1
1
CATALOG
Setting Daikin's new standards in
indoor comfort and efficiency
Table of Contents
OVERVIEW
Overview 4 VRV Accessories 114
Why choose Daikin? 5 Branch Selector Boxes 114
What is Daikin VRV ? 6 REFNET Pipe Joints 116
Why choose Daikin VRV ? 7 Hail Guard Kit for VRV IV 117
Which VRV System Offers the Best Solution? 8 AHU (Air Handling Kit) Integration Kit 118
PRODUCT PORTFOLIO
Setting the Standards 10 Control Box EKE_CBAV3-US 120
Daikin VRV 12
Ventilation 123
Setting the Standards, Again 12
FXMQ_MFVJU - 100% Outside Air Processing Unit 126
What does a VRV installation mean to you? 24
VAM-GVJU - Energy Recovery Ventilator 128
Vertical Market Applications 26
DVS Dedicated Outside Air System 130
Product Portfolio 29
Controls 131
Outdoor Units 30
VRV Controls Solution 132
Indoor Units 32
VRV Controls Systems Overview 134
Accessories 34
INDOOR UNITS
Individual Controllers 136
Indoor units 41 BRC1E73 - Navigation™ Remote Controller 136
Indoor Units Overview 44 BRC4C82/BRC7E818/BRC7E83/BRC7E830 - 140
Wireless Remote Controller
FXMQ_PBVJU - HSP DC Concealed Ducted Unit 46
AZAI6WSCDKA-DKN Cloud Wi-Fi Adaptor 140
FXSQ_TAVJU - MSP Concealed Ducted Unit 48
BRC2A71 - Simplified Remote Controller 140
FXDQ_MVJU - LSP Slim Concealed Ducted Unit 50
Advanced Multi-Zone Controllers 142
FXTQ_TAVJU Multi-Position Air Handling Unit 52
DCM601A71 - intelligent Touch Manager™ (iTM) 142
FXMQ_MVJU - HSP High Capacity Concealed Ducted Unit 54
OUTDOOR UNITS
DCS601C71 - intelligent Touch Controller™(iTC) 144
FXNQ_MVJU9 - Concealed Floor-Standing Unit 56
Centralized Controllers 146
FXFQ_TVJU - Round Flow Sensing Cassette 58
DCS302CT1 - Central Remote Control 146
FXUQ_PVJU - 4-Way Ceiling-Suspended Cassette 62
DCS301C71 - Unified ON/OFF Controller 147
FXZQ_TAVJU - VISTATM 2x2 Cassette 64
DST301BA61 - Schedule Timer 147
FXEQ_PVJU - Ceiling-Mounted Cassette 66
External Equipment Control 148
FXHQ_MVJU - Ceiling-Suspended Unit 68
DCM009A51 - iTM™ BACnet ® Client Option 148
FXAQ_PVJU - Wall-Mounted Unit 70
750-831 - Daikin WAGO ® BACnet ®/IP Controller 149
FXLQ_MVJU9 - Floor-Standing Unit 72
Interface Solutions 150
VENTILATION
DZK Zoning Kit for VRV Indoor Units 74
DCM014A51 - iTM™ BACnet ® Server Gateway Option 150
Outdoor units 77 DMS502B71 - Interface for use BACnet ® 152
VRV IV X - Air-Cooled Heat Recovery 80 DMS504C71 - Interface for LonWorks® 152
VRV IV X Indoor Units 80-97% AFUE Communicating Gas Furnace DTA116A51 - DIII-Net/Modbus® Adaptor 152
VRV A-Coil CXTQ_TASBLU 84 VRV Monitoring Services 153
Daikin VRV AURORA™ Heat Recovery 86 D-NET Air Conditioning Network Service System 153
Daikin VRV AURORA™ Heat Pump 90 Controls Product List 154
VRV IV - Air-Cooled Heat Recovery 94
Support and Tools 157
CONTROLS
VRV IV - Air-Cooled Heat Pump 98
Support and tools overview 158
VRV T-Series Water-Cooled Systems 102
Selection software 159
VRV IV S - Series - Heat Pump 108
Energy screening and simulation tools 160
VRV IV, I VRV III PC, VRV T-Series Water-Cooled Systems, & VRV IV-S 110
- Installation Space Design and verification 161
VRV IV, VRV III PC, VRV T-Series Water-Cooled Systems, & VRV IV-S 112 Online and tablet reference material 161
- Piping Length Smartphone and mobile reference 162
After sales and service 163
SUPPORT & TOOLS
3
4 www.daikincomfort.com
Why choose Daikin?
Refrigerant control
Efficient heat transport
DAIKIN Manufacturing
CORE
TECHNOLOGY
Sales
VRV is built upon 4 basic “Building Blocks” — Outdoor This makes it very flexible and ideal for energy-efficient
Unit, Indoor Unit, Piping, and Controls — providing the and comfortable cooling and heating of many types of
attributes of a central chilled water system but with the buildings such as banks, health care, skilled care, libraries,
simplicity of a split system. storage facilities, conference centers, etc.
+ + +
Outdoor Unit Indoor Unit Piping Controls
Applications
»» Multi-family
residences
»» Retail
»» Hotels
»» Office buildings
»» Schools, etc.
6 www.daikincomfort.com
Why choose Daikin VRV?
OVERVIEW
Inventor and leader in VRV systems since 1982
Unique products that make the difference
»» In efficiency »» In control
-- Variable Refrigerant Temperature (VRT) technology -- intelligent Touch Manager™ (iTM)— a mini-
leading to excellent energy efficiency BMS/Centralized Controller that integrates
-- Indoor units with advanced sensing technology all units in a cost-efficient system
and optional self-cleaning air filter panel -- Easy integrating with third party BMS
»» In comfort -- Dedicated control solutions for applications
-- Variable Refrigerant Temperature such as offices, shops, hotels, schools, etc.
technology preventing cold droughts »» In system design
-- 13 different indoor unit types and 81 models -- User friendly sizing and selection software
-- Low sound indoor and outdoor units -- CAD drawings and Revit* families
»» In aesthetics -- Comprehensive engineering manuals
-- Stylish cassettes integrated in the ceiling »» In after market support
-- Ceiling suspended cassettes -- Nationwide field support organization
-- Elegant wall mounted units -- 50+ product training facilities in North America
»» In installation -- Dedicated tech support team
-- Automatic refrigerant charge function »» In reliability
-- Self-addressing control system after installation -- Refrigerant-cooled electronics in outdoor unit
-- VRV Configurator for simplified and -- Extensive testing before new units leave the factory
time saving commissioning -- Spare parts available in the US
-- Flexible connection possibilities for -- ISO 9001 compliant manufacturing
indoor and outdoor units
-- One of the best warranties** in the industry
Air-cooled South
»» Fast and easy to install — no need for
additional components
»» Low maintenance costs
»» Can be installed both outdoors and indoors
»» Up to 38 tons capacity for one system
Components:
Water-cooled
»» Suitable for multi-story and large buildings because
of the almost unlimited possibilities of water piping
»» Not affected by outdoor
temperature/climate conditions
»» Reduce CO2 emissions thanks to the
possibility of geothermal energy as a
renewable energy source
Components:
(Geothermal)
water loop
8 www.daikincomfort.com
OVERVIEW
Heat Recovery or Heat Pump?
Cooling Heating
Components:
Components:
1982 1987 1990 1991 1998 2003 2005 2007 2014 2017 2019
World’s first VRV system First inverter VRV World’s first R407C VRV 2nd generation New VRV T-Series
is developed auto addressing VRV water-cooled Water-Cooled
(no rotary or dip switches) technology
10 www.daikincomfort.com
OVERVIEW
Our quality control is based on the idea that the added value we give to
products is quality, and that this quality is what customers are buying.
And each Daikin employee constantly puts quality ahead of everything else.
IN
RG
OPTIMIZED
LL
easy to design, install, and VRV IV X adapts VRV to North American HVAC market needs
maintain, means that it is LIFE CYCLE by expanding the applications in which VRV can be leveraged to
E A SY
life cycle cost. AI VRV IV X is the industry's first 3-phase variable refrigerant flow
M
DE
NT O
A IN YT system with dual-fuel capability, after Daikin's launch of 1-phase
E AS
VRV LIFE™ in 2018. The new series is equipped with features
to optimize initial capital required on phased installations and
provides ease of service and maintenance.
VRV Heat Pump and Heat Recovery - Single, dual, and triple modules
CAPACITY - TONS
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
VRV IV Heat Pump
VRV IV X Heat
Recovery
12 www.daikincomfort.com
OVERVIEW
VRV IV X - Adapting VRV to North American market needs
Gas Furnace Connectivity
Expanding VRV into applications that were limited to
gas-based heating, VRV IV X is the first 3-phase dual-fuel
variable refrigerant flow system in North America that
integrates with communicating gas furnaces.
VRV IV X offers outstanding design flexibility when
connected to Daikin communicating 80%, 96%, and
97% AFUE gas furnaces and CXTQ coils. The new
VRV IV X enables the use of VRV technology to provide
utility cost based heating solutions. With the flexibility
to switch between electric heat pump heating and gas
heating, operational costs can be optimized to building
owner's choice for a heating source.
»» Space-saving with ability to connect multiple gas
furnaces to one outdoor unit with 14 selectable settings.
»» Customizable changeover temperatures to
switch from heat pump to gas heat.
»» Ability to provide system-wide heating independent
of outdoor ambient temperature.
Phased Installation
VRV IV X delivers enhanced design flexibility thanks to its ability »» Help reduce initial capital and design complexity
to expand with the building's phased construction. compared to systems that do not offer phased installation.
»» Expand the system from a single to a dual module or from dual »» Optimize piping design, branch selector boxes, and
to triple module without changes to main pipe sizes that are indoor units per phase of installation.
already installed.
CLOSED OPEN
CLOSED OPEN
Case study – Measured monthly energy usage for a VRV system without VRT and with VRT, installed in a European retail shop
VRT
5000 54% annual
Monthly energy usage (kWh)
Heating degree days and cooling degree days, that are Ambient air temperature
quantitative indications reflecting demand for energy to heat
86
or cool buildings, were the same for year 1 and year 2. Year 1 - Average max
Ambient air temperature (ºF)
32
14
Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb
14 www.daikincomfort.com
OVERVIEW
Fine control to match user preference available through mode selection
Basic mode is selected to maintain optimal comfort. VRT is selected to save energy and prevent excessive cooling.
Selecting VRT enables operation to be optimised for either energy efficiency or rapid cooling.
Floating Te Fixed Te
Reaction speed Very Fast Reaction speed Fast Reaction speed Medium Unable to change Te
» Can boost capacity above » Gives priority to fast » Gives priority to efficiency.
100% if needed. reaction speed. The refrigerant temperature goes
The refrigerant temperature The refrigerant temperature down gradually giving priority to
can go lower in cooling than goes down fast to keep the the efficiency of the system
the set minimum. room setpoint stable. instead of the reaction speed.
» Gives priority to very fast
reaction speed.
The refrigerant temperature
goes down fast to keep the
room setpoint stable.
*
In markets where cooling is dominant. VRT functionality
for heating operation improves the efficiency as well.
COOLING
75 F
60 F
A
AURORA Series Standard Operating Range
SIMULTANEOUS
B
HEATING
HEATING
23 F C
10 F D
-4 F
E
-13 F
-22 F
VIA technical cooling function
VIA extended capacity tables
Cooling operation for VRV IV Heat Pump single AIR-COOLED WATER-COOLED
module systems (RXYQ72/96/120/144/168T) can be PIPING
extended down to 10˚F, from the standard limitation LIMITATIONS VRV-IV VRV-IV / X VRV
of 23˚F under defined conditions. Liquid Line VRV IV-S VRV IV-S VRV IV-W
Heat Heat AURORA™ VRV T-Series
Contact your local Daikin manufacturer’s Max (ft) (3 Ton) (4 & 5 Ton) PC-Series
representative or distributor for details. Pump Recovery Low Ambient
80
E Linear
Standard Range
540 540 540 164 230 390 540
for Continuous
Operation Length
70
Total
Range 3280 3280 1640 820 984 980 980
60 for Network
Operation
50
1
Setting adjustment on condensing unit required.
*EWT Below 50˚F
2
Application rules apply. Refer to Installation Manual for further details.
Requires Antifreeze 3
Possible refrigerant noise can be mitigated (via setting adjustments on ODU) when linear length
40
exceeds 390 ft.
34
23*
20
14
50 59 70 80 82 90
Indoor Temperature (˚FWB)
*Limited to 27º F (for the PC series)
16 www.daikincomfort.com
OVERVIEW
Improved connection ratio flexibility
To properly match outdoor units with indoor units, VRV system
designers calculate the connection ratio.
Connection ratio 50%–200%*
If a system has more combined indoor unit capacity index
than combined outdoor unit capacity index, the result is a
combination ratio that is greater than 100%. If the outdoor unit
combined capacity index is higher than the index for indoor
units, the combination ratio is less than 100%. Total capacity index
Most Variable refrigerant flow system systems do not allow of the indoor units
Connection ratio =
the combination ratio to be more than 130%. However, due Total capacity index
to the advanced design of the Daikin VRV IV system, the of the outdoor units
connection ratio is in most cases allowed to be up to 200%.
18 www.daikincomfort.com
OVERVIEW
New efficient technology from Daikin
Automatic Automatic
sequencing sequencing
1 2 3 3 1 2 2 3 1
20 www.daikincomfort.com
OVERVIEW
With the VRV IV heat pump and heat recovery systems, the Daikin
brand is one of the most extensive lines of heating and cooling systems
in North America.
22 www.daikincomfort.com
OVERVIEW
VRV system configuration and commissioning
» The VRV configurator is an advanced software solution that » Multiple systems at different sites can be managed
allows for easy system configuration and commissioning. in exactly the same way, thus offering simplified
» Less time is required on the roof configuring the commissioning for key accounts.
outdoor unit. » Initial settings on the outdoor unit can be easily retrieved.
Simplified commissioning
* Complete warranty details available from your local Daikin manufacturer’s representative
or distributor or online at www.daikincomfort.com or www.daikinac.com.
24 www.daikincomfort.com
OVERVIEW
Installers Architects
Daikin VRV IV sets the standard with state-of-the-art »» Indoor units with a sleek and sophisticated design
technology and time-saving commissioning and servicing. »» Space efficient outdoor units
»» Simplified and time-saving commissioning with »» Low sound levels for both indoor and outdoor units
VRV configurator »» Wide range of indoor units to allow installation in
»» Unique range of single and multi Branch Selector boxes most environments
reduce installation time compared to previous generation
»» Wide range of outdoor units (up to 38 Tons for
heat recovery)
»» One supplier equals one point of contact
»» Maximum flexibility to meet customer requirements
»» Customized training to maximize expertise
26 www.daikincomfort.com
OVERVIEW
VRV for retail and restaurants VRV for schools
Our retail solutions offer: Our school solution offers:
»» Scalable project opportunities with modular design »» Flexible, scalable total HVAC solution for school classrooms,
»» Individual zone control for advanced zoning capabilities common areas and administrative offices
»» Enhanced efficiency in retail chain operations and energy »» Over 12,000 Daikin VRV systems in schools in
usage from Daikin's complete Building Management System North America
with Intelligent Touch Manager »» Quiet operating sound levels as low as 28 dB(A)
»» Centralized building control & autonomy from VRV remote »» Minimal occupant air temperature variations
commissioning and management capability »» Advanced zoning capabilities with user-friendly and
»» 10-Years Parts and Compressor Warranty* intuitive controls
»» Modular in design accommodating unique school and
classroom spaces
»» Self-cleaning filter option for Round Flow cassette simplifies
maintenance process and increases operational efficiency
»» Combined benefits of energy and operations efficiency
for both school administrators & maintenance staff
»» 10-Year Parts and Compressor Warranty*
*
Complete warranty details available from your local
Daikin manufacturer’s representative or distributor or
online at www.daikincomfort.com or www.daikinac.com.
Outdoor Units
Industry’s first 3-phase variable refrigerant »» Total comfort solution for heating,
flow system to integrate with communicating cooling, ventilation and controls
gas furnaces »» Energy efficiency values (IEER) up to 28.0
»» Equipped with Daikin’s patented inverter based »» Incorporates VRV IV standards and technologies such as
vapor-injection compressor to provide high variable refrigerant temperature and all inverter compressors
heating capacities down to -13°F WB »» Best-In-class warranty* with 10 year compressor
»» Enhanced design flexibility by allowing for phased and parts limited warranty as standard
installations with predefined pipe sizes and design rules »» Daikin VRV IV is the first variable refrigerant flow
»» New service window provides ease of access to the system to be assembled in North America.
multi-functional display without removing the main
electrical panel. The built-in multifunctional display
is utilized for commissioning and maintenance and Air-Cooled
quickly converts to digital gauges to provide refrigerant VRV IV-S systems are equipped with
pressure and temperatures. built-in intelligence which provide
independent zoning control with maximum
flexibility and energy savings. With the
VRV AURORA™ Heat Recovery & Heat Pump ability to connect up to ten indoor units
»» Variable refrigerant flow system Industry’s to one outdoor unit, the space-saving
first air-cooled system that delivers heating VRV IV-S system is ideal for most light
down to -22°F (-30°C) as standard commercial and residential applications.
»» Hot gas base pan circuit allows installation »» Available in 3, 4 and 5 ton modules
without an additional drain pan heater »» Increase in efficiency up to 18 SEER & 10.5+ HSPF
»» Designed to provide continuous heating »» Year round comfort and energy savings delivered
during defrost and oil return1 by VRT technology
»» Engineered with Daikin vapor injection compressor »» Broader diversity with ability to connect up to 9 indoor units
for optimized part load efficiencies
»» Space saving design with under 39”** height.
Over 25% smaller as compared to VRV III-S
Heat Recovery »» Easier to install with over 39% weight reduction vs VRV III-S
»» Fully integrated solution with heat »» Low sound levels for comfort
recovery offers high efficiencies »» Higher reliability with Daikin’s swing compressor
with IEER values up to 29.3 »» Dependable operation in extreme ambient conditions up to 122°F
»» Total comfort solution »» Added safety and peace of mind with optional
for heating, cooling, ventilation, and controls auto changeover to auxiliary heat
»» Outstanding warranty* with 10-Year Compressor »» Backed by a best in class 10-Year Parts Limited Warranty*
and Parts Limited Warranty as standard
»» Perfect personal comfort for guests / tenants via
simultaneous cooling and heating
VRV T-Series Water-Cooled Condensing
»» Incorporates VRV IV standards and technologies such as
variable refrigerant temperature and all inverter compressors Unit Heat Pump/Heat Recovery
»» Flexible System design with increased
»» Unique range of single and multi-port branch selector boxes
diversity up to 150%†
»» Heating function down to -13°F ambient air temperature
»» Can be applied to both geothermal and
»» Daikin VRV IV is the first variable refrigerant flow boiler/tower applications as standard with
system to be assembled in North America. condenser water inlet temperature as low as 14°F† in heating
and 23°F† in cooling is possible
»» Triple-stack capable to deliver up to 36 tons in just under
11.5 feet ceiling height thanks to the compact design
»» Engineered with heat rejection cancellation technology†
to eliminate mechanical room conditioning requirements
1
Multi module heat recovery systems only for continuous heating during defrost »» 2-9V variable water flow control logic† as standard to
†
Conditions/rules apply. Refer to Installation and Engineering Manual for
further details. increase waterside system operational efficiencies
* Complete warranty details available from your local Daikin manufacturer’s »» Drop-down switch box for easy service to key components
representative or distributor or online at www.daikincomfort.com or
www.daikinac.com. »» Field selectable top or front refrigerant connections for
** Varies based on condensing unit model selected flexible and easy installation
30 www.daikincomfort.com
CAPACITY (TONS)
TYPE MODEL FEATURES PRODUCT NAME
3 4 5 6 8 10 12 14 16 18 20 21 22 24 26 28 30 32 34 36 38
»» Industry’s first 3-phase variable refrigerant flow system REYQ_X
system to integrate with communicating gas furnaces n n n n n
»» Equipped with Daikin’s patented inverter based
vapor-injection compressor to provide high
heating capacities down to -13°F WB
VRV IV X Heat Recovery
n n n n n n n
»» Enhanced design flexibility by allowing for
phased installations with predefined pipe
sizes and design rules
»» New service window provides ease of access
to the multi-functional display without
PRODUCT PORTFOLIO
removing the main electrical panel. The
n n n n n
built-in multifunctional display is utilized for
commissioning and maintenance and quickly
converts to digital gauges to provide refrigerant
pressure and temperatures.
n n n
n ** n n n
»»Enables use of geothermal energy as a renewable
energy source
Heat Recovery / Heat Pump
Indoor Units
(Single flow) »» The indoor unit can be set to 5 predetermined fan speeds which allows for optimum and comfortable airflow
»» Factory installed condensate pump with a lift capacity of up to 33- 7⁄16" (measured from the bottom of the unit)
32 www.daikincomfort.com
CAPACITY
MBH 5.8 7.5 9.5 12 15 18 24 30 36 42 48 54 60 72 96
TON 0.5 0.6 0.75 1 1.25 1.5 2 2.5 3 3.5 4 4.5 5 6 8
PRODUCT PORTFOLIO
n n n n n n n n n n
n n n n n n n n n n n
n n n n n
n n n n n n n n n
n n
n n n n n
n n n n n n n n n
n n n n n
n n n n n n
n n n n n n
n n n
n n n n n
n n n n n
Accessories
Branch Selector Boxes
Providing flexibility and minimizing mechanical and electrical installation costs, Daikin's branch selector boxes that are used
PRODUCT PORTFOLIO
in Heat Recovery systems, are ideal for spaces that require individual heating and cooling control.
REFNET
REFNET joints distribute correct flow of refrigerant
in every branch of the piping network.
