Simplex-4009 IDNet NAC Extender Installation Manual Rev B
Simplex-4009 IDNet NAC Extender Installation Manual Rev B
Installation Instructions
Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of the
carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
• 4009-9808 Class A Adapter Option Card - allows fault tolerance in the case of
open circuit wiring faults on the NACs.
• 4009-9807 NAC Option Card - adds four conventional Notification Appliance
Circuits.
• 4009-9809 IDNet Repeater Option Card - regenerates and provides a power and
distance boost for the IDNet channel. When IDNet Repeater Option Card is
used, the fiber option is not available to the 4009 IDNet.
• 4009-9810 (Class B)/4009-9811 (Class A) Fiber Optic Receiver - receives
IDNet communication over a fiber optic channel and regenerates the IDNet
signal. The fiber option is used with the 4090-9105 (Class B)/4090-9107
(Class A) Fiber Optic Transmitter to form an IDNet fiber link.
Introduction, continued The 4009 IDNet connects as an end-of-line device to a compatible notification
appliance circuit from the host panel. It provides eight amperes of DC signaling
power to either four or eight supervised reverse-polarity NACs, style Y or style
Z. Alarms from the host panel signal the four (or eight) 4009 IDNet NACs to
extend the alarm.
The 4009 IDNet can also minimize transmission line losses associated with
sending large currents long distances within buildings. In a fire alarm system
with the 4009 IDNet power supply and batteries for notification appliances are
located near the actual notification appliances, saving system power and battery
capacity while minimizing line losses.
4009 IDNet Configuration When the desired options have been installed in the 4009 IDNet, set the
Hardware Configuration Switch SW1 to match the installed options (see
Table 1). If the 4009 is not connected to IDNet, set SW1/Position 8 to ON for
hardwire control (see paragraph “Hardwired 4009 IDNet Control”). The desired
control options for the 4009 IDNet are set by the Software Configuration DIP
Switch SW2 (see Tables 2 and 3).
When the 4009 IDNet is connected to IDNet, set the Hardware Configuration
Switch SW1 (see Table 1) to match the installed options; and set SW1/Position 8
to OFF for IDNet addressable control (see paragraph “Addressable 4009 IDNet
IDNet Control”). Set the IDNet address on SW2 using Figure 5 as a reference.
2
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
Inputs 1 and 2 can be configured either as EOL devices on the host NAC or as
appliances on that NAC, based on whether an end-of-line load is presented to the
host. Up to four 4009 IDNet NAC Extenders can be attached to the FACP(s)
NAC.
TRANSFORMER
ASSEMBLY
AC WIRING HARNESS
733-991 (120VAC 4009) or
733-992 (220/240VAC
4009 SYSTEM BOARD 4009)
565-771 (see Figure 4)
AC WIRING BLOCK
3
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
The 4009 IDNet system board provides 4 hardwired NACs. NACs 1 through 4
are Class B, reverse polarity Notification Appliance Circuits. Each circuit has one
polarity for supervision state and the opposite polarity for alarm state. Field wiring
terminations are provided for 12 AWG - 18 AWG wire. Refer to the 842-068
Field Wiring Diagram for complete wiring, compatible appliances, current, and
line distance information. Each circuit is capable of being independently
controlled by the 4009 IDNet, as commanded by the host panel.
The notification circuits use a 10k end-of-line resistor for supervision. The circuit
is monitored for short and open circuit line faults when in the standby (not
energized) condition. In the event of a short circuit, the 4009 IDNet will not
activate the NAC while the short circuit fault is present. During coded signal
operation, the 4009 IDNet checks for a short during each “off”, and holds the
circuit off if a short is detected. Short and open circuit faults are reported to the
host panel via the command channel (either IDNet or hardwired, depending on
configuration) and can be identified by a blinking trouble LED on the 4009 IDNet
during supervisory state.
The NACs are configurable as “Class A” circuits with the addition of an option
card that plugs onto the base board. The option card also provides the additional
field wiring terminations needed for Class A. The 4009 IDNet monitors for
insertion of the Class A Option Card. The presence of the Class A Adapter Option
Card must match the Hardware Configuration Switch (SW1) for proper operation
(see Table 1).
