Mangla Dam Dtails
Mangla Dam Dtails
INTRODUCTION ................................................................................................................................................................5
2.2 DAM:..........................................................................................................................................................................17
PRIME MOVER.................................................................................................................................................................24
4.2 TRANSFORMER:..........................................................................................................................................................39
4.2.1 Power Transformer: ..........................................................................................................................................39
5.3 FUSES:.....................................................................................................................................................................57
5.5 ISOLATOR:...............................................................................................................................................................59
2
6.5.1 Latching relay: ..................................................................................................................................................68
CONCLUSION: ..................................................................................................................................................................83
3
ABBREVIATIONS .............................................................................................................................................................84
REFERENCES ...................................................................................................................................................................85
4
List of Figures
5
Figure 23: AVR (Automatic voltage regulator) .................................................................................... 36
6
Figure 47: Over current relay................................................................................................................ 74
7
List of Tables
Table 18: 132kv outgoing circuits from mangla power station ............................................................ 63
Table 19: 220kv outgoing circuits from mangla power station ............................................................ 63
8
Chapter #01 Introduction
Mangla Dam Project was actually conceived in 1950's as a multipurpose project to be constructed at
a place called Mangla on river Jhelum located about 30 km upstream of Jhelum city (120 km from
Capital Islamabad). The initial investigation and its feasibility studies were completed in 1958. Later
on the project was included in the Indus Basin Project. The construction of Mangla Dam was started
As a consequence of the partition of Indo-Pakistan Sub –Continent, in1947 India & Pakistan became
two independent sovereign states. The irrigation system which existed at that time was divided
between the two countries without any regards to the irrigation boundaries which resulted in an
international water dispute which was finally resolved by signing of the INDUS WATER TREATY
in 1960 under the aegis of World Bank. The treaty assigned to India the three Eastern Rivers (Ravi ,
Beas & Sutlej) and to Pakistan the three western rivers (Indus, Jhelum & Chenab) and provided for
construction of replacement works which were called Indus Basin Projects for transfer of irrigation
9
supplies from the western rivers to the areas in Pakistan formerly served by the eastern rivers. The
Works proposed under the treaty were two dams, five barrages, one syphon and eight inter-river link
canals. Mangla Dam on river Jhelum and Tarbela Dam on river Indus were the two dams.
Mangla Dam Project is a multipurpose project designed to conserve & control the flood water of river
Jhelum through significant reduction in flood peaks and volumes at downstream by incidental use of
the available storage space. The other by products are Power Generation to meet the power demand
of the country, Fish culture to provide protein rich diet, Tourism to provide healthy recreation
facilities to the people and Navigation. The Project is located on river Jhelum in District Mirpur of
The construction of Mangla Dam project was started in 1962 and completed in 1967. The project
consists of two dams (Main Dam &Jari Dam), two dykes (Sukian & Kakra) to contain reservoir, two
10
Spillways (Main Spillway & Emergency Spillway) for out flow regulations, Intake structure with five
tunnels (each 1600feet long with internal diameters varying between 26 feet & 30 feet), Power
Station (rated capacity of 1000MW with 10 generating units each of 100 MW) and Tailrace canal
(length of 25000 feet with discharge capacity of 49000 cusecs). Mangla Dam Project was inaugurated
on 23rd November, 1967 by the then President of Pakistan Field Marshal Muhammad Ayub Khan.
11
Unit No. DATE
1 03-07-1967
2 14-07-1967
3 07-03-1968
4 17-06-1969
5 29-12-1973
6 11-03-1974
7 25-05-1981
8 22-07-1981
9 24-09-1993
10 06-07-1994
The existing Power Station is located at downstream of five tunnels. Its building comprises the
machine hall accommodating Generating Unit (1 to 10), eastern loading bay; western loading bays,
control block and Admin block building. The Power Station accommodates 10 generation units on
five tunnels each of 100 MW capacities. The Rotary exciter of unit 1 to 6 (static exciter for remaining
units) is located at 865.5’ SPD floor and connected to the rotor of generator through an upper shaft
coupling with the turbine at 840.5’ SPD. The generated power is transmitted to national grid through
12
220/132 KV bus bars at switchyard. Mangla is also capable of controlling system frequency; all Units
can be selected for this purpose. While on Remote Control (SCADA), these units receive direct
Two electric overhead traveling cranes each with lifting capacity of 200 ton and 30 ton auxiliary hoist
range over the power station super structure. These are provided with a lifting beam and other
paralleling facilities to give a combined lifting capacity of 400 tons at the centre of the beam. An
electric Gantry crane 35/25 ton capacity with 3 ton auxiliary hoist runs on downstream deck of power
station. It is used to lift and pull irrigation valves and draft tube gates.
The downstream galleries of the power station building include battery rooms, various stores and
service rooms. The upstream galleries include LV Switch Board, Cable gallery and ventilation duct.
The control block is at the east end of power station building and comprises control room, air
conditioning plant room, cable flat, 11 KV switchgear room, relay room and different offices while
admin block is at the west end of power station building and comprises R.E (P) office, Auditorium,
Telephone Exchange and different Admin & Accounts Offices. Generator transformers are sited on
ground level upstream side of power station. A cable tunnel runs between power station and
13
1.3 Main Function:
Generation
Switching
Fist main function of dam is water store and control for irrigation purpose. Most of the rivers have
non-uniform run-offs. During rainy period is high but the power requirements are low because of the
absence of irrigation load. It is necessary to store water during excess flow periods so that the same
may be used during lean flow period in most of the streams. The flow is deficient during the part of
the year regulation through artificial storage is necessary The main function of storage is to make
more water available deficient flow times thus increase the firm capacity of the station
1.3.2 Generation:
The second main function of dam is production of electrical energy. Hydro-electric project harness
water power for generation of electrical energy. When water drops through a height it energy is able
1.3.3 Switching:
Third main function is switching and controlling of different circuit during working & fault condition
All generated power transmits & distribute toward the load in 220 KV 132KV LINEs
14
Chapter #02 Hydraulic structure
A hydraulic structure is a structure submerged or partially submerged in any body of water, which
disrupts the natural flow of water. They can be used to divert, disrupt or completely stop the flow.
Reservoir
Dam
Screen
Intake
Penstock
Spiral casing
Spillway
Draft-Tube
Irrigation valve
2.1 Reservoir:
Most of the rivers have non-uniform run-offs. During rainy period is high but the power requirements
are low because of the absence of irrigation load. It is necessary to store water during excess flow
periods so that the same may be used during lean flow period. The storage reservoir thus helps in
supplying water to the turbines according to the load on the plant. Low head plants require very big
15
Figure 6: reservoir
At the time of initial construction of Dam, provision was kept for 40ft rising at Additional Cost of US
$ 18 million. Since the reservoir capacity had reduced to 4.674 MAF from 5.88 MAF due to sediment
16
deposition, rising of Mangla Dam by 30 ft. was taken in hand which has been now completed. The
Project has provided additional water storage of 2.88 MAF, increase in water head by 40 ft. and
additional power generation of 644 GWh per annum and further flood alleviation.
2.2 Dam:
A dam is a man-made structure built across a river. Most dams are built to control river flow, improve
navigation, and regulate flooding. However, some dams are built to produce hydroelectric power.
The function of dam in hydro electric project; is to create artificial head and storage
Diverts the flow of water so the same could used for generation of power. It is most expensive and
Figure 7: dam
The dam also helps in increasing the working head of the power plant. Dams are generally built to
2.3 Screen:
The water intake from the dam or from the fore bay is provided with trash rack. The main function of
trash rack is to prevent the entry of any debris which may damage the wicket gates and turbine
runners or choke-up the nozzles of impulse turbine. During winter season when water forms ice, to
17
prevent the ice from clinging to the trash racks, they are often heated electrically. Sometimes air
bubbling system is provided in the vicinity of the trash racks which bring warmer water to the surface
Screen is a filter that use for the filtration of water and remove the sedimentation from water the
Length 57’ – 8”
Radius 16’ – 4”
Width 32’ - 10”
Thickness of bar ½”
2.4 Intake:
The function of intake is to provide a passage to water to flow into the conduit, channel or penstock.
