Performance Analyses of Helical Coil Heat Exchangers. The Effect of External Coil Surface Modification On Heat Exchanger Effectiveness
Performance Analyses of Helical Coil Heat Exchangers. The Effect of External Coil Surface Modification On Heat Exchanger Effectiveness
of thermodynamics
Vol. 37(2016), No. 4, 137–159
DOI: 10.1515/aoter-2016-0032
RAFAŁ ANDRZEJCZYK
TOMASZ MUSZYŃSKI∗
Abstract The shell and coil heat exchangers are commonly used in heat-
ing, ventilation, nuclear industry, process plant, heat recovery and air con-
ditioning systems. This type of recuperators benefits from simple construc-
tion, the low value of pressure drops and high heat transfer. In helical coil,
centrifugal force is acting on the moving fluid due to the curvature of the
tube results in the development. It has been long recognized that the heat
transfer in the helical tube is much better than in the straight ones be-
cause of the occurrence of secondary flow in planes normal to the main flow
inside the helical structure. Helical tubes show good performance in heat
transfer enhancement, while the uniform curvature of spiral structure is in-
convenient in pipe installation in heat exchangers. Authors have presented
their own construction of shell and tube heat exchanger with intensified
heat transfer. The purpose of this article is to assess the influence of the
surface modification over the performance coefficient and effectiveness. The
experiments have been performed for the steady-state heat transfer. Ex-
perimental data points were gathered for both laminar and turbulent flow,
both for co current- and countercurrent flow arrangement. To find optimal
heat transfer intensification on the shell-side authors applied the number of
transfer units analysis.
∗
Corresponding Author. E-mail: [email protected]
Unauthenticated
Download Date | 5/8/17 6:36 PM
138 R. Andrzejczyk and T. Muszyński
Nomenclature
Greek symbols
α – heat transfer coefficient, w/m2 K
δ – wall thickness, m
γ – area ratio
ρ – density, kg/m3
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 139
Subscripts
av – average
c – cold
cor – corrected
c−a – average at coil side
c−s – coil side
con – contraction
CU – copper
exp – expansion
h – hot
i0 – internal
min – minimum
max – maximum
s−a – average at shell side
s – surface
sh – shell side
t – tube
w – wall
1 Introduction
Striving to ensure high performance of the heat exchangers, HX, nowadays
is a source of universal trend both to the miniaturization of these devices
for both industrial and domestic applications, while maintaining the high-
est possible size to thermal energy ratio. As is well known, in the case of
recuperators the heat transfer coefficient has a decisive influence on their
efficiency [1]. Overall heat transfer coefficient, depends mainly on the lower
value of heat transfer value (HTC) from working media [2]. It is, therefore,
most significant to improve the heat transfer with special attention on the
side of the medium with lower heat transfer coefficient [3].
Helical coils are widely used in applications such as heat recovery sys-
tems, chemical processing, food processing, nuclear reactors, and high-
temperature gas cooling reactors. Helical coils have been widely studied
both experimentally [4] and numerically [5].
Helical coils are characterized by their compactness and high heat trans-
fer coefficient. When fluid flows through a helically coiled tube, the cur-
Unauthenticated
Download Date | 5/8/17 6:36 PM
140 R. Andrzejczyk and T. Muszyński
vature of the coil induces centrifugal force, causing the development of the
secondary flow. This secondary flow enhances fluid mixing and thus heat
transfer. Fluid flow in a helical tube is characterized by the Dean number.
The Dean number, D, is a measure of the geometric average of inertial and
centrifugal forces to the viscous force ratio, and thus is a measure of a mag-
nitude of the secondary flow. For laminar flow and small pipe to coil radius
aspect ratio r/R, frictional loss in a curved tube may be represented as a
function of the Dean number. One of the most frequent uses of helically
coiled tubes is in the shell and coiled tube heat exchangers.
The majority of the studies related to helically coiled tubes and heat
exchangers have dealt with two major boundary conditions, i.e., constant
heat flux and constant wall temperature [6,7]. However, these boundary
conditions are not encountered in most single-phase heat exchangers.
