AMF25
Controller for single gen-set
applications
SW version 1.7.0
1 Document information 6
2 System overview 10
3 Applications overview 19
4 Installation and wiring 21
5 Controller setup 50
6 Communication 132
7 Technical data 159
8 Appendix 161
2 System overview 10
2.1 General description 10
2.1.1 The key features of InteliLite 10
2.2 True RMS measurement 10
2.3 Configurability and monitoring 10
2.3.1 Supported configuration and monitoring tools 11
2.3.2 Configuration parts 11
2.4 PC Tools 12
2.4.1 InteliConfig 12
2.4.2 WebSupervisor 12
2.4.3 WinScope 13
2.5 Plug-in Modules 13
2.5.1 CM-Ethernet 13
2.5.2 CM-4G-GPS 14
2.5.3 CM-GPRS 14
2.5.4 CM-RS232-485 14
2.5.5 EM-BIO8-EFCP 15
2.6 CAN modules 15
2.6.1 Inteli IO8/8 15
2.6.2 Inteli AIN8 16
2.6.3 Inteli AIN8TC 16
2.6.4 Inteli AIO9/1 17
2.6.5 IGS-PTM 17
2.6.6 IGL-RA15 18
5 Controller setup 50
5.1 Default configuration 50
5.1.1 Binary inputs 50
5.1.2 Binary outputs 50
5.1.3 Analog inputs 50
5.2 Controller configuration and PC tools connection 51
5.2.1 USB 51
5.2.2 RS232/RS485 52
5.2.3 Ethernet 53
5.3 Operator Guide 58
5.3.1 Front panel elements 58
6 Communication 132
6.1 PC 132
6.1.1 Direct communication 132
6.1.2 Remote communication 134
6.2 Connection to 3rd party systems 145
6.2.1 SNMP 145
8 Appendix 161
8.1 Controller objects 162
8.1.1 Setpoints 163
8.1.2 Values 453
8.1.3 Logical binary inputs 501
8.1.4 Logical binary outputs 545
8.1.5 Logical analog inputs 605
8.1.6 PLC 637
8.2 Alarms 650
8.2.1 Alarms level 1 650
8.2.2 Alarms level 2 677
8.2.3 Fail sensor and other types 695
8.3 Modules 697
8.3.1 Plug-In modules 698
8.3.2 CAN modules 713
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or unproper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
IMPORTANT: Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper configuration and
setpoint settings are set in the controller).
The following instructions are for qualified personnel only. To avoid personal injury do not perform any action not
specified in related guides for product.
EN 61000-6-4
EN 61010-1
EN 61000-2-30
Connector - Resistor
3 x Phases Grounding
male adjustable
Active Resistive
current Contact GSM sensor
sensor RPTC
GSM RS 232
Contactor
AirGate modem male
Controller RS 232
IG-AVRi
Alternating simplified female
current
Module IG-AVRi
Starter
Analog simplified TRANS
modem
Switch -
Current
Jumper manually
measuring
Battery operated
Current
Load Transformer
Binary measuring
output
USB type B
Diode Mains male
Breaker
contact
Ethernet USB type B
Mains female
Breaker male
contact
Voltage
Ethernet Mobile
measuring
female provider
Breaker
Passive Wifi / WAN /
Fuel
current LAN
solenoid
Breaker sensor
6 back to Document
information
Fuse Pick - up
Breaker
Note: Use the InteliConfig PC software to read, view and modify configuration from the controller or disk and
write the new configuration to the controller or disk.
The firmware of controller contains a large number of binary inputs and outputs needed for all necessary
functions available. However, not all functions are required at the same time on the same gen-set and also the
controller hardware does not have so many input and output terminals. One of the main tasks of the
configuration is mapping of “logical” firmware inputs and outputs to the “physical” hardware inputs and outputs.
2.4 PC Tools
2.4.1 InteliConfig
Configuration and monitoring tool for InteliLite controllers. See more in InteliConfig Reference Guide.
2.4.2 WebSupervisor
Web-based system for monitoring and controlling of controllers. See more at the WebSupervisor webpage.
2.5.3 CM-GPRS
GSM/GPRS Internet module
Wireless integrated solution
Quick and easy installation
Support of WebSupervisor
Instant alarm SMS notification
System control over SMS
Quad Band GPRS/EDGE modem,
850/900/1800/1900 MHz
GPRS multi-slot class 10
TCP/IP communication over GPRS
2.5.4 CM-RS232-485
Communication module with two communication ports.
RS232 and RS485 interface
MODBUS
Serial connection to InteliConfig
Configuration 8/8
8 Binary inputs (options: pull up or pull down
logic)
8 Binary outputs (options: Low side switch (LSS)
or High side switch (HSS))
2 Analog outputs (options: voltage (0-10V),
current (0-20mA) and PWM (5V, adjustable
frequency 200Hz-2,4kHz))
Configuration 16/0
16 Binary inputs (options: pull up or pull down
logic)
0 Binary outputs
2 Analog outputs (options: voltage (0-10V),
current (0-20mA) and PWM (5V, adjustable
frequency 200Hz-2,4kHz))
Supported sensors:
Resistor 3-wire input
Common resistor: 0-250Ω, 0-2400Ω, 0-10kΩ
Temperature sensor: Pt100, Pt1000, Ni100,
Ni1000
Current (active or passive sensors)
±20mA , 0-20mA, 4-20mA
Voltage
±1V, 0-2,4V, 0-5V, 0-10V
Lambda probes
Thermocouples are not supported (the
measuring loop was designed for lambda
probes, what caused non-support of
thermocouples)
2.6.5 IGS-PTM
The unit offers the user the flexibility to configure the unit to have 8 binary inputs, 8 binary outputs, 4 analog
inputs and 1 analog outputs.
Configurable 8 binary and 4 analog inputs
Configurable 8 binary and 1 analog output
LEDs indicate the state of binary inputs/outputs
Measures values from Pt100 and Ni100 sensors
Analog inputs (resistance range 0-250 Ohms,
voltage range 0-100mV, current range 0-20mA -
selectable via jumper)
UL certified
Note: The package does not contain a communication or extension modules. The required modules should be
ordered separately.
① Plug-in module
Note: Dimension x depends on plug-in module
4.2.2 Mounting
The controller is to be mounted onto the switchboard door. Requested cutout size is 187 x 132 mm. Use the
screw holders delivered with the controller to fix the controller into the door as described on pictures below.
Recommended torque for holders is 0.15 N·m.
CAN bus and RS485 H, COM, L CAN bus and RS485 wiring (page 42)
Note: Wiring terminal markings to included tightening torque: 0,5 N-m (4,5 lb-in)., and wire size: 2 mm2 (12-
26AWG).
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
For Mains(Bus) Voltage, Generator Voltage and Current terminals
4.4.2 Grounding
The shortest possible length of wire should be used for controller grounding. Use cable min 2.5 mm2.
The negative " - " battery terminal must be properly grounded.
Switchboard and engine must be grounded at common point. Use as short cable as possible to the grounding
point.
For the connections with 12 V DC power supply, the controller includes internal capacitors that allow the
controller to continue operation during cranking if the battery voltage dip occurs. If the voltage before dip is 10 V,
after 100 ms the voltage recovers to 7 V, the controller continues operating. During this voltage dip the controller
screen backlight can turn off and on but the controller keeps operating. It is also possible to further support the
controller by connecting the external capacitor and separating diode.
The capacitor size depends on required time. It shall be approximately thousands of μF. The capacitor size
should be 5 000 μF to withstand 150 ms voltage dip under following conditions:
Voltage before dip is 12 V, after 150 ms the voltage recovers to min. allowed voltage, i.e. 8 V.
IMPORTANT: When the controller is power up only by USB and the USB is disconnected then the
actual statistics can be lost.
Note: Suitable conductor protection shall be provided in accordance with NFPA 70, Article 240.
Note: Low voltage circuits (35 volts or less) shall be supplied from the engine starting battery or an isolated
secondary circuit.
CT Location
3 phase application:
It is necessary to ensure that potential difference between current COM terminal and battery “-” terminal is
maximally ± 2 V. Therefore is strongly recommended to interconnect these two terminals together.
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.
The generator protections are evaluated from different voltages based on Connection type (page 171) setting:
3Ph 4W – Ph-Ph voltage, Ph-N voltage
3Ph 3W – Ph-Ph voltage
Split Ph – Ph-N voltage
Mono Ph – Ph-N voltage
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.
The generator protections are evaluated from different voltages based on Connection type (page 171) setting:
3Ph 4W – Ph-Ph voltage, Ph-N voltage
3Ph 3W – Ph-Ph voltage
Split Ph – Ph-N voltage
Mono Ph – Ph-N voltage
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.
Note: The name and function or alarm type for each binary input have to be assigned during the configuration.
Note: Every single low current binary output can provide up to 0,5 A of steady current.
Note: Binary output 1 (terminal 4) and binary output 2 (terminal 5) are high current outputs (5 A for long term).
Note: Schemes show only analog input connection overview, not actual wiring.
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Voltage sensors
Sensor’s output
R1 (Ω) R2 (Ω)
range (V)
0 - 10 390 100
0 - 30 1500 100
0 - 70 3300 100
0 - 10 V
V 0 1 2 3 4 5 6 7 8 9 10
Ω 81 145 219 306 409 539 685 887 1125 1458 1933
0 - 30 V
V 0 2 4 6 8 10 12 14
Ω 95 134 177 223 274 330 395 465
V 16 18 20 22 24 26 28 30
Ω 543 633 735 853 993 1154 1350 1589
0 - 70 V
V 0 2 4 6 8 10 12 14 16 18 20 22
Ω 99 117 137 155 175 196 219 242 266 291 318 346
V 24 26 28 30 32 34 36 38 40 42 44 46
Ω 375 406 439 473 510 549 589 633 679 729 781 838
V 48 50 52 54 56 58 60 62 64 66 68 70
Ω 873 963 1033 1110 1193 1283 1383 1492 1612 1748 1896 2065
Note: This is a conversion of voltage from voltage sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.
Current sensors
Sensor’s output
R (Ω)
range (mA)
0-20 100
0 - 22 mA
mA 0 1 2 3 4 5 6 7 8 9 10 11
Ω 100 133 167 202 241 283 328 375 431 489 553 625
mA 12 13 14 15 16 17 18 19 20 21 22
Ω 707 793 894 1007 1136 1287 1460 1666 1914 2222 2596
Note: This is a conversion of current from current sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.
Image 4.20 Analog inputs as tristate Image 4.21 Analog inputs as binary
Note: The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Note: Tristate and binary sensors are not suitable for Analog Switch functions.
1Recommended data cables: BELDEN (http://www.belden.com) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)
Note: A termination resistor at the CAN (120 Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.
Note: Shielding shall be grounded at one end only. Shielding shall not be connected to CAN COM terminal
① Recommended PT5-HF-12DC-ST1
RS485 wiring
The wiring of the RS485 communication should be provided in such a way that the following rules are observed:
Note: A termination resistor at the CAN (120Ω) is already implemented on the PCB. For connecting, close the
jumper near the appropriate CAN terminal.
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)
① Recommended PT5HF-5DC-ST1
Note: Communication circuits shall be connected to communication circuits of Listed equipment.
4.4.11 USB
This is required for computer connection. Use the shielded USB A-B cable.
Controller can by also power by USB (only for service purpose like a uploading firmware, change of
configuration etc.).
IMPORTANT: Power supply by USB is only for service purpose. Binary inputs and outputs are in
logical 0. Also plug-in modules are not working.
After locking the plug-in module into holders, place back the back cover (small cover for connectors has to be
removed from back cover). Finally insert the small cover for connectors. Small covers are unique for each plug-
in module.
The battery is located in a holder on the circuit board. Remove the old battery with a small sharp screwdriver
and push with a finger the new battery into the holder.
Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention that the cover
is in correct position and not upside down!
Put back the plugin modules and back cover.
Power the controller on, adjust date and time and check all setpoints.
5.2.1 USB
You may connect to the controller using the USB port. In this case standard USB A to B cable should be used.
5.2.2 RS232/RS485
It is possible to connect to the controller using RS232 or RS485 direct connection (serial port or USB to
RS232/RS485 converter may be used). The following settings need to be checked in the controller:
COM1 Mode (page 345) = Direct
Controller Address (page 177) has to be set to the same value as in the PC tool
5.2.3 Ethernet
It is possible to connect to the controller using ethernet port either directly or using ComAp's AirGate service.
Direct connection
When you use direct connection the controller needs to be reachable directly from the PC you use (i.e. one LAN
or WAN without any firewalls and other points that may not allow the connection). The following settings need to
be checked in the controller:
AirGate connection
You can use ComAp's AirGate service that allows you to connect to any controller via internet no matter what
are the restrictions of the local network (if the controller can connect to the internet AirGate service will work).
The following setpoints have to be adjusted:
Control buttons
Position Picture Description
LEFT button. Use this button to move left or to change the mode. The button can
change the mode only if the main screen with the indicator of currently selected
mode is displayed.
Note: This button will not change the mode if the controller mode is forced by
one of binary inputs listed in the Reference Guide – “Operating modes” chapter.
RIGHT button. Use this button to move right or to change the mode. The button can
change the mode only if the main screen with the indicator of currently selected
mode is displayed.
HORN RESET button. Use this button to deactivate the horn output without
acknowledging the alarms.
FAULT RESET button. Use this button to acknowledge alarms and deactivate the
horn output. Inactive alarms will disappear immediately and status of active alarms
will be changed to "confirmed" so they will disappear as soon as their reasons
dismiss.
ENTER button. Use this button to finish editing a setpoint or moving right in the
history page.
START button. Works in MAN mode only. Press this button to initiate the start
sequence of the engine.
STOP button. Works in MAN mode only. Press this button to initiate the stop
sequence of the gen-set. Repeated pressing of button will cancel current phase of
stop sequence (like cooling) and next phase will continue.
GCB button. Works in MAN and TEST modes only. Press this button to open or
close the GCB.
MCB button. Works in MAN and TEST modes only. Press this button to open or
close the MCB.
MAINS status indicator. There are two states - Mains OK (indicator is green) and Mains failure
(indicator is red). Green LED is on, if mains is present and within limits. Red LED starts blinking
when the mains failure is detected and after the gen-set has started and connected to the load it
lights permanently until the mains failure disappears.
MCB ON. Green LEDs are on if MCB is closed and Mains is healthy. If Mains is not healthy and
MCB is closed than middle LED is on. It is driven by MCB CLOSE/OPEN output or by MCB
feedback signal.
Main Screen
Symbols
Padlock - active when LBI ACCESS LOCK is active
R - active when there is active remote connection to controller
Exclamation mark - active when there is any alarm in alarmlist
Note: From all of these pages it is possible to switch seamlessly to the setpoint group page by pressing Page
button.
Note: There can be some additional screens and also some screens can be hidden. Screen’s visibility
depends on actual configuration (usage of extension or communication modules, ECU, etc.).
Setpoint Screens
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: Use Page button to discard changes, to set setpoint to previous value and to return to the list of
setpoints of selected group.
IMPORTANT: Cannot change setpoint? Setpoints marked with an padlock are password protected.
Enter password as described in the chapter Password (page 74).
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: From setpoint group page we can fluently go to the history log pages by pressing Page button.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the next page of history log.
Note: Use Enter button to move to the first page of history log.
Note: This is only basic history record. There can be some additional screens in case that in controller is
extension module or ECU is configured. Also it depends on connection type.
Active alarms are displayed as white text on black background. It means the alarm is still active, i.e. the
appropriate alarm conditions are still present.
Inactive alarms are displayed as black text on white background. It means the alarm is no more active, i.e.
the appropriate alarm conditions are gone.
Not confirmed alarms are displayed with an asterisk. It means the alarm is still not acknowledged
(confirmed).
ECU alarms: SPN/FMI/OC/SC
SPN - Suspect parameter number
FMI - type of protection
OC - number of errors
SC - source of error
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: Use Enter button to confirm the password or Page button to cancel entering the password.
Note: In case that invalid password is entered, the controller shows Invalid password screen. Use Page
button to go back to menu.
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: After setting new password use Enter button to confirm adjusted password.
Note: After setting new password again use Enter button to confirm adjusted password or Page button to
discard changes and to cancel changing password.
Note: Before changing the password controller has to be unlocked. In case that controller is locked, the
controller shows Password required screen. In that case the password has to be entered before changing the
password.
Note: From all measurement pages we can fluently go to the setpoint group page by pressing Page button.
Note: In case that invalid password is entered, the controller shows Invalid password screen. Use Page
button to go back to menu.
Lost Password
IMPORTANT: Display the information screen containing the serial number and password decode
number as described in the chapter Information screen (page 80) and send them to your local
distributor.
+
Note: On Main measurement screen press Enter and Page button together. Enter button has to be pressed
first.
+
Note: On Main measurement screen press Enter and Page button together. Enter button has to be pressed
first.
+ +
Note: On any measurement screen press Enter and Note: On any measurement screen press Enter and
Down button together for lower contrast. Up button together for higher contrast.
5.4 Functions
5.4.1 Start-stop sequence 83
5.4.2 AMF sequence 85
5.4.3 Operating Modes 86
5.4.4 Engine start 87
5.4.5 Stabilization 91
Note: If all generator parameters are OK and Minimal Stabilization Time (page 194) elapsed, indicates that GCB
is possible to close. In AUTO Mode GCB is closed in this moment automatically.
Note: The start-up sequence can be interrupted in any time by stop request
Note: If during start-up sequence mains returns, then MCB is reclosed with delay MCB Close Delay (page 235)(if
opened, depending on MCB Opens On (page 241) setpoint) and start-up sequence is interrupted.
Note: If mains fails during stop procedure (cooling) again, stop sequence is interrupted, MCB opened and GCB
re-closed with Transfer Delay (page 234).
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
Remote OFF (page 542)
Remote TEST (page 543)
Remote MAN (page 541)
Remote AUTO (page 541)
If the respective input is active the controller will change the mode to the respective position according to the
active input. If multiple inputs are active, the mode will be changed according to priorities of the inputs. The
priorities match the order in the list above. If all inputs are deactivated, the mode will return to the original
position given by the setpoint.
OFF
No start of the gen-set is possible .Controller stays in Not ready status and cannot be started any way. The
MCB is closed permanently (MCB Opens On (page 241) = GENRUN) or is open or closed according to whether
the mains is present or not (MCB Opens On (page 241) = MAINSFAIL). No AMF function will be performed. The
buttons MCB , GCB , Start and Stop including the appropriate binary inputs for external buttons
are not active.
IMPORTANT: When engine is running, it is not possible to switch gen-set to OFF mode.
MAN
The engine can be started and stopped manually using the Start and Stop buttons (or external buttons
wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can be closed. Also
MCB can be closed and opened manually using the MCB button, regardless of whether the mains are present or
not. No auto start is performed.
Note: The controller provides interlock between GCB and MCB, it means it is never possible to close both CB
together.
TEST
The gen-set will be started when the controller is put to TEST mode and will remain running unloaded. If a mains
failure occurs, the MCB will be opened and after Transfer Delay (page 234) the GCB will be closed and the gen-
set will supply the load. After the mains have recovered, the delay Mains Return Delay (page 233)l will count
down and if it elapses and the mains is still ok, the controller will transfer the load back to the mains after
Transfer Delay (page 234) and the gen-set will remain running unloaded again until the mode is changed.
The maximum duration that the output STARTER (PAGE 600) is energized is determined by the setpoint
Maximum Cranking Time (page 184). If the engine does not start within this period, outputs STARTER (PAGE
600) and FUEL SOLENOID (PAGE 579) are de-energized and a pause with length determined by Cranking Fail
Pause (page 184) will follow. PRESTART (PAGE 596), GLOW PLUGS (PAGE 585) and IGNITION (PAGE 588)
outputs are active during the pause. After the pause has elapsed, the next start attempt is executed. The
number of start attempts is given by the setpoint Cranking Attempts (page 183).
Once the engine is started, the Idle period follows. The binary output IDLE/NOMINAL (PAGE 588) remains
inactive (as it was during the start). The idle period duration is adjusted by the setpoint Idle Time (page 192).
