Instruction Manual: © Toshiba Energy Systems & Solutions Corporation 2017 All Rights Reserved
Instruction Manual: © Toshiba Energy Systems & Solutions Corporation 2017 All Rights Reserved
Instruction Manual: © Toshiba Energy Systems & Solutions Corporation 2017 All Rights Reserved
INSTRUCTION MANUAL
GRB150-***B
( Ver. 1.1 )
6 F 2 S 0 7 9 0
Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRB150. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
⎯1⎯
6 F 2 S 0 7 9 0
DANGER
• Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING
• Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage generated
is dangerous.
• Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply.
It takes approximately 30 seconds for the voltage to discharge.
• Fiber optic
When connecting this equipment via an optical fibre, do not look directly at the optical signal.
CAUTION
• Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
• Operating environment
The equipment must only used within the range of ambient temperature, humidity and dust
detailed in the specification and in an environment free of abnormal vibration.
• Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that
they conform to the equipment ratings.
• Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is on, as
this may cause the equipment to malfunction.
• External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
• Connection cable
Carefully handle the connection cable without applying excessive force.
• Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
• Disposal
When disposing of this equipment, do so in a safe manner according to local regulations.
⎯2⎯
6 F 2 S 0 7 9 0
Contents
Safety Precautions 1
1. Introduction 6
2. Application Notes 7
2.1 Application 7
2.2 High-impedance Differential Protection 8
2.2.1 Principle of operation 8
2.2.2 Through Fault Stability 8
2.2.3 Current Transformer Requirements 10
2.2.4 Fault Setting or Primary Operating Current 10
2.2.5 Peak Voltage Developed under Internal Fault Conditions 11
2.2.6 CT Supervision 11
2.3 Scheme Logic 12
2.3.1 High-impedance Differential Protection 12
2.3.2 Cold Load Protection 12
2.4 Setting 13
2.5 Tripping Output 13
3. Technical Description 14
3.1 Hardware Description 14
3.2 Input and Output Signals 19
3.2.1 Input Signals 19
3.2.2 Binary Output Signals 20
3.3 Automatic Supervision 21
3.3.1 Basic Concept of Supervision 21
3.3.2 Relay Monitoring 21
3.3.3 Failure Alarms 22
3.3.4 Trip Blocking 23
3.3.5 Setting 23
3.4 Recording Function 24
3.4.1 Fault Recording 24
3.4.2 Event Recording 25
3.4.3 Disturbance Recording 26
3.5 Metering Function 26
4. User Interface 27
4.1 Outline of User Interface 27
4.1.1 Front Panel 27
4.1.2 Communication Ports 29
4.2 Operation of the User Interface 30
4.2.1 LCD and LED Displays 30
4.2.2 Relay Menu 32
⎯3⎯
6 F 2 S 0 7 9 0
⎯4⎯
6 F 2 S 0 7 9 0
The data given in this manual are subject to change without notice. (Ver.1.1)
5
6 F 2 S 0 7 9 0
1. Introduction
The GRB150 is a numerical high-impedance differential relay for busbar protection and restricted
earth fault protection.
The GRB150 is a member of the G-series numerical single-function relays which are built on
common hardware modules and equipped with the following functions:
Automatic supervision
⎯6⎯
6 F 2 S 0 7 9 0
2. Application Notes
2.1 Application
The GRB150 provides high-impedance differential protection scheme and is applied for the
following protections:
• Restricted earth fault protection
• Single or one-and-a-half busbar protection
• T zone protection of one-and-a-half busbar arrangement
• Short line cable protection
The high-impedance differential protection detects a fault even if the CT is saturated by fault current.
The GRB150 provides the following human interfaces for issuing alarms, setting relay
parameters or viewing stored data.
• Relay front panel: LCD, LED display and operation keys
• Local PC
• Remote PC
The relay can be integrated with a local PC or a remote PC through a communication port.
A local PC can be connected via the RS232C port on the front panel of the relay. A remote PC can
also be connected through the RS485 port on the rear panel of the relay.
IEC60870-5-103 protocol is provided for communication with substation control and automation
systems.
The GRB150 has two models, model 101 and model 201. The model 101 is used for single-phase
applications and for restricted earth fault protection. The model 201 is used for three-phase
applications and for three-phase busbar, T zone and short line cable protection.
⎯7⎯
6 F 2 S 0 7 9 0
Busbar Busbar
EB-101 or EB-101 or
EB102 Resistor EB102 Resistor
GRB150 GRB150
Varistor Varistor
In the case of an internal fault the current transformer secondary currents will be in the same
direction and their sum will correspond to the total primary fault current. The corresponding
driving voltages will be in the same direction and a high voltage will be developed in the
differential circuit as it attempts to drive the secondary current through the burden presented by
the high-impedance relay. Dependent upon its setting the voltage relay will operate.
Note that in Figure 2.2.1 an external unit, either type EB-101 for single-phase protection or
EB-102 for three-phase protection has been shown. These include a varistor to limit the high
voltage developed in the differential circuit during internal faults and a series resistor to fix the
relay input impedance at 667ohms. Refer to Sections, 2.2.4 “Fault Setting or Primary Operating
Current” and 2.2.5 “Peak Voltage Developed under Internal Fault Conditions”.
The stability of a current differential system using a high-impedance relay and low reactance
current transformers is determined by means of calculation. If the relay setting voltage is made
equal to or greater than the maximum voltage that can appear across the relay circuit for a given
value of through fault current the current differential system will be stable. In calculating the
required setting voltage for the relay it is assumed that one current transformer will become fully
saturated and that the remaining current transformers will maintain their ratio. An example to
illustrate this point is shown in Figure 2.2.2 for a current differential system for a busbar with
several feeders.
⎯8⎯
6 F 2 S 0 7 9 0
Busbar
EB-101 or
EB102 Resistor
GRB150
Varistor
In this example an external fault is fed through a single circuit with the fault current being
supplied through all of the other circuits connected to the busbar. Since the total busbar current
has to be transformed by the current transformer on the faulted feeder there is a high probability
of this current transformer saturating whilst the current transformers on the other more lightly
loaded circuits remain unsaturated. Under these conditions a secondary current will flow in the
differential circuit that is equivalent to the primary fault current. The voltage drop caused by the
secondary current that flows in the differential circuit therefore determines the voltage input at the
relay.
In the equivalent circuit the shunt impedance for the fully saturated CT is negligible and the CT
will not produce an output, this is shown as a short circuit across the excitation impedance in
Figure 2.2.3.
Busbar
GRB150 +
CT1 ZE1 ZR EB-101/ ZE2 CT2
EB-102
Figure 2.2.3 Equivalent Circuit of the Differential Circuit for an External Fault
The total voltage drop is therefore due to the secondary fault current through the secondary
winding resistance of the saturated CT together with the wiring connecting it to the relay circuit
terminals. Provided that the relay setting voltage exceeds the value of VR in Equation (1) the
scheme will remain stable.
⎯9⎯
6 F 2 S 0 7 9 0
Factor K1 is associated with the design of the GRB150 relay and directly relates to its inherent
capability to block the unidirectional transient component of the fault current. This is based on
previous service experience and extensive laboratory tests.
In addition to K1 an inherent safety factor exists because the basic assumption of complete
saturation of one current transformer with no ratio error of the complementary one is an extreme
case of unbalance. In practice it is unlikely to occur as when one current transformer begins to
saturate its burden is transferred to the other current transformer(s) due to the fact that they are of
the same construction and experience the same secondary voltage.
• All current transformers used in the scheme shall have the same turns ratio
• All current transformers shall be of the low reactance type class X as specified in B.S.3938 in
terms of turns ratio, knee point voltage, secondary winding resistance and secondary exciting
current
• Bushing or toroidal current transformers with fully distributed windings and low leakage flux
shall be used.
• The secondary winding resistance must be kept to a minimum
• It is preferable that the current transformers are of similar design
• Other devices must not be connected to the same CT core
• CT knee-point voltage, Vk ≥ 2×VR
For an internal fault it is essential that the current transformer(s) produce sufficient output to
operate the relay. In order to achieve this, cater for any current transformer ratio errors and ensure
a high speed of operation the current transformers should have a VK of at least twice that of the
relay setting voltage as stated above.
A setting example is provided in Appendix L.
During an internal fault, the fault current must provide the exciting current for all of the connected
current transformers as well as the relay circuit current. To ensure positive operation, the current
requirement of the relay and the magnetising current requirement of all of the connected current
transformers at the relay setting voltage must be less than the minimum fault current that the relay
is required to detect. Therefore the secondary effective setting is the sum of the relay minimum
operating current and the excitation losses in all parallel connected current transformers. The
⎯ 10 ⎯
6 F 2 S 0 7 9 0
currents are not in-phase and hence the summation should be vectorial. However, an arithmetic
addition is acceptable resulting in the calculated setting being slightly higher than the actual
setting.
If the value calculated for Imin is too low the sensitivity can be reduced by the use of a shunt
resistor connected across the relay/varistor unit input.
A setting example is provided in Appendix L.
Under internal fault conditions a high voltage is developed in the differential circuit by the current
transformer so a varistor, (non-linear resistor) is connected in parallel to the relay to limit the
overvoltage. A varistor unit EB-101 is provided for single-phase protection and the EB-102 unit
for three-phase protection.
Note: It is our standard practice to use the EB-101 and EB-102 varistor units when applying
the GRB150. For those who prefer the more traditional approach of using externally
mounted components in place of the EB-101 and EB-102 units the GRB150 can be
applied with externally mounted suitably rated, linear and non-linear devices
provided that the input impedance is maintained at 667 ohms.
2.2.6 CT Supervision
The DIFSV element provides CT supervision to detect any unbalance in the CT secondary circuit
in the event of a fault in the wiring or the CT itself. The voltage setting of this element must be
greater than any erroneous voltage that can be developed under normal service conditions. The
two main sources of error are: -
• CT turns ratio error
• Differences in the respective lengths of the CT secondary connecting leads to the
paralleling point of the differential circuit
The setting of the DIFSV element is best illustrated with an example which is given in Appendix
L.
⎯ 11 ⎯
6 F 2 S 0 7 9 0
Figure 2.3.1 shows the scheme logic for the high-impedance differential protection type
GRB150. The differential protection operates on a per phase basis, although output signals of the
high-impedance differential element DIF can perform instantaneous three-phase tripping of the
circuit breaker. The supervisory element DIFSV will detect any erroneous differential voltage
appearing as a result of CT circuit failure. The tripping output signal of the DIF elements can be
blocked when the DIFSV element output is maintained for the setting time of TVDSV. To block
the tripping output with DIFSV operation, set scheme switch [VDCHK] to “ON” and set
[SVCNT] to “ALM&BLK”.
The output signal VD ERR of DIFSV element is used for alarm purposes.
Tripping
output relay
28
11, 12 , 13 0 t
DIF TP-1
&
0.2 s (Trip1)
TP-2
0 t
1 (Trip2)
&
14, 15, 16
TVDSV 0 .01 s 27
t 0
DIFSV & VD ERR
(Alarm)
0.1 0 - 60 .0 0s
[SVCNT]
+
[VDCHK]
+ "A LM&BLK "
"ON"
⎯ 12 ⎯
6 F 2 S 0 7 9 0
Two separate operational functions are available and they depend on the status of binary input
BI1. (Refer to Appendix N.)