Naphon [8] has investigated thermal performance of helical coils with
and without fins. Two different coil diameters with 9.5 mm diameter cop-
per tube having thirteen turns were used. Hot and cold water were used as
working fluid in the range from 0.10 to 0.22 kg/s and from 0.02 to 0.12 kg/s,
respectively. They have shown that with increasing hot water mass flow
rate the friction factor decreased.
Various helical coils made from a 12.5 mm ID (inside diameter) tube
with various coil diameters ranging from 92 to 1282 mm have been inves-
tigated by Srinivasan et al. [9] to determine friction factors. Four different
coil pitches of 2.5, 3.3, 6.6, and 13.2 tube diameters were tested and graphs
of friction factors with respect to the Dean number were produced. All the
graphs showed breakpoints which were interpreted as the critical Reynolds
number value so that equation was found to describe this critical value for
different tube diameter to shell diameter ratio.
Kumar et al. [10] studied a tube-in-tube helically coiled heat exchanger
for turbulent flow regime. Numerical investigations were done to under-
stand forced laminar fluid flow in rectangular coiled pipes with circular
cross-section by Conte and Peng [11]. Their focus was addressed on explor-
ing the flow pattern and temperature distribution through the pipe.
Patankar et al. [12] discussed the effects of the Dean number on friction
factor and heat transfer in the developing and fully developed regions of
helically coiled pipes. Comparisons between the proposed model and the
experiment showed good agreement. However, the effects of the torsion
and the Prandtl number were not taken into account in the aforementioned
model.
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 141
Unauthenticated
Download Date | 5/8/17 6:36 PM
142 R. Andrzejczyk and T. Muszyński
first part of this paper presents the construction of the test facility and the
design and construction of test exchangers. The second part presents ex-
periments which were carried out on single-phase convection heat transfer
with distilled water as a working medium.
where µ and µp are the dynamic viscosity of the wall and fluid, respectively.
In shell side flow, Reynolds number is calculated as the mass flow rate, Gsh ,
through equivalent diameter, De ,
Gsh De
Resh = . (3)
µl
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 143
a)
Figure 1: Shell coil heat exchanger view (a), centrifugal force acting on the flowing fluid
and axial speed (b), resulting secondary flows (c).
Unauthenticated
Download Date | 5/8/17 6:36 PM
144 R. Andrzejczyk and T. Muszyński
where δ is the wall thickness, and αDB means the heat transfer coefficient
calculated by Eq. (6), Re is based on inner pipe diameter, d0 , and fluid
velocity inside the coil, wc−s
wc−s d0
Re = , (8)
ν
where ν is the kinematic viscosity of fluid.
Overall heat transfer coefficient can be calculated as
D0
1 1 1 ln d0
= + + + Rt + Rsh . (9)
U αsh αi0 2πλcu L
In present study required heat load was set as Q̇ = 1200 W. Thus the
contact area, A, can be calculated from
Q̇
A= . (10)
U LMTD
The logarithmic mean temperature difference LMTD can be used as an
average acting temperature gradient between two fluids. It can be written
as
(T ′ h − T ′ c ) − (T ′′ h − T ′′ c )
LMTD = ′ ′
, (11)
ln T′′ h − T ′′c
T h−T c
where subscripts h and c indicate hot and cold fluids, and superscripts
‘prim’ and ‘double prim’ denote temperature at inlet and outlet, respec-
tively.
LMTD is corrected with the fluid correction factor, F
The account for perpendicular flow, the correction factor of 0.99 [7].
The coil heat exchanger has been developed by using values of water
properties for average temperature, Tav , of cold and hot media. The pres-
sure drop of the heat exchanger for shell and coil side accordingly yields:
H w s−a 2 ρ X w s−a 2 ρ
∆P sh = CD + ζ , (13)
De 2 2
L wa−c 2 ρ X w a−c 2 ρ
∆P c−s = f + ζ , (14)
d0 2 2
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 145
where ρ is the fluid density and overbar denotes the average velocity.
The friction factor for flow inside the coil can be calculated from relation
[22]
" 1/2 # 0.27
0.3164 d0 µw
f= + 0.03 , (15)
Re0.25 E µ
Unauthenticated
Download Date | 5/8/17 6:36 PM
146 R. Andrzejczyk and T. Muszyński
Local drag coefficients for Eqs. (13) and (14) were taken from Bell [23] and
Achenbach [24].
