Introduction

An excellent value in its class, the B856 features a compact 1/16 DIN package, the
precision of digital setting, versatile functionality, and a straightforward button-per-
digit interface.
It can be easily programmed to perform any standard timing operation: On-Delay, Off-
Delay, Interval 1, Interval 2, or Repeat Cycle. A unique On-Delay /Interval Mode can in
many cases perform the function of two separate timers. Output is via DPDT relay
contacts.
Five selectable time ranges, and a programmable decimal point provide preset times
ranging from .01 seconds to 9999 hours.
An available model's output features separate timed and instantaneous SPDT
contacts.
Simplicity of operation is maintained while still providing a high level of
functionality. All programming is done through the front panel, with an intuitive
button-per-digit keypad that makes entry
of preset times quick and easy. A crisp
dual line LCD display lets the operator
readily view elapsed or remaining cycle
time as well as the preset value. Prominent
annunciators indicate information such as Technical Manual
the time range and the status of the input
and outputs.
702070-0001
Reliability is a key feature of the B856.
IEC Level 4 noise immunity ensures
flawless operation in harsh electrical
environments, while its IEC IP65
Eagle Signal brand
enclosure rating allows use in washdown conditions.
Wiring via an industry standard 11 pin socket and a power supply that can
Series B856
accept 24 - 240 VAC or 24 VDC vastly simplify setup.
Multifunction
Features
• Field programmable choice of 6 operating
Index
Overview LCD Timer
modes Panel Mounting page 2
Wiring Connections page 2
• 5 selectable time ranges with resolution down
Front Panel Operation page 2
to 0.01 seconds
Programming
• High Contrast LCD display indicates both Program Mode page 3-4
process time and preset value Operating Modes
• Simple button per digit interface Timing Diagrams page 5
General
• Programmable security levels prevent Specifications page 8
unauthorized setpoint or program changes Ordering Information page 8
• Universal Power Supply (24 - 240 VAC, Warranty page 8
24 VDC)
• External Start and Reset Inputs
• UL and CUL recognized, CE marked
• IEC IP65 rated front panel
• Model with Instantaneous contacts also
available
O V E R V I E W

INSTALLATION & WIRING

8mm Socket
To wire the unit, an 11 pin socket is required. The
unit can then either be DIN rail mounted or panel
mounted using the supplied mounting bracket. For
panel mounting, place the unit in the cutout, then
48mm slide the bracket forward over the rear of the unit so
that the tabs catch in the grooves on the housing and
the bracket is as far forward as possible. Tighten the
panel mount screws until there is a snug fit against
66mm
the panel. Do not overtighten.
81mm

Reset
Start
5 6 7
For the -511 version, 4 8
Pins 1, 3, 4 are the
instantaneous contacts 3 9
2 10
1 11

Power
FRONT PANEL OPERATION Time Range Indicator
Illuminates to show the time base: H for
hours, M for minutes, S for seconds.
Multiple indicators will be illuminated
I/O Status Indicators
EAGLE SIGNAL when the time base is Hours:Minutes or
Illuminates to display when an input or Minutes:Seconds.

1234
IN H H
OUT M M
output is active: "IN' for the start input, RST S
"OUT" for the timed output, and "RST" for the Set Value
external reset signal.
Timing
1234 Settable value used to trigger the timed
output.
Time Indicators 4 3 2 1
The word "Timing" flashes when a timing
function is taking place. The applicable Numeric Keys
E P
arrow also lights to indicate if the display Each of the number keys is used to
is set to time up or time down. increment or decrement the value of the
corresponding digit of the preset or a
Time Value parameter value (increments if unit is set
Indicates the elapsed/remaining time to in time up mode and decrements if set in
preset. time down mode).
Edit Key Program Key
Many of the parameters in Program Mode require selection of a Pressing the key continuously for 3 seconds moves the unit in and
specific choice as opposed to a numeric value. The Edit key is out of Program mode. Once in Program mode, pressing and
used to scroll through the available choices. In Operation mode, releasing the key will scroll the display from one parameter to the
the Edit key can be pressed simultaneously with the Program key to next.
reset the timer.