Intake structure has to be provided with trash rocks, screens and bottom to divert and prevent entry
debris and ice in to the turbines Intake can be classified in two main i.e. high pressures intake and low
pressure intake ones are used in the cause of big storage reservoirs. A low pressure intakes is used for
small ponds meant to store small quantity for daily and weekly load variations
18
Manufacture: VOEST _
WAAGNER_BIRO. AUSTRIA
Year of Construction: 1963
No of Gates. 5
Bottom of Screen Rail 953.17 ft SPD
Sill level of Gate 953.17 ft SPD
Size of Gate: 35.6’ x 18’
Weight of each Gate: 100 Tons
2.5 Penstock:
Penstock carries water from the water storage system to the turbine. It may be a low pressure type. A
low pressure penstock may be a canal flume or a steel pipe. The high pressure penstocks consist of
thick steel pipes. Diameter may be up to a few meters for large units. Each turbine has separate
The primary function of the guide or stay vanes is to convert the pressure energy of the fluid into the
momentum energy. It also serves to direct the flow at design angles to the runner blades.
The spiral casing around the runner of the turbine is known as the volute casing or scroll case.
Throughout its length, it has numerous openings at regular intervals to allow the working fluid to
impinge on the blades of the runner. These openings convert the pressure energy of the fluid into
momentum energy just before the fluid impinges on the blades. This maintains a constant flow rate
despite the fact that numerous openings have been provided for the fluid to enter the blades, as the
19
Figure 9: Spiral causing
2.8 Draft-tube:
The draft tube is a conduit that connects the runner exit to the tail race where the water is discharged
from the turbine. Its primary function is to reduce the velocity of discharged water to minimize the
loss of kinetic energy at the outlet. This permits the turbine to be set above the tail water without
appreciable drop of available head. A draft tube is required to discharge the water, living the turbine,
in to the river. It is necessary that the draft tube must remain water sealed all the time. Impulse
turbine doesn’t need draft tube and discharge water directly. The design and size of the draft tube
should be such that water has free existed and the jet of the water, after it leave turbine, has
unimpeded passage.
20
2.9 Irrigation valve:
Irrigation valve is a relive valve that is a emergency water exit way in cause emergency unit shut
down. Another purpose of the irrigation valve is use extra removal of water for irrigation. These are
the valves that turn on and off the sprinklers; they also may be used for drip irrigation systems. Other
2.10 Spillway:
Every dam is provided with an arrangement to discharge excess water during floods. This
arrangement may be a spillway or a by-pass tunnel or conduit. The spillway should be so designed as
to discharge the major flood water with damage to the dam but at the same time maintain a
21
predetermined head. A spillway is a structure used to provide the controlled release of flows from
a dam or levee into a downstream area, typically the riverbed of the dammed river itself. In the UK
they may be known as overflow channels. Spillways ensure that the water does not overflow and
A spillway is located at the top of the reservoir pool. Dams may also have bottom outlets with valves
or gates which may be operated to release flood flow, and a few dams lack overflow spillways and
A controlled spillway has mechanical structures or gates to regulate the rate of flow. This design
allows nearly the full height of the dam to be used for water storage year-round, and flood waters can
22
An uncontrolled spillway, in contrast, does not have gates; when the water rises above the lip
or crest of the spillway it begins to be released from the reservoir. The rate of discharge is controlled
only by the depth of water above the reservoir's spillway. Storage volume in the reservoir above the
spillway crest can only be used for the temporary storage of floodwater; it cannot be used as water
EMERGENCY SPILLYAY
Type Unregulated Weir
Capacity at 1260 SPD 2,30,000 Cusecs
Width 500 ft
23
Chapter #03 Prime mover
combustion engine) designed to receive and modify force and motion as supplied by some
3.1 Turbine:
Turbine is a rotary machine that converts kinetic energy and potential energy of water into
mechanical work. Water turbines were developed in the 19th century and were widely used for
industrial power prior to electrical grids. Now they are mostly used for electric power generation.
Water turbines are mostly found in dams to generate electric power from water kinetic energy.
Flowing water is directed on to the blades of a turbine runner, creating a force on the blades. Since
the runner is spinning, the force acts through a distance (force acting through a distance is the
definition of work). In this way, energy is transferred from the water flow to the turbine
24
The Francis turbine is a type of water turbine that was developed by James B. Francis in Lowell,
Massachusetts. It is an inward-flow reaction turbine that combines radial and axial flow concepts.
Francis turbines are the most common water turbine in use today. They operate in a water head from
40 to 600 m (130 to 2,000 ft) and are primarily used for electrical power production. The electric
generators that most often use this type of turbine have a power output that generally ranges from just
a few kilowatts up to 800 MW, though mini-hydro installations may be lower. Penstock (input pipes)
diameters are between 3 and 33 ft (0.91 and 10 m). The speed range of the turbine is from 75 to
1000 rpm. A wicket gate around the outside of the turbine's rotating runner controls the rate of water
flow through the turbine for different power production rates. Francis turbines are almost always
mounted with the shaft vertical to isolate water from the generator. This also facilitates installation
and maintenance. The Francis turbine is a type of reaction turbine, a category of turbine in which the
working fluid comes to the turbine under immense pressure and the energy is extracted by the turbine
blades from the working fluid. A part of the energy is given up by the fluid because of pressure
changes occurring in the blades of the turbine, quantified by the expression of Degree of reaction,
while the remaining part of the energy is extracted by the volute casing of the turbine. At the exit,
water acts on the spinning cup-shaped runner features, leaving at low velocity and low swirl with
very little kinetic or potential energy left. The turbine's exit tube is shaped to help decelerate the water
25
TURBINE UNITS 1,2,3,4 UNITS 5 & 6 UNITS 7 & 8 UNITS 9 & 10
Mitsubishi Skoda ACEC Skoda
Manufacturer
Japan Czechoslovakia Belgium Czechoslovakia
Francis Francis Francis Francis
Type
Vertical Shaft Vertical Shaft Vertical Shaft Vertical Shaft
1,38,000 BHP/ 1,38,000 BHP/ 1,38,000 BHP/ 1,38,000 BHP/
Rated out Put
103MW 103MW 103MW 103MW
1,98,000 BHP/ 1,98,000 BHP/ 1,98,000 BHP/ 1,98,000 BHP/
Maximum Out Put
148MW 148MW 148MW 148MW
Net Head 295 Feet 295 Feet 295 Feet 295 Feet
Discharge 4550 Cusecs 4515 Cusecs 4306 Cusecs 4515 Cusecs
Speed 166.7 RPM 166.7 RPM 166.7 RPM 166.7 RPM
Runner Vanes 17 15 14 15
Guide Vanes 24 24 26 24
M.G.B Pads 2 Sleeves 12 2 Sleeves 12
L.G.B Pads 24 24 22 24
T.B Oil Injection
10 10 14 10
Pads
U.G.B Pads 16 8 12 12
No of Brake Pads 10 10 8 10
No. of Jacks 10 10 8 10
26
Chapter#04 Electrical equipments
Electrical equipment includes any machine powered by electricity. It usually consists of an enclosure,
a variety of electrical components, and often a power switch. Examples of these include
Generator
Transformer
Motor
4.1 Generator:
Generator is a device that converts mechanical energy to electrical energy for use in an
external circuit.
Generator is a device that converts mechanical energy to electrical energy for use in an
external circuit. Sources of mechanical energy include steam turbines, gas turbines, water
turbines, internal combustion engines and even hand cranks. The first electromagnetic generator, the
Faraday disk, was built in 1831 by British scientist Michael Faraday. Generators provide nearly all of
the power for electric power grids. According to the Faraday's law of electromagnetic induction,
Whenever a conductor moves in a magnetic field EMF gets induced across the conductor. If the close
path is provided to the conductor, induced emf causes current to flow in the circuit.
27
The working principle of alternator is very simple. It is just like basic principle of DC generator. It
also depends upon Faraday's law of electromagnetic induction which says the current is induced in
the conductor inside a magnetic field when there is a relative motion between that conductor and the
magnetic field. For understanding working of alternator let's think about a single rectangular turn
Say this single turn loop ABCD can rotate against axis a-b. Suppose this loop starts rotating
clockwise. After 90o rotation the side AB or conductor AB of the loop comes in front of S-pole and
conductor CD comes in front of N-pole. At this position the tangential motion of the conductor AB is
just perpendicular to the magnetic flux lines from N to S pole. Hence rate of flux cutting by the
conductor AB is maximum here and for that flux cutting there will be an induced current in the
conductor AB and direction of the induced current can be determined by Fleming’s right hand rule.