3 Experimental setup
The main aim of surface modification was to increase turbulization at the
outer surface of the coil. As well-known from literature, the heat transfer
coefficient at shell side in case of typical helical heat exchangers is smaller
than the one at coil side [13].
Figure 3: Obtained construction of helical coils: at the left side – coil made from smooth
copper pipe, in the middle – coil with modified surface, at the right side –
photo of modified surface.
Both coils have been made by using a small, smooth copper minichannel
(see Fig. 3). The average length of channels is 1400 mm and average fin
height was equal to 0.5 mm. Each one of built heat exchangers has the
same shell construction.
The rig consists of two closed loops of test fluid. The facility was in-
tended to work with any non-chemically aggressive working fluids. In both
loops, circulation is forced by electrically powered pumps with a magnetic
coupling, capable of providing the mass flow rate from 0.001 to 0.005 g/s
and the overpressure up to 0.8 MPa. This type of pumps has been chosen
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 147
to provide the circulation of fluid in the test sections and to avoid flow pul-
sations. Adjustment of the mass flow rate is realized by two independent
inverters. Figure 4 presents a schematic diagram of the test facility.
The heat exchanger consists of a copper coiled tube and an insulated
shell. The dimensions of the heat exchangers are depicted in Tab. 1. The
hot fluid circuit is heated using a thermostatic bath. A pump circulates the
hot water in the loop with a preset temperature. A set of valves is used to
control the flow rate of cold and hot water, respectively. To measure the
flow rates of the cold and hot fluids a Coriolis-type mass flow meters are in-
stalled upstream of the heat exchanger. The inlet and outlet temperatures
of hot and cold water were recorded using four T-type thermocouples in-
serted at the inlet and outlet collectors. Also, all the pipes and connections
between the temperature measuring stations and heat exchanger were duly
insulated. In order to exclude heat capacity of heat exchanger casing from
calculations, data points were gathered for steady state conditions. After
obtaining constant parameters, temperatures were measured three times
with an accuracy of 0.5 o C in the time steps of 20 min, and the average
values were used for further analysis. Appropriate arrangements were pro-
vided to measure the pressure loss of both tube and shell side. All the tube-
and shell-side fluid properties were assessed at the mean temperature of the
fluid (average of inlet and outlet temperatures). The measured uncertainty
parameters are shown in Tab. 3.
Unauthenticated
Download Date | 5/8/17 6:36 PM
148 R. Andrzejczyk and T. Muszyński
4 Data reduction
The hot and cold heat flux are calculated as a product of water mass flux,
water specific heat capacity and the inlet-outlet water temperature differ-
ence:
Q̇c = cp mc (Tc,out − Tc,in ) , (18)
where γ is the area ratio (Atest−section /Aheader ) and Ccon is the coefficient
of contraction, which is, in turn, a function of this area ratio,
1
Ccon = . (22)
0.639(1 − γ)0.5 + 1
For the expansion into the header from the test section, the following flow
model recommended by Hewitt et al. [27] was also used:
G2 γ(1 − γ)ψs
∆Pexp = , (23)
ρ
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 149
UA
NTU = (24)
Wmin
where U is the overall heat transfer coefficient and A is the heat transfer
surface area of the heat exchanger,
where Wc and Wh are the heat capacity rates of the cold and hot fluids,
respectively. In heat exchanger analysis, it is also convenient to define
another dimensionless quantity called the capacity ratio as
Wmin
W = , (26)
Wmax
Q̇
ε= . (27)
Q̇max
The actual heat transfer rate in a heat exchanger can be determined from
an energy balance on the hot or cold fluids and can be expressed as
Unauthenticated
Download Date | 5/8/17 6:36 PM
150 R. Andrzejczyk and T. Muszyński
where Wmin is the lower heat capacity of cold and hot fluid.