2
P R O G R A M M I N G

PROGRAM MODE

• Enter the Program Mode by holding down the "P" key for 3 seconds
• Press the "P" key to move the top display from one parameter to the next
• Press the "E" key to scroll the bottom display through the available choices for that parameter
• While in Program Mode the unit will stop timing, and the output will retain its last state. The new
settings will only become effective after returning to Operation Mode by holding down the "P" key
for 3 seconds

P
For 3 Seconds

Operating Function: Determines how outputs will operate in relation to the set value. Choices are:
F u n c • On-Delay (OndL)
O n d L • Off Delay (OFdL)
• Interval 1 (int1)
• Interval 2 (int2)
P • Delay/Interval (dint)
• Repeat Cycle (CYCL)
See Appendix A for timing charts.

First Operation: Determines whether the Repeat Cycle will start with an On or an Off Operation
1 S t Note: This parameter will only appear if Repeat Cycle is chosen as the Operating
O n Function
P

Interval Time: Sets the amount of time the output will be active after the On-Delay function has timed
i n t out. Use the 1 through 4 keys to set the value in a range from 0.1 to 999.9 seconds.
1 . 0 S Note: This parameter will only appear if Delay/Interval is chosen as the Operating
Function
P

Time Range: Sets the unit of measure for the time values that will be shown on the display in
t r n G Operation Mode. Choices are:
S • Seconds
• Minutes
• Hours
P • Minutes:Seconds
• Hours:Minutes

Decimal Position: Sets the decimal position for the time display. Choices are: no decimal point (0),
d E c P 1/10ths position (0.0), or Hundredths position (0.00). The time range selected in the previous
0S parameter will remain illuminated for reference.
Note: This parameter will not appear if Minutes:Seconds or Hours:Minutes is
selected as the time range

3
P R O G R A M M I N G

Timing Direction: Determines whether the time value will increment from zero and change the state
t d i r of the output at the set value (uP) or decrement from the set value and change the state of the output
u P at zero (dn).

Power Reset Enable: After a loss of power, the unit can be programmed to either reset upon
P r S t reapplication of power (On) or continue from the point of power interruption (Off).
O n

Front Panel Reset Enable: When active (On), the timing operation can be reset in Operation Mode by
F r S t simultaneously pressing the "E" and "P" keys. If inactive (Off), the timing operation can only be reset
O n through the remote input.

Security Level: 4 different levels of security are available:


S L u L 0 = Full Access
0 1 = SP Locked Out
2 = Access to Program Mode only by holding the "P" key for 8 seconds
3 = SP Locked Out and access to Program Mode only by holding the "P" key for 8
seconds

4
O P E R A T I N G M O D E S

TIMING DIAGRAMS

On-Delay Off-Delay
Power
Power
Start
T Start
Output
Reset
Output T T
Instant.
Output
The output is activated at the leading edge of the start signal. Timing begins
Timing begins on the leading edge of the start input. The output will activate on the trailing edge. The output will remain active until the preset time (T)
at the completion of the preset time (T) and will remain active until the reset has elapsed or power is interrupted.* Reapplying the start signal before T has
signal is applied or power is interrupted.* The instantaneous output will elapsed will reset the time value. The reset input is not used.
activate upon the start signal and will remain active until the reset signal is
applied or power is interrupted.*

Interval 1 Interval 2

Power Power

Start Start

Output Output
T T T T

On the leading of the start input, the output is activated and timing begins. On the leading of the start input, the output is activated and timing begins.
The output will remain active until the preset time (T) has elapsed or power The output will remain active until the preset time (T) has elapsed or power
is interrupted.* Removal of the start signal will also cause the output to be is interrupted.* The reset input is not used.
deactivated and the time value to be reset. The reset input is not used.

Repeat Cycle Delay/Interval

Power Power
Start Start
T T T
Output
T1
Output T2
Reset
Timing begins on the leading edge of the start signal. A cycle is initiated where
the output will be OFF for the preset time (T), then ON for the preset time. This
The delay cycle begins upon application of the start signal. The output will
cycle will continue until a reset signal is applied, start signal is removed or power
activate at the completion of the preset time (T1). Upon activation of the
is interrupted.* The unit can also be programmed for the timing sequence to
output, the Interval cycle will begin. The output will be deactivated at the end
begin with an ON cycle.
of the Interval time (T2). T1 is the primary preset value and is set in Operation
Mode. T2 is set in Program Mode in a range from 0.1 to 999.9 seconds. The
timing sequence and output can also be reset through the reset input or
interruption of power.*
* The Power Reset parameter in Program Mode can be set so that a timing
sequence will not be reset upon power interruption but instead continue
5
on when power is restored.
N O T E S

