Outer cones are used in double feeder panels (width 2 x 400 mm) Shockproof cable connector systems are always to be used. A
and in panels as shown in fig. 8.1.1.2.1 (width 600 mm). selection of connector systems which can be used within the
space available is shown in tables 7.7.2.1 to 7.7.3.2. When mak-
Outer cone device termination components to EN 50181, fitted ing your selection, please take account of the current and short-
gas-tight in the wall between the panel module and the cable ter- circuit capacities of the cables and connector systems. Please
mination compartment, facilitate connection of cables and surge consult the latest catalogues from the manufacturers for precise
arresters (figs. 7.7.1 to 7.7.2). When the shutter on the cable ter- ordering details and information on any coupling units required.
mination compartment has been removed, the cables are acces-
sible from the rear of the system.
Fig. 7.7.1: View into the cable termination area with outer cones in air Fig. 7.7.2: View into the cable termination compartment in air with shock-
proof cable connectors (ABB type CSE-A) and cables
In the form of the product CSE-A, ABB offers outercone connec- All connector sleeves are routinely tested with regards to partial
tors for polymeric cables of all current cable cross-sections and discharge and AC, to ensure that supplied accessories are of
cable diameters. highest quality.
The connectors are made of rubber and they are cold mountable. The kits are supplied with adaptor, cable lug and connector hood
The outer conductive layer of the conductor ensures a touch proof with pre-installed earth conductor. Extra material such as earthing
system is approximate 2 mm thick and vulcanized together in one kits, crutch seals for 3-core cables and screen potential mate-
process with the insulation and inner deflector. This method gives rial for cable armouring is also within the ABB range of products.
a robust product with highest mechanical withstand. Kindly contact ABB Sales Representative for more information.
Fig. 7.7.1.1: Connector ABB type CSE-A-36630-01 Fig. 7.7.1.2: Connector ABB type Kabeldon CSE-A-36630-02
Table 7.7.1.1: Technical data of the connector ABB Kabeldon type CSE-A
Table 7.7.2.1 a: Selection of cable connectors, panel width 600 mm, 12 kV, max. 630 A
Cables fitted Cable connector manufacturer / connector type
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 12630-01
CSE-A 12630-01
●
CSEP-A 12630-01
CSE-A 12630-01
25 - 70 ●
CSAP-A 12xx
CSE-A 12630-01
● CSEP-A 12630-01
CSAP-A 12xx
● 430TB CB12-630 RSTI-58xx
● ● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
CB12-630
● 430TBM-P3
2xCC12-630
430TB CB12-630 RSTI-58xx
●
300SA CSA12-... RSTI-CC-58SA
12 630 25 - 300
400TB/G
● ●
400PB
CB12-630 RSTI-58xx
430TBM-P2
● CC12-630 RSTI-CC-58xx
300SA
CSA12-... RSTI-CC-58SA
CB12-630
● 2 x CC12-630
CSA12-...
● SET12
SET12
●
SEHDK13.1
SET12
50- 300 ●
MUT13
SET12
● SEHDK13.1
MUT13
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 484TB/G
● 484TB/M-P2
● 484TB/M-P3
70 - 630 484TB/G
●
800SA
484TB/M-P2
●
800SA
● CSE-A 12630-02
CSE-A 12630-02
●
CSEP-A 12630-02
CSE-A 12630-02
95 - 300 ●
CSAP-A 12xx
CSE-A 12630-02
12 630 ● CSEP-A 12630-02
CSAP-A 12xx
● SEHDT13
300 - 500 SEHDT13
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA12-..
● CSE-A 12630-03 440TB/G
● 440TB/G-P2
CSE-A 12630-03 440TB/G
400 - 630 ●
CSAP-A 12xx 400PB
440TB/G-P2
●
400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
CB12-630 RSTI-58xx
● 430TBM-P3
2 x CC12-630 2 x RSTI-CC-58xx
CB12-630 RSTI-58xx
400TB/G
25 - 300 ● CC12-630 RSTI-CC-58xx
400PB
CSA12... RSTI-CC-58SA
430TBM-P2
●
300SA
CB12-630 RSTI-58xx
● 2 x CC12-630 2 x RSTI-CC-58xx
CSA12... RSTI-CC-58SA
● 484TB/M-P2
● 484TB/M-P3
484TB/M-P2
70 - 630 ●
800SA
484TB/M-P3
●
800SA
CSE-A 12630-02
12 1250 ●
CSEP-A 12630-02
CSE-A 12630-02
●
2 x CSEP-A 12630-02
CSE-A 12630-02
95 - 300
● CSEP-A 12630-02
CSAP-A 12..
