455 D Control
SUPPLEMENTAL INSTALLATION
INSTRUCTIONS
CONTENTS
General Description 2
Programming 8
Maintenance 14
Limited Warranty 16
J2
J1 terminal block for low-
RADIO
voltage accessories
+ - F
1-455D115 = 115V
J2 quick connector port
1-455D = 230V
F Function Push Button
V1-4
61C455D
— Programming Push
Button
M
F1 + Programming Push
M
Button
220 115
FUSES
VAC VAC
F1
J5 J6 5A 10 A
J4 J1
22 23 24 25 Main Power
FCA1
J3
FCC1
FCA2
FCC2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
N L COM OP CL COM OP
MOTOR 1 MOTOR 2
CL LAMP A B NC
STOP
CL OP
FSW
- - - +
+24 V
+ TX
FSW W. L.
LOCK
F2 800 800
MAIN
Accessories mA mA
November, 2003
P a ge 455 D Control Pa nel Installat ion Instr uctions
N L 22 23 24 25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
COM OP CL COM OP CL LAMP CL OP - - - + + -
MOTOR 1 MOTOR 2 FSW 24V FSW W.LIGHT LOCK
ELECTRIC LOCK
BLUE
BLUE
C1 C2
FOR WHEN THE FAAC
GATECODERS ARE USED
Other safeties
Figure 2.
The terminal strip wiring of the 455
D with photo-beams
1
FSWOP
2
1
3
2
NOTE: In order to comply with UL 325, two sets 4
Op.1 Op.2
Cord grip or
conduit from
normally open (N.O.) contacts. Connect such devices to U.L. Listed gate
terminals 9 and 14. operator(s)
Page 7 shows how to connect a three or four wire OP_A Command Given No Command
receiver. OP_B Command Given No Command
DECODER CARD: If you are installing the Digicard Stop No Command Command Given
magnetic card reader, or the Digikey keyboard, use the
quick-fit connector J2 for the DS decoder card (see
Figure 1). FSW Opening reversing Reversing device
Open devices clear triggered
NOTE: If your using both a receiver and decoder,
hard wire the decoder and plug in the receiver. FSW Closing reversing Reversing device
Close devices clear triggered
OPEN/HOLD OPEN DEVICE: To open and hold open the
gate, simply maintain a contact across terminals 9 and FCA1 Flashes when gate coder is in use.
14. (“A” Mode only) FCC1 Operator 1
STOP BUTTON: The stop button you install must have FCA 2 Flashes when gate coder is in use.
normally closed (N.C.) contacts. Multiple FCC 2 Operator 2
stop buttons must be wired in series. Connect your stop
device between terminals 11 and 16.
F SW O P F C A1 FSWOP FCA1
NOTE: The 455 will not operate the motors without
a closed circuit between 11 & 16. O P_ A OP_A
FCC1 FCC1
The LED Indicators: The nine light emitting diodes ST O P STOP
(LEDs) on the control panel can be used to check for the FCC2 FCC2
proper function of the devices attached to the panel. O P_ B OP_B
The LED lights are on whenever the contacts are closed
across each of the respective terminals. F SW C L F C A2 FSWCL FCA2
OP_A and OP_B (Partial Opening) should illuminate only This display shows the This display shows the normal
when an activating signal is sent for 2 and 1 gate leaves, meaning of each LED. status of the control panel.
respectively. STOP should be illuminated except when
the stop button is pressed. FSWOP and FSWCL should be
illuminated except when the reversing devices, for Figure 3.5 The 455 D display.
November, 2003
P a ge 6 455 D Control Pa nel Installat ion Instr uctions
opening and closing, respectively, are triggered. Use • E (semi-automatic): This mode requires a
the LEDs and the next table to determine if the command to open and a command to close. A
accessory devices you have installed are operating second command during opening stops the
properly. gate. A second command during closing
reopens the gate.
