SCHEDULE OF LOADS

CKT. LOAD WATTS/ PIECE PCS WATTS VOLTAGE CURRENT PROTECTION WIRE CONDUIT
Compact Fluorescent Lamp 25 6 150
1 230 2.03 15 AT 2P MCCB 2.0 mm² THHN 20MM DIA. PVC
Fluorescent Lamp 53 6 318
Compact Fluorescent Lamp 25 6 150
2 230 1.58 15 AT 2P MCCB 2.0 mm² THHN 20MM DIA PVC
Fluorescent Lamp 53 4 212
3 Compact Fluorescent Lamp 25 13 800 230 3.48 15 AT 2P MCCB 2.0 mm² THHN 20MM DIA PVC
4 Small Appliance Outlet 187.5 8 1500 230 6.52 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
5 Small Appliance Outlet 187.5 8 1500 230 6.52 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
6 Small Appliance Outlet 187.5 8 1500 230 6.52 20 AT 2P MCCB 5.5 mm² THHN 20MM DIA PVC
7 ACU 3 HP 1 3910 230 17.00 30 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
8 ACU 3 HP 1 3910 230 17.00 30 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
9 ACU 1.5 HP 1 2300 230 10.00 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
10 ACU 1.5 HP 1 2300 230 10.00 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
11 ACU 1.5 HP 1 2300 230 10.00 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
12 ACU 2.0 HP 1 2760 230 12.00 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
13 Bathroom Circuit (GFCI) 1500 1 1500 230 6.52 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
14 Tankless Water Heater 5000 1 5000 230 21.74 30 AT 2P MCCB 5.5 mm² THHN 25MM DIA PVC
15 Laundry Circuit 1500 1 1500 230 6.52 20 AT 2P MCCB 3.5 mm² THHN 20MM DIA PVC
16 Electric Range 8000 1 8000 230 34.78 50 AT 2P MCCB 5.5 mm² THHN 25MM DIA PVC
17 SPARE 4600 1 4600 230 20.00 20 AT 2P MCCB - -
18 SPARE 4600 1 4600 230 20.00 20 AT 2P MCCB - -

IMPORTANT NOTE: ALL SMALL APPLIANCE OUTLETS, ACUs, WATER HEATER, LAUNDRY CIRCUIT, BATHROOM CIRCUIT, ELECTRIC RANGE SHALL HAVE 3.5MM2 THHN GROUND WIRE.

TOTAL LOADS IN DESIGN


(a) Air Conditioning Loads MAIN CIRCUIT BREAKER
Two (2) - 3HP Airconditioning units, 17A x 230V x 2 = 7820VA 7820VA Inverse Time Circuit Breaker (Molded Case)
Three (3) - 1.5HP Airconditioning Units, 10A x 230V x 3 = 6900VA 6900VA (250%x3910 + 3910 + 6900 + 2760 + 3840 + 8000 +5000)/230 = 174.72 Amps
One (1) - 2.0HP Airconditioning Unit, 12A x 230V = 2760VA 2760VA Use 175AT , 2P Molded Case Circuit Breaker, Inverse Time.
SUBTOTAL 12500VA

(b) General Lighting Loads SERVICE ENTRANCE CONDUCTORS


160 Sq. Meter x 24VA per square meter = 3840VA 3840VA Total Full Load Current Calculation
[29340 + 0.25(3910)]VA / 230V = 131.82A
(c) Cooking Load However, the Main CB is rated at 175AT, so therefore the service entrance ampacity must be
One 8kW Electric Range 8000VA greater than or equal the Main CB Rating (Ampacity > = CB Rating).
Therefore, use 2-80mm2 THHN + 14mm2 THHN GROUNDING Service Entrance Conductors (Parallel)
(d) Other Loads Connected
with Total Ampacity of 205A.
One Tankless Water Heater @ 100% Demand Factor, 5000VA x 1 5000VA
20A Small Appliance Circuits, 3 Circuits x 1500VA/Circuit = 4500VA 4500VA MAINTENANCE ISOLATING SWITCH
20A Laundry Circuit, 1 Circuit x1500VA/Circuit = 1500VA 1500VA Use 200A Disconnect Switch
20A Bathroom Circuit, 1 Circuit x1500VA/Circuit = 1500VA 1500VA
SUBTOTAL 12500VA
Demand Factor Application, 12500VA x 0.40 = 5000 5000VA
Total NET COMPUTED LOAD 29340VA

ELECTRICAL SYSTEMS DESIGN

LOAD SCHEDULE AND SERVICE ENTRANCE

ENGR. FEDERICO CUDIA, PEE ENGR. KURT RUSSEL TO, CE


Professional Electrical Engineer Civil Engineer / Owner 3/10/2011 FOR PEE REVIEW 0
KRT CONTRACTORS, INC License Number PEE-002513 License Number CE-022711 DATE ANNOTATION REV