As per this rule the direction of this current will be from A to B. At the same time conductor CD
comes under N pole and here also if we apply Fleming right hand rule we will get the direction of
Now after clockwise rotation of another 90o the turn ABCD comes at vertical position as shown
below. At this position tangential motion of conductor AB and CD is just parallel to the magnetic flux
lines; hence there will be no flux cutting that is any current in the conductor. While the turn ABCD
comes from horizontal position to vertical position, angle between flux lines and direction of motion
28
of conductor, reduces from 90o to 0o and consequently the induced current in the turn is reduced to
After another clockwise rotation of 90o the turn again come to horizontal position and here conductor
AB comes under N-pole and CD comes under S-pole, and here if we again apply Fleming’s right
hand rule, we will see that induced current in conductor AB, is from point B to A and induced current
As at this position the turn comes at horizontal position from its vertical position, the current in the
conductors comes to its maximum value from zero. That means current is circulating in the close turn
from point B to A, from A to D, from D to C and from C to B. Just reverse of the previous horizontal
29
While the turn further proceeds to its vertical position the current is again reduced to zero. So if the
turn continues to rotate the current in the turn continually alternate its direction. During every full
revolution of the turn, the current in the turn gradually reaches to its maximum value then reduces to
zero and then again it comes to its maximum value but in opposite direction and again it comes to
zero. In this way the current completes one full sine wave form during each 360o revolution of the
turn. So we have seen how an alternating current is produced in a turn is rotated inside a magnetic
field. From this, we will now come to the actual working principle of alternator.
Now we cut the loop and connect its two ends with two slip rings and stationary brush is placed on
each slip ring. If we connect two terminals of an external load with these two brushes, we will get an
Having understood the very basic principle of alternator, let us now have an insight into its basic
considered that the magnetic field is stationary and conductors (armature) are rotating. But generally
in practical construction of alternator, armature conductors are stationary and field magnets rotate
between them. The rotor of an alternator or a synchronous generator is mechanically coupled to the
shaft or the turbine blades, which on being made to rotate at synchronous speed Ns under some
mechanical force results in magnetic flux cutting of the stationary armature conductors housed on the
stator. As a direct consequence of this flux cutting an induced EMF and current starts to flow through
30
the armature conductors which first flow in one direction for the first half cycle and then in the other
direction for the second half cycle for each winding with a definite time lag of 120o due to the space
displaced arrangement of 120o between them as shown in the figure below. These particular
phenomena results in 3φ power flow out of the alternator which is then transmitted to the distribution
Main parts of the alternator obviously consist of stator and rotor. But, the unlike other machines, in
most of the alternators, field exciters are rotating and the armature coil is stationary.
4.1.1.2 Stator:
Unlike in DC machine stator of an alternator is not meant to serve path for magnetic flux.
Instead, the stator is used for holding armature winding. The stator core is made up of lamination of
31
Figure 20: Generator stator
At high voltages, It easier to insulate stationary armature winding. Which may be as high as 30 kV or
more. The high voltage output can be directly taken out from the stationary armature. Whereas, for a
rotary armature, there will be large brush contact drop at higher voltages, also the sparking at the
brush surface will occur. Field exciter winding is placed in rotor, and the low dc voltage can be
transferred safely. The armature winding can be braced well, so as to prevent deformation caused by
4.1.1.3 Rotor:
Salient type
Cylindrical type
Salient pole type: Salient pole type rotor is used in low and medium speed
alternators. Construction of AC generator of salient pole type rotor is shown in the figure above. This
type of rotor consists of large number of projected poles (called salient poles), bolted on a magnetic
wheel. These poles are also laminated to minimize the eddy current losses. Alternators featuring this
32
Figure 21: Generator rotor
Cylindrical type rotors are used in high speed alternators, especially in turbo -alternators. This type of
rotor consists of a smooth and solid steel cylinder having slots along its outer periphery. Field
windings are placed in these slots. The DC supply is given to the rotor winding through the slip rings
Governing system or governor is the main controller of the hydraulic turbine. The governor varies
the water flow through the turbine to control its speed or power output. Generating units speed and
33
Figure 22: Governor Cabinet internal
i. To start maintain and adjust unit speed for synchronizing with the running units/grid.
ii. To maintain system frequency after synchronization by adjusting turbine output to load
changes.
iii. To share load changes with the other units in a planned manner in response to system
frequency error.
iv. To adjust output of the unit in response to operator or other supervisory commands.
v. To perform normal shut down or emergency over speed shut down for protection.
In isolated systems the governor controls frequency. In large system it may be needed for load
operation control for the system. A block diagram is shown in figure 6.1. Digital electronic load
governor are now employed. Mechanical analogue electronic governors used in earlier plants are also
briefly discussed. In small hydro units digital governors are employed for plant control and protection
also which is discussed in detail in Vol. II - Control and Protection. Basic Control System Governor
control system for Hydro Turbines is basically a feed back control system which senses the speed and
power of the generating unit or the water level of the fore bay of the hydroelectric installation etc. and
takes control action for operating the discharge/load controlling devices in accordance with the
34
deviation of actual set point from the reference point. Governor control system of all units controls
the speed and power output of the hydroelectric turbine. Water level controlled power output
Basic Governor Control System. The control section may be mechanical; analogue electronic or
digital electronic. Actuator can be hydraulic controlled, mechanical (motor) or load actuator. Load
actuator are used in micro hydro range; mechanical (motor operated) actuators may be used say up to
about 1000 kW unit size. Hydraulic actuators are mostly used. Actuator system compares the desired
turbine actuator position command with the actual actuator position. In most of the hydroelectric units
reaction turbines are used. In these turbines it requires positioning of wicket gates, including turbine
blades in Kaplan units. In Peloton units it requires positioning of spear and deflector. Pressure oil
system with oil servomotor is most commonly used actuator. In micro hydro electronic loads
Automatic voltage regulator on a generator stops fluctuation of voltage produced by it during various
load conditions. I will try and explain it in simple manner. The principle of voltage generation
requires a source of magnet which is in a relative motion with conductors. When magnetic lines of
forces cut the conductors, current is produced. The magnet here is not a permanent magnet but an
electro magnet which draws a small current from produced current which induces the electromagnet.
Greater the amount of current drawn from circuit, greater the electromagnetic power will be
produced, and so a greater voltage will be produced at the generator output. So something should be
responsible for regulating the amount of current given to electromagnet to produce a particular set
voltage, say 440 V. This particular thing is known as AVR. As you switch on a heavier load say a
motor, a voltage dip occurs (you can notice this by watching light bulbs going dim for a short period,
35
1–4 seconds). The AVR senses this drop in voltage and increases the feed current through an
AC
UNITS 1,2,3,4 UNITS 5 & 6 UNITS 7 & 8 UNITS 9 & 10
GENERATOR
Hitachi SKODA Hitachi SKODA
Manufacturer
Japan Czechoslovakia Japan Czechoslovakia
Type Vertical Shaft, Salient pole, Umbrella type
MVA Rating 125 MVA 125 MVA 125 MVA 125 MVA
Rated Out Put 100 MW 100 MW 100 MW 100 MW
Maximum Out
115% 115% 115% 115%
Put
Power Factor 0.8 0.8 0.8 0.8
No. of Phases 3 3 3 3
No. of Coolers 12 12 12 12
No. of Poles 36 36 36 36
No. of Brake
10 10 8 10
Pads
Speed 166.7 RPM 166.7 RPM 166.7 RPM 166.7 RPM
Frequency 50 HZ 50 HZ 50 HZ 50 HZ
Voltage 13.2 KV 13.2 KV 13.2 KV 13.2 KV
Current 5467 A 5465 A 5467 A 5467 A
Excitation
261 V 343 V 440 V 325 V
Voltage
Excitation
990 A 1040 A 1363 A 1430 A
Current
Insulation class B F B F
36
On the rotor of the generator, so as to reach the set voltage i.e. 440V again and power is regulated.
Various types of AVR are present today. Modern AVRs based on auto transformer principle have
produced better results in reducing the recovery time (during drop of voltage) to less than 3 sec
Exciter generator is a dc generator that use for the field excitation of main generator. It coupled with
main generator shaft and produced DC current. It self-excited generator. Due to residual magnetism
present in the poles of the stator self-excited DC generators can able to produce their own magnetic
These are simple in design and no need to have the external circuit to vary the field excitation. Again
these self-excited DC generators are classified into shunt, series, and compound generators.