Electric Locks: An electric lock can be wired to the 455
D in terminals 18 and 21 (12Vac pulsed provided). If a • EP (semi-automatic, step by step): This mode
reversing stroke is needed to allow the electric lock to requires a command to open and a command to
release, this must be done in advanced programming. close. A second command during opening or
closing causes the gate to stop. A third
See page 7 for the connections for a magnetic locking command then reverses the previous motion of
device. the gate.
WARNING LIGHT: Connect a warning light to
terminals 18 and 20 in the group labeled W.LIGHT • B (manned, pulsed): This mode is designed for
in terminal block J1 and J5. The terminals provide guard station use and requires a three-button
an output voltage of 24 VDC, maximum power 3 switch (pulsed) to open, close, and stop the
Watts. This output voltage will power most 24 VDC gate.
warning lights.
• C (manned and constant): This mode requires
NOTE: The behavior of the warning light varies constant pressure switches. One to open and
according to the logic you have set. one to close. No pressure on a switch stops the
gate.
LOGICS A, S, E, EP, AND B: The warning light is on
steadily during opening and the pause phase. During The three programming push buttons allow the
closing, the light flashes. programming of the torque (or pressure), the pause
time between opening and closing, and the leaf delay on
LOGIC C: The warning light is on steadily during opening closing.
and flashes during closing.
WARNING! Turn the main power off before you
make any electrical connections.
SET OTHER OPERATING CONTROLS For all FAAC hydraulic operators using the 455 D
control panel, the force must be set at its maximum
WARNING! Turn the main power off before you setting of 50 in order to supply the correct voltage to
make any electrical connections. the operator.
You need to program the control panel for your gate's PAUSE TIME: The pause time between opening and
operation. The 455 D Control Panel has on board closing can be adjusted from 0 seconds to 4 minutes.
programming that controls a wide range of functions. Time is adjusted in one-second increments from 0—59
seconds. When 60 seconds is reached, time is adjusted
OPERATING LOGICS in 10 second increments up to 4 minutes. i.e. if display
shows 2.5, it means 2 minutes and 50 seconds.
NOTE: The 455 provides inputs for opening
reversing devices and closing reversing devices.
FAAC strongly recommends the use of LEAF DELAY: You may choose to delay one leaf on
reversing devices, such as photocells or other closing for overlapping gate leaves. Be sure the operator
non-contact sensors. on the leaf for delayed closing is connected to Motor 1.
On opening, the leaf connected to Motor 2 is delayed
• A (automatic): The gate opens on command 2.5 sec.
and automatically closes after a pause phase. A
second command while opening is ignored; a NOTE: If an opening leaf delay is desired, it must be
second command during the pause phase enabled in the Advance Programming. However, if
interrupts the pause time; a second command enabled, you cannot adjust this opening delay of
during closing reopens the gate. A maintained the operator connected to Motor 2.
open command will hold the gate open.
The closing leaf-delay time is adjustable from 0 to 4
• S (security): The security mode is like A logic minutes.
except that a second command during opening
immediately closes the gate. A maintained NOTE: If the opening/closing time is set at less
open command will not hold the gate open. than the leaf delay time, the delayed leaf closes at
the end of the closing time.
November, 2003
455 D Control Pa nel Installation Instructions P a ge 7
- Lock
+
17
12 vac
9 NO 14 Relay
14 C 18 N.C.
N.O.
21
COM
2 N.O.
14
3 RX 7 COM
17
4 8
FAAC
3 & 4 Wire Radio Receiv ers
Rev ersing Photocells
(f or closing)
Additional
Reversing Devices
1
TX If 4 Wire Receiver
2
19
14 C
17
1 9 NO
12
2 14 -
19
3 RX 17 +
17
4
5
• When you reach the last function, press the “F” Simple Learning +
key to exit the program, and the display resumes ~ 1 s.
showing the status of the inputs.
EXIT PROGRAMMING
PROGRAM BUTTONS Exit from programming and return
to display of inputs status.
+ - F
LEFT MIDDLE RIGHT * With Hydraulic operators the Force/Torque must be set to
the maximum setting of 50.
