximum airflow setpoints.
a. If supply air temperature from the air handler is greater than room temperature,
cooling supply airflow setpoint shall be no higher than the minimum.
Standard 90.1-2016 limits overhead supply air to 11°C (20°F) above space
temperature (e.g., 32°C (90°F) at 21°C (70°F) space temperature setpoint) to
minimize stratification.
1. The Heating Loop shall reset the discharge temperature from the current AHU SAT
setpoint to a maximum of MaxΔT above space temperature setpoint.
2. The heating coil shall be modulated to maintain the discharge temperature at setpoint.
(Directly controlling heating off zone temperature control loop is not acceptable).
5.9.5.4. The VAV damper shall be modulated to maintain the measured airflow at setpoint.
5.9.5.5. Fan Control: Fan shall run whenever zone is in Heating or Cooling Zone State, or if the
associated Zone Group is in Occupied Mode. Prior to starting the fan, the damper is
first driven fully closed to ensure that the fan is not rotating backwards. Once the fan
is proven on for a fixed time delay (15 seconds), the damper override is released.
5.9.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 82
5.9.6.2. Low Discharge Air Temperature
1. If heating hot water plant is proven on and the discharge air temperature is 8.3°C
(15°F) less than setpoint for 10 minutes, generate a Level 3 alarm.
2. If heating hot water plant is proven on and the discharge air temperature is 17°C
(30°F) less than setpoint for 10 minutes, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its Hot Water reset
Trim & Respond control loop, low discharge air temperature alarms shall be
suppressed for that zone.
5.9.6.3. Fan alarm is indicated by the status input being different from the output command after
a period of 15 seconds after a change in output status.
5.9.6.4. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.9.6.5. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the zone
is proven on, generate a Level 4 alarm.
5.9.6.6. Leaking valve. If the valve position is 0% for 15 minutes and discharge air temperature
is above AHU SAT by 3°C (5°F), generate a Level 4 alarm.
5.9.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 83
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the discharge air temperature is 17°C (30°F) less than setpoint for 5 minutes, send
3 Requests,
2. Else if the discharge air temperature is 8.3°C (15°F) less than setpoint for 5 minutes,
send 2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 84
5.9.8.4. If there is a hot water coil and a heating hot water plant, Heating Hot Water Plant
Requests. Send the heating hot water plant that serves the zone a Heating Hot Water
Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
5.10.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.10.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.10.3. See 3.1.2.6 for zone minimum airflow setpoint Vmin, zone maximum cooling airflow
setpoint Vcool-max, the series fan maximum heating airflow Sfan-htgmax, and the
maximum discharge air temperature rise above heating setpoint, MaxΔT.
5.10.4. Active maximum and minimum primary air setpoints shall vary depending on the Mode of
the Zone Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
5.10.5. Control logic is depicted schematically in the figure below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation. In
the chart below, OA-min is Voz (if using ASHRAE Standard 62.1 ventilation logic) or
Zone-Abs-OA-min (if using Title 24 ventilation logic).
In the heating zone state, the logic keeps the fan airflow rate low while supply air
temperature is increased as the first heating stage. This presumes that the temperature
of the air the fan is supplying is neutral or below the space temperature, as it would be
if the fan draws air directly from the space and as it might be if the fan draws air from
a return air plenum that is cooled by roof and wall heat losses. In the past, return air
plenums were warmed by recessed light fixtures, but pendant lights are more and more
common so the potential for “free” heating from the plenum is smaller than it once
was. Since there is the potential that the plenum is colder than the space due to
envelope loads, the logic leads with the supply air temperature rather than with an
increase in fan speed. If the designer is confident that the plenum will always be
warmer, the logic can be reversed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 85
1. The Cooling Loop output shall be mapped to the primary airflow setpoint from the
cooling minimum to the cooling maximum airflow setpoints.
a. If supply air temperature from the air handler is greater than room temperature,
primary airflow setpoint shall be no higher than the minimum and the series fan
airflow setpoint shall be no higher than OA-min.
2. The series fan airflow setpoint shall be the larger of OA-min and the primary airflow
setpoint.
Standard 90.1-2016 limits overhead supply air to 11°C (20°F) above space
temperature (e.g., 32°C (90°F) at 21°C (70°F) space temperature setpoint) to
minimize stratification.
1. From 0-50%, the Heating Loop output shall reset the discharge temperature setpoint
from the current AHU SAT setpoint to a maximum of MaxΔT above space
temperature setpoint. The primary airflow setpoint shall be the minimum airflow
setpoint, and the series fan airflow setpoint shall be OA-min.
2. From 50-100%, the Heating Loop output shall reset the series fan airflow setpoint
from OA-min to a Sfan-htgmax. The primary airflow setpoint shall be the minimum
airflow setpoint.
3. The heating coil shall be modulated to maintain the discharge temperature at setpoint.
(Directly controlling heating off zone temperature control loop is not acceptable).
5.10.5.4. The VAV damper shall be modulated to maintain the measured airflow at setpoint.
5.10.5.5. Fan Control: Fan shall run whenever zone is in Heating or Cooling Zone State, or if the
associated Zone Group is in Occupied Mode. Prior to starting the fan, the damper is
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 86
first driven fully closed to ensure that the fan is not rotating backwards. Once the fan
is proven on for a fixed time delay (15 seconds), the damper override is released.
5.10.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
1. If heating hot water plant is proven on and the discharge air temperature is 8.3°C
(15°F) less than setpoint for 10 minutes, generate a Level 3 alarm.
2. If heating hot water plant is proven on and the discharge air temperature is 17°C
(30°F) less than setpoint for 10 minutes, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its Hot Water reset
Trim & Respond control loop, low discharge air temperature alarms shall be
suppressed for that zone.
5.10.6.3. Fan alarm is indicated by the status input being different from the output command after
a period of 15 seconds after a change in output status.
5.10.6.4. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the cooling maximum airflow setpoint, generate
a Level 3 alarm.
5.10.6.5. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the zone
is proven on, generate a Level 4 alarm.
5.10.6.6. Leaking valve. If the valve position is 0% for 15 minutes and discharge air temperature
is above AHU SAT by 3°C (5°F), generate a Level 4 alarm.
5.10.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 88
4. Else if the Damper position is less than 95%, send 0 Requests
1. If the discharge air temperature is 17°C (30°F) less than setpoint for 5 minutes, send
3 Requests,
2. Else if the discharge air temperature is 8.3°C (15°F) less than setpoint for 5 minutes,
send 2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
5.10.8.4. If there is a hot water coil and a heating hot water plant, Heating Hot Water Plant
Requests. Send the heating hot water plant that serves the zone a Heating Hot Water
Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
Snap Acting Control logic is the first choice among the various DD control schemes – it is
the most efficient and does not require DD boxes with mixing sections that have a high
pressure drop. It allows use of dual standard airflow sensors, one at each inlet, with
standard pressure independent logic blocks; alternatively, a single discharge airflow
sensor may be used.
However, snap acting logic is not ideal for CO2 control because it can cause the zone to
oscillate between Cooling and Heating. This occurs when the CO2 control pushes the
Vmin* up to Vcool-max; at that point, temperature control is lost and if the space is
overcooled, it will be pushed into Heating, where it will be overheated, then back again.
If CO2 demand controlled ventilation is required, the mixing logic described in the next
section should be used.
This logic assumes no ability to mix hot and cold air to prevent overly low supply air
temperatures that may occur on systems with high outdoor airflows and no preheat coil.
So a preheat coil is likely to be required on such systems if mixed air temperature can fall
below 7°C (45°F) or so in winter.
Note that snap acting logic can also be problematic for zones with high minimums, since
the room itself is acting as the mixing box.
Because no cold duct air is supplied during heating mode, the heating system must include
ventilation air either with direct outdoor air intake or indirectly via transfer air from over-
ventilated spaces on the same system. Refer to Standard 62.1-2016 and the Standard 62.1-
2016 User’s Manual.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 89
5.11.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.11.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.11.3. See 3.1.2.7 for zone minimum airflow setpoint Vmin, maximum cooling airflow setpoint
Vcool-max, and the zone maximum heating airflow setpoint Vheat-max.
5.11.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
Heating
Vheat-max 0 0 Vheat-max Vheat-max 0
maximum
5.11.5. Control logic is depicted schematically in the figures below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
Cooling
Transition from Cooling towards Heating
Maximum
Heating
Maximum
Hot Duct Airflow
Minimum Airflow
Setpoint
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 90
Heating
Maximum
Hot Duct Airflow
Minimum Airflow
Setpoint
The following subsection “5.11.5.1” should be used if there are airflow sensors at both inlets
to the box. If instead there is a single airflow sensor at the box discharge, delete subsection
“5.11.5.1” and skip to subsection “5.11.5.2.”
5.11.5.1. Temperature and Damper Control with dual inlet airflow sensors:
1. When the Zone State is Cooling, the Cooling Loop output shall reset the cooling
supply airflow setpoint from the minimum to cooling maximum setpoints. The
cooling damper shall be modulated by a control loop to maintain the measured cooling
airflow at setpoint. The heating damper shall be closed.
a. If cold deck supply air temperature from air handler is greater than room
temperature, cooling supply airflow setpoint shall be no higher than the minimum.
2. When the Zone State is Deadband, the cooling and heating airflow setpoints shall be
their last setpoints just before entering Deadband. In other words, when going from
Cooling to Deadband, the cooling airflow setpoint is equal to the zone minimum and
the heating setpoint is zero. When going from Heating to Deadband, the heating
airflow setpoint is equal to the zone minimum and the cooling setpoint is zero. This
results in a snap-action switch in the damper setpoint as indicated in the figures above.
With snap acting logic, the deadband airflow is maintained by the damper from
the last mode, rather than always using the cold deck, as per the mixing
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 91
sequences below. This is to avoid instability when transitioning from heating
to deadband.
3. When the Zone State is Heating, the Heating Loop output shall reset the heating
supply airflow setpoint from the minimum to heating maximum setpoints. The
heating damper shall be modulated by a control loop to maintain the measured heating
airflow at setpoint. The cooling damper shall be closed.
a. If hot deck supply air temperature from air handler is less than room temperature,
heating supply airflow setpoint shall be no higher than the minimum.
The following subsection “5.11.5.2” should be used if there is a single airflow sensor at the
box discharge. If instead there are airflow sensors at both inlets to the box, delete subsection
“5.11.5.2” and use subsection “5.11.5.1,” above.
5.11.5.2. Temperature and Damper Control with a single discharge airflow sensor:
1. When the Zone State is Cooling, the Cooling Loop output shall reset the discharge
airflow setpoint from the minimum to cooling maximum setpoints. The cooling
damper shall be modulated by a control loop to maintain the measured discharge
airflow at setpoint. The heating damper shall be closed.
2. When the Zone State is Deadband, the discharge airflow setpoint shall be the zone
minimum, maintained by the damper that was operative just before entering
Deadband. The other damper shall remain closed. In other words, when going from
Cooling to Deadband, the cooling damper shall maintain the discharge airflow at the
zone minimum setpoint and the heating damper shall be closed. When going from
Heating to Deadband, the heating damper shall maintain the discharge airflow at the
zone minimum setpoint and the cooling damper shall be closed. This results in a
snap-action switch in the damper setpoint as indicated in the figures above.
3. When the Zone State is Heating, the Heating Loop output shall reset the discharge
airflow setpoint from the minimum to heating maximum setpoints. The heating
damper shall be modulated by a control loop to maintain the measured discharge
airflow at setpoint. The cooling damper shall be closed.
This concludes the section where the airflow sensor configuration is selected.
When the sequences are complete, only one of subsection “5.11.5.1” and subsection
“5.11.5.2” above should remain. The other subsection should be deleted, along with these
flag notes.
5.11.5.3. Overriding above logic (to avoid backflow from one duct to the other)
1. If heating air handler is not proven on, the heating damper shall be closed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 92
2. If cooling air handler is not proven on, the cooling damper shall be closed.
5.11.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
5.11.6.2. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the maximum airflow setpoint, generate a Level
3 alarm.
5.11.6.3. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the
damper is proven on, generate a Level 4 alarm.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 93
5.11.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below)
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing A VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the zone temperature is below the zone’s heating setpoint by 3°C (5°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 3
Requests,
2. Else if the zone temperature is below the zone’s heating setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 94
3. Else if the Heating Loop is greater than 95%, send 1 Request until the Heating Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
5.11.8.5. Heating Fan Requests. Send the heating fan that serves the zone a Heating Fan Request
as follows:
1. If the Heating Loop is greater than 15%, send 1 Request until the Heating Loop is less
than 1%
5.12 Dual Duct VAV Terminal Unit – Mixing Control with Inlet Airflow Sensors
Mixing Control logic is the preferred option for use with demand control ventilation. If
the box serves more than one room, it requires a DD box with mixing capability – a pair
of single-duct boxes strapped together with a common plenum will not work because the
discharge air will stratify rather than mix. However, if only a single room is served – as
is typical for a zone using DCV – then the room becomes the mixing box and this issue can
be disregarded.
