IALA Guideline 2012
IALA Guideline 2012
IALA Guideline 2012
For The
Protection of Lighthouses
and
Aids to Navigation
against Damage
from Lightning
Edition 2.1
December 2005
AISM Association Internationale de Signalisation Maritime IALA
Document Revisions
Revisions to the IALA Document are to be noted in the table prior to the issue of a
revised document.
01/12/2005 Page 2 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
Table of Contents
1 INTRODUCTION ...................................................................................... 4
2 SCOPE .....................................................................................................4
5 DESIGN ....................................................................................................6
6 INSTALLATION ....................................................................................... 9
7.4 Records.................................................................................................................................... 24
8 REFERENCE DOCUMENTS.................................................................. 25
01/12/2005 Page 3 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
2 SCOPE
Persons and equipment within buildings can be at risk from lightning currents and
associated voltages which may be conducted into the building as a consequence of a
lightning strike to the building or associated services. Some equipment (e.g. electronic
equipment, including computers) is especially susceptible to damage from over
voltages in the electricity supply caused by lightning and such damage may occur
even when the lightning strike is remote from the building (e.g. from a surge
conducted into the building via the electricity supply).
Measures should to be taken to protect persons and equipment within buildings from
the effects of lightning.
These guidelines describe the practical design installation, inspection and testing of
lightning protection systems for marine aids to navigation structures, equipment and
systems. These guidelines are not intended as a rigorous treatise on lightning
protection and the reader should refer to their national or an international standard for
a more complete description of the protection methods.
3 NEEDS ANALYSIS
It must be emphasized at the outset that complete protection from the effects of
lightning is not always practicable. It is an unfortunate fact that “solid state” elements
(transistors, integrated circuits, microchips etc.) essential to complex modern
electronics systems, are inherently much more susceptible to damage from excessive
voltages than older types of equipment. There are several factors that have to be
considered when evaluating the need for lightning protection. Is there enough of a
threat from lightning to justify protection? Is the cost of replacement of the equipment
sufficient to justify the cost of protection? Is the service critical enough to justify the
cost of protection? The environment of the equipment must be considered because a
01/12/2005 Page 4 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
dry ground plane will require an extensive installation while a wet one will provide a
ground path with a minimum installation.
A risk analysis based on British Standard 6651 : 1992, “The protection of
structures against lightning” suggests a need for protection at most Marine
Aids to Navigation facilities with few exceptions.
The decision to install protection is based mainly on the vulnerability of the
equipment contained within the installation or the structure itself. If the structure is
particularly resilient against lightning strike (such as a metallic day mark) or contains
no equipment vulnerable to a strike, protection is not warranted by the specifications.
For most sites proper grounding installations for lighthouses and equipment
accommodation are essential to minimise danger to personnel and damage to
buildings. Simple and relatively inexpensive measures for the treatment of incoming
telecommunication line circuits and electrical power supply circuits should give
worthwhile additional protection, even to the modern types of communications and
telemetry equipment.
01/12/2005 Page 5 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
5 DESIGN
5.1 The Basics of Lightning Protection
The magnitude of a lightning discharge defies any attempt to block lightning current
from damaging equipment. As a result, the basic philosophy of lightning protection is
to divert the lightning current past personnel and vulnerable equipment along an
efficient path to ground where it can safely dissipate.
The first stage in installing lightning protection is the location of suitable air
terminations, down conductors and a ground termination network that will collect any
lightning discharges and get them to earth with the minimum of disturbance. The
design of the lightning termination network should be completed in accordance with
appropriate national standards. The rolling sphere technique, using a 10 kA (45 metre
radius) sphere, is recommended for determining the location of air terminations at all
but the most rudimentary navigational facilities. For simple structures not exceeding
20 metre in height, the 45 degree zone of protection technique is adequate.
The second stage and an equally important one, is bonding, shielding and interface
protection. The concept here is that even with an efficient termination network,
lightning is such a violent phenomena that large voltages and electromagnetic fields
will still be created at the site and can cause damage.
To illustrate this, Figure 1 shows a lighthouse and building powered by an overhead
supply. The installation is remotely monitored though a telephone line. The lightning
termination system in Figure 1 has been properly designed and an earth impedance of
2 ohms created to dissipate the lightning current. Bonding of the tower and building
and the down conductor has resulted in very low down conductor resistance although
the tower lighthouse may create a down conductor inductance of approximately 10
µH.