37
EXCITER UNITS 1,2,3,4 UNITS 5 & 6 UNITS 7 & 8 UNITS 9 & 10
Hitachi SKODA Hitachi SKODA
Manufacturer
Japan Czechoslovakia Japan Czechoslovakia
Type Rotary Rotary Static Static
Power 600 KW 600 KW ----- -----
Speed 166.7 RPM 166.7 RPM ----- -----
Full Load Voltage 440 V 420 V 470 V 400 V
3 bridges Each 5 bridges Each
bridge consists of bridge consists of
Full Load Current 1364 A 1430 A
6 Thrusters 1363 6 Thrusters 1363
A A
Insulation Class Class B Class F ----- -----
A permanent magnet synchronous generator is a generator where the excitation field is provided by a
permanent magnet instead of a coil. The term synchronous refers here to the fact that the rotor and
magnetic field rotate with the same speed, because the magnetic field is generated through a shaft
mounted permanent magnet mechanism and current is induced into the stationary armature.PMG use
for the speed regulation. It coupled the main generator shaft. They are known as synchronous
generators because f, the frequency of the induced voltage in the stator (armature conductors)
conventionally measured in hertz, is directly proportional to RPM, the rotation rate of the rotor
usually given in revolutions per minute (or angular speed). It supply give the reaction motor.
38
4.1.4 HTD (Hitachi tune Dynamo):
HTD is a dc generator that use field for the file excitation when requirement is high. It is a induction
motor drive generator work as simple dc generator. It supply give to the AVR (Automatic voltage
regulator) cabinet
4.2 Transformer:
A transformer is an electrical device that transfers electrical energy between two or more circuits
A transformer is an electrical device that transfers electrical energy between two or more circuits
within a conductor which is exposed to time varying magnetic fields. Transformers are used to
1. Laminated core
2. Windings
3. Insulating materials
4. Transformer oil
39
5. Tap changer
6. Conservator
7. Breather
8. Cooling tubes
9. Buchholz Relay
4.2.1.1 Core
The core is used to support the windings in the transformer. It also provides a low reluctance path to
the flow of magnetic flux. It is made of laminated soft iron core in order to reduce eddy current loss
and Hysteresis loss. The composition of a transformer core depends on such factors as voltage,
current, and frequency. The diameter of the transformer core is directly proportional to copper loss
and is inversely proportional to iron loss. If the diameter of the core is decreased, the weight of the
steel in the core is reduced, which leads to less core loss of the transformer and the copper loss
increase. When the diameter of the core is increased, the opposite occurs.
4.2.1.2 Windings:
There are two windings wound over the transformer core that are insulated from each other.
Windings consist of several turns of copper coils bundled together, and each bundle is connected in
1. Primary windings - These are the windings to which the input voltage is applied.
40
2. Secondary windings - These are the windings to which the output voltage is applied.
1. High voltage winding - These are made of copper coil. The number of turns is the multiple of the
number of turns in the low voltage windings. The copper coils are thinner than those of the low
voltage windings.
2. Low voltage windings - These have fewer turns than the high voltage windings. It is made of thick
copper conductors. This is because the current in the low voltage windings is higher than that of high
voltage windings. Transformers can be supplied from either low voltage (LV) or high voltage (HV)
Insulating paper and cardboard are used in transformers to isolate primary and secondary windings
from each other and from the transformer core. Transformer oil is another insulating material.
Transformer oil can actually have two functions: in addition to insulating it can also work to cool the
core and coil assembly. The transformer's core and windings must be completely immersed in the oil.
Normally, hydrocarbon mineral oils are used as transformer oil. Oil contamination is a serious
problem because contamination robs the oil of its dielectric properties and renders it useless as an
insulating medium.
4.2.1.4 Conservator:
The conservator conserves the transformer oil. It is an airtight, metallic, cylindrical drum that is fitted
above the transformer. The conservator tank is vented to the atmosphere at the top, and the normal oil
level is approximately in the middle of the conservator to allow the oil to expand and contract as the
temperature varies. The conservator is connected to the main tank inside the transformer, which is
41
4.2.1.5 Breather:
The breather controls the moisture level in the transformer. Moisture can arise when temperature
variations cause expansion and contraction of the insulating oil, which then causes the pressure to
change inside the conservator. Pressure changes are balanced by a flow of atmospheric air in and out
of the conservator, which is how moisture can enter the system. If the insulating oil encounters
moisture, it can affect the paper insulation or may even lead to internal faults. Therefore, it is
necessary that the air entering the tank is moisture-free. The transformer's breather is a cylindrical
container that is filled with silica gel. When the atmospheric air passes through the silica gel of the
breather, the air's moisture is absorbed by the silica crystals. The breather acts like an air filter for the
transformer and controls the moisture level inside a transformer. It is connected to the end of breather
pipe.
The output voltage may vary according to the input voltage and the load. During loaded conditions,
the voltage on the output terminal decreases, whereas during off-load conditions the output voltage
increases. In order to balance the voltage variations, tap changers are used. Tap changers can be either
on-load tap changers or off-load tap changers. In an on-load tap changer, the tapping can be changed
without isolating the transformer from the supply. In an off-load tap changer, it is done after
Cooling tubes are used to cool the transformer oil. The transformer oil is circulated through the
cooling tubes. The circulation of the oil may either be natural or forced. In natural circulation, when
the temperature of the oil raises the hot oil naturally rises to the top and the cold oil sinks downward.
42
Thus the oil naturally circulates through the tubes. In forced circulation, an external pump is used to
The Buchholz Relay is a protective device container housed over the connecting pipe from the main
tank to the conservator tank. It is used to sense the faults occurring inside the transformer. It is a
simple relay that operates by the gases emitted due to the decomposition of transformer oil during
internal faults. It helps in sensing and protecting the transformer from internal faults.
The explosion vent is used to expel boiling oil in the transformer during heavy internal faults in order
to avoid the explosion of the transformer. During heavy faults, the oil rushes out of the vent. The
level of the explosion vent is normally maintained above the level of the conservatory tank
Power transformer has a small number of turns (LV side) while the transformer secondary side has
many number of turns (HV side). That means an energy flows from the LV to HV side.
43
The most important application of step-up transformer is a generator step-up (GSU) transformer
which is used in all generating plants. Those transformers usually have large turn’s ratio value. The
voltage value produced in energy generation is increased and prepared to the long distance energy
transmission. The energy produced in generating plant is characterized by allow voltage and high
current value. Depending on the generating plant type, the GSU transformer has nominal primary
voltage value from 113.2 up to 220 kV. The nominal voltage value of GSU secondary side can be 132
kV, 220 kV, depending on energy transmission system which is connected to the GSU secondary side
Year of
1966 1966 1992
Manufacturing
Serial No. 58926 58927 965359
Rating 138 MVA 138 MVA 138 MVA
Voltage Ratio 12.5/132 KV 12.5/132 KV 12.5/132 KV
Frequency 50 Hz 50 Hz 50 Hz
Vector Group Yd 11 Yd 11 Y N d 11
No. Of Taps 5 5 5
Alarm 95 C° 95 C° 95 C°
44
Unit 3, 8, 9 & Unit No. 4, 5
220 KV Transformers Unit No. 7 Spare
10 &6
12.5/220
Voltage Ratio 12.5/220 KV 12.5/220KV 12.5/220 KV
KV
Frequency 50 Hz 50 Hz 50 Hz 50 Hz
15.9
13.8
Impedance % (unit 15.52
13.75 15.59 13.87
wise) 15.7
13.74
15.64
Vector Group YNd 11 Yd 11 Yd 11 Yd 11
No. Of Taps 5 5 5 5
Alarm 95 C° 95 C° 95 C° 95 C°
The function of the interconnecting transformer-as the name suggests interconnecting two systems at
different voltages. Normally, they will be either 220KV/132KV or 220KV of say about 138 MVA.
They are bidirectional .During the plant start-up; they import power from grid either at 132KV or
220KV and step down to220KV or 132KV to supply the station auxiliaries. Once the plant is started
and synchronized to the grid, the same transformer can now be used to export power to the grid.
