Eaton 9E UPS: 1kVA/2kVA/3kVA/6kVA/10kVA/15kVA/20kVA
Eaton 9E UPS: 1kVA/2kVA/3kVA/6kVA/10kVA/15kVA/20kVA
Eaton 9E UPS: 1kVA/2kVA/3kVA/6kVA/10kVA/15kVA/20kVA
Eaton 9E UPS
1kVA/2kVA/3kVA/6kVA/10kVA/15kVA/20kVA
9E 10kVA
Flexibility
• The internal bypass allows service continuity in case of an
internal fault. A maintenance bypass is also available as
standard for easy maintenance of the UPS without powering
Advanced protection for:
down critical systems.
• ATM
• Make your installation more flexible with a combo input
• Infrastucture (3:1 and 1:1) on the 10kVA, 15kVA, and 20kVA.
• Industrial and Medical IT
• Extend runtime as you like by adding up to 4 external battery
• Networking modules (EBM) for 2kVA and above. For extra-long runtime, XL
• Storage models with internal supercharger are also available at 3kVA,
• Telecom 10kVA and 20kVA.
• Transportation
Eaton 9E UPS
3
1
2
4
5
6
TECHNICAL SPECIFICATIONS 6kVA 1:1 10kVA 1:1 and 3:1 15kVA 1:1 and 3:1 20kVA 1:1 and 3:1
Rating (VA/W) 6kVA/4.8kW 10kVA/8kW 15kVA/12kW 20kVA/16kW
Format Tower
Electrical Characteristics
Technology Online double conversion
Input voltage 220/230/240V
Input voltage range without using batteries 176-276V without derating (up to 110-276V with derating)
Output voltage/THDU 220V/230V/240V ±2 %, THDU<3%
Input frequency range 45Hz-66Hz, 50/60Hz autoselection
Efficiency Up to 93% in Online mode, 97% in ECO mode
Short circuit current 82A 137A 205A 273A
Overload capacity 105%-110% : 5min, 110%-130% : 1min, 130%-150% : 10s, >150% : 100ms
Connections
Input Terminal block
Outputs Terminal block
Typical backup times at 50% and 75% load
9E 20/12 15/9 16/9 15/9
9E + 1 EBM 75/47 60/36 38/26 27/19
9E + 4 EBM 222/140 170/110 117/76 82/54
Communication
Communication ports 1USB port + 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously)
Communication slot 1 slot for Network-MS, ModBus-MS or Relay-MS cards
Software Intelligent Power Software
Operating conditions, Standards and Approvals
Operating temperature 0 to 40°C
Noise level <55dB
Safety IEC/EN 62040-1
EMC, Performance IEC/EN 62040-2
Approvals CE, CB report (TUV)
Dimensions D x H x W / Weight
UPS Dimensions (mm) 612.9 x 708.5 x262.4 612.9 x 708.5 x262.4 706 x 815.5 x 350 706 x 815.5 x 350
UPS Weight (kg) 68 85.4 145.3 159.9
EBM dimensions (mm) 579.4 x 708.5 x 262.4 579.4 x 708.5 x 262.4 579.4 x 708.5 x 262.4 579.4 x 708.5 x 262.4
EBM weight (kg) 105.5 132 132 132
UPS with supercharger (and no batteries) dimensions (mm) - 612.9 x 708.5 x 262.4 - 706 x 815.5 x 350
UPS with supercharger (and no batteries) weight (kg) - 28.9 - 47.8
Customer Service & Support
Warranty 2 years 2 years 1 year 1 year
* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
In the interests of continuous product improvement, all specifications are subject to change without notice.
© 2018 Eaton