Experimental values of Nusselt number, Nu, at shell side and coil side
were calculated as
αexp _sh De
Nuexp _sh = , (31)
λ
αexp _c−s d0
Nuexp _c−s = . (32)
λ
The Dean number, D, is a dimensionless group in fluid mechanics, which
occurs in the study of flow in curved pipes and channels (Fig. 2):
1
ρwd0 d0 2
D= , (33)
µ 2r
1
U= . (34)
D0
1 1 ln d0
+ +
αexpα_sh αexpα_i0 2πλCU L
5 Experimental results
In order to estimate the influence of surface modifications on flow through
the heat exchanger, as the first step of experimental validation hydraulic
performance of heat exchanger was examined. Because only coil external
surface was modified only shell side flow was investigated in detail for both
reference and modified geometry.
As can be seen in Fig 5. there is no significant difference between the
hydraulic characteristic of plain and modified helical coil heat exchanger.
It should be noted also that the predicted value of pressure drop with
Eq. (13) has good agreement with experimental results, but it tends to
over predict ∆P values for higher flow rates. As well as pressure drop in
shell side the experimental data for pressure drop at coil side was compared
with the prediction given by Eq. (14). Figure 6 clearly presents acceptable
agreement between predictions and experimentally obtained results.
Figure 7 presents’ linear regression values for experimental series grouped
in constant shell side fluid velocities (cold). The resulting heat transfer
coefficient of cold fluid from experimental data was calculated based on
Wilsons plot method [3]. The heat transfer coefficient was calculated for
the tube thickness of 1 mm. The tube material (copper) has the thermal
conductivity, λ, equal to 389 W/mK. It has to be noted that overall heat
transfer coefficient generally is larger for the modified construction of heat
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 151
Unauthenticated
Download Date | 5/8/17 6:36 PM
152 R. Andrzejczyk and T. Muszyński
Figure 7: Linear regression of experimental data for calculating heat transfer coefficient
by Wilsons plot method, for varying hot and constant cold fluid mass flow rate
in case of countercurrent flow.
exchanger. But the difference is quite small. The low values for the small
flow velocities could also be due to the nature of the Wilson plots. It was
noted that small changes in the coefficients used in the Wilson plots had a
small effect on the inner Nusselt numbers, but much larger effects on the
annulus Nusselt numbers. So the Wilson plots may be part of the reason
for the divergence between the experimental and predicted values.
Based on a comparison of theoretical values of Nusselt numbers and
experimental results a good agreement of used correlations can be stated.
The differences at shell side and coil side are not larger than 30%. Re-
sults were shown in Figs. 8 and 9. As was expected based on analytical
modeling of coil heat exchanger the Nusselt number for coil side are clearly
larger than the shell side. Considering pressure drop at shell side are also
significantly smaller than at the coil side.
Figure 10 represents the variations of Nusselt number versus Dean num-
ber for three different water inlet temperatures at shell side and at coil side
for reference heat exchanger construction. It is important to notice that
increment of water temperature reduces obtained Nusselt numbers at shell
side, especially in the low Dean number region. Unfortunately for coil side
the difference is so small than even after zoom experimental points, it is
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 153
Figure 8: Comparison of experimental and theoretical Nusselt number for shell side in
case of the unmodified surface.
Unauthenticated
Download Date | 5/8/17 6:36 PM
154 R. Andrzejczyk and T. Muszyński
Figure 9: Comparison of experimental and theoretical Nusselt number for coil side in
case of the unmodified surface.
a) b)
Figure 10: Variation of Nusselt number with Dean number for different fluid inlet tem-
perature in case of unmodified surface: a) for shell side, b) for coil side.
coiled configuration is highest in case ‘b)’, for spiral coiled with external
surface modification. Parallel flow configuration results with the effective-
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 155
ness of intensified heat exchanger lower about 5% than reference type, but
for lower mass flow rates. This can be explained by measurement error
which is higher for lower flow rates.