This sequence utilizes two airflow sensors, one at each inlet. This eliminates the need for
a restriction at the discharge to facilitate flow measurement (and its associated pressure
drop). A discharge restriction may still be required for mixing; see previous paragraph.
When the majority of the airflow is through one duct, the airflow velocity in the other duct
may be too low to read and result in hunting at that damper. This is not a problem because
the absolute airflow in that duct will be too low for minor fluctuations to be detectable,
while the airflow in the dominant duct is sufficient to provide a clear velocity signal.
Because no cold duct air is supplied during most of the heating mode, the heating system
must include ventilation air either with direct outdoor air intake or indirectly via transfer
air from over-ventilated spaces on the same system. Refer to Standard 62.1-2016 and the
Standard 62.1-2016 User’s Manual.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 95
5.12.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.12.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.12.3. See 3.1.2.7 for zone minimum airflow setpoint Vmin, zone maximum cooling airflow
setpoint Vcool-max, and the zone maximum heating airflow setpoint Vheat-max.
5.12.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
Heating
Vheat-max 0 0 Vheat-max Vheat-max 0
maximum
5.12.5. Control logic is depicted schematically in the figures below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
Cooling
Maximum
Heating
Maximum
Minimum Airflow
Setpoint
1. When the Zone State is Cooling, the Cooling Loop output shall reset the cooling
supply airflow setpoint from minimum to the maximum cooling setpoint. The cooling
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 96
damper shall be modulated by a control loop to maintain the measured cooling airflow
at setpoint.
a. If cold deck supply air temperature from air handler is greater than room
temperature, cooling supply airflow setpoint shall be no higher than the minimum.
2. When the Zone State is Deadband, the cooling airflow setpoint shall be the minimum
setpoint. The cooling damper shall be modulated by a control loop to maintain the
measured cooling airflow at setpoint. The heating damper shall be closed.
The deadband airflow is maintained by the cooling damper since the cooling system has a
definite source of ventilation. With dual fan dual duct, the heating fan generally has no
direct ventilation source; typically, ventilation is indirect via return air from interior zones
that are over-ventilated due to the outdoor air economizer.
3. When the Zone State is Heating, the Heating Loop output shall reset the heating
supply airflow setpoint from zero to the maximum heating setpoint. The heating
damper shall be modulated by a control loop to maintain the measured heating airflow
at setpoint. The cooling damper shall be controlled to maintain the sum of the
measured inlet airflows at the minimum airflow setpoint.
a. If hot deck supply air temperature from air handler is less than room temperature,
heating supply airflow setpoint shall be no higher than the minimum.
5.12.5.2. Overriding above logic (to avoid backflow from one duct to the other)
1. If heating air handler is not proven on, the heating damper shall be closed.
2. If cooling air handler is not proven on, the cooling damper shall be closed.
5.12.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
5.12.6.2. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the maximum airflow setpoint, generate a Level
3 alarm.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 97
5.12.6.3. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the
damper is proven on, generate a Level 4 alarm.
5.12.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below).
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 98
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the zone temperature is below the zone’s heating setpoint by 3°C (5°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 3
Requests,
2. Else if the zone temperature is below the zone’s heating setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Heating Loop is greater than 95%, send 1 Request until the Heating Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
5.12.8.5. Heating Fan Requests. Send the heating fan that serves the zone a Heating Fan Request
as follows:
1. If the Heating Loop is greater than 15%, send 1 Request until the Heating Loop is less
than 1%
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 99
5.13 Dual Duct VAV Terminal Unit – Mixing Control with Discharge Airflow Sensor
Mixing Control logic is the preferred option for use with demand control ventilation. If
the box serves more than one room, it requires a DD box with mixing capability – a pair
of single-duct boxes strapped together with a common plenum will not work because the
discharge air will stratify rather than mix. However, if only a single room is served – as
is typical for a zone using DCV – then the room becomes the mixing box and this issue can
be disregarded.
This sequence utilizes a single airflow sensor at the discharge outlet. This requires a
restriction at the outlet to ensure that airflow velocity is high enough to measure, which
adds extra pressure drop. It is somewhat a legacy approach, from when adding a second
airflow sensor was much more expensive. As dual-airflow-sensor controllers are now
more common, the previous sequence (mixing control with inlet airflow sensors) is
generally preferred.
Because no cold duct air is supplied during heating mode, the heating system must include
ventilation air either with direct outdoor air intake or indirectly via transfer air from over-
ventilated spaces on the same system. Refer to Standard 62.1-2016 and the Standard 62.1-
2016 User’s Manual.
5.13.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.13.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.13.3. See 3.1.2.7 for zone minimum airflow setpoint Vmin, zone maximum cooling airflow
setpoint Vcool-max, and the zone maximum heating airflow setpoint Vheat-max.
5.13.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
Heating
Vheat-max 0 0 Vheat-max Vheat-max 0
maximum
5.13.5. Control logic is depicted schematically in the figures below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 100
Cooling
Maximum
Heating
Maximum
Minimum Airflow
Setpoint
Because there is only a single airflow sensor on the combined discharge, typical
pressure-independent control will not work for both dampers. Instead, the cooling
damper is controlled using pressure independent control while the heating damper
position equals the Heating loop signal (i.e., pressure dependent control).
1. When the Zone State is Cooling, the Cooling Loop output shall reset the cooling
supply airflow setpoint from minimum to the maximum cooling setpoint. The cooling
damper shall be modulated by a control loop to maintain the measured cooling airflow
at setpoint.
a. If cold deck supply air temperature from air handler is greater than room
temperature, cooling supply airflow setpoint shall be no higher than the minimum.
2. When the Zone State is Deadband, the cooling airflow setpoint shall be the minimum
setpoint. The cooling damper shall be modulated by a control loop to maintain the
measured cooling airflow at setpoint. The heating damper shall be closed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 101
The deadband airflow is maintained by the cooling damper since the cooling
system has a definite source of ventilation. With dual fan dual duct, the heating
fan generally has no direct ventilation source; typically, ventilation is indirect
via return air from interior zones that are over-ventilated due to the outdoor
air economizer.
3. When the Zone State is Heating, the Heating Loop output shall be mapped to the
heating damper position. The cooling damper is modulated to maintain measured
discharge airflow at the minimum airflow setpoint.
a. If hot deck supply air temperature from air handler is less than room temperature,
heating damper shall be closed.
5.13.5.2. Overriding above logic (to avoid backflow from one duct to the other)
1. If heating air handler is not proven on, the heating damper shall be closed.
2. If cooling air handler is not proven on, the cooling damper shall be closed.
5.13.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 102
5.13.6.2. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the maximum airflow setpoint, generate a Level
3 alarm.
5.13.6.3. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the
damper is proven on, generate a Level 4 alarm.
5.13.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below)
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 103
5.13.8.2. Cold Duct Static Pressure Reset Requests
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the zone temperature is below the zone’s heating setpoint by 3°C (5°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 3
Requests,
2. Else if the zone temperature is below the zone’s heating setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Heating Loop is greater than 95%, send 1 Request until the Heating Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
5.13.8.5. Heating Fan Requests. Send the heating fan that serves the zone a Heating Fan Request
as follows:
1. If the Heating Loop is greater than 15%, send 1 Request until the Heating Loop is less
than 1%
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 104
5.14 Dual Duct VAV Terminal Unit – Cold Duct Minimum Control
Cold Duct Minimum Control logic is the most conventional but least efficient dual duct
control strategy. It assures ventilation rates without Standard 62.1-2016 “generalized
multiple spaces” considerations since only the cold duct has ventilation air with DFDD
systems.
This strategy utilizes dual airflow sensors, one at each inlet. It may be used with or without
demand control ventilation.
The designer must ensure that the minimum and heating maximum sum to less than the
cooling maximum to avoid over-supplying the diffusers.
5.14.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.14.2. See Generic Ventilation Zones (5.2) for calculation of zone minimum outdoor airflow.
5.14.3. See 3.1.2.7 for zone minimum airflow setpoint Vmin, zone maximum cooling airflow
setpoint Vcool-max, and the zone maximum heating airflow setpoint Vheat-max.
5.14.4. Active maximum and minimum setpoints shall vary depending on the Mode of the Zone
Group the zone is a part of:
Cooling
Vcool-max Vcool-max Vcool-max 0 0 0
maximum
Minimum Vmin* 0 0 0 0 0
Heating
Vheat-max 0 0 Vheat-max Vheat-max 0
maximum
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 105
5.14.5. Control logic is depicted schematically in the figures below and described in the following
sections. Relative levels of various setpoints are depicted for Occupied Mode operation.
Cooling
Maximum
Heating
Maximum
Minimum Airflow
Setpoint
1. When the Zone State is Cooling, the Cooling Loop output shall reset the cooling
supply airflow setpoint from the minimum to cooling maximum setpoints. The
cooling damper shall be modulated by a control loop to maintain the measured cooling
airflow at setpoint. The heating damper shall be closed.
a. If cold deck supply air temperature from air handler is greater than room
temperature, cooling supply airflow setpoint shall be no higher than the minimum.
2. When the Zone State is Deadband, the cooling airflow setpoint shall be the minimum
setpoint. The cooling damper shall be modulated by a control loop to maintain the
measured cooling airflow at setpoint. The heating damper shall be closed.
a. The Heating Loop output shall reset the heating supply airflow setpoint from zero
to heating maximum setpoint. The heating damper shall be modulated by a control
loop to maintain the measured heating airflow at setpoint.
b. The cooling airflow setpoint shall be the minimum setpoint. The cooling damper
shall be modulated by a control loop to maintain the measured cooling airflow at
setpoint.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 106
c. If hot deck supply air temperature from air handler is less than room temperature,
heating damper shall be closed.
5.14.5.2. Overriding above logic (to avoid backflow from one duct to the other)
1. If heating air handler is not proven on, the heating damper shall be closed.
2. If cooling air handler is not proven on, the cooling damper shall be closed.
5.14.6. Alarms
1. If the measured airflow is less than 70% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 3 alarm.
2. If the measured airflow is less than 50% of setpoint for 5 minutes while setpoint is
greater than zero, generate a Level 2 alarm.
3. If a zone has an Importance multiplier of 0 [see 5.1.14.2.1.a] for its static pressure
reset Trim & Respond control loop, low airflow alarms shall be suppressed for that
zone.
5.14.6.2. Airflow sensor calibration. If the fan serving the zone has been off for 10 minutes and
airflow sensor reading is above 10% of the maximum airflow setpoint, generate a Level
3 alarm.
5.14.6.3. Leaking damper. If the damper position is 0% and airflow sensor reading is above 10%
of the cooling maximum airflow setpoint for 10 minutes while the fan serving the
damper is proven on, generate a Level 4 alarm.
5.14.7.7. Reset request-hours accumulator point to zero (provide one point for each reset type
listed below)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 107
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
1. If the zone temperature exceeds the zone’s cooling setpoint by 3°C (5°F) for 2 minutes
and after suppression period due to setpoint change per 5.1.20, send 3 Requests,
2. Else if the zone temperature exceeds the zone’s cooling setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Cooling Loop is greater than 95%, send 1 Request until the Cooling Loop
is less than 85%,
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
and the damper position is greater than 95% for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero and the damper position is greater than 95% for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
1. If the zone temperature is below the zone’s heating setpoint by 3°C (5°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 3
Requests,
2. Else if the zone temperature is below the zone’s heating setpoint by 2°C (3°F) for 2
minutes and after suppression period due to setpoint change per 5.1.20, send 2
Requests,
3. Else if the Heating Loop is greater than 95%, send 1 Request until the Heating Loop
is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 108
4. Else if the Heating Loop is less than 95%, send 0 Requests
1. If the measured airflow is less than 50% of setpoint while setpoint is greater than zero
for 1 minute, send 3 Requests,
2. Else if the measured airflow is less than 70% of setpoint while setpoint is greater than
zero for 1 minute, send 2 Requests,
3. Else if the Damper position is greater than 95%, send 1 Request until the Damper
position is less than 85%,
5.14.8.5. Heating Fan Requests. Send the heating fan that serves the zone a Heating Fan Request
as follows:
1. If the Heating Loop is greater than 15%, send 1 Request until the Heating Loop is less
than 1%
5.15.1. AHU system Modes are the same as the Mode of the Zone Group served by the system.
When Zone Group served by an air handling system are in different modes, the following
hierarchy applies (highest one sets AHU mode).