VRV IV Heat Pump / VRV AURORA™ Heat Pump REFNET Joint REFNET Header
RXYQ192T RXYQ312T
RXYQ72T RXYQ120T
RXYQ216T RXYQ336T RXYQ360T
RXYQ96T RXYQ144T
OPTIONAL ACCESSORIES RXYQ240T RXLQ144T RXYQ384T
RXLQ72T RXYQ168T
RXYQ264T RXLQ192T RXYQ408T
RXLQ96T RXLQ120
RXYQ288T RXLQ240T
KHRP26M22H (max. 4 branch)
KHRP26M22H (max. 4 branch)
KHRP26M22H (max. 4 branch) KHRP26M33H (max. 8 branch)
Distributed REFNET Header KHRP26M33H (max. 8 branch)
KHRP26M33H (max. 8 branch) KHRP26M72H (max. 8 branch)
piping KHRP26M72H (max. 8 branch)
KHRP26M73H (max. 8 branch)
REFNET Joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26M72TU KHRP26A22T, KHRP26A33T, KHRP26M72TU, KHRP26M73TU
Outdoor unit multi connection piping kit — BHFP22P100U BHFP22P151U
VRV IV X Heat Recovery / VRV IV Heat Recovery / VRV AURORA™ Heat Recovery
REYQ192T
REYQ216T REYQ360T
REYQ72T REYQ120T REYQ240T REYQ384T
REYQ144T REYQ264T REYQ408T
REYQ96T REYQ168T REYQ288T REYQ432T
RELQ72T REYQ312T REYQ456T
REYQ336T RELQ144T
OPTIONAL ACCESSORIES RELQ96T RELQ120T RELQ192T
REYQ192X RELQ240T
REYQ216X REYQ360X
REYQ120X REYQ240X REYQ384X
REYQ72X
REYQ144X REYQ264X REYQ408X
REYQ96X
REYQ168X REYQ288X REYQ432X
REYQ312X REYQ456X
REYQ336X
34 www.daikincomfort.com
VRV T-Series Water-Cooled Heat Pump / Heat Recovery and VRV-IV-S
PRODUCT PORTFOLIO
VRV T-SERIES WATER-COOLED VRV-IV-S
UNIT MODEL RWEQ192,216,240,
RXTQ36TAVJ9
NUMBER RWEQ96TATJU RWEQ120TATJU RWEQ144TATJU 264,288TATJU RWEQ312,336,360TATJU
RXTQ48TAVJU
RWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ192,216,240, RWEQ312,336,360TAYDU
RXTQ60TAVJU
264,288TAYDU
KHRP26M22H9 (Max 4 branch),
Heat KHRP26M22HR (Max 4 branch) KHRP26M22H9 (Max 4 branch), KHRP26M33H9 (Max 8 branch) KHRP26M22H9 (Max. 4 branch)
KHRP26M33H9 (Max 8 branch)
Pump KHRP26M33H9 (Max 8 branch) KHRP26M72H9 (Max 8 branch), KHRP26M73HU9 (Max 8 branch) KHRP26M33H9 (Max. 8 branch
REFNET KHRP26M72H9 (Max 8 branch)
Header
Heat KHRP25M33H9 (Max 8 branch) KHRP25M33H9 (Max 8 branch), KHRP25M72H9 (Max 8 branch)
KHRP26M33H9 (Max 8 branch) __
Recovery KHRP25M72H9 (Max 8 branch) KHRP25M73HU9 (Max 8 branch)
Heat
KHRP26A22T9, KHRP26A33T9 KHRP26A22T9, KHRP26A33T9, KHRP26M72TU9 KHRP26A22T9, KHRP26A33T9, KHRP26A72UT9, KHRP26M73TU9 KHRP26A22T9
REFNET Pump
Joint
Heat
KHRP25A22T9, KHRP25A33T9 KHRP25A22T9, KHRP25A33T9, KHRP25M72TU9 KHRP25A22T9, KHRP25A33T9, KHRP25A72TU9, KHRP25M73TU9 __
Recovery
Outdoor Heat
__ BHFP22T84U BHFP22T126U __
Unit Multi Pump
Piping
Connection Heat
__ BHFP26T84U BHFP26T126U __
Kit Recovery
Accessories (continued)
DZK (Daikin Zoning Kit)
The optional DZK increases the flexibility of the Daikin VRV and SkyAir systems in both residential and
commercial applications by adding a Zoning Box to an indoor unit fan coil, allowing several separate
PRODUCT PORTFOLIO
ducts to supply air to different individually controlled zones. The DZK BACnet® Interface module will
work with any BACnet/IP compatible Building Management System.
intelligent
DKN Cloud Navigation™ Simplified intelligent Touch BACnet® LonWorks® Modbus®
Wi-Fi Adaptor Remote Controller Remote Controller Touch Controller ™ Manager ™ Interface Interface Interface
Individual zone control n n n
Independent cool and heat setpoints n n n n
Individual zone control with weekly n n n n
programmable scheduling
Basic central point on/off control of all air handling units n n n n n n
Advanced multi-zone control of small to n n n n n
medium size projects
Advanced multi-zone control of large n n n n
commercial projects
Advanced multi-zone control with n n
scheduling logic and calendar
Automatic cooling/heating changeover n n
for heat pump systems
Single input batch shutdown of all n n n n n
connected air handlers
Web browser control and monitoring n n n n n
via Intranet and Internet
E-mail notification of system alarms and n n n n n
equipment malfunctions
Multiple tenant power billing for shared n n
condenser applications
Temperature set-point range restrictions n n n n n
Graphical user interface with floor plan layout n n n n
Start/stop control of ancillary building systems* n n n n n
Daikin VRV integration with BACnet n n
based automation systems
Daikin VRV integration with LonWorks n
based automation systems
Daikin VRV integration with Modbus n
based automation systems
Wi-Fi option remote access through smartphone app n
*
Requires one or more DEC102A51-US2 Digital Input/Output units or WAGO ® IO module (for use with iTM only).
n Native application or feature for this device. n Dependent upon capabilities of the third party energy management system
36 www.daikincomfort.com
The configurable display and operation buttons on the Navigation™
Remote Controller will provide as much or as little control as the
PRODUCT PORTFOLIO
installed VRV system requires.
Accessories (continued)
Network solutions
PRODUCT PORTFOLIO
Layout screen n
Screen
Touch screen n n
Mini BMS for heating, air conditioning applied systems n
Integration and refrigeration units (BACnet and WAGO)
3rd party equipment integration (BACnet and WAGO) n
Basic control functions: on/off, set point setting, n n n n n
air flow settings, operation mode
Temperature limitation n n
Setback n
Control Automatic changeover n n
Weekly schedule and special day pattern n n
Timer extension n
Forced off n n n n
Interlock n n
Basic control functions: ON/OFF status, n n n n n
operation mode, set point temp.
Filter status n n n n n
Monitoring Malfunction code n n n n n
History (operation, malfunction…) n n
History (Indoor and outdoor unit operation data) n
Visualization n n
PPD (Power Proportional Distribution) n n
Web access and control n Std
HTTP option n
Options BACnet Client n
BACnet Server n
D-Net Service n n
Operation Data n
Powerful Service Tool with Indoor and Outdoor Unit Operation Data Points
38 www.daikincomfort.com
Air treatment systems
Daikin’s Outside Air Processing Unit can combine fresh air consumption. This is achieved by providing fresh outside air
PRODUCT PORTFOLIO
treatment and air conditioning, supplied from a single system. and recovering waste heat from exhaust air leaving the
conditioned space.
The compact Energy Recovery Ventilator is designed to improve
indoor air quality while reducing the overall HVAC system power
As many as 64 separate indoor units can be connected to a refrigerant circuit with a single outdoor
unit of up to 38 tons capacity. The Daikin VRV indoor unit range is one of the widest on the market,
offering no less than 13 stylish and elegant indoor units types in 81 different models — all designed
to maximize comfort, minimize operating sound and simplify installation and servicing.
Indoor unit models include Round Flow ceiling mounted (user adjustable), leading to yearly energy savings of up to 50%.
cassette, ceiling concealed ducted, ceiling suspended, wall Dust from the filter is collected in the unit for easy and quick
mounted and floor standing models. removal (when indicated) with a standard vacuum cleaner.
The Round Flow sensing cassette now includes an Designed to fit rooms of any size and shape, Daikin indoor units
optional variable refrigerant flow system industry first are also user friendly, ultra reliable, easy to control and quiet
self-cleaning filter, which automatically cleans itself daily in operation.
42 www.daikincomfort.com
CAPACITY
INDOOR UNIT TYPE MBH 5.8 7.5 09 12 15 18 24 30 36 42 48 54 60 72 96
TONS 0.5 0.6 0.75 1 1.25 1.5 2 2.5 3 3.5 4 4.5 5 6 8
FXMQ_PBVJU
HSP DC Concealed Ducted Unit
FXSQ_TAVJU
MSP Concealed Ducted Unit
INDOOR UNITS
FXDQ_MVJU
LSP Slim Concealed Ducted Unit
DUCTED
FXTQ_TAVJU
Multi-Position Air Handling Unit
(Upflow, Downflow, Horizontal Left
and Horizontal Right)
FXMQ_MVJU
HSP High Capacity Concealed
Ducted Unit
FXNQ_MVJU9 Concealed
Floor- Standing Unit
FXFQ_TVJU
Round Flow Sensing Cassette,
Ceiling Mounted
FXUQ_PVJU
4-Way Blow
Ceiling-Suspended Cassette
FXZQ_TAVJU
VISTATM 2x2 Cassette for VRV
DUCT-FREE
FXEQ_PVJU
Ceiling-Mounted Cassette
(Single Flow)
FXHQ_MVJU
Ceiling-Suspended Unit
FXAQ_PVJU
Wall-Mounted Unit
FXLQ_MVJU9
Floor-Standing Unit
FXMQ_PBVJU FXMQ_MVJU
HSP DC Concealed Ducted Unit HSP High Capacity Concealed Ducted
Ceiling mounted DC-Ducted Ideal unit for larger open
unit — ideal for small to large space floor plans usually
spaces in need of a concealed found in offices, retails,
air-conditioning system. hotels or education facilities.
INDOOR UNITS
FXSQ_TAVJU FXTQ_TAVJU
MSP Concealed Ducted Multi-Position Air Handling Unit
Ducted unit with compact Vertical air handling unit ideal
design and powerful static for both residential and light
pressure capabilities. commercial applications.
It has upflow,
downflow,
horizontal
left and
horizontal right
possibilities.
FXDQ_MVJU FXNQ_MVJU9
LSP Slim Concealed Ducted Unit Concealed Floor-Standing Unit
Slim duct built-in concealed Floor-standing unit that can
unit with low profile and low easily be installed along a
sound level. perimeter wall — or concealed
FXLQ_MVJU9
Floor-Standing Unit
Great way to save space.
The floor-standing units can
easily be installed along a
perimeter wall.
44 www.daikincomfort.com
FXFQ_TVJU FXZQ_TAVJU
Round Flow Sensing Cassette, Ceiling Mounted VISTATM 2x2 Cassette for VRV
Ideal for open plan applications 2'x2' 4-way Cassette best
such as classrooms and for open plan applications
offices where adaptive such as classrooms, offices
comfort control is preferred. and retail.
Provides excellent comfort
level, energy efficiency, and
flexibility due to advanced
INDOOR UNITS
control functions.
FXUQ_PVJU FXEQ_PVJU
4-Way Blow Ceiling-Suspended Cassette Ceiling-Mounted Cassette (Single Flow)
Perfect solution for rooms Slim and compact design
without a false ceiling, or for installation flexibility.
minimal space above a false For hotel rooms, offices
ceiling, where adaptive and residential.
comfort control is preferred.
FXAQ_PVJU FXHQ_MVJU
Wall-Mounted Unit Ceiling-Suspended Unit
Unit ideal for cooling or Ceiling-suspended with slim
heating smaller zones and elegant design.
such as stores, offices and
restaurants. Compact and
stylish design.
Ducted Unit
Integration Possible
»» Offices
»» Hotels
»» Schools
»» Retail
46 www.daikincomfort.com
FXMQ_PBVJU
0.6 Ton 0.75 Ton 1.0 Ton 1.25 Ton 1.5 Ton 2.0 Ton 2.5 Ton 3.0 Ton 4.0 Ton 4.5 Ton
SPECIFICATIONS
Model Name FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling
BTU/h 7,500 9,500 12,000 15,000 18,000 24,000 30,000 36,000 48,000 54,000
Capacity
Rated Heating
BTU/h 8,500 10,500 13,500 17,000 20,000 27,000 34,000 40,000 54,000 60,000
Capacity
Airflow Rate
CFM 317/264/229 450/410/388 560/530/500 635/582/529 688/618/565 1,094/953/812 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
(H/M/L)
Height in. 11-3/16
Width in. 21-5/8 27-9/16 39-3/8 55-1/8
Depth in. 27-9/16
Weight lbs. 55 (25) 62 (28) 80 (36) 102 (46) 104 (47)
Condensate
in. 18-3/8
Pump Lift
Sound Pressure
dB(A) 33/31/29 39/37/35 40/38/37 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(H/M/L)
Condensate Pipe
in. O.D. 1-1/4
Connection
Pipe Gas in. 1/2 (Flare) 5/8 (Flare)
Connections Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum
INDOOR UNITS
Overcurrent A 15
Protective Device
Minimum
A 0.6 1.4 1.5 1.6 1.8 2.8 2.9 3.4
Circuit Amps
Protection Devices Fuse and Fan Driver Overload Protector
External Finish Galvanized Steel Plate
External Static
in. Wg 0.40/0.12 0.80/0.20 0.56/0.20
Pressure (H/L)
MERV 13 Filter Kit Option contains a MERV 13 filter, adaptor frame and easy to follow ENTHALPY ECONOMIZER (FIELD APPLIED ACCESSORY)
installation instructions and can be installed on the following models only: Model Indoor Unit
Kit Model Indoor Unit ECONMQ12P-8-1K (MERV 8 Filter)
DACA-FXMQ12131K FXMQ07-09PBVJU FXMQ07-09PBVJU
ECONMQ12P-13-1K (MERV 13 Filter)
DACA-FXMQ14131K FXMQ12PBVJU ECONMQ30P-8-1K (MERV 8 Filter)
DACA-FXMQ30131K FXMQ15-24PBVJU ECONMQ30P-13-1K (MERV 13 Filter) FXMQ15-24PBVJU
DACA-FXMQ48131K FXMQ30-54PBVJU ECONMQ48P-8-1K (MERV 8 Filter)
ECONMQ48P-13-1K (MERV 13 Filter) FXMQ30-54PBVJU
FXMQ_PBVJU ACCESSORIES
Model Name FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJU
Navigation™ Remote
BRC1E73
Controller*
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired
BRC2A71
Remote Controller*
Wireless Remote
BRC4C82
Controller
Remote Sensor Kit KRCS01-4B
Wiring Adaptor PCB
(interface with aux/
KRP1C74
primary heater, humidifier,
OA damper/fan)
Group Control Adaptor
PCB (connects to KRP4A71
external BMS)
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
99" or more
if no ceiling
if no ceiling
Ceiling Ceiling
Ducted Unit
Integration Possible
Applications
»» Offices
»» Hotel Rooms
»» Multi-family
residences
»» Single-family
residences
»» Schools
48 www.daikincomfort.com
SPECIFICATIONS 0.5 TON 0.6 TON 0.75 TON 1.0 TON 1.25 TON 1.5 TON
Model Name FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJU FXSQ18TAVJU
Capacity Index 5.8 7.5 9.5 12 15 18
Power Supply V/ph/Hz 208/230VAC, 60Hz, 1 phase
Nominal Cooling Capacity*1 Btu/h (kW) 5,800 (1.7) 7,500 (2.2) 9,500 (2.8) 12,000 (3.6) 15,000 (4.5) 18,000 (5.6)
Nominal Heating Capacity*2 Btu/h (kW) 6,500 (1.9) 8,500 (2.5) 10,500 (3.1) 13,500 (4.0) 16,500 (5.6) 20,000 (6.3)
Type Sirocco fan
Motor Output W 78 130 230
Air Flow Rate (H/M/L) CFM 281 / 265 / 230 318 / 265 / 230 335 / 283 / 247 530 / 441 / 371 600 / 512 / 406
Fan
Drive Type DC Direct Drive
External Static
0.2 / 0.6 0.4 / 0.6
Pressure (Std./Max)
Height in. 9-11/16
Width in. 21-11/16 27-9/16 39-3/8
Depth in. 31-1/2
Weight lb. 55 (25) 60 (27) 77 (35)
Condensate Pump Lift in. 25-5/16 (643)
Sound Pressure Level (H/M/L speed) dB(A) 33 / 30 / 28 34 / 32 / 30 36 / 33 / 30 34 / 32 / 29
Liquid in. 1/4 (Flare)
Pipe
Gas in. 1/2 (Flare)
Connections
Condensate Drain in. VP25
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protection Device A 15
Minimum Circuit Ampacity A 0.8 1.4 1.6
INDOOR UNITS
SPECIFICATIONS 2.0 TON 2.5 TON 3.0 TON 4.0 TON 4.5 TON
Model Name FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJU
Capacity Index 24 30 36 48 54
Power Supply V/ph/Hz 208/230VAC, 60Hz, 1 phase
Nominal Cooling Capacity*1 Btu/h (kW) 24,000 (7.1) 30,000 (9.0) 36,000 (11.2) 48,000 (14.0) 54,000 (15.8)
Nominal Heating Capacity*2 Btu/h (kW) 27,000 (8.0) 34,000 (10.0) 40,000 (11.7) 54,000 (16.0) 60,000 (17.6)
Type Sirocco fan
Motor Output W 230 300 350
Air Flow Rate (H/M/L) CFM 742 / 618 / 512 812 / 689 / 565 1130 / 953 / 795 1307 / 1112 / 918 1377 / 1183 / 989
Fan
Drive Type DC Direct Drive
External Static
0.4 / 0.6 0.4 / 0.56
Pressure (Std./Max)
Height in. 9-11/16
Width in. 39-3/8 55-1/8 61
Depth in. 31-1/2
Weight lb. 82 (37) 101 (46) 104 (47) 115 (52)
Condensate Pump Lift in. 25-5/16 (643 mm)
Sound Pressure Level (H/M/L speed) dB(A) 36 / 32 / 29 37.5 / 34 / 30 39 / 35 / 32 42 / 38.5 / 35 43 / 40 / 36
Liquid in. 3/8 (Flare)
Pipe
Gas in. 5/8 (Flare)
Connections
Condensate Drain in. VP25
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protection Device A 15
Minimum Circuit Ampacity A 1.8 2.5 2.8 3.3
Note: *1 Nominal cooling capacities are based on the following conditions: 80 °FDB / 67 °FWB (26.7 °CDB / 19.4 °CWB) return air temperature;
95 °FDB (35 °CDB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
*2
Nominal heating capacities are based on the following conditions: 70 °FDB (21.1 °CDB) return air temperature;
47 °FDB / 43 °FWB (8.3 °CDB / 6.1 °CWB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
FXSQ
Air Air
Outlet Inlet
99" or more
if no ceiling
Ducted Unit
Integration Possible
Filter
Included
Applications
»» Hotel rooms
»» Multi-family
residences
»» Single family
residences
»» School dormitories
50 www.daikincomfort.com
FXDQ_MVJU SPECIFICATIONS 0.6 TON 0.75 TON 1 TON 1.5 TONS 2 TONS
Model Name FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 7,500 9,500 12,000 18,000 24,000
Rated Heating Capacity BTU/h 8,500 10,500 13,500 20,000 27,000
Airflow Rate (H/L) CFM 280/226 440/350 580/460
Weight lbs. 51 63 71
Height in. 7-7/8
Width in. 27-9/16 35-7/16 43-5/16
Depth in. 24-7/16
Sound Pressure (H/L) dB(A) 33/29 35/31 36/32
Condensate Pump Lift in. 21-5/8
Condensate Pipe Connection in. O.D. 1-1/32
Gas in. 1/2 (Flare) 5/8 (Flare)
Pipe Connections
Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device A 15
Minimum Circuit Amps A 0.9 1.3 1.4
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish Galvanized Steel Plate
Standard Filter Type Removable, Washable, Mildew Proof
External Static Pressure (H/L) in. Wg 0.12/0.04 0.17/0.06 0.17/0.06
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
INDOOR UNITS
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXDQ_MVJU ACCESSORIES
Model Name FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC4C82
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater,
KRP1C75
humidifier, OA damper/fan)
Group Control Adaptor PCB (connects to external BMS) KRP4A74
Access Panel (single door) APFXDQ070912 APFXDQ18 APFXDQ24
Access Panel with return air filter (single door) APRFFXDQ070912 APRFFXDQ18 APRFFXDQ24
Filter Media Replacement APRFFXDQ070912F APRFFXDQ18F APRFFXDQ24F
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
Protection net
Air inlet
12" 12"
or more or more Chamber lid
Control Box
Protection net
H = 9-1/2"
Air inlet
7-7/8"
or more
13/16" or more
100"or more
Chamber lid
Chamber lid Protection net
Ceiling
Floor surface
(length : in.) Air inlet
AI
Integration Aluminum
Multi-Position Possible
Variable
Coil
Applications
Electric Heater Options
»» Multi-family
ELECTRICAL HEATER CAPACITY
»» Single-family
Model Name 3kW 5kW 6kW 8kW 10kW 15kW 19kW 20kW 25kW
»» Hotels
FXTQ09TAVJUA(D) n n
»» Offices FXTQ12TAVJUA(D) n n n
FXTQ18TAVJUA(D) n n n n n
FXTQ24TAVJUA(D) n n n n n
FXTQ30TAVJUA(D) n n n n n
FXTQ36TAVJUA(D) n n n n n
FXTQ42TAVJUA(D) n n n n n n
FXTQ48TAVJUA(D) n n n n n n
FXTQ54TAVJUA(D) n n n n n n n
FXTQ60TAVJUA(D) n n n n n n n
52 www.daikincomfort.com
SPECIFICATIONS 0.75 TON 1 TON 1.5 TON 2 TON 2.5 TON
Model Name FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUA
Model Name (With factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD
Power Supply V/ph/Hz 208/230VAC, 60Hz, 1 phase
Nominal Cooling Capacity*1 Btu/h 9,500 12,000 18,000 24,000 30,000
Nominal Heating Capacity*2 Btu/h 10,500 13,500 20,000 27000 34,000
Type Sirocco FC Centrifugal
Motor Output HP 1/2
Fan Air Flow Rate (H/M/L CFM 300 / 275 / 250 400 / 340 / 280 600 / 510 / 420 800 / 680 / 560 1000 / 850 / 700
Static Pressure*3 in. Wg 0.18” / 0.9” 0.23” / 0.9”
Drive Type Variable speed ECM
Height in. 45
Width in. 17.5
Depth in. 21
Weight (net) (TAVJUA/TAVJUD) lbs. 105/108 112/115 111/118 112/115 113/116
Sound Pressure Level (H speed) dB(A) 36 45 52
Liquid in. 1/4 (Braze) 3/8 (Braze)
Pipe
Gas in. 1/2 (Braze) 5/8 (Braze)
Connections
Condensate Drain in. 3/4 (fpt)
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent
A 15
Protective Device
Minimum Circuit Amps A 4.9
INDOOR UNITS
SPECIFICATIONS 3 TON 3.5 TON 4 TON 4.5 TON 5 TON
Model Name FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUA
Model Name (With factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD
Power Supply V/ph/Hz 208/230VAC, 60Hz, 1 phase
Nominal Cooling Capacity*1 Btu/h 36,000 42,000 48,000 54,000 60,000
Nominal Heating Capacity*2 Btu/h 40,000 46,000 54,000 60,000 66,000
Type Sirocco FC Centrifugal
Motor Output HP 1/2 3/4 1.0
Fan Air Flow Rate (H/M/L CFM 1050 / 900 / 750 1400 / 1190 / 980 1520 / 1290 /1060 1800 / 1530 / 1260 1800 / 1530 / 120
Static Pressure*3 in. Wg 0.23” / 0.9” 0.28” / 0.9”
Drive Type Variable speed ECM
Height in. 45 53.43 58
Width in. 17.5 21 24.5
Depth in. 21
Weight (net) (TAVJUA/TAVJUD) lbs. 113/116 144/147 165/168
Sound Pressure Level (H speed) dB(A) 52 54 50
Liquid in. 3/8 (Braze)
Pipe
Gas in. 5/8 (Braze)
Connections
Condensate Drain in. 3/4 (fpt)
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent
A 15
Protective Device
Minimum Circuit Amps A 4.9 6.5 8.6
*1
Nominal cooling capacities are based on the following conditions: 80 °FDB / 67 °FWB (26.7 °CDB / 19.4 °CWB) return air temperature;
95 °FDB (35 °CDB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
*2
Nominal heating capacities are based on the following conditions: 70 °FDB (21.1 °CDB) return air temperature;
47 °FDB / 43 °FWB (8.3 °CDB / 6.1 °CWB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
*3
External static pressures are indicated as rated / maximum allowable range.