- Function 1: used when ‘CB closing command’ is allocated to BI1 input”.
- Function 2: used when ‘CB contact’ is allocated to BI1 input.
These functions are selected by the scheme switch [CLEN].
When using the ’CB close command’ function, set [CLEN] to “F1”.
When using the ’CB contact’, set [CLEN] to “F2”.
If the cold load protection is disabled, set [CLEN] to “OFF”.
The [CLPTST] switch is used for testing purposes – please refer to Section 4.2.7.1.
The timing chart of cold load status judgment is shown in Appendix N.
If the cold protection is not to be used and BI1 is to be used for Indication Reset, then scheme
switch [IND. R] must be set to “ON”.
2.4 Setting
The following list shows the setting elements for the high-impedance differential protection and
their setting ranges.
Element Range Step Default
[VDCHK] Off / On - On
[CLEN] Off / F1 / F2 - Off
[IND. R] Off / On On
[SVCNT] ALM&BLK / ALM - ALM&BLK
DIF 10 - 600V 1V 100 V
DIFSV 5 - 100V 1V 50 V
TVDSV 0.10 - 60.00s 0.01s 0.50 s
DIFCC 1.00 – 10.00 0.01 1.00
TCLP 0.01 – 100.00s 0.01s 0.01 s
TCLE 0.00 – 100.00s 0.01s 0.00 s
TCLR 0.00 – 100.00s 0.01s 0.00 s
⎯ 13 ⎯
6 F 2 S 0 7 9 0
3. Technical Description
3.1 Hardware Description
Case outlines of GRB150, EB-101 and EB-102 are shown in Appendix E.
The hardware structure of GRB150 is shown in Figure 3.1.1.
The GRB150 relay unit consists of the following hardware modules. These modules are fixed to
the front panel and cannot be taken off individually. The human machine interface module is
provided with the front panel.
• Binary input and analogue input module (DI/AI)
• Main processing module (MPU)
• Binary output and communication module (DO/COM)
• Human machine interface module (HMI)
The hardware block diagram of GRB150 is shown in Figure 3.1.2.
Frame
DI / AI
DO/COM
HMI
IN SERVICE VIEW
MPU TRIP
ALARM
(back of front TESTING
panel) RESET
A B 0V
CAN
CEL ENTER
⎯ 14 ⎯
6 F 2 S 0 7 9 0
Auxiliary relay
Binary (high speed) Binary output
input ×2 Trip
Photocoupler command
Local
personal RS232C Monitoring
computer I/F jacks
DI/AI Module
The DI/AI module insulates internal circuits from external circuits through auxiliary transformers
and transforms the magnitude of AC input signals to suit the electronic circuits. The AC input
signals are single-phase or three-phase current which is the output from the varistor units EB-101
or EB-102.
There are 1 or 3 auxiliary CTs depending on the relay model. (For the correspondence between
the relay model and terminal number AC input signals, see Table 3.2.1.)
This module incorporates a DC/DC converter, analogue filter, multiplexer, analogue to digital
(A/D) converter and a photo-coupler circuit for the binary input signal.
The input voltage rating of DC/DC converter is 48V, 110V/125V or 220/250V. The normal range
of input voltage is −20% to +20%.
The analogue filter performs low-pass filtering for the corresponding current signals.
The A/D converter has a resolution of 12 bits and samples input signals at sampling frequencies
of 2400 Hz (at 50 Hz) or 2880 Hz (at 60 Hz).
This module is also provided with an IRIG-B port. This port collects the serial IRIG-B format
data from the external clock for synchronisation of the relay calendar clock. The IRIG-B port is
insulated from the external circuit by a photo-coupler. A BNC connector is used as the input
connector.
⎯ 15 ⎯
6 F 2 S 0 7 9 0
MPU Module
The MPU module consists of main a processing unit (MPU), random access memory (RAM) and
a read only memory (ROM) and executes all kinds of processing such as protection,
measurement, recording and display.
The MPU implements two 60 MIPS (Million Instructions Per Second) RISC (Reduced
Instruction Set Computer) type 32-bit microprocessors.
DO/COM Module
The DO/COM module incorporates two auxiliary relays (TP-1 and TP-2) dedicated to the circuit
breaker tripping command, 7 auxiliary relays (BO1-BO6 and FAIL) for binary output signals and
an RS485 transceiver.
TP-1 and TP-2 are the high-speed operation type and have one normally open contact.
The auxiliary relay FAIL has one normally closed contact, and operates when a relay failure or
abnormality in the DC circuit is detected. BO1 to BO6 have one normally open contacts.
The RS485 transceiver is used for the link with the relay setting and monitoring (RSM) system.
The external signal is isolated from the relay internal signal.
LED1 and LED2 are user-configurable. Each is driven via a logic gate which can be programmed
for OR gate or AND gate operation. Further, each LED has a programmable reset characteristic,
settable for instantaneous drop-off, or for latching operation. A configurable LED can be
programmed to indicate the OR combination of a maximum of 4 elements. For the setting, see
Section 4.2.6.10.
The VIEW key starts the LCD indication and switches between windows. The RESET key
clears the LCD indication and turns off the LCD back-light.
Once a trip command is issued, the TRIP LED remains lit even after the trip command disappears.
Pressing the RESET key resets it. The other LEDs operate as long as a signal is present. The
⎯ 16 ⎯
6 F 2 S 0 7 9 0
Liquid crystal
display
IN SERVICE VIEW
TRIP
Light emitting ALARM
diodes (LED) TESTING
RESET
Type GRB150
Model 201B-21-10
In
Vn ___
Operation keys
Fn 50Hz
Vdc 110/125Vdc
Light emitting Made in Japan
diodes (LED)
A B 0V
CAN
Monitoring Jacks CEL ENTER
To a local PC
Screw for handle Screw for cover
⎯ 17 ⎯
6 F 2 S 0 7 9 0
2 kΩ
TB1-1 2 kΩ TB1-4
2 kΩ
11Ω
TB1-2 Varistor TB1-5
TB1-8
Earth
(a) EB-101
2 kΩ
TB1-1 2 kΩ TB2-1
2 kΩ
11Ω A phase
2 kΩ
TB1-3 2 kΩ TB2-3
2 kΩ
B phase
11Ω
TB1-4 Varistor TB2-
2 kΩ
TB1-5 2 kΩ TB2-5
2 kΩ
11Ω C phase
TB1-8 Earth
(b) EB-102
⎯ 18 ⎯
6 F 2 S 0 7 9 0
AC input signals
Table 3.2.1 shows the AC input signals necessary for each of the GRB150 models and their
respective input terminal numbers.
⎯ 19 ⎯
6 F 2 S 0 7 9 0
GRB150
(+) (−)
[BISW1] 1
BI1 COMMAND
BI1 "N"
1
"I "
0V
The number of binary output signals and their output terminals are shown in Appendix F. All
outputs, except tripping commands and a relay failure signal, can be configured.
The signals shown in the signal list in Appendix B can be assigned to the output relay BO1 to
BO6 individually or in arbitrary combinations. Signals can be combined using either an AND
circuit or OR circuit with 4 gates each as shown in Figure 3.2.2. The output circuit can be
configured according to the setting menu. Appendix C shows the factory default settings.
Further, each BO has a programmable reset characteristic, settable for instantaneous drop-off, for
delayed drop-off, or for latching operation by the scheme switch [RESET].
The relay failure contact closes the contact when a relay defect or abnormality in the DC power
supply circuit is detected.
Signal List
≥1 4 GATES
0 t
&
[RESET]
0.2s
+ "DEL"
& S
F/F
"LATCH"
R
Reset button
+
≥
REMOTE RESET
⎯ 20 ⎯
6 F 2 S 0 7 9 0
Though the protection system is in a non-operating state under normal conditions, it is waiting for
a power system fault to occur at any time and must operate without fail when it occurs. Therefore,
the automatic supervision function, which checks the health of the protection system during
normal operation, plays an important role. A numerical relay based on the microprocessor
operations is suitable for implementing this automatic supervision function of the protection
system. The GRB150 implements the automatic supervision function taking advantage of this
feature based on the following concept:
• The supervising function should not affect the protection performance.
• Perform supervision with no omissions wherever possible.
• When a relay failure occurs, it should be able to easily identify the location of the failure.
Note: Automatic supervision function includes the automatic monitoring function and automatic
testing function. For the terminology, refer to IEC IEV 60448.
Memory monitoring
The memories are monitored as follows depending on the type of memory, and checked that the
memory circuits are healthy:
• Random access memory monitoring:
Writes/reads prescribed data and checks the storage function.
• Program memory monitoring: Checks the checksum value of the written data.
• Setting value monitoring: Checks the discrepancy between the setting values stored in
duplicate.
Watchdog timer
A hardware timer which is cleared periodically by software is provided and it is checked that the
software is running normally.
⎯ 21 ⎯
6 F 2 S 0 7 9 0
DC Supply Monitoring
The secondary voltage level of the built-in DC/DC converter is monitored and checks that the DC
voltage is within a prescribed range.
When a failure is detected by the automatic supervision, it is followed with an LCD message,
“ALARM” LED indication, external alarm and event recording. Table 3.3.1 summarises the
supervision items and alarms.
The alarms can be disabled collectively by setting the scheme switch [AMF] (Automatic
Monitoring Function) to OFF. The setting is used to block unnecessary alarms during
commissioning, testing or maintenance.
When the watchdog timer detects that the software is not running normally, the LCD display and
event recording of the failure may not function normally.
Supervision Item [SVCNT] LCD LED LED Ext. alarm Event record
switch* Message "IN SERVICE" "ALARM" Message
Differential voltage ALM & BLK Off On
monitoring (1) (2) Vd err
ALM On On
A/D accuracy check
(1) Off On (3) Relay fail
Memory monitoring
Watchdog Timer ---- Off On (3) ----
DC supply monitoring ---- Off (4) (3) ----
*: For [SVCNT] (supervision control) switch, see Appendix G and for its scheme logic, see
Appendix A.
(1) Diverse messages are provided as expressed with " Err:---" in the table in Section 6.7.2.
(2) The configurable signal “VD ERR” operates. (See Appendix B.)
(3) The binary output relay "FAIL" operates.
(4) Whether the LED is lit or not depends on the degree of the voltage drop.
⎯ 22 ⎯
6 F 2 S 0 7 9 0
When a failure is detected by the following supervision items, the trip function is blocked for as
long as the failure exists and is restored when the failure is removed.
• Differential voltage monitoring (selectable)
• A/D accuracy check
• Memory monitoring
• Watchdog Timer
• DC supply monitoring
When a failure is detected by the differential voltage monitoring, the scheme switch [SVCNT]
setting can be used to determine if both tripping is blocked and an alarm is initiated, or, if only an
alarm is initiated. (For the setting, see Section 4.2.6.7)
3.3.5 Setting
The setting elements necessary for the automatic supervision and their setting range are shown in
the table below.
⎯ 23 ⎯
6 F 2 S 0 7 9 0
Fault recording is started by a tripping command of the GRB150 and the following items are
recorded for one fault:
Date and time of fault occurrence
Operating phase
Relevant events
Power system quantities
Up to 8 most-recent faults are stored as fault records. If a new fault occurs when 8 faults have
been stored, the record of the oldest fault is deleted and the latest fault one is then stored.
