Brosur Datasheet Sariling-Perkins-Sae 300 Kva Silent Type PDF
Brosur Datasheet Sariling-Perkins-Sae 300 Kva Silent Type PDF
Brosur Datasheet Sariling-Perkins-Sae 300 Kva Silent Type PDF
Ruko Dasana Xenter Blok ED.25 Dasana Indah (021) 5420 2425
Kel. Bojongnangka Kec. Kelapa Dua (021) 5464 708
Kab. Tangerang - Banten. Indonesia [email protected]
PERKINS Series
PERKINS Series SAE - 300 P
STANDARD FEATURES
General Features:
Engine ( Perkins 1606A-E93TAG4 )
o
Radiator 50 C max, fans are driven by belt,
with safety guard
12V charge alternator
Alternator: single bearing alternator IP23,
insulation class H/H
Absorber
Dry type air filter, fuel filter, oil filter,
coolant filter
Main line circuit breaker
Standard control panel
Two 12 batteries, rack and cable
Ripple flex exhaust pipe, exhaust siphone,
flange, muffler
User manual
GENERATOR RATINGS
Voltage 440/254 415/240 400/230 380/220
HZ 50 50 50 50
Phase 3 3 3 3
P.F ( COS ¢) 0.8 0.8 0.8 0.8
Standby Amps 541 547 595 627
Standby Ratings ( KW/KVA ) 220/275 220/275 220/275 220/275
Prime Ratings ( KW/KVA ) 240/300 240/300 240/300 240/300
for an unlimited number of annual hours in variable
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load
application, in accordance with GB/T2820-97 (eqvISO8528) ; A 10% overload capability is available
for a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power
for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation
capability is available at this rating.
SALES PROMISES
SARILING provides a full line of brand new and high quality products. Each and every unit is strictly
factory tested.
Warranty is according to our standard conditions: 12 months or 1,000 running hours, subject to the
earlier one.
Service and parts are available from SARILING or distributors in your location.
www.sariling.co.id
www.sariling.co.id
PERKINS Series
PERKINS Series SAE - 300 P
ENGINE DATA
Manufacturer / Model Perkins 1606A-E93TAG4, 4 - cycle
Air Intake System Turbocharge air to air charge cooling
Fuel Injection System MEUI
Cylinder Arrangement 6 Vertical, in Line
Displacement 9.3 L
Bore and Stroke 117 x 146 ( mm )
Compression Ratio 17.2:1
Rated RPM 1500 rpm
Max. Standby Power at Rated RPM 287 Kw
Govemor Type Electronic
EXHAUST SYSTEM
FUEL SYSTEM
OIL SYSTEM
Total Engine Oil Capacity 36 L
Oil Consumption 0.1% ( As a percentage of fuel consumption )
Engine Oil Tank Capacity 33 L
Min Oil Pressure at Reted RPM 379 - 413 kPa
COOLANT SYSTEM
Total Coolant Capacity 309 L
o
Thermostat 86 - 89 C
o
Max Water Temperature 107 C
www.sariling.co.id
www.sariling.co.id
PERKINS Series
PERKINS Series SAE - 300 P
ALTERNATOR DATA
Number of Phase 3
Connecting Type 3 Phase and 4 Wires, “Y” type connection
Number of Bearing 1
Power Factor 0.8
Protection Grade IP23
Altitude ≤ 1000m
Exciter Type Brushless, Self-Exciting
Insulation Class, Temperature Rise H/H
Telephone Influence Factor (TIF) < 50
THF < 2%
Alternator Capacity 300 KVA
Alternator Efficiencies 93%
www.sariling.co.id
www.sariling.co.id
PERKINS Series
PERKINS Series SAE - 300 P
STANDARD FEATURES
OPTIONS
Soundproof Type
Overall Size : 3890 x 1460 x 2150 (mm)
Weight : 3770 Kg
www.sariling.co.id
PERKINS Series
PERKINS Series SAE - 300 P
www.sariling.co.id