November, 2003
455 D Control Pa nel Installation Instructions P a ge 9
Display
ADVANCED PROGRAMMING Function Default
F + + INDICATOR-LICHT:
If 0 is selected, the output functions
as a standard indicator-light (lighted
at opening and pause, flashing at
Display Function Default closing, and off when gate closed).
Different figures correspond to timed
MAXIMUM TORQUE AT INITIAL THRUST: activation of the output, which can be
The motors operate at maximum used (via a relay) to power a courtesy
torque (ignoring the torque setting) lamp. Time can be adjusted from 0
at start of movement. Useful for to 59s in 1s increments, and from 1.0
heavy leaves. to 4.1 min. in 10s steps.
4 = Enable
No = Disabled 0 = Standard Indicator-Light
From 1 to 4.1 = Timed Output
LAST STROKE AT CLOSING:
The motors are activated at full
speed for 1s to facilitate locking of CLOSING PHOTOCELLS REVERSE AT
the electric lock. RELEASE:
4 = Enable Enable this function if you want the
No = Disabled closing photocells to stop the gate
movement and reverse it after the
REVERSING STROKE: beam is cleared. Default setting is
Before opening, while the gate is immediate reverse.
closed, the motors thrust to close
for 2 s thus facilitating release of the 4 = Enable
electric lock. No = Disabled
4 = Enable
No = Disabled A.D.M.A.P. FUNCTION:
If this function is enabled, the safety
LEAF 2 OPENING DELAY (2S): devices operate in compliance with
Enables delayed start (at opening) of French standard NFP 25/362.
leaf 2, avoiding interference between
leaves. 4 = Enable
4 = Enable No = Disabled
No = Disabled ASSISTANCE REQUEST (COMBINED WITH
NEXT FUNCTION):
FAIL SAFE: If activated, at the end of countdown
If this function is activated, it (settable with the next function, i.e.
enables a function test of the “Cycle programming”) it effects 8s of
photocells before any gate pre-flashing at every Open pulse (job
movement. If the test fails request). Can be useful for setting
(photocells not serviceable), the gate scheduled maintenance jobs.
does not start the movement.
4 = Enable
4 = Enable No = Disabled
No = Disabled
CYCLE PROGRAMMING:
PRE FLASHING (5S): For setting count down of system
Activates the flashing lamp for 5s operation cycles. Settable (in
before start of movement. thousands) from 0 to 99 thousand
cycles. The displayed value is
4 = Enable updated as cycles proceed. This
No = Disabled function can be used to check use of
the board or to exploit the
ELECTRIC LOCK ON LEAF 2:
“Assistance Request” function.
For using the electric lock on leaf 2
instead of on leaf 1. EXIT PROGRAMMING:
Exit from programming and return to
4 = Enable display of inputs status.
No = Disabled
November, 2003
P a ge 1 0 455 D Control Pa nel Installat ion Instr uctions
LEARNING OF OPERATING TIMES • When gate operator (1) reaches the position
that you want it to slow down, an open
WARNING: During the learning procedure, the command must be given to start the slow
safety devices are disabled! Therefore, any traffic down phase.
must be avoided in the path of the gate leaf(s). • When gate operator (1) reaches the positive
stop and the desired motor run time has been
NOTE: Must start with gate(s) in the closed reached, an open command must be given to
position. shut the motor off. At this point gate operator
(2) will automatically start to open.
Opening/closing time is established by the learning • When gate operator (2) reaches the position
procedure which varies slightly according to whether that you want it to slow down, an open
you are or are not using Gatecoders. command must be given to start the slow
down phase.
• When gate operator (2) reaches the positive
LEARNING OF NORMAL TIMES stop and the desired motor run time has been
reached, an open command must be given to
shut the motor off. At this point gate operator
Normal learning (i.e. without Gatecoders) can be done in
(2) will automatically start to close.
two different ways:
• When gate operator (2) reaches the position
that you want it to slow down, an open
SIMPLE LEARNING command must be given to start the slow
down phase.
