2 Electrical qualifications
(1) Before a worker climbs or is supported by a pole or structure, or before any work is done that will affect its stability,
(a) the pole or structure must be tested for soundness and stability, and
(b) if there is any doubt as to soundness or stability, the pole or structure must be effectively supported before any wires or cables are changed,
and the supports must be left in place until workers are clear of the pole or structure.
(2) A worker must not climb or be on a pole or structure supported laterally by pike poles only.
(1) Mailboxes, signs, clotheslines, or other obstructions are prohibited on or close to poles on which workers are required to work.
(2) Tags authorized by the owner which are placed on a pole for identification purposes must be less than 1.7 m (5.5 ft) above grade, on the side
of the pole which a climbing worker will face.
A worker must be informed of the potential electrical hazards before being permitted to do work in proximity to energized electrical conductors or
equipment.
Note: If excavating near underground utilities, refer to the excavation requirements in Part 20 (Construction, Excavation and Demolition).
If practicable, service rooms and electrical vaults must be used only for the purpose for which they were intended.
(1) Passageways and working space around electrical equipment must be kept clear of obstructions, be arranged so as to give authorized persons
ready access to all parts requiring attention, and not be used for storage.
(2) Flammable material must not be stored or placed close to electrical equipment.
(1) In this section, "elevating work platform" has the same meaning as in section 13.1.
(2) The employer must ensure that, at least once every 12 months,
(a) an insulated elevating work platform intended for use by a worker is dielectrically tested in accordance with section 5.3.4 of CSA Standard
CAN/CSA-C225-10 Vehicle-mounted aerial devices, and
(b) the insulating capability of the platform referred to in paragraph (a) is certified by the testing agency.
(3) If an insulated elevating work platform does not pass the testing required by subsection (2),
(a) the platform must be considered non-insulated, and
(b) the employer must ensure that
(i) any markings or identification on the platform indicating insulated capability are removed or effectively covered over,
(ii) the platform's inspection and maintenance records indicate the platform is non-insulated,
(iii) the platform's operation and maintenance manuals are revised to indicate the platform is non-insulated, and
(iv) before using the platform, workers are informed the platform is non-insulated.
[Enacted by B.C. Reg. 312/2012, effective February 1, 2013.]
Back to Top
(1) Before working on a power system that for reasons of safety must be de-energized, the worker in charge must ensure that the part of the
system being worked on is isolated and grounded, and locked out as required by this Regulation.
(2) Barriers or distinctive identification must be used to differentiate high voltage electrical equipment which has been de-energized for safety
reasons from similar energized equipment at the work location if lack of such identification would result in undue risk to workers.
(3) If it is impracticable to lock out a power system or part of the power system
(a) the boundaries of the power system or part must be clearly defined,
(b) written work procedures governing the issue of safety protection guarantees, and which address the requirements of sections 19.19 to 19.23,
must be followed, and
(c) all major equipment used to establish safety protection guarantees must be uniquely identified at a conspicuous place on or near the equipment.
(1) One person must be assigned at any one time the exclusive authority as the person in charge to establish the conditions for, and to issue safety
protection guarantees for, the power system or a part of it.
(2) The person in charge must
(a) ensure that the status of the power system or assigned part of the power system is accurately represented on a mimic display,
(b) maintain a log of switching details, safety protection guarantees and operational events, and
(c) authorize the commencement of any work on the power system or assigned part of it.
(3) There must be an effective communication system between the person in charge and the workers doing the work.
(4) Only a worker specifically authorized by the owner may receive a safety protection guarantee or do work on the power system.
If a switching sequence requires the operation of 3 or more devices, a written switching order must be prepared and followed.
(1) Isolating devices used for safety protection guarantees must provide for visual verification of the opening of the isolation point.
(2) Lockable isolating devices must be locked in the position or condition required to protect workers before work commences under a safety
protection guarantee.
(3) A distinctive "DO NOT OPERATE" tag must be placed securely on each isolating device used for a safety protection guarantee.