Relevant events
Such events as for evolving faults are recorded with time-tags.
- Magnitude of differential voltage (Vd) for model 101 or phase differential voltage (Vda,
Vdb, Vdc) for model 201
⎯ 24 ⎯
6 F 2 S 0 7 9 0
Note: A change of setting is classified into three events. The event "System setting changed"
corresponds to all the setting changes except setting changes in the sub-menu "Protection".
(See section 4.2.6 for changing the settings). The event "Relay setting changed" corresponds
to a setting change of the measuring elements and timers in the sub-menu "Protection". The
event "Group setting changed" corresponds to other setting changes in the sub-menu
"Protection".
Setting
Recording mode can be set for each event. One of the following four modes is selectable except
for a change of setting(s).
• Not to record the event
• To record the event when status changes to "operate".
• To record the event when status changes to "reset".
• To record the event when status changes both to "operate" and "reset".
For “System setting changed”, “Relay setting changed” and “System setting changed”, one of the
following modes is selectable.
• Not to record the event
• To record the event when status changes to "operate".
⎯ 25 ⎯
6 F 2 S 0 7 9 0
Disturbance recording is started when the supervisory element DIFSV operates or a tripping
command is initiated. In Model 201, the records include three analogue signals (Vda, Vdb, Vdc :
phase differential voltage), eight binary signals listed below and the dates and times at which
recording started.
- DIF-A - DIFSV-A - Trip
- DIF-B - DIFSV-B - Cold load
- DIF-C - DIFSV-C
In Model 101, the records include an analogue signal (Vd: differential voltage), four binary
signals (DIF, DIFSV, Trip, Cold load) and the dates and times.
The LCD display only shows the dates and times of the disturbance records stored. Details can be
displayed on a PC. For how to obtain disturbance records on the PC, see the “Instruction Manual
PC Interface, RSM100”.
The pre-fault recording time is fixed at 0.3s and post-fault recording time can be set between 0.1
and 3.0s.
The number of records stored depends on the post-fault recording time. The approximate
relationship between the post-fault recording time and the number of records stored is shown in
Table 3.4.2.
Note: If the recording time setting is changed, the records stored so far are deleted.
Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored
⎯ 26 ⎯
6 F 2 S 0 7 9 0
4. User Interface
4.1 Outline of User Interface
The user can access the relay from the front panel.
Local communication with the relay is also possible using a personal computer (PC) via an
RS232C port. Furthermore, remote communication is also possible using RSM (Relay Setting
and Monitoring) or IEC60870-5-103 communication via RS485 port.
This section describes the front panel configuration and the basic configuration of the menu tree
of the local human machine communication ports and HMI (Human Machine Interface).
As shown in Figure 3.1.3, the front panel is provided with a liquid crystal display (LCD), light
emitting diodes (LED), operation keys, VIEW and RESET keys, monitoring jacks and an
RS232C connector.
LCD
The LCD screen, with a 2-line, 16-character display and back-light, provides the user with
information of the relay interior such as records, statuses and settings. The LCD screen is
normally unlit, but pressing the VIEW key will display the digest screen and pressing any key
other than VIEW and RESET will display the menu screen.
These screens are turned off by pressing the RESET key or the END key. If any display is left
for 5 minutes or longer without operation, the back-light will go off.
LED
There are 6 LED displays. The signal labels and LED colors are defined as follows:
Label Color Remarks
IN SERVICE Green Lit when the relay is in service.
TRIP Red Lit when trip command is issued.
ALARM Red Lit when a failure is detected.
TESTING Red Lit when test condition is set.
(LED1) Red User configurable
(LED2) Red User configurable
Operation keys
The operation keys are used to display records, statuses, and setting values on the LCD, as well as
⎯ 27 ⎯
6 F 2 S 0 7 9 0
to input or change setting values. The functions of each operation key are as follows:
c , , , : Used to move lines displayed on an LCD screen. Keys and are also
used to enter numerical values.
d CANCEL : Used to cancel entries or return to the upper (previous) screen.
e END : Used to end entering operation, or return to the upper (previous) screen or
turn off the display.
f ENTER : Used to store or establish entries.
Monitoring jacks
The two monitoring jacks A and B and their respective LEDs can be used when the test mode is
selected on the LCD screen. By selecting the signal to be observed from the "Signal List" (See
Appendix B) and setting it on the screen, the signal can be displayed on LED A or LED B, or by
using an oscilloscope via the monitoring jacks.
RS232C connector
The RS232C connector is a 9-way D-type connector for serial RS232C connection with a local
personal computer.
⎯ 28 ⎯
6 F 2 S 0 7 9 0
RS232C port
This connector is a standard 9-way D-type connector for serial port RS232C transmission and is
mounted on the front panel. By connecting a personal computer using this connector or via
modems and a telephone line, setting operation and display functions can be performed on the
personal computer.
RS485 port
The RS485 port is used for the RSM (Remote Setting and Monitoring system) via the protocol
converter G1PR2 and IEC60870-5-103 communication via BCU/RTU (Bay Control Unit /
Remote Terminal Unit) to connect between relays and to construct a network communication
system. (See Figure 4.4.1 in Section 4.4.)
One or two (dual) RS485 ports (COM1 and COM2) are provided on the rear of the relay as shown
in Figure 4.1.1 and Appendix F.
IRIG-B port
The IRIG-B port collects serial IRIG-B format data from the external clock to synchronise the
relay calendar clock. The IRIG-B port is isolated from the external circuit by using a
photo-coupler. A BNC connector is used as the input connector.
This port is provided on the back of the relay and Figure 4.1.1 shows the location of this
connector. The rated voltage level of the signal is from 2 to 8 Vpeak (4 to 16 Vpeak-to-peak).
TB2
TB1
TB3
RS485 CN1
connection IRIG BNC
terminal E
connector
Rear view
Figure 4.1.1 Locations of RS485 Port and IRIG Port
⎯ 29 ⎯
6 F 2 S 0 7 9 0
V d ∗ ∗ ∗ . ∗ V
D I F - A B C
T r i p
E r r :
To clear the latched indications (latched LEDs, LCD screen of Latest fault), press RESET key
for 3 seconds or more.
For any display, the back-light is automatically turned off after five minutes.
Displays in tripping
If a fault occurs and a tripping command is output when the LCD is off, the red "TRIP" LED and
other configurable LED if signals assigned to trigger by tripping
Press the VIEW key to scroll the LCD screen to read the rest of messages.
Press the RESET key to turn off the LEDs and LCD display.
Notes:
1) When configurable LEDs (LED1 and LED2) are assigned to latch signals by trigger of tripping,
press the RESET key more than 3s until the LCD screens relight. Confirm turning off the
configurable LEDs. Refer to Table 4.2.1 Step 1.
2) Then, press the RESET key again on the "Latest fault" screen in short period, confirm turning
off the "TRIP" LED. Refer to Table 4.2.1 Step 2.
3) When only the "TRIP" LED is go off by pressing the RESET key in short period, press the
RESET key again to reset remained LEDs in the manner 1) on the "Latest fault" screen or
other digest screens. LED1 and LED2 will remain lit in case the assigned signals are still active
state.
⎯ 30 ⎯
6 F 2 S 0 7 9 0
When any of the menu screens is displayed, the VIEW and RESET keys do not function.
To return from menu screen to the digest "Latest fault" screen, do the following:
• Return to the top screen of the menu by repeatedly pressing the END key.
• Press the VIEW key to display the digest "Latest fault" screen.
If the automatic supervision function detects a failure while the LCD is off, the
"Auto-supervision" screen is displayed automatically, showing the location of the failure, and the
"ALARM" LED lights.
Press the VIEW key to display other digest screens in turn including the "Metering" and "Latest
fault" screens.
Press the RESET key to turn off the LEDs and LCD display. However, if the failure continues,
the "ALARM" LED remains lit.
After recovery from a failure, the "ALARM" LED and "Auto-supervision" display turn off
automatically.
If a failure is detected while any of the screens is displayed, the current screen remains displayed
and the "ALARM" LED lights.
Notes:
1) When configurable LEDs (LED1 and LED2) are assigned to latch signals by issuing an alarm,
press the RESET key more than 3s until all LEDs reset except "IN SERVICE" LED.
2) When configurable LED is still lit by pressing RESET key in short period, press RESET
key again to reset remained LED in the above manner.
3) LED1 and LED2 will remain lit in case the assigned signals are still active state.
⎯ 31 ⎯
6 F 2 S 0 7 9 0
While any of the menu screens is displayed, the VIEW and RESET keys do not function. To
return to the digest "Auto-supervision" screen, do the following:
• Return to the top screen of the menu by repeatedly pressing the END key.
Figure 4.2.1 shows the menu hierarchy in the GRB150. The menu has five sub-menus, "Record",
"Status", "Set. (view)", "Set. (change)", and "Test". For details of the menu hierarchy, see
Appendix D.
⎯ 32 ⎯
6 F 2 S 0 7 9 0
Status Metering
Binary I/O
Ry element
Time synch.
Clock adjust.
LCD contrast
⎯ 33 ⎯
6 F 2 S 0 7 9 0
Record
In the "Record" menu, the fault record, event record and disturbance record can be displayed or
erased.
Status
The "Status" menu displays the power system quantities, binary input and output status, relay
measuring element status, signal source for time synchronisation (IRIG-B, RSM or
IEC60870-5-103) and adjusts the clock and LCD contrast.
Set. (view)
The "Set. (view)" menu displays the relay version, description, relay address and baud rate in
RSM or IEC60870-5-103 communication, the current settings of record, status, protection, binary
inputs, configurable binary outputs and the configurable LEDs.
Set. (change)
The "Set. (change)" menu is used to change the settings of password, description, relay address
and baud rate in RSM or IEC60870-5-103 communication, record, status, protection, binary
inputs, configurable binary outputs and configurable LEDs.
Since this is an important menu and is used to change settings related to relay tripping, it has a
password security protection.
Test
The "Test" menu is used to set testing switches, to forcibly operate binary output relays and to
observe the binary signals in the logic circuit.
When the LCD is off, press any key other than the VIEW and RESET keys to display the top
"MENU" screen and then proceed to the relay menus.
M E N U
• R e c o r d
• S t a t u s
• S e t . ( v i e w )
• S e t . ( c h a n g e )
• T e s t
To display the "MENU" screen when the digest screen is displayed, press the RESET key to
turn off the LCD, then press any key other than the VIEW and RESET keys.
Press the END key when the top screen is displayed to turn off the LCD.
An example of the sub-menu screen is shown below. The top line shows the hierarchical layer.
The last item is not displayed for all the screens. "/4" displayed on the far left means that the
screen is in the fourth hierarchical layer, while " " or " " displayed on the far right shows that
upper or lower lines exist.
To move the cursor downward or upward for setting or for viewing other lines not displayed on
the window, use or key.
⎯ 34 ⎯
6 F 2 S 0 7 9 0
/ 4 S c h e m e s w
T r i p 1 _
O f f / O n
V d e r r 1 _
O f f / O n
To return to the higher screen or move from the right side screen to the left side screen in
Appendix D, press the END key.