After the idle period has finished, the output IDLE/NOMINAL (PAGE 588) is activated and the start-up
sequence is finished. The Stabilization (page 91) phase follows.
Note: The value of the Minimal Stabilization Time (page 194) setpoint has to be lower than the value of Maximal
Stabilization Time (page 195) setpoint.
Note: The automatic start of the gen-set due to AMF function can be disabled by the binary inputs AMF START
BLOCK (PAGE 504) or MAINS FAIL BLOCK (PAGE 537).
If the setpoint MCB Opens On (page 241) is set to Gen Run, the MCB is opened once the generator voltage is
within limits (after Minimal Stabilization Time (page 194) elapses).
After Transfer Delay (page 234) elapses, the GCB is closed and the gen-set begins to supply the load.
After the mains restored to normal, the timer Mains Return Delay (page 233) begins to count down.
Maximum time between closing of MCB and opening GCB is given by the setpoint Transfer Delay (page
234). After GCB is opened, the gen-set cools down and a stop.
IMPORTANT: Controller has this behavior only in AUTO mode!
IMPORTANT: Dual operation is in fail also during process of adjustment of setpoints. In this
moment slave still tries to control MCB.
IMPORTANT: Setpoint MCB Opens On (page 241) has to be set-up to Mains Fail option.
IMPORTANT: LBI MAINS FAIL BLOCK (PAGE 537) can cause fail of dual operation system. In case of
different states of mains on master and slave controllers, alarm Dual Operation Different Mains
(page 670) is activated and gen-sets are switched to normal operation.
Note: LBI AMF START BLOCK (PAGE 504) is evaluated on both controllers. When this LBI is activated, gen-set
can’t start in dual operation. Second gen-set (without active AMF START BLOCK (PAGE 504)) will start. Gen-
sets are not swapping the load until this LBI is active. Behaviour is the same like with alarm of 2nd level.
Note: MCB Fail protection is not used in Slave controller during Dual Operation. MCB is controlled only via
Master. Slave controller has MCB Close/Open in open position all the time during Dual Operation.
Start/stop events
Event Dual AMF
Mains Fail Evaluated by Master only
LBI REMOTE START /STOP (PAGE 542) Evaluated by Master only
IMPORTANT: It is not possible to use Auto Run option in Exercise timers with dual operation.
Start/stop events
Event Dual MRS
LBI REMOTE START /STOP (PAGE 542) Evaluated by Master only
Communication
Communication is establish on RS232 or RS485 communication line. Plug-in module CM-RS232-485 is
required. Communication line is selected via setpoints COM1 Mode (page 345) or COM2 Mode (page 347). There
are options DualMaster and DualSlave. These options adjust, which communication line is selected and which
role controller has in Dual Operation.
IMPORTANT: For correct communication it is necessary to have one Master and one Slave
controller on the same communication line.
IMPORTANT: There are no shared setpoints. It is necessary to have the same settings of AMF
setpoints and engine timers in both controllers.
In case of communication fail between controllers, alarm Dual Operation Fail (page 670) is activated. This
alarm is activated on both controllers. Both controllers are switched to normal operation.
Switching of gen-sets
Switching of gen-sets is based on their Running Hours (page 475). The time how long the gen-set is running is
adjusted via setpoint Running Hours Max Difference (page 241). When difference of Running Hours (page 475)
between gen-sets is bigger then value adjusted in this setpoint, load is transferred from first gen-set to second
gen-set. First gen-set is supplying the load until second gen-set is in running state. Then the GCB of first gen-
set is opened. From this moment timer Transfer Delay (page 234) counts down. When it counts down, GCB of
second gen-set can be closed.
Note: Value of Running Hours (page 475) can be modified by setpoint Running Hours Base (page 242). This
setpoint can add or remove additional running hours to value from statistics. This modified value of running
hours is used in dual operation function.
Note: In case that both gen-sets have the same running hours, Master controller has higher priority.
Note: Switching of gen-sets can be inhibit by setpoint Swap Gen-sets (page 242) or by binary input DUAL SWAP
GEN-SETS (PAGE 530).
Alarm handling
There are three different alarm categories regarding the period when the alarms are evaluated. The category is
selectable for alarms assigned to binary/analog inputs and fixed for built-in alarms. The categories are the
following:
The alarm is evaluated all the time when the controller is switched on.
The alarm is evaluated only when the engine is running. This type should be used for e.g. oil pressure. These
alarms begin to be evaluated after the engine has been started with the delay given by the setpoint Protect
Hold Off (page 195).
The alarm is evaluated only when the generator is excited. These alarms begin to be evaluated after the
engine has been started and Maximal Stabilization Time (page 195) has elapsed or the GCB has been closed.
They remain evaluated until cooling has finished. Only Generator under/overvoltage, Generator voltage
unbalance and Generator under/overfrequency belong to this category. This category is not configurable to
binary and analog input alarms.
If an alarm is being evaluated and the appropriate alarm condition is fulfilled, the delay of evaluation will start to
run. The delay is adjustable by a setpoint (in the case of built-in alarms, analog input alarms) or is adjusted via
configuration window in InteliConfig (in the case of binary input alarms). If the conditions persist, the alarm will
activate. The alarm will not activate if the condition is dismissed while the delay is still running.
After pressing the Fault reset button or activating the binary input FAULT RESET BUTTON (PAGE 531), all active
alarms change to confirmed state. Confirmed alarms will disappear from the Alarmlist as soon as the respective
condition dismisses. If the condition is dismissed before acknowledging the alarm, the alarm will remain in the
Alarmlist as Inactive.
Alarm states
An alarm can have following states:
Active alarm: the alarm condition persists, alarm delay has elapsed.
Inactive alarm: the alarm condition has disappeared, but the alarm has not been confirmed.
Confirmed alarm: the alarm condition persists, but the alarm has already been confirmed.
Warning (Wrn)
The alarm appears in the Alarmlist and is recorded into the history log. Activates the output AL COMMON W RN
(PAGE 552) as well as the standard alarm outputs (HORN (PAGE 587) and ALARM (PAGE 560)).
IMPORTANT: The gen-set can start by itself after acknowledging the alarms if there is no longer an
active red alarm and the controller is in AUTO or TEST mode!
Alarmlist
Alarmlist is a container of active and inactive alarms. It will appear automatically on the controller display, if a
new alarm occurs, or can be displayed manually from the display menu.
Active alarms are shown as inverted, not yet confirmed alarms are marked with asterisk before them.
Alarmlist contains three types of alarms:
Controller built-in alarms
User configured alarms on binary or analog inputs
ECU alarms
ECU alarms
The ECU alarms are received from the ECU. The alarms are represented by the Diagnostic Trouble Code,
which contains information about the subsystem where the alarm occurred, the alarm type and the alarm
occurrence counter.
The most common fault codes are translated into text form. Other fault codes are displayed as a numeric code
and the engine fault codes list must be used to determine the reason.
Events Protection
Description
specification type
Value measured on analog input 1 is </> than Analog Protection 1
Analog Input 1 Wrn WRN
Wrn (page 244) setpoint.
Value measured on analog input 1 is </> than Analog Protection 1 Sd
Analog Input 1 Sd SD
(page 244) setpoint.
Value measured on analog input 2 is </> than Analog Protection 2
Analog Input 2 Wrn WRN
Wrn (page 246) setpoint.
Value measured on analog input 2 is </> than Analog Protection 2 Sd
Analog Input 2 Sd SD
(page 247) setpoint.
Value measured on analog input 3 is </> than Analog Protection 3
Analog Input 3 Wrn WRN
Wrn (page 249) setpoint.
Value measured on analog input 3 is </> than Analog Protection 3 Sd
Analog Input 3 Sd SD
(page 250) setpoint.
Value measured on analog input 4 is </> than Analog Protection 4
Analog Input 4 Wrn WRN
Wrn (page 252) setpoint.
Value measured on analog input 4 is </> than Analog Protection 4 Sd
Analog Input 4 Sd SD
(page 253) setpoint.
Battery voltage is out of limits given by Battery Undervoltage (page
Wrn Battery Voltage WRN
214) and Battery Overvoltage (page 215) setpoints.
Binary input Configurable Warning/BOC/Shutdown alarms on the binary inputs.
If the controller switches off during starting sequence (STARTER
Sd Battery Flat SD (PAGE 600) output is active) it doesn’t try to start again and activates
this protection (controller assumes bad battery condition).
Sd Start Fail SD Gen-set start failed. All crank attempts were tried without success.
Wrong check-sum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
Parameters Fail NONE
controller stays in INIT mode. Check all parameters, change value of
at least one parameter.
Sd Gen Lx >V
SD The generator voltage is out of limits given by Gen <V BOC and Gen
BOC Gen Lx <V
BOC >V Sd setpoints.
(where x=1,2,3)
BOC Gen V The generator voltage is unbalanced more than the value of Voltage
BOC
Unbalance Unbalance BOC (page 225) setpoint.
The generator frequency is out of limits given by Generator
BOC Gen >,
BOC Overfrequency BOC (page 226) and Generator Underfrequency BOC
<Frequency
(page 226) setpoints.
BOC Current The generator current is unbalanced more than the value of Current
BOC
Unbalance Unbalance BOC (page 223) setpoint.
Generator current exceeds the limit for IDMT protection given by
BOC Current IDMT BOC
Nominal Current (page 170) and IDMT Overcurrent Delay (page 222)
Note: This table does not contain all alarms in controller. It is only list of the most common alarms.
Record structure
Note: When some setpoint is changed, in history log is written its number of communication object.
An output for control of a contactor. Its state represents the breaker position requested by the
Close/Open controller. The breaker must react within 5 seconds to a close or open command, otherwise
an alarm is issued.
An output giving a 5 second pulse in the moment the breaker has to be closed. The output is
ON coil
intended for control of close coils of circuit breakers.
An output giving a pulse in the moment the breaker has to be opened. The pulse lasts until
OFF coil the feedback deactivates, but at least for 5 seconds. The output is intended for control of
open coils of circuit breakers.
The GCB UV coil output is active the whole time the gen-set is running (not in idle or cooling).
The MCB UV coil output is active when the controller is switched on. The output is
UV coil
deactivated for at least 5 seconds in the moment the breaker has to be switched off. The
output is intended for control of undervoltage coils of circuit breakers.
IMPORTANT: Also it is possible to use breakers without feedbacks. In this case there is check of
breaker real state.
There are three different time delays for breaker fail detection – see following diagrams.
When binary output breaker close/open is in steady state and breaker feedback is changed the breaker fail is
detected immediately (no delay).
When binary output breaker close/open opens there is 5 sec delay for breaker fail detection.
When binary output breaker close/open closes there is 5 sec delay for breaker fail detection.
Once mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 305).
In timer mode select Once. In timer settings adjust date and time of occurrence of timer. Also adjust the duration
of timer.
Daily mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 305).
In timer mode select Repeat. In repetition type select Daily. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th day of repetition
(Timer 1 Refresh Period (page 309)) and behavior of timer on weekends (Timer 1 Weekends (page 310)).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 3rd day at 12:00 for 1 hour including weekends.
In timer mode select Repeat. In repetition type select Weekly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the x-th week of repetition
(Timer 1 Refresh Period (page 309)) and days when timer should be active (Timer 1 Day (page 310)).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd week on Monday, Wednesday and Friday at 12:00 for 1 hour.
Monthly mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint Timer 1 Setup.
Note: First of all function of timer has to be adjusted via setpoint Timer 1 Function (page 305).
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition and the x-th day of repetition (Timer 1 Repeat Day In Month (page 311)). Than select the x-th month of
repetition.
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd day in 2nd month at 12:00 for 1 hour.
In timer mode select Repeat. In repetition type select Monthly. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the type of monthly
repetition, the x-th week of repetition and days in week. Than select the x-th month of repetition.
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 2nd week in 2nd month on Monday, Wednesday and Friday at 12:00 for 1 hour.
In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the interval of repetition
(shorter than 1 day).
Example: On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 4th hour for 1 hour.
Note: When the engine was running before and all above conditions are fulfilled, additional 2 s delay is
necessary to confirm “still engine”.
When any engine running conditions are appeared on still engine than the Wrn Stop Fail (page 668) is
activated with following delay:
for generator voltage from 10 V to < 50 % of nominal voltage, Wrn Stop Fail has delay 1 s
for generator voltage > 50 % of nominal voltage, Wrn Stop Fail has delay 200 ms
Oil pressure > Starting Oil Pressure (page 186), Wrn Stop Fail has delay 1 s
for detected RPM, there is no delay.
When the total time of stopping will exceed setpoint Stop Time (page 197) than the Wrn Stop Fail (page 668)
and binary outputs are activated. The controller will continuously try to stop the engine.
Image 5.31 Engine stops after first Stop Time (page 197)
Note: Curves can be modified via InteliConfig. In InteliConfig are also prepared some standard curves.
IMPORTANT: For right behavior of function, curve for this analog input has to be in percentage and
setpoint Fuel Tank Volume (page 210) has to be adjusted correctly.
6 back to Functions
Note: To delete PLC block just click on it and press delete button. Also delete selection function can by used.
Note: To see context help for selected PLC block just press F1 button.
Outputs
Sheet outputs are located at the right side of a sheet. Follow the procedure below to add or edit an input.
Doubleclick on a free output position to add new sheet output.
Doubleclick on an already created output to configure the output onto a controller output terminal or a logical
binary input (first of all some PLC block output has to be connected to this output to enable configuration of
output).
IMPORTANT: It is necessary to click on Connect button after selecting the output. Otherwise PLC
output is not connected to output.
Creating wires
Wires can be create between PLC inputs and PLC blocks and between PLC blocks and PLC outputs.
IMPORTANT: Keep the order of starting and finishing connection points. Wires between inputs and
blocks have to start from inputs. Wires between blocks and outputs have to start from blocks.
Note: To delete wire just click on it and press delete button. Also delete selection function can by used.
IMPORTANT: Please always check that the blocks are ordered correctly, especially if you use direct
feedbacks from outputs to inputs within one sheet. Wrong order may lead to incorrect results!!!
Hints
Use this function to enable or disable quick hints for blocks (controller help is not affected by this function).
PLC monitor
PLC monitor is a powerful tool for monitoring your PLC. Just click on PLC monitor button on main InteliConfig
page to see you PLC. Active inputs and outputs have blue color. Also wires with active signals have blue color.
IMPORTANT: It is not possible to edit PLC in PLC monitor tool.
5.4.23 Geo-fencing
Geo-fencing function is kind of protection that evaluates whether the actual GPS location is within predefined
area and based on the evaluation takes an action (sends sms, stops engine, make history record etc.). Function
is enabled by setpoint Geo-Fencing (page 326) or by logical binary input GEO-FENCING ENABLED (PAGE 535).
Using InteliConfig, it is possible to set two concentric geo-circles within which the unit is allowed to be located.
Each geo-circle is defined as circular geographic area with centre (common for both geo-circles) named Home
Position adjusted via setpoints Home Latitude (page 324) and Home Longitude (page 324) and radius named
Fence Radius adjusted via setpoints .Fence Radius 1 (page 325) and Fence Radius 2 (page 325).
Protections can be different for both circles. Protection are adjusted via setpoints Fence 1 Protection (page 327)
and Fence 2 Protection (page 328).
It is also possible to see the current position of the controller in WebSupervisor map view.
Note: Lamp icon blinking is defined as displaying active lamp icon and inverse colored active lamp icon in
required frequency.
Configuration sets can be changed via logical binary inputs ALTERNATE CONFIG 2 (PAGE 503) and ALTERNATE
CONFIG 3 (PAGE 503). Configuration set 1 is active when there is no input activated. In case that inputs
ALTERNATE CONFIG 2 (PAGE 503) and ALTERNATE CONFIG 3 (PAGE 503) are active at the same time, the
configuration set 3 is took in account.
ALTERNATE CONFIG 2 (PAGE 503) ALTERNATE CONFIG 3 (PAGE 503) Active configuration set
0 0 1
1 0 2
0 1 3
1 1 3
6.1 PC
6.1.1 Direct communication 132
6.1.2 Remote communication 134
Next way is to switch the CM-Ethernet to automatic IP address mode. Adjust the setpoint IP Address Mode
(page 380) to AUTOMATIC. In that case all IP settings are assigned by DHCP server. Then configure the
DHCP server to assign always the same IP address (i.e. static IP address) to the particular CM-Ethernet
according to it's MAC address.
Internet connection
Public static IP
If public static IP connection is to be used from the Internet, the IP address, which is entered into the client
computer, must be static and public in scope of the Internet.
If CM-Ethernet is connected to Internet via a local ethernet network then in most cases port forwarding
must be created from the public IP address of the network gateway to the local IP address of CM-
Ethernet at the port specified for ComAp protocol. Different port numbers can be used to create multiple
port forwarding rules in the same local network.
AirGate
This connection type is intended for remote connection from InteliConfig,or any other ComAp PC tool over the
Internet in situations, where obtaining fixed public IP address is not possible. Only two remote clients can be
connected at the same time.
This connection type is active if AirGate connection is enabled. Setpoint AirGate Address (page 386) must
contain AirGate server address. It can be entered in text form as well as numeric form. There is a public AirGate
server available at address "airgate.comap.cz".
Once the controller is attached to the Internet and the AirGate server address is properly adjusted then the
controller registers automatically to the server and an identification string AirGate ID is given to a controller,
which is visible at the controller screen.
To connect your PC tool to the controller use the AirGate connection, put the the same AirGate address as in
the controller into the AIRGATE ADDRESS field and use the AirGate ID displayed on the controller.
Event SMS
The InteliLite controller equipped with the CM-GPRS or CM-4G-GPS communication module is able to send
Event SMS according to the setting of setpoint:
Event Message (page 376)
Alarm SMS
The InteliLite controller equipped with the CM-GPRS or CM-4G-GPS communication module is able to send
Alarm SMS according to the setting of setpoints:
Wrn Message (page 377)
BOC Message (page 377)
Sd Messages (page 377)
Message structure:
Gen-set Name
AL=(Alarm 1, Alarm 2, Alarm x)
Note: Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active.
IMPORTANT: If wrong controller access code is set, then only help command is working.
Note: Between commands are internal delays adjusted due to system requirements.
Example: When the controller, in AUTO mode, with a controller name of “InteliLite-Test”, with the CM-
GPRS module and access code “0” receives the SMS:
0 man, start, gcb close, gcb open, stop, auto
Controller mode will be changed to MANUAL mode. The engine will be started and GCB will close. Then
GCB will open, the engine will stop and it will go into AUTO mode again.
The controller will send back the SMS (controller will respond to SMS after every command has been
finished, not sooner.):
#InteliLite-Test: <OK>,<OK>,<OK>, <OK>,<OK>, <OK>
The value <OK> or <ERROR> means if the command has been performed succesfuly or not.
Event Email
The InteliLite controller equipped with the CM-Ethernet communication module is able to send Event Email
according to the setting of setpoint:
Event Message (page 376)
Note: Firstly setpoints Email Address 1 (page 373) and SMTP Sender Address (page 367) (for CM-GPRS) or
SMTP Sender Address (page 379) (for CM-Ethernet) have to be adjusted.
Note: #Summer Time Mode (page 304) and Time Zone (page 376) have to be adjusted for correct time in emails.
Message structure:
Controller
-----------------------------------------------
Name: XXX
Serial number: XXX
SW branch: XXX
SW version: XXX
Application: XXX
Appl. version: XXX
Date: dd/mm/yyyy
Time: hh:mm:ss
Alarm list
-----------------------------------------------
Alarm 1
Alarm 2
Alarm 3
Events
-----------------------------------------------
hh:mm:ss Event 1
hh:mm:ss Event 2
hh:mm:ss Event 3
Note: Firstly setpoints Email Address 1 (page 373) and SMTP Sender Address (page 367) (for CM-GPRS) or
SMTP Sender Address (page 379) (for CM-Ethernet) have to be adjusted.
Note: #Summer Time Mode (page 304) and Time Zone (page 376) have to be adjusted for correct time in emails.