(1) After a safety protection guarantee is in effect, the equipment to be worked on must be tested to verify isolation before grounding and blocking
begins.
(2) After testing to verify isolation, the person at the worksite responsible for each crew must verify that required grounding and blocking devices
are in place before work begins.
(3) Grounding and blocking of any equipment that may be hazardous to workers must be carried out as close as practicable to the worksite.
(4) If grounding and blocking is not safe or practicable, written safe work procedures acceptable to the Board must be followed.
(5) Grounding and blocking devices may be removed for the purpose of conducting tests.
If a safety protection guarantee involves 2 or more power systems, or 2 or more persons in charge of different parts of a system, appropriate
written procedures must be established and followed to ensure that any safety protection guarantee will be effective.
Back to Top
(1) A control system must be designed, installed, operated and maintained in accordance with a standard acceptable to the Board.
(2) Only qualified and authorized persons may design, install, operate and maintain a control system.
(3) When designing a control system, the types of potential system failure and the effects of failures on the control system and the controlled
equipment must be analysed.
(4) Where practicable and required to minimize risk to workers, a control system must be designed so that
(a) the controlled equipment cannot be inadvertently activated,
(b) an effective basic diagnostic capability is incorporated,
(c) hardwired emergency stop devices are provided at operator stations, and
(d) operator controls other than emergency stop devices can be activated at only one station at a time.
(5) A control system must be used to prevent automatic startup after a power interruption or low voltage occurrence, if automatic startup in such
circumstances is likely to create a hazard to workers.
(6) A control system must, where practicable, be designed so that the controlled equipment does not create a hazard to workers if the system fails
or is shut down.
(7) Equipment operated by a new or altered control system must not be used until the control system has been thoroughly checked and tested to
verify that it will function in the intended manner.
(8) The employer must ensure there is up-to-date documentation which is readily available to affected workers describing the design, installation,
operation and maintenance of a control system.
(9) Control system hardware must be protected from circumstances that could adversely affect the performance of the system including mechanical
damage, vibration, extreme temperatures or humidity levels, high electromagnetic field levels, and power disturbances.
(10) Written safe work procedures must be developed for the use of equipment operated by a control system, including lockout procedures as
required by this Regulation.
(1) The documentation provided for a programmable control system must include a copy of the control program that will allow the equipment to be
reprogrammed if necessary to ensure the safe operation of the system.
(2) Only qualified and authorized persons may have access to the installed control system software.
Where practicable and required to prevent a hazard to workers, a control system must be designed so that during an automatic sequence
(a) the operator may make an emergency stop of the controlled equipment,
(b) the operator may, if safe, be allowed manual control of the equipment, and
(c) the sequence will abort when a protective timer completes its assigned time without an expected event occurring.
(1) The maximum distance from which the operator may control equipment operated by a remote control system must be specified by the
manufacturer.
(2) Written safe work procedures must be established
(a) that specify the maximum distance from which the operator is allowed to remotely control the equipment, and
(b) to ensure that workers remain at a safe distance from remotely controlled moving parts, and any remotely controlled mobile machine.
(1) High voltage electrical equipment must, if practicable, be completely isolated, grounded, and locked out as required by this Regulation before
starting work on it.
(2) If it is not practicable to completely isolate high voltage electrical equipment,
(a) written safe work procedures acceptable to the Board must be followed,
(b) two or more qualified and authorized persons must be present while the work is being done, unless the procedures being followed under
paragraph (a) specifically permit the work to be done by one person,
(c) appropriate electrical protective equipment, including rubber blankets, hoses, hoods, gloves and live line tools must be selected, used, stored,
tested, and maintained in accordance with a standard acceptable to the Board, and
(d) the use of metal ladders, wire reinforced side rail wooden ladders, metal scaffolds or metal work platforms must be in accordance with the
procedures established under paragraph (a).