Close the gates, enter “BASIC PROGRAMMING”, select the
TIME LEARNING function and press the + push-button
• When gate operator (2) reaches the positive
for 1 second the display begins flashing and the leaves stop and the desired motor run time has been
begin the opening movement. reached, an open command must be given to
shut the motor off. At this point gate operator
Wait for the leaves to reach the opening positive stop (1) will automatically start to close.
and then supply an OPEN A command after the desired • When gate operator (1) reaches the position
motor run time has been reached (by push-button or that you want it to slow down, an open
radio control) to stop the movement: the leaves stop command must be given to start the slow
and the display stops flashing. One more command down phase.
given will close the gate. • When gate operator (1) reaches the positive
stop and the desired motor run time has been
The procedure has ended and the gate is ready to reached, an open command must be given to
operate. shut the motor off.
COMPLETE LEARNING The display stops flashing and the gate is ready for
normal operation.
NOTES:
• If you do not wish to slow the gate operator(s) LEARNING TIMES WITH GATECODER
down, wait for the gate to reach its positive
stop and supply two (2) consecutive open Learning with the Gatecoder can be done in two
commands (within 1 second). different ways:
• If only one gate operator (1) is used, you must SIMPLE LEARNING
go through the entire programming procedure,
as if you were programming for two gate Close the gates, enter “Basic Programming”, select the
operators (2). When the operator has finished TIME LEARNING function and press the + push-button
opening, supply 5 open commands until the for 1 second: the display begins flashing and the leaves
gate operator begins to close, and then resume begin the opening movement.
normal operations.
The movement stops automatically when the opening
Close the gates, enter “BASIC PROGRAMMING”, select the positive stop is reached and the display stops flashing.
TIME LEARNING function and press the + push-button
for more than 3 seconds: the display begins flashing The procedure has ended and the gate is ready to
and leaf 1 begins opening. The following functions can operate, using default slow down automatically set by
be commanded by the OPEN A (by push-button wired to the control panel.
terminals 9 and 14, or radio control):
November, 2003
455 D Control Pa nel Installation Instructions P a ge 1 1
COMPLETE LEARNING • When gate operator (2) reaches the position that
you want it to slow down, an open command must
NOTES: be given to start the slow down phase. When the
gate operator reaches its positive stop, the
• If only one gate operator (1) is used, you operator will automatically shut off.
must go through the entire programming • An open command must be given to start closing
procedure, as if you were programming a gate operator (1).
gate operator (2). When the gate operator • When gate operator (1) reaches the position that
(1) has finished opening, supply 5 open you want it to slow down, an open command must
commands until the gate operator begins to be given to start the slow down phase. When the
close, and then resume normal operations. gate operator reaches its positive stop, the
operator will automatically shut off.
Close the gates, enter “BASIC PROGRAMMING”, select the
TIME LEARNING function and press the + push-button The display stops flashing and the gate is ready for normal
for more than 3 seconds: the display begins flashing operation.
and leaf 1 begins opening movement. The following
functions can be commanded by the OPEN A NOTES:
command (by radio control or key push-button):
• The open command to slow down the gate should
• When gate operator (1) reaches the position be given before the gate reaches the positive stop
that you want it to slow down, an open to prevent the gate from hitting the stop at full
command must be given to start the slow speed. The positive stop could be mistaken for an
down phase. When the gate operator obstacle and then upon hitting it, the gate(s) would
reaches its positive stop, the operator will automatically reverse on contact.
automatically shut off.
• An open command must be given to start
opening gate operator (2). AUTOMATED SYSTEM TEST
• When gate operator (2) reaches the position
that you want it to slow down, an open When you have finished programming, check if the system is
command must be given to start the slow operating correctly.
down phase. When the gate operator
reaches its positive stop, the operator will Most important of all, check that the force is adequately
automatically shut off. adjusted and that the safety devices are operating correctly.
• An open command must be given to start
closing gate operator (2). If pressure adjustments on hydraulic operators are not set
before programming. It may need to be reprogrammed for
desired results.