1. Occupied Mode
2. Cool-down Mode
3. Setup Mode
4. Warmup Mode
5. Setback Mode
7. Unoccupied Mode
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 109
5.16 Multiple Zone VAV Air Handling Unit
This section applies primarily to a cooling VAV air handling system. It can be adapted to apply
to a heating air handler serving a dual duct VAV system by editing out logic that does not apply
and by adjusting supply air temperature setpoints.
1. Supply fan shall run when system is in the Cool-down Mode, Setup Mode, or
Occupied Mode.
2. If there are any VAV-reheat boxes on perimeter zones, supply fan shall also run when
system is in Setback Mode or Warmup Mode (i.e., all Modes except Unoccupied).
Delete the following paragraph if air handler serves dual duct boxes that do not have hot
duct inlet airflow sensors, i.e., those that have only a box discharge airflow sensor. This
paragraph may also be deleted if there is a supply AFMS.
3. Totalize current airflow rate from VAV boxes to a software point, Vps.
VAV box airflow rates are summed to get overall supply air rate without the need
for an airflow measuring station at the air handler discharge. This is used for
ventilation rate calculations and may also be used for display and diagnostics.
1. Static pressure setpoint: Setpoint shall be reset using Trim & Respond logic [see
5.1.14] using the following parameters:
Variable Value
Device Supply Fan
SP0 120 Pa. (0.5 inches)
SPmin 25 Pa. (0.1 inches)
SPmax Max_DSP
(See 3.2.1.1)
Td 10 minutes
T 2 minutes
I 2
R Zone Static Pressure
Reset Requests
SPtrim -12 Pa (-0.05 inches)
SPres 15 Pa (+0.06 inches)
SPres-max 32 Pa (+0.13 inches)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 110
The trim & respond reset parameters above are suggested as a starting place; they
will most likely require adjustment during the commissioning/tuning phase.
1. Supply fan speed is controlled to maintain duct static pressure at setpoint when the
fan is proven on. Where the Zone Groups served by the system are small, provide
multiple sets of gains that are used in the control loop as a function of a load indicator
(such as supply fan airflow rate, the area of the Zone Groups that are occupied, etc.).
High pressure trips may occur if all VAV boxes are closed (as in Unoccupied
Mode) or if fire/smoke dampers are closed (in some FSD designs, the dampers
are interlocked to the fan status rather than being controlled by smoke
detectors). Multiple sets of gains are used to provide control loop stability as
system characteristics change.
5.16.2.1. Control loop is enabled when the supply air fan is proven on, and disabled and output
set to Deadband (no heating, minimum economizer) otherwise.
The default range of outdoor air temperatures [21°C (70°F) – 16°C (60°F)] used to
reset the Occupied Mode SAT setpoint was chosen to maximize economizer hours. It
may be preferable to use a lower range of OATs [e.g., 18°C (65°F) – 13°C (55°F)] to
minimize fan energy if:
• There is a 24/7 chiller plant that is running anyway
• Reheat is minimized, as in a VAV dual-fan, dual-duct system
• The climate severely limits the number of available economizer hours
If using this logic, the engineer should oversize interior zones and rooms with high
cooling loads (design them to be satisfied by the warmest SAT) so these zones don’t
drive the T&R block to the minimum SAT setpoint.
2. During Occupied Mode and Setup Mode: Setpoint shall be reset from Min_ClgSAT
when the outdoor air temperature is OAT_Max and above, proportionally up to T-
max when the outdoor air temperature is OAT_Min and below.
a. T-max shall be reset using Trim & Respond logic [see 5.1.14] between
Min_ClgSAT and Max_ClgSAT. The following parameters are suggested as a
starting place, but they will require adjustment during the commissioning/tuning
phase:
Variable Value
Device Supply Fan
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 111
Variable Value
SP0 SPmax
SPmin Min_ClgSAT
SPmax Max_ClgSAT
Td 10 minutes
T 2 minutes
I 2
R Zone Cooling SAT
Requests
SPtrim +0.1°C (+0.2ºF)
SPres -0.2°C (-0.3ºF)
SPres-max -0.6°C (-1.0ºF)
The net result of this SAT reset strategy is depicted in the chart below
for Min_ClgSAT = 12°C (55°F), Max_ClgSAT = 18°C (65°F),
OAT_Max=21°C (70°F), and OAT_Min = 16°C (60°F):
Min_ClgSAT
12°C (55°F)
OAT_Min Outdoor Air Temperature OAT_Max
16°C (60°F) 21°C (70°F)
The trim & respond reset parameters above are suggested as a starting
place; they will most likely require adjustment during the
commissioning/tuning phase.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 112
Raising the SAT setpoint in warmup will effectively lock out the economizer and
cooling coil, which is desirable for warmup even if there is no heating coil at the
AHU to meet the higher SAT.
This does not apply in the case of a DFDD AHU, or if all the zones are equipped
with fan-powered boxes such that the AHU is off in warmup and setback.
5.16.2.3. Supply air temperature shall be controlled to setpoint using a control loop whose output
is mapped to sequence the heating coil (if applicable), outdoor air damper, return air
damper, and cooling coil as shown in the diagram below.
The engineer must specify whether minimum outdoor air and economizer functions utilize
separate dedicated dampers or a single common damper.
If there are separate dedicated dampers, keep subsection “2” and delete subsection “3.”
If there is a single common damper, keep subsection “3” and delete subsection “2.”
Note that a single common damper requires an outdoor air AFMS. It is not a valid choice if
minimum outdoor air control is being done by differential pressure [i.e., if 5.16.4 is being
used].
2. For units with a separate minimum outdoor air damper: MinOA-P is 0% and MaxRA-
P is modulated to control minimum outdoor air volume [see 5.16.4 and 5.16.5].
3. For units with a single common minimum outdoor air and economizer damper:
MaxRA-P and MinOA-P are modulated to control minimum outdoor air volume [see
5.16.6].
4. The points of transition along the x-axis shown and described below are
representative. Separate gains shall be provided for each section of the control map
(heating coil, economizer, cooling coil), that are determined by the Contractor to
provide stable control. Alternatively, Contractor shall adjust the precise value of the
x-axis thresholds shown in the figure to provide stable control. Damper control
depends on the type of building pressure control system:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 113
MaxOA-P
100% MaxRA-P
Economizer
Damper/valve Position, % open
Return Air Outdoor Air
Damper Damper Position
Position
Economizer
Outdoor Air
Damper Cooling Coil
Position
MinOA-P
0%
Supply Air Temperature Control Loop Signal
Outdoor air and return air dampers are sequenced rather than complementary (as per
traditional sequences) to reduce fan power at part loads.
100%
MaxRA-P
Economizer
Damper/valve Position, % open
Outdoor Air
Return Air Damper Position
Damper Position
Relief/Exhaust Air
Damper Position
0%
Supply Air Temperature Control Loop Signal
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 114
100%
MaxRA-P
Economizer
0%
Supply Air Temperature Control Loop Signal
For air handling units with return fans, the outdoor air damper remains fully open
whenever the AHU is on while the return air damper modulates to maintain supply air
temperature and minimum outdoor airflow at setpoint. For return fan systems using
airflow tracking building pressure control logic, the relief/exhaust damper inversely
tracks the outdoor air damper. Outdoor air dampers on air handlers with return fans
have no impact on the outdoor air flowrate into the mixing plenum. Instead, the return
fan and return damper controls dictate outdoor air flow. See ASHRAE Guideline 16.
The engineer must select between options for determining the outdoor airflow setpoint based
on the ventilation logic being used.
The following section “5.16.3.1” should be used for ventilation logic that complies with
Standard 62. If instead the project is to comply with California Title 24 ventilation
requirements, delete subsection “5.16.3.1” and use subsection “5.16.3.2.”
CO2 DCV at the system level is not yet implemented for Standard 62.1
compliance pending results of RP-1747
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 115
The following logic solves the Standard 62.1 Multiple Spaces Equation
dynamically. This is required prescriptively by Standard 90.1 for single
duct VAV systems. The logic does not strictly apply to VAV systems with
multiple recirculation paths, such as dual fan/dual duct and systems with
fan-powered terminals, nor is it required by Standard 90.1 for these
systems. Logic for dynamic reset for these systems has yet to be developed.
3. Outdoor air absolute minimum and design minimum setpoints are recalculated
continuously based on the Mode of the zones being served.
a. Calculate the uncorrected outdoor air rate Vou for all zones in all Zone Groups that
are in Occupied Mode, but note that Vou shall be no larger than the design
uncorrected outdoor air rate, DesVou.
b. Vps is the sum of the zone primary airflow rates, Vpz, as measured by VAV boxes
for all zones in all Zone Groups that are in Occupied Mode.
c. For each zone in Occupied Mode, calculate the zone primary outdoor air fraction
Zpz:
Zpz = Voz / Vpz
See ASHRAE Guideline 13 for best practices in locating programming
logic for the zone primary outdoor air fraction calculation based on
network architecture.
d. Calculate the maximum zone outdoor air fraction, Zp:
Zp = MAX(Zpz)
e. Calculate the current system ventilation efficiency Ev:
Ev = 1 + (Vou / Vps) - Zp
f. Calculate the effective minimum outdoor air setpoint MinOAsp as the uncorrected
outdoor air intake divided by the system ventilation efficiency, but no larger than
the design total outdoor air rate, DesVot:
V
MinOAsp = MIN � Eou � DesVot �
v
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 116
The following section “5.16.3.2” should be used for ventilation logic that complies
with California Title 24. If instead the project is to comply with Standard 62.1
ventilation requirements, delete subsection “5.16.3.2” and use subsection “5.16.3.1.”
1. See 5.2.1.4.2 for zone outdoor air rates Zone-Abs-OA-min and Zone-Des-OA-min.
3. Effective outdoor air absolute minimum and design minimum setpoints are
recalculated continuously based on the Mode of the zones being served.
a. AbsMinOA* is the sum of Zone-Abs-OA-min for all zones in all Zone Groups that
are in Occupied Mode, but shall be no larger than the absolute minimum outdoor
airflow, AbsMinOA.
b. DesMinOA* is the sum of Zone-Des-OA-min for all zones in all Zone Groups that
are in Occupied Mode but shall be no larger than the design minimum outdoor
airflow, DesMinOA.
This concludes the section where the method for determining the outdoor airflow setpoint is
selected.
When the sequences are complete, only one of subsection “5.16.3.1” or subsection “5.16.3.2”
above should remain. The other subsection should be deleted, along with these flag notes.
The engineer must select among options for minimum outdoor air control logic. This
decision is based on two criteria:
• Do the minimum outdoor air and economizer functions utilize separate dedicated
dampers or a single common damper?
• Is outdoor air volume measured by differential pressure (ΔP) or an airflow measurement
station (AFMS)?
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 117
5.16.4. Minimum Outdoor Air Control with a separate minimum outdoor air damper and
differential pressure control
The following section “5.16.4.1” should be used for ventilation logic which complies
with Standard 62.1. If instead the project is to comply with California Title 24
ventilation requirements, delete subsection “5.16.4.1” and use subsection “5.16.4.2.”
MinOAsp 2
MinDPsp = DesMinDP � �
Des𝑉𝑉𝑜𝑜𝑜𝑜
The following section “5.16.4.2” should be used for ventilation logic that complies
with California Title 24. If instead the project is to comply with Standard 62.1
ventilation requirements, delete subsection “5.16.4.2” and use subsection “5.16.4.1.”
4. The active minimum differential pressure setpoints, AbsDPsp* and DesDPsp*, shall
be determined by the equations below:
AbsMinOA* 2
AbsDPsp* = AbsMinDP � �
AbsMinOA
DesMinOA* 2
DesDPsp* = DesMinDP � �
DesMinOA
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 118
This equation prevents excess outdoor air from being supplied during periods of
partial occupancy.
5. The minimum outdoor air DP setpoint (MinDPsp) shall be reset based on the highest
zone CO2 control loop signal from AbsDPsp* at 50% signal to DesDPsp* at 100%
signal.
6. The minimum outdoor air setpoint (MinOAsp) shall be reset based on the highest
zone CO2 control loop signal from AbsMinOA* at 50% signal to DesMinOA* at
100% signal.
This concludes the section where the ventilation logic option is selected.
When the sequences are complete, only one of subsection “5.16.4.1” and subsection
“5.16.4.2” above should remain. The other subsection should be deleted, along with
these flag notes.
5.16.4.3. Open minimum outdoor air damper when the supply air fan is proven on and the system
is in Occupied Mode and MinDPsp is greater than zero. Damper shall be closed
otherwise.