(1) Before completing installation and after energizing high voltage electrical equipment, conspicuous signs visible to workers must be placed close
to the equipment stating "Danger -- Energized Equipment".
(2) Repealed. [B.C. Reg. 312/2003, effective October 29, 2003.]
Back to Top
(1) Before commencing tree pruning or falling close to energized high voltage overhead conductors, the worksite must be inspected by a qualified
person, authorized by the owner of the power system, to identify any hazardous areas, including situations where any part of a tree to be pruned or
felled is within the applicable minimum distance from an energized conductor as specified in Table 19-1A, or may fall within that distance.
(2) Immediately before commencing work, an inspection must be performed by a qualified person to verify the results of the initial inspection done
under subsection (1) are still valid.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
19.32 Qualifications
Tree pruning or falling within the minimum distances in Table 19-1A from overhead energized high voltage conductors must be carried out by a
worker authorized by the owner of the power system to do such work.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
Tree pruning or falling is not permitted within the minimum distances in Table 19-1A from overhead high voltage energized conductors, unless
(a) a certified utility arborist or a qualified electrical worker is present at the site and directing the work, and
(b) at least one additional qualified person, trained in appropriate emergency rescue procedures, is present.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
(1) Subject to section 19.34.1, a certified utility arborist and any conductive tool must not be closer to an energized high voltage conductor than
the applicable limit of approach in column B of Table 19-3.
(2) An apprentice utility arborist, except as provided in subsection (3), and any tool being used must not be closer to an energized high voltage
conductor than the applicable limit of approach in column C of Table 19-3, or to any vegetation that is closer than the column C limit or that could
swing closer while being cut.
(3) An apprentice utility arborist may work up to the limit of approach permitted for a certified utility arborist in subsections (1) and (5) if the
apprentice utility arborist is in the presence of and under the direct supervision of a certified utility arborist.
(4) Vegetation closer to an energized high voltage conductor than the applicable limit in column B of Table 19-3 must be cut using approved
insulated tools.
(5) An insulated tool acceptable to the Board may be used by a certified utility arborist
(a) up to the limit of approach in column A of Table 19-3, and
(b) from an insulated aerial device to remove vegetation closer than the limit of approach in column A of Table 19-3 up to but not touching an
energized high voltage conductor of 75 kV or less.
(6) Vegetation touching an energized high voltage conductor or within the applicable limit in column A of Table 19-3 for a conductor at a potential
of 75 kV or more may be removed only if
(a) the line is isolated and grounded by a qualified electrical worker, or
(b) the vegetation is removed by a qualified electrical worker who
(i) is authorized by the owner of the power system to remove the vegetation, and
(ii) uses insulated tools and work methods approved under the authorization referred to in subparagraph (i).
(7) Vegetation encroaching past the limits of approach in column B of Table 19-3 that cannot be removed using an insulated aerial device must be
restrained from encroaching past the limit of approach in column A before removal.
(8) A tree must be topped before being felled, or other precautions must be taken to prevent the tree or any part of it from falling closer than the
limit of approach in column A of Table 19-3.
[Amended by B.C. Reg. 312/2012, effective February 1, 2013.]
Table 19-3: Limits of approach for utility arborists
A. Insulated tool limit for B. Work limit for certified C. Work limit for apprentice
Voltage range
certified utility arborists utility arborists utility arborists
Phase to phase Metres Feet Metres Feet Metres Feet
Over 750 V to 20 kV 0.3 1 0.9 3 3 10
Over 20 kV to 30 kV 0.5 1.5 1.2 4 3 10
Over 30 kV to 75 kV 0.9 3 1.5 5 3 10
Over 75 kV to 250 kV 2.1 7 3 10 4.5 15
Over 250 kV to 325 kV 2.6 8.5 4.5 15 6 20
Over 325 kV to 550 kV 3.7 12 6 20 6 20
Column 2
Column 1
Minimum clearance distance from overhead conductor when crossing the neutral
Voltage
conductor
Phase to phase Metres Feet
Over 750 V to 20 Kv 0.60 2.0
Over 20 kV to 30 kV 0.75 2.5
Over 30 kV to 75 kV 0.90 3.0
(1) An insulated tool must be used, stored, tested and maintained as required by section 19.16(2)(c).
