Power Station Operations Millmerran Power Station Feed Water Dissolved Oxygen Control
Power Station Operations Millmerran Power Station Feed Water Dissolved Oxygen Control
Power Station Operations Millmerran Power Station Feed Water Dissolved Oxygen Control
A dissertation submitted by
Mmitsi Lefhoko
Submitted: 1/11/07
ABSTRACT
This project investigated the operation of a coal fired power station. The project
developed and analysed some operational control system engineering problems faced by
Millmerran power station. The main area covered in this project is on feed water
dissolved oxygen control. This involved feeding of oxygen gas at required amounts into
the boiler water to protect boiler tubes from corrosion effects. Millmerran power plant
uses a supercritical once through boiler which operates at extremely high temperatures of
ο
about 540 c and pressure of 24 Mega Pascal which can accelerate corrosion of the boiler
tubes.
In this dissertation, simulation models for the behavior of the advanced PID controller
and a servo DC motor under various time delays were carried out using simulink and
matlab software. The simulation models showed that by varying the process dead times,
the process variable was becoming stable. This was only experienced during small time
delays of less than 6 minutes. To obtain a quick and more stable response of the OT
process control, the dead time can be reduced by simply moving the injection point closer
to the oxygen sensor. This will help in maintaining the protective oxide layer hence
reducing chances of oxide exfoliation which can lead to boiler tube failures and power
plant shut down. A proper OT control will help protect the boiler hence saving millions
of dollars for the power plant.
ii
University of Southern Queensland
Limitations of Use
The council of the University of Southern Queensland, its Faculty of Engineering and
Surveying, and the staff of the University of Southern Queensland, do not accept any
responsibility for the truth, accuracy or completeness of material contained within or
associated with this dissertation.
Persons using all or any part of this material do so at their own risk, and not at the risk of
the council of the University of Southern Queensland, its Faculty of Engineering and
Surveying or the staff of the University of Southern Queensland.
This dissertation reports an educational exercise and has no purpose or validity beyond
this exercise. The sole purpose of the course pair entitled ''Research Project'' is to
contribute to the overall student's chosen degree program. This document, the associated
hardware, software, drawings and other materials set out in the associated appendices
should not be used for any other purpose: if they are so used, it is entirely at the risk of
the user.
iii
Certification
I certify that the ideas, designs and experimental work, results, analyses and conclusions
set out in this dissertation are entirely my own effort, except where otherwise indicated
and acknowledged.
I further certify that the work is original and has not been previously submitted for
assessment in any other course or institution, except where specifically stated.
Mmitsi Lefhoko
__________________________
Signature
__________________________
Date
iv
ACKNOWLEDGEMENT
I would also like to acknowledge the help of the control systems specialist Engineer of
Millmerran power plant Mr Michael Smith and the power plant chemistry engineer Mr
Shane Burge. I would like to thank the power plant management for arranging time for
me to visit the power station and meet with plant operators to obtain data for my research
project.
v
Table of contents
ABSTRACT ............................................................................................................. II
CERTIFICATION ........................................................................................................ IV
ACKNOWLEDGEMENT ....................................................................................... V
TABLE OF CONTENTS ................................................................................................. VI
LIST OF FIGURES........................................................................................................ IX
LIST OF TABLES .......................................................................................................... XI
1. INTRODUCTION ................................................................................................. 1
1.1. Project Methodology .......................................................................2
1.2. Project Program ................................................................................2
1.3. Project Objectives ............................................................................3
1.4. Assessment of consequential effects .............................................3
1.5. Risk Assessment .................................................................................4
vi
2.2.4. Demineralization by ion-exchange ..............................................16
2.2.5. Degasification Process ...................................................................17
2.3. Corrosion in boiler tubes.................................................................19
2.3.1. Uniform Corrosion ...........................................................................20
2.3.2. Pitting corrosion...............................................................................21
2.3.3. Scale Formation ..............................................................................22
2.3.4. Erosion-Corrosion ............................................................................23
2.3.5. Typical Locations of water side corrosion of a boiler..................24
2.4. Feed water measurement techniques.........................................25
2.4.1. Manual measurement techniques ...............................................25
2.4.2. On- line measurement techniques ...............................................27
vii
4.2.1 Steam cycle for supercritical boilers.............................................45
4.2.2 Oxygenated treatment control background information .........46
4.2.3 Oxygen & Ammonium Hydroxide (AVT) Feed ..........................47
4.2.4 Oxygen Feed System arrangement..............................................48
4.2.5 Historian data of oxygenated treatment process.......................49
4.3 OXYGENATED TREATMENT CONTROL SYSTEM PROCESS MODELING ........................ 50
4.3.1 Servo valve modeling.....................................................................53
4.3.2 Advanced PID Controller Tuning...................................................57
5. INTRODUCTION ............................................................................................... 62
5.1. SYSTEM ANALYSIS ........................................................................................ 63
5.2. CHAPTER SUMMARY .................................................................................... 65
6. INTRODUCTION ............................................................................................... 67
6.1. DISSOLVED OXYGEN MEASURING INSTRUMENT ............................................... 67
6.2. PH MEASURING INSTRUMENT ........................................................................ 68
REFERENCES .......................................................................................................... 70
APPENDIX A.......................................................................................................... 71
APPENDIX B........................................................................................................... 73
viii
List of Figures
ix
Figure 4-4 Millmerran power plant oxygen injection controller structure ....................... 48
Figure 4-5 Millmerran dissolved oxygen control response (5 days sampling)................. 50
Figure 4-6 Advanced PID controller................................................................................. 51
Figure 4-7 Dead-time due to fluid transport delay............................................................ 52
Figure 4-8 Narrow fluid passage....................................................................................... 52
Figure 4-9 Simplified structure of oxygenated treatment process control........................ 53
Figure 4-10 Oxygenated treatment control valve panel.................................................... 54
Figure 4-11 Servo valve.................................................................................................... 55
Figure 4-12 Servomotor and controller inputs and outputs .............................................. 55
Figure 4-13 Servo valve transfer function ........................................................................ 57
Figure 4-14 S shaped open loop response of a system ..................................................... 58
Figure 4-15 Ziegler Nichols first trial............................................................................... 60
Figure 5-1 A system model of a servo valve and advanced PID controller ....................... 0
Figure 5-2: Unstable Response ......................................................................................... 63
Figure 5-3: Unstable Response ......................................................................................... 64
Figure 5-4: Stable System................................................................................................. 64
Figure 5-5: A stable system with reduced dead time ........................................................ 65
Figure 6-1Dissolved oxygen sensor.................................................................................. 68
Figure 6-2High purity pH sensor (model 320Hp)............................................................. 68
x
List of tables
xi
Chapter 1 Background
1. Introduction
This project defines the Millmerran power station operations. The main focus is on feed
water dissolved oxygen control system operations of the power plant. This power plant is
located in southern Queensland. The project will be looking at the dissolved oxygen
control engineering problems of Millmerran power station and possible solutions and
recommendations to these problems. Millmerran power station uses a sophisticated
supercritical boiler technology which produces 10% fewer greenhouse gas emissions than
the conventional coal-fired plants. The power station also uses air-cooled condenser
technology. This system condense the steam from the turbine exhaust resulting in
reduced water usage of about 90% compared to the conventional plants. The power plant
uses Sewage water from Toowoomba which is treated by the latest water treatment
technology to make it suitable for power generation.