The CANCEL key can also be used to return to the higher screen but it must be used carefully
because it may cancel entries made so far.
To move between screens of the same hierarchical depth, first return to the higher screen and then
move to the lower screen.
The sub-menu of "Record" is used to display fault records, event records and disturbance records.
# 1 1 6 / O c t / 1 9 9 7
1 8 : 1 3 : 5 7 . 0 3 1
# 2 2 0 / S e p / 1 9 9 7
1 5 : 2 9 : 2 2 . 1 0 1
# 3 0 4 / J u l / 1 9 9 7
1 1 : 5 4 : 5 3 . 2 9 9
# 4 2 8 / F e b / 1 9 9 7
0 7 : 3 0 : 1 8 . 4 1 2
• Move the cursor to the fault record line to be displayed using the and keys and press
the ENTER key to display the details of the fault record.
⎯ 35 ⎯
6 F 2 S 0 7 9 0
/ 3 F . r e c o r d # 1
1 6 / O c t / 1 9 9 7
1 8 : 1 3 : 5 7 . 0 3 1
D I F - A B C
T r i p
P r e f a u l t v a l u e s
V d a ∗ ∗ ∗ . ∗ V
V d b ∗ ∗ ∗ . ∗ V
V d c ∗ ∗ ∗ . ∗ V
F a u l t v a l u e s
V d a ∗ ∗ ∗ . ∗ V
V d b ∗ ∗ ∗ . ∗ V
V d c ∗ ∗ ∗ . ∗ V
The lines which are not displayed in the window can be displayed by pressing the and
keys.
• Press the END (= Y) key to clear all the fault records stored in non-volatile memory.
If all fault records have been cleared, the "Latest fault" screen of the digest screens is not
displayed.
1 6 / O c t / 1 9 9 7
T r i p O n
1 6 / O c t / 1 9 9 7
V d e r r O n
1 6 / O c t / 1 9 9 7
R l y . c h a n g e
The time is displayed by pressing the key.
⎯ 36 ⎯
6 F 2 S 0 7 9 0
/ 3 E . r e c o r d
1 8 : 1 3 : 5 8 . 2 5 5
T r i p O n
1 8 : 1 3 : 5 8 . 0 2 8
V d e r r O n
1 8 : 1 3 : 5 8 . 5 2 8
R l y . c h a n g e
Press the key to return the screen with date.
The lines which are not displayed in the window can be displayed by pressing the and keys.
• Press the END (= Y) key to clear all the event records stored in non-volatile memory.
# 1 1 6 / O c t / 1 9 9 7
1 8 : 1 3 : 5 7 . 4 0 1
# 2 2 0 / S e p / 1 9 9 7
1 5 : 2 9 : 2 2 . 3 8 8
# 3 0 4 / J u l / 1 9 9 7
1 1 : 5 4 : 5 3 . 4 4 4
# 4 2 8 / F e b / 1 9 9 7
0 7 : 3 0 : 1 8 . 8 7 6
The lines which are not displayed in the window can be displayed by pressing the and
⎯ 37 ⎯
6 F 2 S 0 7 9 0
keys.
• Press the END (= Y) key to clear all the disturbance records stored in non-volatile
memory.
From the sub-menu of "Status", the following status condition can be displayed on the LCD and is
updated every second:
Metering data of the protected line
Status of binary inputs and outputs
Status of relay elements
Status of time synchronisation source
The user can also adjust the time of the internal clock and the LCD contrast in this sub-menu.
/ 2 M e t e r i n g
V d a ∗ ∗ ∗ . ∗ V
V d b ∗ ∗ ∗ . ∗ V
V d c ∗ ∗ ∗ . ∗ V
(Model 201)
⎯ 38 ⎯
6 F 2 S 0 7 9 0
• Select "Status" on the top "MENU" screen to display the "Status" screen.
• Select "Binary I/O" to display the binary inputs and outputs status.
/ 2 B i n a r y I / O
I P [ 0 ]
O P 1 [ 0 0 ]
O P 2 [ 0 0 0 0 0 0 0 ]
[ ]
Input (IP) BI1 — — — — — — —
Output (OP1) TP-1 TP-2 — — — — — —
Output (OP2) BO1 BO2 BO3 BO4 BO5 BO6 FAIL —
Line 1 shows the binary input status. BI1 corresponds to a binary input signal. For the binary
input signal, see Appendix F. The status is expressed with logical level "1" or "0" at the
photo-coupler output circuit.
Lines 2 and 3 show the binary output statuses. TP-1 and TP-2 of line 2 correspond to the tripping
command outputs. FAIL of line 3 corresponds to the relay failure output. Other outputs expressed
with BO1 to BO6 are configurable. The status of these outputs is expressed with logical level "1"
or "0" at the input circuit of the output relay driver. That is, the output relay is energised when the
status is "1".
To display all the lines, press the and keys.
Model 201:
/ 2 R y e l e m e n t
[ 0 0 0 0 0 0 ]
Model 201:
[ ]
A B C A B C
DIF, DIFSV
DIF DIFSV
⎯ 39 ⎯
6 F 2 S 0 7 9 0
This shows the operation status of differential elements and the supervisory element.
The status of each element is expressed with logical level "1" or "0". Status "1" means the element
is in operation.
⎯ 40 ⎯
6 F 2 S 0 7 9 0
is displayed on the top line and the adjustment is discarded. Adjust again.
• Press the or key to adjust the contrast. The screen becomes dark by pressing the
key and light by pressing the key.
The sub-menu "Set. (view)" is used to view the settings set in the sub-menu "Set. (change)".
The following items are displayed:
Relay version
Description
Relay address and baud rate in the RSM (relay setting and monitoring system) or
IEC60870-5-103 communication
Recording setting
Status setting
Protection setting
Binary input setting
Binary output setting
LED setting
⎯ 41 ⎯
6 F 2 S 0 7 9 0
• S e r i a l N o .
• S o f t w a r e
• Select "Relay type" to display the relay type form and model number.
G R B 1 5 0 - 2 0 1 B - 1 2
- 3 0
4.2.5.2 Description
• Select "Description" to display the "Description" screen.
/ 2 D e s c r i p t i o n
• P l a n t n a m e
• D e s c r i p t i o n
4.2.5.3 Settings
The "Comms", "Record", "Status", "Protection", "Binary I/O", "Binary O/P" and "LED" screens
display the current settings input using the "Set. (change)" sub-menu.
The "Set. (change)" sub-menu is used to make or change settings for the following items:
Password
Description
Relay address and baud rate in the RSM or IEC60870-5-103 communication
Recording
Status
Protection
Binary input
Binary output
LED
All of the above settings except the password can be seen using the "Set. (view)" sub-menu.
⎯ 42 ⎯
6 F 2 S 0 7 9 0
- Numerical values
A selected item
If a screen below is displayed, perform the settings as follows.
The cursor can be moved to upper or lower lines within the screen by pressing the and
keys. If a setting (change) is not required, skip the line with the and keys.
/ 1 S e t . ( c h a n g e)
• P a s s w o r d
• D e s c r i p t i o n
• C o m m s
• R e c o r d
• S t a t u s
• P r o t e c t i o n
• B i n a r y I / P
• B i n a r y O / P
• L E D
A text string
Text strings are entered under "Plant name" or "Description" screen.
/ 2 D e s c r i p t i o n
• P l a n t n a m e
• D e s c r i p t i o n
To select a character, use keys , , and to move the blinking cursor down, left, up and
right. "→" and "←" on each of lines 4, 8 and 10 indicate a space and backspace, respectively. A
maximum of 22 characters can be entered within the brackets.
A B C D E F G
H I L K L M N
O P Q R S T U
V W X Y Z ←→
a b c d e f g
h i j k l m n
o p q r s t u
v w x y z ←→
0 1 2 3 4 5 6
7 8 9 ←→
( ) [ ] @_ {
} ∗ / + − < =
> ! “ # $ %&
‘ : ; , . ˆ `
• Set the cursor position in the bracket by selecting "→" or "←" and pressing the ENTER
key.
• Move the blinking cursor to a selecting character.
⎯ 43 ⎯
6 F 2 S 0 7 9 0
• Press the ENTER key to enter the blinking character at the cursor position in the
brackets.
• Press the END key to confirm the entry and return to the upper screen.
To correct the entered character, do either of the following:
• Discard the character by selecting "←" and pressing the ENTER key and enter the new
character.
• Discard the whole entry by pressing the CANCEL key and restart the entry from the first
step.
Numerical values
When a screen shown below is displayed, perform the settings as follows:
The number to the left of the cursor shows the current setting or default setting set at shipment.
The cursor can be moved to the upper or lower lines within the screen by pressing the and
keys. If a setting (change) is not required, skip the line with the and keys.
/ 6 P r o t . e l e m e n t
D I F V
1 0 _
D I F S V V
5 _
T V D S V s
0 . 5 0 _
D I F C C
1 . 0 0 _
T C L P s
0 . 0 1 _
T C L E s
0 . 0 0 _
T C L R s
0 . 0 0 _
• Move the cursor to a setting line.
• Press the or key to set a desired value. The value is up or down by pressing the or
key.
• Press the ENTER key to confirm the entry.
• After completing the setting on the screen, press the END key to return to the upper
screen.
To correct the entered numerical value, do the following.
• If it is before pressing the ENTER key, press the CANCEL key and enter the new
numerical value.
• If it is after pressing the ENTER key, move the cursor to the correcting line by pressing
the and keys and enter the new numerical value.
Note: If the CANCEL key is pressed after any of the entry is confirmed by pressing the ENTER
key, all the entries made so far on the screen concerned are canceled and screen returns to the
⎯ 44 ⎯
6 F 2 S 0 7 9 0
upper one.
• When the screen is displayed, press the ENTER key to start operation using the new
settings, or press the CANCEL key to correct or cancel the entries. In the latter case, the
screen turns back to the setting screen to enable re-entries. Press the CANCEL key to
cancel entries made so far and to turn to the "Set. (change)" sub-menu.
4.2.6.2 Password
For the sake of security of setting changes, password protection can be set as follows:
• Select "Set. (change)" on the main "MENU" screen to display the "Setting change" screen.
• Select "Password" to display the "Password" screen.
• Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
I n p u t [ _ ]
0 1 2 3 4 5 6 7 8 9 ←
• For confirmation, enter the same 4-digit number in the brackets after "Retype".
R e t y p e [ _ ]
0 1 2 3 4 5 6 7 8 9 ←
• Press the END key to display the confirmation screen. If the retyped number is different
from that first entered, the following message is displayed on the bottom of the "Password"
screen before returning to the upper screen.
"Unmatch password!"
Re-entry is then requested.
Password trap
After the password has been set, the password must be entered in order to enter the setting change
screens.
If "Set. (change)" is entered on the top "MENU" screen, the password trap screen "Password" is
displayed. If the password is not entered correctly, it is not possible to move to the "Set. (change)"
sub-menu screens.
P a s s w o r d [ _ ]
0 1 2 3 4 5 6 7 8 9 ←
⎯ 45 ⎯
6 F 2 S 0 7 9 0
4.2.6.3 Description
To enter the plant name and other data, do the following. These data are attached to records.
• Select "Set. (change)" on the main "MENU" screen to display the "Set. (change)" screen.