CSE-A 12630-02
● 2 x CSEP-A 12630-02
CSAP-A 12..
300 - 500 ● SEHDT13
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA12-...
CB36-630(1250)
● 2 x CC36-630(1250)
CSA12-...
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 12630-03
●
CSEP-A 12630-03
CSE-A 12630-03
●
2 x CSEP-A 12630-03
CSE-A 12630-03
● CSEP-A 12630-03
400 - 630 CSAP-A 12..
CSE-A 12630-03
● 2 x CSEP-A 12630-03
CSAP-A 12..
● 440TB/G-P2
440TB/G-P2
●
400PB
12 1250
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
●
2 x RSTI-CC-x95x
RSTI-x95x
●
400 - 800 RSTI-CC-68SA
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SA
RSTI-x95x
● 2 x RSTI-CC-x95x
RSTI-CC-68SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 24630-01
CSE-A 24630-01
●
CSEP-A 24630-01
CSE-A 24630-01
25 - 70 ●
CSAP-A 24xx
CSE-A 24630-01
● CSEP-A 24630-01
CSAP-A 24xx
● SET24
SET24
●
SEHDK23.1
SET24
25- 240 ●
MUT23
SET24
● SEHDK23.1
MUT23
● CB24-630 RSTI-58xx
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
24 630 CB24-630
●
2xCC24-630
CB24-630 RSTI-58xx
●
25 - 300 CSA24-... RSTI-CC-58SA
CB24-630 RSTI-58xx
● CC24-630 RSTI-CC-58xx
CSA24-... RSTI-CC-58SA
CB24-630
● 2 x CC24-630
CSA24-...
● K430TB
● ● K400TB/G
● K430TBM-P2
● K430TBM-P3
K430TB
35 - 300 ●
300SA
K400TB/G
● ●
400PB
K430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● K484TB/G
● K484TB/M-P2
● K484TB/M-P3
70 - 630 K484TB/G
●
800SA
K484TB/M-P2
●
800SA
● CSE-A 24630-02
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
95 - 300 ●
CSAP-A 24xx
CSE-A 24630-02
24 630 ● CSEP-A 24630-02
CSAP-A 24xx
● SEHDT23
300 - 500 SEHDT23
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA24-..
● CSE-A 24630-03 K440TB/G
● K440TB/G-P2
CSE-A 24630-03 K440TB/G
400 - 630 ●
CSEP-A 24630-03 400PB
K440TB/G-P2
●
400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
CB24-630 RSTI-58xx
●
2 x CC24-630 2 x RSTI-CC-58xx
CB24-630 RSTI-58xx
25-300
● CC24-630 RSTI-CC-58xx
CSA24... RSTI-CC-58SA
CB24-630 RSTI-58xx
● 2 x CC24-630 2 x RSTI-CC-58xx
CSA24... RSTI-CC-58SA
● K400TB/G
● K430TBM-P2
● K430TBM-P3
35 - 300 K400TB/G
●
400PB
K430TBM-P2
●
300SA
● K484TB/M-P2
● K484TB/M-P3
K484TB/M-P2
70 - 630 ●
800SA
K484TB/M-P3
24 1250 ●
800SA
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
●
2 x CSEP-A 24630-02
CSE-A 24630-02
95 - 300
● CSEP-A 24630-02
CSAP-A 24..
CSE-A 24630-02
● 2 x CSEP-A 24630-02
CSAP-A 24..
300 - 500 ● SEHDT13
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA12-...
CB36-630(1250)
● 2 x CC36-630(1250)
CSA12-...
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 24630-03
●
CSEP-A 24630-03
CSE-A 24630-03
●
2 x CSEP-A 24630-03
CSE-A 24630-03
● CSEP-A 24630-03
400 - 630 CSAP-A 24..
CSE-A 24630-03
● 2 x CSEP-A 24630-03
CSAP-A 24..