Millmerran power station is an advanced modern power station which has operations that
involves real time monitoring and running of the power plant processes. These modern
control systems play an important role in the plant performance. Millmerran power
station control systems provide the necessary tools to enable the operators to monitor the
plant’s operation which results in a continuous and efficient production of electricity. The
power station uses super-heated steam which can result in diverse power plant disorders
such as corrosion, boiler tube failures, and rise in temperatures, sediments accumulation
and fatigue.
In this project, Millmerran power station oxygenated treatment control problems for
dissolved oxygen is investigated. The oxygenated treatment (OT) control is good at
1
steady load but would be great if it could control on load changes. The oxygen dispenser
consists of the advanced PID controller (function code FC156) which becomes unstable
when the power plant experiences load changes. An open and closed loop response tests
are carried out by DCS engineers to determine the dead-time and process lags of the
system.
This section of the project includes the requirements for the execution of a major
technical task. The project methodology comprises of the project program, project
objectives, assessment of consequential effects, and risk assessment.
This part of the research project gives a wider understanding of the control systems
theory application and its importance in feed water chemistry control and monitoring. It
provides an appreciation of power plant control systems strategies and future
modifications. The following aspects need to be achieved in this project.
2
1.3. Project Objectives
The objective of the project is to investigate on the functions of the oxygenated treatment
control, and the problems associated with its operation. The control system of the process
involves the PID controller performance. Various system tuning methods are considered
like the Ziegler/ Nichols and the internal model control (IMC) method to work out the
robustness of the controller for oxygen injection process. The change in load at
Millmerran power plant causes the oxygen injection process to become unstable due to
some dead-time and process lags. Processes with large dead times present some
challenges to any controller. The controller must wait until the dead time has passed
before it gets any feedback from the process. This research is focusing mainly on how to
bring about a better control system which can withstand load changes and remain stable.
The project work involves a consideration of the outcomes. A sustainable attempt has to
be put in place to provide the best outcomes for the human and natural environment for
now and the future. This project provides a control strategy on how to utilize recycled
waste water for power production. A good corrosion control of the boiler tubes can
minimize costs of replacing a boiler and power plant shutdown. The project plays an
important role in reducing air pollution by the use of super-heated steam which is
produced from less coal hence less emissions.
The oxygenated treatment strategy prevents scaling in the boiler tubes which reduces heat
transfer efficiency in the boiler tubes. As a result of this oxygen injection program, less
coal is utilized hence emissions are also cut down. The reason for this research project
work is to provide possible utilization of waste water in power stations leading to
availability of clean water for human consumption. The power plant operates at high
temperatures, voltages and pressures so human intervention with the power plant is
reduced by the use of plant automation. This reduces the risk to power plant operators.
3
1.5. Risk Assessment
This aspect is very important in every engineering research projects because it addresses
the hazards and dangers involved during the work. Power station has a higher level of
hazard due to high voltages, high temperatures and excessive noise from machines. Risk
management has to be practiced. Risk management is a logical and systematic approach
to the uncertainty of hazards identified in the workplace.
In this research project, the control of dissolved oxygen in the feed water is very
important and if the system fails to meet the required specifications, a major damage can
result in power plant such as explosions and shutdown.
Risk assessment in a power station can be extended to the use of emergency switches and
alarms. In a power station, if there is part of the plant that is not working a warning signal
can be seen on the screen. The engineers will have to attend to the faulty section of the
plant by identifying the hazard, assessing the risk, controlling the risk and reviewing and
monitoring. According to this research, care should be taken when in the power plant
premises. Some electronic devices like mobile phones need to be switched off especially
at the generator section since electricity production involves magnetic fluxes that might
be extending to some areas in the power plant. Exposure of these devices may cause
electric shocks due to interference of the signals. No smoking in the power plant
4
environment because there are some flammable gases such as oxygen that can result in
fire. Use of pathways is important to reduce contact of body parts with hot surfaces and
high voltage cables.
5
Chapter 2 Coal Fired Power Station
6
Figure 2-2: Coal Bunkers
7
2.1.1. Coal Handling System
Millmerran power station uses coal from the adjacent open cut coal mine. Raw coal is
taken to the transfer building (Figure 2-3) through unloading conveyer belt. In the
transfer building some of the coal goes to the crusher while some is stockpiled. In the
crusher, raw coal is reduced in size. From the crusher it is transported to the power plant
through conveyers where it is pilled up in the storage units (silos or bunkers Figure 2-2)
to become ready for use in the electricity production. Coal bunkers can hold 600 tonnes
of coal each and when full can run coal for 10 to 12 hours before emptying with coal
feeder speeds at 50 to 60 tonne per hour. Before coal enters the boiler unit, it is crushed
further in the pulverizer to about 5cm in size. A mixture of crushed coal and air is blown
into the furnace with the help of forced draft fans (FD fans), this mixture of air and coal
is burnt to heat up the water in the boiler tubes.
Burning coal-air mixture heats the water in the boiler tubes to a temperature of about 540
degrees Celsius. The water is pre-compressed to 24 mega Pascal or 240 atmospheres
from a series of heaters (low pressure and high pressure heaters) and about 350kg of
water is turned into steam in a second. Millmerran power plant uses a once-through boiler
which does not involve a stem drum. Super heated steam drives the turbines which are
connected to the generator by a shaft and electricity is produced.
Feed water is pre-heated in the low pressure (LP), intermediate pressure (IP) and high
pressure (HP) heaters before it reaches the super heater. These heaters are powered by
extraction steam from the turbine exhaust as can be seen in Figure 2-1[1]. So energy
conversion takes place from heated steam to the feed water that has low temperatures.
The steam is then condensed through a series of air cooled condensers.
8
2.1.4. Circulating Water System
9
The steam from the turbine exhaust is re-used by going through the air cooled condensers
(cooling towers) which turn it back into water and it is called condensate. This
condensate goes through the cycle and it is used in the electricity production process.
Make up water from the pre-treatment plant is used to top up water that is lost through
leakages in the circulating water system. Figure 2-4 shows the cooling towers at
Millmerran power plant. These cooling towers consist of 36 individual fans and
gearboxes. Cool air is blown by the fan (Figure 2-5) through the condenser fins hence
lowering the temperature of the steam pipes and resulting in condensation.
Burning coal produces sulfur dioxide gas, carbon dioxide gas and nitrogen oxides. These
combustion gases require additional treatment for removal of fly ash particulates, sulfur
dioxide, and nitrogen oxides by the plant pollution control systems before the gases are
released through the plant exhaust stack. The bag-house (Figure 2-6) extracts dust
particles from the boiler flue gases. The gases are drawn from the boiler by the induced
draft fans (ID fans) and forced out through the stack into the atmosphere.
