Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

1. Location : MPSS/ 6.

6KV SWBD

Feeder Name : Trafo Feeder-13 / P.No:10

2. Name plate details:

3. General Inspection: OK

4. Secondary Injection Test:

Ref Pickup Volt (V) Drop off Volt (V)


5. Buch Trip(5, 6) 151.8 24.8
WTI Trip(7,8) 154.5 21.7
OTI Trip(9,10) 154.9 20.8
Functional checks: (Whether Operational Checks OK / Not OK / Not Applicable)

1 Correct operation of appropriate indicators and auxiliary relays OK


2 Correct initiation of alarm contacts OK
3 Correct initiation of tripping contacts OK

6. Comments : Nil.

7. Remarks : Relay Found Healthy.