45
Figure 28: Interconnector transformer
They are normally auto-transformers and they will have a delta connected tertiary winding, for
providing a circulating path for the Zero sequence currents. Then the Transformer rating will be
132/220, 138 MVA. Transformers are a critical and expensive component of the power system. Due
to the long lead time for repair of and replacement of transformers, a major goal of transformer
protection is limiting the damage to a faulted transformer. Some protection functions, such as over
excitation protection and temperature-based protection may aid this goal by identifying operating
conditions that may cause transformer failure. The comprehensive transformer protection provided by
multiple function protective relays is appropriate for critical transformers of all applications
46
INTERCONNECTOR
I/C T/F No. 1 I/C T/F No. 2 I/C T/F No. 3 Spare
TRANSFORMERS
Savigliano Savigliano Lueng Chemming ABB
Manufacturer
Italy Italy Shandong, China Germany
Year of Manufacturing 1965 1973 2007 1990
138
Rating 138 MVA 138 MVA 138 MVA
MVA
220/132
Voltage Ratio 220/132 KV 220/132 KV 220/132 KV
KV
603.6
LV Current 604.3 Amp 604.3 Amp 603.59 Amp
Amp
Frequency 50 Hz 50 Hz 50 Hz 50 Hz
Impedance 9.11 % 9.28 % 9.11 % 9.7 %
YNao
Vector Group Yyo (d11) Yyo (d11) YNa od1
(d11)
Volume of Oil (Tons) 40 40 55 35
Alarm 95 C° 95 C° 88 C° 95 C°
Trip 110 C° 110 C° 105 C° 110 C°
Type of Cooling OFB OFB ONAF2 OFAF
No. of Cooling Fan
3 3 3 2
Groups
3 Fans in
2 Fans in each 2 Fans in each 2 groups of 7 fans
No. of Cooling Fan each
group group 1 group of 4 fans
group
Total No. Of Cooling
6 6 18 6
Fans
Station transformer is the step down transformer which is generally used in the generation station. It
is mounted before the generator transformer. It takes the supply from the generator output and step
down it to 11KV which is supplied to the auxiliary panel. So it is use to power the auxiliaries in the
power plant. When it comes to the power system, it serves the same purpose but instead provide
47
STATION TRANSFORMERS
Savigliano
Manufacturer
Italy
Year of Manufacturing 1965
Rating 7.5 MVA
Voltage Ratio 132/11 KV
LV Current 394 Amp
Frequency 50 Hz
Impedance (St. T/F-1, St. T/F2) 7.8%, 7.76 %
Vector Group Yyo
Weight of Oil 10.5 Tons
Volume of Oil -------
Alarm 95 C°
Trip 110 C°
No. Of Taps 19
Type of Cooling ON
Excitation transformers are use to magnetize generators. Generator terminal voltage gives the
excitation transformer input and converts to step down voltage from 13.2kv/440v for generator field
excitation
48
Figure 29: Excitation transformer
Auxiliary transformer is used to supply low voltage for AC power system inside substation such as
lighting, air conditioners and other AC supply system and DC power system such as protection
relays, batteries, SCADA & telecom system and other DC supply system
AUXILIARY TRANSFORMERS
PEL
Manufacturer
Pakistan
Type IDA 316-11
Year of Manufacturing 1966
Rating 300 KVA
Voltage Ratio 11/0.4 KV
LV Current 415 Amp
Frequency 50 Hz
Impedance 4.98 %, 4.88%
Vector Group DY 11
Weight of Oil 0.41 Ton
Volume of Oil -------
No. Of Taps 5
Type of Cooling O.N
49
4.3 Motor:
An electrical motor is such an electromechanical device which converts electrical energy into a
mechanical energy.
Servomotor is a rotary actuator or linear actuator that allows for precise control of angular or linear
position, velocity and acceleration. It consists of a suitable motor coupled to a sensor for position
feedback. It also requires a relatively sophisticated controller, often a dedicated module designed
specifically for use with servomotors. A servomotor is a closed-loop servomechanism that uses
position feedback to control its motion and final position. The input to its control is a signal (either
analogue or digital) representing the position commanded for the output shaft. The motor is paired
with some type of encoder to provide position and speed feedback. In the simplest case, only the
position is measured. The measured position of the output is compared to the command position, the
external input to the controller. If the output position differs from that required, an error signal is
generated which then causes the motor to rotate in either direction, as needed to bring the output shaft
to the appropriate position. As the positions approach, the error signal reduces to zero and the motor
stops. The very simplest servomotors use position-only sensing via a potentiometer and bang-bang
control of their motor; the motor always rotates at full speed (or is stopped). This type of servomotor
is not widely used in industrial motion control, but it forms the basis of the simple and
cheap servos used for radio-controlled models. More sophisticated servomotors use optical rotary
encoders to measure the speed of the output shaft and a variable-speed drive to control the motor
speed. Both of these enhancements, usually in combination with a PID control algorithm, allow the
servomotor to be brought to its commanded position more quickly and more precisely, with less
50
4.3.2 Induction Motor:
An electrical motor is such an electromechanical device which converts electrical energy into a
mechanical energy. In case of three phase AC operation, most widely used motor is three phase
induction motor as this type of motor does not require any starting device or we can say they are self.
Induction motor use for oil circulating pump and water circulating pump and other function
51
Chapter #05 Control & switching
Condition monitoring systems are a basic data provider for advanced asset management strategies,
focusing on system reliability or risk. They allow consistently accessing the health status of your
switchgear and thus can be used to increase maintenance efficiency. To reflect the asset specific
importance and your individual needs, our monitoring offering is graded, starting from
DC step-up system controls the AC input from the household power supply and boosts the voltage to that required by the
battery using a DC/DC circuit. The MCU performs both PFC* control and control of the DC/DC step-up circuit. In
addition to battery cell monitor MCUs, Rennes’s supplies analog and power devices suitable for battery charger/DC-DC
control systems.
D.C Battery system is the lifeline for any control or protection system. The Battery System of the
Power Station is therefore of great importance. Two types of Battery Voltage have been used in the
Power Station. 230V system for protection and control and 50 V systems for indications and alarms.
There are two battery rooms in the Power Station, each having 2 sets of 230V and 50V batteries along
with charger. There is a separate 230V D.C system in the Switchyard, which is similar to those
installed in the Power Station. The rating of 230V and 50V Battery Systems installed in power house
Each 230V D.C system has 2 sets of batteries. The two sets, each comprising of 115 cells are
connected in parallel to increase the reliability and Ampere Hour rating of the battery system. A 3
52
phase input battery charger (Rectifier) has been provided in parallel with the battery sets. The rated
voltage of one cell (without charger) is 2 volts. 115 cells are therefore required for one set. There will
therefore be 230 cells for the two sets in a 230V system. In charged condition the voltage of one cell
is 2.3 to 2.4V therefore in the event when the charger is working, the number of cells required for
maintaining 230V is 103.The remaining 12 cells are called booster cells. These cells remain out of
circuit when the charger is working. Upon failure of the charger the booster cells come into
Besides 230V DC battery system in switchyard there is a 110V DC battery system for the control and
protection of - 1 bay. The rating of 110V battery system is 300 ampere hour. A three phase input
battery charger (rectifier) has been provided in parallel with this system. There are 55 cells with 2V
50Volt systems are similar to 230V system described above except that number of cells are
The following points should be noted regarding the operation of Battery Systems. Whenever the
indication 'Battery Volts L o w ” i s received in Control Room during supply change over, the battery
volts should always be checked in the charger Room/E.C.D in order to ascertain whether the booster
cells have come in circuit or not. In case the booster cells have not come in circuit or if the indication
does not vanish after two minutes, the concerned section should immediately be informed. While
53
recording the battery reading of set No. 1 the reading of two volt meters which show whether there is
some grounding or not, should also be recorded. Battery reading of switchyard should also be
50 V/20A = + 25V
50 V/3A
110 V/2A
The voltmeter of 230V D.C has been installed on E.C.D to enable the Shift Engineers to keep a
continuous watch over the battery readings. In case of failure of A.C supply, or after any
changeover of supply, the voltage should be checked and if it is low, the fuse of booster cells
should be checked and replaced, if required. For Battery Set No. 2 indication "230 V Battery Set No.
2 earth Fault" appears in control room when grounding occurs. Ground volt meters have also
been installed. When the indication appears and persists or if it repeatedly appears, the
visit Battery Charger Rooms at least once a shift and see that the fan and air conditioner are working.