DANAHER CONTROLS has representatives and distributors located in major cities within the United States and
throughout the world. For information about the distributor or sales office nearest you, contact our customer
service department:

Customer Service Internet Presence


Veeder-Root
call Toll Free 800.873.8731 E-Mail: [email protected] Dynapar
or 847.662.2666 Worldwide Web: http://www.dancon.com
6 Eagle Signal
N O T E S

DANAHER CONTROLS has representatives and distributors located in major cities within the United States and
throughout the world. For information about the distributor or sales office nearest you, contact our customer
service department:

Customer Service Internet Presence


Veeder-Root
call Toll Free 800.873.8731 E-Mail: [email protected] Dynapar
or 847.662.2666 Worldwide Web: http://www.dancon.com
Eagle Signal 7
G E N E R A L

ORDERING INFORMATION Operation


SPECIFICATIONS Supply Voltage: 24 - 240 VAC 50/60Hz, or 24 VDC
Power Consumption: 50 VA @ 240 VAC
Time Ranges: Hours, Minutes, Seconds, Hours:Minutes,
Inputs Minutes:Seconds
Start: NPN or Dry Contact Resolution: Settable for XXXX or XX.XX for Hours,
Reset: NPN or Dry Contact Minutes and Seconds ranges
Operating Modes: On Delay, Off Delay, Interval 1, Interval 2,
Outputs Repeat, Delay/Interval
Timed (B856-500): DPDT - 5 amp Repeat Accuracy: + 0.03%
Timed (B856-511): SPDT - 5 amp Electrical Service Life: 100,000 cycles at full load
Instantaneous (B856 -511): SPDT - 5 amp Mechanical Service Life: 10 million cycles at min. load
Activation Time: 15 msec. max. Weight: 100 grams (3.5 ounces)

Physical Environmental
Dimensions: 48mm x 48mm, 81mm deep Front Panel Rating: IEC IP65
Mounting Panel Mounting 45 x 45 cutout, or Operating Temperature: B856-500: 0° to 60° C (32° to 140° F)
DIN rail B856-511: 0° to 50° C (32° to 122° F)
Wiring Connection Via 11 pin plug in socket Storage Temperature: -40° to 90° C (-40° to 194° F)
Humidity: 5% to 95% RH non-condensing
Approvals: UL, CUL recognized; CE certified

ORDERING INFORMATION

Description Model # Description Model #


Multifunction Timer, 24 - 240 VAC, 24 VDC B856-500 11 Pin Socket 60SR3P06
Timer w/Instant Cont, 24 - 240 VAC, 24 VDC B856-511 11 Pin Socket - Outward Facing Terminals PBT-03172

WARRANTY

Standard B856 products manufactured by the Company are Products which the Company consents to have returned shall be
warranted to be free from defects in workmanship and material for shipped F.O.B. the Company's factory. The Company cannot assume
a period of two years from the date of shipment, and products responsibility or accept invoices for unauthorized repairs to its
which are defective in workmanship or material will be repaired or components, even though defective. The life of the products of the
replaced, at the option of the Company, at no charge to the Buyer. Company depends, to a large extent, upon the type of usage thereof,
Final determination as to whether a product is actually defective and THE COMPANY MAKES NO WARRANTY AS TO FITNESS OF ITS
rests with the Company. The obligation of the Company hereunder PRODUCTS FOR SPECIFIC APPLICATIONS BY THE BUYER NOR AS
shall be limited solely to repair and replacement of products that TO PERIOD OF SERVICE UNLESS THE COMPANY SPECIFICALLY
fall within the foregoing limitations, and shall be conditioned upon AGREES OTHERWISE IN WRITING AFTER THE PROPOSED USAGE
receipt by the Company of written notice of any alleged defects or HAS BEEN MADE KNOWN TO IT.
deficiency promptly after discovery within the warranty period, and THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL
in the case of components or units purchased by the Company, the OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING, BUT
obligation of the Company shall not exceed the settlement that the NOT LIMITED TO ANY WARRANTY OF MERCHANTABILITY OR OF
Company is able to obtain from the supplier thereof. No products FITNESS FOR A PARTICULAR PURPOSE.
shall be returned to the Company without its prior consent.

Printed in U.S.A.
#702070-0001