Applications
»» Hotel/conference
centers
»» Schools
»» Retail/shopping
centers
»» Large open-plan
offices
»» Churches
54 www.daikincomfort.com
FXMQ_MVJU SPECIFICATIONS 6 TON 8 TON
Model Name FXMQ72MVJU FXMQ96MVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 72,000 96,000
Rated Heating Capacity BTU/h 81,000 108,000
Airflow Rate (H/L) CFM 2,047/1,764 2,541/2,188
Weight lbs. 380
Height in. 18-1/8
Width in. 54-3/8
Depth in. 43-5/16
Sound Pressure (H/L) dB(A) 48/45
Condensate Pipe Connection in. O.D. 1
Gas in. 3/4 (Flare) 7/8 (Flare)
Pipe Connections
Liquid in. 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device A 15
Minimum Circuit Amps A 9.5 10.7
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish Galvanized Steel Plate
External Static Pressure (Nominal/Maximum) in. Wg 0.38/0.95 0.43/1.1
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
INDOOR UNITS
Level Difference: 0 ft. Level Difference: 0 ft.
FXMQ_MVJU ACCESSORIES
Model Name FXMQ72MVJU FXMQ96MVJU
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC4C82
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater, humidifier, OA damper/fan) KRP1C74
Group Control Adaptor PCB (connects to external BMS) KRP4A71
High Efficiency Filter Kit (MERV 13) DACA-MQ96M-13-1K
High Efficiency Filter Kit (MERV 8) DACA-MQ96M-8-1K
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
99" or more
if no ceiling
if no ceiling
Ceiling Ceiling
Floor-Standing Unit
Included
Applications
»» Multi-family
residences
»» Single-family
residences
»» Churches
»» Historic buildings
»» Schools
»» Offices
56 www.daikincomfort.com
FXNQ_MVJU9 SPECIFICATIONS 0.6 TON 0.75 TON 1 TON 1.5 TON 2 TON
Model Name FXNQ07MVJU9 FXNQ09MVJU9 FXNQ12MVJU9 FXNQ18MVJU9 FXNQ24MVJU9
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 7,500 9,500 12,000 18,000 24,000
Rated Heating Capacity BTU/h 8,500 10,500 13,500 20,000 27,000
Airflow Rate (H/L) CFM 245/210 280/210 490/380 560/420
Weight lbs. 47 56 60
Height in. 24
Width in. 36-5/8 42-1/8 53-1/8
Depth in. 8-5/8
Sound Pressure (H/L) dB(A) 35/32 36/33 40/35 41/36
Condensate Pipe Connection in. O.D. 27/32
Gas in. 1/2 5/8
Pipe Connections
Liquid in. 1/4 3/8
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent
A 15
Protective Device
Minimum Circuit Amps A 0.3 0.5 0.6
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish Galvanized Steel Plate
Standard Filter Type Resin Net (with Mold Resistant)
INDOOR UNITS
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXNQ_MVJU9 ACCESSORIES
Model Name FXNQ07MVJU9 FXNQ09MVJU9 FXNQ12MVJU9 FXNQ18MVJU9 FXNQ24MVJU9
Navigation™ Remote Controller BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC4C82
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater, humidifier, OA damper/fan) KRP1C74
Group Control Adaptor PCB (connects to external BMS) KRP4A71
Condensate Pump DACA-CP3-1
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
Air inlet
24-5/8"
direction
Base Maintenance
area
3-1/8" or more
IMPORTANT
Leave sufficient clearance for air inlet and maintenance. Ao
r
B o mor
MODEL A (IN.) B (IN.) rm e
FXNQ12MVJU9 28 46 ore
FXNQ18 - 24MVJU9 39 57
FXNQ07-09MVJU 23 41
Sensing Cassette
Integration Possible Sensor Kit as Standard
Filter
Included
Much fewer
Areas of uneven areas of uneven
temperature temperature
58 www.daikincomfort.com
Advanced design for comfort and efficiency
INDOOR UNITS
Enables additional energy Decoration Panel
savings and increased comfort
»» Efficient due to large air
Optional Self-Cleaning discharge outlets
Filter Panel »» Unique 360° airflow
distribution
Provides optimum efficiency, airflow
and reduced maintenance »» 4 individually controlled
louvers enables optimized
comfort in the space
»» Possibility to close 1, 2 or 3
louvers adds flexibility
Air flow from the indoor unit is automatically adjusted to always maintain
a comfortable environment — even when occupancy changes.
Filter
Sensor Kit as Standard
Included
Air filter
INDOOR UNITS
Air filter
brush
At the programmed time, the air filter rotates while the air filter
brush turns back and forth to brush the filter.
Dust from the air filter brush is deposited into the dust collection
container during the fully automatic self-cleaning process.
60 www.daikincomfort.com
FXFQ_TVJU SPECIFICATIONS 0.60 TON 0.75 TON 1 TON 1.25 TON 1.5 TON 2 TON 2.5 TON 3 TON 4 TON
Model Name FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJU FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJU
Power Supply (V/ph/Hz) 208-230/1/60
Rated Cooling Capacity BTU/h 7,500 9,500 12,000 15,000 18,000 24,000 30,000 36,000 48,000
Rated Heating Capacity BTU/h 8,500 10,500 13,500 17,000 20,000 27,000 34,000 40,000 54,000
Airflow Rate (H/M/L) CFM 420/406/353 441/406/353 441/406/353 512/459/388 742/618/477 777/618/477 1,112/918/671 1,165/918/671 1,218/971/742
Weight lbs. 48 48 58
Height in. 9-11/16 11-5/16
Width in. 33-1/16
Depth in. 33-1/16
Sound Pressure (H/M/L) dB(A) 30/28.5/27 31/29/27 35.5/32/28 36/32/28 43.5/38/32 44/38/32 45/40/35
Condensate Pump Lift in. 33-1/2
Condensate Pipe Connection in. O.D. 1-1/4
Pipe Gas in. 1/2 (Flare) 5/8 (Flare)
Connections Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent
A 15
Protective Device
Minimum Circuit Amps A 0.3 0.4 0.6 0.7 1.3 1.5 1.8
Protection Devices Fuse/Breaker and Fan Motor Thermal Protector
External Finish Galvanized Steel Plate
Standard Filter Type Mold-Resistant Resin Net
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
INDOOR UNITS
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
Exhaust
Exhaust
Indoor unit
Indoor unit Lighting fan Indoor unit
Indoor unit
fan
At least 60" from any fixture
60" or (A) 60
more from more
a wall 60" or more aw
80" or more
160" or more
charge Discharge Suction Discharge
At least 70"
from a floor
Airflow Angles
Applications Auto Swing: Wide discharge angle: 0° to 60°
»» Retail
»» Schools 0° 0°
»» Offices
»» Restaurants
60° 60°
0° 0°
60° 60°
62 www.daikincomfort.com
FXUQ_PVJU SPECIFICATIONS 1.5 TON 2 TON 2.5 TON 3 TON
Model Name FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJU
Power Supply (V/ph/Hz) 208-230/1/60
Rated Cooling Capacity BTU/h 18,000 24,000 30,000 36,000
Rated Heating Capacity BTU/h 20,000 27,000 34,000 40,000
Airflow Rate (H/M/L) CFM 795/689/565 1095/918/742
Weight lbs. 58 60
Height in. 7-13/16
Width in. 37 3/8
Depth in. 37 3/8
Sound Pressure (H/M/L) dB(A) 40/38/36 47/44/40
Condensate Pump Lift in. 19.5
Condensate Pipe Connection in. O.D. VP20
Pipe Gas in. 1/2 (Flare) 5/8 (Flare) 5/8 (Flare)
Connections Liquid in. 1/4 (Flare) 3/8 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device A 15
Minimum Circuit Amps A 0.6 1.4
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish White Casing
Standard Filter Type Resin Net (with Mold Resister)
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
INDOOR UNITS
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXUQ_PVJU ACCESSORIES
Model Name FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJU
Sealing Member of Air Discharge Outlet KDBHP49B140
Decoration Panel for Air Discharge KDBTP49B140
Replacement Long-Life Filter KAFP551K160
Remote Control (wired type) BRC1E73
Sensor Kit 2 BRE49B1F
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Group Control Adaptor Printed Circuit Board1 KRP4A74
Installation Box for Adaptor PCB KRP1BA97
Remote Sensor 2 KRCS01-48
¹ Installation box for Adaptor PCB (KRP1BA97) is necessary. ² Remote Sensor can only be installed when Sensor Kit is not installed.
13/16"
7-13/16"
2-1/4"
100" or more
(Required space)
Air-flow from the indoor unit is automatically adjusted to always maintain a comfortable environment — even when occupancy changes.
Designer Comfort
VISTA ™ is a remarkable blend of iconic design and
engineering excellence with an elegant white or a silver
and white finish. Fitting within the ceiling grid, VISTA™ is
stylish, low profile, and compact. Energy efficiency and
comfort can be enhanced through the combined use of
optional floor and presence sensors. It is also possible
to close individual louvers via the wired remote control
INDOOR UNITS
Airflow Angles
»» Retail
»» Schools
»» Offices 0° 0°
60° 60°
Fixed Angles: 5 Levels
0° 0°
60° 60°
L-Shaped
64 www.daikincomfort.com 4-Way Flow 3-Way Flow
2-Way Flow
SPECIFICATIONS 0.5 TON 0.6 TON 0.75 TON 1 TON 1.25 TON 1.5 TON
Model Name FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJU
Capacity Index 5.8 7.5 9.5 12 15 18
Power Supply V/ph/Hz 208/230VAC, 60Hz, 1 phase
Nominal Cooling Capacity*1 Btu/h (kW) 5,800 (1.7) 7,500 (2.2) 9,500 (2.8) 12,000 (3.5) 15,000 (4.5) 18,000 (5.3)
Nominal Heating Capacity*2 Btu/h (kW) 6,500 (1.9) 8,500 (2.5) 10,500 (3.1) 13,500 (4.0) 17,000 (5.0) 20,000 (5.9)
Type Turbo Fan
Motor Output W 50
Fan
Air Flow Rate (H/M/L) CFM 300 / 247 / 229 307 / 264 / 229 317 / 282 / 229 353 / 300 / 247 405 / 335 / 282 511 / 441 / 353
Drive Type DC Direct Drive
Dimensions - Unit Body (H x W x D) in. (mm) 10-1/4 x 22-5/8 x 22-5/8 (260x575x575)
Dimensions - Decoration Panel (H x W x D) in. (mm) 1-13/16 x 24-7/16 x 24-7/16 (46x620x620)
Weight (net) lb. (kg) 40.4 (18.3) 42.6 (19.3) 47 (21.3)
Condensate Pump Lift in. (mm) 24-15/16 (630)
Sound Pressure Level (H/M/L speed) dB(A) 32 / 29.5 / 25.5 33 / 30 / 29.5 33.5 / 30 / 26 37 / 32 / 28 43 / 40 / 33
Liquid in. 1/4 (Flare)
Pipe
Gas in. 1/2 (Flare)
Connections
Condensate Drain in. VP20
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protection Device A 15
Minimum Circuit Ampacity A 0.3 0.4 0.6
INDOOR UNITS
Decoration Panel – White BYFQ60C3W1W
Decoration Panel – Silver/White BYFQ60C3W1S
Note: *1 Nominal cooling capacities are based on the following conditions: 80 °FDB / 67 °FWB (26.7 °CDB / 19.4 °CWB) return air temperature;
95 °FDB (35 °CDB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
*2
Nominal heating capacities are based on the following conditions: 70 °FDB (21.1 °CDB) return air temperature;
47 °FDB / 43 °FWB (8.3 °CDB / 6.1 °CWB) outdoor temperature; 25 ft. (7.6 m) equivalent refrigerant piping.
FXZQ_TAVJU ACCESSORIES
Model Name FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJU
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Infrared Remote Controller - White** BRC082A42W
Infrared Remote Controller - Silver** BRC082A42S
Space and Presence Sensor Kit - White** BRYQ60A2W
Space and Presence Sensor Kit - Silver** BRYQ60A2S
VISTA Decoration Panel - White BYFQ60C3W1W
VISTA Decoration Panel - Silver BYFQ60C3W1S
Legacy MVJU9-style Decoration Panel BYFQ60B3W1
Remote Sensor Kit KRCS01-4B
Wiring Adaptor PCB (interface with aux heater, humidifier, OA damper/fan) KRC1C75
Long-Life Replacement Filter KAFQ441BA60
Sealing Member of Air Discharge Kit BDBHQ44C60
Fresh Air Intake Kit KDDQ44XA60
*Optional face plates to provide a more intuitive user interface and disable specific functions
**Not compatible with the legacy-style decoration panel
H MODEL HEIGHT
FXZQ05-18TAVJU 11.75" or more
60" or more
*60" or *60" or
more Air Air Air more
discharge inlet discharge *Leave 7-7/8" or more space on sides
where the air outlet is closed.
use this style of indoor unit in the tightest of spaces. »» A Ventilation Air knock-out is provided to allow up
»» The innovative discharge air louver design forces air in to 15% of the rated airflow through the unit to be
heating mode to ground level to improve the overall pretreated outside air.
space heating effect of the indoor unit. »» The innovative “smooth finish” decoration panel design
helps to minimize dust and dirt build-up and facilitates
Front view Side view easier cleaning.
»» The Indoor Unit
is equipped with
Overview of the vertical fins Balance of horizontal fins to
a factory installed
to the right or left up to 45˚ frequent between 20˚ and 70˚ condensate pump with
a lift capacity of up to
»» The unit is equipped with both horizontal and vertical 33-7/16" (measured
louvers that can be freely adjusted with the remote from the bottom of
controller providing a capability to optimize the airflow the unit).
31-½"
and throw to suit your room design. »» The units are equipped
»» The utilization of both a DC-style Fan Motor and with customizable
integrated Condensate Pump allow for improvements auxiliary heat control
in energy consumption as well as lower operating settings to facilitate the
sound levels than other styles of indoor units. On/Off control of an external auxiliary heat solution.
»» This Indoor unit can be set to 5 predetermined fan speeds »» For ease of service and maintenance activities,
using the BRC1E73 wired remote controller, which allows it is possible to access the main components
for optimum and comfortable airflow. of the unit by only removing the decoration panel.
Applications
»» Hotel Rooms
»» Offices
»» Residential
(Apartments,
Condominiums,
etc.)
66 www.daikincomfort.com
FXEQ_PVJU SPECIFICATIONS 0.6 TON 0.75 TON 1.0 TON 1.25 TON 1.5 TON 2 TON
Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJU
Power Supply 1 phase 60Hz 208/230V
Cooling
*1,*3 Btu/h 7500 9500 12000 15000 18000 24000
capacity
Heating
*2,*3 Btu/h 8500 10500 13500 17000 20000 27000
capacity
Min. circuit amps (MCA) A 0.3 0.4 0.4 0.5 0.5 0.7
Electrical Max. overcurrent protection
A 15 15 15 15 15 15
(MOP)
Casing/color Galvanized steel plate
Dimensions: (H x W x D) in. 7-7∕ 8 x 18-½ x 33-1-1/16 7-7∕ 8 x 18-½ x 48-13/16
Type Sirocco fan
Air flow rate Cooling
Fan CFM 212/191/173/155/141 244/226/205/187/170 283/265/247/223/194 346/311/276/247/219 441/403/367/336/307 530/481/431/389/346
(Dry coiI) (H/HM/M/ML/L)
Drive Direct drive
Cooling
Sound pressure level dBA 30/29/28/27/26 32/31/30/29/28 35/34/33/32/30 38/37/35/33/31 38/37/35/33/31 43/41/39/37/35
(H/HM/M/ML/L)
Weight lbs. 38 40 51
ø 3 ∕8
Liquid in. ø ¼ (flare connection) (fIare connection)
Piping
ø 5 ∕8
connections Gas in. ø ½ (flare connection) (flare connection)
Drain in. PVC26 (0.D. 1-1/32 x I.D. 13/16
INDOOR UNITS
Drain pump lift in. 25
Refrigerant control Electronic expansion valve
Connectable outdoor unit R-410A VRV Series
Model BYEP40AW1 BYEP63AW1
Decoration Color Fresh White
paneI Dimensions (H x W x D) in. 3-3/16 x 21- 5 ∕ 8 x 37-13/32 3-3/16 x 21- 5 ∕ 8 x 53-5/32
(required
Air filter Resin net (with mold resistant)
option)
Weight Ibs. 17.6 22
Note: * 1. Nominal cooling capacities are based on the following conditions: return air temperature: 80.0˚ FDB (26.7˚C DB), 67.0˚ FWB (19.4˚CWB), outdoor temperature: 95.0˚ FDB (35.˚C DB)
equivalent ref. piping: 25ft. (7.6m) (Horizontal)
* 2.
Nominal heating capacities are based on the following conditions: return air temperature: 70.0˚ FDB (21.1˚C DB), outdoor temperature: 47.0˚ FDB (8.3˚C DB), 43.0˚ FDB (6.1˚C WB)
equivalent ref. piping: 25ft. (7.6m) (Horizontal)
* 3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
FXEQ_PVJU ACCESSORIES
Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJU
Name of Option Note
Decoration panel BYEP40AW1 BYEP63AW1
Wired remote controller BRC1E73
Simplified remote controller BRC2A71
Remote sensor KRCS01-4B
Wiring adaptor printed circuit board 2 KRP1C75
Group control adaptor printed circuit board 2 KRP4A74
Adaptor mounting box KRP1B101
Note: *1. Electrical box (No.5-1/6-1) is required for controlIer (No. 5/6) *2. Adaptor mounting box (No.12) is necessary.
[Ceiling]
More than
40(1000)
Figure 1
»» Long-life filter is standard Uses the quiet stream fan and many more advanced technologies.
»» Models range from 12 MBH to 36 MBH Sound absorption
member
Applications
»» Retail/shops
»» Offices
»» Restaurants
68 www.daikincomfort.com
FXHQ_MVJU SPECIFICATIONS 1 TON 2 TON 3 TON
Model Name FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 12,000 24,000 36,000
Rated Heating Capacity BTU/h 13,500 27,000 40,000
Airflow Rate (H/L) CFM 410/340 710/600 830/670
Weight lbs. 55 80 90
Height in. 7-11/16
Width in. 37-13/16 55-1/8 62-5/8
Depth in. 26-3/4
Sound Pressure (H/L) dB(A) 42/33 44/36 46/41
Condensate Pipe Connection in. O.D. 1
Gas in. 1/2 (Flare) 5/8 (Flare)
Pipe Connections
Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device A 15
Minimum Circuit Amps A 0.8 1.0 1.4
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish White Casing
Standard Filter Type Resin Net (with Mold Resistant)
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
INDOOR UNITS
Level Difference: 0 ft. Level Difference: 0 ft.