Message structure:
Controller
-----------------------------------------------
Name: XXX
Serial number: XXX
SW branch: XXX
SW version: XXX
Application: XXX
Appl. version: XXX
Date: dd/mm/yyyy
Time: hh:mm:ss
Alarm list
-----------------------------------------------
Alarm 1
Alarm 2
Alarm 3
History events
-----------------------------------------------
0 dd/mm/yyyy hh:mm:ss.0 Event 1
-1 dd/mm/yyyy hh:mm:ss.0 Event 2
-2 dd/mm/yyyy hh:mm:ss.0 Event 3
Note: Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active.
The Web Server is designed for basic monitoring and adjustment of the controller using a web browser. Just put
the controller IP address into the browser to display the main controller web page like http://192.168.1.254. You
will be asked for the controller access code prior to entering the web pages.
IMPORTANT: Do not use the browser navigation buttons as "Back", "Forward" or "Reload". Use
the links and the reload button located in the toolbar instead.
Note: Only two remote clients can be connected to the Web Server at one moment. If you close your web
browser without disconnecting from the CM-Ethernet ("Exit" button at the web pages), the connection will be
blocked for next 5 minutes.
6 back to Communication
6 back to Communication
6.2.1 SNMP
SNMP is an UDP-based client-server protocol used for providing data and events into a supervisory system
(building management system). The controller plays the role of a „SNMP Agent“ while the supervisory system
plays the role of a „SNMP Manager“.
CM-Ethernet module is required for SNMP function
Supported versions - SNMP v1 and SNMP v2c
The SNMP Agent function is to be enabled by the setpoint SNMP Agent (page 383) in the CM-Ethernet setpoint
group. The setpoints SNMP RD Community String (page 383) and SNMP WR Community String (page 384) in the
MIB table
The „MIB table“ (Management Information Base) is a table which gives to the Manager description of all objects
provided by the Agent.
The MIB table is specific for each controller type and configuration
The MIB table is to be exported from the controller configuration using InteliConfig
Controllers with identical firmware and configuration share also identical MIB table, however if the
configuration and/or firmware is not identical the MIB table is different and must be exported separately for
each controller.
The root node of the MIB table of InteliLite controller is enterprises.comapProjekt.il, which is
1.3.6.1.4.1.28634.14. Under this node there are following sub-nodes :
Notifications group (SMI v2 only) contains definitions of all notification-type objects that the Agent may send
to the Manager.
GroupRdFix contains read-only objects that exist in all controller regardless of the firmware version/type and
configuration.
GroupRdCfg contains read-only objects that depend on the firmware version/type and configuration.
GroupWrFix contains read-write objects that exist in all controller regardless of the firmware version/type
and configuration.
GroupWrCfg contains read-write objects that depend on the firmware version/type and configuration.
GroupW contains write-only objects.
NotificationData group contains objects that are accessible only as bindings of the notification messages.
SMI version
In InteliConfig the MIB table may be exported in two different formats – SMI v1 and SMI v2. The format which
shall be used for export depends on the SNMP Manager and SMI version that it does support.
Typically, SMI v1 is used for SNMP v1 and vice versa, but it is not a rule and SMI v2 may be also used for
SNMP v1.
1) For list of commands, arguments and description of the procedure of invoking commands see the description
of the MODBUS protocol.
Address space
The object address space is separated into several areas as described in the table below. The actual mapping of
specific controller data objects to specific MODBUS addresses, which depends on configuration, can be
exported into a text file from the appropriate controller archive using InteliConfig. There are several special
registers with fixed meaning (reserved registers) which are listed in a separate table in this chapter.
Number of
Data type Meaning Data maping
registers
MSB = sign extension
Integer8 1-byte signed integer 1
LSB = value
MSB = 0
Unsigned8 1-byte unsigned integer 1
LSB = value
MSB = value, MSB
Integer16 2-byte signed integer 1
LSB = value, LSB
MSB = value, MSB
Unsigned16 2-byte unsigned integer 1
LSB = value, LSB
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Integer32 4-byte signed integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
MSB1 = value, byte 3 (MSB)
LSB1 = value, byte 2
Unsigned32 4-byte unsigned integer 2
MSB2 = value, byte 1
LSB2 = value, byte 0 (LSB)
MSB = 0
Binary8 8-bit binary value 1
LSB = value, bits 0-7
MSB = value, bits 8-15
Binary16 16-bit binary value 1
LSB = value, bits 0-7
MSB1 = value, bits 24-31
LSB1 = value, bits 16-23
Binary32 32-bit binary value 2
MSB2 = value, bits 8-15
LSB2 = value, bits 0-7
MSB = 0
Char 1-byte ASCII character 1
LSB = ASCII value of the character
MSB = 0
StrList Index into a list of strings 1
LSB = index into the list
ShortStr Zero-terminated string of 8 MSB1 = ASCII value of the 1. character
Reserved registers
There are several registers with specific meaning. These registers are available in all controllers regardless of
the configuration.
Register Number of
Access Data type Meaning
addresses registers
4200 - 4201 2 read/write Time RTC Time in BCD code
4202 - 4203 2 read/write Date RTC Date in BCD code
Index of the language that is used for text
4204 1 read/write Unsigned8 data provided by MODBUS (e.g. alarmlist
messages).
Last application error. To be read after the
4205 - 4206 2 read Unsigned32 device returns the exception code 04. It
contains specific information about the error.
Writing:command argument
4207 - 4208 2 read/write Unsigned32
Reading: command return value
4209 1 write Unsigned16 Command code
4010 1 - - Not implemented
4211 1 write Unsigned16 Password
4212 - 4213 2 read Unsigned32 Communication status
4214 1 read Unsigned8 Number of items in the Alarmlist
4215 - 4241 27 read Alarm 1. record in alarm list
4242 - 4268 27 read Alarm 2. record in alarm list
4269 - 4295 27 read Alarm 3. record in alarm list
4296 - 4322 27 read Alarm 4. record in alarm list
4323 - 4349 27 read Alarm 5. record in alarm list
4350 - 4376 27 read Alarm 6. record in alarm list
4377 - 4403 27 read Alarm 7. record in alarm list
4404 - 4430 27 read Alarm 8. record in alarm list
4431 - 4457 27 read Alarm 9. record in alarm list
4458 - 4484 27 read Alarm 10. record in alarm list
4485 - 4511 27 read Alarm 11. record in alarm list
4512 - 4538 27 read Alarm 12. record in alarm list
4539 - 4565 27 read Alarm 13. record in alarm list
Table: Values
Allowed MODBUS functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Controller
01053 8213 BatteryVoltage V Integer 2 1 0 400
I/O
We read value 240 from register 01053. From table of modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.
Reading Nominal power
Export table of values from InteliConfig
Table: Values
Allowed MODBUS functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
01228 9018 Nominal Power kW Integer 2 0 0 32767 Generator
Table: Values
Allowed MODBUS functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Binary
01068 8235 Binary#2 2 0 - - Controller I/O
Inputs
Binary inputs is 00010010. It means Binary input 2 and binary input 5 are active.
Note: You can use modbus function 4 insted of 3, rest of data remain same (CRC differs).
Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses Source
C.O.# Name of Value Bit Name
Modbus Addr. = Value Bit # Group
State # Name of State Activated by protection(s):
Prot. Addr. = State
00000 Value 8235 Binary Inputs 1 GCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 2 MCB Feedback Controller I/O
00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I/O
Note: Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).
Table: Setpoints
Allowed MODBUS functions: 03, 04, 06, 16
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Nominal Basic
03008 8276 kW Unsigned 2 0 1 5000
Power Settings
Table: Values
Allowed MODBUS functions: 03, 04
Register(s) Com.Obj. Name Dimension Type Len Dec Min Max Group
Controller
01053 8213 BatteryVoltage V Integer 2 1 0 400
I/O
We read value 240 from register 01053. From table of modbus registers we get dimension of read value and
"Dec". Dec=1 means shift one decimal place to the right. So battery voltage is 24.0 V.
6 back to Connection to 3rd party systems
Range 0-2500 Ω
Max. output current 250 mA / 36 V
Input impedance 170 Ω
Charging fail
Adjustable ±2 % from value in range
threshold
Accuracy 0-2500 Ω
Voltage measurement ±1,5 kΩ in range 2,5-15 kΩ
3ph-n Gen voltage , 3ph-n
Measurement inputs Magnetic pickup
Mains
4 Vpk-pk to 50 Vpk-pk in
Measurement range 277 V
range 4 Hz to 1 kHz
Max. allowed voltage 350 V
6 Vpk-pk to 50 Vpk-pk in
Accuracy 1% Voltage input range
range 1 kHz to 5 kHz
Frequency range 40-70 Hz (accuracy 0.1 Hz) 10 Vpk-pk to 50 Vpk-pk in
Input impedance 0,72 MΩ ph-ph , 0,36 MΩ ph-n range 5 kHz to 10 kHz
Frequency input
4 Hz to 10 kHz
range
Frequency
measurement 0,2 % from range 10 kHz
tolerance
For full list of setpoints go to the chapter List of setpoints (page 164).
Generator <> Frequency Analog Protection 1 Delay 245 Analog Protection 9 Delay 268
Delay 227 Analog Switch 1 On 245 Analog Switch 9 On 269
Analog Switch 1 Off 246 Analog Switch 9 Off 270
Load Shedding Analog Protection 2 Wrn 246 Analog Protection 10 Wrn 270
Overload Protection 228 Analog Protection 2 Sd 247 Analog Protection 10 Sd 271
Short Circuit Protection 228 Analog Protection 2 Delay 247 Analog Protection 10
IDMT Overcurrent Analog Switch 2 On 248 Delay 271
Protection 229 Analog Switch 2 Off 249 Analog Switch 10 On 272
Current Unbalance Analog Protection 3 Wrn 249 Analog Switch 10 Off 273
Protection 229 Analog Protection 11 Wrn 273
Analog Protection 3 Sd 250
Gen-Set Name
Setpoint group Basic settings Related FW 1.7.0
Range [units] 0 .. 15 characters [-]
Default value InteliLite Alternative config NO
Step [-]
Comm object 8637 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-Set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller’s
configuration menu.
Note: If the Gen-Set Name is "TurboRunHours", the running hours will be counted faster - 1 minute in
real will represent 1 hour.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Power Split Phase 1
(page 335), Nominal Power Split Phase 2 (page 339) and Nominal Power Split Phase 3 (page 343).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Power 1 (page 335),
Nominal Power 2 (page 339) and Nominal Power 3 (page 343).
Nominal Current
Setpoint group Basic settings Related FW 1.7.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1A
Comm object 8275 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type (page 171).
Description
It is current limit for mains current protections and means maximal continuous mains current. Nominal
Current can be different from mains rated current value.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Current 1 (page 333),
Nominal Current 2 (page 337) and Nominal Current 3 (page 341).
CT Location
Setpoint group Basic settings Related FW 1.7.0
Range [units] Load / Gen-set [-]
Default value Gen-set Alternative config NO
Step [-]
Comm object 11625 Related applications AMF
Config level Advanced
Setpoint visibility Always
Description
Adjustment of location of current measurement.
Load: Current CT´s are physically placed on Load (typically between GCB and MCB).
Gen-Set: Current CT´s are physically placed on GenSet (typically before GCB).
Note: For more details about this function see chapter CT Location (page 28).
Connection type
Setpoint group Basic settings Related FW 1.7.0
Range [units] Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 11628 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
Split Phase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: To lock this setpoint against editing you also have to lock setpoint Connection Type 1 (page 331),
Connection type 2 (page 335) and Connection type 3 (page 339).
PT Ratio
Setpoint group Basic settings Related FW 1.7.0
Range [units] 0,1 .. 500,0 [V/V]
Default value 1,0 V/V Alternative config NO
Step 0,1 V/V
Comm object 9579 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
Nominal Frequency
Setpoint group Basic settings Related FW 1.7.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 8278 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Frequency 1 (page
333), Nominal Frequency 2 (page 337) and Nominal Frequency 3 (page 341).
Nominal RPM
Setpoint group Basic settings Related FW 1.7.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 8253 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal RPM 1 (page 333),
Nominal RPM 2 (page 337) and Nominal RPM 3 (page 341).
Controller mode
Setpoint group Basic settings Related FW 1.7.0
Range [units] OFF / MAN / AUTO / TEST [-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via MODBUS. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
Power On Mode
Setpoint group Basic settings Related FW 1.7.0
Range [units] Previous / OFF [-]
Default value Previous Alternative config NO
Step [-]
Comm object 13000 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts controller mode after power on of controller.
Previous When controller is power on, than is switched into last mode before power off.
OFF When controller is power on, than is switched into OFF mode.
Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via LBI.
After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
Controller Address
Setpoint group Basic settings Related FW 1.7.0
Range [units] 1 .. 32 [-]
Default value 1 Alternative config NO
Step 1
Comm object 24537 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more IL controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note: When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Backlight Timeout
Setpoint group Basic settings Related FW 1.7.0
Range [units] Disabled / 1 .. 255 [min]
Default value Disabled Alternative config NO
Step 1 min
Comm object 10121 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
Note: Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
AUTO If there is some ECU which send valid running hours, then this value is used.
Otherwise value from internal counter is used.
ECU Running hours are taken from ECU if ECU send valid data. It is not possible to set
and reset this value in statistics.
INTERNAL Running hours are taken from internal counter. It is possible to set and reset this value
in statistics.
Note: It is not necessary to restart controller when this setpoint is changed. Change of this setpoint
should be applied immediately.
Cranking Attempts
Setpoint group Engine settings Related FW 1.7.0
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
Starting RPM
Setpoint group Engine settings Related FW 1.7.0
Range [units] 5 .. 50 [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 175)
Comm object 8254 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the “firing” speed level as percent value of the Nominal RPM (page 175). If this level is
exceeded the engine is considered as started.
Choke Function
Setpoint group Engine settings Related FW 1.7.0
Range [units] Disabled /Fixed Time / Temp Based [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15717 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 574) is configured.
Description
This setpoint defines choke function behavior.
Disabled Choke function is disabled and logical binary output CHOKE (PAGE 574) is activated
under no circumstances.
Fixed Time Choke time is fixedly defined by Choke Time (page 187) setpoint.
Temp Based Choke time is calculated using actual engine (coolant) temperature. Setpoints Choke
Start Temp (page 188) and Choke Increment (page 189) are taken into consideration.
Choke Time
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0–3600 [s]
Default value 0s Alternative config NO
Step 1s
Comm object 13011 Related applications MRS. AMF
Config level Advanced
Only when LBO CHOKE (PAGE 574) is configured and setpoint Choke Function (page
Setpoint visibility
187) = Fixed Time.
Description
Defines time logical binary output CHOKE (PAGE 574) is activated for when fixed time is used. When setpoint
Choke Function (page 187) is set to Temp Based value, Choke Time value have no effect.
Note: If setpoint Choke Lead (page 191) is set to nonzero value, total time the CHOKE output is activated
still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than Choke
Leadto ensure expected Choke behavior.
Note: If setpoint Choke Lead (page 191) is set to nonzero value, total time the CHOKE output is activated
still matches calculated value (based on actual temperature and setpoints Choke Increment and Choke
Start Temp (page 188)) This mean that adjusted parameters should ensure that calculated Choke Time
will be longer than Choke Leadto ensure expected Choke behavior.
Note: LBO PRESTART (PAGE 596) goes to logical zero when Fuel Solenoid Lead goes to logical one.
Note: This setpoint is used only for diesel Fuel Solenoid (page 183)
Idle Time
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. 600 [s]
Default value 12 s Alternative config NO
Step 1s
Comm object 9097 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Idle Time delay starts when RPM exceeds Starting RPM (page 185). Start fail is detected when during Idle
state RPM decreases below 2 RPM.
The output IDLE/NOMINAL (PAGE 588) remains inactive during the idle period. Binary output Idle/Nominal
opens during Cooling period again. This output can be used for switching the governor between idle and
Subgroup: Stopping
Cooling Speed
Setpoint group Engine settings Related FW 1.7.0
Range [units] Idle / Nominal [-]
Default value Nominal Alternative config NO
Step [-]
Comm object 10046 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Selects the function of the binary output IDLE/NOMINAL (PAGE 588) during engine cooling state.
Idle Cooling is executed at Idle speed and generator protections are switched off.
Nominal Cooling is executed at Nominal speed and generator protections are active.
Note: When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note: Binary output IDLE/NOMINAL (PAGE 588) must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
Cooling Time
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. 3 600 [s]
Default value 30 s Alternative config NO
Step 1s
Comm object 8258 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Stop Time
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. 600 [s]
Default value 60 s Alternative config NO
Step 1s
Comm object 9815 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID (PAGE
579) has been de-energized and the STOP SOLENOID (PAGE 601) energized. The stop solenoid remains
energized for the entire stop time period.
Subgroup: D+ Function
D+ Function
Setpoint group Engine settings Related FW 1.7.0
Range [units] Enabled / ChargeFail / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9683 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Behavior of D+ terminal.
Enabled The D+ terminal is used for both functions – “running engine” detection and charge fail
D+ Delay
Setpoint group Engine settings Related FW 1.7.0
Range [units] 1..255 [s]
Default value 1s Alternative config NO
Step 1s
Comm object 14960 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 198) is not set to Disabled value.
Description
This setpoint adjusts delay for D+ function. This delay is used for:
Alarm Charging Alternator Fail.
For engine running condition - disengagement of starter
D+ Alarm Type
Setpoint group Engine settings Related FW 1.7.0
Range [units] No Protec/Wrn/Sd [-]
Default value Wrn Alternative config NO
Step [-]
Comm object 15751 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 198) is not set to Disabled value.
Description
This setpoint adjusts type of alarm Charging Alternator Fail.
Overspeed Sd
Setpoint group Engine settings Related FW 1.7.0
Range [units] Underspeed Sd (page 201) .. 200 [%]
Default value 115% Alternative config NO
Step 1 % of Nominal RPM (page 175)
Comm object 8263 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for over speed protection. Relative to the nominal speed.
Underspeed Sd
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. Overspeed Sd (page 201) [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 175)
Comm object 8260 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
Overspeed Overshot
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. 50 [%]
Default value 20% Alternative config NO
Step 1 % of Nominal RPM (page 175)
Comm object 14107 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint rise the upper limit of overspeed protection for the time which is defined in setpoint Overspeed
Overshot Period (page 202). In this time the upper limit of protection is Overspeed Sd (page 201) + Overspeed
Overshoot.
Oil Pressure Sd
Setpoint group Engine settings Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
the value is defined by
Default value Alternative config NO
analog sensor curve
Step the step is defined by analog sensor curve
Comm object 12779 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input OIL PRESSURE (PAGE 637) is configured
Description
Shutdown threshold level for OIL PRESSURE (PAGE 637).
Coolant Temperature Sd
Setpoint group Engine settings Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
the value is defined by
Default value Alternative config NO
analog sensor curve
Step the step is defined by analog sensor curve
Comm object 12780 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input COOLANT TEMP (PAGE 634) is configured
Description
Shutdown or BOC threshold level for COOLANT TEMP (PAGE 634).
Temperature Switch On
Setpoint group Engine settings Related FW 1.7.0
Range [units] the range is define by sensor curve (analog or ECU)
the value is defined by
Default value sensor curve (analog or Alternative config NO
ECU)
Step the step is defined by sensor curve (analog or ECU)
Comm object 8688 Related applications AMF, MRS
Config level Standard
Visible only if the logical binary output TEMPERATURE SWITCH (PAGE 603) is
Setpoint visibility
configured.
Description
Threshold level for switching the binary output TEMPERATURE SWITCH (PAGE 603) on.
Note: Value from analog input has higher priority than ECU.
Fuel Level Sd
Setpoint group Engine settings Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
the value is defined by
Default value Alternative config NO
analog sensor curve
Step the step is defined by analog sensor curve
Comm object 12898 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input FUEL LEVEL (PAGE 635) is configured
Description
Shutdown or BOC threshold level for FUEL LEVEL (PAGE 635).