Counterflow configuration also depicts similar effectiveness for low flow
rates, but significantly larger for Dean numbers above 3000. In authors,
opinion difference in results may be explained by entrance effects in both
heat exchangers. For parallel flow at the inlet of heat exchanger heat is
Unauthenticated
Download Date | 5/8/17 6:36 PM
156 R. Andrzejczyk and T. Muszyński
Figure 13: Effectiveness of helical coils heat exchanger, as a function of the Dean number
(D): a) parallel flow configuration, b) counter-flow configuration.
transferred due to the large temperature difference, also heat transfer coef-
ficient is enhanced due to inlet effects, therefore surface enhancement does
not play a significant role in it. Afterward with lower temperature differ-
ence in heat exchanger, enhancement of heat transfer coefficient falls within
the measurement error. On another hand for counter flow configuration,
working fluids have similar temperature gradient along the flow path, there-
fore after inlet effects are suppressed, modified surface offers heat transfer
enhancement that is measurable due to the higher temperature difference.
6 Conclusions
Authors presented and successfully implemented, a simple mathematical
methodology to model the shell and coil heat exchanger. In this paper,
results show a comparison between helically coiled heat exchanger with
surface modification by means of micro fins. During the experiments the
mass flow rate in the inner tube and the annulus were both varied, both
the counter and parallel flow configuration was tested. The experimental
values of heat transfer coefficient have been obtained by the Wilson plot
method.
It was observed that the overall heat transfer coefficient increases with
increase in the inner coiled tube Dean number for a constant flow rate in
the annulus region. Similar trends in the variation of overall heat transfer
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 157
coefficient were observed for different flow rates in the annulus region for
a constant flow rate in the inner coiled tube. It was shown that obtained
average Nusselt numbers for the shell side have increased with surface mod-
ifications.
The literature predictions for hydrodynamics and fully developed heat
transfer were in good agreement with experimental results. The agreement
with the numerical and experimental predictions of Nusselt number values
was well within 30%.
As was expected based on presented above facts the heat exchanger
with surface modification on average has larger effectiveness than reference
construction.
References
[1] Muszynski T. Kozieł S.M.: Parametric study of fluid flow and heat transfer over
louvered fins of air heat pump evaporator. Arch. Thermodyn. 37(2016), 3, 41–58,
DOI:10.1515/aoter-2016-0019.
[2] Muszynski T., Andrzejczyk R.: Heat transfer characteristics of hybrid mi-
crojet – Microchannel cooling module. Appl. Therm. Eng. 93(2016), 1360–1366,
DOI:10.1016/j.applthermaleng.2015.08.085.
[3] Muszynski T., Andrzejczyk R.: Applicability of arrays of microjet heat transfer
correlations to design compact heat exchangers. Appl. Therm. Eng. 100(2016), 105–
113, DOI:10.1016/j.applthermaleng.2016.01.120.
[4] Rozzi S., Massini R., Paciello G., Pagliarini G., Rainieri S., Trifiro A.:
Heat treatment of fluid foods in a shell and tube heat exchanger: Comparison be-
tween smooth and helically corrugated wall tubes. J. Food Eng. 79(2007) 249–254,
DOI:10.1016/j.jfoodeng.2006.01.050.
[5] Jayakumar J.S., Mahajani S.M., Mandal J.C., Vijayan P.K., Bhoi R.: Ex-
perimental and CFD estimation of heat transfer in helically coiled heat exchangers.
Chem. Eng. Res. Des. 86(2008), 221–232, DOI:10.1016/j.cherd.2007.10.021.
[6] Berger S.A., Talbot L., Yao L.S.: Flow in curved pipes. Annu. Rev. Fluid Mech.
15(1983), 461–512.
[7] Kakaç S., Shah R.K., Aung W.: Handbook of single-phase convective heat trans-
fer. Wiley New York et al., 1987.
[8] Naphon P., Wongwises S.: A review of flow and heat transfer characteristics
in curved tubes. Renew. Sustain. Energy Rev. 10 (2006), 463–490, DOI:10.1016/
j.rser.2004.09.014.
[9] Lin C.X., Zhang P., Ebadian M.A.: Laminar forced convection in the entrance
region of helical pipes. Int. J. Heat Mass Transf. 40(1997), 3293–3304.
Unauthenticated
Download Date | 5/8/17 6:36 PM
158 R. Andrzejczyk and T. Muszyński
[10] Kumar V., Faizee B., Mridha M., Nigam K.D.P.: Numerical studies of
a tube-in- tube helically coiled heat exchanger. Chem. Eng. Process. Process Intensif.
