PID Controller Design
PID Controller Design
http://ctms.engin.umich.edu/CTMS/index.php?example=Introduction§ion=ControlPID
In this tutorial we will introduce a simple, yet versatile, feedback compensator structure: the Proportional-Integral-Derivative (PID)
controller. The PID controller is widely employed because it is very understandable and because it is quite effective. One attraction
of the PID controller is that all engineers understand conceptually differentiation and integration, so they can implement the control
system even without a deep understanding of control theory. Further, even though the compensator is simple, it is quite sophisticated
in that it captures the history of the system (through integration) and anticipates the future behavior of the system (through
differentiation). We will discuss the effect of each of the PID parameters on the dynamics of a closed-loop system and will demonstrate
Key MATLAB commands used in this tutorial are: tf , step , pid , feedback , pidtune
Related Tutorial Links
Contents
PID Overview
Example Problem
Proportional Control
Proportional-Derivative Control
Proportional-Integral Control
Proportional-Integral-Derivative Control
The output of a PID controller, which is equal to the control input to the plant, is calculated in the time domain from the feedback error
as follows:
(1)
First, let's take a look at how the PID controller works in a closed-loop system using the schematic shown above. The variable ( )
represents the tracking error, the difference between the desired output ( ) and the actual output ( ). This error signal ( ) is fed to
the PID controller, and the controller computes both the derivative and the integral of this error signal with respect to time. The control
signal ( ) to the plant is equal to the proportional gain ( ) times the magnitude of the error plus the integral gain ( ) times the
integral of the error plus the derivative gain ( ) times the derivative of the error.
This control signal ( ) is fed to the plant and the new output ( ) is obtained. The new output ( ) is then fed back and compared to
the reference to find the new error signal ( ). The controller takes this new error signal and computes an update of the control input.
The transfer function of a PID controller is found by taking the Laplace transform of Equation (1).
(2)
We can define a PID controller in MATLAB using a transfer function model directly, for example:
Kp = 1;
Ki = 1;
Kd = 1;
s = tf('s');
C = Kp + Ki/s + Kd*s
C =
s^2 + s + 1
-----------
Alternatively, we may use MATLAB's pid object to generate an equivalent continuous-time controller as follows:
C = pid(Kp,Ki,Kd)
C =
Kp + Ki * --- + Kd * s
with Kp = 1, Ki = 1, Kd = 1
Let's convert the pid object to a transfer function to verify that it yields the same result as above:
tf(C)
ans =
s^2 + s + 1
-----------
Increasing the proportional gain ( ) has the effect of proportionally increasing the control signal for the same level of error. The fact
that the controller will "push" harder for a given level of error tends to cause the closed-loop system to react more quickly, but also to
overshoot more. Another effect of increasing is that it tends to reduce, but not eliminate, the steady-state error.
The addition of a derivative term to the controller ( ) adds the ability of the controller to "anticipate" error. With simple proportional
control, if is fixed, the only way that the control will increase is if the error increases. With derivative control, the control signal can
become large if the error begins sloping upward, even while the magnitude of the error is still relatively small. This anticipation tends
to add damping to the system, thereby decreasing overshoot. The addition of a derivative term, however, has no effect on the steady-
state error.
The addition of an integral term to the controller ( ) tends to help reduce steady-state error. If there is a persistent, steady error, the
integrator builds and builds, thereby increasing the control signal and driving the error down. A drawback of the integral term, however,
is that it can make the system more sluggish (and oscillatory) since when the error signal changes sign, it may take a while for the
integrator to "unwind."
The general effects of each controller parameter ( , , ) on a closed-loop system are summarized in the table below. Note,
these guidelines hold in many cases, but not all. If you truly want to know the effect of tuning the individual gains, you will have to do
(3)
Taking the Laplace transform of the governing equation, we get
(4)
The transfer function between the input force and the output displacement then becomes
(5)
m = 1 kg
b = 10 N s/m
k = 20 N/m
F = 1 N
(6)
The goal of this problem is to show how each of the terms, , , and , contributes to obtaining the common goals of:
Minimal overshoot
Let's first view the open-loop step response. Create a new m-file and run the following code:
s = tf('s');
step(P)
The DC gain of the plant transfer function is 1/20, so 0.05 is the final value of the output to a unit step input. This corresponds to a
steady-state error of 0.95, which is quite large. Furthermore, the rise time is about one second, and the settling time is about 1.5
seconds. Let's design a controller that will reduce the rise time, reduce the settling time, and eliminate the steady-state error.
Proportional Control
From the table shown above, we see that the proportional controller ( ) reduces the rise time, increases the overshoot, and reduces
The closed-loop transfer function of our unity-feedback system with a proportional controller is the following, where is our
(7)
Let the proportional gain ( ) equal 300 and change the m-file to the following:
Kp = 300;
C = pid(Kp)
T = feedback(C*P,1)
t = 0:0.01:2;
step(T,t)
C =
Kp = 300
P-only controller.