01/12/2005 Page 6 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
01/12/2005 Page 7 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
efficiently and by the shortest path to the lightning protection system. If possible, only
one connection should be made to the lightning protection down conductor from each
equipotential zone in order to ensure that direct lightning current does not flow
through the bonding network of the zone on its way to earth.
The lightning protection system needs to be designed to ensure that the absolute
minimum of voltage is generated along the lightning discharge path. Otherwise
unnecessary voltage will be generated between the equipotential zones complicating
the protection of interfaces connecting the zones. Protection of the interfaces and
cables which interconnect the zones including cables from remote areas, for example
PSTN lines, need to be designed to prevent damage given the voltages which are
expected and the lightning protection termination system installed.
01/12/2005 Page 8 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
6 INSTALLATION
6.1 Protection of Structures
6.1.1 General
Vertical down conductors of not less than 50mm 2 should be provided at evenly spaced
horizontal intervals of not less than 20m (10m if the structure exceeds 20m in height)
around the perimeter of the outside of the building (many structures have lightning
conductors on the inside).
Each down conductor should run vertically, sharp bends are to be avoided wherever
possible and re-entrant loops exceeding 8d are not permitted (Figure 2).
FIGURE 2
Each earth electrode should have a test joint at about 300mm above ground level
All down conductors should be connected together by a continuous horizontal (ring)
conductor of not less than 50 mm2. This band should be located at the lowest possible
01/12/2005 Page 9 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
point above the test joints. Where the structure exceeds 20m in height, additional ring
conductors should be provided, spaced evenly throughout the height of the structure.
It is essential that each down conductor should have a separate earth electrode.
Existing down conductors should be inspected and tested. A test joint should be fitted
if one does not already exist. The earth should be inspected and tested in accordance
with Section 6.4 below.
Where the aid to navigation is a lantern and it has a metal murette, each down
conductor should have its top bonded to the murette. Where the lantern or lantern roof
is non conductive, an air terminal network should be provided at the highest point on
the structure and all down conductors bonded to this network. The air termination
should be in the form of a mesh of strip conductors set out so that no part of the roof
is more than 5 metres from a conductor. Where vertical air termination finials are
provided, these should be greater than 0.3m in height, located at intersections of the
horizontal mesh and spaced not more than 10m apart. All metallic projections on or
above the roof should be bonded to the air terminal. Where handrails are provided on
the roof, these may form the air terminal provided that they are bonded at frequent
intervals to a ring conductor which is bonded to the down conductors.
01/12/2005 Page 10 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
FIGURE 3
01/12/2005 Page 11 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
FIGURE 4
01/12/2005 Page 12 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
6.2 Bonding
6.2.1 Services
All incoming and outgoing services should be bonded to the lightning protection
system at the point of entry into the building. These bonds should be as short and
direct as possible, see Figure 4 above. The size of bonding conductor should be not
less than 30mm2. Conductors used for compliance with current national wiring
regulations are not suitable for lightning protection purposes.
The appropriate utility provider may need to be consulted before this work is carried
out. In some cases it may be necessary for the provider to relocate the point of entry
into the building.
Conductors entering the building could be carrying lightning currents or voltage
transients and are considered to be “dirty”. Internal conductors after the earth bonding
point, and surge protection where appropriate (see Section 6.3), are considered
“clean”. It is essential that clean conductors are not routed near or parallel to dirty
conductors. Figure 5 below shows the arrangement for routing cables to and from
surge protectors.
Figure 5
01/12/2005 Page 13 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
6.3.1 General
All isolated metalwork, e.g. sector light pedestals, metal windows, rainwater pipes
and metal soil pipes, should be bonded to the lightning protection system. Vertical
metal pipes should be bonded at the top and bottom. Voltage drops in conductors are
due to inductance rather than resistance, it is therefore essential that the bonding
conductors are kept as short and straight as possible.
FIGURE 6
01/12/2005 Page 14 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
6.4.1 Conduit
Galvanised steel conduit provides the best protection for cables against the effects of
lightning, therefore this method is recommended for cables connecting vulnerable
equipment. All joints should be screwed in to the full depth of the coupler.
6.4.2 Trunking
Metal trunking provides the second best form of protection provided that the
removable covers are permanently bonded by means of a permanent, flexible
connection at each end.
01/12/2005 Page 15 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
induced voltages). In the majority of cases, the effect of this on circulating currents is
negligible.
Where single point earthing is essential due to induced noise onto signal conductors,
additional surge arrestors may be used to provide the earth at the remote end. In
addition the use of double screen cables may be considered with the outer sheath
earthed at both ends for lightning protection purposes and the inner sheath earthed at
one end to minimise induced noise.