1. Return air damper minimum outdoor air control is enabled when the minimum
outdoor air damper is open and the economizer outdoor air damper is less than MOA-
P where MOA-P is 5% when supply fan speed is at 100% design speed proportionally
up to 80% when the fan is at minimum speed.
2. Return air damper minimum outdoor air control is disabled when the minimum
outdoor air damper is closed or the economizer outdoor air damper is 10% above
MOA-P determined above.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 119
The economizer outdoor air damper enabling setpoint assumes the minimum
outdoor air can be maintained by a combination of outdoor air coming through the
economizer outdoor air damper as well as the minimum outdoor air damper.
Higher damper position setpoints ensure minimum outdoor airflow will be
maintained but at the expense of fan energy. These setpoints could also be
determined empirically during TAB work as well.
The engineer must select among options for minimum outdoor air control logic. This
decision is based on two criteria:
• Do the minimum outdoor air and economizer functions utilize separate dedicated
dampers or a single common damper?
• Is outdoor air volume measured by differential pressure (ΔP) or an airflow measurement
station (AFMS)?
5.16.5. Minimum Outdoor Air Control with a separate minimum outdoor air damper and
airflow measurement
The following section “5.16.6.1” should be used for ventilation logic that complies
with Standard 62.1. If instead the project is to comply with California Title 24
ventilation requirements, delete subsection “5.16.6.1” and use subsection “5.16.6.2.”
The following section “5.16.6.2” should be used for ventilation logic that complies
with California Title 24. If instead the project is to comply with Standard 62.1
ventilation requirements, delete subsection “5.16.6.2” and use subsection “5.16.6.1.”
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 120
2. See zone CO2 control logic under terminal unit sequences.
3. The minimum outdoor air setpoint MinOAsp shall be reset based on the highest zone
CO2 control loop signal from AbsMinOA* at 50% signal to DesMinOA* at 100%
signal.
This concludes the section where the ventilation logic option is selected.
When the sequences are complete, only one of subsection “5.16.6.1” and subsection
“5.16.6.2” above should remain. The other subsection should be deleted, along with
these flag notes.
1. Minimum outdoor air control loop is enabled when the supply fan is proven on and
in Occupied Mode and disabled and output set to zero otherwise.
2. The minimum outdoor airflow rate shall be maintained at the minimum outdoor air
setpoint MinOAsp by a reverse-acting control loop whose output is 0-100%. From
0% to 50% loop output, the minimum outdoor air damper is opened from 0% to 100%.
a. Return air damper minimum outdoor air control is enabled when the minimum
outdoor air damper is 100% open and the economizer outdoor air damper is less
than MOA-P where MOA-P is 5% when supply fan speed is at 100% design speed
proportionally up to 80% when the fan is at minimum speed.
b. Return air damper minimum outdoor air control is disabled when the minimum
outdoor air damper is less than 100% open or the economizer outdoor air damper
is 10% above MOA-P determined above.
The engineer must select among options for minimum outdoor air control logic. This
decision is based on two criteria:
• Do the minimum outdoor air and economizer functions utilize separate dedicated
dampers or a single common damper?
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 121
• Is outdoor air volume measured by differential pressure (ΔP) or an airflow measurement
station (AFMS)?
5.16.6. Minimum Outdoor Air Control with a single common damper for minimum outdoor air
and economizer functions, and airflow measurement
The following section “5.16.6.1” should be used for ventilation logic that complies
with Standard 62.1. If instead the project is to comply with California Title 24
ventilation requirements, delete subsection “5.16.6.1” and use subsection “5.16.6.2.”
The following section “5.16.6.2” should be used for ventilation logic that complies
with California Title 24. If instead the project is to comply with Standard 62.1
ventilation requirements, delete subsection “5.16.6.2” and use subsection “5.16.6.1.”
3. The minimum outdoor air setpoint MinOAsp shall be reset based on the highest zone
CO2 control loop signal from AbsMinOA* at 50% signal to DesMinOA* at 100%
signal.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 122
This concludes the section where the ventilation logic option is selected.
When the sequences are complete, only one of subsection “5.16.6.1” and subsection
“5.16.6.2” above should remain. The other subsection should be deleted, along with
these flag notes.
1. Minimum outdoor air control loop is enabled when the supply fan is proven on and
the AHU is in Occupied Mode and disabled and output set to zero otherwise.
2. The outdoor airflow rate shall be maintained at the minimum outdoor air setpoint
MinOAsp by a reverse-acting control loop whose output is mapped to economizer
damper minimum position, MinOA-P, and return air damper maximum position,
MaxRA-P, as indicated in the figure below.
100%
MaxRA-P MinOA-P
MinOA-P
Damper Position, % open
MaxRA-P
0%
0% 50%
Outdoor Airflow Control Loop Output
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 123
This concludes the section where the minimum outdoor air control logic is selected.
When the sequences are complete, only one of section “5.16.4,” section “5.16.5,” and section
“5.16.6” above should remain. The other two sections should be deleted, along with these
flag notes.
5.16.7.1. The normal sequencing of the economizer dampers (above) shall be disabled in
accordance with 5.1.17.
5.16.7.3. Once the economizer is disabled, it shall not be re-enabled within 10 minutes, and vice
versa.
3. Wait 3 minutes, then release return air damper for minimum outdoor air control.
The return air damper is at first opened to avoid drawing the mixing plenum too
negative.
The three-minute delay is because the minimum OA damper may be pressure controlled.
In that case, delay allows time for the plenum pressure to stabilize so that the return
damper loop becomes unstable chasing a fluctuating pressure reading.
The engineer must select among control logic options for return/relief/exhaust. This decision
is based on the AHU configuration.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 124
5.16.8.1. Relief dampers shall be enabled when the associated supply fan is proven on, and
disabled otherwise.
5.16.8.2. When enabled, use a P-only control loop to modulate relief dampers to maintain 0.05”
building static pressure. Close damper when disabled.
The engineer must select among control logic options for return/relief/exhaust. This decision
is based on the AHU configuration.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 125
5.16.9. Relief Fan Control
Relief fans are enabled and disabled with their associated supply fans, but all relief fans
that are running, and serve a common volume of space, run at the same speed. All
operating relief fans that serve a common/shared air volume shall be controlled as if
they were one system, running at the same speed and using the same control loop, even
if they are associated with different air handling units.
This prevents relief fans from fighting each other, which can lead to flow reversal or
space pressurization problems.
The appropriate boundaries between relief systems, establishing which relief fans run
together, will need to be determined by the engineer based on building geometry.
5.16.9.1. All operating relief fans that serve a common/shared air volume shall be grouped and
controlled as if they were one system, running at the same speed and using the same
control loop, even if they are associated with different air handling units.
5.16.9.2. A relief fan shall be enabled when its associated supply fan is proven on, and shall be
disabled otherwise.
5.16.9.3. Building static pressure shall be time averaged with a sliding 5-minute window and 15
second sampling rate (to dampen fluctuations). The averaged value shall be that
displayed and used for control.
5.16.9.4. A P-only control loop maintains the building pressure at a setpoint of 0.05 inches with
an output ranging from 0 to 100%. The loop is disabled and output set to zero when all
fans in the relief system group are disabled.
The following is intended to use barometric relief as the first stage, and then
maintain many fans on at low speed to minimize noise and reduce losses through
discharge dampers and louvers. Fans are staged off only when minimum speed is
reached.
For best results, fan speed minimums should be set as low as possible.
5.16.9.5. Fan speed signal to all operating fans in the relief system group shall be the same and
shall be equal to the PID signal but no less than the minimum speed. Except for Stage
0, discharge dampers of all relief fans shall be open only when fan is commanded on.
1. Stage 0 (barometric relief): When relief system is enabled and the control loop output
is above 5%, open the motorized dampers to all relief fans serving the relief system
group that are enabled; close the dampers when the loop output drops to 0% for 5
minutes.
2. Stage Up: When control loop is above minimum speed plus 15%, start Stage Up
Timer. Each time Timer reaches 7 minutes, start next relief fan (and open associated
damper) in the relief system group per staging order and reset Timer to 0. Timer is
reset to 0 and frozen if control loop is below minimum speed plus 15%. Note: when
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 126
staging from Stage 0 (no relief fans) to Stage 1 (one relief fan), the discharge dampers
of all non-operating relief fans must be closed.
3. Stage Down: When PID loop is below minimum speed, then start Stage Down Timer.
Each time Timer reaches 5 minutes, shut off lag fan per staging order and reset Timer
to 0. Timer is reset to 0 and frozen if PID loop rises above minimum speed or all fans
are off. If all fans are off, go to Stage 0 (all dampers open and all fans off).
5.16.9.6. For fans in a Level 2 alarm and status is off, discharge damper shall be closed when
stage is above Stage 0.
The engineer must select among control logic options for return/relief/exhaust. This decision
is based on the AHU configuration.
5.16.10.1. Return fan operates whenever associated supply fan is proven on and shall be off
otherwise.
5.16.10.2. Return fans shall be controlled to maintain return fan discharge static pressure at
setpoint (see below).
5.16.10.3. Exhaust dampers shall only be enabled when the associated supply and return fans are
proven on and the minimum outdoor air damper is open. The exhaust dampers shall be
closed when disabled.
5.16.10.4. Building static pressure shall be time averaged with a sliding 5-minute window (to
dampen fluctuations). The averaged value shall be that displayed and used for control.
Due to the potential for interaction between the building pressurization and return fan
control loops, extra care must be taken in selecting the control loop gains. To prevent
excessive control loop interaction, the closed loop response time of the building
pressurization loop should not exceed 1/5 the closed loop response time of the return
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 127
fan control loop. This can be accomplished by decreasing the gain of the building
pressurization control loop.
5.16.10.5. When exhaust dampers are enabled, a control loop shall modulate exhaust dampers in
sequence with the return fan static pressure setpoint as shown in the figure below to
maintain the building pressure at a setpoint of 12 Pa (0.05 inches).
100% RFDSPmax
Damper Position, % open
RF DP setpoint
Relief/exhaust air
RF DP setpoint
Damper
0%
RFDSPmin
1. From 0% - 50%, the building pressure control loop shall modulate the exhaust
dampers from 0% to 100% open.
2. From 51% - 100%, the building pressure control loop shall reset the return fan
discharge static pressure setpoint from RFDSPmin at 50% loop output to RFDSPmax
at 100% of loop output. See 3.2.1.4 for RFDSPmin and RFDSPmax.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 128
The engineer must select among control logic options for return/relief/exhaust. This decision
is based on the AHU configuration.
5.16.11.1. Return fan operates whenever associated supply fan is proven on.
5.16.11.2. Return fan speed shall be controlled to maintain return airflow equal to supply airflow
less differential S-R-DIFF determined per 3.2.1.5.
5.16.11.3. Relief/exhaust dampers shall be enabled when the associated supply and return fans are
proven on and closed otherwise. Exhaust dampers shall modulate as the inverse of the
return air damper per 5.16.2.3.4.
Airflow tracking requires a measurement of supply airflow and return airflow. The
figure in 6.9 shows AFMS at both fans. These are actually not mandatory, although
they may improve accuracy if properly installed. The supply airflow can be calculated
by summing VAV box airflow rates. Return airflow can be approximated by return fan
speed if there are no dampers in the return air path (the geometry of the return air
system must be static for speed to track airflow.)
This concludes the section where the control logic for return/relief/exhaust is selected.
When the sequences are complete, at most, one of sections “5.16.8,” “5.16.9,” “5.16.10,” and
“5.16.11” should remain. If relief is barometric (without actuators) only, then all four
subsections should be deleted. Delete these flag notes after the decision has been made.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 129
There are three stages of freeze protection. The first stage modulates the heating valve
to maintain a safe SAT. The second stage eliminates outdoor air ventilation, in case
heating is not available for whatever reason. The third stage shuts down the unit and
activates coil valves and pumps to circulate water, in case the second stage does not
work (e.g., stuck economizer damper).
There are three stages of freeze protection. The first stage modulates the heating valve
to maintain a safe SAT. The second stage eliminates outdoor air ventilation, in case
heating is not available for whatever reason. The third stage shuts down the unit and
activates coil valves and pumps to circulate water, in case the second stage does not
work (e.g., stuck economizer damper).
5.16.12.1. If the supply air temperature drops below 4.4°C (40°F) for 5 minutes, send two (or more,
as required to ensure that heating plant is active) Heating Hot Water Plant Requests,
override the outdoor air damper to the minimum position, and modulate the heating coil
to maintain a supply air temperature of at least 6°C (42°F). Disable this function when
supply air temperature rises above 7°C (45°F) for 5 minutes.