FXHQ_MVJU ACCESSORIES
Model Name FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC7E83
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater, humidifier, OA damper/fan) KRP1C74
Group Control Adaptor PCB (connects to external BMS) KRP4A72
Replacement long-life filter KAFJ501D56 KAFJ501D112 KAFJ501D160
Condensate Pump DACA-CP3-1
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
Obstruction
Floor
Applications
»» Retail
»» Restaurants
»» Offices
»» Hotels
»» Multi-family
residences
70 www.daikincomfort.com
FXAQ_PVJU SPECIFICATIONS 0.6 TON 0.75 TON 1 TON 1.5 TON 2 TON
Model Name FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 7,500 9,500 12,000 18,000 24,000
Rated Heating Capacity BTU/h 8,500 10,500 13,500 20,000 27,000
Airflow Rate (H/L) CFM 260/160 280/175 290/180 500/400 635/470
Weight lbs. 26 31
Height in. 11-3/8
Width in. 31-1/4 41-3/8
Depth in. 9
Sound Pressure (H/L) dB(A) 36/31 37/31 38/31 43/37 47/41
Condensate Pipe Connection in. O.D. 11/16
Gas in. 1/2 (Flare) 5/8 (Flare)
Pipe Connections
Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device A 15
Minimum Circuit Amps A 0.4 0.5 0.6
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish White Casing
Standard Filter Type Resin Net (washable)
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
INDOOR UNITS
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXAQ_PVJU ACCESSORIES
Model Name FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJU
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC7E818
Remote Sensor Kit KRCS01-1B
Group Control Adaptor PCB (Connects to external BMS) KRP4A71
Condensate Pump DACA-CP1-1
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
≥ 2" ≥ 2"
≥ 1-1/4"
≤ 4-3/4"
Back-right pipe
Floor
Fig.1 Fig.2 Fig.3 Bottom-right pipe
Applications
»» Multi-family
residences
»» Single-family
residences
»» Churches
»» Historic buildings
»» Schools
»» Offices
72 www.daikincomfort.com
FXLQ_MVJU9 SPECIFICATIONS 0.6 TON 0.75 TON 1 TON 1.5 TON 2 TON
Model Name FXLQ07MVJU9 FXLQ09MVJU9 FXLQ12MVJU9 FXLQ18MVJU9 FXLQ24MVJU9
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 7,500 9,500 12,000 18,000 24,000
Rated Heating Capacity BTU/h 8,500 10,500 13,500 20,000 27,000
Airflow Rate (H/L) CFM 245/210 280/210 490/380 560/420
Weight lbs. 58 66 80
Height in. 23-5/8
Width in. 39-3/8 44-7/8 55-7/8
Depth in. 8-3/4
Sound Pressure (H/L) dB(A) 35/32 36/33 40/35 41/36
Condensate Pipe Connection in. O.D. 27/32
Gas in. 1/2 (Flare) 5/8 (Flare)
Pipe Connections
Liquid in. 1/4 (Flare) 3/8 (Flare)
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent
A 15
Protective Device
Minimum Circuit Amps A 0.3 0.5 0.6
Protection Devices Fuse and Fan Motor Thermal Protector
External Finish Ivory White Casing
Standard Filter Type Resin Net (with Mold Resistant)
INDOOR UNITS
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXLQ_MVJU9 ACCESSORIES
Model Name FXLQ12MVJU9 FXLQ18MVJU9 FXLQ24MVJU9 FXNQ12MVJU9 FXNQ18MVJU9 FXNQ24MVJU9
Navigation™ Remote Controller* BRC1E73
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA
Simplified Wired Remote Controller* BRC2A71
Wireless Remote Controller BRC4C82
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater,
KRP1C74
humidifier, OA damper/fan)
Group Control Adaptor PCB (connects to external BMS) KRP4A71
*
Optional face plates available to provide a more intuitive user interface and disable specific functions
Air inlet
direction
Base
A complete Daikin Zoning Kit consists of Zoning Box (with Zoning Box with Control Box
Control Board), Wired Thermostat, and Wireless Thermostats. (Model Depends on Indoor Unit)
The optional DZK BACnet Interface enables any BACnet/IP
The Zoning Box in the Daikin Zoning
compatible Building Management System to be used for
Kit mounts easily on Daikin’s Indoor
remote monitoring and control of the DZK.
Unit FXMQ–P or FXSQ series fan
Wired Thermostat coils. It consists of the enclosure,
individually motorized dampers, and a
The 3rd generation DZK introduces all new, control box. It is available in different sizes
redesigned Wired and Wireless thermostats. and damper configurations and by utilizing
The revised form factor offers a slim profile ducts for air supply it can be used to control
and capacitive touch capability for an enhanced the air temperature in up to 6 zones. The wired
user experience. thermostat and the wireless thermostats provide tem-
The wired thermostat in the DZK is a graphical colored, touch- perature inputs and user interfaces for programming
screen interface with text menus, intuitive icons, and guided and adjustment of the control functions for each zone.
scheduling capability. It displays temperatures and operating
DZK BACnet Interface
values, and selects the operating mode for the system.
If VRV systems are
Wireless Thermostats installed with the DZK
The optional Wireless thermostat offers a system to accomplish
backlit, low energy E Ink display with capacitive a variety of zoning
touch buttons. The user can adjust the zone set solutions and there is a
point temperature, set user mode schedules, requirement to be able
activate local ventilation, and more. to monitor and control the various DZK zone dampers from
a centralized control system, it is possible to utilize the DZK
The optional Wireless Lite thermostat offers BACnet Interface to address this solution.
a sleek, simple user interface to adjust the
local zone set point temperature using led-lit The DZK BACnet Interface will work with any BACnet/IP
capacitive touch buttons. compatible Building Management System.
74 www.daikincomfort.com
DAIKIN ZONING KIT (DZK) - GENERAL TECHNICAL DATA
DZK Model DZKS015E3-3 DZKS015E4-3 DZKS030E4-3 DZKS030E5-3 DZKS048E4-3 DZKS048E6-3 DZK030E4-3 DZK030E5-3 DZK048E4-3 DZK048E6-3
Height in. 9-5/8 9-5/16 9-5/8 9-5/16 9-5/8 9-5/16 10-7/16 10-1/4 10-7/16 10-1/4
Width in. 34-3/16 43-5/8 53-7/16 43-9/16 53-7/16
Depth in. 10-7/16
Weight lb. 16 18 18 20 18 23 18 20 20 23
No. of Zones 3 4 4 5 4 6 4 5 4 6
Ø of Outlets in. 8 6 8 6 8 6 8 6 8 6
VAC 110/230 VAC
Power
ph 1
Supply
Hz 60
DZKS048E6-3
DZKS048E4-3
DZKS030E5-3
DZKS030E4-3
DZKS015E4-3
DZKS015E4-3
DZK048E6-3
DZK030E5-3
DZK048E4-3
DZK030E4-3
VRV Indoor Unit
FXSQ15TAVJU ■ ■
FXSQ18/24/30TAVJU ■ ■
FXSQ36/48TAVJU ■ ■
FXMQ15/18/24PBVJU ■ ■
INDOOR UNITS
FXMQ30/36/48/54PBVJU ■ ■
DZK-MTS-3-W* ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
DZK-ZTS-3-W ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
DZK-LTS-3-W ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
DZK-BACNET-3 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
*Minimum (1) required per DZK Zoning Kit
Zoning Box
Control Box
Zoning Box
Air-Cooled Condensers
460V/60Hz/3ph
The VRV Water-Cooled system combines the
Daikin VRV AURORA Series systems characteristics of a water-cooled system with
introduce a new benchmark for variable the air-cooled VRV system and still use the same VRV indoor
refrigerant flow technology by integrating advanced technologies units, similar refrigerant piping methods, branch selector boxes,
to provide comfort, control, energy efficiency and reliability. and controls as air-cooled VRV systems. The main difference is
The Daikin VRV AURORA Series systems set a new industry that heat is rejected or absorbed via the condensing units to and
standard for heating and cooling solutions by delivering high from the 2-pipe water circuit instead of the outside air.
heat capacities at low ambient applications. »» Flexible System design with increased diversity up to 150%††
»» variable refrigerant flow Industry’s first air-cooled system »» Can be applied to both geothermal and boiler/tower applications
that delivers heating down to -22°F (-30°C) as standard as standard with condenser water inlet temperature as low as
»» Hot gas base pan circuit allows installation 14°F†† in heating and 23°F†† in cooling is possible
without an additional drain pan heater »» Triple-stack capable to deliver up to 36 tons thanks to the
»» Designed to provide continuous heating compact design
during defrost and oil return1 »» Engineered with heat rejection cancellation technology††
»» Engineered with Daikin vapor injection compressor to eliminate mechanical room conditioning requirements
for optimized part load efficiencies »» 2-9V variable water flow control logic†† as standard to
increase waterside system operational efficiencies
»» Drop-down switch box for easy service to key components
Heat Pump & Heat Recovery »» Field selectable top or front refrigerant connections for flexible
6 to 382 Tons 208-230V/60Hz/3ph or and easy installation
460V/60Hz/3ph 1
Multi module heat recovery systems only for continuous heating during defrost
2
Maximum 34 tons for Heat Pump
Daikin's VRV IV systems integrate †
6 -ton model (RWEYQ72PC) is PC series. T and PC series models cannot be
combined to form multi-module systems.
advanced technology to provide comfort ††
Conditions/rules apply. Refer to Installation and Engineering Manual for
control to help maximize energy efficiency further details.
and reliability. Currently available in heat
pump and heat recovery configurations, VRV IV provides
a solution for multi-family residential to large commercial
applications desiring heating or cooling. The VRV IV is the
first variable refrigerant flow system to be assembled in
North America.
78 www.daikincomfort.com
Local assembly of products OUTDOOR UNITS
80 www.daikincomfort.com
VRV IV X CERTIFIED DATA - HEAT RECOVERY, 208-230V/60HZ/3PH, 460V/60HZ/3PH
EER Non-Ducted
Capacity (Tons)
Product #
SCHE Ducted
IEER Ducted
SCHE Mixed
EER Ducted
IEER Mixed
EER Mixed
REYQ72XA 6 25.20 21.30 23.25 26.10 22.00 24.05 4.30 3.68 3.99 2.50 2.25 2.38 15.80 13.90 14.85
REYQ96XA 8 27.80 21.90 24.85 26.40 21.10 23.75 4.23 3.56 3.90 2.63 2.31 2.47 14.60 12.50 13.55
REYQ120XA 10 25.50 22.60 24.05 26.00 22.00 24.00 3.81 3.48 3.65 2.54 2.28 2.41 13.20 12.30 12.75
REYQ144XA 12 23.50 21.60 22.55 25.50 22.00 23.75 3.75 3.42 3.59 2.16 2.12 2.14 11.90 11.60 11.75
REYQ168XA 14 22.30 20.40 21.35 25.50 22.20 23.85 3.49 3.24 3.37 2.08 2.05 2.07 10.70 10.60 10.65
REYQ192XA 16 22.60 21.40 22.00 26.60 22.80 24.70 3.85 3.67 3.76 2.50 2.37 2.44 13.00 13.00 13.00
REYQ216XA 18 23.10 21.70 22.40 25.50 21.90 23.70 3.76 3.52 3.64 2.34 2.20 2.27 12.40 12.30 12.35
REYQ240XA 20 22.20 20.00 21.10 25.60 21.80 23.70 3.68 3.39 3.54 2.34 2.16 2.25 11.60 11.70 11.65
REYQ264XA 22 21.60 18.00 19.80 26.10 18.20 22.15 3.62 3.20 3.41 2.22 2.07 2.15 11.20 10.40 10.80
REYQ288XA 24 21.00 17.90 19.45 23.30 19.90 21.60 3.51 3.20 3.36 2.20 2.06 2.13 11.00 10.30 10.65
REYQ312XA 26 20.40 18.00 19.20 24.30 20.70 22.50 3.56 3.20 3.38 2.09 2.05 2.07 10.10 9.90 10.00
REYQ336XA 28 20.00 17.30 18.65 23.30 19.80 21.55 3.53 3.20 3.37 2.12 2.05 2.09 9.90 9.50 9.70
REYQ360XA 30 20.00 18.80 19.40 23.00 19.40 21.20 3.56 3.20 3.38 2.25 2.10 2.18 10.90 10.60 10.75
REYQ384XA 32 19.00 17.60 18.30 21.90 17.00 19.45 3.21 3.20 3.21 2.22 2.06 2.14 9.70 9.90 9.80
REYQ408XA 34 17.20 17.70 17.45 21.80 18.30 20.05 3.21 3.20 3.21 2.09 2.05 2.07 9.80 9.70 9.75
REYQ432XA 36 16.20 17.30 16.75 20.20 18.10 19.15 3.21 3.20 3.21 2.08 2.06 2.07 9.80 9.70 9.75
OUTDOOR UNITS
REYQ456XA 38 16.20 16.70 16.45 18.80 17.90 18.35 3.21 3.20 3.21 2.07 2.05 2.06 9.30 9.50 9.40
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV Series.
The VRV IV X Series has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy (DOE) and baseline efficiencies
as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED OPERATION RANGES FOR VRV IV X REYQ_X HEAT RECOVERY OUTDOOR UNITS TECHNICAL COOLING FEATURE FOR VRV IV X REYQ_X
HEAT RECOVERY OUTDOOR UNITS
Cooling Heating
Technical Cooling - Cooling
110 60 Cooling operation 110
extended from 23°F
ambient air temperature 100
100 50 down to -4°.
The Technical Cooling 90
operation
up operation
operation
continuous operation
continuous operation
operation
pull-down operation
40
continuous operation
pull-down operation
80
operation
settings on the outdoor
Outdoor temperature (˚F WB)
Outdoor temperature (˚F DB)
forcontinuous
forpull-down
forcontinuous
for pull-down
and allows operation 60
forwarming
Rangefor
Range for
Rangefor
40
Range
Range
Range
Range
Range
82 www.daikincomfort.com
22 Ton 24 Ton 26 Ton 28 Ton 30 Ton 32 Ton 34 Ton 36 Ton2 38 Ton
REYQ264XATJU REYQ288XATJU REYQ312XATJU REYQ336XATJU REYQ360XATJU REYQ384XATJU REYQ408XATJU REYQ432XATJU REYQ456XATJU
REYQ264XAYDU REYQ288XAYDU REYQ312XAYDU REYQ336XAYDU REYQ360XAYDU REYQ384XAYDU REYQ408XAYDU REYQ432XAYDU REYQ456XAYDU
1 x REYQ120XA 1 x REYQ144A 2 x REYQ120XA 1 x REYQ120XA 2 x REYQ144XA
2 x REYQ144XA 2 x REYQ168XA 3 x REYQ120XA 3 x REYQ144XA
1 x REYQ144XA 1 x REYQ168XA 1 x REYQ144XA 2 x REYQ144XA 1 x REYQ168XA
252,000 274,000 296,000 320,000 342,000 364,000 388,000 410,000 430,000
282,000 294,000 320,000 338,000 376,000 386,000 394,000 405,000 414,000
23 to 122
-13 to 60
69 69 69 69 70 71 71 71 71
7989 + 9480 9480 + 9480 9480 + 9480 9480 + 9480 7989 + 7989 + 7989 7989 + 7989 + 9480 7989 + 9480 + 9480 9480 + 9480 + 9480 9480 + 9480 + 9480
0.12 / 0.32
2 3
6504 + 5214 4794 + 4794 5286 + 5286 5664 + 5664 6606 + 6606 + 6606 6426 + 6426 + 5070 6162 + 4470 + 4470 4350 + 4350 + 4350 4470 + 4470 + 4470
5-100 7-100 7-100 6-100 4-100 3-100 3-100 5-100 4-100
164 (295 With Field Setting)
OUTDOOR UNITS
100
541
620
3,280
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
1-3/8 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8
50 - 2001
45 49 54 58 64
50 + 70 / 70 + 70 / 70 + 70 / 70 + 70 / 50 + 50 + 50 / 50 + 50 + 70 / 50 + 70 + 70 / 70 + 70 + 70 / 70 + 70 + 70 /
25 + 40 40 + 40 40 + 40 40 + 40 25 + 25 + 25 25 + 25 + 40 25 + 40 + 40 40 + 40 + 40 40 + 40 + 40/
43.0+ 58.3 / 58.3+ 58.3 / 58.3+ 61.9 / 61.9+ 61.9 / 43.0+ 43.0 + 43.0 / 43.0+ 43.0 + 58.3/ 43.0 + 58.3 + 58.3/ 58.3 + 58.3 + 58.3/ 58.3 + 58.3 + 61.9/
21.1 + 27.9 27.9 + 27.9 27.9 + 31.1 31.1 + 31.1 21.1 + 21.1 + 21.1 21.1 + 21.1 + 27.9 21.1 + 27.9 + 27.9 27.9 + 27.9 + 27.9 27.9 + 27.9 + 31.1 /
32.9 + 42.1 / 43.5 + 43.5 / 46.5 + 46.5 / 50.1 + 50.1 / 32.7 + 32.7 + 32.7 / 33.8 + 33.8 + 43.7 / 35.7 + 45.1 + 45.1 / 45.1 + 45.1 + 45.1 / 47.0 + 47.0 + 47.0 /
14.9 + 19.0 19.7 + 19.7 21.0 + 21.0 22.7 + 22.7 14.8 + 14.8 + 14.8 15.3 + 15.3 + 19.8 16.2 + 20.4 + 20.4 20.4 + 20.4 + 20.4 21.3 + 21.3 + 21.3
25.8 + 25.8 25.8 + 25.8 + 25.8
727 + 793 793 + 793 793 + 793 793 + 793 727 + 727 + 727 727 + 727 + 793 727 + 793 + 793 793 + 793 + 793 793 + 793 + 793
66-11/16 x 48-7/8 x 30-3/16 + 66-11/16 x 48-7/8 x 30-3/16 66-11/16 x 48-7/8 x 30-3/16 + 66-11/16 x 48-7/8 x 30-3/16 + 66-11/16 x 48-7/8 x 30-3/16
For additional technical information please refer to specific Engineering Data Books.
Features
»» Compatible with VRV IV X outdoor units. Available from
60,000 Btu up to 120,000 Btu
»» Durable heat exchanger – Unique tubular stainless-steel
construction formed using wrinkle-bend technology results
in an extremely durable heat exchanger. Paired with a
stainless-steel secondary heat exchanger, this combination
provides for reliability, durability and efficiency.
»» Modulating gas valve – Operates between 35% - 100%
capacity, providing precise efficiency and the ultimate
in comfort.
»» Continuous air circulation – Provides filtration and keeps
air moving throughout your home to help maintain comfort.
»» Self-diagnostic control board – continuously monitors
the system for consistent, reliable operation.
OUTDOOR UNITS
84 www.daikincomfort.com
COMFORTABLE LIMITED VRV IV X
WARRANTY* PROTECTION
* Complete commercial warranty details available from your local dealer/
contractor or at www.daikincomfort.com. To receive the 10-Year Parts
VRV A-Coil
Limited Warranties, online registration must be completed within 60 days
of installation Online registration and some of the additional requirements
are not required in California or Quebec.
CXTQ_TASBLU
OUTDOOR UNITS
1
Rules apply, refer to installation manual for details.
INDOOR – CXTQ
Model Name CXTQ24TASBLU CXTQ36TASBLU CXTQ48TASBLU CXTQ60TASBLU
inverter compressors and inverter fan motors »» Long pipe lengths up to 1640 ft total and ability to connect up to
»» Refrigerant-cooled efficient and stable inverter board 41*** indoor units with up to 100 ft vertical separation between
operation, independent of ambient conditions indoor units provides design and installation flexibility
»» Hot gas base pan circuit allows installation »» Corrosion resistant, 1000 hours salt spray tested Daikin PE
without an additional drain pan heater blue fin heat exchanger
»» Designed to provide continuous heating »» Ships factory standard with coil guards
during defrost and oil return** »» Outstanding 10-Year Parts Warranty* as standard.
»» Engineered with Daikin vapor injection compressor * Complete commercial warranty details available from your local
for optimized part load efficiencies distributor or manufacturer’s representative or at www.daikincomfort.com
or www.daikinac.com.
»» Added peace of mind with Auto Changeover ability **Multi modules only for continuous heating during defrost
to back up (auxiliary) heat ***Varies by model
86 www.daikincomfort.com
VRV AURORA™ HEAT RECOVERY CERTIFIED DATA - HEAT RECOVERY, 208-230V/60HZ/3PH AND 460V/60HZ/3PH
EER Non-Ducted
Capacity (Tons)
Product #
SCHE Ducted
IEER Ducted
SCHE Mixed
EER Ducted
IEER Mixed
EER Mixed
RELQ72T 6 24.00 20.80 22.40 26.10 22.60 24.30 4.30 3.68 3.99 2.50 2.30 2.40 15.80 13.70 14.70
RELQ96T 8 24.80 19.10 21.90 25.70 19.70 22.70 4.23 3.42 3.83 2.50 2.25 2.37 15.30 12.50 13.90
RELQ120T 10 23.40 19.60 21.50 26.70 21.10 24.00 3.98 3.51 3.74 2.25 2.25 2.25 13.70 12.40 13.00
RELQ144T 12 22.50 18.60 20.50 25.50 23.80 24.60 3.81 3.55 3.68 2.20 2.20 2.20 12.90 12.60 12.70
RELQ192T 16 22.10 19.00 20.50 25.50 21.20 23.30 3.85 3.57 3.71 2.20 2.15 2.17 12.50 12.70 12.60
RELQ240T 20 21.10 18.60 19.80 24.90 20.80 22.80 3.68 3.49 3.59 2.20 2.13 2.16 12.30 11.70 12.00
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV
Series. The VRV AURORA Series has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy
(DOE) and baseline efficiencies as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED OPERATION RANGES FOR VRV RELQ_T HEAT RECOVERY OUTDOOR UNITS TECHNICAL COOLING FEATURE FOR VRV RELQ_T
HEAT RECOVERY OUTDOOR UNITS
Cooling Heating Technical Cooling - Cooling
OUTDOOR UNITS
110 60 Cooling operation extended 110
from 23°F ambient air
100
temperature down to -4°. 100
50
The Technical Cooling feature
Outdoor temperature (˚F DB)
pull-down operation
branch selector boxes. It 80
continuous operation
operation
Range for continuous operation
for pull-down
forcontinuous
60
70 20 temperature in cooling mode.