• Select "Description" to display the "Description" screen.
/ 2 D e s c r i p t i o n
• P l a n t n a m e
• D e s c r i p t i o n
• To enter the plant name, select "Plant name" on the "Description" screen.
To enter special items, select "Description" on the "Description" screen.
• Enter the text string.
The plant name and special items entered are viewed with the "Set. (view)" sub-menu and
attached to disturbance records when they are displayed on a local or a remote PC.
4.2.6.4 Communication
If the relay is linked with RSM (relay setting and monitoring system) or IEC60870-5-103
communication, the relay address must be set. Do this as follows:
Note: The settings related to IEC60870-5-103 communication are available for the relay with dual
RS485 port.
• Select "Set. (change)" on the main "MENU" screen to display the " Set. (change)" screen.
• Select "Comms" to display the "Comms" screen.
/ 2 C o m m s
• A d d r . / P a r a m .
• S w i t c h
• Select "Addr./Param." on the "Comms" screen to enter the relay address number.
/ 3 A d d r . / P a r a m .
H D L C
1 _
I E C
2
• Enter the relay address number on "HDLC" line for RSM or "IEC" line for
IEC60870-5-103 and press the ENTER key.
⎯ 46 ⎯
6 F 2 S 0 7 9 0
I E C B R 1
9 . 6 / 1 9 . 2
I E C B L K 0
N o r m a l / B l o c k e d
<IECBR>
This line is to select the baud rate when the IEC60870-5-103 system is applied.
<IECBLK>
Select 1 (=Blocked) to block the monitor direction in the IEC60870-5-103 communication.
T r i p 3 3 _
N / O / R / B
V d e r r 3 3 _
N / O / R / B
I n d . r e s e t 3 3 _
N / O / R / B
R e l a y f a i l 3 3 _
N / O / R / B
C o l d l o a d
N / O / R / B
S y s . c h a n g e 1 1 _
N / O
R l y . c h a n g e 1 1 _
N / O
G r p . c h a n g e 1 1 _
N / O
• Enter 0 or 1 or 2 or 3 and press the ENTER key. Repeat this for all events.
⎯ 47 ⎯
6 F 2 S 0 7 9 0
T i m e s
2 . 0 _
T R I P 1 _
O f f / O n
V d e r r 1 _
O f f / O n
• Enter 1 to use as a starter.
• If the selected switch is not used as a starter, enter 0.
4.2.6.6 Status
To set the status display described in Section 4.2.4, do the following:
Select "Status" on the "Set. (change)" sub-menu to display the "Status setting" screen.
/ 2 S t a t u s
• T i m e s y n c
• T i m e z o n e
T i m e s y n c 1 _
⎯ 48 ⎯
6 F 2 S 0 7 9 0
O f f / I R I / R S M / I E C
G M T h r s
+ 9
• Enter the difference between GMT and local time from –12 to +12 and press the ENTER
key.
4.2.6.7 Protection
The GRB150 can have 4 setting groups for protection in order to accommodate changes in the
operation of the power system, one setting group is assigned active. To set protection, do the
following:
• Select "Protection" on the "Set. (change)" screen to display the "Protection" screen.
/ 2 P r o t e c t i o n
• C h a n g e a c t . g p .
• C h a n g e s e t
• C o p y g p .
⎯ 49 ⎯
6 F 2 S 0 7 9 0
• Select the group number to change the settings and press the ENTER key.
/ 4 G r o u p ∗
• P a r a m e t e r
• T r i p
V D C H K 1 _
O f f / O n
S V C N T 0
A L M & B L K / A L M
I N D . R 1
O f f / O n
C L E N 0
O f f / F 1 / F 2
<VDCHK>
• Enter 1 to perform the differential voltage supervision or enter 0 if you do not need to
perform it, and press the ENTER key.
⎯ 50 ⎯
6 F 2 S 0 7 9 0
<SVCNT>
• Enter 0 (= ALM&BLK) to output an alarm and to block the trip function by the differential
voltage monitoring.
<IND.R>
• Enter 1 (= On) to use BI1 for the indication reset.
• Enter 0 (= Off) not to use BI1 for the indication reset.
<CLEN>
• Enter 1 (= F1) to use BI1 for the function 1 of the cold load protection.
• Enter 2 (= F2) to use BI1 for the function 2 of the cold load protection.
• Enter 0 (= Off) not to use BI1 for the cold load protection.
• Press the END key to return to the "Trip" screen.
D I F V
1 0 _
D I F S V V
5 _
T V D S V s
0 . 5 0 _
<DIF>
• Enter the numerical value and press the ENTER key.
<DIFSV>
• Enter the numerical value and press the ENTER key.
<TVDSV>
• Enter the numerical value and press the ENTER key.
• After setting, press the END key to return to the "Trip" screen.
A _
B _
⎯ 51 ⎯
6 F 2 S 0 7 9 0
• Enter the group number to be copied in line A and press the ENTER key.
• Enter the group number to be overwritten by the copy in line B and press the ENTER
key.
B I S W1 1 _
N o r m / I n v
Note: The setting is required for all the binary outputs. If any of the binary outputs are not used, enter
0 to logic gates #1 to #4 in assigning signals.
• Enter the output relay number (BO number) and press the ENTER key to display the
"Set. (BO∗∗)" screen.
/ 3 S e t . ( B O ∗ ∗ )
• L o g i c / R e s e t
• F u n c t i o n s
⎯ 52 ⎯
6 F 2 S 0 7 9 0
L o g i c 0 _
O R / A N D
R e s e t 0
I n s t / D e l / L a t c h
• Enter 0 (= OR) or 1 (= AND) to use an OR gate or AND gate and press the ENTER key.
• Enter 0 (= Instantaneous) or 1 (= Delayed) or 2 (=Latched) to select the reset timing and
press the ENTER key.
Assigning signals
• Select "Functions" on the "Set. (BO∗∗)" screen to display the "Functions" screen.
/ 4 F u n c t i o n s
I n # 1
2 1 _
I n # 2
4 _
I n # 3
6 7 _
I n # 4
0 _
• Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix B. Do not assign the signal numbers 120 to 125 (signal names: "BO1
OP" to "BO6 OP").
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).
Repeat this process for the outputs to be configured.
4.2.6.10 LEDs
Two LEDs of the GRB150 are user-configurable. A configurable LED can be programmed to
indicate the OR/AND combination of a maximum of 4 elements. One of the signals listed in
Appendix B can be assigned to each LED as follows:
• Select "LED" on the "Set. (change)" screen to display the "LED" screen.
/ 2 L E D
• L E D 1
• L E D 2
Note: The setting is required for all the LEDs. If any of the LEDs are not used, enter 0 to logic
gates #1 to #4 in assigning signals.
• Select the LED number and press the ENTER key to display the "LED∗" screen.
/ 3 L E D ∗
• L o g i c / R e s e t
• F u n c t i o n s
⎯ 53 ⎯
6 F 2 S 0 7 9 0
L o g i c 0 _
O R / A N D
R e s e t 0
I n s t / L a t c h
• Enter 0 (= OR) or 1 (= AND) to use an OR gate or AND gate and press the ENTER key.
• Enter 0 (= Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER
key.
• Press the END key to return to the "LED∗" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.
Assigning signals
• Select "Functions" on the "LED∗" screen to display the "Functions" screen.
/ 5 F u n c t i o n s
I n # 1
2 1 _
I n # 2
1 1
I n # 3
2 4
I n # 4
0
• Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix B.
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).
4.2.7 Testing
The sub-menu "Test" provides such functions as disabling the automatic monitoring function,
forced operation of binary outputs, and logic signal observation.
⎯ 54 ⎯
6 F 2 S 0 7 9 0
• Select "Test" on the top "MENU" screen to display the "Test" screen.
/ 1 T e s t
• S w i t c h
• B i n a r y O / P
• L o g i c c i r c u i t
A . M . F . 1 _
O f f / O n
C L P T S T
O f f / N - C L / C L
I E C T S T 0
O f f / O n
• Enter 0 or 1 to disable the A.M.F. or not and press the ENTER key for each switch.
• Enter 0(=Off) to disable the cold load protection, or enter 1(=N-CL) forcibly to set to
“No-cold load condition” or enter 2(=CL) forcibly to set to “Cold load condition”. And
press the ENTER key.
• Enter 1(=On) for IECTST to transmit ‘test mode’ to the control system by
IEC60870-5-103 communication when testing the local relay, and press the ENTER key.
• Press the END key to return to the "Test" screen.
T P - 1 0 _
D i s a b l e / E n a b l e
T P - 2 0 _
D i s a b l e / E n a b l e
B O 1 0 _
D i s a b l e / E n a b l e
B O 2 0 _
D i s a b l e / E n a b l e
B O 3 0 _
D i s a b l e / E n a b l e
B O 4 0 _
D i s a b l e / E n a b l e
B O 5 0 _
D i s a b l e / E n a b l e
B O 6 0 _
D i s a b l e / E n a b l e
F A I L 0 _
D i s a b l e / E n a b l e
⎯ 55 ⎯
6 F 2 S 0 7 9 0
• Enter 1 and press the ENTER key to operate the output relay(s) forcibly.
• After completing the entries, press the END key. Then the LCD displays the screen
shown below.
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the assigned output relay(s).
• Press the CANCEL key to return to the upper "Binary O/P" screen.
• Enter a signal number to be observed at monitoring jack A and press the ENTER key.
• Enter the other signal number to be observed at monitoring jack B and press the ENTER
key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.
⎯ 56 ⎯
6 F 2 S 0 7 9 0
Twisted-pair
cable
⎯ 57 ⎯
6 F 2 S 0 7 9 0
The calendar clock can run locally or be synchronised with the external IRIG-B time standard
signal, RSM or IEC clock. This can be selected by setting.
If it is necessary to synchronise with the IRIG-B time standard signal, it is possible to transform
GMT to the local time by setting.
When the relays are connected to the RSM system as shown in Figure 4.4.1, the calendar clock of
each relay is synchronised with the RSM clock. If the RSM clock is synchronised with the
external time standard (GPS clock etc.), then all the relay clocks are synchronised with the
external time standard.
⎯ 58 ⎯
6 F 2 S 0 7 9 0
5. Installation
5.1 Receipt of Relays
When relays are received, carry out the acceptance inspection immediately. In particular, check
for damage during transportation, and if any damage is found, contact the vendor.
Check that the following accessories are attached.
• 3 pins for the monitoring jack, packed in a plastic bag.
Always store the relays in a clean, dry environment.
CAUTION
• Before removing the relay unit, ensure that you are at the same electrostatic potential as the
equipment by touching the case.
• Use the handle to draw out the relay unit. Avoid touching the electronic components,
printed circuit board or connectors.
• Do not pass the relay unit to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
⎯ 59 ⎯
6 F 2 S 0 7 9 0
• Place the relay unit on an anti-static surface, or on a conducting surface which is at the
same potential as yourself.
• Do not place the relay unit in polystyrene trays.
It is strongly recommended that detailed investigations on electronic circuitry should be carried
out in a Special Handling Area such as described in the aforementioned IEC 60747.
⎯ 60 ⎯
6 F 2 S 0 7 9 0
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by monitoring which
circuits function when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests
These tests are performed for the following functions that are fully software-based.