In addition, when configured as an IDNet peripheral, each NAC has the ability,
under software control, to disconnect its supervision, allowing earth fault
isolation (this operation is also performed automatically as part of the power-up
sequence).
Battery Charger
The battery charger charges lead acid batteries up to 18AH. Batteries are
supervised for low/missing battery and depleted battery. The battery charger
output remains disabled until a battery is sensed.
The Canadian version of the 4009 IDNet NAC Extender includes a low battery
cutout module and harness. The factory installed battery cutout module replaces
the standard (US version) battery harness. The module disconnects the batteries
if the terminal voltage drops below 19.3VDC during battery standby operation.
Connection to the batteries is restored on resumption of AC power.
4
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
System Configuration A functional block diagram depicting the interconnections between modules is
shown in Figure 3. Alarm signal and 0V connections provide alarm and trouble
operation. The host FACP can detect EARTH faults on any NAC signal.
Notes:
1. This option card position is for the IDNet Repeater Option Card or the Fiber Receiver Option Card.
2. The Fiber Transmitter Option Card is a remote connection and not part of the 4009 cabinet assembly.
Figure 3. 4009 IDNet Functional Block Diagram
5
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
TB1, TB2
HARDWIRED NAC
(NAC 1-4)
P4
P1 AND P2 4-CIRCUIT NAC
CLASS A ADAPTER OPTION CARD
INTERFACE INTERFACE
LED(s) 1-4
NAC STATUS LED(s) 5-8
INDICATORS SYSTEM TROUBLE
INDICATORS
TB6 LED 9
AUXILARY POWER AC POWER
OUTPUT INDICATOR
(1 AMP AVAILABLE)
BROWNOUT
ADJUSTMENT
(SEE NOTE)
TB5
NAC CONTROL
INTERFACE
(HOST NAC IN)
P6
IDNet REPEATER
CARD or FIBER
RECEIVER CARD
6
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
System Switches and Note: DIP switch in “1” position is “ON” while DIP switch in “0” position is
Indicators, continued “OFF”.
1 2 3 4 5 6 7 8
ON
OFF 1 = ON 0 = OFF
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
1000 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
0100 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
0110 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
1110 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
1001 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251
0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252
1011 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253
0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254
1111 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255
7
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
Each output NAC has a yellow LED (see Figure 4 for location of LEDs) to
indicate a trouble condition or the active state of that NAC. The condition/state
for the NACs are as follows:
The system trouble indicators consist of a bank of four yellow LEDs (see Figure
4 for location of LEDs) that are used to signify various trouble conditions within
the 4009 IDNet system. Only one trouble at a time is indicated, highest trouble
state indicated first. When that trouble clears, additional troubles, if present, will
be indicated. Table 4 lists system troubles from highest trouble state (invalid
configuration) to lowest trouble state (Normal).
8
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
4009 IDNet Option Interfaces The 4009 IDNet supports several optional add-on cards. Connectors are
provided on the base assembly of the 4009 IDNet System Board (565-771) to
support the available option cards. Optional hardware must be configured with
the Hardware Configuration DIP Switch SW1 for proper system operation.
The Class A Adapter Option Cards (see Figure 4) plug into connectors P1 and
P2 located on the 4009 IDNet system Board (see Figure 4). One Class A
Adapter Option Card provides Class A/Style Z functionality on two NACs.
Refer to the 4009-9808 Class A Adapter Option Card Installation Instructions
(574-326) for detailed information on installing this option card.
The 4-ciruit NAC Card is an option card for the 4009 IDNet. Refer to the 4009
9807 NAC Option Card Installation Instructions (574-325) for detailed
information on installing this option card. The NAC option card provides four
additional hardwired NACs to the 4009 IDNet base configuration of four NACs.
Each of the four NACs on the NAC option card is functionally equivalent to the
NACs on the 4009 system board, except that the option NACs are rated at 1.5
amps. The NAC option card plugs into connector P4 (see Figure 4) on the 4009
system board. The NACs are configurable as “Class A” circuits with the addition
of Class A Adapter Option Cards that connect to the two Class A adapter connector
interfaces located on the NAC Option Card. The NAC Option Card signal power
for the four NACs is received from 4009 IDNet system board connector P7 (see
Figure 4) using wiring harness 733-972.