● K440TB/G-P2
K440TB/G-P2
●
400PB
24 1250
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
●
2 x RSTI-CC-x95x
RSTI-x95x
●
400 - 800 RSTI-CC-68SA
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SA
RSTI-x95x
● 2 x RSTI-CC-x95x
RSTI-CC-68SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CB36-630
CB36-630
●
CC36-630
CB36-630
25 - 300 ●
CSA36-...
CB36-630
● CC36-630
CSA36-...
● M484TB/G
● M484TB/M-P2
● M484TB/M-P3
M484TB/G
●
35 - 630 800SA
M484TB/M-P2
●
800SA
36 630
M484TB/M-P3
●
800SA
● CSE-A 36630-01
50 - 70 CSE-A 36630-01
●
CSEP-A 36630-01
● M430TB
● M400TB/G
● M400TB/G-P2
● M430TBM-P2
M430TB
50 - 240 ●
300SA
M400TB/G
● ●
400PBxx
M430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● RSTI-68xx
RSTI-68xx
●
RSTI-CC-68xx
RSTI-68xx
50 - 300 ●
RSTI-CC-68SAxx
RSTI-68xx
● RSTI-CC-68xx
RSTI-CC-68SAxx
● SET36
70 - 300 SET36
●
MUT33
● CSE-A 36630-02
95 - 300 CSE-A 36630-02
●
CSEP-A 36630-02
36 630 ● SEHDT33
300 - 500 SEHDT33
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA36-..
● M440TB/G
● M440TB/G-P2
M440TB/G
300 - 630 ●
400PBxx
M440TB/G-P2
●
400PBxx
● CSE-A 36630-03
400 - 630 CSE-A 36630-03
●
CSEP-A 36630-03
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CB36-630
●
CC36-630
CB36-630
●
2 x CC36-630
CB36-630
25 - 300
● CC36-630
CSA36-...
CB36-630
● 2 x CC36-630
CSA36-...
● M484TB/M-P2
35 - 630 M484TB/M-P2
●
800SA
● M400TB/G-P2
● M430TBM-P2
M400TB/G
50 - 240 ●
+400PBxx
M430TBM-P2
●
+300SA
RSTI-68xx
●
RSTI-CC-68xx
RSTI-68xx
●
36 1250 2 x RSTI-CC-68xx
RSTI-68xx
50 - 300
● 2 x RSTI-CC-68xx
RSTI-CC-68SA
RSTI-68xx
● 2 x RSTI-CC-68xx
RSTI-CC-68SA
CSE-A 36630-02
95 - 300 ●
CSEP-A 36630-02
300 - 500 ● SEHDT33
● M440TB/G-P2
300 - 630 M440TB/G-P2
●
400PBxx
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA36-..
CB36-630(1250)
● 2 x CC36-630(1250)
CSA36-..
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 36630-03
400 - 630 ●
CSEP-A 36630-03
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
36 1250 ●
2 x RSTI-CC-x95x
400 - 800
RSTI-x95x
●
RSTI-CC-68SAxx
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SAxx
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 12630-01
CSE-A 12630-01
●
CSEP-A 12630-01
CSE-A 12630-01
25 - 70 ●
CSAP-A 12xx
CSE-A 12630-01
● CSEP-A 12630-01
CSAP-A 12xx
● 430TB CB12-630 RSTI-58xx
● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
430TB CB12-630 RSTI-58xx
●
12 630 25 - 300 300SA CSA12-... RSTI-CC-58SA
400TB/G
●
400PB
CB12-630 RSTI-58xx
430TBM-P2
● CC12-630 RSTI-CC-58xx
300SA
CSA12-... RSTI-CC-58SA
● SET12
SET12
●
SEHDK13.1
SET12
50- 300 ●
MUT13
SET12
● SEHDK13.1
MUT13
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 484TB/G
● 484TB/M-P2
484TB/G
70 - 630 ●
800SA
484TB/M-P2
●
800SA
● CSE-A 12630-02
CSE-A 12630-02
●
CSEP-A 12630-02
CSE-A 12630-02
95 - 300 ●
CSAP-A 12xx
12 630 CSE-A 12630-02
● CSEP-A 12630-02
CSAP-A 12xx
● SEHDT13
300 - 500 SEHDT13
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA12-..