Measuring elements
Metering and recording
Human interface
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other external
equipment.
⎯ 61 ⎯
6 F 2 S 0 7 9 0
6.2 Cautions
6.2.1 Safety Precautions
CAUTION
• The relay rack is provided with an earthing terminal.
Before starting the work, always make sure the relay rack is earthed.
• When connecting the cable to the back of the relay, firmly fix it to the terminal block and
attach the cover provided on top of it.
• Before checking the interior of the relay, be sure to turn off the power.
Failure to observe any of the precautions above may cause electric shock or malfunction.
CAUTION
• When testing the relay, house it in the case and test it.
• While the power is on, do not draw out/insert the relay unit.
• Before turning on the power, check the followings:
- Make sure the polarity and voltage of the power supply are correct.
- Make sure the CT circuit is not open.
• If dc power has not been supplied to the relay for two days or more, then it is recommended
that all fault records, event records and disturbance records be cleared soon after restoring
the power. This is because the back-up RAM may have discharged and may contain
uncertain data.
• Be careful that the relay is not damaged due to an overcurrent or overvoltage.
• If settings are changed for testing, remember to reset them to the original settings.
Failure to observe any of the precautions above may cause damage or malfunction of the relay.
⎯ 62 ⎯
6 F 2 S 0 7 9 0
6.3 Preparations
Test equipment
The following test equipment is required for the commissioning tests.
1 Single-phase voltage source
1 DC power supply
1 AC voltmeter
1 DC voltmeter
1 Time counter, precision timer
1 PC (not essential)
Relay settings
Before starting the tests, it must be specified whether the tests will use the user’s settings or the
default settings.
Relay ratings
Check that the items described on the nameplate on the front of the relay conform to the user’s
specification. The items are: relay type and model, AC voltage, current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC
When using a local PC, connect it with the relay via the RS232C port on the front of the relay.
RSM100 software is required to run the PC.
For the details, see the separate manual "PC INTERFACE RSM100".
⎯ 63 ⎯
6 F 2 S 0 7 9 0
This test ensures that the LCD, LEDs and keys function correctly.
LCD display
• Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD will display the "Err: " screen when the DC voltage is applied.
• Press the RESET key and check that black dots appear on the whole screen.
LED display
• Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
• Press the RESET key and check that remaining five LEDs are lit in red.
, , and keys
• Press any key when the LCD is off and check that the LCD displays the "MENU" screen.
Press the END key to turn off the LCD.
• Repeat this for all keys.
⎯ 64 ⎯
6 F 2 S 0 7 9 0
GRB150
TB3 -B3
BI1
-A4
DC + TB3 -A5
power
supply − -B5
This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers
and output relays. Operation of the output contacts is monitored at the output terminal. The output
contact and corresponding terminal number are shown in Appendix F.
• Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. The LCD will
display the name of the output relay.
/ 2 B i n a r y O / P
T P - 1 0 _
D i s a b l e / E n a b l e
T P - 2 0 _
D i s a b l e / E n a b l e
B O 1 0 _
D i s a b l e / E n a b l e
B O 2 0 _
D i s a b l e / E n a b l e
B O 3 0 _
⎯ 65 ⎯
6 F 2 S 0 7 9 0
• After completing the entries, press the END key. The LCD will display the screen shown
below. If 1 is entered for all the output relays, the following forcible operation can be
performed collectively.
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the output relays forcibly.
This test can be performed by applying the checking voltages to the AC input circuits and
verifying that the values applied coincide with the values displayed on the LCD screen.
The testing circuit is shown in Figure 6.4.2. A single-phase voltage source is required.
GRB150
EB-10∗
V TB1-1 TB2-1 TB1 -1
-2 Va -2 Va
Single-phase -2
voltage -3 -3
source Vb -3
-4 -4 Vb
-5 -4
Vc -5
-6 -6 -5
Vc
-8 -6
+ TB3 -A5
DC
power
supply − -B5
⎯ 66 ⎯
6 F 2 S 0 7 9 0
Measuring element characteristics are realised by software, so it is possible to verify the overall
characteristics by checking representative points.
Operation of the element under test is observed by the binary output signal at monitoring jacks A
or B or by the LED indications above the jacks. In any case, the signal number corresponding to
each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
/ 2 L o g i c
c i r c u i t
T e r m A
1 _
T e r m B
4 8 _
When a signal number is entered for the Term A line, the signal is observed at monitoring jack A
and when entered for the Term B line, it is observed at monitoring jack B.
Note: The voltage level at the monitoring jacks is +5V for logic level "1" and less than 0.1V for
logic level "0".
CAUTION
• Use test equipment with more than 1 kΩ of internal impedance when observing the output
signal at the monitoring jacks.
• Do not apply an external voltage to the monitoring jacks.
• Do not leave the A or B terminal shorted to 0V terminal for a long time.
In case of a three-phase element, it is sufficient to test for a representative phase. The A-phase
element is selected hereafter.
⎯ 67 ⎯
6 F 2 S 0 7 9 0
-3
A
-4 Monitoring
jack
-8 -5 0V
-6
DC + TB3 -A5
power
supply − -B5
+
DC
voltmeter
−
*(Note) EB-101: single-phase, EB-102: three-phase. The terminal No. shown in the parentheses are in the case of EB-102.
• Select "Logic circuit" on the "Test" sub-menu screen to display the "Logic circuit" screen.
• Enter signal number 11 to observe the DIF-A operation at monitoring jack A and press the
ENTER key.
• Apply a test voltage and change the magnitude of the voltage applied and measure the
value at which the element operates.
Check that the measured value is within 10% of the setting value.
⎯ 68 ⎯
6 F 2 S 0 7 9 0
Operating time
The testing circuit is shown in Figure 6.5.2.
GRB150
V EB-10∗
TB1-1 TB1-4 TB1 -1
Single-phase (TB1-1) (TB2-1)
Va
voltage
source TB1-2 TB1-5 -2
(TB1-2) (TB2-2)
A
Monitoring
jack
0V
-8
DC + TB3 -A5
power
supply − -B5
Start
Time
counter
Stop
0V
*(Note) EB-101: single-phase, EB-102: three-phase. The terminal No. shown in the parentheses are in the case of EB-102.
• Select "Logic circuit" on the "Test" sub-menu screen to display the "Logic circuit" screen.
• Enter signal number 14 to observe the DIFSV-A operation at monitoring jack A and press
⎯ 69 ⎯
6 F 2 S 0 7 9 0
In the protection scheme tests, a dynamic test set is required to simulate power system pre-fault,
fault and post-fault conditions.
Tripping is observed with the tripping command output relays TP-1 and 2.
Differential tripping
The tripping should be checked for the voltage which is two times or larger than the minimum
operating voltage DIF. Operating time is measured by the operating time of the tripping
command output relay. It is usually 20ms.
Check that the indications and recordings are correct.
The metering function can be checked while testing the AC input circuit. See Section 6.4.4.
Fault recording can be checked while testing the protection schemes. Open the "Fault records"
screen and check that the descriptions are correct for the fault concerned.
Recording events are listed in Table 3.4.1. The top event is an external event and others are
internal events. Event recording on the external event can be checked by changing the status of
binary input signals. Change the status in the same way as the binary input circuit test (see Section
6.4.2) and check that the description displayed on the "Event Records" screen is correct.
Note: Whether to record or not can be set for each event. Change the status of the binary input signal
after confirming that the related event is set to record. (The default setting enables all the
events to be recorded.)
Some of the internal events can be checked in the protection scheme tests.
Disturbance recording can be checked while testing the protection schemes. The LCD display
only shows the date and time when a disturbance is recorded. Open the "Disturbance records"
screen and check that the descriptions are correct.
Details can be displayed on the PC with the RSM100 software. Check that the descriptions on the
PC are correct. For details on how to obtain disturbance records on the PC, see the RSM100
Manual.
⎯ 70 ⎯
6 F 2 S 0 7 9 0
With the relay connected to the line which is carrying a load current, it is possible to check the
polarity of the current transformer with the metering displays on the LCD screen.
• Open the following "Metering" screen from the "Status" sub-menu.
/ 2 M e t e r i n g
V d ∗ ∗ ∗ . ∗ V
(Model 101)
/ 2 M e t e r i n g
V d a ∗ ∗ ∗ . ∗ V
V d b ∗ ∗ ∗ . ∗ V
V d c ∗ ∗ ∗ . ∗ V
(Model 201)
• Check that the differential voltage Vd or Vda, Vdb and Vdc are sufficiently smaller than
the DIF and DIFSV setting values.
The tripping circuit including the circuit breaker is checked by forcibly operating the output relay
and monitoring the circuit breaker to confirm that it is tripped. Forcible operation of the output
relay is performed on the "Binary O/P " screen of the "Test" sub-menu as described in Section
6.4.3.
Tripping circuit
• Set the breaker to be closed.
• Select "Binary O/P" on the "Test" sub-menu screen to display the "Binary O/P" screen.
TP-1 and -2 are output relays with one normally open contact.
• Enter 1 for TP-1 and press the ENTER key.
• Press the END key. Then the LCD displays the screen shown below.
O p e r a t e ?
E N T E R = Y C A N C E L = N
• Keep pressing the ENTER key to operate the output relay TP-1 and check that the No.1
breaker is tripped.
• Stop pressing the ENTER key to reset the operation.
⎯ 71 ⎯
6 F 2 S 0 7 9 0
6.7 Maintenance
6.7.1 Regular Testing
The relay is almost completely self-supervised. The circuits that can not be supervised are binary
input and output circuits and human interfaces.
Therefore, regular testing is minimised to checking the unsupervised circuits. The test procedures
are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3.
⎯ 72 ⎯
6 F 2 S 0 7 9 0
If no message is shown on the LCD, this means that the failure location is either in the DC power
supply circuit or in the microprocessors.
When a failure is detected by automatic supervision or regular testing, replace the failed relay
unit.
Note: When a failure or an abnormality is detected during the regular test, confirm the following
first:
- Test circuit connections are correct.
- Relay unit is securely inserted in position.
- Correct DC power voltage with correct polarity is applied and connected to the correct
terminals.
- Correct AC inputs are applied and connected to the correct terminals.
- Test procedures comply with those stated in the manual.
If a failure is identified in the relay unit and the user has a spare relay unit, the user can recover the
protection by replacing the failed relay unit.
Repair at the site should be limited to relay unit replacement. Maintenance at the component level
is not recommended.
Check that the replacement relay unit has an identical Model No. and relay version (software type
form) as the removed relay.
The Model No. is indicated on the front of the relay. For the relay version, see Section 4.2.5.1
⎯ 73 ⎯
6 F 2 S 0 7 9 0
RESET RESET
END END
Handle
Pull up handle
Bind screw
After replacing the failed relay unit or repairing failed external circuits, take the following
procedures to put the relay into service.
• Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and
the "ALARM" red LED is not lit.
• Supply the AC inputs and reconnect the trip outputs.
6.7.5 Storage
The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the
storage temperature should be between −25°C and +70°C, but the temperature of 0°C to +40°C is
recommended for long-term storage.