The IDNet Repeater Card is an option card for the 4009 IDNet. The IDNet
Repeater Option Card takes the IDNet signal that the 4009 IDNet receiver has
received, and retransmits it on its output side at host panel IDNet levels. The
IDNet Repeater Option Card is used in IDNet mode only (SW1/Position 8 OFF).
Refer to the 4009 IDNet Repeater Option Card Installation Instructions (574-
327) for detailed information on installing this option card. The IDNet Repeater
Option Card connects via a 14-pin header to 4009 IDNet system board connector
P6 (see Figure 4).
9
Technical Manuals Online! - http://www.tech-man.com
4009 IDNet NAC Extender, Continued
4009 IDNet Option Interfaces, Fiber Receiver Card (565-903 Class B or 565-902 Class A) and Fiber
continued Transmitter Card (565-901 Class B or 565-900 Class A)
The IDNet Fiber Transmitter and 4009 IDNet Fiber Receiver work together to
form a fiber optic link from an IDNet run to a remote 4009 Addressable NAC.
Refer to the 4009 Fiber Optic Link Installation Instructions (574-182) for
detailed information on installing this option card. The primary intent of the
fiber optic link is to allow remote buildings (within 3,000ft.) to be connected to
the IDNet channel, but to minimize susceptibility to electrical transients. The
fiber optic link is made up of these two boards and the optical fibers. The 4009
IDNet Fiber Receiver Card receives power from, and communicates with the
4009 IDNet through 14-pin connector P6 (on the 4009 IDNet system board).
The fiber receiver regenerates the IDNet channel for connection to other IDNet
peripherals at the remote site.
The IDNet Fiber Transmitter is located on the FACP end of the fiber optic link
and receives power (24VDC) from the host panel.
10
Technical Manuals Online! - http://www.tech-man.com
System Installation
General Information Important: Notify the appropriate personnel (building occupants, fire
department, monitoring facility, etc.) of the installation.
The following paragraphs contain material which is applicable to all 4009 IDNet
systems. Be sure that you are thoroughly familiar with this material before
installing your 4009 IDNet.
To help you with installation of this and other Simplex Fire Alarm equipment,
the following publication is available for general reference: How to Wire a
Building for a Fire Alarm System (FA2-91-001 or 575-892).
Tools and Equipment The following tools and equipment are required to install the 4009 IDNet:
Required
• 1/4-inch flat-tip screwdriver, 8-inches long
• 1/8-inch flat-tip screwdriver, 4-inches long
• Volt-Ohmmeter
• Diagonal cutting pliers
• Wire strippers
• Listed end-of-line resistors (ordered seperately)
10K resistor (733-804)
• Field Wiring Diagram 842-068.
General Notes 1. All wiring must be installed in accordance with local codes.
2. A minimum of 6 inches of free conductor is required at each electrical box
to facilitate terminations.
3. A 12-inch service loop of cable is required for all continuous pulls through
an electrical box.
4. All system wiring subject to physical damage must be mechanically
protected based on the environment to which the cable is subjected.
5. A neatly wired system helps assure an accurate inspection of all connections
and simplify troubleshooting.
11
Technical Manuals Online! - http://www.tech-man.com
System Installation, Continued
Mounting the 4009 IDNet Note: The following pages provide a detailed description of the installation.
If you experience problems that cannot be resolved, call your local
Simplex Branch Office.
Use the following procedure when mounting a 4009 IDNet.
CAUTION: Read all instructions carefully before cutting conduit/service
entrances and installing back box. Failure to comply with all
installation requirements may result in a violation of UL or
FCC regulations.
1. Carefully open the shipping container.
2. Remove the 4009 IDNet from the shipping container and lay the unit on a
flat surface.
3. Unlock and open the panel door. Remove the electronic card cage assembly
and store it in a safe dry area. Disconnect the AC wiring harness from the
card cage before removing it from the box.