10
2.2. Millmerran Power Station feed water Treatment Cycle
This section of the report is the main area of concern in this research project. Feed water
quality is very essential for supercritical boilers. At higher operating pressures and
temperatures of the modern steam power plants, the effects of dissolved and suspended
constituents in the feed water makes the boiler tubes more susceptible to damage. Boiler
tube corrosion problems are a major concern in power plants, so feed water chemistry
control has to be practiced precisely to reduce the corrosion impact on boiler tubes. In
this project, it is crucial to consider ways of managing the feed water quality. Millmerran
power plant feed water purification and treatment will be studied in more details.
Measuring
oxygen at
Economizer
-inlet
BOILER
HP
Deaerator Heater
8
IP IP
Heater Heater
Condensate
5 6
Polishers
Clarifier
Condensate
Collection
Tank Demineralised Filtered
Demin
Water Plant Water
Water
Tanks
Tanks
Filtered
Demin Water Clearwell
Condensate Water Forwarding
Pumps Pump
Pumps Pumps
11
2.2.1. Boiler water pre-treatment plant
Sewage water is recycled and used in the power production. This raw water contains
some dissolved substances which can cause corrosion to the power plant boiler tubes. It is
therefore necessary to treat the water before entering the feed water cycle. In once-
through boilers, high purity of the feed water needs to be maintained. Raw water is
separated from mud and other dense particles in the clarifier. Mud settles at the bottom of
the clarifier and clear water is pumped by the clear-well forwarding pump through a
filtering tank which further removes suspended particles from the water. From this point,
water goes to the demineraliser where ion exchange and reverse osmosis processes take
place.
12
Raw water has a lot of dissolved substances which have different ionic concentrations.
Osmosis is a process whereby a solution of different ionic concentration is separated by a
permeable membrane. The membrane only allows water molecules to cross from the
lower concentration to the higher concentration side (Figure 2-8A) until equilibrium is
achieved. Reverse osmosis in the other hand is a process where the solution is pressurized
from a higher concentration to a lower concentration. The semi permeable membrane is
prevented from fouling by carrying out the reverse osmosis process. Millmerran power
plant feed water pretreatment system has the reverse osmosis process as shown in Figure
2-10.
13
Figure 2-10 Millmerran power plant reverse osmosis water treatment unit
Figure 2-9 shows a simplified diagram of the reverse osmosis system configuration. Raw
water is pumped in to the RO modules by the RO feed pump from the cartridge filter
which uses filter elements mounted in a pressure vessel. This pump creates a pressure
which reverses the flow of water molecules from a lower concentration point. A
continuous reverse osmosis process results in an improved water quality that undergoes
other levels of purification.
The demineralization train converts raw water containing between 100 and 1500ppm
dissolved solids in to water that contains no more than 10 to 20 ppb dissolved solids.
These treatment processes includes filtering and reverse osmosis (RO), softening,
chlorine removal, degasification and ion exchange. Reverse osmosis usually requires
14
pretreatment which include removing of solid suspended contaminants to prevent fouling
the membrane surfaces [7]. The types of fouling that can be prevented or reduced by
pretreatment include the following:
• Membrane scaling,
• Metal oxide fouling,
• Plugging,
• Biological fouling.
If fouling occurs, the membrane must be cleaned. Various cleaning solutions that can be
used are mentioned in the following Error! Reference source not found.. If cleaning is
carried out properly most foulants will be removed [1].
Chemical
X = denote yes
- = denote not
15
2.2.4. Demineralization by ion-exchange
Demineralization is basically the removal of dissolved ionic impurities that are present in
the water. Demineralization can consist of the ion exchange, membrane desalination and
thermal desalination. Ion exchange is one of the most effective processes for the
production of high purity water that is required in supercritical boilers. The process
involves an exchange of ions with the resin. Cation resins have a fixed negatively (OH-)
charged sides and exchanges with a positively charged ion in the solution. In the other
hand we have an anion resin which has a fixed positively (H+) charged sites that will
react with any negatively charged ion in the water.
In the process of ion exchange, the hydrogen ion (H+) is displaced from the cation resin
and this hydrogen ion (H+), will react with the hydroxide ion that is displaced from the
anion resin. The whole idea of this process is to remove the dissolved ions from the water
and replace them by pure water. The reaction of the resins with dissolved water
impurities can be represented as follows [1]:
Cation resin: R − H + + C + ⇔ R −C + + H +
2 R − H + + C 2+ ⇔ R2−C 2+ + 2 H +
Anion resin: R + OH − + A− ⇔ R + A− + OH −
2+ 2+ +
C = cation such as Ca , Mg and Na ; and
−− −2
A = anions such as HCO3 , Cl , and SO4 .
16
The process of ion exchange is cyclic; therefore the resins can get exhausted or cannot
remove other impurities without releasing impurities into the water. In this situation, the
resin is enriched or regenerated with a solution of sulfuric acid which is a recommended
regenerant for cation resins. The same regeneration process has to be done to anion resin
this time with the sodium hydroxide solution. Similarly the reactions are shown below for
the regeneration of the resins.
In these chemical reactions, gases can be released such as oxygen and carbon dioxide.
Presence of these gases above certain amounts can result in other problems such as
corrosion downstream of the feed water cycle. Presence of ingress gases can lead to
inappropriate performance of the oxygenated treatment process. A treatment process
called degasification is involved to help in removing these gases from the water. Oxygen
can be removed by vacuum degasification while carbon dioxide can be removed by either
vacuum degasification or forced draft degasification. Figure 2-12 below shows a vacuum
degasification system layout.
17
Millmerran power plant uses vacuum degasification process to remove gases in the feed
water. In a vacuum degasifier, water is sprayed and the gases are removed by maintaining
a vacuum in the tower.
Figure 2-11 shows how the system works. A vacuum is maintained with the help of
degasifier vacuum pumps [1]. For the oxygenated treatment to work efficiently, all the
gases must be removed from the feed water. The vacuum degasifier prepares the make-up
water that will be used later in topping up the condensate waters.
18
Figure 2-12 two-stage vacuum degasifier
Corrosion is the deterioration of the boiler tube surfaces when they are exposed to
chemical reactions. Most metals form an oxide or hydroxide layer when exposed to
water. The oxide layer acts as a protective coating from further chemical attack. The
formed oxide layer may collapse and become carry over. As the oxide layer exfoliates,
more and more chemical reactions takes place which will result in more corrosion effects.
19
Figure 2-13 Schematic showing difference between pitting attack
and uniform corrosion
This is a common form of boiler tube corrosion where by the metal surface is turned into
an oxide. The formation of this oxide reduces the boiler tube thickness. A protective layer
of magnetite ( Fe3O4 ) reduces the corrosion rate with time to a low constant rate. A layer
can be a non-protective scale which will have significantly higher corrosion rates. In once
20
through boilers, oxygen can be injected in to the feed water to form a protective layer
which will also protect metal from getting exposed to corrosion.
Pitting is a localized form of corrosion where by the protective oxide film breaks down.