⎯ 74 ⎯
6 F 2 S 0 7 9 0
⎯ 75 ⎯
6 F 2 S 0 7 9 0
⎯ 76 ⎯
6 F 2 S 0 7 9 0
Appendix A
Block Diagram
⎯ 77 ⎯
6 F 2 S 0 7 9 0
Tripping
output relay
0 t
DIF &
TP-1
0.2s (Trip1)
TP-2
0 t
1
&
0.01s
t 0
DIFSV & Alarm
0.5s (VD ERR)
[SVCNT]
+
[VDCHK]
+ "ALM&BLK"
"ON"
Block Diagram of GRB150-101
Tripping
output relay
0 t
A & ≥1 TP-1
0.2s
DIF 0 t
B & TP-2
0.2s
0 t
C &
0.2s
0 t
& 1
0.01s
t 0
A & Alarm
≥1
0.5s (VD ERR)
DIFSV t 0
B &
0.5s
C t 0
&
0.5s
[VDCHK] [SVCNT]
+ +
"ON" "ALM&BLK"
⎯ 78 ⎯
6 F 2 S 0 7 9 0
Appendix B
Signal List
⎯ 79 ⎯
6 F 2 S 0 7 9 0
SIGNAL LIST
No . SIG NAL NAME CO NTENTS No . SIG NAL N AME C O NTENTS No. SIG NAL N AME CO NTENTS
⎯ 80 ⎯
6 F 2 S 0 7 9 0
Appendix C
Binary Output Default Setting List
⎯ 81 ⎯
6 F 2 S 0 7 9 0
201
BO1 VD ERR-A Voltage Differential error 24 0 0 0 0 1
BO2 VD ERR-B Voltage Differential error 25 0 0 0 0 1
BO3 VD ERR-C Voltage Differential error 26 0 0 0 0 1
BO4 TRIP-A Trip signal 21 0 0 0 0 1
BO5 TRIP-B Trip signal 22 0 0 0 0 1
BO6 TRIP-C Trip signal 23 0 0 0 0 1
⎯ 82 ⎯
6 F 2 S 0 7 9 0
Appendix D
Details of Relay Menu and
LCD & Button Operation Instruction
⎯ 83 ⎯
6 F 2 S 0 7 9 0
MENU
xRecord
xStatus
xSet. (view)
xSet. (change)
xTest
/1 Record
xF. record
xE. record
xD. record
/2 E.record /3 E.record
xDisplay
xClear 16/Oct/1997
Refer to Section Ext. trip A On
4.2.3.2.
Clear records?
END=Y CANCEL=N
/2 D.record /3 D.record
xDisplay
xClear #1 16/Oct/1997
Refer to Section 18:13:57.401
4.2.3.3.
Clear records?
END=Y CANCEL=N
a-1
⎯ 84 ⎯
6 F 2 S 0 7 9 0
a-1
/1 Status /2 Metering
xMetering Vda ***.* V
xBinary I/O
/2 Binary I/O
xRelay element
IP [0 ]
xTime sync.
xClock adjust. /2 Ry element
xLCD contrast [000 000 ]
Refer to Section 4.2.4.
/2 Time sync.
*IRIG: Act
/2 12/Nov/1999
22:56:19 [L]
/2 LCD contrast
/1 Set. (view)
xVersion
xDescription
xComms
xRecord
xStatus
xProtection
xBinary I/P
xBinary O/P Refer to Section 4.2.5
xLED
/2 Version GRB150-201B-12
xRelay type -30
xSerial No.
xSoftware ∗∗∗∗∗∗∗∗∗∗∗∗∗∗
∗∗∗∗∗∗
/2 Description
GS1BP1-03-*
xPlant name
xDescription
/2 Comms /3 Addr./Param.
xAddr./Param.
xSwitch
/3 Switch
a-1, b-1
⎯ 85 ⎯
6 F 2 S 0 7 9 0
a-1 b-1
/2 Record /3 E.record
xE.record
xD.record
/3 D.record /4 Time/starter
xTime/starter Time 2.0s
x Scheme sw
/4 Scheme sw
/2 Status /3 Time sync.
xTime sync.
xTime zone
/3 Time zone
GMT +9hrs
/2 Act. gp. =*
xGroup1
xGroup2
xGroup3
xGroup4
/3 Group1
xParameter
xTrip
/4 Parameter ∗∗∗∗∗∗∗∗∗∗∗∗∗∗
xLine name ∗∗∗∗∗∗
/4 Trip /5 Scheme sw
xScheme sw
xProt.element
/5 Prot.element
DIF 10V
/3 Group2
xParameter
/3 Group4
xParameter
a-1 b-1
⎯ 86 ⎯
6 F 2 S 0 7 9 0
a-1 b-1
/2 Binary I/P
BISW1 1 _
Norm/Inv
/2 Binary O/P
BO1 AND, D
( 1, 10, 29, 0)
BO6 AND, D
( 0, 0, 0, 0)
/2 LED
LED1 21
LED2 11
/1 Set.(change)
xPassword
xDescription
: Password trap
xComms
Password [_ ]
xRecord
1234567890←
xStatus
: Confirmation trap
xProtection
xBinary I/O Change settings?
ENTER=Y CANCEL=N
xBinary O/P
xLED
Input [_ ] Retype [_ ]
1234567890← 1234567890←
Refer to Section
4.2.6.2.
/2 Description _
xPlant name ABCDEFG
xDescription
_
Refer to Section
4.2.6.3. ABCDEFG
a-1 b-2
⎯ 87 ⎯
6 F 2 S 0 7 9 0
a-1 b-2
/2 Comms /3 Addr./Param.
xAddr./Param.
xSwitch
Refer to Section /3 Switch
4.2.6.4.
/2 Record /3 E.record
xE.record
xD.record Trip 3 3 _
N/O/R/B
Refer to Section
4.2.6.5.
Grp. change 1 1 _
N/O
/3 D.record /4 Time/Starter
xTime/Starter
xScheme sw
/4 Scheme sw
/2 Protection
xChange act. gp.
xChange set. Refer to Section
xCopy gp. 4.2.6.7.
/3 Change act.
gp.
/3 Act gp.=1
xGroup1
xGroup2
xGroup3
xGroup4
⎯ 88 ⎯
6 F 2 S 0 7 9 0
/4 Group*
xParameter
xTrip
/5 Parameter _
xLine name ABCDEFG
/5 Trip /6 Scheme sw
xScheme sw
xProt.element VDCHK 1 _
Off/On
SVCNT 0 _
ALM&BLK/ALM
IND.R 1 _
Off/On
CLEN 0 _
Off/N-CL/CL
/6 Prot.element
DIF V
10 _
DIFSV V
/4 Group2 5 _
xParameter TVDSV s
0.50 _
/4 Group4 DIFCC
xParameter 1.00 _
TCLP s
/3 Copy A to B 0.01 _
TCLE s
A _ 0.00 _
B _ TCLR s
0.00 _
/2 Binary I/P
BISW1 1 _
Norm/Inv
Refer to Section
4.2.6.8.
a-1, b-2
⎯ 89 ⎯
6 F 2 S 0 7 9 0
a-1, b-2
/1 Test /2 Switch
xSwitch
xBinary O/P A.M.F. 1 _
xLogic circuit Off/On
Refer to Section 4.2.7. CLPTST 0
Off/N-CL/CL
IECTST 0
Off/On
/2 Logic
circuit
TermA
1 _
TermB
100
⎯ 90 ⎯
6 F 2 S 0 7 9 0
MANUAL 1=RECORD
2=EVENT RECORD
PRESS ANY
BUTTON MENU
EXCEPT FOR 2=STATUS
VIEW "VIEW" AND ( DISPLAY ON )
"RESET"
1=METERING
2=BINARY INPUT&OUPUT
1=RELAY VERSION
2=DESCRIPTION
LATEST FAULT * AUTO-
(DISPLAY ON) 3=RSM COMMUNICATION
MODE 2
RELAY 4=RECORD
FAILED ! 5=STATUS
VIEW RESET
ALARM 6=PROTECTION
( LED ON )
7=BINARY INPUT
8=BINARY OUTPUT
AUTO SUPERVISION *
9=LED
(DISPLAY ON)
*. "LATEST FAULT" AND "AUTO
SUPERVISION" SCREEN IS 4=SETTING
DISPLAYED ONLY IF DATA (CHANGE) Same as SETTING (VIEW) menu
IS STORED
VIEW RESET
5=TEST
1=SWITCH
2=BINARY
O
3=LOGIC CIRCUIT
⎯ 91 ⎯
6 F 2 S 0 7 9 0
⎯ 92 ⎯
6 F 2 S 0 7 9 0
Appendix E
Outline of GRB150 and EB-101, -102
• Case Type of GRB150: Flush Mount Type
• EB-101 and EB-102
⎯ 93 ⎯
6 F 2 S 0 7 9 0
IN SERVICE VIEW
TRIP
ALARM
TESTING
25 8
RESET
A B 0V
CAN
CEL ENTER
END
15.6 243.5 32
104
Side view
Front view
4 holes-φ4.5 4 holes-φ5.5
TB2
TB1
TB3
24 9
239
CN1
56
Rear view
102
TB2 TB1
A1 B1
1 2 Panel cut-out
3 4
5 6
TB3
A1 B1
A6 B6
⎯ 94 ⎯
6 F 2 S 0 7 9 0
M4 Ring
terminal
TB1
1
205 226.5
Terminal block
Top view
6-φ5.5 for mounting
TB1
70
225
70
42.5
214.4
234
252
(a) EB-101
M4 Ring
M4 Ring terminal
terminal TB2
TB1 1
1
205 226.5
8
12
TB2
TB1
70
225
70
42.5
362.4
382
400
Front view Side view
(b) EB-102
Note: When mounting varistor units longitudinally, the TB1 should be located in the down side.
⎯ 95 ⎯
6 F 2 S 0 7 9 0
⎯ 96 ⎯
6 F 2 S 0 7 9 0
Appendix F
External Connection
⎯ 97 ⎯
6 F 2 S 0 7 9 0
OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)
EB-101
TB2-A1 BO1 VD ERR ALARM
TB1 -1 TB1 -4 TB1 -1 TRIP - 1 BO2 VD ERR ALARM
TP-1 BO3 VD ERR ALARM
B1
-2 BO4 TRIP ALARM
A2
TB1 -2 TB1 -5 BO5 TRIP ALARM
TP-2 B2 TRIP - 2 BO6 TRIP ALARM
TB1 -8
FRAME EARTH
A5
BO1 B5
A6
BO2 B6
A7
BO3 B7
A8
BO4 B8
A9
BO5 B9
A10
BO6 B10
TB2
(+) A1 B1 TB1
1 2
FAIL TB2-A15 5 6
TB3 -B3
BI1 RELAY FAILURE
B15 TB3
-A4
A1 B1
TB2-A17
COM1-A A6 B6
IRIG-B
A16
COM1-B A18 B18
E
RS485 I/F for RSM
A18
0V
RELAY FAIL.
≧1 TB2-B17
Terminal Block Arrangement (Rear view)
DD FAIL. COM2-A
TB3 -A5 +5Vdc
DC (+) DC-DC B16
COM2-B
SUPPLY -B5 RS485 I/F for IEC103
0V
(-) (Provided with two-port model).