Also the ambient Temp should be noted from the thermometer already installed and the temp
5.2 Switchyard:
The apparatus used for switching, controlling and protecting the electrical circuits and equipment is
known as switchyard the switchgear equipment is essentially concerned with switching and
54
interrupting currents either under normal or abnormal operating conditions. The tumbler switch with
ordinary fuse is the simplest form of switchgear and is used to control and protect lights and other
equipment in homes, offices etc. For circuits of higher rating, a high-rupturing capacity (H.R.C.) fuse
in conjunction with a switch may serve the purpose of controlling and protecting the circuit.
However, such a switchgear cannot be used profitably on high voltage system (3·3 kV) for two
reasons. Firstly, when a fuse blows, it takes some time to replace it and consequently there is
interruption of service to the customers. Secondly, the fuse cannot successfully interrupt large fault
With the advancement of power system, lines and other equipments operate at high voltages and
carry large currents. When a short circuit occurs on the system, heavy current flowing through the
equipment may cause considerable damage. In order to interrupt such heavy fault currents, automatic
circuit breakers (or simply circuit breakers) are used. A circuit breaker is switchgear which can open
or close an electrical circuit under both normal and abnormal conditions. Even in instances where a
fuse is adequate, as regards to breaking capacity, a circuit breaker may be preferable. It is because a
circuit breaker can close circuits, as well as break them without replacement and thus has wider range
Substations transform voltage from high to low, or the reverse, or perform any of several other
important functions. Between the generating station and consumer, electric power may flow
through several substations at different voltage levels. A substation may include transformers to
change voltage levels between high transmission voltages and lower distribution voltages, or at
55
5 Substations may be owned and operated by an electrical utility, or may be owned by a large
With the continued trend of interconnection and the increasing capacity of generating stations, the
need for reliable switchgear has become of paramount importance. This is not surprising because
switchgear is added to the power system to improve the reliability. When fault occurs on any part of
the power system, the switchgear must operate to isolate the faulty section from the remainder circuit.
When fault occurs on any section of the power system, the switchgear must be able to discriminate
between the faulty section and the healthy section. It should isolate the faulty section from the system
without affecting the healthy section. This will ensure continuity of supply.
When fault occurs on any part of the power system, the switchgear must. Operate quickly so that no
damage is done to generators, transformers and other equipment by the short-circuit currents. If fault
is not cleared by switchgear quickly, it is likely to spread into healthy parts, thus endangering
Switchgear must have provision for manual control. In case the electrical (or electronics) control fails,
56
There must be provision for instruments which may be required. These may be in the form of
ammeter or voltmeter on the unit itself or the necessary current and voltage transformers for
5.3 Fuses:
A fuse is a short piece of wire or thin strip which melts when excessive current flows through it for
sufficient time. It is inserted in series with the circuit to be protected. Under normal operating
conditions the fuse element it at a temperature below its melting point. Therefore, it carries the
normal load current without overheating. However when a short circuit or overload occurs, the
current through the fuse element increases beyond its rated capacity. This raises the temperature and
the fuse element melts (or blows out), disconnecting the circuit protected by it. In this way, a fuse
protects the machines and equipment from damage due to excessive currents. It is worthwhile to note
57
Figure 31: Fuse
Earth switch connect the live parts/ line conductors and earth. This switch is normally open. Earth
switch is used to earth the live parts during maintenance and during testing. During maintenance
although circuit is open still there are some voltages on line, due to which capacitance between line
and earth is charged. Before proceeding to maintenance work the voltage s discharged to earth, by
58
.1. Maintenance Earth Switch: These are two or three pole units with a manual operating mechanism.
2. High Speed Earth Switch: These are operated by spring energy. Spring is charged by motor-
mechanism.
5.5 Isolator:
Circuit breaker (C.B) always trip the circuit but open contacts of breaker cannot be visible physically
from outside of the breaker and that is why it is recommended not to touch any electrical circuit just
by switching off the circuit breaker. So for better safety there must be some arrangement so that one
can see open condition of the section of the circuit before touching it. Isolator is a mechanical switch
Electrical isolators separate a part of the system from rest for safe maintenance works. Bus side
isolator: the isolator is directly connected with main bus. Line side isolator: the isolator is situated at
line side of any feeder. Transfer bus side isolator: the isolator is directly connected with transformer.
59
5.6 Surge Arrester:
A surge arrester is a device used to protect electrical equipment from over-voltage transients caused
by external (lightning) or internal (switching) events. This class of device is used to protect
The sulphur hexafluoride gas (SF6) is an electronegative gas and has a strong tendency to absorb free
electrons. The contacts of the breaker are opened in a high pressure flow of Sulphur hexafluoride gas
and an arc is struck between them. The gas captures the conducting free electrons in the arc to form
relatively immobile negative ions. This loss of conducting electrons in the arc quickly builds up
enough insulation strength to extinguish the arc. A gas blast applied to the arc must be able to cool it
rapidly so that gas temperature between the contacts is reduced from 20,000 K to less than 2000 K in
a few hundred microseconds, so that it is able to withstand the transient recovery voltage that is
applied across the contacts after current interruption. Sulfur hexafluoride is generally used in present
high-voltage circuit breakers at rated voltage higher than 52 kV. There are mainly three types of SF6
CB depending upon the voltage level of application. Single interrupter SF6 CB applied for up to 245
60
KV systems. Two interrupter SF6 CB applied for up to 420KV systems. Four interrupter SF6 CB
Air blast circuit breakers employ a high-pressure air blast as an arc quenching medium. Under normal
condition the contacts are closed. When a fault occurs, contacts are opened and an arc is struck
between them. The opening of contacts is done by a flow of air blast established by the opening of
blast valve (located between air reservoir and arcing chamber). The air blast cools the arc and sweeps
away the arching products in to the atmosphere. Thus, the dielectric strength of the medium is
increased, prevents from re-establishing the arc. The arc gets extinguished and flow of current is
interrupted. Air blast circuit breakers were used for the system voltage of 245 KV, 420 KV and even
more, especially where faster breaker operation was required. Air blast circuit breaker has some
specific Advantages over oil circuit breaker which are listed as follows. There is no chance of fire
hazard caused by oil. The breaking speed of circuit breaker is much higher during operation of air
blast circuit breaker. Arc quenching is much faster during operation of air blast circuit breaker. The
61
duration of arc is same for all values of small as well as high currents interruptions. As the duration of
arc is smaller, so lesser amount of heat realized from arc to current carrying contacts hence the
service life of the contacts becomes longer. The stability of the system can be well maintained as it
depends on the speed of operation of circuit breaker. Requires much less maintenance compared to oil
circuit breaker. There are also some disadvantages of air blast circuit breakers. In order to have
frequent operations, it is necessary to have sufficiently high capacity air compressor. Frequent
maintenance of compressor, associated air pipes and automatic control equipment is also required.
Due to high speed, current interruption there is always a chance of high rate of rise of re-striking
voltage and current chopping. There also a chance of air pressure leakage from air pipes junctions.
62
5 New Bong Escape –I 7 Zegalo
6 New Bong Escape –II 7 Zegalo
7 Dinga 71 Cukoo
8 Kuthialan Sheikhan 109 Cukoo
9 Mirpur 7.79 Lynux
10 Kallar syedan 78 Lynux
11 Dudyal-I 36.6 Rail
11 Dudyal-II 36.6 Rail
13 Old Rawat-II 78
Sr.
220 KV Transmission Lines Length (KM)
No. Conductor
1 Ghakhar-1 114.9 Rail
2 Ghakhar-2 113.7 Rail
3 New Ghakar 145 Rail
4 Kala Shah Kaku-1 173 Rail
5 Kala Shah Kaku-2 173 Rail
6 Kala Shah Kaku-3 172 Rail
7 Mangla New Rawat-1 79 Rail
8 Mangla New Rawat-2 79 Rail
63
Chapter #06 P&I (Protection & Instrumentation)
A current transformer (CT) is an electric device that produces an alternating current (AC) in its
secondary which is proportional to the AC in its primary. Current transformers, together with voltage
transformers (VTs) or potential transformers (PTs), which are designed for measurement, are known
as instrument transformers. When a current is too high to measure directly or the voltage of the circuit
is too high, a current transformer can be used to provide an isolated lower current in its secondary
which is proportional to the current in the primary circuit. The induced secondary current is then
suitable for measuring instruments or processing in electronic equipment. Current transformers also
have little effect on the primary circuit. Often, in electronic equipment, the isolation between the
primary and secondary circuit is the important characteristic. Current transformers are used in
electronic equipment and are widely used for metering and protective relays in the electrical power
industry.