Fuel Pump On
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. Fuel Pump Off (page 212) [%]
Default value 20 % Alternative config NO
Step 1%
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Visible only if the logical binary output FUEL PUMP (PAGE 579) is configured and
Setpoint visibility
logical binary input FUEL PUMP ON/OFF (PAGE 533) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 579) on.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 533) is configured then binary
output FUEL PUMP (PAGE 579) is control by this binary input. Setpoints Description (page 211)
and Fuel Pump Off (page 212) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 579) is configured.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 533) is configured then binary
output FUEL PUMP (PAGE 579) is control by this binary input. Setpoints Fuel Pump On (page 211)
and Fuel Pump Off (page 212) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 579) is configured.
Subgroup: Maintenance
Maintenance Timer 1
Setpoint group Engine settings Related FW 1.7.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1h
Comm object 11616 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 3
Setpoint group Engine settings Related FW 1.7.0
Range [units] -10 000 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1h
Comm object 11618 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 3 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Battery Undervoltage
Setpoint group Engine settings Related FW 1.7.0
Range [units] 8,0 V .. Battery Overvoltage (page 215) [V]
Default value 18,0 V Alternative config NO
Step 0,1 V
Comm object 8387 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery voltage.
Power Switch On
Setpoint group Engine settings Related FW 1.7.0
Range [units] 0 .. 32 000 [kW]
Default value 100 kW Alternative config NO
Step 1 kW
Comm object 11658 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Visible only if the logical binary output POWER SWITCH (PAGE 596) is configured.
Overload BOC
Setpoint group Generator settings Related FW 1.7.0
Range [units] Overload Wrn (page 220) .. 200 [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 170)
Comm object 8280 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker Open
and gen-set Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Overload Wrn
Setpoint group Generator settings Related FW 1.7.0
Range [units] 0 .. Overload BOC (page 220) [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 170)
Comm object 9685 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for generator overload (in % of Nominal power) protection. This is only warning.
Overload Delay
Setpoint group Generator settings Related FW 1.7.0
Range [units] 0,0 .. 600,0 [s]
Default value 5,0 s Alternative config NO
Step 0,1 s
Comm object 8281 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Overload BOC (page 220)Overload BOC (page 220) and Overload Wrn (page 220) protection.
Note: Reaction time is limited to 3600 s = 60 minutes. IDMT protection is not active for Reaction time
values longer than 60 minutes.
Overcurrent
Overcurrent IDMT Delay
≤ 100 % 101 % 110 %
Reaction time 0,2 s No action 20 s 2s
2s No action 200 s 20 s
20 s No action 2000 s 200 s
Generator Overvoltage Sd
Setpoint group Generator settings Related FW 1.7.0
Range [units] Generator Overvoltage Wrn (page 224) .. 200 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-N (page 173) or Nominal Voltage Ph-Ph (page 173)
Comm object 8291 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Overload Protection
Setpoint group Protections Related FW 1.7.0
Range [units] Enabled/Disabled/By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15664 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Overload protection.
Protection is enabled. Behavior of protection is adjusted via setpoints Short Circuit BOC
Enabled:
(page 221) and Short Circuit BOC Delay (page 221).
Disabled: Protection is disabled.
By LBI: Protection is enabled or disabled by the state of LBI PROTECTION ENABLE (PAGE 539).
Underspeed Protection
Setpoint group Protections Related FW 1.7.0
Range [units] Enabled / Disabled / By LBI [-]
Default value Enabled Alternative config NO
Step [-]
Comm object 15671 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts the behavior of generator Underspeed protection.
If some delay between MCB FEEDBACK (PAGE 538) deactivation and closing of GCB CLOSE/OPEN (PAGE
580) output is required, then the Transfer Delay must be set to sum of “MCB opening” + “Delay” time.
This delay is also used in dual operation function. This delay is used when load from first gen-set is
transferred to second gen-set. Delay starts to countdown when GCB of first gen-set is open. When this
delay countdown, GCB of second gen-set is closed. This delay is important for correct function of external
interlock.
Mains Overvoltage
Setpoint group AMF settings Related FW 1.7.0
Range [units] Mains Undervoltage (page 236) .. 150 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-Ph (page 173)
Comm object 8305 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Operation Mode (page 177)
Description
Threshold for mains overvoltage. All three phases are checked. Maximum out of three is used.
Mains Undervoltage
Setpoint group AMF settings Related FW 1.7.0
Range [units] 50 .. Mains Overvoltage (page 236) [%]
Default value 60 % Alternative config YES
Step 1 % of Nominal Voltage Ph-Ph (page 173)
Comm object 8307 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Operation Mode (page 177)
Description
Threshold for mains undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Mains Overfrequency
Setpoint group AMF settings Related FW 1.7.0
Range [units] Description (page 238) .. 150 [%]
Default value 102,0 % Alternative config NO
Step 1,0 % of Nominal Frequency (page 174)
Comm object 8310 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Operation Mode (page 177)
Description
Threshold for mains overfrequency.
When Return From Island = MANUAL and there is a Mains Fail, gen-set is started and
take the load. After mains return the load have to manually transfer to mains. Also in
Manual Alarmlist will be displayed Manual Restore (page 674) alarm.
Note: Select MANUAL in case you need to manually control the moment when the
load is transferred back to the mains.
Auto No automatic mode change is performed.
MCB Logic
Setpoint group AMF settings Related FW 1.7.0
Range [units] Close On / Close Off [-]
Default value Close Off Alternative config NO
Step [-]
Comm object 8444 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Operation Mode (page 177)
Description
The set point influences the behavior of the output MCB CLOSE/OPEN (PAGE 590).
Close On When the output MCB CLOSE/OPEN (PAGE 590) is closed – MCB should be closed.
Close Off When the output MCB CLOSE/OPEN (PAGE 590) is closed – MCB should be opened.
Mains Fail The command to open the MCB is given immediately after mains fail condition is evaluated.
If the mains will return into parameters after MCB was opened and before GCB is closed, timer
MCB Close Delay (page 235) is applied before MCB closing.
Gen Run MCB will be opened when engine will be running and it will be possible to transfer load from
Mains to gen-set (after stabilisation phase).
Note: This option should be used for MCBs using 230V control and not equipped with the undervoltage
coil.
Swap Gen-sets
Setpoint group Dual Operation Related FW 1.7.0
Range [units] Enabled / Disabled [-]
Default value Enabled h Alternative config NO
Step [-]
Comm object 16041 Related applications AMF, MRS
Config level Advanced
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
Setpoint visibility
345) and COM2 Mode (page 347)
Description
This setpoint enables or disables swapping of gen-sets on load in dual operation.
Enabled Master and Slave are swapped based on their actual running hours.
Master and Slave are not swapped. Controller with lower running hours starts and then runs
Disabled
until mains returns or until controller shutdown - then second controller starts.
Analog Protection 1 Sd
Setpoint group General Analog Inputs Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
the value is defined by
Default value Alternative config NO
analog sensor curve
Step the step is defined by analog sensor curve
Comm object 9260 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT 01 (PAGE 607) is configured
Description
Shutdown or BOC threshold level for AIN PROT 01 (PAGE 607).
Note: These setpoints are used only if LAI AIN PROT 01 (PAGE 607) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Switch 1 On
Setpoint group General Analog Inputs Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
the value is defined by
Default value Alternative config NO
analog sensor curve
Step the step is defined by analog sensor curve
Comm object 11407 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical binary output AIN SWITCH01 (PAGE 560) is configured
Description
Threshold level for switching the binary output AIN SWITCH01 (PAGE 560) on. The value is measured from
AIN SWITCH 01 (PAGE 627) analog input.
Group: Scheduler
Subgroup: Time & Date
Time
Setpoint group Scheduler Related FW 1.7.0
Range [units] HH:MM:SS [-]
Default value 0:0:0 Alternative config NO
Step [-]
Comm object 24554 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Real time clock adjustment.
Timer 1 Function
Setpoint group Scheduler Related FW 1.7.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / Mode OFF [-]
Default value Disable Alternative config NO
Step [-]
Comm object 15358 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following timer functions. Binary output EXERCISE TIMER 1 (PAGE 578) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 305) is configured for OFF mode and
Timer 2 Function (page 312) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 1 Repetition
Setpoint group Scheduler Related FW 1.7.0
Range [units] Off / Once / Repeated [-]
Default value Off Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 305)
Description
Defines repetition of Timer 1 Function (page 305).
Timer 1 Duration
Setpoint group Scheduler Related FW 1.7.0
Range [units] [HH:MM]
Default value 00:00 Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 305)
Description
Timer 1 Function (page 305) duration time.
Range [units]: 1 .. 1000 [day]. This setpoint adjust that every X day the timer will be
activated.
Daily Example: If you have daily repetition and you set this setpoint to 2, then every
second day from first occurrence of Timer 1 Function (page 305), the Timer 1
Function (page 305) will be activated.
Range [units]: 1 .. 60 [week]. This setpoint adjust that every X week the timer will be
activated.
Example: If you have weekly repetition and you set this setpoint to 2, then every
Weekly
second week from first occurrence of Timer 1 Function (page 305), the Timer 1
Function (page 305) will be activated in selected days adjusted by Timer 1 Day
(page 310).
Range [units]: 1 .. 12 [month]. This setpoint adjust that every X month the timer will be
activated.
Example: If you have monthly repetition and you set this setpoint to 2, then every
Monthly second month from first occurrence of Timer 1 Function (page 305), the Timer 1
Function (page 305) will be activated in selected day of month adjusted by Timer 1
Repeat Day In Month (page 311) or in selected days of week of month adjusted by
Timer 1 Day (page 310) and Timer 1 Repeat Week In Month (page 312).
Range [units]: [HH:MM]. This setpoint adjust that every X short period the timer will
be activated.
Short Period Example: If you have short period repetition and you set this setpoint to 2, then
every second minute from first occurrence of Timer 1 Function (page 305), the
Timer 1 Function (page 305) will be activated.
Timer 1 Function (page 305) counter is running on the weekends and Timer 1 Function
Including
(page 305) can be active.
Timer 1 Function (page 305) counter is running on the weekends but Timer 1 Function
Skip
(page 305) isn’t active.
Timer 1 Function (page 305) counter isn’t running on the weekends and Timer 1 Function
(page 305) isn’t active. If the activation of timer is counted on the weekend, than timer will
Postpone
be activated after weekend. Another activation of timer is counted from original date of
first occurrence date.
Timer 1 Day
Setpoint group Scheduler Related FW 1.7.0
Range [units] Monday / Tuesday / Wednesday / Thursday / Friday / Saturday/ Sunday[-]
Default value All OFF Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 305)
Description
Use this setpoint to include or exclude individual days of week. To select the day use Up and Down buttons.
To change the value of day use Enter button.
Repeated Day Chose one day in month when Timer 1 Function (page 305) will be activated.
Repeated Day In Week Chose days in one week when Timer 1 Function (page 305) will be activated.
Subgroup: Timer 2
Timer 2 Function
Setpoint group Scheduler Related FW 1.7.0
Range [units] Disable / No Func / TEST / Test OnLd / MFail Blk / Mode OFF [-]
Default value No Func Alternative config NO
Step [-]
Comm object 15359 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose from following Timer functions. Binary output EXERCISE TIMER 2 (PAGE 578) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 305) is configured for OFF mode and
Timer 2 Function (page 312) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Timer 2 Repetition
Setpoint group Scheduler Related FW 1.7.0
Range [units] Off / Once / Repeated [-]
Default value Off Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 312)
Description
Defines repetition of Timer 2 Function (page 312).
Timer 2 Duration
Setpoint group Scheduler Related FW 1.7.0
Range [units] [HH:MM]
Default value 00:00 Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 312)
Description
Timer 2 Function (page 312) duration time.
Range [units]: 1 .. 1000 [day]. This setpoint adjust that every X day the timer will be
activated.
Daily Example: If you have daily repetition and you set this setpoint to 2, then every
second day from first occurrence of Timer 2 Function (page 312), the Timer 2
Function (page 312) will be activated.
Range [units]: 1 .. 60 [week]. This setpoint adjust that every X week the timer will be
activated.
Example: If you have weekly repetition and you set this setpoint to 2, then every
Weekly
second week from first occurrence of Timer 2 Function (page 312), the Timer 2
Function (page 312) will be activated in selected days adjusted by Timer 2 Day
(page 317).
Range [units]: 1 .. 12 [month]. This setpoint adjust that every X month the timer will be
activated.
Example: If you have monthly repetition and you set this setpoint to 2, then every
Monthly second month from first occurrence of Timer 2 Function (page 312), the Timer 2
Function (page 312) will be activated in selected day of month adjusted by Timer 2
Repeat Day In Month (page 318) or in selected days of week of month adjusted by
Timer 2 Day (page 317) and Timer 2 Repeat Week In Month (page 319).
Range [units]: [HH:MM]. This setpoint adjust that every X short period the timer will
be activated.
Short Period Example: If you have short period repetition and you set this setpoint to 2, then
every second minute from first occurrence of Timer 2 Function (page 312), the
Timer 2 Function (page 312) will be activated.
Timer 2 Function (page 312) counter is running on the weekends and Timer 2 Function
Including
(page 312) can be active.
Timer 2 Function (page 312) counter is running on the weekends but Timer 2 Function
Skip
(page 312) isn’t active.
Timer 2 Function (page 312) counter isn’t running on the weekends and Timer 2 Function
(page 312) isn’t active. If the activation of timer is counted on the weekend, than timer will
Postpone
be activated after weekend. Another activation of timer is counted from original date of
first occurrence date.
Timer 2 Day
Setpoint group Scheduler Related FW 1.7.0
Range [units] Monday / Tuesday / Wednesday / Thursday / Friday / Saturday/ Sunday[-]
Default value All OFF Alternative config NO
Step [-]
Comm object 0 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 2 Function (page 312)
Description
Use this setpoint to include or exclude individual days of week. To select the day use Up and Down buttons.
To change the value of day use Enter button.
Repeated Day Chose one day in month when Timer 2 Function (page 312) will be activated.
Repeated Day In Week Chose days in one week when Timer 2 Function (page 312) will be activated.
Rental Timer 1
Setpoint group Scheduler Related FW 1.7.0
Range [units] Disabled / 1 .. 8 760 [h]
Default value Disabled Alternative config NO
Step 1h
Comm object 14326 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Another engine start is not allowed when this timer elapsed. This timer is based on engine running hours. The
alarm Rental Timer 1 Elapsed (page 658) will be recorded in alarm list and the binary output AL RENTAL
TIMER 1 (PAGE 558) will close.
IMPORTANT: To reset Rental Timer 1 (page 319) we have to set up Rental Timer 1 (page 319)
again. It means go to setpoint group Scheduler and to the setpoint Rental Timer 1 (page 319).
Then press enter button , change the value if it is necessary and press enter button
again.
When the Rental Timer 1 (page 319) elapsed during engine run the gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 323)timer will start in this moment. The engine will be cooled and stopped
when the Rental Timer BOC (page 323) time elapsed.
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 1 (page 319) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 323) protection.
Rental Timer 2
Setpoint group Scheduler Related FW 1.7.0
Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Alternative config NO
Step 1 day
Comm object 14367 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Another engine start is not allowed when this timer elapsed. This timer is based on date. At the midnight of
the last day the alarm Rental Timer 2 Elapsed (page 658) will be recorded in alarm list and the binary
output AL RENTAL TIMER 2 (PAGE 559) will close.
IMPORTANT: To reset Rental Timer 2 (page 321) we have to set up Rental Timer 2 (page 321)
again. It means go to setpoint group Scheduler and to the setpoint Rental Timer 2 (page 321).
Then press enter button , change the value if it is necessary and press enter button
again.
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 2 (page 321) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 323) protection.
Note: This value can be also obtained automatically via logical binary input GEO HOME POSITION (PAGE
534). In case of activation of this binary input for at least 2 seconds, setpoint will be adjusted
automatically from actual coordinates from GPS signal.
Home Longitude
Setpoint group Geo-Fencing Related FW 1.7.0
Range [units] -180,0000..180,0000 [°]
Default value 0,0000 ° Alternative config NO
Step 0,0001 °
Comm object 14607 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust longitude of "home" position. Home is position where gen-set should runs. Positions on
east hemisphere have positive value, position on west hemisphere have negative value.
Note: This value with Home Latitude (page 324) are used for counting Fence Radius 1 (page 325) and
Fence Radius 2 (page 325).
Note: This value can be also obtained automatically via logical binary input GEO HOME POSITION (PAGE
534). In case of activation of this binary input for at least 2 seconds, setpoint will be adjusted
automatically from actual coordinates from GPS signal.
Fence Radius 2
Setpoint group Geo-Fencing Related FW 1.7.0
Range [units] 0,0..99,9 [km]
Default value 0,0 km Alternative config NO
Step 0,1 km
Comm object 14608 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Radius for circle area 2. When the gen-set leaves this area, Fence 2 Protection (page 328) is activated after
Fence 2 Delay (page 326).
Note: The center of this circle area is defined by "Home" position - setpoints Home Longitude (page 324)
and Home Latitude (page 324).
Fence 1 Delay
Setpoint group Geo-Fencing Related FW 1.7.0
Range [units] 0..3600 [s]
Default value 0s Alternative config NO
Step 1s
Comm object 11682 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Delay for Fence 1 Protection (page 327).
Geo-Fencing
Setpoint group Geo-Fencing Related FW 1.7.0
Range [units] Disabled / Enabled / LBI Enable [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 11681 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables geo-fencing function.
Disabled Fence 1 Protection (page 327) and Fence 2 Protection (page 328) are disabled.
Enabled Fence 1 Protection (page 327) and Fence 2 Protection (page 328) are enabled.
Fence 1 Protection (page 327) and Fence 2 Protection (page 328) are enabled only when
LBI Enable
logical binary input .GEO-FENCING ENABLED (PAGE 535) is active.
Protection types
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence Radius 1 (page 325).
Wrn Position of gen-set is used for warning protection only. Protection is activated when
position of the gen-set is out of Fence Radius 1 (page 325).
Sd Position of gen-set is used for shutdown protection. Protection is activated when
position of the gen-set is out of Fence Radius 1 (page 325).
BOC Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection
is activated when position of the gen-set is out of Fence Radius 1 (page 325).
Note: Protection is activated also when GPS signal is lost for Fence 1 Delay (page 325).
Protection types
HistRecOnl Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of Fence Radius 2 (page 325).
Wrn Position of gen-set is used for warning protection only. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 325).
Sd Position of gen-set is used for shutdown protection. Protection is activated when
position of the gen-set is out of Fence Radius 2 (page 325).
BOC Position of gen-set is used for BOC (Breaker Open and Cooling) protection. Protection
is activated when position of the gen-set is out of Fence Radius 2 (page 325).
Note: Protection is activated also when GPS signal is lost for Fence 2 Delay (page 326).
CU AIN1 Calibration
Setpoint group CU AIN Calibration Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by analog sensor curve
Comm object 8431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 1.
CU AIN2 Calibration
Setpoint group CU AIN Calibration Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by analog sensor curve
Comm object 8407 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 2.
CU AIN3 Calibration
Setpoint group CU AIN Calibration Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by analog sensor curve
Comm object 8467 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 3.
CU AIN4 Calibration
Setpoint group CU AIN Calibration Related FW 1.7.0
Range [units] the range is defined by analog sensor curve
0 (number of decimal is
Default value Alternative config NO
given by sensor curve)
Step the step is defined by analog sensor curve
Comm object 8793 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via InteliConfig in configuration of analog input 4.
Connection Type 1
Setpoint group Basic settings Related FW 1.7.0
Range [units] Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12058 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
Split Phase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when any other alternate configuration is not active.
Nominal Frequency 1
Setpoint group Basic settings Related FW 1.7.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9913 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when any other alternate configuration is not active.
Nominal RPM 1
Setpoint group Basic settings Related FW 1.7.0
Range [units] 100 .. 4000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9915 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when any other alternate configuration is not active.
Note: This value is used when any other alternate configuration is not active.
Note: This value is used when any other alternate configuration is not active.
Connection type 2
Setpoint group Basic settings Related FW 1.7.0
Range [units] Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12059 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
Split Phase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 503) is active.
Nominal Frequency 2
Setpoint group Basic settings Related FW 1.7.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9914 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 503) is active.
Nominal RPM 2
Setpoint group Basic settings Related FW 1.7.0
Range [units] 100 .. 4000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9916 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 503) is active.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 503) is active.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 503) is active.