The first stage of freeze protection locks out the economizer. Most likely this has already
occurred by this time, but this logic provides insurance.
5.16.12.2. If the supply air temperature drops below 3.3°C (38°F) for 5 minutes, fully close both
the economizer damper and the minimum outdoor air damper for one hour, and set a
Level 3 alarm noting that minimum ventilation was interrupted. After one hour, the unit
shall resume minimum outdoor air ventilation and enter the previous stage of freeze
protection (see 5.16.12.1).
A timer is used (rather than an OAT threshold) to exit the second stage of freeze
protection because a bad OAT sensor could lock out ventilation indefinitely, while a
timer should just work and thus avoid problems with the unit getting “stuck” in this
mode with no ventilation.
Upon timer expiration, the unit will re-enter the previous stage of freeze protection
(minOA ventilation, with heating to maintain SAT of 6°C (42°F)), after which one of
three possibilities will occur:
1) If it is warm enough that the SAT rises above 7°C (45°F) with minimum
ventilation, the unit will remain in Stage “a” freeze protection for five minutes,
then resume normal operation.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 130
2) If it is cold enough that SAT remains between 3.3°C (38°F) and 7°C (45°F) with
heating and minimum ventilation, the unit will remain in Stage “a” freeze
protection indefinitely, until outdoor conditions warm up.
3) If it is so cold that SAT is less than 3.3°F (38°F) with minimum ventilation,
despite heating, then the unit will revert to Stage “b” freeze protection, where it
will remain for one hour. This process will then repeat.
5.16.12.3. Upon signal from the freezestat (if installed) or if supply air temperature drops below
3.3°C (38F) for 15 minutes or below 1°C (34°F) for 5 minutes, shut down supply and
return/relief fan(s), close outdoor air damper, open the cooling coil valve to 100%, and
energize the chilled water pump system. Also send two (or more, as required to ensure
that heating plant is active) Heating Hot Water Plant Requests, modulate the heating
coil to maintain the higher of the supply air temperature or the mixed air temperature at
27°C (80°F), and set a Level 2 alarm indicating the unit is shut down by freeze
protection.
Stage three can be triggered by either of two conditions. The second condition is meant
to respond to an extreme and sudden cold snap.
Protecting the cooling coil in this situation will require water movement through the
coil, which means that the CHW pumps need to be energized.
Heating coil is controlled to an air temperature setpoint. The sensors will not read
accurately with the fan off, but they will be influenced by proximity to the heating coil.
A temperature of 27°C (80°F) at either of these sensors indicates that the interior of the
unit is sufficiently warm. This avoids the situation where a fixed valve position leads to
very high (and potentially damaging) temperatures inside the unit.
5.16.13. Alarms
5.16.13.1. Maintenance interval alarm when fan has operated for more than 1,500 hours: Level 4.
Reset interval count when alarm is acknowledged.
5.16.13.2. Fan alarm is indicated by the status being different from the command for a period of
15 seconds.
5.16.13.3. Filter pressure drop exceeds alarm limit: Level 4. The alarm limit shall vary with total
airflow (if available; use fan speed if total airflow is not known) as follows:
DPx = DP100 ( x )
1.4
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 131
where DP100 is the high limit pressure drop at design airflow (determine limit
from filter manufacturer) and DPx is the high limit at the current airflow rate x
(expressed as a fraction). For instance, the setpoint at 50% of design airflow
would be (.5)1.4 or 38% of the design high limit pressure drop.
5.16.13.5. Low building pressure (less than 0 Pa (0.0”), i.e., negative): Level 4
Automatic Fault Detection and Diagnostics (AFDD) is a sophisticated system for detecting
and diagnosing air handler faults.
To function correctly, it requires specific sensors and data be available, as detailed in the
sequences below. If this information is not available, AFDD tests that do not apply should
be deleted.
The Automatic Fault Detection and Diagnostics (AFDD) routines for AHUs
continually assesses AHU performance by comparing the values of BAS inputs and
outputs to a subset of potential fault conditions. The subset of potential fault conditions
that is assessed at any point depends on the Operating State of the AHU, as determined
by the position of the cooling and heating valves and the economizer damper. Time
delays are applied to the evaluation and reporting of fault conditions, to suppress false
alarms. Fault conditions that pass these filters are reported to the building operator
along with a series of possible causes.
These equations assume that the air handler is equipped with hydronic heating and
cooling coils, as well as a fully integrated economizer. If any of these components are
not present, the associated tests, and variables should be omitted from the
programming.
Note that these alarms rely on reasonably accurate measurement of mixed air
temperature. An MAT sensor is required for many of these alarms to work, and an
averaging sensor is strongly recommended for best accuracy.
5.16.14.1. AFDD conditions are evaluated continuously and separately for each operating air
handling unit.
5.16.14.2. The Operating State (OS) of each AHU shall be defined by the commanded positions
of the heating coil control valve, cooling coil control valve, and economizer damper in
accordance with the following table and corresponding graphic.
The Operating State is distinct from and should not be confused with the Zone
Status (Cooling, Heating, Deadband) or Zone Group Mode (Occupied,
Warmup, etc.).
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 132
OS#1 – OS#4 represent normal operation during which a fault may
nevertheless occur, if so determined by the fault condition tests in section e
below. By contrast, OS#5 may represent an abnormal or incorrect condition
(such as simultaneous heating and cooling) arising from a controller failure
or programming error, but it may also occur normally, e.g., when
dehumidification is active or during warmup.
Heating Cooling
Valve Valve Outdoor Air
Operating State Position Position Damper Position
#1: Heating >0 =0 = MIN
#2: Free Cooling, Modulating OA =0 =0 MIN < X < 100%
#3: Mechanical + Economizer Cooling =0 >0 = 100%
#4: Mechanical Cooling, Min OA =0 >0 = MIN
#5: Unknown or Dehumidification No other OS applies
100%
Damper/Valve Position, % Open
Cooling Coil
Outdoor Air
Heating
Damper
Coil
0%
5.16.14.3. The following points must be available to the AFDD routines for each AHU:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 133
3. RAT = Return air temperature
11. CCET = cooling coil entering temperature; depending on the AHU configuration,
this could be the MAT or a separate sensor for this specific purpose.
12. CCLT = cooling coil leaving temperature; depending on the AHU configuration,
this could be the SAT or a separate sensor for this specific purpose.
13. HCET = heating coil entering temperature; depending on the AHU configuration,
this could be the MAT or a separate sensor for this specific purpose.
14. HCLT = heating coil leaving temperature; depending on the AHU configuration,
this could be the SAT or a separate sensor for this specific purpose.
5.16.14.4. The following values must be continuously calculated by the AFDD routines for each
AHU:
1. 5-minute rolling averages with 1-minute sampling time of the following point values;
operator shall have the ability to adjust the averaging window and sampling period
for each point independently
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 134
h. HCETAVG = rolling average of heating coil entering temperature
MAT - RAT
2. %OA = actual outdoor air fraction as a percentage = OAT - RAT
or per airflow
measurement station if available.
4. ∆OS = number of changes in Operating State during the previous 60 minutes (moving
window)
5.16.14.5. The following internal variables shall be defined for each AHU. All parameters are
adjustable by the operator, with initial values as given below:
Default values are derived from NISTIR 7365 (Jeffrey Schein, October 2006) and have
been validated in field trials. They are expected to be appropriate for most
circumstances, but individual installations may benefit from tuning to improve
sensitivity and reduce false alarms.
The default values have been intentionally biased towards minimizing false alarms, if
necessary at the expense of missing real alarms. This avoids excessive false alarms that
will erode user confidence and responsiveness. However, if the goal is to achieve the
best possible energy performance and system operation, these values should be adjusted
based on field measurement and operational experience.
Values for physical factors such as fan heat, duct heat gain, and sensor error can be
measured in the field or derived from trend logs. Likewise, the occupancy delay and
switch delays can be refined by observing in trend data the time required to achieve
quasi steady state operation.
Other factors can be tuned by observing false positives and false negatives (i.e.,
unreported faults). If transient conditions or noise cause false errors, increase the
alarm delay. Likewise, failure to report real faults can be addressed by adjusting the
heating coil, cooling coil, temperature, or flow thresholds.
Default
Variable Name Description Value
∆TSF Temperature rise across supply fan 1°C (2°F)
Minimum difference between OAT and RAT
6°C
∆TMIN to evaluate economizer error conditions
(FC#6) (10° F)
ƐSAT Temperature error threshold for SAT sensor 1°C (2°F)
ƐRAT Temperature error threshold for RAT sensor 1°C (2°F)
ƐMAT Temperature error threshold for MAT sensor 3°C (5°F)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 135
Default
Variable Name Description Value
1°C (2°F) if
local sensor
@ unit.
ƐOAT Temperature error threshold for OAT sensor
3°C (5°F) if
global
sensor.
ƐF Airflow error threshold 30%
ƐVFDSPD VFD speed error threshold 5%
ƐDSP Duct static pressure error threshold 25 Pa (0.1”)
Cooling coil entering temperature sensor
ƐCCET
error. Equal to ƐMAT or dedicated sensor error
Cooling coil leaving temperature sensor error.
ƐCCLT
Equal to ƐSAT or dedicated sensor error Varies, see
Heating coil entering temperature sensor Description
ƐHCET
error; equal to ƐMAT or dedicated sensor error
Heating coil leaving temperature sensor error.
ƐHCLT
Equal to ƐSAT or dedicated sensor error
Maximum number of changes in Operating
∆OSMAX State during the previous 60 minutes (moving 7
window)
Time in minutes to suspend Fault Condition
ModeDelay 30
evaluation after a change in Mode
Time in minutes to that a Fault Condition
AlarmDelay 30
must persist before triggering an alarm
TestModeDelay Time in minutes that Test Mode is enabled 120
The purpose of ΔTMIN is to ensure that the mixing box/economizer damper tests
are meaningful. These tests are based on the relationship between supply,
return, and outdoor air. If RAT ≈ MAT, these tests will not be accurate and
will produce false alarms.
The purpose of TestModeDelay is to ensure that normal fault reporting occurs
after the testing and commissioning process is completed as prescribed in
5.16.14.12.
5.16.14.6. The following are potential Fault Conditions that can be evaluated by the AFDD
routines. If the equation statement is true, then the specified fault condition exists. The
Fault Conditions to be evaluated at any given time will depend on the Operating State
of the AHU.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 136
These equations assume that the SAT sensor is located downstream of the supply fan,
and the RAT sensor is located downstream of the return fan. If actual sensor locations
differ from these assumptions, it may be necessary to add or delete fan heat correction
factors.
To detect the required economizer faults in Title 24 section 120.2(i)7, use Fault
Conditions #2, 3, and 5-13 at a minimum. Other Title 24 AFDD requirements, including
acceptance tests, are not met through these fault conditions.
DSP < DSPSP - ƐDSP
Equation and
VFDSPD ≥ 99% - ƐVFDSPD
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 137
Equation SATAVG + ƐSAT ≤ MATAVG - ƐMAT + ∆TSF
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 138
Equation OATAVG - ƐOAT > SATSP - ∆TSF + ƐSAT
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 139
FC#14 Equation Applies
CCETAVG - CCLTAVG ≥ �ƐCCET 2 + ƐCCLT 2 + ∆TSF* to OS
*Fan heat factor included or not depending on location of #1, #2
sensors used for CCET and CCLT
Description Temperature drop across inactive cooling coil
Possible CCET sensor error
Diagnosis CCLT sensor error
Cooling coil valve stuck open or leaking
DX cooling stuck on
FC#15 Equation 2 2
Applies
HCLTAVG - HCETAVG ≥ �ƐHCET + ƐHCLT + ∆TSF* to OS
*Fan heat factor included or not depending on location of #2 – #4
sensors used for HCET and HCLT
Description Temperature rise across inactive heating coil
Possible HCET sensor error
Diagnosis HCLT sensor error
Heating coil valve stuck open or leaking.
5.16.14.7. A subset of all potential fault conditions is evaluated by the AFDD routines. The set of
applicable fault conditions depends on the Operating State of the AHU:
a. FC#1: Duct static pressure is too low with fan at full speed
a. FC#1: Duct static pressure is too low with fan at full speed
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 140
e. FC#8: SAT and MAT should be approximately equal
f. FC#9: OAT is too high for free cooling without mechanical cooling
a. FC#1: Duct static pressure is too low with fan at full speed
4. In OS#4 (Mechanical Cooling, Min OA), the following Fault Conditions shall be
evaluated:
a. FC#1: Duct static pressure is too low with fan at full speed
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 141
a. FC#1: Duct static pressure is too low with fan at full speed
5.16.14.8. For each air handler, the operator shall be able to suppress the alarm for any Fault
Condition.
