Iecex Bas 09.0076X
Iecex Bas 09.0076X
Iecex Bas 09.0076X
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Marking:
Ex ia IIC T4 Ga
Ex ia IIC T5 Ga
HART Versions
Ex ia IIC T4 Ga
Fieldbus / Profibus / FISCO Versions
See Certificate Schedule for full Model, Certification & ambient temperature range information
Signature:
(for printed version)
Date:
STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was
found to comply with the following standards:
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the
Test Report:
GB/BAS/QAR06.0072/08
IECEx Certificate
of Conformity
Certificate No: IECEx BAS 09.0076X Issue No: 6
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
The Model 3051 Series Pressure Transmitters is designed to convert process pressure measurements into a 4-20mA HART, Fieldbus
/ Profibus or FISCO signal. The apparatus contains a number of printed circuit boards consisting of an appropriate terminal block, one
or two output boards, a sensor board, a sensor and an optional liquid crystal display all housed in either a polyurethane coated
aluminium or stainless steel enclosure. When the optional display is fitted the housing cover contains a glass window. External
connections to the integral terminal block are made via one of two tapped holes.
This certificate covers the Model 3051C, 3051L, 3051H, 3051HT, 3051T, 3051CA, 3001C, 3001CL and 3051CH Pressure
Transmitters, which vary in the process connection.
The above models can be fitted with either a Standard, Enhanced, or Low Power 4-20mA HART output board, or a Fieldbus output
board permitting connection to either Foundation Fieldbus or Profibus PA systems. The Fieldbus variant can alternatively be fitted with
a FISCO transient protection board to form a FISCO variant of the Model 3051 Fieldbus Pressure Transmitter.
See the additional page for further model information and certification codes.
1) If the apparatus is fitted with an optional 90V transient suppressor, it is not capable of withstanding the 500V insulation test
required by clause 6.3.12 of IEC 60079-11: 2011. This must be taken into account when installing the apparatus.
2) The enclosure may be made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken
to protect it from impact or abrasion if located in Zone 0.
IECEx Certificate
of Conformity
Certificate No: IECEx BAS 09.0076X Issue No: 6
Variation 6.1
To permit the fitting of an alternative sensor board to form the Model 3051HT Pressure Transmitters. These variants of the equipment
are of a similar construction, and have the same input parameters and temperature classification as those previously assessed, but
with a reduced ambient temperature range. The marking section on page 1 and the Certificate Schedule on page 3 of the
certificate were updated to list the 3051HT variants.
Variation 6.2
To permit the removal of the variants of the equipment fitted with Sensor Board 3 from the certification. As a result of this, Drawing
No’s 03031-0585, 03031-0586 & 03031-0587 have been made obsolete and the Sensor Board Assembly removed from the parts list.
Variation 6.3
To permit the removal of Model 3051P Pressure Transmitter from the certification. The Certificate Schedule on page 3 of the certificate
was revised to remove reference to the Model 3051P.
IECEx Certificate
of Conformity
Certificate No: IECEx BAS 09.0076X Issue No: 6
Additional information:
All models of the Model 3051 Series Pressure Transmitters can be alternatively mounted on process connection pipework to form the
following Flowmeters: -
Annex:
Model 3051 / 3001, Model 3051 Enhanced and Model 3051 Low Power HART Pressure
Transmitters Input Parameters
Ui = 30V Ci = 0.012µF
Ii = 200mA Li = 0
Pi = 0.9W
The above parameters apply to both Group IIC and Group IIB and the Ci and Li values do not
exceed those specified for the FISCO model.
Page 1 of 1