See the Engineering Data 50
book for complete application
60 10
rules and contact your local
Range for
Rangefor
40
Daikin representative for
Range
Range
wind cover specification
50 0
requirements. 30
20
40 -10
10
30 -20
0
20 -30 -10
50 60 70 80 90 50 60 70 80 90 60 70 80
Indoor temperature (˚F WB) Indoor temperature (˚F DB) Indoor temperature (˚F WB)
TECHNICAL DATA FOR VRV AURORA RELQ_TATJU/TAYDU HEAT RECOVERY OUTDOOR UNITS
6 Ton 8 Ton 10 Ton
208-230V/3Ph/60Hz RELQ72TATJU RELQ96TATJU RELQ120TATJU
Model 460V/3Ph/60Hz RELQ72TAYDU RELQ96TAYDU RELQ120TAYDU
OUTDOOR UNITS
Combination
Rated Cooling Capacity BTU/h 69,000 92,000 114,000
Rated Heating Capacity BTU/h 77,000 103,000 129,000
Operation Range Cooling °F (°C) DB 231 to 122
Operation Range Heating °F (°C) WB -22 to 60
Performance
Sound Pressure dB(A) 60 61 64
Airflow (Cooling) CFM 6956 7989 8806
Airflow (Heating) CFM 7283 7283 7283
Fan ESP, Standard/Max in. Wg 0.12 / 0.32
Compressors, all inverter Qty 1
Compressor Revolutions per minute RPM 3738 3342 4350
Capacity Control Range % 11~100 10~100 9~100
Maximum Vertical Pipe Length Above Unit ft. 164 (295 With Field Setting)
Maximum Vertical Pipe Length Below Unit ft. 131 (195 With Field Setting)
Refrigerant Piping, Maximum Vertical Pipe Length Between IDU ft. 100
Layout Maximum Actual Pipe Length ft. 541
Maximum Equivalent Pipe Length ft. 620
Maximum Total Pipe Length ft. 1,640
Liquid Pipe (Main Line) in. 3/8 3/8 1/2
Refrigerant Piping,
Suction Gas Pipe (Main Line) in. 3/4 7/8 1-1/8
Connections
Discharge Gas Pipe (Main Line) in. 5/8 3/4 3/4
Standard Connectable Indoor Unit Ratio % 70 - 2002
Connection Ratio
Maximum Number of Indoor Units Qty 12 16 20
Maximum Overcurrent Protection, MOP (RELQ_TATJU / RELQ_TAYDU) A 70 / 35 80 / 45 90 / 50
Electrical Minimum Circuit Amps, MCA (RELQ_TATJU / RELQ_TAYDU) A 60.8 / 28.1 76.5 / 39.8 83.4 / 43.4
Compressor Rated Load Amps, RLA (RELQ_TATJU / RELQ_TAYDU) A 20.7 / 9.4 36.8 / 16.6 39.3 / 17.8
Factory Refrigerant Charge lbs. 25.8
Unit Weight lbs. 727 793 793
Dimensions (H x W x D) in. 66-11/16 X 48-7/8 X 30-3/16
1
Cooling operation can be extended down to -4ºF with application rules and conditions
2
Varies based on indoor model selected
88 www.daikincomfort.com
12 Ton 16 Ton 20 Ton
208-230V/3Ph/60Hz RELQ144TATJU RELQ192TATJU RELQ240TATJU
Model 460V/3Ph/60Hz RELQ144TAYDU RELQ192TAYDU RELQ240TAYDU
OUTDOOR UNITS
Combination 2 x RELQ72T 2 x RELQ96T 2 x RELQ120T
Rated Cooling Capacity BTU/h 138,000 184,000 228,000
Rated Heating Capacity BTU/h 154,000 206,000 256,000
Operation Range Cooling °F (°C) DB 231 to 122
Operation Range Heating °F (°C) WB -22 to 60
Performance
Sound Pressure dB(A) 63 64 67
Airflow (Cooling) CFM 7283 + 7283 7989 + 7989 8806 + 8806
Airflow (Heating) CFM 6956 + 6956 7283 + 7283 7283 + 7283
Fan ESP, Standard/Max in. Wg 0.12 / 0.32
Compressors, all inverter Qty 2
Compressor Revolutions per minute RPM 3786 + 3786 3294 + 3294 4230 + 4230
Capacity Control Range % 6~100 5~100 4~100
Maximum Vertical Pipe Length Above Unit ft. 164 (295 With Field Setting)
Maximum Vertical Pipe Length Below Unit ft. 131 (195 With Field Setting)
Refrigerant Piping, Maximum Vertical Pipe Length Between IDU ft. 100
Layout Maximum Actual Pipe Length ft. 541
Maximum Equivalent Pipe Length ft. 620
Maximum Total Pipe Length ft. 1,640
Liquid Pipe (Main Line) in. 1/2 5/8 5/8
Refrigerant Piping,
Suction Gas Pipe (Main Line) in. 1-1/8 1-1/8 1-3/8
Connections
Discharge Gas Pipe (Main Line) in. 7/8 1-1/8 1-1/8
Standard Connectable Indoor Unit Ratio % 70 - 2002
Connection Ratio
Maximum Number of Indoor Units Qty 25 33 41
Maximum Overcurrent Protection, MOP (RELQ_TATJU / RELQ_TAYDU) A 70 + 70 / 35 + 35 80 + 80 / 45 + 45 90 + 90 / 50+ 50
Electrical Minimum Circuit Amps, MCA (RELQ_TATJU / RELQ_TAYDU) A 60.8 + 60.8 / 28.1 + 28.1 76.5 + 76.5 / 39.8 + 39.8 83.4 + 83.4 / 43.4 + 43.4
Compressor Rated Load Amps, RLA (RELQ_TATJU / RELQ_TAYDU) A 21.6 + 21.6 / 9.8 + 9.8 38.1 + 38.1 / 17.3 + 17.3 40.4 + 40.4 / 18.3 + 18.3
Factory Refrigerant Charge lbs. 25.8 + 25.8
Unit Weight lbs. 2 x 727 2 x 793 2 x 793
Dimensions (H x W x D) in. 66-11/16 X 48-7/8 X 30-3/16 + 66-11/16 X 48-7/8 X 30-3/16
»» Year round comfort and energy savings with Variable »» Long pipe lengths up to 1640 ft. total and ability
Refrigerant Temperature technology (VRT) to connect up to 41** indoor units with up to
»» Refrigerant-cooled efficient and stable inverter board 100 ft. vertical separation between indoor units
operation, independent of ambient conditions provides design and installation flexibility
»» Hot gas base pan circuit allows installation »» Corrosion resistant, 1000 hours salt spray
without an additional drain pan heater tested Daikin PE blue fin heat exchanger
»» Added peace of mind with Auto Changeover »» Ships factory standard with coil guards
ability to back up (auxiliary) heat »» Outstanding 10-Year Parts Warranty* as standard.
* Complete commercial warranty details available from your local
distributor or manufacturer’s representative or at www.daikincomfort.com
or www.daikinac.com.
** Varies by model
90 www.daikincomfort.com
VRV AURORA™ HEAT PUMP CERTIFIED DATA - HEAT PUMP, 208-230V/60HZ/3PH, 460V/60HZ/3PH
EER Non-Ducted
Capacity (Tons)
Product #
IEER Ducted
EER Ducted
IEER Mixed
EER Mixed
RXLQ72T 6 24.00 20.40 22.20 4.37 3.73 4.05 2.52 2.31 2.42 15.10 13.00 14.05
RXLQ96T 8 24.70 18.90 21.80 4.29 3.49 3.89 2.51 2.26 2.39 14.90 12.30 13.60
RXLQ120T 10 23.30 19.40 21.35 4.05 3.56 3.81 2.27 2.26 2.27 13.50 12.20 12.85
RXLQ144T 12 22.40 18.20 20.30 3.86 3.56 3.71 2.21 2.21 2.21 12.70 12.40 12.55
RXLQ192T 16 22.00 18.80 20.40 3.90 3.61 3.76 2.22 2.16 2.19 12.30 12.50 12.40
RXLQ240T 20 21.00 18.60 19.80 3.77 3.53 3.65 2.22 2.13 2.18 12.10 11.50 11.80
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV
Series. The VRV AURORA Series has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy
(DOE) and baseline efficiencies as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED OPERATION RANGES FOR VRV RXLQ_T HEAT PUMP OUTDOOR UNITS
Cooling Heating
OUTDOOR UNITS
110 60
100
50
Outdoor temperature (˚F DB)
90
40
Range for continuous operation
80 30
70 20
60 10
50 0
40 -10
30 -20
20 -30
50 60 70 80 90 50 60 70 80 90
Combination
Rated Cooling Capacity BTU/h 69,000 92,000 114,000
Rated Heating Capacity BTU/h 77,000 103,000 129,000
Operation Range Cooling °F (°C) DB 23 to 122
Performance Operation Range Heating °F (°C) WB -22 to 60
Sound Pressure dB(A) 60 61 64
Airflow CFM 7283 7989 8806
Fan ESP, Standard/Max in. Wg 0.12 / 0.32
Compressors, all inverter Qty 1
Compressor Revolutions per minute RPM 3738 3294 4350
Capacity Control Range % 11~100 13~100 12~100
Maximum Vertical Pipe Length Above Unit ft. 164 (295 With Field Setting)
Maximum Vertical Pipe Length Below Unit ft. 131 (195 With Field Setting)
Refrigerant Piping, Maximum Vertical Pipe Length Between IDU ft. 100
Layout Maximum Actual Pipe Length ft. 541
Maximum Equivalent Pipe Length ft. 620
Maximum Total Pipe Length ft. 1,640
Refrigerant Piping, Liquid Pipe (Main Line) in. 3/8 3/8 1/2
Connections Suction Gas Pipe (Main Line) in. 3/4 7/8 1-1/8
Standard Connectable Indoor Unit Ratio % 70 - 2001
Connection Ratio
Maximum Number of Indoor Units Qty 12 16 20
Maximum Overcurrent Protection, MOP (RXLQ_TATJU / RXLQ_TAYDU) A 70 / 35 80 / 45 90 / 50
Electrical Minimum Circuit Amps, MCA (RXLQ_TATJU / RXLQ_TAYDU) A 60.8 / 28.1 76.5 / 39.8 83.4 / 43.4
Compressor Rated Load Amps, RLA (RXLQ_TATJU / RXLQ_TAYDU) A 23.9 / 10.4 42.2 / 18.3 41.4 / 18.0
Factory Refrigerant Charge lbs. 25.8
Unit Weight lbs. 727 793 793
Dimensions (H x W x D) in. 66-11/16 X 48-7/8 X 30-3/16
1
Varies based on indoor model selected
92 www.daikincomfort.com
12 Ton 16 Ton 20 Ton
208-230V/3Ph/60Hz RXLQ144TATJU RXLQ192TATJU RXLQ240TATJU
Model 460V/3Ph/60Hz RXLQ144TAYDU RXLQ192TAYDU RXLQ240TAYDU
OUTDOOR UNITS
Combination 2 x RXLQ72T 2 x RXLQ96T 2 x RXLQ120T
Rated Cooling Capacity BTU/h 138,000 184,000 228,000
Rated Heating Capacity BTU/h 154,000 206,000 256,000
Operation Range Cooling °F (°C) DB 23 to 122
Performance Operation Range Heating °F (°C) WB -22 to 60
Sound Pressure dB(A) 63 64 67
Airflow (Cooling) CFM 7283 + 7283 7989 + 7989 8806 + 8806
Fan ESP, Standard/Max in. Wg 0.12 / 0.32
Compressors, all inverter Qty 2
Compressor Revolutions per minute RPM 3804 + 3804 3342 + 3342 4230 + 4230
Capacity Control Range % 6~100 6~100 6~100
Maximum Vertical Pipe Length Above Unit ft. 164 (295 With Field Setting)
Maximum Vertical Pipe Length Below Unit ft. 131 (195 With Field Setting)
Refrigerant Piping, Maximum Vertical Pipe Length Between IDU ft. 100
Layout Maximum Actual Pipe Length ft. 541
Maximum Equivalent Pipe Length ft. 620
Maximum Total Pipe Length ft. 1,640
Refrigerant Piping, Liquid Pipe (Main Line) in. 1/2 5/8 5/8
Connections Suction Gas Pipe (Main Line) in. 1-1/8 1-1/8 1-3/8
Standard Connectable Indoor Unit Ratio % 70 - 2001
Connection Ratio
Maximum Number of Indoor Units Qty 25 33 41
Maximum Overcurrent Protection, MOP (RXLQ_TATJU / RXLQ_TAYDU) A 70 + 70 / 35 + 35 80 + 80 / 45 + 45 90 + 90 / 50+ 50
Electrical Minimum Circuit Amps, MCA (RXLQ_TATJU / RXLQ_TAYDU) A 60.8 + 60.8 / 28.1 + 28.1 76.5 + 76.5 / 39.8 + 39.8 83.4 + 83.4 / 43.4 + 43.4
Compressor Rated Load Amps, RLA (RXLQ_TATJU / RXLQ_TAYDU) A 23.9 + 23.9 / 10.4 + 10.4 40.8 + 40.8 / 17.7 + 17.7 41.7 + 41.7 / 18.2 + 18.2
Factory Refrigerant Charge lbs. 25.8 + 25.8
Unit Weight lbs. 2 x 727 2 x 793 2 x 793
Dimensions (H x W x D) in. 66-11/16 X 48-7/8 X 30-3/16 + 66-11/16 X 48-7/8 X 30-3/16
»» Compatible with Daikin DVS series of Dedicated Outdoor »» Single/multiple port branch selector boxes provide compact
Air Systems (DOAS). dimensions and a wide range of product offerings (single, 4,
6, 8, 10 and 12 port options).
»» High energy efficiency with IEER values up to 29.3.
»» Reduced commissioning time with VRV
»» Integrated inverter technology delivers high
configuration software and Graphical User
efficiency during part load conditions and
Interface (GUI), as compared to VRV III.
provides precise individual zone control.
»» VRV IV takes advantage of Daikin's unique zone and
»» Design flexibility with long piping lengths up to 3,280 ft.
centralized controls that are optimized for the specific
total, and up to 100 ft. vertical separation between
needs of North America.
indoor units.
»» Outstanding 10-Year Parts Warranty* as standard.
»» Daikin PE blue fin heat exchanger. * Complete commercial warranty details available from your local
distributor or manufacturer’s representative or at www.daikincomfort.com
or www.daikinac.com.
94 www.daikincomfort.com
VRV IV CERTIFIED DATA - HEAT RECOVERY, 208-230V/60HZ/3PH AND 460V/60HZ/3PH
EER Non-Ducted
Capacity (Tons)
Product #
SCHE Ducted
IEER Ducted
SCHE Mixed
EER Ducted
IEER Mixed
EER Mixed
REYQ72T 6 24.90 20.90 22.90 25.40 21.40 23.40 4.31 3.58 3.95 2.70 2.43 2.56 15.00 12.20 13.60
REYQ96T 8 29.30 23.10 26.20 24.70 23.00 23.85 4.25 3.67 3.96 2.47 2.25 2.36 14.20 12.40 13.30
REYQ120T 10 25.40 22.60 24.00 25.90 25.10 25.50 4.00 3.51 3.76 2.45 2.25 2.35 12.90 12.10 12.50
REYQ144T 12 23.50 21.60 22.55 25.00 23.80 24.40 3.81 3.48 3.65 2.52 2.29 2.40 12.40 11.90 12.15
REYQ168T 14 21.90 20.40 21.15 26.00 24.10 25.05 3.64 3.21 3.43 2.20 2.09 2.15 11.30 10.90 11.10
REYQ192T 16 22.90 21.10 22.00 26.60 23.10 24.85 3.85 3.67 3.76 2.38 2.26 2.32 12.50 12.30 12.40
REYQ216T 18 23.00 20.80 21.90 25.60 22.80 24.20 3.74 3.66 3.70 2.32 2.18 2.25 12.50 12.20 12.35
REYQ240T 20 21.90 19.80 20.85 25.60 22.70 24.15 3.68 3.51 3.60 2.24 2.09 2.17 11.90 11.60 11.75
REYQ264T 22 21.60 18.60 20.10 24.40 22.00 23.20 3.55 3.20 3.38 2.33 2.08 2.21 11.60 10.40 11.00
REYQ288T 24 21.00 17.90 19.45 23.30 21.80 22.55 3.51 3.20 3.36 2.41 2.13 2.27 11.40 10.30 10.85
REYQ312T 26 20.20 18.00 19.10 23.90 20.70 22.30 3.57 3.20 3.39 2.35 2.10 2.23 11.00 10.00 10.50
REYQ336T 28 19.00 17.30 18.15 23.50 20.60 22.05 3.53 3.20 3.37 2.18 2.05 2.12 10.30 9.60 9.95
REYQ360T 30 19.60 18.80 19.20 22.70 20.30 21.50 3.52 3.27 3.40 2.28 2.05 2.17 10.80 10.70 10.75
REYQ384T 32 18.30 18.00 18.15 22.50 18.70 20.60 3.21 3.20 3.21 2.22 2.05 2.14 9.80 9.80 9.80
REYQ408T 34 17.20 17.70 17.45 21.80 18.30 20.05 3.21 3.20 3.21 2.09 2.05 2.07 9.80 9.70 9.75
REYQ432T 36 16.20 17.30 16.75 20.20 18.10 19.15 3.21 3.20 3.21 2.08 2.06 2.07 9.80 9.70 9.75
OUTDOOR UNITS
REYQ456T 38 16.20 16.70 16.45 18.80 17.90 18.35 3.21 3.20 3.21 2.07 2.05 2.06 9.30 9.50 9.40
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV Series.
The VRV IV Series has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy (DOE) and baseline efficiencies
as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED OPERATION RANGES FOR VRV IV REYQ_T HEAT RECOVERY OUTDOOR UNITS TECHNICAL COOLING FEATURE FOR VRV IV REYQ_T
HEAT RECOVERY OUTDOOR UNITS
Cooling Heating
Technical Cooling - Cooling
110 60 Cooling operation 110
extended from 23°F
ambient air temperature 100
100 50 down to -4°.
The Technical Cooling 90
operation
up operation
operation
continuous operation
continuous operation
operation
pull-down operation
40
continuous operation
pull-down operation
80
operation
settings on the outdoor
Outdoor temperature (˚F WB)
Outdoor temperature (˚F DB)
forcontinuous
forpull-down
forcontinuous
for pull-down
and allows operation 60
forwarming
Rangefor
Range for
Rangefor
40
Range
Range
Range
Range
Range
96 www.daikincomfort.com
22 Ton 24 Ton 26 Ton 28 Ton 30 Ton 32 Ton 34 Ton 36 Ton 38 Ton
REYQ264TATJU REYQ288TATJU REYQ312TATJU REYQ336TATJU REYQ360TATJU REYQ384TATJU REYQ408TATJU REYQ432TATJU REYQ456TATJU
REYQ264TAYDU REYQ288TAYDU REYQ312TAYDU REYQ336TAYDU REYQ360TAYDU REYQ384TAYDU REYQ408TAYDU REYQ432TAYDU REYQ456TAYDU
1 x REYQ168T 1 x REYQ168T
1 x REYQ144T 1 x REYQ168T 1 x REYQ168T
2 x REYQ144T 2 x REYQ168T 3 x REYQ120T 1 x REYQ120T 1 x REYQ144T 3 x REYQ144T
1 x REYQ120T 1 x REYQ144T 2 x REYQ144T
1 x REYQ96T 1 x REYQ96T
252,000 274,000 296,000 320,000 342,000 364,000 388,000 410,000 430,000
274,000 288,000 306,000 316,000 376,000 386,000 394,000 405,000 415,000
66 68 66 68 69 70
18.6 / 21.6 17.9 / 21.0 18.0 / 20.2 17.3 / 19.0 18.8 / 19.6 18.0 / 18.3 17.7 / 17.2 17.3 / 16.2 16.7 / 16.2
6,286 + 8,228 8,228 + 8,228 8,228 + 8,228 6,286 + 6,286 + 6,286 5,827 + 6,286 + 8,228 5,827 + 8,228 + 8,228 8,228 + 8,228 + 8,228
0.12/0.32
4 6
(4710, 4710), (5070, 5070) x (5040, 5040),
(4740, 4740) x 2 (5790, 5790) x 2 (5010, 5010) x 3 (5220, 5220) x 3 (5730, 5730) x 3
(4800, 4800) 2, (5160, 5160) (5130, 5130) x 2
5-100 3-100
164 (295 With Field Setting)
OUTDOOR UNITS
100
541
620
3,280
Ø1-3/8 (34.9) C1220T (Brazing Connection) Ø1-5/8 (41.3) C1220T (Brazing Connection)
Ø1-1/8 (28.6) C1220T (Brazing Connection) Ø1-3/8 (34.9) C1220T (Brazing Connection)
50 - 200
45 49 54 58 64
50 + 50 + 50 / 25 + 70 + 70 + 70 / 70 + 70 + 70 /
50 + 70 / 25 + 40 70 + 70 / 40 + 40 45 + 50 + 70 / 25 + 25 + 40 45 + 70 + 70 / 25 + 40 + 40
25 + 25 40 + 40 + 40 40 + 40 + 40
(15 + 15) + (16.2 + (16.2 + 22.6) + (17.4 (13.7 + 13.7) + (16.2 + 22.6) (13.7 + 13.7) + (16.2 + 22.6) (16.2 + 22.6) x 2 +
(16.2 + 22.6 x 2 / (17.4 + 24.4)x 2 / (15 + 15) x 3 / (16.2 + 22.6) x 3 /
22.6) / (6.8 + 6.8) + + 24.4) / (7.3 + 10.3) + (17.4 + 24.4) / (6.2 + 6.2) + + (17.4 + 24.4) / (6.2 + 6.2) + (17.4 + 24.4) / (7.3 +
(7.3 + 10.3) x 2 (7.9 + 11.1) x 2 (6.8 + 6.8) x 3 (7.3 + 10.3) x 3
(7.3 + 10.3) + (7.9 + 11.1) (6.8 + 6.8) + (7.9 + 11.1) (7.3 + 10.3) + (7.9 + 11.1) 10.3) x 2 + (7.9 + 11.1)
(66-11/16 x 48-7/8 x 30-3/16) + (66-11/16 x 48-7/8 x 30-3/16) (66-11/16 x 48-7/8 x 30-3/16) + (66-11/16 x 48-7/8 x 30-3/16) + (66-11/16 x 48-7/8 x 30-3/16)
For additional technical information please refer to specific Engineering Data Books.
by combining VRV and VRT technologies. »» Reduced commissioning time with VRV configuration
»» High energy efficiency with IEER values up to 27.3. software and Graphical User Interface (GUI), as compared to
»» Integrated inverter technology delivers high efficiency during VRV III.
part load conditions and provides precise individual zone »» VRV IV takes advantage of Daikin's unique zone and
control. centralized controls that are optimized for the specific
»» Design flexibility with long piping lengths up to 3,280 ft. needs of North America.
total, and up to 100 ft. vertical separation between »» Outstanding 10-Year Parts Warranty* as standard.
indoor units. * Complete commercial warranty details available from your local
distributor or manufacturer’s representative or at www.daikincomfort.com
»» Corrosion resistant 1000 hr. salt-spray tested Daikin PE or www.daikinac.com.
blue fin heat exchanger.