(2) An insulated hand tool and insulated aerial device must be maintained in a clean condition and be dielectrically tested to a standard acceptable
to the Board.
Note: An insulated aerial device is not considered an insulated tool.
In this Part
"apprentice utility arborist" means a worker who is not yet a certified utility arborist but has completed a course of instruction recognized by the
certifying authority;
"approved" as applied to electrical equipment, means that the equipment meets the requirements of the Electrical Safety Regulation;
"certified utility arborist" means a person who has completed a course of instruction, has a minimum of 1,200 hours of practical experience and
is certified by an authority acceptable to the Board;
"conductor" means a wire, cable or other metal component installed for the purpose of conveying electric current from one piece of equipment to
another or to ground;
"control system" means a manual, remote, automatic or partially automatic system for controlling the operation of equipment;
"damp location" means an exterior or interior location that is subject to condensation of moisture in, on or adjacent to portable electrical
equipment;
"electrical equipment" includes machinery, plant, works, wires, pipes, poles, conduits, apparatus, appliances and equipment, designed or used,
or intended for use, for or in connection with generation, transmission, supply, distribution or use of electrical energy for any purpose;
"electrical worker" means a person who meets the requirements of the Electrical Safety Regulation for installing, altering or maintaining electrical
equipment;
"electrofishing" means the capture or control of fish by the use of electrical equipment;
"exposed", as applied to electrical equipment or conductors, means that the conductor or a part of the equipment is
(a) electrically connected to a source of voltage difference or electrically charged to have a voltage different from that of earth,
(b) not guarded or insulated in an approved manner, and
(c) in a location where a person or any tool, equipment or material the person is touching or using might come closer than a safe distance away
from the conductor or part;
"hardwired" means the electrical connection of components within a system by means of electrical conductors so that the only way the system
can be modified is by changing the connections;
"high voltage" means a potential difference (voltage) of more than 750 volts between conductors or between a conductor and ground;
"isolated" means that normal sources of energy have been disconnected by opening and securing all associated switches, and that mechanical
equipment has been rendered and secured non-operative by disconnecting, stopping, depressurizing, draining, venting or other effective means;
"low voltage" means a potential difference (voltage) from 31 to 750 volts inclusive, between conductors or between a conductor and ground;
"mimic display" means a symbolic representation of the configuration and status of all or part of a power system, complete with device
designations;
"power system" means all plant and equipment essential to the generation, transmission or distribution of electricity, including any plant or
equipment that is out of service, being constructed or being installed;
"safety protection guarantee" means an assurance that a power system or part of the power system is isolated and will remain isolated;
"safety watcher" means a qualified person whose sole task is to observe the activity when equipment, vegetation or material will be moved
relative to energized electrical equipment or conductors, and signal in a clear and predetermined manner to stop the movement whenever contact
with electrical equipment, conductors or guarding appears probable, or whenever conditions prevent the watcher from having a clear view of the
movement relative to the electrical equipment;
"service room" means a room or space in a building provided to accommodate building service equipment, and meeting the requirements of the
BC Building Code or other applicable legislation;
"vault" means an isolated enclosure, either above or below ground, with fire-resisting walls, ceilings and floors for the purpose of housing
transformers and other electrical equipment;
"wet location" means an exterior or interior location in which uncontrolled liquid may drip, splash or flow on or against portable electrical
equipment.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
19.10 Disconnection and lockout
(1) Low voltage electrical equipment must be completely disconnected and locked out as required by this regulation before starting work on it.