47(2008), 2287–2295.
[11] Conte I., Peng X.F.: Numerical investigations of laminar flow in coiled pipes.
Appl. Therm. Eng. 28(2008), 423–432.
[12] Patankar S.V., Pratap V.S., Spalding D.B.: Prediction of laminar flow and
heat transfer in helically coiled pipes. J. Fluid Mech. 62(1974), 539–551.
[13] Jamshidi N., Farhadi M., Ganji D.D., Sedighi K.: Experimental analysis of
heat transfer enhancement in shell and helical tube heat exchangers. Appl. Therm.
Eng. 51(2013), 644–652, DOI:10.1016/j.applthermaleng.2012.10.008.
[14] Xin R.C., Awwad A., Dong Z.F., Ebadian M.A.: An experimental study of
single-phase and two-phase flow pressure drop in annular helicoidal pipes. Int. J.
Heat Fluid Flow. 18(1997), 482–488.
[15] Petrakis M.A., Karahalios G.T.: Exponentially decaying flow in a gently curved
annular pipe. Int. J. Non. Linear. Mech. 32(1997), 823–835.
[16] Petrakis M.A., Karahalios G.T.: Fluid flow behaviour in a curved annular
conduit. Int. J. Non. Linear. Mech. 34(1999), 13–25.
[17] Di Liberto M., Ciofalo M.: A study of turbulent heat transfer in curved pipes by
numerical simulation. Int. J. Heat Mass Transf. 59(2013), 112–125.
[18] Moawed M.: Experimental study of forced convection from helical coiled tubes with
different parameters. Energy Convers. Manag. 52(2011), 1150–1156.
[19] Designing_Helical_Coil_Heat Exgr_1982.pdf.
[20] Ankanna B.C., Reddy B.S.: Performance analysis of fabricated helical coil heat
exchanger. Int. J. Eng. Res. 3(2014), Iss. 1, 33–39.
[21] Kast W., Gaddis E.S., Wirth K.-E., Stichlmair J.: L1 Pressure Drop in
Single Phase Flow. In: VDI Heat Atlas, Springer, 2010, 1053–1116.
[22] Brauer H.: Strömungswiderstand und Wärmeübergang bei quer angeströmten
Wärmeaustauschern mit kreuzgitterförmig angeordneten glatten und berippten
Rohren. Chemie Ing. Tech. 36 (1964) 247–260, DOI:10.1002/cite.330360314 (in Ger-
man).
[23] Bell K.J.: Delaware Method for Shell-side Design. Taylor & Francis, New York
1988.
[24] Achenbach E.: Investigations on the flow through a staggered tube bundle at
Reynolds numbers up to Re = 107. Wärme-Und Stoffübertragung. 2(1969), 47–52.
[25] Lazova M., Huisseune H., Kaya A., Lecompte S., Kosmadakis G., De Paepe
M.: Performance evaluation of a helical coil heat exchanger working under super-
critical conditions in a solar organic Rankine cycle installation. Energies. 9(2016),
432, DOI:10.3390/en9060432.
[26] Jo D., Al-Yahia O.S., Altamimi R.M., Park J., Chae H.: Experimen-
tal investigation of convective heat transfer in a narrow rectangular channel
for upward and downward flows. Nucl. Eng. Technol. 46(2014), 2, 195–206,
DOI:10.5516/NET.02.2013.057.
Unauthenticated
Download Date | 5/8/17 6:36 PM
Performance analyses of helical coil heat exchangers. . . 159
[27] Hewitt G.F., Shires G.L., Bott T.R.: Process Heat Transfer. CRC press Boca
Raton, FL, 1994.
[28] Muszynski T.: Design and experimental investigations of a cylindrical micro-
jet heat exchanger for waste heat recovery systems. Appl. Therm. Eng. (2017),
DOI:10.1016/j.applthermaleng.2017.01.021.
[29] Laskowski R.: The concept of a new approximate relation for exchanger heat trans-
fer effectiveness for a cross-flow heat exchanger with unmixed fluids. J. Power Tech-
nol. 91(2011), 93–101.