98 www.daikincomfort.com
VRV IV CERTIFIED DATA - HEAT PUMP, 208-230V/60HZ/3PH AND 460V/60HZ/3PH
EER Non-Ducted
Capacity (Tons)
EER Ducted
IEER Mixed
EER Mixed
RXYQ72T 6 25.80 20.70 23.25 3.67 3.30 3.49 2.44 2.25 2.35 14.70 12.70 13.70
RXYQ96T 8 27.30 22.50 24.90 4.00 3.49 3.75 2.63 2.48 2.56 14.00 12.60 13.30
RXYQ120T 10 25.40 22.00 23.70 3.50 3.30 3.40 2.25 2.37 2.31 12.00 11.60 11.80
RXYQ144T 12 24.80 22.60 23.70 3.64 3.34 3.49 2.33 2.20 2.27 12.10 11.50 11.80
RXYQ168T 14 22.60 19.80 21.20 3.34 3.20 3.27 2.34 2.27 2.31 10.60 10.60 10.60
RXYQ192T 16 22.20 21.20 21.70 3.62 3.29 3.46 2.27 2.23 2.25 11.10 11.60 11.35
RXYQ216T 18 20.50 21.10 20.80 3.83 3.50 3.67 2.57 2.46 2.52 10.70 10.90 10.80
RXYQ240T 20 20.80 20.90 20.85 3.63 3.33 3.48 2.41 2.34 2.38 11.00 11.20 11.10
RXYQ264T 22 20.30 19.60 19.95 3.33 3.24 3.29 2.43 2.30 2.37 10.30 9.60 9.95
RXYQ288T 24 20.10 19.60 19.85 3.25 3.30 3.28 2.07 2.13 2.10 10.50 10.10 10.30
RXYQ312T 26 19.90 18.80 19.35 3.30 3.21 3.26 2.32 2.20 2.26 9.80 9.60 9.70
RXYQ336T 28 20.60 18.50 19.55 3.22 3.20 3.21 2.38 2.27 2.33 9.50 9.50 9.50
RXYQ360T 30 19.40 18.50 18.95 3.46 3.20 3.33 2.47 2.36 2.42 10.30 9.80 10.05
RXYQ384T 32 21.10 18.50 19.80 3.30 3.20 3.25 2.28 2.27 2.28 9.50 9.50 9.50
RXYQ408T 34 21.10 19.00 20.05 3.24 3.20 3.22 2.18 2.10 2.14 9.50 9.50 9.50
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV Series.
OUTDOOR UNITS
The VRV IV Series has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy (DOE) and baseline efficiencies
as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED OPERATION RANGES FOR VRV IV RXYQ_T HEAT PUMP OUTDOOR UNITS LOW AMBIENT COOLING OPERATION FOR VRV IV RXYQ_T SINGLE
MODULE HEAT PUMP OUTDOOR UNITS
Cooling
Heating Cooling operation may Cooling
110
60 be extended from 23°F 110
ambient air temperature
100 down to 10°F. 100
Cooling operation
50 90
may be extended for
operation
operation
pull-down operation
continuous operation
pull-down operation
80
operation
pump systems under
continuous operation
up operation
operation
Outdoor temperature (˚F WB)
Outdoor temperature (˚F DB)
operation
forcontinuous
for pull-down
application rules, or 60
warmingup
70 30
for continuous
60
Range for
Range for
20
Rangefor
40
Range
Range
Range
Rangefor
Rangefor
Range
50 30
Range
Range
10
40 20
0 10
30
0
20 -10 -10
50 60 70 80 90 50 60 70 80 90 60 70 80
Indoor temperature (˚F WB) Indoor temperature (˚F DB) Indoor temperature (˚F WB)
100 www.daikincomfort.com
22 Ton 24 Ton 26 Ton 28 Ton 30 Ton 32 Ton 34 Ton
RXYQ264TATJU RXYQ288TATJU RXYQ312TATJU RXYQ336TATJU RXYQ360TATJU RXYQ384TATJU RXYQ408TATJU
RXYQ264TAYDU RXYQ288TAYDU RXYQ312TAYDU RXYQ336TAYDU RXYQ360TAYDU RXYQ384TAYDU RXYQ408TAYDU
1 x RXYQ168T 1 x RXYQ168T
1 x RXYQ144T 1 x RXYQ168T
2 x RXYQ144T 2 x RXYQ168T 3 x RXYQ120T 1 x RXYQ120T 1 x RXYQ144T
1 x RXYQ120T 1 x RXYQ144T
1 x RXYQ96T 1 x RXYQ96T
252,000 274,000 296,000 312,000 342,000 356,000 372,000
282,000 308,000 334,000 342,000 372,000 396,000 435,000
66 67 68 66 68
19.6 / 20.3 19.6 / 20.1 18.8 / 19.9 18.5 / 20.6 18.5 / 19.4 18.5 / 21.1 19.0 / 21.1
6286 + 8228 8228 + 8228 6286 + 6286 + 6286 5827 + 6286 + 8228 6286 + 6286 + 8228
0.12 / 0.32
3 4 3 4 5
(7008, 7608), (7680, 8280), 7650, (7008, 7608), (7680,
7746, (7008, 7608) (7008, 7608), (7680, 8280) 7746, 7746, 7746 7650, 7746, (7680, 8280)
(7008, 7608) (7680, 8280) 8280)
13-100 11-100 10-100 15-100 13-100 12-100
164 (295 With Field Setting)
OUTDOOR UNITS
100
541
620
3,280
Ø1-3/8 (34.9) C1220T (Brazing Connection) Ø1-5/8 (41.3) C1220T (Brazing Connection)
50 - 200
45 49 54 58 62 64
45 + 60 / 25 + 35 60 + 60 / 35 + 35 45 + 45 + 45 / 25 + 25 + 25 45 + 45 + 60 / 25 + 25 + 35 45 + 60 + 60 / 25 + 35 + 35
For additional technical information please refer to specific Engineering Data Books.
to 100 ft. vertical separation between indoor units Connects to cooling Connects to
»» Engineered with heat rejection cancellation technology2 tower and/or boiler Daikin’s line-up of
combination or set up VRV indoor units
to minimize mechanical room conditioning requirements
as geothermal.
»» Year round comfort and energy efficiency by
combining VRV and VRT technologies
»» Wide water temperature operation range - Can be
applied to both geothermal and boiler/tower applications
as standard with condenser water inlet temperature as
low as 14°F in heating and 23°F in cooling is possible.
»» 2-9V variable water flow control logic2 as standard to The condensers are
smaller and can be
increase waterside system operational efficiencies
stacked, reducing
»» Refrigerant cooled inverter technology to deliver the installation space
consistent and reliable PCB operations and increasing the
customers' usable
»» Easy commissioning with ability to program square footage.
settings off site using new configurator tool
»» 3-digit 7-segment digital display on the unit for improved
and faster configuration, commissioning, and troubleshooting
»» Engineered for easy service with drop-down switch box
to access key components
1
Model specific, check product specification for details
2
Refer to installation manual for field settings and other requirements
to activate this feature
VRV Water-Cooled System Series design is based on This is a simple system that allows manifolding together up
a modular design concept. It is composed of unified to three condensers to form one system of up to 36 tons.
condensing units that require simply connecting a two-pipe The condensers are designed for internal mounting only.
refrigerant network for heat pump applications or a three- * 6-ton model (RWEYQ72PC) is PC series. T and PC series models cannot be
pipe refrigerant network for heat recovery applications. combined to form multi-module systems.
102 www.daikincomfort.com
VRV T-SERIES WATER-COOLED CERTIFIED DATA, 208-230V/60HZ/3PH AND 460V/60HZ/3PH
EER Non-Ducted
System Name
SCHE Ducted
IEER Ducted
SCHE Mixed
EER Ducted
IEER Mixed
EER Mixed
Function
Tonnage
RWEYQ72PC 6 Tons 24.1 22.3 23.2 N/A N/A N/A 14.0 14.0 14.0 4.89 4.78 4.84
RWEQ96T 8 Tons 30.8 25.4 28.1 N/A N/A N/A 19.6 15.4 17.5 6.27 5.8 6.035
RWEQ120T 10 Tons 29.4 23.5 26.45 N/A N/A N/A 16 13.6 14.8 6.1 5.55 5.83
RWEQ144T 12 Tons 24.3 19.8 22.05 N/A N/A N/A 15.4 12.6 14.0 6.01 5.33 5.67
RWEQ192T 16 Tons 26.8 24.7 25.75 N/A N/A N/A 16.5 14.6 15.55 5.82 5.82 5.82
RWEQ216T 18 Tons 26.3 23.8 25.05 N/A N/A N/A 15.0 13.8 14.4 5.68 5.62 5.65
Heat Pump
RWEQ240T 20 Tons 25.7 22.7 24.2 N/A N/A N/A 14.0 12.8 13.4 5.52 5.38 5.45
RWEQ264T 22 Tons 23.5 2.00 21.75 N/A N/A N/A 13.5 12.1 12.8 5.34 4.96 5.15
RWEQ288T 24 Tons 20.9 18.8 19.85 N/A N/A N/A 12.6 11.3 11.95 5.3 4.81 5.06
RWEQ312T 26 Tons 21.9 21.8 21.85 N/A N/A N/A 13.7 12.7 13.2 5.5 4.86 5.18
RWEQ336T 28 Tons 21.5 21.4 21.45 N/A N/A N/A 13.5 12.3 12.9 5.42 4.73 5.08
RWEQ360T 30 Tons 21.2 20.2 20.7 N/A N/A N/A 12.4 11.7 12.05 5.3 4.7 5.0
RWEQ384T 32 Tons 19.5 17.9 18.7 N/A N/A N/A 12 11 11.5 4.53 4.12 4.33
RWEQ408T 34 Tons 18.2 17.2 17.7 N/A N/A N/A 11.1 10.7 10.9 4.35 4.03 4.19
RWEQ432T 36 Tons 17.0 16.6 16.8 N/A N/A N/A 10.5 10.3 10.4 4.19 3.92 4.06
RWEYQ72PC 6 Tons 24.1 22.3 23.2 17.8 19.2 18.5 14.0 14.0 14.0 4.89 4.78 4.84
RWEQ96T 8 Tons 30.8 25.4 28.1 25.7 21.3 23.5 19.6 15.4 17.5 6.27 5.8 6.035
RWEQ120T 10 Tons 29.4 23.5 26.45 26.3 22.5 24.4 16 13.6 14.8 6.1 5.55 5.83
RWEQ144T 12 Tons 24.3 19.8 22.05 26.5 22.7 24.6 15.4 12.6 14 6.01 5.33 5.67
RWEQ192T 16 Tons 26.8 24.7 25.75 26.0 22.9 24.45 16.5 14.6 15.55 5.82 5.82 5.82
RWEQ216T 18 Tons 26.3 23.8 25.05 25.5 22.1 23.8 15.0 13.8 14.4 5.68 5.62 5.65
Heat Recovery
RWEQ240T 20 Tons 25.7 22.7 24.2 25.4 21.9 23.65 14.0 12.8 13.4 5.52 5.38 5.45
RWEQ264T 22 Tons 23.5 2.00 21.75 25.2 19.2 22.2 13.5 12.1 12.8 5.34 4.96 5.15
RWEQ288T 24 Tons 20.9 18.8 19.85 23.5 20.0 21.75 12.6 11.3 11.95 5.3 4.81 5.06
RWEQ312T 26 Tons 21.9 21.8 21.85 24.5 20.7 22.6 13.7 12.7 13.2 5.5 4.86 5.18
RWEQ336T 28 Tons 21.5 21.4 21.45 23.5 20.0 21.75 13.5 12.3 12.9 5.42 4.73 5.08
RWEQ360T 30 Tons 21.2 20.2 20.7 23.2 19.1 21.15 12.4 11.7 12.05 5.3 4.7 5.0
OUTDOOR UNITS
RWEQ384T 32 Tons 19.5 17.9 18.7 22.0 19.1 20.55 12.0 11.0 11.5 4.53 4.12 4.33
RWEQ408T 34 Tons 18.2 17.2 17.7 21.2 18.5 19.85 11.1 10.7 10.9 4.35 4.03 4.19
RWEQ432T 36 Tons 17.0 16.6 16.8 20.5 17.7 19.1 10.5 10.3 10.4 4.19 3.92 4.055
Certified efficiency data in accordance with ANSI/AHRI Standard 1230 2014, “Performance Rating of Variable Refrigerant Flow Multi-Split Air Conditioning and Heat Pump Equipment” for the VRV T-Series Water-Cooled.
The VRV T-Series Water-Cooled has been designed and optimized to meet or exceed the latest minimum efficiency requirements in 10 C.F.R. Part 431 as determined by the U.S. Department of Energy (DOE) and
baseline efficiencies as defined by ASHRAE 90.1 2016. Systems under 65MBH are currently certified to AHRI 210/240. IEER ratings are as defined in ASHRAE 90.1 2016.
DETAILED STANDARD OPERATION RANGES FOR VRV T-SERIES WATER-COOLED CONDENSING UNITS
Cooling
Range Range
operation
Inlet water temperature (˚F)
continuous operation
operation
pull-down operation
for continuous
90 90 90
for warming
for pull-down
80 80 80
Rangefor
Range for
Range for
Range
Range
70 70 70
Range
60 60 60
Range for Range for Range for
operation operation operation
50 50 50
60 70 80 90 50 60 70 80 90 50 59 80 (Heating unit / ˚F DB)
Indoor temperature (˚F WB) Indoor temperature (˚F DB)
(Cooling unit / ˚F WB) 57 77 82
Indoor temperature
See the Engineering Data book for complete application rules and extended geothermal operation ranges
Performance
Power V/ph/Hz 208-230/3/60
Sound Pressure Level @ 3 ft. dB(A) 50 54 55 60.5 57 57.5 58
System Configuration: Heat Pump:
HP HR HP HR HP HR HP HR HP HR HP HR HP HR
HP, Heat Recovery: HR
Liquid Pipe (Main Line) in. 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8
Suction Gas Pipe (Main Line) in. 3/4 5/8 7/8 3/4 1-1/8 3/4 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8
Refrigerant Piping Discharge Gas Pipe (Main Line) in. N/A 3/4 N/A 7/8 N/A 1-1/8 N/A 1-1/8 N/A 1-1/8 N/A 1-1/8 N/A 1-3/8
Vertical Pipe Length
ft. 164 (130) 164 (130)
(if unit is below FCU)
Actual Pipe Length (Equivalent Length) ft. 390 (459) 540 (623)
Total Pipe Length ft. 980 980
Standard Connectable Indoor Unit Ratio % 50 - 130 50 - 150 4
Connection Ratio
Maximum Number of Indoor Units Qty. 12 16 20 25 33 37 41
BPHE Inlet Pipe (Female Thread) in. 1-1/4 1-1/4 1-1/4 1-1/4 2 x 1-1/4 2 x 1-1/4 2 x 1-1/4
BPHE Outlet Pipe (Female Thread) in. 1-1/4 1-1/4 1-1/4 1-1/4 2 x 1-1/4 2 x 1-1/4 2 x 1-1/4
Drain Pipe (Female Thread) in. 1/2 3/8 3/8 3/8 2 x 3/8 2 x 3/8 2 x 3/8
Maximum System Water
psi 285 464
Pressure (BPHE)
Water Side
(Standard) Standard Inlet Water
°F 50 - 113
Temperature Range Cooling
Standard Inlet Water
°F 50 - 113
Temperature Range Heating
Recommended Inlet Water Flow
gpm 13.2 ~ 39.6
Rate per Module (minimum)5
Inlet Water Temperature
°F 27 - 113 23 - 113
Range Cooling6
Water Side
Inlet Water Temperature
(Geothermal) °F 14 - 95 14 - 95
Range Heating6
Water Flow Rate5 gpm 21.2 - 39.6 21.2 - 39.6
Weight lbs. 330 419 423 423 2 x 419 419 + 423 2 x 423
Unit 39-3/8 x 30-3/4 x
Dimensions (H x W x D) in. 38-9/16 x 30-1/8 x 22-1/16 38-9/16 x (30-1/8 x 2) x 22-1/16
21-11/16
Voltage Range (min - max) V 187 - 253
Maximum Overcurrent Protection (MOP) A 30 35 45 50 35 + 35 35 + 45 45 + 45
Electrical
Minimum Circuit Amps (MCA) A 22.4 28.8 36.5 44.6 28.8 + 28.8 28.8 + 36.5 36.5 + 36.5
Compressor Rated Load Amps (RLA) A 11.6 19 20.9 29.4 19 + 19 19 + 20.9 20.9 + 20.9
Compressor Type Daikin G-Type Scroll Daikin K-Type Scroll
Compressor Compressor Set-Up 1 INV 1 INV + 1 INV
Compressor Capacity Control % 23 - 100 16 - 100 14 - 100 11 - 100 8 - 100 8 - 100 7 - 100
1
Some features and benefits may not be available for this model. ²Indoor temp.: 80°FDB, 67°FWB/inlet water temp.: 3
Indoor temp.: 70°FDB, 60°FWB/inlet water temp.:
Please contact your local Daikin sales representative for more details. 85°F/ Equivalent piping length : 25 ft., level difference : 0 ft. 70°F / Equivalent piping length: 25 ft., level difference : 0 ft.
104 www.daikincomfort.com
RWEQ_TATJU/TAYDU
OUTDOOR UNITS
208-230/3/60
61.5 63.5 59 59.5 60 62 64 65
HP HR HP HR HP HR HP HR HP HR HP HR HP HR HP HR
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-5/8 1-3/8 1-5/8 1-3/8 1-5/8 1-3/8 1-5/8 1-3/8
N/A 1-3/8 N/A 1-3/8 N/A 1-3/8 N/A 1-3/8 N/A 1-5/8 N/A 1-5/8 N/A 1-5/8 N/A 1-5/8
164 (130)
540 (623)
980
50 - 150 4
45 49 54 58 62 64 64 64
2 x 1-1/4 2 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4
2 x 1-1/4 2 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4
2 x 3/8 2 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8
464
50 - 113
50 - 113
13.2 ~ 39.6
23 - 113
14 - 95
21.2 - 39.6
2 x 423 2 x 423 2 x 419 + 423 419 + 2 x 423 3 x 423 3 x 423 3 x 423 3 x 423
38-9/16 x (30-1/8 x 2) x 22-1/16 38-9/16 x (30-1/8 x 3) x 22-1/16
187 - 253
45 + 50 50 + 50 35 + 35 + 45 35 + 45 + 45 45 + 45 + 45 45 + 45 + 50 45 + 50 + 50 50 + 50 + 50
36.5 + 44.6 44.6 + 44.6 28.8 + 28.8 + 36.5 28.8 + 36.5 + 36.5 36.5 + 36.5 + 36.5 36.5 + 36.5 + 44.6 36.5 + 44.6 + 44.6 44.6 + 44.6 + 44.6
20.9 + 29.4 29.4 + 29.4 19 + 19 + 20.9 19 + 20.9 + 20.9 20.9 + 20.9 + 20.9 20.9 + 20.9 + 29.4 20.9 + 29.4 + 29.4 29.4 + 29.4 + 29.4
Daikin K-Type Scroll
1 INV + 1 INV 1 INV + 1 INV + 1 INV
6 - 100 5 - 100 5 - 100 5 - 100 5 - 100 4 - 100 4 - 100 4 - 100
4
Varies based on indoor and condensing unit model 5
Please note that a water strainer (standard accessory for the 6
Application rules apply below 50°F. Please contact your local
selected; refer to Engineering Manual for details. T-series, field supplied for the PC-series) is required for each Daikin sales representative for design assistance and approval.
condensing unit model.
Performance
Power V/ph/Hz 460/3/60
Sound Pressure Level @ 3 ft. dB(A) 50 54 55 60.5 57 57.5 58
System Configuration: Heat
HP HR HP HR HP HR HP HR HP HR HP HR HP HR
Pump: HP, Heat Recovery: HR
Liquid Pipe (Main Line) in. 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8
Suction Gas Pipe (Main Line) in. 3/4 5/8 7/8 3/4 1-1/8 3/4 1-1/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8
Refrigerant Piping Discharge Gas Pipe (Main Line) in. N/A 3/4 N/A 7/8 N/A 1-1/8 N/A 1-1/8 N/A 1-1/8 N/A 1-1/8 N/A 1-3/8
Vertical Pipe Length
ft. 164 (130) 164 (130)
(if unit is below FCU)
Actual Pipe Length (Equivalent Length) ft. 390 (459) 540 (623)
Total Pipe Length ft. 980 980
Connection Standard Connectable Indoor Unit Ratio % 50 - 130 50 - 150 4
Ratio Maximum Number of Indoor Units Qty. 12 16 20 25 33 37 41
BPHE Inlet Pipe (Female Thread) in. 1-1/4 1-1/4 1-1/4 1-1/4 2 x 1-1/4 2 x 1-1/4 2 x 1-1/4
BPHE Outlet Pipe (Female Thread) in. 1-1/4 1-1/4 1-1/4 1-1/4 2 x 1-1/4 2 x 1-1/4 2 x 1-1/4
Drain Pipe (Female Thread) in. 1/2 3/8 3/8 3/8 2 x 3/8 2 x 3/8 2 x 3/8
Maximum System Water
psi 285 536.6
Pressure (BPHE)
Water Side
Standard Inlet Water
(Standard) °F 50 - 113
Temperature Range Cooling
Standard Inlet Water
°F 50 - 113
Temperature Range Heating
Recommended Inlet Water Flow
gpm 13.2 ~ 39.6
Rate per Module (minimum)5
Inlet Water Temperature
°F 27 - 113 23 - 113
Range Cooling6
Water Side
Inlet Water Temperature
(Geothermal) °F 14 - 113 14 - 95
Range Heating6
Water Flow Rate5 gpm 21.2 - 39.6 21.2 - 39.6
Weight lbs. 343 426 430 430 2 x 426 426 + 430 2 x 430
Unit 39-3/8 x 30-3/4 x
Dimensions (H x W x D) in. 38-9/16 x 30-1/8 x 22-1/16 38-9/16 x (30-1/8 x 2) x 22-1/16
21-11/16
Voltage Range (min - max) V 414 - 506
Maximum Overcurrent Protection (MOP) A 15 15 20 25 15 + 15 15 + 20 20 + 20
Electrical
Minimum Circuit Amps (MCA) A 10.2 13 16.5 20.2 13 + 13 13 + 16.5 16.5 + 16.5
Compressor Rated Load Amps (RLA) A 5.3 8.6 9.4 13.3 8.6 + 8.6 8.6 + 9.4 9.4 + 9.4
Compressor Type Daikin G-Type Scroll Daikin K-Type Scroll
Compressor Compressor Set-Up 1 INV 1 INV + 1 INV
Compressor Capacity Control % 23 - 100 16 - 100 14 - 100 11 - 100 8 - 100 8 - 100 7 - 100
1
Some features and benefits may not be available for this model. ²Indoor temp.: 80°FDB, 67°FWB/inlet water temp.: 3
Indoor temp.: 70°FDB, 60°FWB/inlet water temp.:
Please contact your local Daikin sales representative for more details. 85°F/ Equivalent piping length : 25 ft., level difference : 0 ft. 70°F / Equivalent piping length: 25 ft., level difference : 0 ft.
