Relay Coordination Chapter3
Relay Coordination Chapter3
Protection system coordination is an important aspect of an electrical system design . The term or
phrase relay coordination therefore covers the concept of discrimination, selectivity and backup .
Further the coordination is not confined only to relays and equipment operating characteristics, but
also includes other protective device characteristics such as Fuse, MCB's, Circuit Breakers as
applicable.
The term ,, selective coordination ‘’ refers to the selection and setting of protective devices in
electrical power system ,as stipulates by National Electrical Code NEC ‘’ where an orderly
shutdown is required to minimize the hazard(s) to personnel and equipment ,a system of
coordination based on the following two conditions shall be permitted:
Coordination short-circuit protection
Overload indication based on monitoring systems or devices
The selected protection principle affects the operating speed of the protection ,which has a
significant impact on the harm cause by short-circuits. The faster the protection operates ,the
smaller the resulting hazards, damage and thermal stress will be .In transmission network ,any
increases of the operation speed of the protection will allow the loading of the lines to be increased
without increasing the risk of loosing the network stability .Thus ,a valid protection system must
be able to [ 9 ] :
understand what and where an event has occurred;
discriminating between situations that are anomalous but tolerable and genuine faults
within a given zone of influence;
avoiding unwarranted trips which lead to unjustified stoppage of a sound part of the
installation;
act as rapidly as possible to limit damage (destruction, accelerated ageing, etc.);
safeguarding continuity and stability of the power supply
The point of connection of the protection with the power system usually defines the zone and
corresponds to the location of the current transformers. Ideally, the zones of protection should
overlap, so that no part of the power system is left unprotected. For practical physical and economic
reasons, this ideal design is not always achieved .
Technically a large number of solutions can be realised regarding coordination of the protection
relay. Selecting which type of coordination to use in the various zones of the installation is strictly
linked to installation and design parameters and stems from a series of compromises so that the
objectives required in terms of reliability and availability are achieved keeping the costs and
limiting the risks within acceptable limits. Its necessary the best balance between technical and
financial requirements according to [ 10 ]:
– functional and safety requirements (acceptable risk levels) and reliability
– the reference value of the electrical values;
– the costs (protection devices, control systems, interconnection components, etc.);
– the effects, the admissible duration and the cost of electrical disservices;
– any future evolution of the system.
As stipulates by National Electrical Code NEC a system of coordination based on short-circuit
condition mentioned previous .Selected short-circuit protection can be achieved in different ways
,such as :
1. Time graded protection
2. Time -and current -graded protection
3. Time -and direction -graded protection
4. Logic-based protection
5. Balance current protection
Correct relay application requires knowledge of the fault current that can flow in each part of the
network. Since large-scale tests are normally impracticable, system analysis must be used. The data
required for a relay setting study are [5 ] [10] :
i. a one-line diagram of the power system involved, showing the type and rating of the
protection devices and their associated current transformers
ii. the impedances in ohms, per cent or per unit, of all power transformers, rotating
machine and feeder circuits
iii. the maximum and minimum values of short circuit currents that are expected to flow
through each protection device
iv. the maximum load current through protection devices v. the starting current
requirements of motors and the starting and locked rotor/stalling times of induction
motors
v. the transformer inrush, thermal withstand and damage characteristics
vi. decrement curves showing the rate of decay of the fault current supplied by the
generators
vii. performance curves of the current transformer
The protection relays have to be set to not operate for the maximum load current but must operate
at the minimum expected fault current. It is recommended to use relays with the identical operating
characteristics in succession. In addition, the relay which is furthest from the source must have a
current setting which is equal to or less than the primary current required to operate the relay behind
it. Furthermore, for the relays to operate correctly, sufficient time has to be left which is referred
to as grading margin. The grading margin depends on the following factors [10]:
circuit breaker’s fault current interrupting time
relay timing errors (variation from the characteristic time delay curve)
the overshoot time of the relay
CT errors
3.2 PRINCIPLE OF RELAY COORDINATION
Studying and planning of time- selective protection schemes is most conveniently carried out using
selectivity -diagram .The selectivity diagram is a set of specific time /current curves which shows
all the times /currents curves ,that is ,the operating characteristics of the relays of the concerned
chain of protection relays .