Connection type 3
Setpoint group Basic settings Related FW 1.7.0
Range [units] Monophase / Splitphase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12060 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
3PH3Wire or 3Ph4Wire
L1 >=100V
L2 >=100V
or
L3 >=100V
Split Phase
L1 >=100V
L2 <= 20V
or
L3 >=100V
Mono Phase
L1 >=100V
L2 <= 20V
or
L3 <= 20V
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 503) is active.
Nominal Frequency 3
Setpoint group Basic settings Related FW 1.7.0
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 15197 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 503) is active.
Nominal RPM 3
Setpoint group Basic settings Related FW 1.7.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 15196 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 503) is active.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 503) is active.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 503) is active.
Group: CM-RS232-485
COM1 Mode
Setpoint group CM-RS232-485 Related FW 1.7.0
Range [units] Direct / MODBUS / DualSlave / Dual Master [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24522 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM1 channel.
Group: CM-GPRS
Internet Connection
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] Email+SMS / SMS Only [-]
Default value Email+SMS Alternative config NO
Step [-]
Comm object 24315 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint adjust the communication mode of module.
Controller is connected to the Internet and is able to send e-mails as well as SMS. The controller
Enabled is also accessible via AirGate. Internet-enabled SIM card must be used. Also APN Name (page
362) has to be adjusted.
Disabled Only SMS are sent. Internet-enabled SIM card is not required.
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
Email Address 1
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24298 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 3
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24145 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Message Language
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] [-]
Default value English Alternative config NO
Step [-]
Comm object 24299 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this setpoint to set the language of SMS and e-mail.
Note: Numbers correspond with languages in language list. See the chapter for Language selection
(page 81) more information.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Event Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10926 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Event Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
BOC Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10566 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables BOC Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Sd Messages
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 8484 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Sd Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Telephone Number 2
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24295 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
Telephone Number 4
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24142 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
AirGate Connection
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] DISABLED / ENABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24273 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361)
Description
This setpoint enable or disable AirGate connection via CM-GPRS or via CM-4G-GPS.
DISABLED: Only SMS are sent. Internet-enabled SIM card is not required. AirGate is not used.
ENABLED This mode uses the “AirGate” service. Internet-enabled SIM card must be used. The
AirGate server address is adjusted by the setpoint AirGate Address (page 386).
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Controller is connected to the Internet and is able to send e-mails as well as SMS. The controller
Enabled is also accessible via AirGate. Internet-enabled SIM card must be used. Also APN Name (page
362) has to be adjusted.
Disabled Only SMS are sent. Internet-enabled SIM card is not required.
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
Email Address 1
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24298 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 3
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24145 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Message Language
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] [-]
Default value English Alternative config NO
Step [-]
Comm object 24299 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this setpoint to set the language of SMS and e-mail.
Note: Numbers correspond with languages in language list. See the chapter for Language selection
(page 81) more information.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Event Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10926 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Event Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
BOC Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10566 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables BOC Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Sd Messages
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 8484 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Sd Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Telephone Number 2
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24295 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
Telephone Number 4
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS
Range [units] 0..31 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24142 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enter in this setpoint either a valid GSM phone number where the alarm messages shall be sent. For GSM
numbers use either the national format (i.e. the number you would dial if you wanted to make a local call) or
the full international format beginning with a “+” character followed by the country prefix.
IMPORTANT: Telephone number has to be entered without spaces.
DISABLED: Only SMS are sent. Internet-enabled SIM card is not required. AirGate is not used.
ENABLED This mode uses the “AirGate” service. Internet-enabled SIM card must be used. The
AirGate server address is adjusted by the setpoint AirGate Address (page 386).
IMPORTANT: When this setpoint is changed the controller has to be restarted to apply
changes.
AirGate Address
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] [-]
Default value airgate.comap.cz Alternative config NO
Step [-]
Comm object 24364 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS module)
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free AirGate
server provided by ComAp at airgate.comap.cz.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Group: CM-Ethernet
Email Address 1
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24298 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 3
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24145 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint Internet Connection
Setpoint visibility
(page 361) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Message Language
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] [-]
Default value English Alternative config NO
Step [-]
Comm object 24299 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Use this setpoint to set the language of SMS and e-mail.
Note: Numbers correspond with languages in language list. See the chapter for Language selection
(page 81) more information.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Event Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10926 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Event Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
BOC Message
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 10566 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables BOC Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Sd Messages
CM-GPRS; CM-4G-
Setpoint group Related FW 1.7.0
GPS; CM-Ethernet
Range [units] ON / OFF [-]
Default value ON Alternative config NO
Step [-]
Comm object 8484 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint enables or disables Sd Messages.
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
DISABLED: The Ethernet connection is fixed by means of the setpoints IP Addr, NetMask, GateIP,
DNS IP Address.
This method should be used for a classic Ethernet or internet connection. When this type
of connection opens, the controller is specified by its IP address. This means that it
would be inconvenient if the IP address were not fixed (static).
ENABLED: The Ethernet connection setting is obtained automatically from the DHCP server. The
obtained settings are then copied to the related setpoints. If the process of obtaining the
settings from the DHCP server is not successful, the value 000.000.000.000 is copied to
the setpoint IP address and the module continues to try to obtain the settings.
IP Address
Setpoint group CM-Ethernet Related FW 1.7.0
Range [units] Valid IP address [-]
Default value 192.168.1.254 Alternative config NO
Step [-]
Comm object 24376 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint IP Address Mode (page
Setpoint visibility
380)
Description
The setpoint is used to select the method how the IP Address is adjusted.
If IP Address Mode (page 380) is FIXED this setpoint is used to adjust the IP address of the ethernet interface
of the controller. Ask your IT specialist for help with this setting.
If IP Address Mode (page 380) is AUTOMATIC this setpoint is inactive. The IP address is assigned by the
DHCP server.
Gateway IP
Setpoint group CM-Ethernet Related FW 1.7.0
Range [units] Valid IP address [-]
Default value 192.168.1.1 Alternative config NO
Step [-]
Comm object 24373 Related applications AMF, MRS
Config level Standard
Only if relevant module is installed + conditioned by the setpoint IP Address Mode (page
Setpoint visibility
380)
Description
The setpoint is used to select the method how the Gateway IP is adjusted.
If IP Address Mode (page 380) is DISABLE this setpoint is used to adjust the IP address of the gateway of
the network segment where the controller is connected.
If IP Address Mode (page 380) is ENABLED this setpoint is used to display the gateway IP address which
has been assigned by the DHCP server.
A gateway is a device which connects the respective segment with the other segments and/or Internet.
DNS IP Address 2
Setpoint group CM-Ethernet Related FW 1.7.0
Range [units] Valid IP address [-]
Default value 8.8.8.8 Alternative config NO
Step [-]
Comm object 24331 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
The setpoint is used to select the method how the DNS Address 2 is adjusted.
If IP Address Mode (page 380) is FIXED this setpoint is used to adjust the domain name server (DNS), which
is needed to translate domain names in email addresses and server names into correct IP addresses.
If IP Address Mode (page 380) is AUTOMATIC this setpoint is inactive. The DNS server IP address is
assigned by the DHCP server.
SNMP Agent
Setpoint group CM-Ethernet Related FW 1.7.0
Range [units] DISABLED / ENABLED [-]
Default value DISABLED Alternative config NO
Step [-]
Comm object 24336 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Enable or disable SNMP v1 Agent.
AirGate Connection
Setpoint group CM-Ethernet Related FW 1.7.0
Range [units] DISABLED / ENABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24365 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint selects the Ethernet connection mode.
DISABLED: This is a standard mode in which the controller listens to the incoming traffic and answers
the TCP/IP queries addressed to it. This mode requires the controller to be accessible
from the remote device (PC), i.e. it must be accessible at a public and static IP address if
you want to connect to it from the internet.
ENABLED This mode enables the AirGate service. The AirGate server address is adjusted by the
setpoint AirGate Address (page 386). Also the standard TCP/IP is enabled.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Earth Fault Sd
Setpoint group EM-BIO8-EFCP Related FW 1.7.0
Range [units] 0,03 .. 5,00 [A]
Default value 0,30 A Alternative config NO
Step 0,01 [A]
Comm object 11632 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Limit value for Earth Fault Current protection.
Invalid flag
If valid data is not available for a particular value, the invalid flag is set to it. This situation may be due to the
following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in InteliConfig and on the controller screen. If such a
value is read out via MODBUS, it will contain the data 32768 in the case of signed values and 65535 in the case
of unsigned values.
For full list of setpoints go to the chapter List of values (page 454).
Generator Voltage L1-L2 461 Mains Frequency 468 Total Fuel Consumption 477
ECU-BIN 1
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10153 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 3
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10155 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 4
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10156 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 5
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10157 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 7
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10159 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 8
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10160 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU-BIN 9
Value group Engine Related FW 1.7.0
Units Depends on ECU value
Comm object 10161 Related applications AMF, MRS
Description
This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.
Note: Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake temperature
[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.
ECU State
Value group Engine Related FW 1.7.0
Units -
Comm object 10034 Related applications AMF, MRS
Description
Shows binary status (0 or 1) of ECU:
ECU Yellow Lamp
ECU Red Lamp
Wait To Start
Speed Request
Value group Engine Related FW 1.7.0
Units %
Comm object 10137 Related applications AMF, MRS
Description
Engine speed control via CAN bus.
Group: Generator
Generator Frequency
Value group Generator Related FW 1.7.0
Units Hz
Comm object 8210 Related applications AMF, MRS
Description
Frequency of generator.
Nominal Current
Value group Generator Related FW 1.7.0
Units A
Comm object 9978 Related applications AMF, MRS
Description
Generator nominal current.
Nominal Power
Value group Generator Related FW 1.7.0
Units V
Comm object 9018 Related applications AMF, MRS
Description
Generator nominal power.
Nominal Voltage
Value group Generator Related FW 1.7.0
Units V
Comm object 9917 Related applications AMF, MRS
Description
Generator nominal voltage.
Load A L2
Value group Load Related FW 1.7.0
Units A
Comm object 8199 Related applications AMF, MRS
Description
Load current phase L2.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load A L3
Value group Load Related FW 1.7.0
Units A
Comm object 8200 Related applications AMF, MRS
Description
Load current phase L3.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load Characteristic
Value group Load Related FW 1.7.0
Units [-]
Comm object 8395 Related applications AMF, MRS
Description
Character of the load. “L” means inductive load, “C” is capacitive and “R” is resistive load (power factor = 1).
Load Characteristic L2
Value group Load Related FW 1.7.0
Units [-]
Comm object 8627 Related applications AMF, MRS
Description
Character of the generator load in the L2 phase. “L” means inductive load, “C” is capacitive and “R” is
resistive load (power factor = 1).
Load Characteristic L3
Value group Load Related FW 1.7.0
Units [-]
Comm object 8628 Related applications AMF, MRS
Description
Character of the generator load in the L3 phase. “L” means inductive load, “C” is capacitive and “R” is
resistive load (power factor = 1).
Load kVA
Value group Load Related FW 1.7.0
Units kVA
Comm object 8565 Related applications AMF, MRS
Description
Load apparent power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kVA L2
Value group Load Related FW 1.7.0
Units kVA
Comm object 8531 Related applications AMF, MRS
Description
Load apparent power L2.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kVA L3
Value group Load Related FW 1.7.0
Units kVA
Comm object 8532 Related applications AMF, MRS
Description
Load apparent power L3.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kVAr
Value group Load Related FW 1.7.0
Units kVAr
Comm object 8203 Related applications AMF, MRS
Description
Load reactive power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kVAr L2
Value group Load Related FW 1.7.0
Units kVAr
Comm object 8528 Related applications AMF, MRS
Description
Load reactive power in phase L2.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kVAr L3
Value group Load Related FW 1.7.0
Units kVAr
Comm object 8529 Related applications AMF, MRS
Description
Load reactive power in phase L3.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kW
Value group Load Related FW 1.7.0
Units kW
Comm object 8202 Related applications AMF, MRS
Description
Load active power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kW L2
Value group Load Related FW 1.7.0
Units kW
Comm object 8525 Related applications AMF, MRS
Description
Load active power in phase L2.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Load kW L3
Value group Load Related FW 1.7.0
Units kW
Comm object 8526 Related applications AMF, MRS
Description
Load active power in phase L3.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Group: Mains
Mains Frequency
Value group Mains Related FW 1.7.0
Units Hz
Comm object 8211 Related applications AMF
Description
Frequency of mains.
Analog Input 3
Value group Controler I/O Related FW 1.7.0
Units Configurable
Comm object 9153 Related applications AMF, MRS
Description
This is the value of the analog input 3 of the controller.
Analog Input 4
Value group Controler I/O Related FW 1.7.0
Units Configurable
Comm object 9154 Related applications AMF, MRS
Description
This is the value of the analog input 4 of the controller.
Battery Volts
Value group Controler I/O Related FW 1.7.0
Units V
Comm object 8213 Related applications AMF, MRS
Description
Controller supply voltage.
Binary Inputs
Value group Controler I/O Related FW 1.7.0
Units [-]
Comm object 8235 Related applications AMF, MRS
Description
State of the binary inputs of the controller.
D+
Value group Controler I/O Related FW 1.7.0
Units V
Comm object 10603 Related applications AMF, MRS
Description
D+ terminal voltage.
Group: Statistics
Genset kVArh
Value group Statistics Related FW 1.7.0
Units kVArh
Comm object 8539 Related applications AMF, MRS
Description
Counter of gen-set reactive power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Genset kWh
Value group Statistics Related FW 1.7.0
Units kWh
Comm object 8205 Related applications AMF, MRS
Description
Counter of gen-set active power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Mains kWh
Value group Statistics Related FW 1.7.0
Units kWh
Comm object 11025 Related applications AMF
Description
Counter of mains active power.
Note: This value can be also switch into one decimal power format (via InteliConfig PC tool). In this
case the range of value is decrease 10 times.
Maintenance 1
Value group Statistics Related FW 1.7.0
Units hours
Comm object 11616 Related applications AMF, MRS
Description
Countdown until next maintenance 1. Initial value can be set in Maintenance Timer 1 (page 213).
Maintenance 2
Value group Statistics Related FW 1.7.0
Units hours
Comm object 11617 Related applications AMF, MRS
Description
Countdown until next maintenance 2. Initial value can be set in Maintenance Timer 2 (page 214).
Num E-Stops
Value group Statistics Related FW 1.7.0
Units [-]
Comm object 11195 Related applications AMF, MRS
Description
Emergency stop alarms counter.
Num Starts
Value group Statistics Related FW 1.7.0
Units [-]
Comm object 8207 Related applications AMF, MRS
Description
Engine start commands counter. The counter is increased by 1 even if the particular start command will take
more than one attempt.
Pulse Counter 1
Value group Statistics Related FW 1.7.0
Units -
Comm object 10986 Related applications AMF, MRS
Description
This is the value of PULSE COUNTER 1 (PAGE 540) function.
Pulse Counter 2
Value group Statistics Related FW 1.7.0
Units -
Comm object 10987 Related applications AMF, MRS
Description
This is the value of PULSE COUNTER 2 (PAGE 540) function.
Rental 2
Value group Statistics Related FW 1.7.0
Units days
Comm object 14369 Related applications AMF, MRS
Description
Remaining hours of Rental Timer 2 (page 321).
Running Hours
Value group Statistics Related FW 1.7.0
Units hours
Comm object 8206 Related applications AMF, MRS
Description
Engine operation hours counter. The engine hours are incremented in the controller while the engine is
running.
Shutdowns
Value group Statistics Related FW 1.7.0
Units [-]
Comm object 11196 Related applications AMF, MRS
Description
Shutdown alarms counter. This counter counts all occurrences of a shutdown alarm, not only real shutdowns
of the gen-set, i.e. the counter is increased by 2 if two shutdown alarms appear simultaneously.
Group: IL InfoInfo
Application
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 8480 Related applications AMF, MRS
Description
The value contains actual application in controller.
Breaker State
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 9245 Related applications AMF, MRS
Description
The value contains actual “breaker state” message which is shown on the main screen of the controller.
Connection Type
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 12944 Related applications AMF, MRS
Description
The text of this value represents the connection type which is adjusted in setpoint Connection type (page
171).
FW Branch
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 8707 Related applications AMF, MRS
Description
The value contains actual branch of firmware in controller.
FW Version
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 24339 Related applications AMF, MRS
Description
Major and minor firmware version number.
ID String
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 24501 Related applications AMF, MRS
Description
Name of controller which is used in InteliConfig in command bar.
Password Decode
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 24202 Related applications AMF, MRS
Description
This value contains a number which can be used for retrieving a lost password. Send this number together
with the controller serial number to your distributor if you have lost your password.
SPI Module B
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 14448 Related applications AMF, MRS
Description
The name of plug-in module which is inserted in slot B.
Timer Text
Value group IL Info Related FW 1.7.0
Units [-]
Comm object 10040 Related applications AMF, MRS
Description
The value contains the numeric code of the “Current process timer” text which is shown on the main screen
of the controller.
The assignment of texts to the codes can be obtained using InteliConfig. Open any connection (also offline
with a previously saved archive) and go to the Tools ribbon -> Generate CFG image (all). The resulting file
will contain the assignment of texts to the codes.
Timer Value
Value group IL Info Related FW 1.7.0
Units [HH:MM:SS]
Comm object 14147 Related applications AMF, MRS
Description
The value contains the "Current process timer" value which is shown on the main screen of the controller.
Log Bout 2
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9144 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 3
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9145 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 4
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9146 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 5
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9147 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 7
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9149 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 8
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 9150 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 9
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 11896 Related applications AMF, MRS
Description
State of binary outputs.
Log Bout 10
Value group Log Bout Related FW 1.7.0
Units [-]
Comm object 11897 Related applications
Description
State of binary outputs.
Code Description
0 SIM card is not inserted
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
AirGate ID
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units [-]
Comm object 24309 Related applications AMF, MRS
Description
Identification string generated by AirGate server for the purpose of establishing communication via
InteliConfig or any other supported PC tool.
Connection Type
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units [-]
Comm object 24146 Related applications AMF, MRS
Description
The type of data connection.
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
4 Module – error in initialization
5 Module – not possible to set the APN
6 Module – not possible to connect to GPRS network
7 Module – not possible to retrieve IP address
8 Module – not accepted DNS IP address
9 Error in modem detection
10 Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or
11
unknown status of SIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
GSM modem did not accepted particular initialization command, possibly caused by
14
locked SIM card
15 Unknown modem
16 Bad answer to complement initialization string
17 Not possible to read GSM signal strength
18 CDMA modem not detected
19 No CDMA network
20 Unsuccessful registration to CDMA network
21 SIMCom/ME909s: can´t read FW version
22 SIMCom: GSM signal not found
23 SIMCom: can´t detect module speed
24 SIMCom: HW reset issued
25 PUK is required
26 Error of SIM card detected
27 ME909s: can't set module bps
28 ME909s: can't set link configuration
29 ME909s: can't do power-off
30 ME909s: can't do power-on
Cell ErrorRate
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units %
Comm object 24300 Related applications AMF, MRS
Description
This value contains information about relative quality of the cellular signal received by the CM-GPRS module
or by CM-4G-GPS module. The lower value means higher quality of signal.
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum length of data can’t be read.
5 No appeal to send command.
6 Command can’t be send.
7 Command can’t be send.
8 HELO command was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server refused the data of email.
19 SMTP server refused the data of email.
20 QUIT command was refused.
21 Lost of connection.
23 Error during closing the connection.
24 No answer from server.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
28 Error of encoding.
29 There was no attempt to send email.
Group: CM-4G-GPS
Altitude
CM-4G-GPS (GPS
Value group Related FW 1.7.0
part)
Units m
Comm object 24266 Related applications AMF, MRS
Description
Actual GPS altitude.
HomePosDist
CM-4G-GPS (GPS
Value group Related FW 1.7.0
part)
Units km
Comm object 11680 Related applications AMF, MRS
Description
Actual distance from home position. Home position is adjusted via setpoints Home Latitude (page 324) and
Home Longitude (page 324) or by binary input GEO HOME POSITION (PAGE 534).