According to Figure 2-14, once the protective layer is destroyed, an active corrosion site
21
is created and corrosion speeds up. The oxide adjacent to the pit is a reducing site
(cathode) for the corrosion reaction, and it is not corroded away. This cathode oxide will
react with any impurity that has an opposite charge to give a neutral solution. At a point
where there is no oxide film, the metal is entirely exposed to impurities which will
actively corrode it forming a pit.
Scale formation on the waterside of boiler heating surfaces is caused by the contact of
certain impurities in the boiler water with hot surfaces [2]. Most common impurities are
0.5 mm 2%
1.0 mm 4%
2.0 mm 6%
4.0 mm 10%
8.0 mm 20%
16.0 mm 40%
30.0 mm 80%
22
Scale is an insulator therefore heat transfer efficiency between the fireside and the
waterside of the boiler tube is decreased. There will be an increase in coal use hence
leading to energy losses and overheating of the boiler tubes. Table 2-2 shows the effect of
scale thickness with an increase in coal usage. These values for Table 2-2 are mainly for
drum boilers. In a once through boiler, the boiler tubes have a small inner diameter which
cannot accommodate scale to this thickness.
2.3.4. Erosion-Corrosion
Erosion corrosion occurs when protective scale is removed by flowing water. Removal of
this protective scale increases the corrosion of the boiler tube surface. There are various
ways in which the flow of water can bring about corrosion of the protective scale. These
can result from the velocity of flow and the angle of impingement. Erosion corrosion can
also result from cavitation which is the formation and implosion of gas bubbles in a fluid.
Erosion corrosion appears in form of grooves or pits, this usually occurs at restrictions
and curving points of the water tube where fluid velocity changes. This form of corrosion
is mostly common in once-through boilers which operate at high temperatures and
pressures.
23
2.3.5. Typical Locations of water side corrosion of a boiler.
Figure 2-16 shows vulnerable sections of the boiler and economizer for pitting corrosion,
stress corrosion and erosion corrosion. These corrosions are mostly common at high
pressure and temperature sections of the boiler. A good water treatment process will
prevent these from occurring.
24
2.4. Feed water measurement techniques
This section of the report outlines various ways of sampling the boiler water for both
formed deposits and corrosion products. These are manual and on-line measurements
which are used to control water treatment. These techniques help in determining
contaminants, investigating failure mechanisms and assist in chemical cleaning.
Manual sampling involves collection of the sample and analysis which should occur in a
short time frame to minimize absorption of atmospheric gases [5]. The American Society
for Testing Materials (ASTM) in New York provided the detailed methods for sampling
of the boiler water. Some of the useful techniques are atomic absorption and ion
chromatography. Atomic absorption involves measurements of elemental concentration
in sample solution. The solution is forced into a flame where the elements are atomized
therefore these atomized elements become capable of absorbing light at a specific
wavelength. Passing a monochromatic light through the sample, the ability of the
elements to absorb this light is measured and compared with absorbencies of known
standards.
Ion chromatography is another useful manual sampling method that involves measuring
of the amount of ions contained in the sample solution. The method involves the
following steps [5]:
25
In ion chromatography, several ions are determined in a single analysis. This process
requires low volume samples of about 20ml and this can occur every 30 minutes. This
technique can be used mainly for determining the anions and cations that are present in
the feed water cycle. Table 2-3 below shows guidelines and techniques for measurements
in power plant systems.
26
Guidelines for Measurements on Manual Sampling
Notes:
1. ASME PTC refers to Performance Test Codes of the American Society of Mechanical
Engineers, New York, New York.
2. ASTM refers to testing procedures of the American Society for Testing and Materials,
Philadelphia, Pennsylvania.
On line measurement is a monitored process of sampling the boiler feed water. This is a
continuous process and provides adequate information on the water quality. Millmerran
power plant uses this technique in monitoring the pH and dissolved oxygen in the boiler
water. On-line monitoring utilizes a computer which is interfaced with dissolved oxygen
and pH detecting devices.
27
Chapter 3 Coal-Fired Power Station Control Systems
In modern power plants, the control actions required to operate the processes are
automated. The reason was to reduce human error in plant operation and thus providing
safety for plant personnel. Secondly, automation reduces the number of operations
required to run the plant, which reduces labor costs. The control functions used in
operating a power plant can be classified in many ways. For the purpose of this report,
the functions of the plant control system are classified by the type of control action used.
There is on-off control known as digital control and modulating control which is
sometimes called closed loop control [1]
This control action produces a control that varies in discrete states. On-off control
involves two states which are either start or stop command and no intermediate states
exist between the running and stopping states. The on-off control operation is applicable
to motor-driven rotating equipment such as pumps, fans, compressors and conveyers.
The On-Off control has an important role in the power plant operations. This control
action involves protective interlocking, sequential control logic, and unit protection logic.
28
Protective interlocking is used for the operation of individual pieces of power-operated
equipment. A motor driven boiler feed pump is a typical example. This feed pump has oil
supply for lubricating the bearings, before the pump start operating, lubricating oil must
be available at the pump bearing, sufficient water must be in the deaerator storage tank,
water path in the suction line must be open and the pump motor must be started against a
closed discharge valve. A control signal from the tank level limit, oil level limit, suction
valve limit, and discharge valve limit is checked and if a correct position of all these
parameters is attained, the pump motor start when the operator issues the starting
command.
The unit protection logic is simply the protective interlocks associated with the operation
of the boiler, the turbines, and the generator. This control function actually ensures
maximum safety to plant personnel and to guard against serious damage to the power
plant equipment. If an abnormal operating condition arises, the boiler, turbines, and
generator are tripped individually. The boiler, turbines and generator are closely coupled;
the boiler supplies steam to the turbine and the turbines drives the generator. If an
unusual condition happens to any of these equipments, the whole system will be disabled.
This will provide protection to the equipment and safety to the plant operators.
29
3.3. Dissolved oxygen closed loop control functions
The figure shows the dissolved oxygen control loop. The dissolved oxygen is controlled
at a desired value (set point) by automatically and continuously modulating the control
valve supplying the oxygen to the deaerator outlet [1]. The basic elements of the loop are
as follows:
The injected oxygen flow to the feed water deaerator outlet is the manipulated variable. If
the dissolved oxygen drops below the oxygen set point, the controller applies a control
30
action to the oxygen deviation (error) and produces a control signal to increase the
opening of the control valve. This increases the oxygen flow into the feed water thus
bringing the dissolved oxygen level back to the set point value. The control loop is said to
be closed in that the controlled variable is measured and the measured value is used to
verify the result of the control action.
The PID (proportional, integral and derivative) parameters are related to the relationship
between the set point error and the controller output to the final element. In proportional
control, the magnitude of the controller output is proportional to the magnitude of the set
point error. A relationship between the input, error and output exists:
Where
P = output
31
The proportional gain is a measure of the sensitivity of the controller and it is an
adjustable parameter of the controller. For example, in the control loop shown in Figure
3-2, given dissolved oxygen level deviation from the set point (error) produces a control
signal that drives the control valve to a corresponding position depending on the
proportional gain. This relationship keeps the dissolved oxygen level at the desired set
point as long as the feed water flow, pressure and temperature supply remain constant. If
any of these conditions changes, the controller must make necessary corrections to
maintain the exit oxygen flow at the set point. These changes are called load changes.