64
6.2 Potential Transformers:
Voltage transformers (VT), also called potential transformers (PT), are a parallel connected type of
instrument transformer, used for metering and protection in high-voltage circuits or phasor phase shift
isolation. They are designed to present negligible load to the supply being measured and to have an
accurate voltage ratio to enable accurate metering. A potential transformer may have several
secondary windings on the same core as a primary winding, for use in different metering or protection
circuits. The primary may be connected phase to ground or phase to phase. The secondary is usually
grounded on one terminal. There are three primary types of voltage transformers (VT):
transformer. The capacitor voltage transformer uses a capacitance potential divider and is used at
higher voltages due to a lower cost than an electromagnetic VT. An optical voltage transformer
exploits the electrical properties of optical materials. Measurement of high voltages is possible by the
potential transformers.
65
6.3 Capacitor Coupled Voltage Transformer (CCVT):
A capacitor voltage transformer (CVT or CCVT), is a transformer used in power systems to step
down extra high voltage signals and provide a low voltage signal, for metering or operating a
protective relay
In its most basic form, the device consists of three parts: two capacitors across which the transmission
Line signal is split, an inductive element to tune the device to the line frequency, and a voltage
transformer to isolate and further step down the voltage for the metering devices or protective relay.
The tuning of the divider to the line frequency makes the overall division ratio less sensitive to
changes in the burden of the connected metering or protection devices. The device has at least four
terminals: a terminal for connection to the high voltage signal, a ground terminal, and two secondary
terminals which connect to the instrumentation or protective relay. In practice, capacitor C1 is often
constructed as a stack of smaller capacitors connected in series. This provides a large voltage drop
across C1 and a relatively small voltage drop across C2. As the majority of the voltage drop is on C1,
this reduces the required insulation level of the voltage transformer. This makes CVTs more
66
economical than the wound voltage transformers under high voltage, as the later one requires more
Resistance temperature detectors (RTDs), are sensors used to measure temperature. Many RTD
elements consist of a length of fine wire wrapped around a ceramic or glass core but other
constructions are also used. The RTD wire is a pure material, typically platinum, nickel, or copper.
indication of temperature. As RTD elements are fragile, they are often housed in protective probes.
RTDs, which have higher accuracy and repeatability Common RTD sensing elements constructed of
platinum, copper or nickel have a repeatable resistance versus temperature relationship (R vs. T)
and operating temperature range. The R vs. T relationship is defined as the amount of resistance
change of the sensor per degree of temperature change. The relative change in resistance (temperature
coefficient of resistance) varies only slightly over the useful range of the sensor.
6.5 RELAYS:
67
A relay is an electrically operated switch. Many relays use an electromagnet to mechanically operate
a switch, but other operating principles are also used, such as solid- state relays. Relays are used
where it is necessary to control a circuit by a low-power signal (with complete electrical isolation
between control and controlled circuits), or where several circuits must be controlled by one signal.
The first relays were used in long distance telegraph circuits as amplifiers: they repeated the signal
coming in from one circuit and re-transmitted it on another circuit. Relays were used extensively in
Latching relay
Buchholz relay
Differential Relays
Asymmetrical Relay
Distance Relay
Directional Relay
A latching relay (also called "impulse", "keep", or "stay" relays) maintains either contact position
indefinitely without power applied to the coil. The advantage is that one coil consumes power only
for an instant while the relay is being switched, and the relay contacts retain this setting across a
power outage. A latching relay allows remote control of building lighting without the hum that may
be produced from a continuously (AC) energized coil. In one mechanism, two opposing coils with an
68
over-centre spring or permanent magnet hold the contacts in position after the coil is de-energized. A
pulse to one coil turns the relay on and a pulse to the opposite coil turns the relay off. This type is
widely used where control is from simple switches or single-ended outputs of a control system and
such relays are found in avionics and numerous industrial applications. Another latching type has a
remnant core that retains the contacts in the operated position by the remnant magnetism in the core.
This type requires a current pulse of opposite polarity to release the contacts. A variation uses a
permanent magnet that produces part of the force required to close the contact; the coil supplies
sufficient force to move the contact open or closed by aiding or opposing the field of the permanent
magnet. A polarity controlled relay needs changeover switches or an H bridge drive circuit to control
it. The relay may be less expensive than other types, but this is partly offset by the increased costs in
A Buchholz relay is a safety device sensing the accumulation of gas in large oil- filled transformers,
which will alarm on slow accumulation of gas or shut down the transformer if gas is produced rapidly
in the transformer oil. The contacts are not operated by an electric current but by the pressure of
accumulated gas or oil flow. Depending on the model, the relay has multiple methods to detect a
69
failing transformer. On a slow accumulation of gas, due perhaps to slight overload, gas produced by
decomposition of insulating oil accumulates in the top of the relay and forces the oil level down. A
float switch in the relay is used to initiate an alarm signal. Depending on design, a second float may
also serve to detect slow oil leaks. If an electrical arc forms, gas accumulation is rapid, and oil flows
rapidly into the conservator. This flow of oil operates a switch attached to a vane located in the path
of the moving oil. This switch normally will operate a circuit breaker to isolate the apparatus before
the fault causes additional damage. Buchholz relays have a test port to allow the accumulated gas to
be withdrawn for testing. Flammable gas found in the relay indicate some internal fault such as
overheating or arcing, whereas air found in the relay may only indicate low oil level or a leak.
Electric motors need over current protection to prevent damage from over-loading the motor, or to
protect against short circuits in connecting cables or internal faults in the motor windings. The
overload sensing devices are a form of heat operated relay where a coil heats a bimetallic strip, or
where a solder pot melts, releasing a spring to operate auxiliary contacts. These auxiliary contacts are
in series with the coil. If the overload senses excess current in the load, the coil is de-energized.
This thermal protection operates relatively slowly allowing the motor to draw higher starting currents
before the protection relay will trip. Where the overload relay is exposed to the same environment as
70
the motor, a useful though crude compensation for motor ambient temperature is provided. The other
common overload protection system uses an electromagnet coil in series with the motor circuit that
directly operates contacts. This is similar to a control relay but requires a rather high fault current to
operate the contacts. To prevent short over current spikes from causing nuisance triggering the
armature movement is damped with a dashpot. The thermal and magnetic overload detections are
typically used together in a motor protection relay. Electronic overload protection relays measure
motor current and can estimate motor winding temperature using a "thermal model" of the motor
armature system that can be set to provide more accurate motor protection. Some motor protection
relays include temperature detector inputs for direct measurement from a thermocouple or resistance
The differential relay is one that operates when there is a difference between two or more similar
electrical quantities exceeds a predetermined value. In differential relay scheme circuit, there are two
currents come from two parts of an electrical power circuit. The relays used in power system
protection are of different types. Among them differential relay is very commonly used relay for
protecting transformers and generators from localized faults. Differential relays are very sensitive to
the faults occurred within the zone of protection but they are least sensitive to the faults that occur
outside the protected zone. Most of the relays operate when any quantity exceeds beyond a
71
predetermined value for example over current relay operates when current through it exceeds
predetermined value. But the principle of differential relay is somewhat different. It operates
depending upon the difference between two or more similar electrical quantities
Distance relays differ in principle from other forms of protection in that their performance is not
governed by the magnitude of the current or voltage in the protected circuit but rather on the ratio of
these two quantities. Distance relays are actually double actuating quantity relays with one coil
energized by voltage and other coil by current. The current element produces a positive or pick up
torque while the voltage element produces a negative or reset torque. The relay operates only when
the V/I ratio falls below a predetermined value (or set value).During a fault on the transmission line
the fault current increases and the voltage at the fault point decreases. The V/I ratio is measured at the
location of CTs and PTs. The voltage at the PT location depends on the distance between the PT and
the fault. If the measured voltage is lesser, that means the fault is nearer and vice-versa. Hence the
72
Figure 45: Distance Relay
A directional relay uses an additional polarizing source of voltage or current to determine the
direction of a fault. Directional elements respond to the phase shift between a polarizing quantity and
an operate quantity. The fault can be located upstream or downstream of the relay's location, allowing
An Over current relay is a type of protective relay which operates when the load current exceeds a
pickup value. Instantaneous over current (IOC) or a Definite Time Over current (DTOC) In a typical
application the over current relay is connected to a current transformer and calibrated to operate at or
above a specific current level. When the relay operates, one or more contacts will operate and
energize to trip (open) a circuit breaker. The Definite Time Over current Relay (DTOC) has been
used extensively in the United Kingdom but its inherent issue of operating slower for faults closer to
73
the source led to the development of the IDMT relay. The ANSI device number for (TOC) or (IDMT)
protection is 51.