Latitude
CM-4G-GPS (GPS
Value group Related FW 1.7.0
part)
Units [-]
Comm object 24268 Related applications AMF, MRS
Description
Actual GPS latitude. Positions on north hemisphere have positive value, position on south hemisphere have
negative value.
Satellites
CM-4G-GPS (GPS
Value group Related FW 1.7.0
part)
Units [-]
Comm object 24265 Related applications AMF, MRS
Description
Number of available satellites for GPS location.
AirGate ID
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units [-]
Comm object 24309 Related applications AMF, MRS
Description
Identification string generated by AirGate server for the purpose of establishing communication via
InteliConfig or any other supported PC tool.
Code Description
0 SIM card is not inserted
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
Connection Type
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units [-]
Comm object 24146 Related applications AMF, MRS
Description
The type of data connection.
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
Cell ErrorRate
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units %
Comm object 24300 Related applications AMF, MRS
Description
This value contains information about relative quality of the cellular signal received by the CM-GPRS module
or by CM-4G-GPS module. The lower value means higher quality of signal.
Cell Status
CM-GPRS; CM-4G-
Value group Related FW 1.7.0
GPS (4G part)
Units [-]
Comm object 24290 Related applications AMF, MRS
Description
The text of this value represents the status of the GSM modem.
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
4 Maximum length of data can’t be read.
5 No appeal to send command.
6 Command can’t be send.
7 Command can’t be send.
8 HELO command was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
18 SMTP server refused the data of email.
19 SMTP server refused the data of email.
20 QUIT command was refused.
21 Lost of connection.
23 Error during closing the connection.
24 No answer from server.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
28 Error of encoding.
29 There was no attempt to send email.
Group: CM-Ethernet
AirGate Status
Value group CM-Ethernet Related FW 1.7.0
Units [-]
Comm object 24344 Related applications AMF, MRS
Description
Diagnostic code for AirGate connection. Helps in troubleshooting.
Code Description
0 Ethernet cable is disconected
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
AirGate ID
Value group CM-EthernetInfo Related FW 1.7.0
Units [-]
Comm object 24345 Related applications AMF, MRS
Description
Identification string generated by AirGate server for the purpose of establishing communication via
InteliConfig or any other supported PC tool.
Current Gateway
Value group CM-Ethernet Related FW 1.7.0
Units [-]
Comm object 24182 Related applications AMF, MRS
Description
Current gateway address.
Current IP Address
Value group CM-Ethernet Related FW 1.7.0
Units [-]
Comm object 24184 Related applications AMF, MRS
Description
Current IP address of the controller.
Code Description
0 Email was successfully sent.
2 It is not possible to establish connection with SMTP server.
3 SMTP server is not ready for communication.
8 HELO command was refused.
9 EHLO commnad was refused.
11 AUTH LOGIN command was refused.
12 Wrong user name.
13 Wrong password.
14 MAIL FROM command was refused.
15 RCPT TO command was refused.
16 DATA command was refused.
17 Sending of email failed.
20 QUIT command was refused.
25 It is impossible to create data for command DATA.
26 It is impossible to read data for command DATA.
27 Email address can’t be read.
30 SMTP server address translation error (from DNS server).
31 Error reading email content data (24327).
MAC Address
Value group CM-Ethernet Related FW 1.7.0
Units [-]
Comm object 24333 Related applications AMF, MRS
Description
Current MAC address of the controller ethernet interface.
Group: Date/Time
Time
Value group Date/Time Related FW 1.7.0
Units HH:MM:SS
Comm object 24554 Related applications AMF, MRS
Description
Shows setup time.
Date
Value group Date/Time Related FW 1.7.0
Units DD.MM.YYYY
Comm object 24553 Related applications AMF, MRS
Description
Shows setup date.
Group: PLC
PLC Resource 1
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10504 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 2
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10505 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 3
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10506 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 4
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10507 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 6
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10509 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 7
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10510 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC Resource 8
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10511 Related applications AMF, MRS
Description
Internal state of PLC countdowns (e.g. state of block Timer etc.).
PLC-BOUT 1
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10424 Related applications AMF, MRS
Description
State of binary outputs of PLC.
PLC-BOUT 3
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10426 Related applications AMF, MRS
Description
State of binary outputs of PLC.
PLC-BOUT 4
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10427 Related applications AMF, MRS
Description
State of binary outputs of PLC.
PLC-BOUT 5
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10428 Related applications AMF, MRS
Description
State of binary outputs of PLC.
PLC-BOUT 6
Value group PLC Related FW 1.7.0
Units [-]
Comm object 10429 Related applications AMF, MRS
Description
State of binary outputs of PLC.
For full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically (page 502).
Alternate Config 2
Related FW 1.7.0 Related applications AMF, MRS
Comm object 859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
Alternate Config 3
Related FW 1.7.0 Related applications AMF, MRS
Comm object 860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
AMF Function
Related FW 1.7.0 Related applications AMF
Comm object 692
Description
This binary input can switch controller function between AMF and MRS.
Note: Binary input “AMF function” has higher priority than the setpoint Operation Mode (page 177) in
Basic settings.
LBI: B
Battery Charger
Related FW 1.7.0 Related applications AMF, MRS
Comm object 623
Description
When binary input is active and his delay Battery Charger Fail Delay (page 215) is out of time than alarm
Battery Charger Fail (page 656) is activated, written into history log and logical binary output AL BATTERY
CHARGER (PAGE 550) is activated.
BIN Protection 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9999
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 03
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9997
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 05
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9995
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 07
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9993
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 09
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9991
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 11
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9989
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 13
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9987
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 15
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9985
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 17
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9983
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 19
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9981
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 21
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9979
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 23
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9977
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 25
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9975
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 27
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9973
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 29
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9971
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 31
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9969
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 33
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9967
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 35
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9965
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 37
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9963
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 39
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9961
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 41
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9959
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 43
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9957
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 45
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9955
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
BIN Protection 47
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9953
Description
This binary input is for general input function used as alarm.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
AL Indic Binary input is not used for protection. Only alarmlist record is made if binary input
is active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
LBI: C
Choke Inhibit
Related FW 1.7.0 Related applications AMF, MRS
Comm object 946
Description
Logical binary input CHOKE INHIBIT prevent Choke functionality when logical binary output CHOKE (PAGE
574) is activated. If CHOKE INHIBIT is activated when CHOKE LBO is active, CHOKE LBO is deactivated
immediately and vice versa if LBI CHOKE INHIBIT is deactivated and LBO CHOKE should be active then is
activated.
Coolant Temp
Related FW 1.7.0 Related applications AMF, MRS
Comm object 625
Description
Binary input for COOLANT TEMP (PAGE 634) protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
Note: After deactivation of dark mode, Front Face status LEDs are turned on due to current situation of
gen-set.
LBI: E
ECU Speed Down
Related FW 1.7.0 Related applications AMF, MRS
Comm object 164
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 219) by binary inputs. When the LBI
is activated the setpoint is decreased by 2%.
ECU Speed Up
Related FW 1.7.0 Related applications AMF, MRS
Comm object 165
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 219) by binary inputs. When the LBI
is activated the setpoint is increase by 2%.
Emergency Stop
Related FW 1.7.0 Related applications AMF, MRS
Comm object 40
Description
The shutdown procedure will start immediately when this input is activated. Input is inverted (NC = normaly
closed) in default configuration.
Note: In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
LBI: F
Fault Reset Button
Related FW 1.7.0 Related applications AMF, MRS
Comm object 191
Description
Binary input has the same function as Fault Reset button on the InteliLite front panel.
Force Regeneration
Related FW 1.7.0 Related applications AMF, MRS
Comm object 680
Description
When this binary input is activated, the controller send request for force regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Fuel Level
Related FW 1.7.0 Related applications AMF, MRS
Comm object 626
Description
Binary input for FUEL LEVEL (PAGE 635) protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
BOC Binary input is used for BOC (Breaker Open and Cooling) protection.
Sd Binary input is used for shutdown protection.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 533) is configured then binary
output FUEL PUMP (PAGE 579) is control by this binary input. Setpoints Fuel Pump On (page 211)
and Fuel Pump Off (page 212) are not evaluated!
LBI: G
GCB Button
Related FW 1.7.0 Related applications AMF, MRS
Comm object 193
Description
Binary input has the same function as GCB button on the InteliLite front panel. It is evaluated in MAN
mode only.
Note: InteliLite controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
LBI: H
Horn Reset Button
Related FW 1.7.0 Related applications AMF, MRS
Comm object 192
Description
Binary input has the same function as Horn reset button on the InteliLite front panel.
LBI: I
Idle Speed
Related FW 1.7.0 Related applications AMF, MRS
Comm object 624
Description
This binary input changes cooling speed from nominal to idle.
Lang Selection 2
Related FW 1.7.0 Related applications AMF, MRS
Comm object 108
Description
Use this binary input with binary input LANG SELECTION 1 (PAGE 536) and LANG SELECTION 3 (PAGE 537) to
choose required language of controller. The system is based on binary numbers.
LBI: M
Mains Fail Block
Related FW 1.7.0 Related applications AMF
Comm object 622
Description
If the input is closed, the automatic start of the gen-set at Mains failure is blocked. In case of running gen-set
in AUTO mode, timer Mains Return Delay (page 233) is started and when it elapses GCB is opened, gen-set
goes to cooling procedure and stops. When GCB is opened after Transfer Delay (page 234) the MCB is
closed.
Note: This input simulates healthy Mains.
MCB Button
Related FW 1.7.0 Related applications AMF
Comm object 194
Description
This binary input has the same function as MCB button on the InteliLite front panel. It is evaluated in
MAN mode only.
Note: InteliLite controller can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
LBI: O
Oil Pressure
Related FW 1.7.0 Related applications AMF, MRS
Comm object 43
Description
Binary input for OIL PRESSURE (PAGE 637) protection.
Protection types
Monitoring Binary input is not used for protection or any other function. Signal is only
monitored.
HistRecOnl Binary input is not used for protection. Only history record is made if binary input is
active.
Wrn Binary input is used for warning protection only.
Sd Binary input is used for shutdown protection.
IMPORTANT: This binary input is also used for evaluating engine running condition.
Example: Normally close connection - when LBI is closed then oil pressure is OK and is higher than
starting oil pressure.
Note: In case that you want to use binary input of oil pressure sensor just for protection please use one
of the BIN PROTECTION 1 (PAGE 504).
LBI: P
Protection Enable
Related FW 1.7.0 Related applications AMF, MRS
Comm object 920
Description
This logic binary input enables or disables protections adjusted as LBI Enable.
Pulse Counter 2
Related FW 1.7.0 Related applications AMF, MRS
Comm object 88
Description
This is the input of the Pulse Counter 2 function. The module counts pulses at the input and if the input
pulses counter reaches value given by the setpoint Conversion Coefficient Pulse 2 (page 216) the counter
value Pulse Counter 2 (page 474) is increased by 0,1 and input pulses counter is reset to 0. Both counter
value and input pulses counter are stored in the nonvolatile memory.
LBI: R
Regeneration Inhib
Related FW 1.7.0 Related applications AMF, MRS
Comm object 679
Description
When this binary input is activated, the controller sends request to inhibit regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Remote Ctrl Lock
Related FW 1.7.0 Related applications AMF, MRS
Comm object 4
Description
If the input is active, the controller will not accept any actions regarding the system control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote MAN
Related FW 1.7.0 Related applications AMF, MRS
Comm object 618
Description
The controller is switched to the MAN mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote Start/Stop
Related FW 1.7.0 Related applications AMF, MRS
Comm object 38
Description
Use this input to start and stop the gen-set in AUTO mode.
Note: If the binary input Remote Start/Stop is active and engine is running and mains failure occurs, the
MCB breaker opens, after Transfer Delay (page 234) the GCB breaker is closed. Once the mains is OK,
the Mains Return Delay (page 233) elapses and the GCB breaker is opened. Then after Transfer Delay
(page 234) is MCB breaker closed. Gen-set remains running as long as binary input Rem Start/Stop is
active. For more details see timing diagram below.
Remote TEST
Related FW 1.7.0 Related applications AMF
Comm object 621
Description
The controller is switched to the TEST mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
LBI: S
Sd Override
Related FW 1.7.0 Related applications AMF, MRS
Comm object 44
Description
If this input is active, all alarms except Emergency Stop and Overspeed are suppressed. The suppressed
alarms will be displayed in the alarm list, but they will not take effect regarding the gen-set control.
Note: Sd Override (page 543) is indicated in the alarm list if Sd Override mode is active to inform the
operator that the engine is not protected.
Start Button
Related FW 1.7.0 Related applications AMF, MRS
Comm object 189
Description
Binary input has the same function as Start Button on the InteliLite front panel. It is evaluated in MAN
mode only.
Binary input has the same function as Stop Button on the InteliLite front panel. It is evaluated in MAN
Mode only.
For full list of Logical binary outputs go to the chapter Logical binary outputs alphabetically (page 546).
AL AIN 1 Sd+BOC
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1386
Description
The output is closed when there is the shutdown or BOC alarm from the analog input 1 of the controller
present in the alarmlist or isn’t confirmed.
AL AIN 1 Wrn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1382
Description
The output is closed when there is the warning alarm from the analog input 1 of the controller present in the
alarmlist or isn’t confirmed.
AL AIN 2 Wrn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1383
Description
The output is closed when there is the warning alarm from the analog input 2 of the controller present in the
alarmlist or isn’t confirmed.
AL AIN 3 Sd+BOC
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1388
Description
The output is closed when there is the shutdown or BOC alarm from the analog input 3 of the controller
present in the alarmlist or isn’t confirmed.
AL AIN 3 Wrn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1384
Description
The output is closed when there is the warning alarm from the analog input 3 of the controller present in the
alarmlist or isn’t confirmed.
AL AIN 4 Sd+BOC
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1389
Description
The output is closed when there is the shutdown or BOC alarm from the analog input 4 of the controller
present in the alarmlist or isn’t confirmed.
AL Battery Flat
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1292
Description
This output is active when the Sd Battery Flat (page 679) or Wrn Battery < Voltage (page 659) alarm is
present in the alarmlist or isn’t confirm.
AL Battery Charger
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1272
Description
This output is active when the Battery Charger Fail (page 656) alarm is present in the alarmlist or isn’t
confirmed.
AL Battery Overvoltage
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1995
Description
This output is active when the Wrn Battery > Voltage (page 659) alarm is present in the alarmlist or isn’t
confirm.
AL Battery Undervoltage
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1994
Description
This output is active when the Wrn Battery < Voltage (page 659) alarm is present in the alarmlist or isn’t
confirm.
AL Common BOC
Related FW 1.7.0 Related applications AMF, MRS
Comm object 9
Description
Output closes when any BOC alarm appears.
The output opens, if:
No BOC alarm is active and
AL Common Fls
Related FW 1.7.0 Related applications AMF, MRS
Comm object 6
Description
Output closes when any sensor fail alarm appears.
The output opens, if:
No sensor fail alarm is active and
AL Common Sd
Related FW 1.7.0 Related applications AMF, MRS
Comm object 4
Description
Output closes when any shutdown alarm appears.
The output opens, if:
No shutdown alarm is active and
AL CoolantTemp Low
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1295
Description
The output is closed when there is the Wrn Coolant Temperature Low (page 660) alarm from the
COOLANT TEMP (PAGE 634) in the alarmlist or isn’t confirmed.
AL CoolantTemp Sd
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1421
Description
The output is closed when there is the shutdown or BOC alarm from the COOLANT TEMP (PAGE 634) in the
alarmlist or isn’t confirmed.
AL CoolantTemp Wrn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1420
Description
The output is closed when there is the warning alarm from the COOLANT TEMP (PAGE 634) in the alarmlist or
isn’t confirmed.
Note: Binary output is also active if protection type is set to HistRecOnl and threshold level for history
record is reach.
AL Earth Fault
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1294
Description
This output is active when the Sd Earth Fault Current (page 680) alarm is present in alarm list or isn’t
confirm.
Note: It is strongly recommended to use this output only onetime.
AL Fence 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1548
Description
This output is active when the Wrn Fence 1 Alarm (page 660) or BOC Fence 1 Alarm (page 689) or Sd
Fence 1 Alarm (page 681) (depends on configuration of alarm type) alarm is present in the alarmlist or isn’t
confirm.
AL Fuel Level Sd
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1423
Description
The output is closed when there is the shutdown or BOC alarm from the FUEL LEVEL (PAGE 635) in the
alarmlist or isn’t confirmed.
AL Gen Frequency
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1266
Description
This output is active when at least one generator frequency BOC or Sd alarm is present in alarmlist or isn’t
confirm.
AL Gen Overvoltage
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1261
Description
This output is active when at least one generator overvoltage alarm is present in alarmlist or isn’t confirm.
AL Gen Underfrequency
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1265
Description
This output is active when at least one generator underfrequency alarm is present in alarmlist or isn’t
confirm.
AL Gen Undervoltage
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1262
Description
This output is active when at least one generator undervoltage alarm is present in alarmlist or isn’t confirm.
AL Mains Fail
Related FW 1.7.0 Related applications AMF
Comm object 197
Description
Output for signaling Mains Failure. This output is active when at least one mains frequency BOC or Sd alarm
or at least one mains voltage BOC or Sd alarm is present in alarmlist or isn’t confirmed.
AL Mains Frequency
Related FW 1.7.0 Related applications AMF
Comm object 1271
Description
This output is active when at least one mains frequency BOC or Sd alarm is present in alarmlist or isn’t
confirm.
AL Mains Voltage
Related FW 1.7.0 Related applications AMF
Comm object 1270
Description
This output is active when at least one mains voltage BOC or Sd alarm is present in the alarmlist or isn’t
confirm.
AL Maintenance 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1254
Description
This output is active when the Alarm Maintenance 1 is present in the alarmlist. It means that counter of
maintenance is on zero or the Alarm Maintenance 1 isn’t confirm.
AL Maintenance 3
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1256
Description
This output is active when the Alarm Maintenance 3 is present in the alarmlist. It means that counter of
maintenance is on zero or the Alarm Maintenance 3 isn’t confirm.
AL Oil Press Sd
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1419
Description
The output is closed when there is the shutdown alarm from the OIL PRESSURE (PAGE 637) in the alarmlist or
isn’t confirmed.
AL Overcurrent
Related FW 1.7.0 Related applications AMF, MRS
Comm object 109
Description
This output is active when the BOC Overcurrent IDMT (page 693) or BOC Short Circuit (page 694)
alarm is present in alarmlist or isn’t confirm.
AL Overload Wrn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1269
Description
This output is active when the Wrn Overload (page 668) alarm is present in alarmlist or isn’t confirm.
AL Overspeed
Related FW 1.7.0 Related applications AMF, MRS
Comm object 779
Description
This output is active when the Sd Overspeed (page 687) alarm is present in the alarmlist or isn’t confirm.
AL Rental Timer 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1370
Description
The binary output closes when the Rental Timer 1 (page 319) elapsed.
AL Start Fail
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1291
Description
This output is active when the Sd Start Fail (page 688) alarm is present in the alarmlist or isn’t confirm.
AL Stop Fail
Related FW 1.7.0 Related applications AMF, MRS
Comm object 339
Description
This output is active when the Wrn Stop Fail (page 668) alarm is present in the alarmlist or isn’t confirm.
AL Underspeed
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1296
Description
This output is active when the Sd Underspeed (page 688) alarm is present in the alarmlist or isn’t confirm.
AIN Switch01
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1400
Description
This is an output from the General Analog Input 1 switch function. The behavior of the switch depends on the
adjustment of the setpoints Analog Switch 1 On (page 245) and Analog Switch 1 Off (page 246). The value is
measured from AIN SWITCH 01 (PAGE 627) analog input.
AIN Switch03
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1402
Description
This is an output from the General Analog Input 3 switch function. The behavior of the switch depends on the
adjustment of the setpoints Analog Switch 3 On (page 251) and Analog Switch 3 Off (page 252). The value is
measured from AIN SWITCH 03 (PAGE 627) analog input.
AIN Switch05
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1787
Description
This is an output from the General Analog Input 5 switch function. The behavior of the switch depends on the
adjustment of the setpoints Analog Switch 5 On (page 257) and Analog Switch 5 Off (page 258). The value is
measured from AIN SWITCH 05 (PAGE 628) analog input.