Where external sensor, control or data cables are installed, e.g. fuel storage tanks, the
cables should be fitted with a surge arrestor, earthed to the lightning protection
system, at the point of entry to the building. Consideration should be given to
implementing extended data cable runs for computers and distributed control systems
using fibre optic cables which are inherently immune to damage by lightning
discharge voltages. Fibre optic cables may have a metallic sheath which should be
stripped well back (2m) from one end if electrical isolation is intended.
Where long sensor cable runs exist these should use MICC cable with the copper
sheath bonded at each end to the lightning protection system or bonded metal
enclosure. Alternatively, standard sensor cables may be run in conduit, or be fitted
with surge arrestors at their point of entry and exit from each equipotential zone.
01/12/2005 Page 16 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
All ground anchors for guyed poles should be bonded to the earth mat.
All building anchors for ‘T’ antennas etc. should be bonded to the building lightning
protection system.
6.6.4 Generators
The frame of the generator(s) should be bonded to the lightning protection system by
means of a flexible conductor of not less than 30mm 2.
01/12/2005 Page 17 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
with a surge arrestor, bonded to the lightning protection system at the point of entry
into the building. In extreme conditions consideration could be given to the use of
self-powered fibre optic sensors where the storage tank is remote from the main
building.
6.7.1 General
All incoming and outgoing power, telephone, data communications, telemetry sensor
and control cables, and radio antenna feeder cables should be fitted with surge
protection at (or as near as practicable) the point of entry into the building.
All surge protectors should be installed in accordance with the manufacturers’
instructions.
Owing to the nature of lighthouse installations, it is likely that there will be a
significant number of vertical cable runs. This considerably increases the risk of both
resistive coupled and induced transient over voltages being introduced into many of
the internal power, control, monitoring and telecommunications circuits. It is,
therefore, essential that each installation be assessed and appropriate surge
suppression installed. Reference documents listed at the end of these guidelines
should be used and, if necessary, the advice of consultants and manufacturers should
be sought in making this assessment.
01/12/2005 Page 18 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
6.8 Earthing
6.8.1 General
Earthing of a system involves the provision of a connection to the general mass of
earth. This connection should have a resistance not greater than 10 ohms. In typical
Aids to Navigation installations, it is often difficult to achieve this ideal. In such
conditions the general philosophy of protection must be to provide an equipotential
site so that damage due to voltage differences within the site are minimised.
Earth electrodes can be installed in a variety or combination of forms including deep
driven spikes, plates, horizontal strips or conductors and sea terminations. The
type(s) of electrode used depend on local conditions.
The resistance to earth of a given electrode depends upon the electrical resistivity of
the soil in which it is installed. Measurement of soil resistivity and consequent length
of earth electrode can be determined in the following manner.
01/12/2005 Page 19 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
Four equally spaced electrodes are driven into the soil to a depth not exceeding 5% of
the spacing between any two electrodes. A current source is connected to the outer
two electrodes and the voltage between the middle two electrodes is measured, see
Figure 7. From the values of the voltage and current, a value for ‘R’ can be calculated
(most resistively measuring equipment gives a direct reading).
FIGURE 7
The soil resistively can be calculated from the formula:
where:
d is the distance between electrodes
R is the resistance (in ohms) measured between the middle electrodes
This measurement gives the soil resistively at a depth equal to the distance between
the electrodes.
If the distance between the electrodes is varied, the measurement repeated and the
results recorded, soil resistance at various depths will be obtained.
The length of earth electrode required, depending on the section used, can be
determined using the following formulae:
Rectangular Section Horizontal Strips.
ρ 200 L2
R= Log 10
275L wD
01/12/2005 Page 20 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
ρ 100L2
R= Log
φD
10
275L
ρ 800L2
R= Log 10
275L wD
ρ 400L2
R= Log 10
275L ND
Where:
R = apparent earth electrode resistance in ohms
ρ = soil resistivity in ohm centimetres
D = depth of electrode in metres
φ = diameter of electrode in centimetres
L = length of electrode in metres
w = width of electrode in centimetres
6.8.2 On Soil
Each down conductor should have an associated earth network. This may comprise a
single earth electrode or a number of electrodes connected together to form a single
network. The total earth resistance of each earth network should not exceed 10 ohms
multiplied by the total number of down conductors.
6.8.3 On Rock
Where a structure is built on rock, it may not be possible to achieve the 10 ohm
maximum value for earth resistance.