5.16.14.9. Evaluation of Fault Conditions shall be suspended under the following conditions:
2. For a period of ModeDelay minutes following a change in Mode (e.g., from Warm
up to Occupied) of any Zone Group served by the AHU.
5.16.14.10. Fault Conditions that are not applicable to the current Operating State shall not be
evaluated.
5.16.14.11. A Fault Condition that evaluates as true must do so continuously for AlarmDelay
minutes before it is reported to the operator.
5.16.14.12. Test Mode shall temporarily set ModeDelay and AlarmDelay to 0 minutes for a
period of TestModeDelay minutes to allow instant testing of the AFDD system, and
ensure normal fault detection occurs after testing is complete.
5.16.14.13. When a Fault Condition is reported to the operator, it shall be a Level 3 alarm and
shall include the description of the fault and the list of possible diagnoses from the table
in 5.16.14.6.
5.16.15.1. If there is a hot water coil, force hot water valve full open
5.16.15.2. If there is a hot water coil, force hot water valve full closed
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 142
Central plant sequences are not part of the initial scope of Guideline 36, but control
logic for Plant Requests are being included for future use, when central plant
sequences are added.
Typically, the chiller or heating hot water plant will start when there is at least one
request for 5 minutes, and stop when there are no requests for 5 minutes, after a
minimum run-time has elapsed.
Chilled Water and Hot Water reset requests are used in Trim & Respond loops to
control supply water temperature and/or pump DP setpoints based on zone and AHU
demands.
1. If the supply air temperature exceeds the supply air temperature setpoint by 3°C (5°F)
for 2 minutes, send 3 Requests,
2. Else if the supply air temperature exceeds the supply air temperature setpoint by 2°C
(3°F) for 2 minutes, send 2 Requests,
3. Else if the CHW valve position is greater than 95%, send 1 Request until the CHW
valve position is less than 85%,
4. Else if the CHW valve position is less than 95%, send 0 Requests
5.16.16.2. Chiller Plant Requests. Send the chiller plant that serves the system a Chiller Plant
Request as follows:
1. If the CHW valve position is greater than 95%, send 1 Request until the CHW valve
position is less than 10%
2. Else if the CHW valve position is less than 95%, send 0 Requests.
1. If the supply air temperature is 17°C (30°F) less than setpoint for 5 minutes, send 3
Requests,
2. Else if the supply air temperature is 8°C (15°F) less than setpoint for 5 minutes, send
2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 143
5.16.16.4. If there is a hot water coil, Heating Hot Water Plant Requests. Send the heating hot
water plant that serves the AHU a Heating Hot Water Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
5.17 Dual Fan Dual Duct Heating VAV Air Handling Unit
1. Fan shall run when system is in the Warmup Mode and Setback Mode, and during
Occupied Mode while there are any Heating Fan Requests with a minimum runtime
of 15 minutes.
Delete the following paragraph if air handler serves dual duct boxes that do not have hot
duct inlet airflow sensors, i.e. those that have only a box discharge airflow sensor. This
paragraph may also be deleted if there is a supply AFMS.
VAV box airflow rates are summed to get overall supply air rate without the need
for an airflow measuring station at the air handler discharge. This is used only for
display and diagnostics and filter alarm.
1. Static pressure setpoint: Setpoint shall be reset using Trim & Respond logic [see
5.1.14] using the following parameters:
Variable Value
Device Supply Fan
SP0 120 Pa (0.5 inches)
SPmin 25 Pa (0.1 inches)
SPmax Max_DSP
(See 3.2.1.1)
Td 10 minutes
T 2 minutes
I 2
R Zone Hot Duct Static
Pressure Reset
Requests
SPtrim -12 Pa (-0.05 inches)
SPres 15 Pa (+0.06 inches)
SPres-max 32 Pa (+0.13 inches)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 144
The trim & respond reset parameters above are suggested as a starting place; they
will most likely require adjustment during the commissioning/tuning phase.
1. Supply fan speed is controlled to maintain duct static pressure at setpoint when the
fan is proven on. Where the Zone Groups served by the system are small, provide
multiple sets of gains that are used in the control loop as a function of a load indicator
(such as supply fan airflow rate, the area of the Zone Groups that are occupied, etc.).
High pressure trips may occur if all VAV boxes are closed (as in Unoccupied Mode)
or if fire/smoke dampers are closed (in some FSD designs, the dampers are
interlocked to the fan status rather than being controlled by smoke detectors).
5.17.2.1. Control loop is enabled when the supply air fan is proven on, and disabled and output
set to zero otherwise.
1. During Occupied Mode: Setpoint shall be reset using Trim & Respond logic [see
5.1.14] between 21°C (70°F) and Max_HtgSAT. See 3.1.5.1 for Max_HtgSAT.
Variable Value
Device Heating Supply Fan
SP0 SPmax
SPmin 21°C (70°F)
SPmax Max_HtgSAT
Td 10 minutes
T 2 minutes
I 2
R Zone Heating SAT
Requests
SPtrim -0.2°C (-0.4ºF)
SPres +0.3°C (+0.6ºF)
SPres-max +0.8°C (+1.4ºF)
The trim & respond reset parameters below are a suggested as a starting
place; they will most likely require adjustment during the
commissioning/tuning phase.
5.17.2.3. Supply air temperature shall be maintained at setpoint by a PID loop modulating the
heating coil.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 145
5.17.3. Alarms
5.17.3.1. Maintenance interval alarm when fan has operated for more than 1,500 hours: Level 4.
Reset interval counter when alarm is acknowledged.
5.17.3.2. Fan alarm is indicated by the status being different from the command for a period of
15 seconds.
5.17.3.3. Filter pressure drop exceeds alarm limit: Level 4. The alarm limit shall vary with total
airflow (if available; use fan speed if total airflow is not known) as follows:
DPx = DP100 ( x )
1. 4
where DP100 is the high limit pressure drop at design airflow (determine limit
from filter manufacturer) and DPx is the high limit at airflow rate x (expressed
as a fraction). For instance, the setpoint at 50% of design airflow would be
(.5)1.4 or 38% of the design high limit pressure drop.
The Automatic Fault Detection and Diagnostics (AFDD) routines for AHUs
continually assesses AHU performance by comparing the values of BAS inputs and
outputs to a subset of potential fault conditions. Time delays are applied to the
evaluation and reporting of fault conditions, to suppress false alarms. Fault conditions
that pass these filters are reported to the building operator along with a series of
possible causes. The AFDD routines listed in this section are intended for heating
ducts only – AFDD routines for cooling ducts are listed in sections 5.16.14 and 5.18.13.
5.17.4.1. AFDD conditions are evaluated continuously and separately for each operating air
handling unit.
5.17.4.2. The following points must be available to the AFDD routines for each AHU:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 146
5. DSPSP = duct static pressure setpoint
5.17.4.3. The following values must be continuously calculated by the AFDD routines for each
AHU:
1. 5-minute rolling averages with 1-minute sampling time of the following point values;
operator shall have the ability to adjust the averaging window and sampling period
for each point independently
5.17.4.4. The following internal variables shall be defined for each AHU. All parameters are
adjustable by the operator, with initial values as given below:
Default values are derived from NISTIR 7365 (Jeffrey Schein, October 2006) and have
been validated in field trials. They are expected to be appropriate for most
circumstances, but individual installations may benefit from tuning to improve
sensitivity and reduce false alarms.
The default values have been intentionally biased towards minimizing false alarms, if
necessary at the expense of missing real alarms. This avoids excessive false alarms that
will erode user confidence and responsiveness. However, if the goal is to achieve the
best possible energy performance and system operation, these values should be adjusted
based on field measurement and operational experience.
Values for physical factors such as fan heat, duct heat gain, and sensor error can be
measured in the field or derived from trend logs. Likewise, the occupancy delay and
switch delays can be refined by observing in trend data the time required to achieve
quasi steady state operation.
Other factors can be tuned by observing false positives and false negatives (i.e.,
unreported faults). If transient conditions or noise cause false errors, increase the
alarm delay. Likewise, failure to report real faults can be addressed by adjusting the
heating coil, cooling coil, temperature, or flow thresholds.
Default
Variable Name Description Value
∆TSF Temperature rise across supply fan 1°C (2° F)
ƐSAT Temperature error threshold for SAT sensor 1°C (2° F)
ƐRAT Temperature error threshold for RAT sensor 1°C (2° F)
ƐVFDSPD VFD speed error threshold 5%
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 147
Default
Variable Name Description Value
ƐDSP Duct static pressure error threshold 25 Pa (0.1”)
Time in minutes to suspend Fault Condition
ModeDelay 30
evaluation after a change in Mode
Time in minutes that a Fault Condition must
AlarmDelay 30
persist before triggering an alarm
TestModeDelay Time in minutes that Test Mode is enabled 120
5.17.4.5. The following are potential Fault Conditions that can be evaluated by the AFDD
routines. If the equation statement is true, then the specified fault condition exists.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 148
5.17.4.6. For each air handler, the operator shall be able to suppress the alarm for any Fault
Condition.
5.17.4.7. Evaluation of Fault Conditions shall be suspended under the following conditions:
2. For a period of ModeDelay minutes following a change in Mode (e.g., from Warm
up to Occupied) of any Zone Group served by the AHU.
5.17.4.8. A Fault Condition that evaluates as true must do so continuously for AlarmDelay
minutes before it is reported to the operator.
5.17.4.9. Test Mode shall temporarily set ModeDelay and AlarmDelay to 0 minutes for a period
of TestModeDelay minutes to allow instant testing of the AFDD system and ensure
normal fault detection occurs after testing is complete.
5.17.4.10. When a Fault Condition is reported to the operator, it shall be a Level 3 alarm and shall
include the description of the fault and the list of possible diagnoses from the table in
5.16.14.6.
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden together at a Zone Group
level, per 5.4.5.
E.g., The CxA can check for leaking dampers by forcing all VAV boxes in a Zone Group
closed and then recording airflow at the AHU.
Central plant sequences are not part of the initial scope of Guideline 36, but control
logic for Plant Requests are being included for future use, when central plant
sequences are added.
Typically, the heating hot water plant will start when there is at least one request for 5
minutes, and stop when there are no requests for 5 minutes, after a minimum run-time
has elapsed.
Hot Water reset requests are used in Trim & Respond loops to control supply water
temperature and/or pump DP setpoints based on zone and AHU demands.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 149
5.17.6. Plant Requests
1. If the supply air temperature is 17°C (30°F) less than setpoint for 5 minutes, send 3
Requests,
2. Else if the supply air temperature is 8°C (15°F) less than setpoint for 5 minutes, send
2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
5.17.6.2. Heating Hot Water Plant Requests. Send the heating hot water plant that serves the AHU
a Heating Hot Water Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
5.18.1. See Generic Thermal Zones (5.3) for setpoints, loops, control modes, alarms, etc.
5.18.4. Supply Fan Speed Control and Supply Air Temperature Setpoint Reset
These sequences use two supply air temperature setpoints, SATsp and SATsp-C, that
are reset at different rates but are controlled using the same sensor and control loop,
as well as a supply fan speed reset that varies depending on outdoor air temperature.
The goal of this scheme is to maximize free cooling and avoid chiller use when the
outdoor air is cool, while avoiding excessive fan energy use and utilizing the cooling
coil when outdoor air is warm.
For this to work, it is essential that both SATsp and SATsp-C are controlled off the
same physical SAT sensor.
It is also critical that the minimum value of the setpoint that controls the economizer
(SATsp) is lower than the minimum value of the setpoint that controls the chilled water
valve (SATsp-C). Otherwise, a brief temperature excursion due to the cooling coil will
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 150
lead to short cycling of the economizer and subsequent unnecessary energy use by the
cooling coil.
5.18.4.1. The supply fan shall run whenever the unit is in any mode other than Unoccupied Mode.
5.18.4.2. Provide a ramp function to prevent changes in fan speed of more than 10% per minute.
1. Medium fan speed (MedSpeed) shall be reset linearly based on outdoor air
temperature from MinSpeed when outdoor air temperature is greater or equal to
endpoint #1 to MaxCoolSpeed when outdoor air temperature is less than or equal to
endpoint #2.
a. Endpoint #1: the lesser of zone temperature +0.5°C (1°F) and maximum supply air
dewpoint MaxDPT.
b. Endpoint #2: the lesser of zone temperature minus 6°C (10°F) and the maximum
supply air dewpoint MaxDPT minus 1°C (2°F).
5.18.4.4. Minimum and maximum supply air temperature setpoints shall be as follows:
1. The Deadband values of SATsp and SATsp-C shall be the average of the zone heating
setpoint and the zone cooling setpoint, but shall be no lower than 21°C (70°F) and no
higher than 24°C (75°F).