● CSE-A 12630-03 440TB/G
400 - 630 CSE-A 12630-03 440TB/G
●
CSAP-A 12xx 400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 24630-01
CSE-A 24630-01
●
CSEP-A 24630-01
CSE-A 24630-01
25 - 70 ●
CSAP-A 24xx
CSE-A 24630-01
● CSEP-A 24630-01
CSAP-A 24xx
● SET24
SET24
●
SEHDK23.1
SET24
25 - 240 ●
MUT23
SET24
● SEHDK23.1
MUT23
24 630 ● CB24-630 RSTI-58xx
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
CB24-630 RSTI-58xx
25 - 300 ●
CSA24-... RSTI-CC-58SA
CB24-630 RSTI-58xx
● CC24-630 RSTI-CC-58xx
CSA24-... RSTI-CC-58SA
● K430TB
● K400TB/G
● K430TBM-P2
K430TB
●
35 - 300 300SA
K400TB/G
●
400PB
K430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● K484TB/G
● K484TB/M-P2
K484TB/G
70 - 630 ●
800SA
K484TB/M-P2
●
800SA
● CSE-A 24630-02
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
95 - 300 ●
CSAP-A 24xx
24 630 CSE-A 24630-02
● CSEP-A 24630-02
CSAP-A 24xx
● SEHDT23
300 - 500 SEHDT23
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA24-..
● CSE-A 24630-03 K440TB/G
400 - 630 CSE-A 24630-03 K440TB/G
●
CSAP-A 24xx 400PB
2300
1760 1760
Fig. 8.1.1.1.3: Feeder panel 2000 A with current and voltage transformer Fig. 8.1.1.1.4: Feeder panel 2500 A with current and voltage transformer
and three cables per phase and four cables per phase, cooling by heat sinks
2300
2870
1760
2090
Fig. 8.1.1.1.5: Feeder panel 2500 A with current sensor, voltage transform-
er and three cables (630 mm2) per phase, cooling by fan
2500
1760
Voltage sensor Inner cone socket 2nd coupling electrode Current transformer
1..3 x Size 2 or for capacitive voltage Current sensor
1..4 x Size 3 indicator in the door
Surge arrester
Current sensor
Voltage sensor
up to 1250 A
Current sensor
Voltage sensor
Current transformer
up to 1250 A
Table 8.1.1.1.1: Overview of variants of incoming and outgoing feeder panels with inner cone termination system
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 600 mm: I r: ... 1250 A (2 ... 3 x size 2 and 1 ... 2 x size 3) 1)
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 800 mm: I r: ... 1250 A (2 x size 2 and 1 ... 3 x size 3) 1)
I r: ... 2500 A (3 ... 4 x size 3)
I p: ... 40 kA
1)
Three sockets per phase only in conjunction with current transformers to fig. 7.11.3.1
Fig. 8.1.1.2.1: Feeder panel with outer cone, 1250 A Fig. 8.1.1.2.2: Double feeder panel 24 kV, 630 A
2300
2300
1760 1760
Voltage
transformer,
isolatable and
plugged
Table 8.1.1.2.1: Overview of variants of feeder panels with outer cone termination system
U r: ... 36 kV
I r: ... 1250 A
Panel width 600 mm:
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 24 kV
Double feeder panel
I r: ... 630 A
Panel width 2 x 400 mm:
I r: ... 25 kA
The structure of the double feeder panel deviates from that of a –– Only the outer cone plug system (one or two cables per
conventional outgoing feeder panel as described below. phase) to DIN 47636 is used.
–– The double panel facilitates even more compact station –– Only ring core current transformers or ring core sensors are
planning for systems up to 24 kV. used.
–– The width (= transport width) of a double feeder panel –– Two separate low voltage compartment doors (width 400
is 800 mm, with two outgoing feeders of 400 mm width mm) are fitted.
grouped together in the double panel.
–– Technical data which deviate from the conventional panel
–– The busbar compartment for the two feeders in a double (compare section 4):
feeder panel is a continuous gas compartment extending
over the panel width of 800 mm. Ur: ...24 kV
–– Ik: ...25 kA
–– The two circuit-breaker compartments in a double feeder Ir (feeder): ...630 A
panel are two independent units. Ir (busbar): ...2500 A
Fig. 8.1.1.2.3: Double feeder panel: version with busbar at the front, two cables per phase and surge arresters
400 mm
800 mm
Incoming feeder panels ( Ir up to 4000 A, fig. 8.1.1.3.1) Outgoing feeder panels within a block with parallel bus-
bars ( I r up to 2500 A, fig. 8.1.1.3.2)
In this version, the busbars of two double busbar panels of
800 mm width each are connected in parallel by the disconnec- The feeder current coming from the two parallel busbars is fed via
tors. These two panels thus perform the function of a single bus- the two disconnectors and the circuit-breaker to the cable sock-
bar panel for currents up to 4000 A. ets. This double busbar panel thus performs the function of a sin-
gle busbar panel with one busbar for currents up to 4000 A.