4. Determine the amount and proper location of conduit/service entrances (see
Figure 6). Make all appropriate entrances into the back box.
Power-Limited and Non-Power Limited wiring must enter through separate
conduit/service entrances. AC power entrance into the back box is
recommended at the bottom right side of the back box.
TOP VIEW
C
KNOCKOUT
B SCREW/NAIL
D HOLES for SEMI-
FLUSH
Recommended Conduit Locations MOUNTING
Locate conduit entry approximately
where shown.
NON-POWER-LIMITED
WIRING ONLY A
12
Technical Manuals Online! - http://www.tech-man.com
System Installation, Continued
Mounting the 4009 IDNet, 5. Mount back box to wall. Back box must be level and plumb. For surface
continued mounting use the teardrop and clearance holes located in the rear of the box
and screw to wall.
6. Wire Non-Power-Limited wiring in the shaded areas only (see Figure 6),
this includes AC input and battery connections. All other wiring is Power-
Limited. Maintain at least ¼-inch spacing between all Power-Limited and
Non-Power-Limited wiring.
7. Connect the AC wiring harness and install the electronic card cage assembly
to the 4009 IDNet cabinet.
Wiring the 4009 IDNet When wiring the 4009 IDNet, refer to the 842-068 Field Wiring Diagram, the
4009 IDNet NAC Extender Connection Diagram (Figure 7), and the following
system wiring requirements.
• All wiring, except incoming power and ground connecting wires, must be
free from grounds or shorts and have a resistance of one megohm, or higher,
to EARTH.
• All wires are to be copper conductors only, except fiber cables. All
equipment must be installed in accordance with the manufacturer’s
recommendations and the specifications and standards of the Authority
Having Jurisdiction (AHJ). The installation of all wiring, cable, and
equipment must be in accordance with NFPA 70.
• If shielded wire is used, the metallic continuity of the shield must be
maintained and insulated throughout the entire length of the cable. The
entire length of the cable must have a resistance of one megohm to earth.
• When running wires to the 4009 IDNet, identify the wires appropriately:
Only system wiring can be run in the same conduit which includes dedicated
NAC wiring, IDNet wiring, 24V AUX wiring, and the four NAC circuits (an
additional four NAC circuits are available as a field-installed option).
Input power and external battery power are Non-Power-limited and
cannot be run with Power-Limited system wiring.
13
Technical Manuals Online! - http://www.tech-man.com
System Installation, Continued
Notes:
1. Refer to 842-068 Field Wiring Diagram for detailed information on 4009 IDNet System
Wiring Configurations.
2. External Battery requires splicing into existing Battery harness (733-945), see Note 1.
14
Technical Manuals Online! - http://www.tech-man.com
System Installation, Continued
Mounting and Wiring Refer to the 842-068 Field Wiring Diagram for detailed information, and the
Peripheral Devices procedure listed below when installing the 4009 IDNet peripheral devices.
1. Determine the mounting locations of the peripheral devices and install
system wires from the mounting location of each peripheral device to the
4009 system board. All wiring to be minimum 18 AWG, supervised, and
Power-Limited.
2. Install all peripheral devices and connect them to appropriate wires. (Refer
to the installation instructions packed with the devices.)
3. For 2-wire Class B/Style Y and 4-wire Class A/Style Z devices, a 10K, 1/2
W (Brown/Black/Orange) End-of-Line Resistor (EOLR) is provided. Refer
to Field Wiring Diagram 842-068.
System Wiring Configurations The base 4009 IDNet NAC Extender has the following system wiring
configurations:
• 2-wire Class B/Style Y NAC (reverse polarity)
• 4-wire Class A/Style Z NAC (reverse polarity)
• Hardwired NAC Control Inputs from host FACP (Class A/Style Z &
Class B/Style Y)
• Addressable IDNet Slave Interface (Class B/Style 4 and Class A/Style 6)
• Addressable IDNet Repeater Interface (Class B/Style 4 and Class A/Style 6)
• Addressable IDNet Fiber Receiver/Transmitter Interface (Class B/Style 4
and Class A/Style 6)
15
Technical Manuals Online! - http://www.tech-man.com
574-181
Rev. B