(2) Except as specified in subsection (3), if it is not practicable to completely disconnect low voltage electrical equipment, work must be performed
by qualified and authorized workers and in accordance with written safe work procedures which
(a) require the use of personal protective equipment and voltage-rated tools, appropriate to the hazards and risks associated with the voltage at
which the electrical equipment is operating,
(b) provide that, if practicable, uncontrolled liquid is not permitted close to any worker working on the equipment, and
(c) if applicable, control the use of metal ladders, wooden ladders with wire reinforced side rails, metal scaffolds or metal work platforms.
(3) Work must not be done on energized parts of electrical equipment associated with lighting circuits operating at more than 250 volts-to-ground
without the prior written permission of the Board.
[Amended by B.C. Reg. 312/2012, effective February 1, 2013.]
(1) Before completing installation and after energizing low voltage electrical equipment, conspicuous signs visible to workers must be placed close
to the equipment stating "Danger, Energized Equipment".
(2) Repealed. [B.C. Reg. 312/2003, effective October 29, 2003.]
[Amended by B.C. Reg. 312/2003, effective October 29, 2003.]
(1) Uninsulated, energized parts of low voltage electrical equipment must be guarded by approved cabinets or enclosures unless the energized
parts are in a suitable room or similar enclosed area that is only accessible to qualified and authorized persons.
(2) Each entrance to a room and other guarded location containing uninsulated and exposed, energized parts must be marked with a conspicuous
warning sign limiting entry to qualified and authorized persons.
(3) If uninsulated energized parts are not guarded with approved cabinets or enclosures
(a) suitable barriers or covers must be provided if a worker unfamiliar with the hazards is working within 1 m (3.3 ft) of the uninsulated, energized
parts, or
(b) the worker must be informed of the potential hazards, and provided with and follow appropriate written safe work procedures.
Each electrical distribution switch, circuit breaker and control must be clearly marked to indicate the equipment it serves.
(1) When used outdoors or in a wet or damp location, portable electrical equipment, including temporary lighting, must be protected by an
approved ground fault circuit interrupter of the class A type installed at the receptacle or on the circuit at the panel, unless another acceptable
means of protection is provided.
(2) A ground fault circuit interrupter must not be used in place of grounding except as permitted by the Electrical Safety Regulation.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
Back to Top
19.24 Informing workers about high voltage electrical equipment and conductors
Before a person starts work close to high voltage electrical equipment or conductors that are exposed or that might become exposed during work
at a workplace, the person must be informed of
(a) the existence, location and voltage of the high voltage electrical equipment and conductors, and
(b) the work arrangements and procedures to be followed to ensure compliance with this Part.
[Enacted by B.C. Reg. 312/2010, effective February 1, 2011.]
19.24.1 Minimum approach distance when working close to exposed electrical equipment and conductors
Subject to section 19.24.2, or unless otherwise permitted by this Part, if exposed electrical equipment or conductors at a workplace have a
voltage within a range set out in Column 1 of Table 19-1A, the following must remain at least the distance from the exposed electrical equipment
and conductors that is set out in Column 2 opposite that range of voltage:
(a) a person working at the workplace;
(b) a tool, a machine, material or equipment at the workplace.
Table 19-1A
Column 1 Column 2
Voltage Minimum approach distance for working close to
exposed electrical equipment or conductors
Phase to phase Metres Feet
Over 750 V to 75 kV 3 10
Over 75 kV to 250 kV 4.5 15
Over 250 kV to 550 kV 6 20
19.24.2 Minimum clearance distance when passing under exposed electrical equipment and conductors
(1) This section applies in the circumstances where a person working at a workplace is moving or is involved in moving equipment under exposed
electrical equipment or conductors and is not performing any work other than work related to moving the equipment.
(2) Unless otherwise permitted by this Part, in the circumstances set out in subsection (1), if exposed electrical equipment or conductors have a
voltage within a range set out in Column 1 of Table 19-1B, the following must maintain at least the clearance distance from the exposed electrical
equipment and conductors that is set out in Column 2 opposite that range of voltage:
(a) a person moving or involved in moving the equipment under the exposed electrical equipment or conductor;
(b) the equipment that a person referred to in paragraph (a) is moving;
(c) the load carried by the equipment referred to in paragraph (b).