5.18.4.5. When the supply fan is proven on, fan speed and supply air temperature setpoints are
controlled as shown in the following diagrams and text. The points of transition along
the x-axis shown and described below are representative. Separate gains shall be
provided for each section of the control map, that are determined by the Contractor to
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 151
provide stable control. Alternatively, Contractor shall adjust the precise value of the x-
axis thresholds shown in the figure to provide stable control.
SATsp-C
Fan Speed
SATsp-C
SATsp
Below, the same diagram is separated into two diagrams for clarity and to illustrate
the relative setpoints. However, both fan speed and supply air temperature setpoints
are reset simultaneously and by the same signal – the value of the Heating Loop or
Cooling Loop.
Maximum
Fan Speed
Medium Fan
Medium Fan Speed Speed at
at low OAT (equal intermediate
OAT
Fan Speed Setpoint
to Maximum Speed)
Maximum Heating Speed
1. For a Heating Loop signal of 100% - 50%, fan speed is reset from MaxHeatSpeed to
MinSpeed.
2. For a Heating Loop signal of 50% - 0%, fan speed setpoint is MinSpeed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 152
3. In Deadband, fan speed setpoint is MinSpeed.
5. For a Cooling Loop signal of 25% - 50%, fan speed is reset from MinSpeed to
MedSpeed.
7. For a Cooling Loop signal of 75% - 100%, fan speed is reset from MedSpeed to
MaxCoolSpeed.
Maximum SATsp
Supply Temperature Setpoint
Minimum
SATsp-C
Minimum SATsp
9. For a Heating Loop signal of 50% - 0%, SATsp is reset from Heat_SAT to the
Deadband value.
11. For a Cooling Loop signal of 0% - 25%, SATsp is reset from the Deadband value
to Cool_SAT minus 1°C (2°F), while SATsp-C is the Deadband value.
12. For a Cooling Loop signal of 25% - 50%, SATsp and SATsp-C are unchanged.
13. For a Cooling Loop signal of 50% - 75%, SATsp remains at Cool_SAT minus 1°C
(2°F), SATsp-C is reset from the Deadband value to Cool_SAT.
14. For a Cooling Loop signal of 75% - 100%, SATsp and SATsp-C are unchanged.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 153
In Cooling, the economizer is controlled to a lower setpoint than the cooling coil
(i.e., SATsp < SATsp-C) so that a low temperature excursion does not cause the
economizer to close inadvertently while cooling with mechanical cooling.
5.18.5.1. There are two supply air temperature setpoints, SATsp and SATsp-C. Each setpoint is
maintained by a separate control loop, but both loops use the same supply air
temperature sensor.
5.18.5.2. The control loop for SATsp is enabled when the supply air fan is proven on and disabled
and set to Neutral otherwise.
1. Supply air temperature shall be controlled to SATsp by a control loop whose output
is mapped to sequence the heating coil (if applicable) and economizer dampers as
shown in the diagram below. Outdoor air damper minimum (MinOA-P) and
maximum (MaxOA-P) positions are limited for economizer lockout and to maintain
minimum outdoor airflow rate as described in paragraphs 5.18.6 and 5.18.7.
These sequences assume that the heat source can be modulated and thus control
SAT to a setpoint in Heating. If this is not the case (e.g., because heating is by
multi-stage furnace or electric coil), then the following will need to be modified to
add appropriate staging logic.
2. The points of transition along the x-axis shown below are representative. Separate
gains shall be provided for each section of the control map (heating coil, economizer)
that are determined by the Contractor to provide stable control. Alternatively,
Contractor shall adjust the precise value of the x-axis thresholds shown in the figure
to provide stable control.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 154
MaxOA-P
100%
Outdoor Air
Return Air Damper Position
Heating Coil
(if applicable)
Return Air
Damper Position
5.18.5.3. The control loop for SATsp-C is enabled when the supply fan is proven on and the Zone
State is Cooling and disabled and set to Neutral otherwise. When enabled, supply air
temperature shall be controlled to SATsp-C by modulating the cooling coil.
This section describes minimum outdoor air control logic for a unit with a single
common minimum OA and economizer damper (i.e., no separate minimum OA damper)
and Demand Control Ventilation.
This logic assumes that there is no airflow measurement station or differential pressure
sensor across the outdoor air intake and controls OA volume directly via damper
position setpoints. This works for a single zone unit because there are no downstream
dampers that would change the relationship between OA damper position and OA
airflow. This logic is not appropriate for a system with actuated dampers downstream
of the AHU.
Other configurations are possible and would require modifications to the points list
(above) and the control logic below.
1. At least once per minute while the zone is in Occupied Mode, the BAS shall calculate
MinPos* as a linear interpolation between MinPosMin and MinPosMax based on the
current fan speed.
2. At least once per minute while the zone is in Occupied Mode, the BAS shall calculate
DesPos* as a linear interpolation between DesPosMin and DesPosMax based on the
current fan speed.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 155
3. If MinOAsp is zero, MinOA-P shall be zero (i.e., outdoor air damper fully closed).
4. If MinOAsp is non-zero, then the outdoor air damper minimum position MinOA-P
shall be the value between MinPos* and DesPos* that is proportional to the value of
MinOAsp between MinOA and DesOA. The following diagram is an illustrative
example (points are chosen arbitrarily and are not meant to be representative):
DesPosMin
100% DesPos*
DesPosMax
The diamond
OA Damper Position, % open
0%
Min Speed Current Speed Max Speed
Supply Fan Speed
This section describes economizer lockout logic for a unit with a common minimum OA
and economizer damper (i.e., no separate minimum OA damper). Other configurations
are possible, and would require modifications to the points list (above) and the control
logic below.
5.18.7.1. The normal sequencing of the economizer dampers (above) shall be disabled in
accordance with 5.1.17.
5.18.7.2. Once the economizer is disabled, it shall not be re-enabled within 10 minutes and vice
versa.
5.18.7.3. When economizer is enabled, MaxOA-P = 100%. When economizer is disabled, set
MaxOA-P equal to MinOA-P. See Supply Air Temperature Control (5.18.5) and
Minimum Outdoor Air Control (5.18.6) for outdoor air damper minimum setpoint.
The engineer must select among control logic options for return/relief/exhaust. This decision
is based on the AHU configuration.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 156
• For AHUs using a return fan, use section “5.18.10” below and delete section “5.18.8” and
section “5.18.9” below.
• For AHUs using non-actuated barometric relief only, delete all three sections “5.18.8,”
“5.18.9,” and “5.18.10” below.
A building pressure sensor is required for option “5.18.9.” One is not required for options
“5.18.8” or “5.18.10.”
5.18.8.2. Relief dampers shall be enabled when the associated supply fan is proven on and any
outdoor air damper is open and disabled and closed otherwise.
5.18.8.3. Relief damper position shall be reset linearly from MinRelief to MaxRelief as the
commanded economizer damper position goes from MinPos* to 100% open.
5.18.9.1. Refer to 5.16.9 Relief Fan Control for multiple-zone air handlers.
Exhaust damper may be barometric (no actuator). In that case, delete subsections
“5.18.10.1” and “5.18.10.4” below.
5.18.10.1. Exhaust damper shall open whenever associated supply fan is proven on.
5.18.10.2. Return fan shall run whenever associated supply fan is proven on.
5.18.10.3. Return fan speed shall be the same as supply fan speed with a user adjustable offset, S-
R-DIFF.
This concludes the section where the control logic for return/relief/exhaust is selected.
When the sequences are complete, at most, one of sections “5.18.8,” “5.18.9,” or “5.18.10”
should remain. If relief is barometric (without actuators) only, then all three subsections
should be deleted. Delete these flag notes after the decision has been made.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 157
If a freezestat is present, it may be hardwired to perform some or all of these functions. In
that case, delete those functions from sequence logic, but maintain the alarms. Delete this
flag note when sequences are complete.
There are three stages of freeze protection. The first stage modulates the heating valve
to maintain a safe SAT. The second stage eliminates outdoor air ventilation, in case
heating is not available for whatever reason. The third stage shuts down the unit and
activates coil valves and pumps to circulate water, in case the second stage does not
work (e.g., stuck economizer damper).
5.18.11.1. If the supply air temperature drops below 4°C (40°F) for 5 minutes, send two (or more,
as required to ensure that heating plant is active) Heating Hot Water Plant Requests,
override the outdoor air damper to the minimum position, and modulate the heating coil
to maintain a supply air temperature of at least 6°C (42°F). Disable this function when
supply air temperature rises above 7°C (45°F) for 5 minutes.
The first stage of freeze protection locks out the economizer. Most likely this has already
occurred by this time, but this logic provides insurance.
5.18.11.2. If the supply air temperature drops below 3°C (38°F) for 5 minutes, fully close both the
economizer damper and the minimum outdoor air damper for one hour, and set a Level
3 alarm noting that minimum ventilation was interrupted. After one hour, the unit shall
resume minimum outdoor air ventilation and enter the previous stage of freeze
protection (see 5.18.11.1).
A timer is used (rather than an OAT threshold) to exit the second stage of freeze
protection because a bad OAT sensor could lock out ventilation indefinitely, while a
timer should just work and thus avoid problems with the unit getting “stuck” in this
mode with no ventilation.
Upon timer expiration, the unit will re-enter the previous stage of freeze protection
(minOA ventilation, with heating to maintain SAT of 6°C (42°F)), after which one of
three possibilities will occur:
1) If it is warm enough that the SAT rises above 7°C (45°F) with minimum
ventilation, the unit will remain in Stage “a” freeze protection for five minutes,
then resume normal operation.
2) If it is cold enough that SAT remains between 3°C (38°F) and 7°C (45°F) with
heating and minimum ventilation, the unit will remain in Stage “a” freeze
protection indefinitely until outdoor conditions warm up.
3) If it is so cold that SAT is less than 3°C (38°F) with minimum ventilation, despite
heating, then the unit will revert to Stage “b” freeze protection, where it will
remain for one hour. This process will then repeat.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 158
5.18.11.3. Upon signal from the freezestat (if installed) or if supply air temperature drops below
3°C (38°F) for 15 minutes or below 1°C (34°F) for 5 minutes, shut down supply and
return/relief fan(s), close outdoor air damper, make the minimum cooling coil valve
position 100%, and energize the chilled water pump system. Send two (or more, as
required to ensure that heating plant is active) Heating Hot Water Plant Requests,
modulate the heating coil to maintain the higher of the supply air temperature or the
mixed air temperature at 27°C (80°F), and set a Level 2 alarm indicating the unit is shut
down by freeze protection.
Stage three can be triggered by either of two conditions. The second condition is meant
to respond to an extreme and sudden cold snap.
Protecting the cooling coil in this situation will require water movement through the
coil, which means that the CHW pumps need to be energized.
Heating coil is controlled to an air temperature setpoint. The sensors will not read
accurately with the fan off, but they will be influenced by proximity to the heating coil.
A temperature of 27°C (80°F) at either of these sensors indicates that the interior of the
unit is sufficiently warm. This avoids the situation where a fixed valve position leads to
very high (and potentially damaging) temperatures inside the unit.
5.18.12.1. Maintenance interval alarm when fan has operated for more than 1,500 hours: Level 4.
Reset interval counter when alarm is acknowledged.
5.18.12.2. Fan alarm is indicated by the status being different from the command for a period of
15 seconds.
Automatic Fault Detection and Diagnostics (AFDD) is a sophisticated system for detecting
and diagnosing air handler faults.
To function correctly, it requires specific sensors and data be available, as detailed in the
sequences below. If this information is not available, AFDD tests that do not apply should
be deleted.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 159
5.18.13. Automatic Fault Detection and Diagnostics
The Automatic Fault Detection and Diagnostics (AFDD) routines for AHUs
continually assesses AHU performance by comparing the values of BAS inputs and
outputs to a subset of potential fault conditions. The subset of potential fault conditions
that is assessed at any point depends on the Operating State of the AHU, as determined
by the position of the cooling and heating valves and the economizer damper. Time
delays are applied to the evaluation and reporting of fault conditions, to suppress false
alarms. Fault conditions that pass these filters are reported to the building operator
along with a series of possible causes.
These equations assume that the air handler is equipped with hydronic heating and
cooling coils, as well as a fully integrated economizer. If any of these components are
not present, the associated tests, and variables, should be omitted from the
programming.
Note that these alarms rely on reasonably accurate measurement of mixed air
temperature. An MAT sensor is required for many of these alarms to work, and an
averaging sensor is strongly recommended for best accuracy. If an MAT sensor is not
installed, omit Fault Conditions #2, #3, #5, #8, #10, and #12.
