2.0 DRS-205C User Manual PDF
2.0 DRS-205C User Manual PDF
1.2 Foreword
1.5 Specifications
1.6 Description
1.7 Dimensions
1.8 Installation
1.10 Operating
User manual
This manual does not contain all of the safety measures for operation of the equipment (module, device), because special
operating conditions, and local code requirements or regulations may necessitate further measures. However, it does contain
information which must be read for your personal safety and to avoid material damages. This information is highlighted by a
warning triangle and is represented as follows, depending on the degree of potential danger.
Warning
This means that failure to observe the instruction can result in death, serious injury or considerable
material damage.
Caution
This means hazard of electric shock and failure to take the necessary safety precautions will result in
death, serious injury or considerable material damage.
Qualified personnel
Operation of the equipment (module, device) described in this manual may only be performed by qualified personnel.
Qualified personnel in this manual means person who are authorized to commission, start up, ground and label
devices, systems and circuits according to safety and Regulatory standards.
The equipment (device, module) may only be used for the application specified in the catalogue and the user manual,
and only be connected with devices and components recommended and approved by Forlong.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport, proper storage, installation and
proper operation and maintenance. When operating electrical equipment, parts of this equipment automatically carry
dangerous voltages. Improper handling can therefore result in serious injuries or material damage.
However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any
errors contained in the information given. The data in this manual is checked regularly and the necessary corrections
are included in subsequent editions. We are grateful for any improvements that you suggest.
1.2 Foreword
Thank you for purchasing the FORLONG DRS205 series DIN rail single phase two wire energy meter. With the
FORLONG product range we have provided a large scale of energy meters on the market suitable for 110V AC to 400V
AC (50 or 60Hz). Besides the normal energy meters we also developed our own pre-paid meters with chip card, chip
card re-loaders and a complete PC management control system. For more information on other products please contact
our sales department at [email protected].
Although we produce the Forlong DRS205 series meter according to EN 50470-3 and our strict quality inspection, there
might be possibilities that our product shows a fault or failure for which we do apologize.
Under normal conditions your product should give you years of benefit and pleasure. In case there is a problem with the
energy meter you should contact your dealer immediately. All energy meters are sealed with a special seal. Once this
seal is broken there is no possibility to claim for warranty. Therefore NEVER open meter by yourself or break the seal
of the energy meter. The warranty time is 6 months after installation, and only valid for construction faults.
The DRS-205 series include two types of energy meter: the one is base on Modbus protocol named DRS-205C Modbus,
the other is base on Metering BUS named DRS-205C MBUS.
*If you don’t fix the type, then your order will be treated as the order of default type. If you don’t need the default
type please mentioned the item number in your order.
When get the certification need add the MID certification, CE declaration and the declaration of conformity
here.
1.5 Specifications:
A LCD
B Terminal block
C Case
D Protection cover
E Security hasp
Material
A
B
112
45
79
36
44
17,5 4 60
1.8 Dimensions
Height 112. mm
Width 17.5 mm
Depth 60 mm
Weight 0.12 Kg (net)
Connection of the wires should be done in accordance with the underneath connection diagram.
1.10 Operating
Consumption indication
There is a LED which has two colors (green and red) while flashing in the front panel of DRS-205 series. When
consumption happens, the LED will flash and display red. The more quickly LED flash, the more consumption there is.
Pulse output
The DRS-205 Series DIN rail energy meter is equipped with a pulse output which is fully separated from the inside
circuit. That generates pulses in proportion to the measured energy for accuracy testing. The pulse output is a polarity
dependent, passive transistor output requiring an external voltage source for correct operation. For this external
voltage source, the voltage (Ui) should is 5-27V DC, and the maximum input current (Imax) is 27mA DC. To connect
the impulse output, connect 5-27V DC to connector 20 (anode), and the signal wire (S) to connector 21 (cathode).
Display function
Software 4 letters
version number
(1600)
(3200)
ID number ID 00 Power on
(XXXXXX.X)
S0 output
*Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate the
smaller the number of meters which can be used) and the circumstances under which the meters are installed.
No light for the Is the A, orB,or C and N Re-install terminal screws on the A, B, C
Power supply indicator connecting correct ? and N. Make sure all screws are fixed.
(Phase A, B & C LED). Than there should be a 230V 50Hz AC
voltage between the terminal screws on
the N and A or B or C, when power
supply is input.
Is the meter ID Check and use the correct the Meter ID.
correct? After the meter finish the production,
the Meter ID defaults to 0~
67H ,69H~FFH .
Please contact
TEL: +86-21-60975591
FAX: +86-21-60975593
Email: [email protected]