CEILING LINE

3-22 MM SQ. THHN + 1-14 MM SQ.


THHN (GND) IN 27 MM DIA. EMT

3-5.5 MM SQ. THHN + 1-5.5 MM SQ.


THHN (GND) IN 16 MM DIA. EMT

5TH FLOOR LINE


pp5 lp5

3-22 MM SQ. THHN + 1-14 MM SQ.


THHN (GND) IN 27 MM DIA. EMT

3-5.5 MM SQ. THHN + 1-5.5 MM SQ.


THHN (GND) IN 16 MM DIA. EMT

4TH FLOOR LINE


pp4 lp4

3-22 MM SQ. THHN + 1-14 MM SQ.


THHN (GND) IN 27 MM DIA. EMT

3-5.5 MM SQ. THHN + 1-5.5 MM SQ.


THHN (GND) IN 16 MM DIA. EMT

3RD FLOOR LINE


pp3 lp3

3-5.5 MM SQ. THHN + 1-5.5 MM SQ. THHN


(GND) IN 16 MM DIA. EMT

2ND FLOOR LINE


lpc5 lpc6 lpc7 lpc8 lpc9 lpc10 lpa2
ppa2

overhead service entrance


connected to 230v ac, 3phase,
4 wire, 60hz

DP5 DP4 DP3 3-5.5 MM SQ. THHN + 1-5.5 MM SQ. THHN


(GND) IN 16 MM DIA. EMT

DPA
ATS PDP MDP DPC M M M M M M M
M M M M M M M

GROUND FLOOR LINE


lpc1 lpc2 lpc3 lpc4 ppa1 lpa1

100 kva (80kw)


genset, 230v,
60hz, 1800 rpm,
0.8pf, 3ph

electrical riser diagram

designer Name of Project owner contents sheet no.

5 storey bldg., call center office a. electrical riser diagram


engr. justin gabriel b. gabotero mr. & mrs. gabotero

address
with commercial stores

address
E
eedesign
prc: 2015-2-00831
ptr: 09152194088

tin: 00031239919
place issued: soutchrest
date issued: feb. 5, 2019 san agustin 2, dasmarinas city, cavite san agustin 2, dasmarinas city, cavite 6