November, 2003
P a ge 1 2 455 D Control Pa nel Installat ion Instr uctions
Closes 1 or both
Opened No effect No effect No effect No effect On
leaves
No effect No effect
Stopped Closes the leaves Closes the leaf (opening is No effect opening is inhib- On
inhibited) ited)
MAINTENANCE
THE 455 MPS CONTROL PANEL
Keep the control panel free from spider webs, insects, etc. Otherwise, the control panel requires no maintenance.
November, 2003
455 D Control Pa nel Installation Instructions P a ge 1 5
LIMITED WARRANTY
To the original purchaser only: FAAC International, been operated under conditions more severe than, or
Inc., warrants, for twenty-four (24) months from the otherwise exceeding, those set forth in the
date of invoice, the gate operator systems and other specifications for such product(s). Neither FAAC S.p.A.
related systems and equipment manufactured by FAAC or FAAC International, Inc., shall be liable for any loss or
S.p.A. and distributed by FAAC International, Inc., to be damage whatsoever resulting, directly or indirectly,
free from defects in material and workmanship under from the use or loss of use of the product(s). Without
normal use and service for which it was intended limiting the foregoing, this exclusion from liability
provided it has been properly installed and operated. embraces a purchaser's expenses for downtime or for
FAAC International, Inc.'s obligations under this making up downtime, damages for which the purchaser
warranty shall be limited to the repair or exchange of may be liable to other persons, damages to property,
any part of parts manufactured by FAAC S.p.A. and and injury to or death of any persons. Neither FAAC
distributed by FAAC International, Inc. Defective S.p.A. or FAAC International, Inc., assumes nor
products must be returned to FAAC International, Inc., authorizes any person to assume for them any other
freight prepaid by purchaser, within the warranty liability in connection with the sale or use of the
period. Items returned will be repaired or replaced, at products of FAAC S.p.A. or FAAC International, Inc. The
FAAC International, Inc.'s option, upon an examination warranty hereinabove set forth shall not be deemed to
of the product by FAAC International, Inc., which cover maintenance parts, including, but not limited to,
discloses, to the satisfaction of FAAC International, Inc., hydraulic oil, filters, or the like. No agreement to replace
that the item is defective. FAAC International, Inc. will or repair shall constitute an admission by FAAC S.p.A. or
return the warranted item freight prepaid. The products FAAC International, Inc., of any legal responsibility to
manufactured by FAAC S.p.A. and distributed by FAAC effect such replacement, to make such repair, or
International, Inc., are not warranted to meet the otherwise. This limited warranty extends only to
specific requirements, if any, of safety codes of any wholesale customers who buy directly through FAAC
particular state, municipality, or other jurisdiction, and International, Inc.'s normal distribution channels. FAAC
neither FAAC S.p.A. or FAAC International, Inc., assume International, Inc., does not warrant its products to end
any risk or liability whatsoever resulting from the use consumers. Consumers must inquire from their selling
thereof, whether used singly or in combination with dealer as to the nature and extent of that dealer's
other machines or apparatus. warranty, if any.
Any products and parts not manufactured by FAAC This warranty is expressly in lieu of all other
S.p.A. and distributed by FAAC International, Inc., will warranties expressed or implied including the war-
carry only the warranty, if any, of the manufacturer. This ranties of merchantability and fitness for use. This
warranty shall not apply to any products or parts thereof warranty shall not apply to products or any part
which have been repaired or altered, without FAAC thereof which have been subject to accident, negli-
International, Inc.'s written consent, outside of FAAC gence, alteration, abuse, or misuse or if damage was
International, Inc.'s workshop, or altered in any way so due to improper installation or use of improper
as, in the judgment of FAAC International, Inc., to affect power source, or if damage was caused by fire, flood,
adversely the stability or reliability of the product(s) or lightning, electrical power surge, explosion, wind
has been subject to misuse, negligence, or accident, or storm, hail, aircraft or vehicles, vandalism, riot or
has not been operated in accordance with FAAC civil commotion, or acts of God.
International, Inc.'s or FAAC S.p.A.'s instructions or has