When a load change is large, the controller will not be able to produce an output to bring
the oxygen injection back precisely to the set point
The PID controller has another parameter called the integral control which is also known
as the reset control. With the integral control, the output of the integral controller changes
whenever there is a set point error. The integral action produces an output that changes at
a rate proportional to the magnitude of the error.
Where
An integral controller according to Equation 3-4 produces an output that keeps changing
for as long as there is an error in the process. The output stops changing once the error is
reduced to zero. From Figure 3-2, when a dissolved oxygen level error exists in the feed
32
water, the integral action of the controller keeps moving the control valve as long as the
exit oxygen is not at the set point. The valve will keep moving until the oxygen is
returned to the set point.
Lastly there is a derivative control parameter which is known as the rate control. The
controller produces an output whenever there is a set point error and the magnitude of the
output is proportional to the rate of change of the error.
Where
With the derivative control, the faster the error changes, the greater the controller output.
In a feedback control configuration, the controller produces a control action only when it
detects an error in the controlled variable. It applies corrective action only after the error
has occurred. So to improve system response to process changes, a technique known as
feed forward control is sometimes added to the feedback controller. The feed forward
control represents a load change in the process, and a signal is passed forward as a
corrective action. The purpose of this signal is to provide a control action before a set
point deviation occurs and thus to minimize any disturbance in the controlled variable
caused by a change. So the PID transfer function becomes;
U = KpE + Ki ∫ Edt + Kd * dE / dt
33
Ki = Integral gain
Kd = derivative gain
E = error signal
t = process time
Load
Demand
Unit load
development
Coordinated
control
The load demand control of the boiler control system uses the load demand signal from
the load dispatcher and converts the signal into demand signal for fuel flow, air flow and
feed water flow as well as the oxygen injection rate demand. The coordinated control
scheme was designed to accommodate the once-through boilers [2]. The basic principle
of the coordinated control scheme is that load demand is provided as a feed forward
signal to both the boiler, and turbine control systems in parallel. Coordinated control
ensures a simultaneous change of processes when a load demand signal is available. A
simple coordinated control scheme is shown in Figure 3-3.
34
According to Figure 3-3, the turbine and the boiler receive the load demand signal in
parallel, but the turbine valve is used to control the pressure, and the firing rate is used to
control megawatts error. This kind of control is an integrated control therefore there is no
simultaneous action to a load signal within a short time frame. Having this kind of
systems will result in large dead-time and system delays.
Unit Load
Input Output
Boiler
Fuel Demand
Firing Rate Demand
Air Demand
The boiler control system is a process in which the energy and mass balances of the
boiler are managed. Figure 3-4 shows a coordinated control system of various controls
that build a single boiler control [4]. To obtain a desired output condition, the feed water
chemistry control, fuel demand, air demand, firing rate demand and steam temperature
control must be regulated depending on the unit load changes. When the load increases,
35
firing rate will also increase creating demands for the mass of fuel and combustion air.
Feed water control is a process control that involves water flow rate and storage tank
level controls as well as feed water chemistry control. Feed water control involves the
boiler water chemistry control to prevent boiler tube scale formation. Boiler feed water
can cause damages to the boiler tubes if not treated precisely. The common boiler tube
problems caused by poorly treated feed water were discussed in the previous chapter.
Oxygen gas is supplied to the boiler water at the deaerator outlet. The gas gets dissolved
in the water and the chemical reactions at high temperatures and pressures provide a
formation of a thin film that prevents formation of scale or adherence of any suspended
particles in the feed water. Oxygen supply is monitored through a process control that
involves a PID controller. A closed loop system is formed with a loop feedback signal
measured from the condensate flow transmitter. The condensate flow transmitter is
located after a series of heaters and thus provides a longer time delay for a sensor to pick
up the dissolved oxygen level signal.
Transportation
lag
Figure 3-5 Typical system for oxygen injection point and detection point
36
Figure 3-5 shows a typical structure of the connections between a valve and a sensor. In
every controller based process, the location of a sensor from the injection point matters a
lot. Locating a sensor close to the injection point will help in reducing the dead-time.
Dead-time can be caused by the following:
Computers are a backbone of every industrial process. Large and sophisticated systems of
modern coal fired power stations which have a wide range of activities that need to be
timely controlled, requires a computer to do the monitoring of the entire plant. This
section of the project includes various ways of managing the control systems applications
of a power plant.
37
In a communications network, components are connected to the network by nodes, and
these components are often referred to as a drop. The pattern in which the drops are
connected to one another within the network is referred to as the network topology. There
are three basic types of network topology, these are: star topology, bus topology and ring
topology (Figure 3-6). In a star network topology, components in the system are
connected to a central computer by a point to point line. In this network topology
information between various components is routed through the central computer. The
network is very much dependent on the integrity of the central computer to keep the
communications lines open.
The bus network topology involves a single cable for transporting information between
devices that are connected to the highway (Figure 3-6). Communication of devices in a
bus topology requires a method for all components on the bus to share the use of
transmission line. Millmerran power plant uses this network strategy to link various
components of the power plant to a transmission line.
The ring network topology links system components in a continuous loop. Information is
passed around the continuous loop until it reaches its destination. Information
transmission on a ring network topology is usually unidirectional. A bidirectional route
can be established by involving sophisticated software and special control devices. Figure
3-7 shows typical connections for a bus topology and ring topology. The diagram consists
of two main transmission highways which links all the computers in the power plant. The
oxygenated treatment control systems can be controlled through sharing connections with
other systems in the network such as the data link server, historian logger where
information for this project was obtained.
38
Figure 3-6 Network topology
39
Figure 3-7 Network Structure
A power station uses computer languages that are used to control the power plant pumps,
motors and other controllers needed in the power plant. The programmable logic
controller (PLC) was a digital control computer developed in 1969 for the automobile
industry replacing the relay control logic. The PLC has special characteristics that made it
different from other control computers:
40
• The PLC was used to control the on-off control functions like protective
interlocking, sequential control logic, and unit protection logic.
• The software was made easy to use by the plant operators.
Programmable logic controllers can be divided into two categories: PLC's used in balance
of plant equipment and the stand alone processes. Stand alone processes refers to the
packaged designs that are supplied by the manufacturer as a complete system with all the
control equipments included [1]. The oxygenated treatment control package is a typical
example of the stand alone process that is compatible with the PLC; other applications
include coal handling systems, steam temperature handling systems and burner control
systems.
The PLC can also install equipments that are used for the balance of plant such as boiler
draft equipments like induced draft fans, forced draft fans and feed water equipment such
as condensate pumps, boiler feed pumps and shutoff valves. PLC application with respect
to balance of plant systems is mainly in the area of on-off or start/stop operations.
The distributed control systems (DCS), was first known to be a control system for the
boiler control and data acquisition functions of the power plant. DCS has replaced the
centralized computer systems. The DCS programming format involves the use of
function blocks. This is like a subroutine consisting of a set of algorithms designed to
execute a specific control or data manipulating functions such as a PID control function
[1]. DCS applications in a power plant typically cover the following:
• Recording functions
• Boiler controls, like firing rate, feed water control loops, steam temperature
controls.