106 www.daikincomfort.com
RWEQ_TATJU/TAYDU
OUTDOOR UNITS
460/3/60
61.5 63.5 59 59.5 60 62 64 65
HP HR HP HR HP HR HP HR HP HR HP HR HP HR HP HR
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8 1-5/8 1-3/8 1-5/8 1-3/8 1-5/8 1-3/8 1-5/8 1-3/8
N/A 1-3/8 N/A 1-3/8 N/A 1-3/8 N/A 1-3/8 N/A 1-5/8 N/A 1-5/8 N/A 1-5/8 N/A 1-5/8
164 (130)
540 (623)
980
50 - 150 4
45 49 54 58 62 64 64 64
2 x 1-1/4 2 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4
2 x 1-1/4 2 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4 3 x 1-1/4
2 x 3/8 2 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8 3 x 3/8
536.6
50 - 113
50 - 113
13.2 ~ 39.6
23 - 113
14 - 95
21.2 - 39.6
2 x 430 2 x 430 2 x 426 + 430 426 + 2 x 430 3 x 430 3 x 430 3 x 430 3 x 430
38-9/16 x (30-1/8 x 2) x 22-1/16 38-9/16 x (30-1/8 x 3) x 22-1/16
414 - 506
20 + 25 25 + 25 15 + 15 + 20 15 + 20 + 20 20 + 20 + 20 20 + 20 + 25 20 + 25 + 25 25 + 25 + 25
16.5 + 20.2 20.2 + 20.2 13 + 13 + 16.5 13 + 16.5 + 16.5 16.5 + 16.5 + 16.5 16.5 + 16.5 + 20.2 16.5 + 20.2 + 20.2 20.2 + 20.2 + 20.2
9.4 + 13.3 13.3 + 13.3 8.6 + 8.6 + 9.4 8.6 + 9.4 + 9.4 9.4 + 9.4 + 9.4 9.4 + 9.4 + 13.3 9.4 + 13.3 + 13.3 13.3 + 13.3 + 13.3
Daikin K-Type Scroll
1 INV + 1 INV 1 INV + 1 INV + 1 INV
6 - 100 5 - 100 5 - 100 5 - 100 5 - 100 4 - 100 4 - 100 4 - 100
4
Varies based on indoor and condensing unit model 5
Please note that a water strainer (standard accessory for the 6
Application rules apply below 50°F. Please contact your local
selected; refer to Engineering Manual for details. T-series, field supplied for the PC-series) is required for each Daikin sales representative for design assistance and approval.
condensing unit model.
Light Commercial
The VRV IV S-series system is a highly efficient solution for
small commercial buildings requiring heating and cooling of
up to 9 zones. A mix of ducted and duct-free indoor units
can be combined to provide individual comfort and ease
of installation.
108 www.daikincomfort.com
CERTIFIED PERFORMANCE DATA
Nominal Cooling Nominal Heating Heating COP Low Heating Heating COP
Model Number Indoor Units Combination EER 95F SEER HSPF
Capacity (BTU/h) Capacity (BTU/h) @ 47 °F Capacity (BTU/h) @ 17 °F
Non-Ducted Indoor Units 36,000 12.0 18.0 40,000 4.10 23,600 3.0 10.3
RXTQ36TAVJ9 Ducted Indoor Units 36,000 10.0 16.0 40,000 3.30 22,000 2.5 9.0
Mixed Ducted and Non-Ducted Indoor Units 36,000 11.0 17.0 40,000 3.70 22,800 2.8 9.7
Non-Ducted Indoor Units 48,000 10.3 18.0 52,000 4.00 32,200 3.0 10.0
RXTQ48TAVJU Ducted Indoor Units 48,000 9.4 16.0 52,000 3.35 32,000 2.7 9.0
Mixed Ducted and Non-Ducted Indoor Units 48,000 9.85 17.0 52,000 3.68 32,100 2.9 9.5
Non-Ducted Indoor Units 57,500 9.8 18.0 57,500 4.30 37,000 3.2 10.5
RXTQ60TAVJU Ducted Indoor Units 57,500 9.2 16.0 57,500 3.70 34,000 2.7 10.5
Mixed Ducted and Non-Ducted Indoor Units 57,500 9.5 17.0 57,500 4.00 35,500 3.0 10.5
OUTDOOR UNITS
Maximum vertical pipe length between IDU ft. 33 49
Actual Pipe Length (Equivalent Length) ft. 164 230
Total Piping Length ft. 820 984
Connectable Indoor Unit Ratio % 50-130
Connection Ratio
Number of Indoor Units Qty 6 8 9
Outdoor Unit Size (HxWxD) 39 x 37 x 12-5/8 39 x 37 x 12-5/8 52-15/16 x 35-7/16 x 12-5/8
Unit
Weight lbs. 172 176 225
Airflow CFM 2682 3741
Fan
Fan Motor Output and Quantity kW 0.20 x 1 0.070 X 2
Maximum Over Current Protection (MOP) A 25 35
Electrical Minimum Circuit Amps (MCA) A 17 29
Rated Load Amps (RLA A 15.3 19.0 23.2
Compressor Type Type Daikin Swing
Compressor
Capacity Control % 14-100
DETAILED OPERATION RANGES FOR VRV IV-S (RXTQ_TAVJU) HEAT PUMP OUTDOOR UNITS
Range for warming up operation
/ / AURORA™
Installation Space Examples »» If the number of units installed is more than that
»» The installation space requirement shown in shown in the pattern in the figure, install the
the figure is a reference for cooling. units so that there is no air short circuiting.
»» During installation, install the units using the most appropriate »» Consider the space needed for the refrigerant piping
of the patterns shown in the figure for the location in when installing the units, as determined by local codes.
question, taking into consideration human traffic and wind. »» If the space requirements in the figure do not apply,
contact your contractor or Daikin directly.
OUTDOOR UNITS
Notes
1. Heights of walls in case of Patterns 1 and 2: 3. When installing, the units
Front: 59in most appropriate pattern
Suction side: 19-5/8in should
Section 3 be selected in
Side: Height unrestricted. order to obtain the best
Installation space shown in this drawing is based on the fit in the space available,
NOTE: If more units are to be installed than are shown in Section 3, your layout should take account of the possibility of short
cooling operation at 95°F outdoor air temperature.
circuiting. always bearing in mind
When the design outdoor temperature exceeds 95°F or the the need to leave enough
load exceeds maximum ability because of much generation space for a person to pass
Section 3
load of heat in all outdoor unit, take the suction-side space between the units and wall and for the air to circulate freely.
more broadly than the space shown in this drawing. 4. The units should be installed to leave sufficient
NOTE:
2. If the aboveIf more
wallunits are toare
heights be installed
exceeded thanthen
are shown
h2/2 in Section
and h1/2 3, your layout should take account
space at the of the possibility
front of shor
for the field refrigerant piping
circuiting.
should be added to the front and suction side service spaces work to be carried out comfortably.
respectively as shown in the figure.
110 www.daikincomfort.com
1. In case of a single installation [inch.] 9. Ventilation space (refer to Engineering 11. Service space above the unit
2. In case of multiple unit installation Data Book for further details) for refrigerant piping (refer to
[inch.] 10. Secure spaces in the front, back, Engineering Data Book for
and top sides as same as the case of further details)
3. Top view
single installation.
4. Side view
5. Condensing unit
1 7
11-13/16
2
19-11/16
7
13-3/4
13/16
11-13/16
9 9 11-13/16 11-13/16
[3]
15-15/16 14-3/4
6 9
piping must be ample
11-13/16
36-7/16
38-9/16
35-7/16
enough to remove the front 5
2-15/16
11-13/16 11-13/16
13/16
6 6
panel.
35-7/16 22-1/16 19-11/16
8
13/16 13/16 13/16
13/16 3-15/16
OUTDOOR UNITS
9-13/16
10
4(1
00
4o )o
rm e
rm ore or
e ore e or
m ore
or or 4(1 e ) rm
m rm 00 or 00 0)o
or )o 4o )o rm 4(1 (50
4 00 rm rmo 20
4(1 ore
4 ore
The long piping length provides more design flexibility, which can match even large-sized buildings.
Max. equivalent
623 ft. 295 ft.
piping length (3-Ton: 213 ft.)
f g h i
Max. level difference
between the outdoor units 295 ft. †
98 ft.
and the indoor units
r
Max. 98 ft.
s Max. 49 ft.+
Max. level difference
100 ft. 49 ft.
between the indoor units (3-Ton: 33 ft.)
Piping for VRV IV X, VRV IV, VRV AURORA, and VRV IV-S
ACTUAL PIPING LENGTH EXAMPLE EQUIVALENT PIPING LENGTH
VRV IV X / VRV IV / VRV AURORA VRV IV-S VRV IV X / VRV IV / VRV AURORA VRV IV-S
3-Ton 4-5 Ton 3-Ton 4-5 Ton
Refrigerant piping length 541 ft. 164 ft. 230 ft. a+b+c+d+e 623 ft 213 ft 295 ft
Total piping length 3281 ft. AURORA: 1640 ft. 820 ft. 984 ft. a+b+c+d+e+f+g+h+i – – –
Maximum allowable
piping length Between the first indoor unit
branch and the farthest 295 ft.* 98 ft. 98 ft. b+c+d+e – – –
indoor unit
112 www.daikincomfort.com
Water-cooled system piping length
Water-Cooled systems provide considerable design flexibility
with total piping lengths of up to 980 ft. and vertical separation of
up to 164 ft.* between condensing units and indoor units.
Water piping
Refrigerant piping REFRIGERANT PIPING LIMITATIONS LIMITATIONS
Linear piping between condensing unit and furthest
540 (623)
located fan coil unit (equivalent), ft.
Level difference between Total “one-way” piping in the complete piping network, ft. 980
indoor units: 98 ft. Vertical (height) separation between the condensing unit
164 (130)
Level difference between the and the fan coil units (if condensing unit is below)*, ft.
OUTDOOR UNITS
VRV T-Series Water Cooled and indoor units: Vertical (height) separation between fan coil units, ft. 98
164 ft. if the condensing unit is above Linear piping between 1st REFNET and furthest located
130 (295)**
130 ft. if the condensing unit is below fan coil unit, ft.
* Conditions apply when the condenser is lower than indoor units. Refer to your local Daikin
representative for further information.
** Conditions/rules apply. Refer to Installation manual for further details.
Indoor installation of condensing unit
Water piping length depends on the heat source equipment
Daikin's branch selector boxes are ideal for spaces that require individual
heating and cooling control.
114 www.daikincomfort.com
TECHNICAL DATA FOR MULTI-PORT BRANCH SELECTOR BOXES
Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS12Q54TVJ
Number of branches 4 6 8 10 12
Maximum capacity index per branch 54
Maximum total capacity index 144 216 290
Maximum connectable indoor units per branch 5
Liquid in. Ø1/4, Ø3/8
IU
Gas in. Ø1/2, Ø5/8
Connecting
Liquid in. Ø3/8 Ø1/2 Ø5/8
Pipes
IU Suction Gas in. Ø7/8 Ø1-1/8
HP/LP Gas in. Ø3/4 Ø1-1/8
Power Supply ph/V/Hz 1/208-230/60
Electrical Maximum Overcurrent Protection, MOP A 15
Minimum Circuit Amps, MCA A 0.6 0.8 1 1.2
Mass (Weight) lbs. 49 68 73 101 106
Dimensions (H x W x D) in. 11-3/4 x 14-9/16 x 18-15/16 11-3/4 x 22-13/16 x 18-15/16 11-3/4 x 32-5/16 x 18-15/16
Field Specific
Minimum
(B) Clearance
(A)
OUTDOOR UNITS
Model BSQ36TVJ BSQ60TVJ BSQ96TVJ
Number of branches 1 1 1
Maximum capacity index 36 60 96
Maximum connectable indoor units 4 8 8
Liquid in. Ø3/8
IU
Gas in. Ø5/8 Ø7/8
Connecting
Liquid in. Ø3/8
Pipes
IU Suction Gas in. Ø5/8 Ø7/8
HP/LP Gas in. Ø1/2 Ø3/4
Power Supply ph/V/Hz 1/208-230/60
Electrical Maximum Overcurrent Protection, MOP A 15
Minimum Circuit Amps, MCA A 0.1
Mass (Weight) lbs. 27 27 33
Dimensions (H x W x D) in. 8-1/8 x 15-1/4 x 12-13/16
(B)
(C) (D)
(A)
(E)
MINIMUM CLEARANCE BSQ36TVJ BSQ60TVJ BSQ96TVJ
A in. 10 10 12
B in. 10 10 12
C in. - 13-3/4 15-3/4
D in. 12 13-3/4 15-3/4
E in. 12 12 11-13/16
For additional technical information and all equipment installation and application limitations please refer to the specific Engineering Data Books.
REFNET
REFNET joints distribute correct flow of refrigerant
in every branch of the piping network.
VRV IV Heat Pump / VRV AURORA™ Heat Pump REFNET Joint REFNET Header
RXYQ192T RXYQ312T
RXYQ72T RXYQ120T
RXYQ216T RXYQ336T RXYQ360T
RXYQ96T RXYQ144T
OPTIONAL ACCESSORIES RXYQ240T RXLQ144T RXYQ384T
RXLQ72T RXYQ168T
RXYQ264T RXLQ192T RXYQ408T
RXLQ96T RXLQ120
RXYQ288T RXLQ240T
KHRP26M22H (max. 4 branch)
KHRP26M22H (max. 4 branch)
KHRP26M22H (max. 4 branch) KHRP26M33H (max. 8 branch)
Distributed REFNET Header KHRP26M33H (max. 8 branch)
KHRP26M33H (max. 8 branch) KHRP26M72H (max. 8 branch)
piping KHRP26M72H (max. 8 branch)
KHRP26M73H (max. 8 branch)
REFNET Joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26M72TU KHRP26A22T, KHRP26A33T, KHRP26M72TU, KHRP26M73TU
Outdoor unit multi connection piping kit — BHFP22P100U BHFP22P151U
VRV IV X Heat Recovery / VRV IV Heat Recovery / VRV AURORA™ Heat Recovery
REYQ192T
OUTDOOR UNITS
REYQ216T REYQ360T
REYQ72T REYQ120T REYQ240T REYQ384T
REYQ144T REYQ264T REYQ408T
REYQ96T REYQ168T REYQ288T REYQ432T
RELQ72T REYQ312T REYQ456T
REYQ336T RELQ144T
OPTIONAL ACCESSORIES RELQ96T RELQ120T RELQ192T
REYQ192X RELQ240T
REYQ216X REYQ360X
REYQ120X REYQ240X REYQ384X
REYQ72X
REYQ144X REYQ264X REYQ408X
REYQ96X
REYQ168X REYQ288X REYQ432X
REYQ312X REYQ456X
REYQ336X
116 www.daikincomfort.com
VRV Accessories
REFNET Pipe Joints &
Hail Guard Kit for VRV IV
OUTDOOR UNITS
The optional hail guard kit for VRV IV and VRV AURORA enables optimal airflow for efficient heat transfer while providing
condenser coil protection from hail damage in severe climates. Each hail guard kit, that is field installed, consists of 4 panels
(Right, Left, Front and Back).
KIT PART NUMBER QUANTITY OF KITS PER ODU MODELS PANEL DIMENSIONS (H X W X D)
R_YQ72T R_YQ96-168T R_YQ192T R_YQ216-336T R_YQ360-456T
R_LQ72-120T R_LQ144-240T Right Panel Left Panel Front Panel Front Panel
R_YQ72-168X R_YQ192-336X R_YQ360-456X
VRV4HGS-K1 1 1 457/8" x 131/4" x 4" 457/8" x 325/8" x 4"
457/8" x 26" x 4" 457/8" x 127/8" x 4"
VRV4HGL-K1 1 1 2 3 457/8" x 24" x 4" 457/8" x 44 3/4" x 4"
Service space requirements for the front, back and sides of the
condensing unit must be at least 4" greater than the service
space requirements provided in the condensing unit installation
manual and engineering guide.
A kit consists of one Control Box and one EEV Box. Two different VRV Outdoor
Non-VRV
control methods can be used for an evaporator coil of up to Unit
Air Handling
16 tons.
Unit
Features and Benefits
»» Enables non-VRV Air Handling Units to be Control Box
OUTDOOR UNITS
* Important! For any VRV systems that utilize the AHU integration kits
to perform as intended, the DX coil(s) in the non-VRV AHU unit(s)
must meet the range of criteria set forth in the AHU Integration Kit
Selection Guide and all associated piping and combination rules
(refer to IOD-7041A and IOD-7042A), and should be installed in
accordance to the installation manual provided with the EKEQ
control boxes.
118 www.daikincomfort.com
ELECTRONIC
EXPANSION
EKEXV50-US EKEXV63-US EKEXV80-US EKEXV100-US EKEXV125-US EKEXV140-US EKEXV200-US EKEXV250-US EKEXV400-US EKEXV500-US
VALVE BOX
SPECIFICATIONS
Nominal Capacity BTU/h 18,000 24,000 30,000 36,000 48,000 60,000 72,000 96,000 144,000 192,000
AHU Heat
Exchanger
BTU/h 17,000-21,000 21,500-26,500 27,000-34,500 34,000-42,000 42,500-52,500 53,000-60,000 60,500-84,000 84,500-105,000 120,000-169,000 170,000-210,000
Cooling Capacity
Range
AHU Heat
Exchanger
BTU/h 19,000-24,000 24,200-30,000 30,500-38,000 38,500-47,000 47,500-59,000 59,500-67,500 68,000-94,500 95,000-118,500 136,000-187,500 188,000-236,500
Heating
Capacity Range
AHU Heat
Exchanger
in3 46-100 101-126 127-161 162-201 202-251 252-281 282-402 403-503 564-804 806-1006
Refrigerant
Volume Range
Power Supply V/ph/Hz 208-230/1/60
Weight lbs. 6.4
Height in. 15-3/4
Width in. 8-1/2
Depth in. 3-1/16
Pipe Connections in. 1/2 x 1/4 3/8 x 5/8 3/4 x 3/8 7/8 x 3/8 1-1/8 x 1/2 1-1/8 x 5/8
* Important! For any VRV systems that utilize the AHU integration kits to perform as intended, the DX coil(s) in the non-VRV AHU unit(s) must meet the range of criteria set forth in the AHU Integration
Kit Selection Guide and all associated piping and combination rules (refer to IOD-7041A and IOD-7042A), and should be installed in accordance to the installation manual provided with the
EKEQ control boxes.
OUTDOOR UNITS
air handling unit
»» Simplified installation with inlet and
outlet brazed connections
»» Wide range that covers from 1.5 ton to 16 ton
»» Same EEVs as used in standard VRV Indoor
product to deliver precise refrigerant control
EKEQMCBAV3 - US
For use with both Daikin VRV indoor
units and custom air handling units
VRV
»» Allows for discharge air control Indoor
»» Seamless integration of non-VRV air handling Unit
EKEQMCB
EKEQFCBAV3 - US
For use with custom air handling
units only BRC1E73
DDC Controller
(Field Supplied) W-Control
120 www.daikincomfort.com
Control Box
EKE_CBAV3-US (cont.)
OUTDOOR UNITS
EKEQMCBAV3-US EKEQFCBAV3-US EKEQMCBAV3-US EKEQFCBAV3-US
CONTROL BOX SPECIFICATIONS COMPATIBILITY MATRIX
(Z-Control) (W-Control) (Z-Control) (W-Control)
Entering Air Temperature Cooling °F 57 WB - 77 WB 95 DB/77 WB VRV IV HP (RXYQ_TATJU/TAYDU) ■ ■
Limits Heating °F 50 DB - 80 DB Min. of 50 DB VRV IV HR (REYQ_TATJU/TAYDU) ■ Not available
Power Supply V/ph/Hz 208-230/1/60 VRV T-Series Water-Cooled (RWEQ_TATJU/TAYDU) ■
Weight lbs. 8 8.6 VRV III PC (REYQ_PCTJ/PCYD) ■ Not available
Height in. 5-13/64 VRV IV S (RXTQ_TAVJU(9) Not available Not available
Width in. 15-3/4
Heat pump configuration only
Depth in. 9-3/8
Connection Ratio 50 - 110% 90 - 110%
EKEXV to AHU 16 ft. 16ft.
Max Piping Distance Standard VRV outdoor unit
ODU to AHU piping limitations based on 164 ft
model selection apply
Max number of IDU/system
VRV IDU + AHU 64 Not available
AHU Only 32 1
Daikin’s Outside Air Processing Unit can be integrated In addition to Outside Air Processing Units, we also offer
with a VRV system to provide outside air treatment and air Energy Heat Recovery units. The Energy Heat Recovery
conditioning in a single system to meet code requirements. VAM-GVJU series units combines compactness, energy
It adjusts the temperature of air from outdoors using a fixed conservation, and extensive operation range of outdoor
discharge temperature control reducing air conditioning load. temperatures. This series provides higher enthalpy
efficiency, due to the greatly enhanced performance
of the thin heat exchanging element. Furthermore,
improved external static pressure offers more flexibility
for installation.
124 www.daikincomfort.com
VENTILATION
OUTSIDE AIR PROCESSING UNIT, FXMQ_MFVJU ENERGY RECOVERY VENTILATOR, VAM-GVJU
»» The nominal airflow rates are 635, 988, and for air-conditioning
1,236 CFM respectively
»» External static pressure capabilities of up to 1.03" W.G.
allows for flexibility with duct work and filtration choices
»» The indoor unit is controlled to a set cooling and heating
discharge air temperature allowing the flexibility to
integrate with a standard Daikin indoor unit or duct
directly to the space
»» A low profile design of only 18.5" high reduces the required
installation space and can eliminate mechanical rooms or
additional structural supports associated with traditional
VENTILATION
OA systems
»» Indoor Air Quality options include MERV 8 and 13 filters
and filter boxes
»» Can be connected to all North American Daikin
VRV systems
»» Connects directly and seamlessly into the Daikin local Applications
and centralized controllers
»» Hotel/conference
Operational Characteristics centers
When the suction air temperature is between 66°F and 109°F, »» Schools
the Outside Air Processing Unit operates in cooling, and »» Retail shopping
when between 23°F and 59°F, it operates in heating. The OA centers
processing unit will work in energy saving fan only between »» Large open- plan
offices
59°F and 66°F.