Table 19-1B
Column 1 Column 2
Voltage Minimum clearance distance for passing under exposed
electrical equipment or conductors
Phase to phase Metres Feet
Over 750 V to 75 kV 2 6.5
Over 75 kV to 250 kV 3 10
Over 250 kV to 550 kV 4 13
(1) If exposed high voltage electrical equipment and conductors cannot be isolated, rerouted or guarded, work must not be done within the
minimum distance in Table 19-1A until the following precautions are taken:
(a) the area within which equipment or materials are to be moved must be barricaded and supervised to restrict entry only to those workers
necessarily engaged in the work;
(b) a safety watcher must be designated;
(c) a positive means must be provided for the safety watcher to give a clear, understandable stop signal to workers in the area, and the watcher
must give the stop signal by no other means.
(2) While equipment is in motion in an area in proximity to energized electrical equipment or conductors, no person other than the equipment
operator may touch any part of the equipment or the material being moved by it.
(3) No person may move a load or any rigging line from its position of natural suspension if it is in proximity to an energized electrical conductor or
equipment.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
[Amended by B.C. Reg. 188/2011, effective February 1, 2012.]
(1) A worker who has taken a course of instruction approved by the Board may work up to the adjusted limits of approach in Table 19-2 when all
the following conditions apply:
(a) the high voltage electrical equipment is energized to a potential of not more than 75kV;
(b) the Board has determined that rerouting, de-energizing or guarding of the equipment is not practicable for the type of work being performed;
(c) the work is not being done for the owner of the power system;
(d) the work is of a type that must be done regularly;
(e) the worker follows written safe work procedures acceptable to the Board.
(2) A qualified electrical worker may work closer than the limits specified in Table 19-2 provided the worker is authorized by the owner of the
power system and uses procedures acceptable to the Board.
Table 19-2: Adjusted limits of approach
Minimum
Voltage distance
Phase to phase
Metres Feet
Over 750 V to 20 kV 0.9 3
Over 20 kV to 30 kV 1.2 4
Over 30 kV to 75 kV 1.5 5
(1) Sections 19.24 to 19.27 do not apply to emergency actions close to energized high voltage electrical equipment or conductors carried out by
workers who have undergone a course of instruction approved by the Board.
(2) During emergency actions, all reasonable precautions must be taken to control the hazards including, where practicable,
(a) restricting entry into the area within which equipment or materials are to be moved to workers necessarily engaged in the work,
(b) designating a safety watcher,
(c) when equipment is in motion, preventing a person other than the equipment operator from touching any part of the equipment or the material
being moved by it, and
(d) requiring the equipment operator to operate the controls from the seat provided on the equipment, or from a metal stand that is integral with the
frame of the equipment and clear of the ground, or from a metallic mat bonded to the frame of the machine and located on the ground beside the
machine.
Qualified workers and workers under their direct supervision may work within the minimum distances to energized high voltage electrical
equipment and conductors, as specified in Table 19-1A and Table 19-2, when authorized by the owner of the power system and using work
procedures acceptable to the Board.
[Amended by B.C. Reg. 312/2010, effective February 1, 2011.]
Back to Top
19.1 Definitions
19.24 Informing workers about high voltage electrical equipment and conductors
19.24.1 Minimum approach distance when working close to exposed electrical equipment and conductors
Table 19-1A: Table 19-1A
19.24.2 Minimum clearance distance when passing under exposed electrical equipment and conductors
Table 19-1B: Table 19-1B
19.25 Assurance in writing
19.26 Assurance not practicable
19.27 Specially trained
Table 19-2: Adjusted limits of approach
19.28 Emergency work
19.29 Authorization by owner
CONTROL SYSTEMS
ELECTROFISHING