Where this is the case, no maximum value is stated and the following procedure
should be adopted.
Each earth electrode should be formed by inserting a 2.4m earth rod into a 75mm
diameter hole core drilled to a minimum depth of 2.4m and the hole back filled with
cement mixed with a conductive carbonaceous aggregate, for example, Marconite.
Bentonite may be used as a substitute for the cement mix but care will be needed to
ensure that the Bentonite is not washed out of the hole or that it becomes dry.
It is important to note that in cases where a low resistance earth cannot be achieved,
the local ground potential rise during a lightning event can be very extreme indeed. If
suitable bonding arrangements have been put in place at the site, this alone may not
cause significant damage to the installation, but extreme damage may occur to
interfaces and wired connections between the site and remote earths (such as PSTN,
01/12/2005 Page 21 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
7.2 Testing
Only disconnect one earth electrode at a time for testing. If only one earth electrode
exists then the installation MUST be disconnected from all sources of mains power
(including generators) before the earth electrode is disconnected for testing. It is not
sufficient to remove the mains earth bond for this test as other connections between
the lightning protection system and mains earth will probably exist.
7.2.1 General
On completion of the installation or any modification to it, the following
measurements and/or checks should be made and the results recorded in a lightning
protection system logbook:
a) The resistance to earth of the earth termination network and of each earth
electrode;
01/12/2005 Page 22 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
b) The results of a visual check on all conductors, bonds and joints or their measured
electrical continuity.
Tests should be repeated at fixed intervals, preferably not exceeding 12 months.
FIGURE 8
The current test electrode (TE1) should be inserted into the ground some 30 to 50
metres from the lightning earth electrode under test. Initially, the voltage electrode
(TE2) should be inserted about midway between E and TE1. The earth electrode
resistance should be measured and recorded. Two further readings should be taken
and recorded with TE2 placed 7 metres closer to and then 7metres further from E. If
the three readings match within 5% then the position of TE1, the initial position of
TE2 and the initial value obtained should be recorded for comparison with future
tests. If the three results do not agree then the distance between E and TE1 should be
increased and the three tests repeated. This process should be repeated until the three
readings agree within the required accuracy.
If the resistance to earth of the lightning protection system exceeds 10 ohms except on
rock (see 7.2.3 below), or if the resistance of an individual electrode exceeds 10 ohms
multiplied by the total number of electrodes, the value should be reduced. If the
resistance is less than 10 ohms but significantly higher than the previous reading, the
cause should be investigated and any necessary remedial action taken.
01/12/2005 Page 23 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
7.4 Records
The following records should be kept on site or by the person responsible for the
upkeep of the installation:
i) Scale drawings showing the nature, dimensions, materials and positions of all
component parts of the lightning protection system;
ii) The nature of the soil and any special earthing arrangements;
iii) The type and position of the earth electrodes, including reference electrodes;
iv) The test conditions and the results obtained (see testing);
v) Any alterations, additions or repairs to the system;
vi) The name of the person responsible for the installation or its upkeep.
01/12/2005 Page 24 of 25
Guideline 1012 – Protection of lighthouses and aids to navigation against damage from
lightning
7.5 Maintenance
The periodic inspections and tests recommended above will show what maintenance,
if any is needed. Particular attention should be given to the following:
• earthing;
• evidence of corrosion or conditions likely to lead to corrosion;
• alterations and additions to the structure which may affect the lightning
protection system (e.g. changes in the use of the building, the erection of
radio antennas etc.).
8 REFERENCE DOCUMENTS
Two publications of the British Standards Institution are particularly important in this
context and reference will be made to them throughout the remainder of these
guidelines. They are:
• British Standard 6651 : 1992, "The protection of structures against
lightning";
• British Standard Code of Practice BS7430 : 1991, "Earthing".
Other documents considered:
• General Lighthouse Authorities; Development Department Report,
"Guidelines for the Protection of Lighthouses and Aids to Navigation
against Damage from Lightning", No. 20/RPD/1995, Trinity House
Lighthouse Service, 1995
• "Lightning Protection", Australian Maritime Safety Authority (AMSA):
AS-1768-1991
• "Lightning Protection", Norwegian Coastal Administration, 1997
• "Lightning Protection for Radio Transmitter Stations", Nautel Ltd., 1985
• "Lightning Protection Systems", USCG, 1995
Other relevant documents:
• IEC 61024 “Protection of Structures against Lightning”
• IEC 61312 “Protection against Lightning Electromagnetic Impulses – IT
Systems”
01/12/2005 Page 25 of 25