5.18.13.1. AFDD conditions are evaluated continuously and separately for each operating air
handling unit.
5.18.13.2. The Operating State (OS) of each AHU shall be defined by the commanded positions
of the heating coil control valve, cooling coil control valve, and economizer damper in
accordance with the following table and corresponding graphic.
The Operating State is distinct from and should not be confused with the Zone
Status (Cooling, Heating, Deadband) or Zone Group Mode (Occupied,
Warmup, etc.).
OS#1 – OS#4 represent normal operation during which a fault may
nevertheless occur, if so determined by the fault condition tests in section e
below. By contrast, OS#5 typically represents an abnormal or incorrect
condition (such as simultaneous heating and cooling) arising from a controller
failure or programming error, but it may also occur normally, e.g., when
dehumidification is active.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 160
Heating Cooling
Valve Valve Outdoor Air
Operating State Position Position Damper Position
#1: Heating >0 =0 = MIN
#2: Free Cooling, Modulating OA =0 =0 MIN < X < 100%
#3: Mechanical + Economizer Cooling =0 >0 = 100%
#4: Mechanical Cooling, Min OA =0 >0 = MIN
#5: Unknown or Dehumidification No other OS applies
OS#1 OS#2 OS#3 OS#4
100%
Damper/Valve Position, % Open
Cooling Coil
Outdoor Air
Damper
Heating Coil
0%
5.18.13.3. The following points must be available to the AFDD routines for each AHU:
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 161
6. SATsp = supply air temperature setpoint for heating coil & economizer control
11. CCET = cooling coil entering temperature; depending on the AHU configuration,
this could be the MAT or a separate sensor for this specific purpose.
12. CCLT = cooling coil leaving temperature; depending on the AHU configuration,
this could be the SAT or a separate sensor for this specific purpose.
13. HCET = heating coil entering temperature; depending on the AHU configuration,
this could be the MAT or a separate sensor for this specific purpose.
14. HCLT = heating coil leaving temperature; depending on the AHU configuration,
this could be the SAT or a separate sensor for this specific purpose.
5.18.13.4. The following values must be continuously calculated by the AFDD routines for each
AHU:
1. 5-minute rolling averages with 1-minute sampling of the following point values;
operator shall have the ability to adjust the averaging window and sampling period
for each point independently.
2. ∆OS = number of changes in Operating State during the previous 60 minutes (moving
window)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 162
5.18.13.5. The following internal variables shall be defined for each AHU. All parameters are
adjustable by the operator, with initial values as given below:
Default values are derived from NISTIR 7365 (Jeffrey Schein, October 2006) and have
been validated in field trials. They are expected to be appropriate for most
circumstances, but individual installations may benefit from tuning to improve
sensitivity and reduce false alarms.
The default values have been intentionally biased towards minimizing false alarms, if
necessary at the expense of missing real alarms. This avoids excessive false alarms that
will erode user confidence and responsiveness. However, if the goal is to achieve the
best possible energy performance and system operation, these values should be adjusted
based on field measurement and operational experience.
Values for physical factors such as fan heat, duct heat gain, and sensor error can be
measured in the field or derived from trend logs. Likewise, the occupancy delay and
switch delays can be refined by observing in trend data the time required to achieve
quasi steady state operation.
Other factors can be tuned by observing false positives and false negatives (i.e.,
unreported faults). If transient conditions or noise cause false errors, increase the
alarm delay. Likewise, failure to report real faults can be addressed by adjusting the
heating coil, cooling coil, temperature, or flow thresholds.
Default
Variable Name Description Value
∆TSF Temperature rise across supply fan 0.5°C (1°F)
Minimum difference between OAT and RAT
∆TMIN to evaluate economizer error conditions 6°C (10°F)
(FC#6)
ƐSAT Temperature error threshold for SAT sensor 1°C (2°F)
ƐRAT Temperature error threshold for RAT sensor 1°C (2°F)
ƐMAT Temperature error threshold for MAT sensor 3°C (5°F)
1°C (2°F) if
local sensor
@ unit.
ƐOAT Temperature error threshold for OAT sensor
3°C (5°F) if
global
sensor.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 163
Cooling coil entering temperature sensor
ƐCCET
error. Equal to ƐMAT or dedicated sensor error
Cooling coil leaving temperature sensor error.
ƐCCLT
Equal to ƐSAT or dedicated sensor error Varies, see
Heating coil entering temperature sensor Description
ƐHCET
error; equal to ƐMAT or dedicated sensor error
Heating coil leaving temperature sensor error.
ƐHCLT
Equal to ƐSAT or dedicated sensor error
Maximum number of changes in Operating
∆OSMAX State during the previous 60 minutes (moving 7
window)
Time in minutes to suspend Fault Condition
ModeDelay 30
evaluation after a change in Mode
Time in minutes that a Fault Condition must
AlarmDelay 30
persist before triggering an alarm
TestModeDelay Time in minutes that Test Mode is enabled 120
The purpose of ΔTMIN is to ensure that the mixing box/economizer damper tests
are meaningful. These tests are based on the relationship between supply,
return, and outdoor air. If RAT ≈ MAT, these tests will not be accurate and
will produce false alarms.
The purpose of TestModeDelay is to ensure that normal fault reporting occurs
after the testing and commissioning process is completed as described in
5.18.13.12.
5.18.13.6. The following are the potential Fault Conditions that can be evaluated by the AFDD
routines. (At most, 14 of the 15 Fault Conditions are actively evaluated, but numbering
was carried over from multiple zone AHUs for consistency.) If the equation statement
is true, then the specified fault condition exists. The Fault Conditions to be evaluated at
any given time will depend on the Operating State of the AHU.
These equations assume that the SAT sensor is located downstream of the supply fan,
and the RAT sensor is located downstream of the return fan. If actual sensor locations
differ from these assumptions, it may be necessary to add or delete fan heat correction
factors.
To detect the required economizer faults in Title 24 section 120.2(i)7, use Fault
Conditions #2, 3, and 5-13 at a minimum. Other Title 24 AFDD requirements, including
acceptance tests, are not met through these fault conditions.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 164
Applies
This fault condition is not used in single zone units, as it requires
FC #1 to OS
a static pressure setpoint.
#1 – #5
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 165
SATAVG < SATSP - ƐSAT
Equation and
HC ≥ 99%
Description SAT too low in full heating
SAT sensor error Applies
FC #7 Cooling coil valve leaking or stuck open to OS
Heating coil valve stuck closed or actuator failure #1
Possible Fouled or undersized heating coil
Diagnosis HW temperature too low or HW unavailable
Gas or electric heat is unavailable
DX cooling is stuck on
Leaking or stuck economizer damper or actuator
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 166
Equation SATAVG - ƐSAT - ∆TSF ≥ MATAVG + ƐMAT
Description SAT too high; should be less than MAT
FC #12 SAT sensor error
(omit if MAT sensor error Applies
no Cooling coil valve stuck closed or actuator failure to OS
MAT Possible Fouled or undersized cooling coil #3, #4
sensor) Diagnosis CHW temperature too high or CHW unavailable
DX cooling unavailable
Gas or electric heat stuck on
Heating coil valve leaking or stuck open
SATAVG > SATSP-C + ƐSAT
Equation and
CC ≥ 99%
Description SAT too high in full cooling
SAT sensor error Applies
FC #13 Cooling coil valve stuck closed or actuator failure to OS
Fouled or undersized cooling coil #3, #4
Possible
CHW temperature too low or CHW unavailable
Diagnosis
DX cooling unavailable
Gas or electric heat stuck on
Heating coil valve leaking or stuck open
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 167
5.18.13.7. A subset of all potential fault conditions is evaluated by the AFDD routines. The set of
applicable fault conditions depends on the Operating State of the AHU. If an MAT
sensor is not installed, omit Fault Conditions #2, #3, #5, #8, #10, and #12:
e. FC#6: OA fraction is too high; MAT should be closer to RAT than to OAT
e. FC#9: OAT is too high for free cooling without mechanical cooling
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 168
f. FC#12: SAT too high; should be less than MAT
4. In OS#4 (Mechanical Cooling, Min OA), the following Fault Conditions shall be
evaluated:
d. FC#6: OA fraction is too high; MAT should be closer to RAT than to OAT
5.18.13.8. For each air handler, the operator shall be able to suppress the alarm for any Fault
Condition.
5.18.13.9. Evaluation of Fault Conditions shall be suspended under the following conditions:
2. For a period of ModeDelay minutes following a change in Mode (e.g., from Warm
up to Occupied) of any Zone Group served by the AHU.
5.18.13.10. Fault Conditions that are not applicable to the current Operating State shall not be
evaluated.
5.18.13.11. A Fault Condition that evaluates as true must do so continuously for AlarmDelay
minutes before it is reported to the operator.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 169
5.18.13.12. Test Mode shall temporarily set ModeDelay and AlarmDelay to 0 minutes for a period
of TestModeDelay minutes to allow instant testing of the AFDD system and ensure
normal fault detection occurs after testing is complete.
5.18.13.13. When a Fault Condition is reported to the operator, it shall be a Level 3 alarm and
shall include the description of the fault and the list of possible diagnoses from the
table in 5.18.13.6.
5.18.14.1. If there is a hot water coil, force hot water valve full open
5.18.14.2. If there is a hot water coil, force hot water valve full closed
5.18.14.3. If there is a chilled water coil, force chilled water valve full open
5.18.14.4. If there is a chilled water coil, force chilled water valve full closed
Per 5.1.11, all hardware points can be overridden through the BAS. Each of the
following points is interlocked so that they can be overridden as a group on a plant
level.
E.g., The CxA can check for valve leakage by simultaneously forcing closed all CHW
valves at all AHUs served by the chiller plant and then recording flow at the chiller.
Central plant sequences are not part of the initial scope of Guideline 36, but control
logic for Plant Requests are being included for future use, when central plant
sequences are added.
Typically, the chiller or heating hot water plant will start when there is at least one
request for 5 minutes and stop when there are no requests for 5 minutes after a
minimum run-time has elapsed.
Chilled Water and Hot Water reset requests are used in Trim & Respond loops to
control supply water temperature and/or pump DP setpoints based on zone and AHU
demands.
1. If the supply air temperature exceeds SATsp-C by 3°C (5°F) for 2 minutes, send 3
Requests,
2. Else if the supply air temperature exceeds SATsp-C by 2°C (3°F) for 2 minutes, send
2 Requests,
3. Else if the CHW valve position is greater than 95%, send 1 Request until the CHW
valve position is less than 85%,
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 170
4. Else if the CHW valve position is less than 95%, send 0 Requests
5.18.15.2. Chiller Plant Requests. Send the chiller plant that serves the system a Chiller Plant
Request as follows:
1. If the CHW valve position is greater than 95%, send 1 Request until the CHW valve
position is less than 10%
2. Else if the CHW valve position is less than 95%, send 0 Requests.
1. If the supply air temperature is 17°C (30°F) less than SATsp for 5 minutes, send 3
Requests,
2. Else if the supply air temperature is 8°C (15°F) less than SATsp for 5 minutes, send
2 Requests,
3. Else if HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 85%,
5.18.15.4. If there is a hot water coil, Heating Hot Water Plant Requests. Send the heating hot
water plant that serves the AHU a Heating Hot Water Plant Request as follows:
1. If the HW valve position is greater than 95%, send 1 Request until the HW valve
position is less than 10%
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 171
6. CONTROL DIAGRAMS (INFORMATIVE APPENDIX)
This section provides control diagrams for a selection of the equipment configurations described
in this document. These diagrams may be used in drawings when appropriate, but they are not
intended to represent all of the possible equipment configurations that are supported by these
sequences. The designer should edit these diagrams as required for the project.
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 172
6.3 Parallel Fan-Powered Terminal Unit, Constant Volume Fan
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 173
6.5 Series Fan-Powered Terminal Unit, Constant Volume Fan
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
BSR.ASHRAE Guideline 36P, High Performance Sequences of Operation for HVAC Systems
Third Public Review Draft
Page 174
6.7 Dual Duct Terminal Unit with Inlet Sensors
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Third Publication Public Review
Page 175
6.9 Multiple Zone VAV Air Handling Unit with Return Fan and OA Measurement Station
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Second Publication Public Review
Page 176
6.10 Multiple Zone VAV Air Handling Unit with Relief Fan & Differential Pressure OA Measurement
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Second Publication Public Review
Page 177
6.11 Dual Fan Dual Duct Heating VAV Air Handling Unit
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Second Publication Public Review
Page 178
6.12 Single Zone VAV Air Handling Unit (Return Fan Option)
ASHRAE Guideline 36: High Performance Sequences of Operation for HVAC Systems
Second Publication Public Review