»» Churches
126 www.daikincomfort.com
FXMQ_MFVJU SPECIFICATIONS 4 TON 6 TON 8 TON
Model Name FXMQ48MFVJU FXMQ72MFVJU FXMQ96MFVJU
Power Supply V/ph/Hz 208-230/1/60
Rated Cooling Capacity BTU/h 48,000 72,000 96,000
Rated Heating Capacity BTU/h 30,000 47,000 59,000
Airflow Rate CFM 635 988 1,236
Weight lbs. 190 271
Height in. 18-1/2
Width in. 29-1/4 54-3/8
Depth in. 43-5/16
Sound Pressure dB(A) 42 47
External Static Pressure in. Wg 0.88 0.96 1.03
Gas in. 5/8 3/4 7/8
Pipe Connections
Liquid in. 3/8
Fuse
Protection Devices
Fan Motor Thermal Protector
External Finish Galvanized Steel Plate
Operating Range - Cooling °F 66 DB/59 WB - 109 DB/90 WB
Operating Range - Heating °F 23 DB to 59 DB
Discharge Air Temp. - Cooling °F 55-77
Discharge Air Temp. - Heating °F 64-86
Nominal Conditions: Cooling Mode Heating Mode Note: Specifications are subject to change
Discharge Set Temperature: 64 °F DB Discharge Set Temperature: 77 °F DB without notice.
Outdoor: 91 °F DB, 82 °F WB (68% RH) Outdoor: 32 °F DB, 27 °F WB (50% RH)
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.
FXMQ_MFVJU ACCESSORIES
Model Name FXMQ48MFVJU FXMQ72MFVJU FXMQ96MFVJU
Navigation™ Remote Controller BRC1E73
Wireless Remote Controller BRC4C82
Remote Sensor Kit KRCS01-1B
Wiring Adaptor PCB (interface with aux/primary heater, humidifier, OA damper/fan) KRP1C74
Group Control Adaptor PCB (connects to external BMS) KRP4A71
High Efficiency Filter Kit (MERV 13) DACA-MQ48F131K DACA-MQ96F131K
High Efficiency Filter Kit (MERV 8) DACA-MQ48F-8-1K DACA-MQ96F-8-1K
VENTILATION
2.5" 2.5"
or more or more 25-9/16"
or more
Ceiling Ceiling
OA SA
128 www.daikincomfort.com
VAM SPECIFICATIONS
Model Name Airflow VAM300GVJU VAM470GVJU VAM600GVJU VAM1200GVJU
100 % 65 68 72
Cooling
Temperature Recovery 75 % 70 72 74
Efficiency Percentage 100 % 65 66 70
Heating
75 % 69 73
100 % 40 45 49
Cooling
Enthalpy Recovery 75 % 48 50 52
Efficiency Percentage 100 % 57 59 60
Heating
75 % 63 65 63
Power Supply V/ph/Hz 208-230/1/60
Heat Exchange Mode 300/300/170 470/470/390 600/600/500 1,200/1,200/930
Airflow Rate (H/M/L) CFM
Bypass Mode 300/300/170 470/470/390 600/600/500 1,200/1,200/930
Weight lbs. 71 121 148 346
Height in. 12-1/16 15-1/4 15-1/4 30-7/8
Width in. 34-5/8 43-11/16 63-3/4
Depth in. 31-1/2 32-3/4 47-13/16
Sound Pressure (H/M/L) dB(A) 37/33.5/25.5 42/38.5/35 42.5/39/36 44.5/41.5/38.5
External Static Pressure (H/M/L) in. Wg 0.64/0.26/0.16 0.73/0.39/0.33 0.76/0.34/0.32 0.56/0.24/0.16
External Finish Galvanized Steel Plate
Insulation Material Self-Extinguishing Urethane Foam
Connection Duct Diameter in. 8 10 14
Ambient Conditions A 5°F ~ 122°FDB 80% RH or less
21" or more
Energy Recovery
Ventilator
(Top View)
(Service space)
26" or more
44" or more
VENTILATION
(Service space)
130 www.daikincomfort.com
Controls
Simplified Wireless
Remote Controller Remote
(BRC2A71) Controller iTM™ (DCM601A71) iTC™ (DCS601C71)
Navigation™
Remote Controller
(BRC1E73)
Interface for
use in BACnet ®
(DMS502B71)
Adaptors
RA Interface
Adaptor
Wiring Adaptor External Control (KRP928BB2S)
(KRP1C74/75) Adaptor (DTA104A53)
132 www.daikincomfort.com
Daikin controls offer comfort control in
an easily managed and operated system.
CONTROLS
Multi-Zone Controllers
with iTC HTTP
Option (DCS007A51)
(DCS601C71)
(DCM601A71)
Interface for
use in BACnet
(DMS502B71)
Interface for
use in LonWorks®
(DMS504C71)
CONTROLS
DIII-Net/Modbus®
Adaptor
(DTA116A51)
Home automation
master controller
Interface Solutions
134 www.daikincomfort.com
VRV Indoor Unit Zone Controllers
Navigation™ Remote
Controller (BRC1E73)
DKN Cloud
Wi-fi Adaptor
DIII-NET
(Communications Transmission)
DIII-NET, Daikin’s unique communication
transmission system, links indoor units ERV
and various other building equipment –
in accordance with applications, scale Simplified Remote
and conditions and transmits vast Controller (BRC2A71)
amounts of information between them.
SkyAir
Wireless Remote
Controller
RA Interface
Mini-Split
Adaptor
(KRP928BB2S)
Complete Control of
CONTROLS
External Equipment with
Custom Programming
Daikin WAGO BACnet/IP
Controller (750-831) MicroTech III
Dedicated Outside Air Supply
(DOAS)
DDC
temperature.
Savings Time (DST) (enhanced)
-- Built in 7, 5+2, 5+1+1, and 1 (everyday) schedule -- In default, the secondary changeover temperature is
with up to 5 actions per day with independent 1° F above the primary changeover temperature
cooling, heating and setback setpoints for cooling or 1°F below the primary
changeover temperature for heating, which
»» More Features
is configurable between 1° F – 4° F.
-- Backlit display
-- Case 2 will happen while the guard
-- Room temperature sensor time is active in case 1.
-- 12/24 hour clock
-- Fahrenheit/Celsius selectable
-- English/French/Spanish languages selectable
-- Remote control group - up to 16 indoor units
136 www.daikincomfort.com
BRC1E73 - Navigation™ Remote Controller (continued)
Model CONTROLS
On/Off
Indoor unit is turned Occupant returns and
Off when no one indoor unit required to
BRC1E73 - Navigation™ Remote Controller (continued) detected in space be turned on manually
On
Energy saving
Unoccupied 2 hrs.
»» Automatic Off by occupancy sensor† »» Auto Setback by sensor†
Auto Off
-- The indoor unit will turn off -- The cooling and heating
when it is determined that the setpoints will graduallyEnergy
relaxsavings when
room is unoccupied
room is unoccupied after a (configurable) internally when
specified time has elapsed. the room is determined
0 2 T (hrs)
-- Can be used in conjunction to be unoccupied.
with the Auto Setback by sensor function -Occupied
- The internal setpoint will return to the original
Unoccupied Occupied
setpoint when room occupancy is detected.
Automatic Off energy savings Automatic setback energy savings
On/Off Cooling
Indoor unit is turned Occupant returns and Setpoint Setback setpoint
Off when no one indoor unit required to (°F) increases 2°F every 15 min.
Auto Setback Setpoint
0 2 T (hrs) 0 15 30 45 60 T (hr)
1)Cooling
8:30 ON 2) 10:30 OFF
Setpoint Setback setpoint
The first
(°F) period starts and the air
increases 2°F every 15 min.
In the second period, the classroom is
Auto Setback Setpoint
conditioner
80 starts the is
room cooling operation.
unoccupied unoccupied and the air conditioner stops.
Energy savings
78 when room is
unoccupied
Unoccupied
CONTROLS
76 15 min.
74
Occupied setpoint returned
when occupancy is detected
138 www.daikincomfort.com
Comfort Individual airflow direction
»» Individual airflow direction† (2)
-- Airflow direction of each of the four air Outlet mark
outlets can be controlled individually.
-- (Positions 0 to 4, Swing, and No individual setting
are selectable.) (3)
(1)
»» Auto airflow rate†
-- Airflow rate is automatically controlled in accordance
with the difference between room temperature and
set temperature.
(4)
†
nly available for VRV 4-Way Flow Ceiling Suspended type
O
FXUQ_P series and Ceiling Mounted Cassette (Round Flow (1) (2)
with Sensing) type FXFQ_T series.
(3) (4)
Summary
REMOTE CONTROLLER COMPATIBILITY WITH VRV INDOOR UNITS
FXFQ_TV FXZQ FXUQ FXDQ FXSQ FXMQ FXHQ FXAQ FXL(N)Q FXTQ FXEQ
Navigation™ remote controller (Wired remote controller) n n n n n n n n n n n
Wireless remote controller (Installed type signal receiver unit) n n n
Wireless remote controller (Separate type signal receiver unit) n n n n
Simplified remote controller n n n n n n n n n n n
DKN Cloud Wi-Fi Adaptor n n n n n n n n n n n
140 www.daikincomfort.com
INDIVIDUAL CONTROL CAPABILITIES
System Capabilities Daikin Controls Options
BRC1E73 BRC2A71
DKN Cloud Wi-Fi Adaptor Navigation™ Simplified Wired Wireless Remote Controller
(AZAI6WSCDKA) Remote Controller Remote Controller (model depends on unit)
Communications 2 Wire / DIII Net 2 Wire / DIII Net 2 Wire / DIII Net Infrared
°F/°C Selector n n °F only °F only
Backlit LCD display n
Room temperature display n n
Schedule and setback capabilities (with Time and Date display) n n
User restriction options n
On/Off, Operation mode, Setpoint, Fan speed n n n n
Louver position adjustment n n
Reports system malfunctions n n n n
Space temperature sensor n n
Simultaneous operation with Daikin multi-zone controllers n n n n
Simultaneous operation with BACnet® and LonWorks® n n n n
Group control capacity Up to 16 indoor units Up to 16 indoor units Up to 16 indoor units Up to 16 indoor units
By providing individual zone control, the occupant of each space has the
ability to set the room temperature where they feel most comfortable.
CONTROLS
based upon tenant (Indoor Unit) demand using the PPD iTM to use the BACnet IP protocol
Software option (DCM002A71).
-- Allows for full monitoring and control of 3rd party
Features BACnet capable equipment
»» 10.4" LCD touch screen, USB drive -- Up to 512 BACnet management points
»» Advanced, scalable and cost-effective management system
-- Up to 650 points (max 512 indoor unit groups »» iTM BACnet Server Gateway Option (DCM014A51)
-- Enable BMS to control indoor units and/or monitor
(1024 indoor units)
outdoor unit operation via BACnet/IP (up to a total of
-- Floor plan layout view 128 BACnet device IDs and 4000 BACnet objects)
Functions -- Virtual router function embedded that enables
»» Dual setpoints or Single setpoint in Occ or Setback in Unocc individual and configurable BACnet device ID for each
»» Setpoint Range Limitation indoor unit group address and each outdoor unit.
142 www.daikincomfort.com
iTM™ System Overview
BACnet®/IP BMS
Web access
Ethernet
Integration of Third BACnet Server Gateway Full Control of Daikin
Party Equipment (DCM014A51) VRV System
Up to 512 groups
Fire alarm (1024 indoor units)
Di/Pi port
kWh meter
Ethernet (BACnet/IP)
DIII-NET
DCM601A71
one DIII-NET system
RS485 RS485 Max. 64 indoor unit groups (128 indoor units)
BACnet Client Option
(DCM009A51)
iTM™ Plus Adapter
Max. 64 indoor unit groups
WAGO I/O ®
Di/Pi port
Lighting Fan Max. 64 indoor unit groups
CONTROLS
Up to 7 adaptors
Dedicated Outside Air Supply
(DOAS)
144 www.daikincomfort.com
iTC™ system overview
Key card
Digital input
(DI) unit Occupancy
sensor
Ancillary
equipment
Digital input/output
(DIO) unit
Emergency/forced
shutdown D
Damper
DIII-Net Plus
Adapter
Energy meter
Power Proportional Distribution (PPD)
- apportions total outdoor unit power consumption PC
among indoor units with optional PPD software
CONTROLS
146 www.daikincomfort.com
DCS301C71 - Unified On/Off Controller DST301BA61 - Schedule Timer
Maximum 16 groups of indoor Maximum 128 indoor units can be
units can be operated operated by programmed schedule.
simultaneously/individually. »» Maximum 128 indoor
»» Maximum 16 groups (128 units controllable
indoor units) controllable »» When used in combination with
»» Operating status indication a Central Remote Controller, a
(Normal operation, Alarm) maximum of 8 weekly schedule
»» Centralized control indication patterns can be set, while the
Central Remote Controller can be used to select
»» Maximum wiring length 3280 ft. (total: 6560 ft.)
desired zones. Up to 2 ON/OFF pairs can be set per day.
»» Compact size casing (thickness: 0.63in)
»» Maximum 48 hours back up power supply
»» Connectable with Central Remote Controller,
»» Maximum wiring length 3280 ft. (total: 6560 ft.)
Schedule Timer and BMS system
»» Compact size casing (thickness: 0.63in)
»» Connectable with Central Remote Controller,
Unified ON/OFF controller and BMS system
CONTROLS
The Central Controllers can monitor and control indoor units by either
group or zone. Their easy-to-read liquid crystal displays (LCDs) allow you
to orchestrate and monitor temperature, time, and airflow volume, etc.
across your entire system at the touch of button.
MicroTech III
DOAS System
(BACnet/IP)
Ethernet
VRV System
Third Party
CONTROLS
devices/equipment
Di/Do/Ai/Ao contacts
750-831
Daikin WAGO ® BACnet/IP
Controller
148 www.daikincomfort.com
External Equipment
Control (cont.)
750-831 - Daikin WAGO® BACnet ®/IP Controller Daikin’s VRV Marketing Controls Group will provide
The Daikin WAGO BACnet/IP Controller (750-831) is a customizable programming (programming and commission
programmable controller that connects the WAGO I/O system fees apply) for applications where external equipment
to the BACnet protocol. This controller provides the three control is needed. The following application programs are
following functionalities: now available:
»» Native server: BACnet objects »» Water-Cooled VRV Valve Control: Valve control for
are generated automatically for Water-Cooled VRV project
the DI, DO, AI, AO modules that »» Ambient Enclosure Heater Control: Damper and
are connected to the controller. auxiliary heater control for outdoor unit dog house
»» Application server: Other projects in cold climate
supported BACnet objects »» Trending: Trending Client for VRV
can be created via program-
»» Custom programming available to fit individual
ming and made available to
project needs
a BACnet network.
»» Application client: Using the client
functionality, BACnet objects 750-831
Daikin WAGO BACnet/IP
and the properties of the external Controller
equipment can be accessed.
CONTROLS
BMS
Ethernet (BACnet®/IP)
150 www.daikincomfort.com
Powerful Service Tool with Indoor and Outdoor Unit Operation Data Points
Object instance number repeated for Occupancy Mode = MO 1 (All indoor units)
every indoor unit point Unit On Off Status = BI 2 (All indoor units)
DMS502B71 - Interface for use in BACnet ® DMS504C71 Interface for use in LonWorks®
»» BACnet: Building Automation and Control Networks »» BMS interface based on LonTalk
-- Standard open protocol based on ANSI/ASHREA »» Interface between Daikin DIII-Net and BMS LonTalk
Standard 135 work station
»» Monitor/Control indoor unit’s points -- Manages up to 64 indoor unit groups (128 indoor
»» Monitor/Control up to 256 indoor units groups units)with network variables for each group
(512 indoor units) -- Manages 1 DIII-Net system
®
»» Certified by BACnet Testing Laboratories (BTL) »» Lon Interface communicates over twisted pair wire
»» Manage up to 4 DIII-Net systems »» External Interface File (XIF) documents device information
-- Option Board (DAM411B51) required available at www.daikinac.com
»Lift in BACnet )
®
in LonWorks )
®
Adapter)
»Pump
»Lighting, etc.
†
BACnet® is a registered trademark of the American
Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE). Energy recovery
Central Controller ventilator
‡
LonWorks ® is a trademark of Echelon Corporation
registered in the United States and other countries.
‡
Modbus ® is a registered trademark of Modicon, Inc.
152 www.daikincomfort.com
VRV Monitoring Services
CONTROLS
Individual Controllers
ITEM MODEL NO. FUNCTION
Navigation™ Remote Controller BRC1E73 Programmable zone controller
DKN Cloud Wi-Fi Adaptor AZAI6WSCDKA Remote control by smartphone app
BRC4C82
BRC7C812
Wireless Remote Controller
BRC7E818 Hand-held zone controller with infrared receiver kit
BRC7E83
BRC7E830
Simplified Remote Controller BRC2A71 Non-programmable zone controller
Optional DIII board DAM411B51 Expansion kit, installed on DMS502B71, to provide 2 more DIII-NET communication ports. Not usable independently.
Interface unit to allow communications between VRV and BMS.
Interface for use in LonWorks® DMS504C71
Operation and monitoring of air-conditioning systems through LonWorks communication
Use of the Modbus protocol enables the connection of the VRV system with a variety of home automation and BMS systems
Interface for use in Modbus® DTA116A51
from other manufacturers.
154 www.daikincomfort.com
Adaptors
ITEM MODEL NO. FUNCTION
Digital Input (Di) Unit DEC101A51-US2 Monitor On/Off and Error status of ancillary equipment
Digital Input/Output (Dio) Unit DEC102A51-US2 Monitor and control of ancillary equipment
Apply to increase the number of outdoor units (up to another 10) connected in one DIII-Net system.
DIII-Net Expander Adaptor DTA109A51
Apply to overcome communication errors in electrically noisy environments.
Unification Adaptor for Turn On/Off the system from a central panel through Centralized Controller or iTouch Controller.
DCS302A72
Computerized Control Monitor On/Off and Error Status.
External control Adaptor Unified changeover of Cool/Heat mode. To change the mode of several outdoor units by one remote controller.
DTA104A53/61/62
for Outdoor Unit Demand Control. Low Noise Control: -2 to 3 dB of outdoor unit
Turn On/Off Remote Control Group. Change setpoint (with resistance interface 0-135 ohm).
Group Control Adaptor KRP4A71/72/73/74
Monitor On/Off and Error status
Remotely manage the operating mode of the heat pump system. Integration point for ambient
ABC Terminal Kit BRP2A81
thermostats to engage lock-out
Wiring Adaptor KRP1C74/75 Thermo-on status. Fan status. AUX heater output. Humidifier output
RA Interface Adaptor for DIII-Net Use KRP928B2S Mini-split can be controlled through DIII-NET
RA PCB Adaptor for Time Clock KRP413A1S Remotely Start / Stop for mini-split indoor units
CONTROLS
PART NUMBER NAME DESCRIPTION
750-831 Daikin WAGO BACnet/IP Controller WAGO BACnet/IP Controller
759-302/000-923 WAGO I/O Check USB kit WAGO I/O Check CD ROM and service cable
787-712 24 VDC Power Supply 24 VDC Power Supply
750-600 End Module WAGO End Module
Daikin’s array of software and support tools are designed to streamline all
stages of project design, application, installation and service/maintenance.
Daikin provides multiple tools to aid the design, The tools have been designed to be simple to use, easily
accessible and to address the various considerations and
selection, analysis, submission, and general
steps in the evolution of a residential or commercial project,
support for its line up of ductless, rooftop, light aimed at helping the architect, consulting engineer, contractor,
commercial split and specifically for the full line installation technician, and service company to enhance
workflows and general project execution.
of Daikin VRV systems.
SUPPORT & TOOLS
158 www.daikincomfort.com
CATEGORIES
Selection
After sales
Design and
verification
and service
and simulation
data, submittal)
reference (spec,
Smartphone and
mobile reference
Online and tablet
Energy screening
n
Daikin VRV support and tools overview
WebXpress
TOOLS
n
Ventilation Xpress
n Controls Configurator
n
Online Energy Calculator
n
IES-VE Daikin VRV plug-in
Performance curves for third-party
n energy simulation Programs
n
Revit models
n
Reference Charge Calculator
n
n
IOMS etc.)
n
Daikin eQuip application
n
Dr. Daikin
n
VRV Configurator
n
Service Checker
n
Online Spare Parts Bank
159
SUPPORT & TOOLS
Support and Tools (cont.)
160 www.daikincomfort.com
Revit www.DaikinCity.com
and installers to optimize the life cycle cost of the VRV systems.
162 www.daikincomfort.com
Daikin VRV Configurator Daikin’s online spare parts databank
164 www.daikincomfort.com
Notes
166 www.daikincomfort.com
COMMERCIAL ■ R E N OVAT I O N ■ NEW CONSTRUCTION
About Daikin:
WARNINGS:
»» Always use a licensed installer or contractor to install »» Read the User’s Manual carefully before using this
this product. Do not try to install the product yourself. product. The User’s Manual provides important
Improper installation can result in water or refrigerant safety instructions and warnings. Be sure to
leakage, electrical shock, fire or explosion. follow these instructions and warnings.
»» Use only those parts and accessories supplied or specified »» For any inquiries, contact your local Daikin sales office.
by Daikin. Ask a licensed contractor to install those parts and
accessories. Use of unauthorized parts and accessories or Additional Information
improper installation of parts and accessories can result in Before purchasing this appliance, read important information
water or refrigerant leakage, electrical shock, fire or explosion. about its estimated annual energy consumption, yearly
operating cost, or energy efficiency rating that is available
from your retailer.
Daikin, VRV, and their designs are trademarks owned by Daikin.
2019
CT-VRV 03-19