The chains of relays in example of Figure 3.2.2 includes two relays .The selectivity diagram also
includes additional information needed for the planning and operation of protection ,such as lowest
and highest fault current levels in relay points ,maximum load current ,nominal current and the
maximum limit values of possible switching inrush currents and start currents.
The time -graded protection can also be implemented with definite time underimpedance relays
(or distance relay ).The relay measures the phases currents and phase to phase or phase to earth
voltages .Base on these values, it determines the appearance impedance seen from the relay
location .The relay operates if the measured impedances falls below the set start value .The set start
value determines so -called reach of relay ,which define at distance faults seen from relaying point
can still detected .The advantages of impedance relays are [5] :
Its operation is independent of the short-circuit power of the incoming network
The reach and operation time relay are unchanged even if the source impedance changes
These relay operates reliability even though the short -circuit current would be particularly
low .
Underimpedance relays are frequency used as feeder protection relays in networks low short
circuit Another typical application is the use of underimpedance relays as back-up protection relays
in
3.2.3 Time -and Current -graded Protection
Time -and Current -graded Protection can be used in cases where the fault current magnitudes in
fault occurring in front of and behind the relaying point are different .Due to the different fault
current levels using invers time relays but also multi stage definite time relays ,different operating
times can be obtained in either direction .
The fault at upstream transformer is higher than downstream transformer or far away at feeder .So
the high set stage current is apply for upstream transformer and the low stage for down stream
transformer
Figure 3.2.3b shows an example time -current -graded protection application .From the selectivity
diagram ,it can be seen that when a fault occur on feeder 4 ,for example, the total fault current fed
by network and other feeder reaches the level indication 4 .At the diagram ,the operation time can
can even be shorter than 0.1 s (100ms) .The fault current fed by the equivalent generator is at least
on the level indicated by 2 .It can be clearly be seen that in this way a reliable time -grading is
obtained between the generator feeders also in case the fault fed by the network is particularly low
or if one generator is out of operation.
Figure 3.2.3b Power plant overcurrent protection implemented with time and current grading
towards the generator feeders. The generators are of equal rated power and their inverse time relays
share the same settings. I ng = rated current of a single generator.
Another way of determining the direction is first to identify the faulty phases on the basis of the
starts of the phase-specific overcurrent functions and then compare the difference between these
current phasors to the difference between the other two phase-to-phase voltages, for example, the
direction of the phasor I L1 - IL2 is compared to the direction of the phasor U 23 −U 31 . Alternatively,
the phasor I L1 - IL2 can also be compared to the direction of the corresponding faulty phase-to-
phase phasor U12 , or to the corresponding positive-sequence voltage U1 ,which must be suitably
rotated according to the fault type in question.
The protection of ring and meshed networks can also be carried out using underimpedance or
distance relays. These relays are frequently used for the protection of transmission and
subtransmission networks, meshed or ring-operated distribution networks or weak radial networks.
The advantages of the use of distance relays are the same as for the underimpedance relays in
general, and the general time-grading principles also apply in this protection concept.
To achieve a good and reliable selectivity and to fulfill the operating speed requirements as well as
possible, it is typically necessary to implement multiple directional underimpedance stages. The
reach of these stages defines the zones of protection toward the desired operating direction, which
can be either forward of reverse [ 9 ]
Figure 3.2.4.2 Load and short circuit impedance in R-X plane
The figure 3.7 shows the principal reaches of the different zones of the example distance relay The
zone Z1 is underreaching the remote end station, making it possible to apply minimum operating
times. Zone Z2 is slightly overreaching the remote end, which means that the time coordination
with zone Z1 of the successive line is required; therefore the operating time is delayed as much as
the grading margin requires .
Backup protection is an important function of the protection system. According to the International
Electrotechnical Vocabulary [8.13.5], ,, backup protection’’ is intended to operate when a power
system fault is not cleared or an abnormal condition is not detected in the required time because of
failure or inability of other protection to operate or failure of the appropriate circuit-breaker(s) to
trip.
,,By providing backup protection, it is possible to reduce the risk for problems when a protection
relay or a switching device fails to operate.‘’ [ 9 ]