The operating current coming from the cable sockets is fed via the
two circuit-breakers and the four disconnectors in the two panels Display of the switch positions and control of the switching de-
to the two parallel busbars. vices are effected by the human-machine interface of the protec-
tion and control unit. The function of the panel as a single busbar
Display of the switch positions and control of the switching de- panel is shown on the display of this human-machine interface.
vices are effected at the master control unit (only one of the two
human-machine interfaces is used for display and control). The On earthing, the earthing switch is operated while the pure dis-
function of the two panels as a single busbar panel is shown on connector remains in the OFF position.
the display of this human-machine interface.
The variants for this panel version can be found in section 8.2.1.
On earthing, the two earthing switches are operated while the
pure disconnectors remain in the OFF position.
2090
1760
Fig. 8.1.1.4.1: Cable termination panel 2000 A Fig. 8.1.1.4.2: Cable termination panel 1250 A with voltage transformer at
the cable
2300
2300
1760 1760
U r: ... 36 kV
Panel width 800 mm: I r: ... 2500 A (3 or 4 x size 3)
I p: ... 40 kA
Voltage sensor Inner cone socket 2nd coupling electrode Current transformer
1..3 x size 2 or for capacitive voltage Current sensor
1..4 x size 3 indicator in the door
Surge arrester
Current sensor
Voltage sensor
up to 1250 A
Current sensor
Voltage sensor
Current transformer
up to 1250 A
Table 8.2.1.1.1: Overview of variants of incoming and outgoing feeder panels with inner cone termination system
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 600 mm: I r: ... 1250 A (2 ... 3 x size 2 and 1 ... 2 x size 3) 1)
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 800 mm: I r: ... 1250 A (2 x size 2 und 1 ... 3 x size 3) 1)
I r: ... 2500 A (3 ... 4 x size 3)
I p: ... 40 kA
1) Three sockets per phase only in conjunction with current transformers to fig. 7.11.3.1
2300
2300
1760 1760
Voltage
transformer,
isolatable and
plugged
Table 8.2.1.2.1: Overview of variants of feeder panels with outer cone termination system
U r: ... 36 kV
I r: ... 1250 A
Panel width 600 mm:
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 24 kV
Double feeder panel
I r: ... 630 A
Panel width 2 x 400 mm:
I r: ... 25 kA
The structure of the double feeder panel deviates from that of a –– Only the outer cone plug system (one or two cables per
conventional outgoing feeder panel as described below. phase) to DIN 47636 is used.
–– The double panel facilitates even more compact station –– Only ring core current transformers or ring core sensors are
planning for systems up to 24 kV. used.
–– The width (= transport width) of a double feeder panel –– Two separate low voltage compartment doors (width
is 800 mm, with two outgoing feeders of 400 mm width 400 mm) are fitted.
grouped together in the double panel.
–– Technical data which deviate from the conventional panel
–– The busbar compartment for the two feeders in a double (compare section 4).
feeder panel is a continuous gas compartment extending
over the panel width of 800 mm. Ur: ...24 kV
Ik: ...25 kA
–– The two circuit-breaker compartments in a double feeder Ir (feeder): ...630 A
panel are two independent units. Ir (busbar): ...2500 A
Fig. 8.2.1.2.3: Double feeder panel: version with two cables per phase and surge arresters
Busbar at rear
Busbar at front
400 mm
800 mm
Fig. 8.2.1.3.1: Cable termination panel 1250 A (Example with continuous Fig. 8.2.1.3.2: Cable termination panel 2000 A (Example with continuous
busbar at the front) busbar at the rear and voltage transformer on the outgoing feeder)
2300
2300
1760 1760
or
U r: ... 36 kV
Panel width 800 mm: I r: ... 2500 A (3 or 4 x size 3)
I p: ... 40 kA