AIN Switch07
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1789
Description
This is an output from the General Analog Input 7 switch function. The behavior of the switch depends on the
adjustment of the setpoints Analog Switch 7 On (page 263) and Analog Switch 7 Off (page 264). The value is
measured from AIN SWITCH 07 (PAGE 629) analog input.
AIN Switch09
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1791
Description
This is an output from the General Analog Input 9 switch function. The behavior of the switch depends on the
adjustment of the setpoints Analog Switch 9 On (page 269) and Analog Switch 9 Off (page 270). The value is
measured from AIN SWITCH 09 (PAGE 629) analog input.
AIN Switch11
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1793
Description
This is an output from the General Analog Input 11 switch function. The behavior of the switch depends on
the adjustment of the setpoints Analog Switch 11 On (page 275) and Analog Switch 11 Off (page 276). The
value is measured from AIN SWITCH 11 (PAGE 630) analog input.
AIN Switch13
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1795
Description
This is an output from the General Analog Input 13 switch function. The behavior of the switch depends on
the adjustment of the setpoints Analog Switch 13 On (page 281) and Analog Switch 13 Off (page 282). The
value is measured from AIN SWITCH 13 (PAGE 631) analog input.
AIN Switch15
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1797
Description
This is an output from the General Analog Input 15 switch function. The behavior of the switch depends on
the adjustment of the setpoints Analog Switch 15 On (page 287) and Analog Switch 15 Off (page 288). The
value is measured from AIN SWITCH 15 (PAGE 631) analog input.
AIN Switch17
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1799
Description
This is an output from the General Analog Input 17 switch function. The behavior of the switch depends on
the adjustment of the setpoints Analog Switch 17 On (page 293) and Analog Switch 17 Off (page 294). The
value is measured from AIN SWITCH 17 (PAGE 632) analog input.
AIN Switch19
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1801
Description
This is an output from the General Analog Input 19 switch function. The behavior of the switch depends on
the adjustment of the setpoints Analog Switch 19 On (page 299) and Analog Switch 19 Off (page 300). The
value is measured from AIN SWITCH 19 (PAGE 633) analog input.
LBO: B
BIN 1 Status
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1374
Description
This output is closed, when Binary Input 1 is active and open when Binary Input 1 is inactive. When Binary
Input 1 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 1 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
BIN 3 Status
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1376
Description
This output is closed, when Binary Input 3 is active and open when Binary Input 3 is inactive. When Binary
Input 3 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 3 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
BIN 5 Status
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1378
Description
This output is closed, when Binary Input 5 is active and open when Binary Input 5 is inactive. When Binary
Input 5 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 5 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
BIN 7 Status
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1380
Description
This output is closed, when Binary Input 7 is active and open when Binary Input 7 is inactive. When Binary
Input 7 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note: When LBI 7 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
LBO: C
Choke
Related FW 1.7.0 Related applications AMF, MRS
Comm object 2091
Description
Logical binary output for choke valve control. Output CHOKE is activated every time when logical binary
output STARTER (PAGE 600) is activated. Output is deactivated when one of these conditions is fulfilled:
Choke Time is elapsed
Generator voltage is higher than Choke Voltage
Logical binary input Choke Inhibit is activated
Or when some of these situations during start occurs:
Any second level alarm
Emergency stop
Stop command
Cranking pause
Cooling
Related FW 1.7.0 Related applications AMF, MRS
Comm object 74
Description
The output closes when gen-set is in Cooling state.
LBO: D
Dual Operation Error
Related FW 1.7.0 Related applications AMF, MRS
Comm object 2097
Description
This LBO is active when there is Dual Operation Fail (page 670) alarm in alarmlist.
Dual Operation OK
Related FW 1.7.0 Related applications AMF, MRS
Comm object 2096
Description
This LBO is active when there is not Dual Operation Fail (page 670) alarm in alarmlist.
ECU Communic OK
Related FW 1.7.0 Related applications AMF, MRS
Comm object 347
Description
This output is active when an ECU is configured, connected and the communication with the ECU is
established.
Exercise Timer 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1250
Description
This is an output from the Exercise timer 1. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 1 (page 305) subgroup. This output is
active when Timer 1 is active.
Exercise Timer 2
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1251
Description
This is an output from the Exercise timer 2. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the Subgroup: Timer 2 (page 312) subgroup. This output is
active when Timer 2 is active.
LBO: F
Fault Reset
Related FW 1.7.0 Related applications AMF, MRS
Comm object 592
Description
When the Fault Reset button is pressed the output is active for 1 s.
Fuel Solenoid
Related FW 1.7.0 Related applications AMF, MRS
Comm object 22
Description
This output controls the fuel solenoid valve. The Fuel Solenoid output has two different behaviors depending
on engine type – gas or diesel. This setting is done by Fuel Solenoid (page 183) setpoint in Engine Settings
group.l
Diesel:
The output closes before binary output STARTER (PAGE 600).The lead time is adjusted by setpoint Fuel
Solenoid Lead (page 192).
Gas:
The output closes together with binary output IGNITION (PAGE 588) when engine RPM exceed 30 RPM (fix
value).
LBO: G
GCB Close/Open
Related FW 1.7.0 Related applications AMF, MRS
GCB UV Coil
Related FW 1.7.0 Related applications AMF, MRS
Comm object 44
Description
The output is intended for control of undervoltage coil of generator circuit breaker. The output is active the
Glow Plugs
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will close for exact time pre-set by setpoint Glow
Plugs Time (page 186) before every starting attempt. The output opens in same time as the STARTER (PAGE
600) output closes (100 ms after PRESTART (PAGE 596) output opens).
When the Glow Plugs Time (page 186) is shorter than Cranking Fail Pause (page 184) then the Glow Plugs Time
(page 186) in Cranking Fail Pause (page 184) is long as normal Glow Plugs Time (page 186).
HEST Lamp
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1373
Description
This output is closed if ECU send signal HEST Lamp. If ECU stop send HEST LAMP signal binary input will
be opened without no matter if alarms in alarmlist are confirmed or not.
Horn
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1
Description
The output designed to be used for acoustic indication of a newly appeared alarm. The output is activated
each time a new alarm has appeared and remains active until one of the following events occurs:
Note: Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Ignition
Related FW 1.7.0 Related applications AMF, MRS
Comm object 37
Description
This output is dedicated to controlling the ignition at a gas engine. The output is closed together with binary
output FUEL SOLENOID (PAGE 579) in the moment when the timer Sd Ventilation Time (page 196) elapsed and
the gen-set reaches at least 30 RPM during cranking. The timer Sd Ventilation Time (page 196) become
active when the gen-set has been stopped for any Sd protection or the controller has been turned on only
before first cranking attempt. The output is opened 500ms after all Additional running engine indication
Additional running engine indications (page 116) will be inactive. The output is opened when the gen-
set has to be stopped or in pause during repeated starts.
Ignition On
Manual Ready
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1258
Description
This output is active when controller is in MAN mode and the engine is stopped and it is possible to start it
i.e. no red alarm is activated or SD OVERRIDE (PAGE 543) is active (Output READY (PAGE 599) is active).
MCB Close/Open
Related FW 1.7.0 Related applications AMF
Comm object 45
Description
The output controls the mains circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note: InteliLite controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
Mode MAN
Related FW 1.7.0 Related applications AMF, MRS
Comm object 18
Description
This output is active whenever the controller is in MAN mode.
Mode OFF
Related FW 1.7.0 Related applications AMF, MRS
Comm object 17
Description
This output is active whenever the controller is in OFF mode.
Mode TEST
Related FW 1.7.0 Related applications AMF
Comm object 20
Description
This output is active whenever the controller is in TEST mode.
LBO: N
Not In AUTO
Related FW 1.7.0 Related applications AMF
Comm object 1248
Description
This output is active when controller isn’t in AUTO mode.
LBO: P
Power Switch
Related FW 1.7.0 Related applications AMF, MRS
Comm object 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment of
the setpoints Power Switch On (page 216) and Power Switch Off (page 217). When the dummy load function is
used the switching ON of Power switch is block when the engine isn’t running and is allowed 30 s after start
of the engine.
Note: Setpoints Power Switch On (page 216) and Power Switch Off (page 217) are invisible until
configuration of this LBO.
Prestart
Related FW 1.7.0 Related applications AMF, MRS
Comm object 36
Description
When the Prestart Time (page 185) is longer than Cranking Fail Pause (page 184) then the Prestart Time (page
185) in Cranking Fail Pause (page 184) is long as Cranking Fail Pause (page 184) minus 100ms.
LBO: R
Ready To AMF
Related FW 1.7.0 Related applications AMF
Comm object 324
Description
The output is closed if the gen-set is ready to start automatically and take the load if the mains fails, i.e.:
the controller is in AMF operating mode
the controller is in AUTO controller mode and
no red alarm is present in the alarmlist
when the red alarm is confirmed during Stop Valve and other requirements are fulfilled then the LBO is
still inactive until the state ready
Ready To Load
Related FW 1.7.0 Related applications AMF, MRS
Comm object 58
Description
The output is closed whenever the GCB is closed or can be closed i.e. the stabilization phase is finished, the
gen-set is running and the Minimal Stabilization Time (page 194) timer has elapsed.
and the gen-set voltage and frequency are within limits.
If GCB is open then gen-set voltage and frequency must be in limits.
If GCB is close then gen-set voltage and frequency can be out of limits, but protection delay can’t be count
down. If gen-set voltage and frequency will return into limits until delay is count down then output is still
closed.
Regen Needed
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1372
Description
This output is closed when DPF lamp from ECU is active.
Running
Related FW 1.7.0 Related applications AMF, MRS
Comm object 67
Description
The output is designed to be used as an indication that the gen-set is running. The output closes if FUEL
SOLENOID (PAGE 579) is closed and STARTER (PAGE 600) and PRESTART (PAGE 596) are open. The out
remains close until engine stop and cooling period elapses.
Starter
Related FW 1.7.0 Related applications AMF, MRS
Comm object 24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
Cranking Attempts (page 183) in Engine Settings group. Cranking fail pause is adjusted by setpoint Cranking
Fail Pause (page 184).
Still Log 1
Related FW 1.7.0 Related applications AMF, MRS
Comm object 27
Description
Logical binary output which is still in logical 1.
Stop Pulse
Related FW 1.7.0 Related applications AMF, MRS
Comm object 25
Description
Output is active for 1 second after STOP SOLENOID (PAGE 601) output activation. This signal is sent to ECU
in case of engine stop request.
Stop Solenoid
Related FW 1.7.0 Related applications AMF, MRS
Comm object 23
Description
This output is dedicated to control the stop solenoid (valve). The output closes when an engine stop
command is received and remains active until the gen-set is stopped.
Note: If Additional running engine indications (page 116) are lost during 5s pause than Stop
Solenoid is not activated again otherwise stop solenoid is activated again.
Swap Start
Related FW 1.7.0 Related applications AMF, MRS
Comm object 1997
Description
This logical binary output is result of internal comparator which compares statistic values Running Hours
(page 475) and Pulse Counter 2 (page 474). Binary output is active when Running Hours (page 475) are equal
or higher than the Pulse Counter 2 (page 474).
LBO: T
Temperature Switch
Related FW 1.7.0 Related applications AMF, MRS
Comm object 563
Description
This is an output from the Temperature switch function. The behavior of the switch depends on the
adjustment of the setpoints Temperature Switch On (page 206) and Temperature Switch Off (page 207).
Note: Setpoints Temperature Switch On (page 206) and Temperature Switch Off (page 207) are invisible
until configuration of this LBO.
Ventilation On Pulse
Related FW 1.7.0 Related applications AMF, MRS
Comm object 2089
Description
This logical binary output is activated on rising edge of VENTILATION (PAGE 604) LBO (at the begining of
prestart period). The pulse duration is adjusted by Ventilation Pulse Time (page 219) setpoint.
Note: The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
For full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically (page 606).
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 02
Related FW 1.7.0 Related applications AMF, MRS
Comm object 210
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH02 (PAGE 561). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
2 On (page 248) and Analog Switch 2 Off (page 249).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 03
Related FW 1.7.0 Related applications AMF, MRS
Comm object 211
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH03 (PAGE 561). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
3 On (page 251) and Analog Switch 3 Off (page 252).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 05
Related FW 1.7.0 Related applications AMF, MRS
Comm object 278
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH05 (PAGE 562). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
5 On (page 257) and Analog Switch 5 Off (page 258).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 06
Related FW 1.7.0 Related applications AMF, MRS
Comm object 279
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH06 (PAGE 563). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
6 On (page 260) and Analog Switch 6 Off (page 261).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 08
Related FW 1.7.0 Related applications AMF, MRS
Comm object 281
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH08 (PAGE 564). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
8 On (page 266) and Analog Switch 8 Off (page 267).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 09
Related FW 1.7.0 Related applications AMF, MRS
Comm object 282
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH09 (PAGE 564). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
9 On (page 269) and Analog Switch 9 Off (page 270).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 11
Related FW 1.7.0 Related applications AMF, MRS
Comm object 284
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH11 (PAGE 565). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
11 On (page 275) and Analog Switch 11 Off (page 276).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 12
Related FW 1.7.0 Related applications AMF, MRS
Comm object 285
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH12 (PAGE 566). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
12 On (page 278) and Analog Switch 12 Off (page 279).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 14
Related FW 1.7.0 Related applications AMF, MRS
Comm object 287
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH14 (PAGE 567). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
14 On (page 284) and Analog Switch 14 Off (page 285).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 15
Related FW 1.7.0 Related applications AMF, MRS
Comm object 288
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH15 (PAGE 567). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
15 On (page 287) and Analog Switch 15 Off (page 288).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 17
Related FW 1.7.0 Related applications AMF, MRS
Comm object 290
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH17 (PAGE 568). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
17 On (page 293) and Analog Switch 17 Off (page 294).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 18
Related FW 1.7.0 Related applications AMF, MRS
Comm object 291
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH18 (PAGE 569). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
18 On (page 296) and Analog Switch 18 Off (page 297).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
AIN Switch 20
Related FW 1.7.0 Related applications AMF, MRS
Comm object 293
Description
Logical analog input designed for general value received from analog sensor. For more information about
wiring of analog inputs see Analog inputs on page 38. This analog input controls logical binary output AIN
SWITCH20 (PAGE 570). The behavior of the switch depends on the adjustment of the setpoints Analog Switch
20 On (page 302) and Analog Switch 20 Off (page 303).
Note: This function is not suitable for tristate or binary analog sensors.
IMPORTANT: This analog input has no protection. Input is designed only to control
appropriate logical binary output.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This analog function can by also configured on binary input as binary function. In this case chose
COOLANT TEMP (PAGE 529) binary input in the list of binary inputs. Delay of this binary input is adjusted
via the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + BOC Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd Analog value is used for warning and shutdown protection.
Sd Analog value is used for shutdown protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
IMPORTANT: For right behavior of this function, curve for analog input has to be in
percentage and setpoint Fuel Tank Volume (page 210) has to be adjusted correctly.
Note: This analog function can by also configured on binary input as binary function. In this case chose
FUEL LEVEL (PAGE 532) binary input in the list of binary inputs. Delay of this binary input is adjusted via
the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Protection types
Monitoring Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn Analog value is used for warning protection only.
Wrn + Sd Analog value is used for warning and Sd protection.
Sd Analog value is used for Sd protection.
Alarm
Under limit Alarm is activated when value of analog input is under adjusted limits
Over limit Alarm is activated when value of analog input is over adjusted limits
Under limit + fls Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Example: Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be activated +
Sensor fail alarm will be activated.
Note: This analog function can by also configured on binary input as binary function. In this case chose
OIL PRESSURE (PAGE 539) binary input in the list of binary inputs. Delay of this binary input is adjusted
via the same setpoint like for analog function.
IMPORTANT: Value from analog input has higher priority than value from ECU.
8.1.6 PLC
List of PLC groups
Group: Basic Logical functions 640
For full list of PLC blocks go to the chapter List of PLC blocks (page 639).
Group: Comparison of
analog inputs
Comparator With
Hysteresis 643
Comparator With Delay 644
Group: Other
functions
Force History Record 649
Force Protection 649
Related FW 1.7.0
Comm object 1
Inputs
Function OR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 1
Function AND
Input 1 Input 2 Output
0 0 0
0 1 0
1 0 0
1 1 1
There have to be at least 2 inputs every time. There may be up to 8 inputs configured.
Function XOR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 0
Function RS
R S Qn+1
0 0 Qn
0 1 1
1 0 0
1 1 0
Note: Level On and Level Off can be constants or values from controller.
IMPORTANT: In case that values on inputs have different decimal numbers than the values
are converted and the name of block is red. It is strongly recommended to use values with
the same decimal numbers.
Related FW 1.7.0
Comm object 14
Inputs
Note: If you want the output to start at logical 0, tick First down option. Otherwise the output will start at
logical 1.
IMPORTANT: In case that inputs are not connected and First down option isn´t tick, than
output is active.
Note: If Input time up or Input time down value is <0, this input is internally set to zero.
Note: Input time up and Input time down values can be constants or values from controller.
Note: Use Pulse on edge option to choose between delay and pulse mode.
Force Protection
PLC group Other functions
Related FW 1.7.0
Related applications AMF, MRS
Comm object 10
Inputs
Note: Prefix of protection (e.g. Wrn, Sd, BOC) is added automatically into alarmlist message.
8.2 Alarms
8.2.1 Alarms level 1 650
8.2.2 Alarms level 2 677
8.2.3 Fail sensor and other types 695
Wrn Maintenance 1
Alarm Type Warning
Alarmlist message Wrn Maintenance 1
Alarm evaluated All the time
Related applications AMF, MRS
Adjust the setpoint Maintenance Timer 1 (page 213) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
Description running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Wrn Maintenance 2
Alarm Type Warning
Alarmlist message Wrn Maintenance 2
Alarm evaluated All the time
Related applications AMF, MRS
Adjust the setpoint Maintenance Timer 2 (page 214) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
Description running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Description
Note: Gen-set cannot be started until this alarm is inactive and reset.
Other type
After-Treatment
Alarm Type Alarm indication
Alarmlist message After-Treatment
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when appropriate after-treatment lamp is active.
EM(A) - insufficient
Alarm Type Other
Alarmlist message EM(A) - insufficient
Alarm evaluated All the time
Related applications AMF, MRS
The alarm indicates that there was a request to send an alarm email to email
Description address which is adjusted in setpoint Email Address 1 (page 373) and email wasn’t
send.
EM(B) - insufficient
Alarm Type Other
Alarmlist message EM(B) - insufficient
Alarm evaluated All the time
Related applications AMF, MRS
The alarm indicates that there was a request to send an alarm email to email
Description address which is adjusted in setpoint Email Address 1 (page 373) and email wasn’t
send.
Manual Restore
Alarm Type Warning
Alarmlist message Manual Restore
Alarm evaluated All the time
Related applications AMF
Alarm is activated when controller is in AUTO mode, Return From Island (page 239)
Description
setpoint is set to manual, load is on gen-set a mains has returned.
Module(slotA) - unexpected
Alarm Type Other
Alarmlist message Module(slotA) - unexpected
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that in slot is inserted different module than which is
Description configured or the module is unconfigured and has to be configured for proper
function.
Module(slotB) - unattended
Alarm Type Other
Alarmlist message Module(slotB) - unattended
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that two same communication modules are inserted in slots
Description
and one of them will be inactive.
Module(slotB) - unexpected
Alarm Type Other
Alarmlist message Module(slotB) - unexpected
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that in slot is inserted different module than which is
Description configured or the module is unconfigured and has to be configured for proper
function.
For full list of Alarms level 2 go to List of alarms level 2 (page 678).
What alarms level 2 are:
The level 2 level alarm indicates that a critical level of the respective value or parameter has been reached. For
more information see Alarm types - Level 2 on page 98.
Description Note: Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function Emergency
Stop to this binary input. It is recommended to use NC contact of the button.
Sd AIN Protec
Alarm Type Sd
Alarmlist message Sd + Name of analog input
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that value the general analog protection is out of shutdown
Description
protection limit.