T =
300
----------------
s^2 + 10 s + 320
The above plot shows that the proportional controller reduced both the rise time and the steady-state error, increased the overshoot,
Proportional-Derivative Control
Now, let's take a look at PD control. From the table shown above, we see that the addition of derivative control ( ) tends to reduce
both the overshoot and the settling time. The closed-loop transfer function of the given system with a PD controller is:
(8)
Let equal 300 as before and let equal 10. Enter the following commands into an m-file and run it in the MATLAB command
window.
Kp = 300;
Kd = 10;
C = pid(Kp,0,Kd)
T = feedback(C*P,1)
t = 0:0.01:2;
step(T,t)
C =
Kp + Kd * s
with Kp = 300, Kd = 10
T =
10 s + 300
----------------
s^2 + 20 s + 320
Proportional-Integral Control
Before proceeding to PID control, let's investigate PI control. From the table, we see that the addition of integral control ( ) tends
to decrease the rise time, increase both the overshoot and the settling time, and reduces the steady-state error. For the given system,
(9)
Let's reduce to 30, and let equal 70. Create a new m-file and enter the following commands.
Kp = 30;
Ki = 70;
C = pid(Kp,Ki)
T = feedback(C*P,1)
t = 0:0.01:2;
step(T,t)
C =
Kp + Ki * ---
with Kp = 30, Ki = 70
T =
30 s + 70
------------------------
s^3 + 10 s^2 + 50 s + 70
) because the integral controller also reduces the rise time and increases the overshoot as the proportional controller does (double
effect). The above response shows that the integral controller eliminated the steady-state error in this case.
Proportional-Integral-Derivative Control
Now, let's examine PID control. The closed-loop transfer function of the given system with a PID controller is:
(10)
After several iterations of tuning, the gains = 350, = 300, and = 50 provided the desired response. To confirm, enter the
following commands to an m-file and run it in the command window. You should obtain the following step response.
Kp = 350;
Ki = 300;
Kd = 50;
C = pid(Kp,Ki,Kd)
T = feedback(C*P,1);
t = 0:0.01:2;
step(T,t)
C =
Kp + Ki * --- + Kd * s
Now, we have designed a closed-loop system with no overshoot, fast rise time, and no steady-state error.
When you are designing a PID controller for a given system, follow the steps shown below to obtain a desired response.
5. Adjust each of the gains , , and until you obtain a desired overall response. You can
always refer to the table shown in this "PID Tutorial" page to find out which controller controls which
characteristics.
Lastly, please keep in mind that you do not need to implement all three controllers (proportional, derivative, and integral) into a single
system, if not necessary. For example, if a PI controller meets the given requirements (like the above example), then you don't need
to implement a derivative controller on the system. Keep the controller as simple as possible.
An example of tuning a PI controller on an actual physical system can be found at the following link. This example also begins to
illustrate some challenges of implementing control, including: control saturation, integrator wind-up, and noise amplification.
Automatic PID Tuning
MATLAB provides tools for automatically choosing optimal PID gains which makes the trial and error process described above
unnecessary. You can access the tuning algorithm directly using pidtune or through a nice graphical user interface (GUI)
using pidTuner.
The MATLAB automated tuning algorithm chooses PID gains to balance performance (response time, bandwidth) and robustness
(stability margins). By default, the algorithm designs for a 60-degree phase margin.
Let's explore these automated tools by first generating a proportional controller for the mass-spring-damper system by entering the
command shown below. In the shown syntax, P is the previously generated plant model, and 'p' specifies that the tuner employ a
proportional controller.
pidTuner(P,'p')
The pidTuner GUI window, like that shown below, should appear.
Notice that the step response shown is slower than the proportional controller we designed by hand. Now click on the Show
Parameters button on the top right. As expected, the proportional gain, , is smaller than the one we employed, = 94.86 < 300.
We can now interactively tune the controller parameters and immediately see the resulting response in the GUI window. Try dragging
the Response Time slider to the right to 0.14 s, as shown in the figure below. This causes the response to indeed speed up, and we
can see is now closer to the manually chosen value. We can also see other performance and robustness parameters for the
system. Note that before we adjusted the slider, the target phase margin was 60 degrees. This is the default for the pidTuner and
Now let's try designing a PID controller for our system. By specifying the previously designed or (baseline) controller, C, as the second
parameter, pidTuner will design another PID controller (instead of P or PI) and will compare the response of the system with the
pidTuner(P,C)
We see in the output window that the automated controller responds slower and exhibits more overshoot than the baseline. Now
choose the Domain: Frequency option from the toolstrip, which reveals frequency domain tuning parameters.
Now type in 32 rad/s for Bandwidth and 90 deg for Phase Margin, to generate a controller similar in performance to the baseline.
Keep in mind that a higher closed-loop bandwidth results in a faster rise time, and a larger phase margin reduces the overshoot and
Finally, we note that we can generate the same controller using the command line tool pidtune instead of the pidTuner GUI
opts = pidtuneOptions('CrossoverFrequency',32,'PhaseMargin',90);
C =
Kp + Ki * --- + Kd * s
info =
Stable: 1
CrossoverFrequency: 32
PhaseMargin: 90