• Burner control and pulveriser control.
• Periodic reports and event logs.
41
• Historical data storage.
Figure 3-8 shows a distributed control system (DCS) room of Millmerran power plant.
The oxygenated treatment process is controlled and monitored by the distributed control
system plant operators through observing the computer graphics and warning indicators
in the control room. Distributed control system has the ability to generate logs and
reports. Any information about what happened in the past can be obtained and used for
investigations. To study the behavior of the oxygenated treatment process, some of the
information was obtained from the DCS.
42
Chapter 4 Boiler water chemistry control and evaluation
The steam-water flow of a coal fired power station has the following roles:
• It generates high purity superheated steam from cooled inlet feed water at a
specified pressure, temperature and flow rate.
• It protects metal components from getting excessive temperature which might
result in boiler tube failure.
43
There is a wide range of circulation systems that is used in coal fired power stations. The
commonly used systems are shown in the diagram above (Figure 4-1). These circulation
systems may be classified as either once-through or recirculation types. In the
recirculation system, water is partially converted in to steam at all load levels. The
remaining water is then recirculated back to the evaporator for further heating.
Millmerran power plant uses a once-through boiler circulation method with part-load
recirculation (Figure 4-1 e). In a pure once-through circulation, water in the boiler tubes
is continuously evaporated to dryness. Availability of a part-load recirculation overcomes
low-load and start-up limitations of pure once-through design.
Error! Reference source not found. above shows different results for dissolved oxygen
level in parts per billion for polisher outlet, deaerator outlet and the boiler feed water
economizer inlet. The measurement for pH level and silica level were also taken for the
44
power station unit #1 steam cycle. All these results were obtained through on-line
sampling. Any offset in the results can be viewed on a computer screen and proper
observation can be made by the plant operators. Offset can be due to ingress gases
entering the feed water cycle through leaks or during make-up. Figure 4-2 shows the
steam cycle, so the results of Error! Reference source not found. were taken from some
sections of the steam cycle mentioned in Error! Reference source not found..
HP IP
Heaters Heaters LP
Deaerator
BOILER 7 and 8 5 and 6 Heaters
1, 2 and
3
Booster
Boiler Feed Pump
Pump
Main
Steam
Start Up
Feed Pump
Hot Air Cooled
Reheat Condenser
Steam
Condensate
Polishers
ACC
HP Duct
Cold Turbine
Reheat IP Turbine LP Turbine
Steam
Condensate
Collection
Tank
ACC
Drain
Pot
Condensate
Pumps
ACC Drain
Pot Pumps
In a supercritical boiler, water is directly turned into steam. So any impurities from the
pre-treatment plant passes through the economizer will either:
45
Be carried forward in suspension in the steam and deposited at the valve opening
hence leading to valve failures due to sticking.
In a supercritical boiler the following parameters are recommended for the feed water:
There are two different boiler water treatment regimes in use at Milmerran power plant.
These are the traditional all-volatile treatment (AVT) and the modern oxygenated
treatment (Figure 4-3). The AVT regime involves the injection of ammonia hydroxide
into the condensate system to monitor the water pH within the range of 9.2 – 9.6. The
AVT regime of Millmerran power plant for ammonia dosing has not worked since the pH
has been upped to offset corrosion in the air cooled condensers (ACC). Other power
stations have switched to conductivity to control dosing. The AVT work together with
OT and it utilizes condensate de-aeration to maintain low dissolved oxygen levels,
typically < 10 parts per billion (ppb). The OT regime injects oxygen in a controlled
manner. The aim of this oxygen injection is to control the condensate dissolved oxygen
level to a range of 50 – 200 ppb. Millmeran plant condensate water pH level is controlled
within the range of 8.0 – 8.5. To prevent removal of gaseous oxygen by de-aeration all
feed heater vents and the de-aerator vent to condenser must remain closed during normal
operation. The AVT is used immediately after boiler start-up and prior to boiler
shutdown. This maintains low dissolved oxygen and pH levels in case of a prolonged
plant shutdown hence reducing the solubility of the formed oxide layer.
47
The oxygen injection varies with the power plant conditions. During a load change in the
power plant, the dissolved oxygen varies anywhere from 50 ppb to 300ppb. The oxygen
control logic is fairly slow and takes some time for changes to be picked up. A recent
information of the OT performance from Millmerran power plant showed that for an
output of 420MW which lasted 8 hours, oxygen started at 205ppb and dropped back to
180ppb by the end of the 8 hour session. Load dropped 380 MW and oxygen came back
to 160ppb. For load changes below 300 MW, oxygenated treatment reverts to AVT and
oxygen injection stops. At this stage a manual operation takes place to maintain the
normal condition of the formed oxide layer.
From condensate
DCS Flow transmitter
APID
CONTROLLER
3
To polisher outlet
To deaerator
outlet
5
1
48
Figure 4-4 above shows the dissolved oxygen injection structure that is used at
Millmerran power plant. The system consists of an advanced PID (proportional, integral
and derivative) controller (3) which has an error detector function. This function
measures the error between the primary variable and the set point. Numbers (1) and (2)
shows the control valves which are controlled by the PID controller to vary the amount of
oxygen injection in the deaerator outlet and the polisher outlet. When the controller is
turned on, the valves are opened at the oxygen sources (5). A controller receives a control
signal from the condensate flow transmitter through the control room and the DCS. At
the control room, the power plant operators can see the process control variability. The
system can be manually controlled and auto-controlled depending on the power plant
conditions. Manual control involves tuning of the controller parameters during start-up to
obtain a better response.
49
Figure 4-5 Millmerran dissolved oxygen control response (5 days sampling)
320.00
1AJFIC202ABMA.PV
300.00
1AJFV202A
280.00
260.00
240.00
220.00
200.00
180.00
160.00
140.00
120.00
100.00
80.00
60.00
40.00
20.00
0.00
12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM 12:00:00 AM
Data in Table 4-3 was obtained from the oxygenated treatment control process.
The signal for the valve (1AJFV202A) was produced from the controller output due to a
demand from the process variable and the set point. The set point for the dissolved
oxygen was set at 200ppb. The response for the process variable shows some variation
which were above and below the set point. This system behavior shows that the dissolved
oxygen is alternating above and below the set-point. This will result in more than the
required amount of dissolved oxygen injection in the feed water. The lower graph shows
the response of the control valve due to variations in the level of dissolved oxygen in the
boiler water.
The oxygen injection process of Millmerran power plant uses an advanced proportional,
integral and derivative controller (A-PID). This controller is different from the normal
PID controller because of the following:
50
o It has a direct use of the feed forward signal into a PID controller
o It has improved algorithms for derivative action calculation
o The controller has bumpless manual to auto transfer
o It has a quick saturation recovery option
Figure 4-6 shows the schematic diagram of the advanced PID controller used for oxygen
injection process at Millmerran power plant. This controller has proportional part,
integral part and derivative part. The controller monitors and controls the amount of
dissolved oxygen in the feedwater by sending electric signals to a servo valve which
either increases or decreases the amount of oxygen gas injection into the feed water.