The stator winding of a hydro generator is often made up of coils with multiple turns in the same slot.
It is therefore possible for faults to develop between adjacent turns on the same phase (turn-to turn
faults). These faults cannot be detected by the stator differential protection because there is no
difference between the neutral- and terminal-side currents. Split-phase protection, an over current
element responding to the difference between the currents in the winding parallel branches, is
typically provided to detect these faults. Ideally, the split-phase element should be sensitive enough to
detect a single shorted turn. Despite the fact that the current in this turn can be six to seven times the
machine nominal current, the current seen by the split-phase protection can be quite small, in the
order of one-twentieth of the generator full-load current. In addition, a spurious split-phase current
can be measured due to current transformer (CT) errors, saturation during external faults in particular.
Therefore, primary considerations in the application of split-phase protection are the method of
measuring the difference in the currents between the parallel branches and the proper selection of the
74
Figure 48: Split phase Relay
Asymmetrical is a condition in which the three-phase voltages in the system differ by an amount
(Amplitude) or if the angle between each two phases is 120°. A measure of the asymmetry of the
voltage is defined as the ratio of the inverse and direct component. The asymmetry in distribution
Under frequency refers to a condition where the frequency of the AC supply drops to a value that is
lower than its defined value such as 50 Hz or 60 Hz. Under frequency is usually caused by
overloading a power source or problems with a prime mover such as engines or turbines.
75
The low-frequency relay is works to protect the load on the frequency of the event generator that falls
below the preset limits. It is activated when the frequency decreases to 49 hertz for 50 hertz
operation. When actuated, the contacts within the relay are approached to signal the annunciate, and
are opened to de-energize the generator switch (contactor), resulting in a display of the fault condition
The elevation of a geographic location is its height above or below a fixed reference point, most
76
an equip gravitational surface (see Geodetic system, vertical datum). Elevation, or geometric height,
is mainly used when referring to points on the Earth's surface, while altitude or geo potential height is
used for points above the surface, such as an aircraft in flight or a spacecraft in orbit, and depth is
Generator Transformer
Exciters
Loading Bays
11KV Switchgear
Relay Room
Ventilation Plants
Machine Hall
Generator
LV switchgear
Normal tail race level (Minimum 835.5ft SPD & Maximum 846ft SPD)
Compressor Area
77
Turbine pits
Excitation Transformers
HTDs
Grease Pumps
Mechanical Workshop
Spiral case
Drainage pits
Ventilation pumps
Control Building
78
Spillway sill Level 1091 FT SPD
79
Chapter # 08 Schedule of Training
5 Auxiliary Section
6 Auxiliary Section
9 Switchyard
10 Switchyard
11 Operation Section
12 Operation Section
13 Operation Section
14 Operation Section
15 Operation Section
16 Operation Section
80
Chapter # 09 Skills Gained
During my internship period the Interpersonal skills, which are the life skills I use every day to how I
communicate with others, but also I got confidence and my ability to listen and understand. Problem
solving, decision making and personal stress management are also considered interpersonal skills.
Through this internship, I found that I matured and I gained many new perspectives, such as problem
solving skill, diversity, effective communication, team work and service recovery, attention to detail,
supervisor was so kind to answer with patience and teach me much that made this internship so
enjoyable. I had gotten a wonderful internship that spent such a happy moment with all of them.
Though, still have so much to learn, I think this challenge was what should include in my career. This
In the section of the company I had been working, most of the time I had work with my supervisor
though gained in terms of improving my team playing skill during my internship period in Mangla
Power Plant
81
9.4 Leadership Skills:
Leadership skills are the tool, behaviors, and capabilities that a person needs in order to be successful
at motivating and directing others. Yet true leadership skills involve something more; the ability to
help people grow in their own abilities. It can be said that the most successful leaders are those that
drive other to active their own success. I gained leadership skills from my supervisor during the
internship period which include managing time, motivating individuals, giving feedback and building
teams
An internship is an opportunity to learn the skills and behaviors along with the work values that are
required for success in the workplace. Workplace ethics are established codes of conduct that reflect
the values of the organization or company where you are employed. I have seen possess willingness
to work hard from my supervisor during my internship period. In addition to working hard it is also
important to work smart. This means I acquired the most efficient way to complete tasks and finding
ways to save time while completing daily assignments. It’s also important to care about my job and
Entrepreneurship is the ability to “create and build something from practically nothing. It is initiating,
doing, achieving and building an enterprise or organization, rather than just watching, analyzing or
describing one. It is the knack of sensing an opportunity where others see chaos, contradiction and
confusion. It is the ability to build a founding team to complement your own skills and talents. It
is the know-how to find, marshal and control resources and to make sure you don’t run out of money
when you need it most. Finally, it is the willingness to take calculated risks, both personal and
financial, and then to do everything possible to get the odds in your favor.”
82
An entrepreneurship education program consists of wide-ranging subjects, and in every
accompany plays an important role, as well as normal lectures in classroom. Of course, in this
respect, the good relationship between educational institutions and business society is very important
for the purpose of implementing an internship program as a part of curriculum. Interns gain firsthand
skills. In this internship I have gained self confidence, information seeking, problem seeking and sees
and acts on opportunities of business in networking. Though helping me to clarify my vision and
Conclusion:
After going through the whole period of internship as an intern I’ve observed so many professional
activities and learnt as well. This internship was very fruitful to me because I had to cover many
different fields. I also learnt new concepts and new ways of working. During this internship period I
acquired practical experience to complement the theoretical content of my study for campus
83
Abbreviations
CT Current transformer
AC Alternating current
VT Voltage transformers
PT Potential transformers
84
References
2. https://en.wikipedia.org/wiki/Hydraulic_structure
3. https://www.merriam-webster.com/dictionary/prime%20mover
4. http://new.abb.com/high-voltage/monitoring
5. https://www.renesas.com/en-us/solutions/automotive/hev-ev/battery-charger.html
6. https://en.wikipedia.org/wiki/Electrical_substation
7. https://en.wikipedia.org/wiki/Elevation
8. https://www.google.com.pk/search?q=spiral+casing&source=lnms&tbm=isch&sa=X&ved=0a
hUKEwiJsrf4wqHWAhVKbxQKHSngD1IQ_AUICigB&biw=1348&bih=633#imgrc=8SbU_
ClVjuGDbM:
9. http://www.wapda.gov.pk/index.php/projects/hydro-power/o-m/mangla
10. http://www.wapda.gov.pk/index.php/projects/hydro-power/o-m/mangla/item/66-mangla-dam-
raising-project
11. http://www.wapda.gov.pk/index.php/projects/hydro-power/o-m/mangla/item/65-mangla-dam-
raising-project
12. https://www.electrical4u.com/signal-generator/
13. https://www.slideshare.net/KeithVaugh/hydropower-11538342?qid=9d5bfaee-8bc5-4150-
a47e-4619f98e6e56&v=&b=&from_search=22
14. https://energy.gov/eere/water/types-hydropower-plants
15. https://water.usgs.gov/edu/hyhowworks.html
16. https://www.google.com.pk/search?biw=1348&bih=633&tbm=isch&sa=1&q=dam+screen&o
q=dam+screen&gs_l=psy-ab.3..0i13k1l4.3076.10832.0.12371.14.13.1.0.0.0.928.2737.4-
1j2j1.4.0....0...1.1.64.psy-ab..9.5.2742...0j0i67k1.jyrzO8kj530#imgrc=IZku93KPky3vzM:
85
17. https://www.quora.com/What-is-function-of-a-draft-tube-in-a-turbine-Why-is-it-tapering-and-
not-cylindrical
18. https://www.quora.com/What-is-the-purpose-of-a-spillway
19. http://www.electronics-tutorials.ws/transformer/transformer-basics.html
20. http://www.jameco.com/jameco/workshop/howitworks/how-servo-motors-work.html
86
Control Room data sheets
87
Figure 52: 220kv Transmission Lines
88
Figure 53: Units Data Sheet
89
Figure 54: Water Flow Data Sheet
90
Figure 55: Spillway Discharge Flow Data Sheet
91
Figure 56: Flow Discharge Data Sheet
92