Sd Battery Flat
Alarm Type Shutdown
Alarmlist message Sd Battery Flat
Alarm evaluated During cranking
Related applications AMF, MRS
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so exhausted
Description
that its voltage drops so low when starter motor is energized that it causes
controller reset.
Sd BIN Protection
Alarm Type Shutdown
Alarmlist message Sd + Name of binary input
Alarm evaluated All the time
Sd Coolant Temp
Alarm Type Shutdown
Alarmlist message Sd Coolant Temp
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that the coolant temperature is higher than the temperature set
Description
in Coolant Temperature Sd (page 204) setpoint.
Sd Current Unbalance
Alarm Type Shutdown
Alarmlist message Sd Current Unbalance
Alarm evaluated All the time
Related applications AMF, MRS
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
Description
Current Unbalance BOC (page 223) adjusts the maximum allowed difference
between the highest and lowest phase current at any given time.
Current Unbalance BOC Delay (page 223) adjusts the alarm delay.
Sd Fence 2 Alarm
Alarm Type Shutdown
Alarmlist message Sd Fence 2 Alarm
Alarm evaluated All the time
Related applications AMF, MRS
This alarm evaluates the GPS position of gen-set. The following setpoint are
related to it:
Sd Fuel Level
Alarm Type Shutdown
Alarmlist message Sd Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that the fuel level is lower than the level set in Fuel Level Sd
Description
(page 208) setpoint.
Sd GCB Fail
Alarm Type Shutdown
Alarmlist message Sd GCB Fail
Alarm evaluated All the time
Sd Oil Pressure
Alarm Type Shutdown
Alarmlist message Sd Oil Pressure
Alarm evaluated Gen-set is running
Related applications AMF, MRS
This alarm indicates that the oil pressure is lover than the pressure set in Oil
Description
Pressure Sd (page 202) setpoint.
Sd Overspeed
Alarm Type Shutdown
Alarmlist message Sd Overspeed
Alarm evaluated All the time
Related applications AMF, MRS
This alarm occurs immediately when the engine speed has exceeded the limit. The
behavior of the overspeed alarm is adjusted by the following setpoints:
Overspeed Sd (page 201) adjust the overspeed limit
Description
Overspeed Overshot (page 201) adjust the additional overspeed limit
Overspeed Overshot Period (page 202) adjust the time period of additional
overspeed limit
Sd Short Circuit
Alarm Type Shutdown
Alarmlist message Sd Short Circuit
Alarm evaluated All the time
Sd Start Fail
Alarm Type Shutdown
Alarmlist message Sd Start Fail
Alarm evaluated When the gen-set is being started
Related applications AMF, MRS
This alarm will be issued after all attempts to start the gen-set have run out but the
Description gen-set did not start. The following setpoints are related to this alarm:
Cranking Attempts (page 183) adjust the number of attempts
Sd Underspeed
Alarm Type Shutdown
Alarmlist message Sd Underspeed
Alarm evaluated Engine running only
Related applications AMF, MRS
This alarm will be issued when the gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint Underspeed Sd (page 201).
Description
The underspeed alarm starts to be evaluated after successful gen-set start and is
being evaluated for the entire time that the fuel solenoid is on.
Other type
BOC AIN Prot
Alarm Type BOC
Alarmlist message BOC + Name of analog input
Alarm evaluated All the time
Related applications AMF, MRS
This alarm indicates that the value of general analog protection is out of BOC
Description
protection limit.
BOC Overcurrent IDMT
Alarm Type Shutdown
Alarmlist message Sd + Name of binary input
Alarm evaluated Generator excited only
Related applications AMF, MRS
The overcurrent alarm is based on IDMT principle. The reaction time of an IDMT
alarm is not fixed, but depends on how much is the protected value (generator
current in this case) above the limit (Nominal Current (page 170)). The higher is the
overcurrent, the shorter the reaction time will be. All generator phases are
evaluated.
Description
The behaviour of the overcurrent alarm is adjusted by the following setpoints:
IDMT Overcurrent Delay (page 222) defines the reaction time of the
protection when the current is twice the amount of nominal value.
Nominal Current (page 170) set the nominal current level, where the alarm
starts to be evaluated. The reaction time is infinite at this point.
BOC Rental Timer
Alarm Type Shutdown
Alarmlist message BOC Rental Timer
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when Rental Timer BOC (page 323) elapses.
For full list of Fails sensor and other types of alarms go to List of fail sensor alarms (page 696).
What Fail sensor and other types of alarms are
If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the Alarmlist. For more information see Sensor fail detection (FLS) on
page 99.
8.3 Modules
8.3.1 Plug-In modules 698
8.3.2 CAN modules 713
IMPORTANT: 2nd generation of InteliLite controllers does not support new modules and 3rd
generation does not support all old modules.
CM-Ethernet
CM-4G-GPS
CM-GPRS
CM-RS232-485
EM-BIO8-EFCP
Communication modules
CM-RS232-485 698
CM-Ethernet 700
CM-GPRS 702
CM-4G-GPS 706
CM-RS232-485
CM-RS232-485 is optional plug-in card to enable InteliLite the RS232 and RS485 communication. This is
required for computer or MODBUS connection. The CM-RS232-485 is a dual port module with RS232 and
RS485 interfaces at independent COM channels. The RS232 is connected to COM1 and RS485 to COM2.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Note: Balancing resistors shall be both closed at only one device in whole RS485 network.
Maximal distance of line is 10m for RS232 line and 1200m for RS485 line.
Terminator 120Ω
Balancing resistor +5V
Technical data
40 mA / 8 VDC
26 mA / 12 VDC
Power consumption
14 mA / 24 VDC
10 mA / 36 VDC
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
CM-Ethernet
CM-Ethernet is a plug-in card with Ethernet 10/100 Mbit interface in RJ45 connector. It provides an interface for
connecting a PC with through ethernet/internet network, for sending active e-mails and for integration of the
controller into a building management (MODBUS TCP and SNMP protocols). This card also enables to monitor
and control the gen-set over web browser from any location with internet access using appropriate security
measures.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Use an Ethernet UTP cable with a RJ45 connector for linking the module with your Ethernet network. The
module can also be connected directly to a PC using cross-wired UTP cable.
Technical data
120 mA / 8 VDC
82 mA / 12 VDC
Power consumption
35 mA / 24 VDC
25 mA / 36 VDC
Module setup
All settings related to the module are to be adjusted via the controller setpoints. The respective setpoints are
located in the setpoint Group: CM-Ethernet (page 373).
All actual operational values like actual IP address etc. are available in controller values in a specific group as
well.
On module is also indication LED. Following states are indicated via this LED:
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
you want to program into the module (in InteliConfig).
Press the OK button to start upgrade of firmware.
The firmware update process may be performed via any kind of connection including connection via the same
module in which the firmware is to be updated. The connection is reestablished again automatically when the
update process is finished.
CM-GPRS
CM-GPRS plug-in module is a GSM/GPRS modem which can works in two modes of operation based on the
settings in the setpoint Internet Connection (page 361).
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
IMPORTANT: CM-4G-GPS and CM-GPRS modules can't be used in one controller in the same time.
Note: GPRS and CSD services must be provided by your GSM/GPRS operator for successful operation.
Note: The GPRS and CSD connection should not be used for the firmware update process.
Technical data
32 mA / 8 VDC
18 mA / 12 VDC
Power consumption
10 mA / 24 VDC
12 mA / 36 VDC
Make sure SIM card does not require PIN code. Use any mobile phone to switch the SIM PIN security off.
Place the SIM card into slot on CM-GPRS card
Connect the antenna to Cellular module antenna connector.
Switch off the controller.
Insert CM-GPRS module into controller
Power up the controller.
Select the mode of CM-GPRS module by adjusting setpoint Mode.
Enter correct APN Name, APN User Name and APN User Password in controller’s setpoint group CM-
GPRS which is accessible by PAGE button from any measurement screen on controller. Setpoints can be
set on controller’s front panel keyboard or by InteliConfig.
Switch the controller off and on.
Wait for approx 2 - 4 minutes for first connection of the system to AirGate. AirGate will generate
automatically the AirGate ID value. Then navigate to measurement screens where you will find signal
strength bar and AirGate ID identifier.
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
4 Module – error in initialization
5 Module – not possible to set the APN
6 Module – not possible to connect to GPRS network
7 Module – not possible to retrieve IP address
8 Module – not accepted DNS IP address
9 Error in modem detection
10 Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or unknown
11
status of SIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
Code Description
0 Waiting for connection to AirGate Server
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
CM-4G-GPS
CM-4G-GPS plug-in module containing a GPS receiver and GSM/WCDMA/LTE modem which can works in
two modes of operation based on the settings in the setpoint Internet Connection (page 361).
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
IMPORTANT: CM-4G-GPS and CM-GPRS modules cant be used in one controller in the same time.
Note: Cellular data service must be enabled in your SIM card by your mobile operator for successful operation.
Technical data
55 mA / 8 VDC
35 mA / 12 VDC
Power consumption
8 mA / 24 VDC
5 mA / 36 VDC
Note: Make sure that your SIM supports the packet data network type you want to use. - i.e. if you want to use
the module in LTE (4G) network you have to confirm with the operator that the particular SIM card supports 4G
network.
Contact your mobile operator for getting packet data APN (APN = Access Point Name), username and
password.
Example: APN Name = "internet", UserName = [blank], Password = [blank].
Make sure SIM card does not require PIN code. Use any mobile phone to switch the SIM PIN security off.
Place the SIM card into slot on CM-4G-GPS card
Connect the antenna to Cellular module antenna connector.
If you want to use the built-in GPS receiver connect also an active GPS antenna to the GPS antenna
connector.
Switch off the controller.
Insert CM-4G-GPS module into controller
Power up the controller.
Select the mode of CM-4G-GPS module by adjusting setpoint Mode.
Enter correct APN Name, APN User Name and APN User Password in controller’s setpoint group CM-4G-
GPS which is accessible by PAGE button from any measurement screen on controller. Setpoints can be set
on controller’s front panel keyboard or by InteliConfig.
Switch the controller off and on.
Wait for approx 2 - 4 minutes for first connection of the system to AirGate. AirGate will generate
automatically the AirGate ID value. Then navigate to measurement screens where you will find signal
strength bar and AirGate ID identifier.
GSM Diag Code – Common list of diagnostic codes for cellular modules
GSM Diag Code – Common list of diagnostic codes for cellular modules
Code Description
0 OK. No error.
1 Not possible to hang up.
2 Modul is switched off
3 Module is switched on
4 Module – error in initialization
5 Module – not possible to set the APN
6 Module – not possible to connect to GPRS network
7 Module – not possible to retrieve IP address
8 Module – not accepted DNS IP address
9 Error in modem detection
10 Error in initialization of analog modem
SIM card is locked (Possibly PIN code required, PIN needs to be deactivated) or unknown
11
status of SIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
Code Description
0 Waiting for connection to AirGate Server
1 Controller registered, waiting for authorization
2 Not possible to register, controller blacklisted
3 Not possible to register, server has no more capacity
4 Not possible to register, other reason
5 Controller registered and authorized
Extension modules
EM-BIO8-EFCP 710
EM-BIO8-EFCP
EM-BIO8-EFCP is optional plug-in card. Through this card controller can accommodate one AC current (CT)
measuring input (1A or 5A input) and up to 8 binary inputs or outputs. In InteliConfig PC configuration tool it is
possible to easily choose if particular I/O will be binary input or output.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to controller.
Binary inputs
Number Up to 8, non-isolated
0-2 VDC close contact
Close/Open indication
>6 VDC open contact
Current measurement
2% from Nominal current
tolerance
Max peak current from CT 150 A / 1 s
Firmware upgrade
Download the newest FW of module from ComAp website (in form of PSI file or installation package)
Instal package to computer or open PSI to instal it into InteliConfig
Plug the module into the controller and power the controller on.
Open a connection with controller via InteliConfig
Go the menu Tools -> Firmware upgrade, select the Plug-in modules tab and select the appropriate firmware
IMPORTANT: In slot 3, 4 and 5 CAN modules Inteli IO8/8 and Inteli IO 16/0 are supported without
analog outputs. Analog outputs of these CAN modules are supported only in slot 1 and 2.
It is possible to add up to 80 binary inputs or up to 68 binary outputs or up to 32 analog inputs on CAN modules.
Extension modules
Inteli AIN8 713
Inteli IO8/8 719
IGS-PTM 726
Inteli AIN8TC 732
Inteli AIO9/1 736
Inteli AIN8
Inteli AIN8 module is extension module equipped with analog inputs. Inteli AIN8 module is connected to
controller by CAN1 bus.
Analog inputs
8 channels
can be configured as:
resistor three wire input
current input
voltage input
All inputs can be configured to any logical function or protection.
IMPORTANT: Impulse input is not supported in controller.
Supported sensors
Sensors
User curves NI100 [°F] (fix) 0-5V
PT100 [°C] (fix) NI1000 [°F] (fix) 0-10V
PT1000 [°C] (fix) 4-20mA passive
CAN address
DIP switch determinates CAN address for analog inputs.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
4. Connect the unit with PC via RS232-null modem cable and AT-Link conv
LED indication
LED status Description
Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address).
Power supply is in the range and the communication between Inteli AIN8 and controller
works properly.
Lights
Or power supply is in range and zero CAN address is set. (in case zero CAN address
module doesn’t communicate with the controller).
Wiring
The following diagrams show the correct connection of sensors.
Terminator
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 110x110x46 mm (4,3”x4,3”x1,8”)
Weight 221,5 grams
Analog inputs
Number of channels 8
Range 0-10 V
Voltage
Accuracy: ± 0,25 % of actual value + ± 25 mV
Range: ±20 mA
Current
Accuracy: ± 0,25 % of actual value + ± 50 µA
Range: 0- 10 kΩ
Resistive
Accuracy: ± 0,5 % of actual value + ± 2 Ω
Inteli IO8/8
Inteli IO8/8 module is an extension module equipped with binary inputs, binary outputs and analog outputs.
Inteli IO8/8 is the name of the module, but it is possible to configure the module (by internal switch) to two
configurations:
Inteli IO8/8 - 8 binary inputs, 8 binary outputs and 2 analog outputs
Inteli IO 16/0 - 16 binary inputs, 0 binary outputs and 2 analog outputs
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO 16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.
Note: In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set. When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs. When this
LED is dark, then the module is configured as 16 binary inputs.
LED at power connector - status LED
Wiring
The following diagrams show the correct connection of inputs and outputs.
Binary inputs - pull up
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the GND (-) - dashed line).
On lower picture is case of wiring between BIN2 and GND (-). Both ways are correct.
Binary inputs - pull down
There are two options of wiring. On upper picture you can see case when binary input is connected between
BIN2 and COM (COM is connected internally to the Ucc (+) - dashed line).
On lower picture is case of wiring between BIN2 and Ucc (+). Both ways are correct.
When high side setting of outputs is chosen - binary output must be connected to the minus potential directly
Terminal VHS (voltage High side) has to be connected to positive potential directly. Maximal current of each
binary output is 500 mA. Size of fuse depends on load.
Binary outputs - low side
When low side setting of outputs is chosen - binary output must be connected to the plus potential of power
supply directly. Minus potential is connected internally - dashed line.
Analog outputs
IMPORTANT: Terminator for analog output has special analog ground (AGND), which must not be
connected to the GND.
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller CAN1
Protection IP20
Storage temperature - 40 °C to + 80 °C
Analog outputs
Number of channels 2
Range 0-10 V
Voltage Accuracy: ± 20 mV + ±0,5 % of actual value
Imax 5 mA
Range: 0-20 mA
Current Accuracy: ± 100 µA + ±0,5 % of actual value
Rmax 500 Ω
Level 5 V
PWM Frequency - adjustable 200÷2400 Hz
Imax 20 mA
Binary inputs
Number of channels 8 for Inteli IO8/8, 16 for Inteli IO 16/0
Input resistance 4400 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact indication 6 to 36 V DC
Binary outputs
Number of channels 8 for Inteli IO8/8, 0 for Inteli IO 16/0
Max current 500 mA
Max switching voltage 36 V DC
IGS-PTM
IGS-PTM module is extension module equipped with binary inputs, binary outputs, analog inputs and analog
output. IGS-PTM module is connected to controller by CAN1 bus.
Analog inputs
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.
Supported sensors
Sensors
PT100 [°C] (fix) User curves
NI100 [°C] (fix) 0-100 mV
PT100 [°F] (fix) 0-2400 ohm
NI100 [°F] (fix) ±20 mA
Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.
ADR1 ADR2 ADR offset BIN module BOUT module AIN module
Open Open 0 (default) 1 1 1
Close Open 1 2 2 2
Open Close 2 3 3 3
Close Close 3 4 4 4
Programing firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper is
used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set.
LED at power connector - status LED
LED status Description
Dark No required power connected.
Quick flashing Program check failure.
One flash and pause Compensation fail.
Three flashes and
Compensation successful.
pause
Flashes There is no communication between IGS-PTM and the controller.
Power supply is in the range and communication between IGS-PTM and controller
Lights
properly works.
Binary outputs
Resistance sensor
Voltage sensor
Analog outputs
Technical data
General data
Power supply 8 to 36 V DC
Current consumption 100 mA at 24V ÷ 500 mA
Interface to controller CAN1
Protection IP20
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Dimensions (WxHxD) 95×96×43 mm (3.7’×3.8’×1.7’)
Analog inputs
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value
Binary inputs
Number of channels 8
Input resistance 4700 Ω
Input range 0 to 36 V DC
Switching voltage level for open contact
0 to 2 V DC
indication
Max voltage level for close contact indication 8 to 36 V DC
Binary outputs
Number of channels 8
Max current 500 mA
Max switching voltage 36 V DC
Number of channels 8
Range 0-100 mV
Voltage
Accuracy: 1,5 % ± 1 mV out of measured value
Range: 0-20 mA
Current
Accuracy: 2.5 % ± 0,5 ohm out of measured value
Range: 0- 250 Ω
Resistive
Accuracy: 1 % ± 2 ohm out of measured value
Inteli AIN8TC
Inteli AIN8TC module is extension module equipped with 8 analog inputs dedicated for thermocouple sensors
only.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Analog inputs
8 channels
can be configured as thermocouple sensors only
Supported sensors
Sensors
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl J [°F] (fix)
Thermocpl K [°F] (fix)
Thermocpl L [°F] (fix)
Thermocpl (nc) J [°C] (fix)
Note: “nc” means not cold junction compensation (by external sensor).In this case is used internal temperature
sensor on the PCB
LED indication
Wiring
Analog inputs
Terminaor
Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24V ÷ 100 mA at 8V
Storage temperature - 40°C to + 80°C
Operating temperature - 30°C to + 70°C
Inteli AIO9/1
Inteli AIO9/1 module is extension module equipped with analog inputs and outputs – designed for DC
measurement.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Terminals
Analog inputs
4 channels AIN1 – AIN4 can be configured as:
Sensor ±65V (it is determinated for measurement of battery voltage)
4 channels AIN5 – AIN8 can be configured as:
Thermocouples – type J,K or L (in °C or °F)
Sensor ±75mV DC – (for connecting current shunts)
1 channel AIN9 can be configured as:
RTD (Pt1000, Ni1000)
Common resistance 0-2400Ω
Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5V, freq 2,4Hz ÷2,4kHz)
Analog output has 4-pins connector – GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.
Supported sensors
Sensors
User curves
PT1000 [°C] (fix)
NI1000 [°C] (fix)
0-2400Ω (fix linear)
± 65 V DC (fix linear)
+-75mV (fix linear)
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl (nc) J [°C] (fix)
Thermocpl (nc) K [°C] (fix)
Thermocpl (nc) L [°C] (fix)
LED indication
Wiring
The following diagrams show the correct connection of sensors.
Technical data
Analog output
I 0-20mA /500Rmax. ± 1 % of actual value + ± 200uA
U 0-10V ± 0.5 % of actual value + ± 50mV
PWM – 5V, 200Hz-2.4kHz 15mA max.
Galvanic separated from power supply
Galvanic separation CAN bus is galvanic separated from the measurement and power supply