The figure above shows the internal structure of the controller. A simplified control loop
for the oxygen injection consists of the controller part, the plant or controlled device
which is a servo valve and a block which represent the delay or transportation lag. The
delay or dead time is simply the duration of the fluid flow through a conduit. The next
Figure 4-7 illustrates the transportation delay of the oxygen injection process.
51
Dissolved
oxygen
sensor Servo valve
In this diagram, the arrow shows direction of fluid flow. The servo valve injects oxygen
gas in to the feed water stream. The amount of time it takes the solution to reach the
dissolved oxygen sensor is called dead time. Dead time can increase due to the size of
pipes which transport the solution. For a narrow pipe the fluid can take less time to travel
through the entire length hence reducing the delay in fluid transportation. In a power
plant, there are small and large fluid passage ways such as low pressure heaters, high
pressure heaters and the boiler which are all in different sizes. This results in a non
uniform flow of the feed water. If we consider a uniform pipe in Figure 4-8, there is a
uniform area and a small volume of liquid passing through the pipe. The liquid will take
less time to travel through the pipe than for a large volume liquid pipe.
52
Millmerran power plant’s advanced PID controller faces some challenges in trying to
control the oxygen gas injection process which has a large dead time of about 12 to 15
minutes. The controller is over working in trying to control the dissolved oxygen to a
required level. To model the behavior of the oxygenated treatment process, matlab and
simulink software were used. In the simulation, a servo valve was used as the model for
the oxygen injection system.
PID
+
R(s) + Integral + Y(s)
Σ Σ Valve Delay
- Derivative
+
Feedback
Figure 4-9 Simplified structure of oxygenated treatment process control
This section of the project is looking into introducing a plant model that will be used in
the demonstration of oxygenated treatment controller behavior. This is a controlled
device that has an integrator and a time constant and it is designed for position control
applications. The valve hosts a DC motor which is driven by an electric current from the
controller. The current from the controller is in the range 4-20 mA. The valve opens and
closes depending on the amount of current which the controller outputs. In this case the
53
valve will be fully open when a current of 20 mA is supplied and fully closed when a
current of 4 mA is supplied from the controller output. In between these current ranges,
the valve opening and closing can be controlled depending on the amount of oxygen
required. Figure 4-10 and Figure 4-11 below shows the connections between the oxygen
sources and the valves at Millmerran power plant.
An electro hydraulic servo valve transforms an electric signal into hydraulic power. This
involves mechanical motion by means of an electromagnetic torque motor which is used
to stroke the mechanical control element of the valve. The torque motor drives the
hydraulic amplifier which in turn strokes the power spool. Figure 4-9 shows the
connections of the valve to the advanced PID controller for the simulink simulation
modeling.
54
Figure 4-11 Servo valve
Mathematical model of the DC motor for the servo valve can be expressed by the time
constant (relating armature voltage and speed) followed by an integration (relating speed
and output shaft position). The dc motor is the heart of a dc servo system. In the dc servo
system, the input is usually considered to be the desired angle and the output is the actual
angle which produces torque and speed (Figure 4-12). The block diagram representation
of a typical dc servo system was modeled as follows:
55
Considering the d.c servo system with the input usually considered being the desired
angle and the output as the actual angle. The block diagram representation of a typical
servo system involves the input angle θ R which is compared with the feedback angle
θ F and the error angle θ E converted into a voltage vE by means of a rotary potentiometer
kp
with a gain .
θR −θF vE
kp
vE = k p (θ R − θ F )
The error voltage v E is amplified to produce the drive voltage vm for the motor.
vE vm
kA
vm = k A v E
k A = amplifier gain
The motor rotates and produce an output speed ω m depending on the voltage applied.
km
= motor gain
Tm
= motor time constant
56
The resulting block diagram shows the servo system transfer function used in the
modeling of the oxygen injection response. For simplicity, this transfer function was used
to model the response of an advanced PID controller for this project. The real system
consists of more complex blocks that are connected between the controller and the servo
valve or the injection valve. Using the system transfer function in the block below, the
effect of system delay can be modeled for different times ranging from small dead time to
large dead time.
The advanced PID controller has 5 tuning parameters which are as follows:
kp
= Proportional gain
ki
= Integral reset (reset per minute)
57
k = Gain multiplier
Modeling the response for the servo valve, the common method for tuning the PID
controller was proposed by Callender et al. (1936). Callender proposed a design for
widely used PID controller by specifying satisfactory values for the controller settings
based on the estimates of the plant parameters that an operating engineer could make
from experiments on the process itself [9]. The approach was developed by Ziegler and
Nichols (1942,1943), who recognized that the step responses of a large number of
process control systems exhibit a process reaction curve as shown in Figure 4-14 below.
The parameters for tuning the PID controller were obtained by using the Ziegler and
Nichols open loop method. The procedure involves the following steps:
58
Table 4-4 Parameters for tuning PID controller
Input
To Workspace
Output
1 1
s s+1 Output
Integrator Servo
input
Scope
Model 4.1
To obtain the tuning parameters for the advanced PID controller, an open loop step
response model for the servo valve transfer function was carried out. It is estimated that
by setting these parameters, a response with an overshoot of 25% and good settling time
should be obtained [9]. In ZN method, tuning is based on the period and the critical gains
which are determined by adjusting the proportional gain until the stability limit is
reached. The parameters L and T were approximated from the open loop response as
follows:
59
Open loo p response
10
input
8 output
Input vs output
6
0
0 2 4 6 8 10
Time (min)
The values of the parameters L and T from Figure 4-14 were estimated as follows:
L = 1.5
T = 9.8
By substituting the values for L and T in Table 4-4, the resulting table consists of Ziegler
Nichols first trial PID tuning parameters.
60
Tuning the advanced PID controller was mostly done by trial and error approach. By
tuning the parameters separately with the help of table 4-4, 4-5 and 4-6, the response was
able to follow the set point. This simulation mainly demonstrates the effect of dead time
on stability of a system. The controller can be automatically tuned during oxygen
injection operation. The controller tuning for this OT process is continuous due to
variations in load.
61
Chapter 5 New Control System Proposals
5. Introduction
The block diagram below shows the complete model for the advanced PID controller
which is used for the oxygen injection process at Millmerran power plant. The process set
point for the dissolved oxygen in the feed water was set to 200 ppb and 180 ppb. To show
the behavior of the controller, the model tests were carried out for different dead times.
This was done by changing the time value in the transport delay block.
Integral
Signal 1
Saturation
Signal Builder -K-
K*ki*dt/60
Error
1
z
Unit Delay2
Proportional 1 1 proj2
-K-
SP s s+1
Output
Gain Saturation1Integrator servo valve Transport
Delay
Derivative
-K- -K-
1
1
z
z
Unit Delay1
Unit Delay
Figure 5-1 A system model of a servo valve and advanced PID controller
62
5.1. System Analysis
300
200
100
0
0 100 200 300 400 500
Time(min utes)
The system response in Figure 5-2 above was obtained by inserting a dead time of 25
minutes in the delay block of . It can be seen that the process variable
developed some overshoot and the system losses stability. With reference to Figure 4-5,
the process response showed upsets and the dissolved oxygen response fluctuated above
and below the set point.
A further reduction in the time delay of 20 minutes led to an unstable system which takes
some time to settle (Figure 5-3). Oxygen injection process of Millmerran power plant is
dynamic and has a large dead time therefore the controller cannot find enough time to
drive the process variable towards the set point during sudden load changes. For a stable
load, the controller performance at Millmerran power plant developed a better response
in the process variable which has small overshoots.
63
APID controller Process with 20 minutes dead-time
350
controller output
300 Process variable
Dissolved oxygen (ppb)
250
200
150
100
50
0
0 100 200 300 400 500
Time(minutes)
150
100
50
0
0 100 200 300 400 500
Time(minutes)
Figure 5-4: Stable System
The dissolved oxygen response can become stable by reducing the dead time. Figure 5-4
illustrates a response which was generated for 10 minutes dead time. The response shows
a better set point tracking. It can be seen that for a reduction in the dead time, the
64
response becomes more and more stable. The best way to control a system with large
dead time is to reduce the dead time. Figure 5-5 shows a perfect response generated for a
small dead time of 5 minutes.
150
100
50 co ntroller output
Process variable
0
0 100 200 300 400 500
Time(min utes)
New control system proposals for the oxygenated treatment control process are as
follows:
Reducing the dead time of the OT process by moving the injection point closer to
the dissolved oxygen sensor.
Eliminate ingress gases during make up
Moving the injection point closer to the sensor location reduces the delay in the solution
transportation. A proper dissolved oxygen control prevents boiler tube failures which can
result in plant shut down and huge amount of capital losses. Therefore relocating the
injection point is a better option for controlling the OT process of Millmerran power
65
plant. Power plant shut down results in massive capital losses; it is therefore important to
put more emphases on preventing corrosion of the boiler tubes. Once through boiler
operates efficiently under highly treated feed water. For the boiler to operate for a long
time, it is important to maintain the required levels of dissolved oxygen and pH.
66
Chapter 6 Instrumentation for Boiler water Quality
6. Introduction
This chapter covers various instruments that are used for determining the boiler water
quality parameters. Instruments that are used in a power plant for boiler water quality
have to be properly selected, installed and maintained to improve the overall plant
performance. The improvement in performance can be in the treatment process such as
more efficient chemical and energy use, increased security, or more consistent water
quality. Instruments also provide more timely and accurate process information to power
plant operators and managers.
In a supercritical boiler, water quality assurance testing plays an important role in the life
of a power plant. The objectives of quality assurance testing are as follows [10]:
Dissolved oxygen reference values are best determined with a reference probe. This
reference probe is calibrated in air and against laboratory prepared solutions of known
dissolved oxygen concentration. The dissolved oxygen in the feed water is measured in
parts per billion (ppb). Figure 6-1 shows the dissolved oxygen sensor. This is a
luminescent dissolved oxygen (LDO) sensor which is the first luminescent sensor to
provide trace oxygen monitoring in pure water processes where ppb level monitoring is
needed.
67
Figure 6-1Dissolved oxygen sensor
Chemical monitoring in the feed water consists of measuring ammonia, pH, conductivity,
and cation conductivity for either AVT or OT. Ammonia can be measured directly or
indirectly from pH and conductivity. Ammonia reacts in water to produce hydroxide ion
(OH-) therefore indirect measuring method is often used. Both conductivity, which is a
measure of the ions in solution, and pH, which is an indirect measurement of OH- can be
combined to yield the ammonia concentration. Figure 6-1 below shows a measuring
instrument that can be used.
68
Chapter 7 Conclusion and Future Work
This project investigated the boiler water dissolved oxygen control system of the modern
supercritical boiler at Millmerran power plant. Boiler water quality plays an important
role in reducing corrosion of the boiler tubes and increasing the efficiency as well as life
of the power plant. Millmerran power plant has a modern oxygen injection process which
helped in maintaining optimum conditions for its supercritical once through boiler
performance. The operation of the oxygen dispenser experienced some stability problems
due to dead time. The controller can perform better if the oxygen injection point can be
moved from the polisher outlet to the high pressure heaters inlet. From the high pressure
heaters, extreme temperatures and pressures start to build up to the superheater, so the
boiler tubes need to be supplied with a required level of dissolved oxygen for protection
and efficiency.
The advanced PID controller can give a better performance with reduced dead time. Any
process with a large dead time present special challenges to a controller, the controller
has to wait until the dead time has passed for it to get feedback from the process. This
new system recommendation will benefit the power plant in managing a good dissolved
oxygen concentration. Enough oxygen gas will be supplied at a required time hence
maintaining the formed oxide film and reducing the chances of a power plant shut down
due to boiler tube failures.
Future work in this study may relate to involvement of other controllers like the smith
predictor and other model based controllers. These controllers are believed to work well
in dead time processes. From a control system point of view, moving injection point
would only give a better controller action. This may have other effects in the power plant
which need to be considered in future.
69
References
[1] Power Plant Engineering 1996, Plant Control System, Augustine H. Chen, New
York.
[2] Steam Boilers 1981, Water Tube Boilers, Harry M. Spring, Jr, Anthony Lawrence
Kohan, USA.
[3] Richard C. Dorf, Robert H. Bishop 2000, Modern Control Systems, New Jersey
07458
[4] Control of Boilers 1991, improving boiler efficiency, Duke low, Sam G. – 2nd Ed.
Kansas State University, USA.
[5] Steven C. Stultz and John B. Kitto, 1992, Babcock & Wilcox, Barberton, Ohio,
U.S.A.
[6] Sadik Kakac, Boilers, Evaporators, and Condensers 1991, University of Miami
Coral Gables, Florida. U.S.A.
[7] David H.F.Liu, Bela G. Liptak, Waste Water Treatment, Boca Raton London,
New York, Washington, D.C.
[8] http://www.me.umn.edu/courses/me4231/labs/Lab6.pdf
[9] Gene F. Franklin, David Powell, Abbas Emami-Naeini, 1986, Feedback Control
Of Dynamic Systems, Upper Saddle River, New Jersey 07458
[10] Skrentner, Robert G. 1988, Instrumentation handbook for water and wastewater
Treatment plants, United States of America.
70
Appendix A
1. Describe the Millmerran power station and operations with specific details of
Millmerran power plant control system.
2. Review and analyse the control system problems that are faced by the Millmerran
power station.
3. Conduct a literature review of similar problems in other coal fired power stations,
solutions to these problems and the theory of control associated with such
problems.
4. Develop solutions to solve the Millmerran power station specific problem
5. Define the cost-benefit of these solutions
71
6. Provide Millmerran with a report of the findings and recommendations.
7. Write dissertation of the project work.
8. If time permits, report on the implementation of any of the recommendations, if
accepted.
72
Appendix B
Matlab code
73