B18
TB3 -A6 0V
-B6
E IRIG-B
CASE EARTH
Note: In AC circuit wiring, the wires of the relay side should be separated from these of the CT side to
avoid the influence of noise.
⎯ 98 ⎯
6 F 2 S 0 7 9 0
BUSBAR
OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)
EB-102 TB2-A1 BO1 VD ERR-A ALARM
A-phase TB1 -1 BO2 VD ERR-B ALARM
TP-1 TRIP - 1
TB1-1 TB2-1 B1 BO3 VD ERR-C ALARM
TB1-2 TB2-2 -2 A2 BO4 TRIP-A ALARM
B-phase TRIP - 2 BO5 TRIP-B ALARM
-3 TP-2 B2 BO6 TRIP-C ALARM
TB1-3 TB2-3
TB1-4 TB2-4 -4
C-phase -5
TB1-5 TB2-5
TB1-6 TB2-6 -6 A5
BO1 B5
TB1-8
FAn FA1
A6
FRAME EARTH
BO2 B6
A7
BO3 B7
A8
BO4 B8
A9
BO5 B9
A10
BO6 B10
TB2
A1 B1 TB1
1 2
(+) 5 6
FAIL TB2-A15 TB3
TB3 -B3 RELAY FAILURE
BI1 A1 B1
B15
-A4
A6 B6
TB2-A17
COM1-A IRIG-B
E
A16 A18 B18
COM1-B
RS485 I/F for RSM
A18
0V Terminal Block Arrangement (Rear view)
RELAY FAIL.
≧1 TB2-B17
DD FAIL. COM2-A
TB3-A5 +5Vdc
DC (+) DC-DC B16
-B5 COM2-B
SUPPLY RS485 I/F for IEC103
0V
(-) (Provided with two-port model).
B18
0V
TB3-A6
-B6
E IRIG-B
CASE EARTH
Note: In AC circuit wiring, the wires of the relay side should be separated from these of the CT side to
avoid the influence of noise.
⎯ 99 ⎯
6 F 2 S 0 7 9 0
⎯ 100 ⎯
6 F 2 S 0 7 9 0
Appendix G
Relay Setting Sheet
1. Relay Identification
2. Busbar parameters
3. Contacts setting
4. Relay setting sheet
⎯ 101 ⎯
6 F 2 S 0 7 9 0
2. Busbar parameters
CT ratio
3. Contacts setting
(1) BO1
BO2
BO3
BO4
BO5
BO6
⎯ 102 ⎯
6 F 2 S 0 7 9 0
⎯ 103 ⎯
6 F 2 S 0 7 9 0
⎯ 104 ⎯
6 F 2 S 0 7 9 0
Appendix H
Commissioning Test Sheet (sample)
1. Relay identification
2. Preliminary check
3. Hardware test
3.1 User interface check
3.2 Binary input/Binary output circuit check
3.3 AC input circuit check
4. Function test
4.1 Differential element DIF test
4.2 Supervisory element DIFSV test
5. Protection scheme test
6. Metering and recording check
7. Conjunctive test
⎯ 105 ⎯
6 F 2 S 0 7 9 0
1. Relay identification
2. Preliminary check
Ratings
CT shorting contacts
DC power supply
Power up
Wiring
Relay inoperative
alarm contact
Calendar and clock
3. Hardware test
⎯ 106 ⎯
6 F 2 S 0 7 9 0
4. Function test
7. Conjunctive test
Scheme Results
On load
Tripping circuit
⎯ 107 ⎯
6 F 2 S 0 7 9 0
⎯ 108 ⎯
6 F 2 S 0 7 9 0
Appendix I
Return Repair Form
⎯ 109 ⎯
6 F 2 S 0 7 9 0
TOSHIBA CORPORATION Fuchu Operations – Industrial and Power Systems & Services
1, Toshiba-cho, Fuchu-shi, Tokyo, Japan
For: Power Systems Protection & Control Department
Quality Assurance Section
Product No.:
Serial No.:
Date:
2. Fault records, event records or disturbance records stored in the relay and relay settings are
very helpful information to investigate the incident.
Please provide relevant information regarding the incident on floppy disk, or fill in the
attached fault record sheet and relay setting sheet.
Fault Record
Date/Month/Year Time / / / : : .
(Example: 04/ Nov./ 1997 15:09:58.442)
Faulty phase:
Prefault values
Vda: V
Vdb: V
Vdc: V
⎯ 110 ⎯
6 F 2 S 0 7 9 0
Fault values
Prefault values
Vda: V
Vdb: V
Vdc: V
3. What was the message on the LCD display at the time of the incident?
⎯ 111 ⎯
6 F 2 S 0 7 9 0
Customer
Name:
Company Name:
Address:
Telephone No.:
Facsimile No.:
Signature:
⎯ 112 ⎯
6 F 2 S 0 7 9 0
Appendix J
Technical Data
⎯ 113 ⎯
6 F 2 S 0 7 9 0
TECHNICAL DATA
Ratings
AC current (In): 1A (fixed)
Frequency: 50Hz or 60Hz
DC power supply: 110Vdc/125Vdc
220Vdc/250Vdc
48Vdc
(Nominal range: −20% and +20% of rated voltage)
AC ripple on DC supply, IEC60255-11: Maximum 12%
DC supply interruption, IEC60255-11
Permissive duration of DC supply voltage interruption to maintain normal operation:
less than 50ms at 110Vdc
Restart time: less than 10s
Overload rating
AC voltage input for varistor unit EB-101 or EB-102:
300V continuous
1kVrms for 0.4s
Burden
DC power supply: less than 10W (quiescent)
less than 15W (operation)
⎯ 114 ⎯
6 F 2 S 0 7 9 0
Communication port
Front communication port (local PC)
Connection: Point to point
Cable type: Multi-core (straight)
Cable length: 15m (max.)
Connector: RS232C 9-way D-type female
Rear communication port (remote PC)
Signal level: RS485
Transmission data rate for RSM system: 64kbps
Connection: Multidrop mode (max. 32 relays)
Connector: Screw terminals
Cable and length: Twisted-pair cable, max. 1200m
Isolation: 2kVac for 1 min.
Contact ratings
Trip contacts:
Make and carry: 5A continuously
30A, 290Vdc for 0.5s (L/R ≥ 10ms)
Break: 0.15A, 290Vdc (L/R=40ms)
Auxiliary contacts:
Make and carry: 4A continuously
10A, 220Vdc for 0.2s (L/R ≥ 5ms)
Break: 0.1A, 220Vdc (L/R=40ms)
Mechanical design
Weight: 5kg
Case color: 2.5Y7.5/1(approximation to Munsell value)
Installation: Flush mounting
⎯ 115 ⎯
6 F 2 S 0 7 9 0
⎯ 116 ⎯
6 F 2 S 0 7 9 0
Appendix K
Symbols Used in Scheme Logic
⎯ 117 ⎯
6 F 2 S 0 7 9 0
Symbols used in the scheme logic and their meanings are as follows:
Signal names
Marked with : Measuring element output signal
Marked with : Binary signal input from or output to the external equipment
Marked with [ ] : Scheme switch
Marked with " " : Scheme switch position
Unmarked : Internal scheme logic signal
AND gates
A A B C Output
B & Output 1 1 1 1
Other cases 0
C
A
A B C Output
B & Output 1 1 0 1
C Other cases 0
A
A B C Output
B & Output
1 0 0 1
C Other cases 0
OR gates
A A B C Output
B ≥1 Output 0 0 0 0
C Other cases 1
A
A B C Output
B ≥1 Output 0 0 1 0
C Other cases 1
A
A B C Output
B ≥1 Output 0 1 1 0
C Other cases 1
⎯ 118 ⎯
6 F 2 S 0 7 9 0
Signal inversion
A Output
A 1 Output 0 1
1 0
Timer
One-shot timer
A
A Output
Output
XXX - YYY
Scheme switch
A Switch Output
A Output
1 ON 1
ON
Other cases 0
Switch Output
+ Output
ON 1
ON OFF 0
⎯ 119 ⎯
6 F 2 S 0 7 9 0
⎯ 120 ⎯
6 F 2 S 0 7 9 0
Appendix L
Setting Calculation
⎯ 121 ⎯
6 F 2 S 0 7 9 0
1. Setting of DIF
Model circuit:
Busbar
GRB150+
CT1 ZE1 ZR ZE2 CT2
EB-101/EB-102
IFmax
Constants:
Setting calculations :
1) Calculate voltage setting value.
VR ≥ 1.2 (RS2 + RL2) × IFmax / N
≥ 1.2 × (1.5 ohms + 1.0 ohm) × 50000 / 800
≥ 188V
2) Calculate minimum operating current value for internal fault.
Imin = (n Ie + Ir + I) N
= (n Ie + Ir + VR / ZR) N
= (14 × 0.003 A + 188 / 667 ohms) × 800
⎯ 122 ⎯
6 F 2 S 0 7 9 0
= 259A
Ir is neglected because it is less than 0.1 mA referring to voltage-current characteristic of
the varistor shown below.
Setting checks:
1) Check that the setting voltage value VR is smaller than half of the CT knee-point voltage
Vk .
1000 / 2 = 500 V > 188V
2) Check that the minimum internal fault current IFmin is larger than the minimum operating
current value Imin.
1000A > 259A
Note: The current sensitivity Imin can be reduced by connecting a shunt resistor across the
relay/varistor unit input. To reduce it from 259A to 400A for example, connect a
resistor of 1067 ohms[= 188V×800/(400A-259A)].
2000
1800
1600
1400
Voltage
(V) 1200
1000
800
600
400
200
⎯ 123 ⎯
6 F 2 S 0 7 9 0
2. Setting of DIFSV
The setting of DIFSV is determined from the maximum erroneous voltage which is generated due
to the following two factors under normal service conditions.
• CT turns ratio errors
• Error due to differences in the respective lengths of the CT secondary connecting
leads to the paralleling point of the differential circuit
Erroneous voltage Ver2 due to differences in the respective lengths of the CT secondary
connecting leads to the paralleling point of the differential circuit:
The maximum erroneous voltage Ver2 must not exceed (RS + RL) × ILmax for the most onerous case,
Ver2 < (RS + RL) × ILmax
< (1.5 ohms + 1.0 ohm) × 5A
< 12.5 V
In a busbar configured with parallel feeders, the load current may increase transiently by up to 1.8
times when one of the parallel feeders is opened. Then assuming that the feeders are fully loaded
under normal conditions,
Ver2 < (1.5 ohms + 1.0 ohm) × 1.8 × 5A
< 22.5 V
⎯ 124 ⎯
6 F 2 S 0 7 9 0
Appendix M
IEC60870-5-103: Interoperability and
Troubleshooting
⎯ 125 ⎯
6 F 2 S 0 7 9 0
IEC60870-5-103 Configurator
IEC103 configurator software is included in a same CD as RSM100, and can be installed easily as
follows:
Installation of IEC103 Configurator
Insert the CD-ROM (RSM100) into a CDROM drive to install this software on a PC.
Double click the “Setup.exe” of the folder “\IEC103Conf” under the root directory, and operate it
according to the message.
When installation has been completed, the IEC103 Configurator will be registered in the start
menu.
Starting IEC103 Configurator
Click [Start]→[Programs]→[IEC103 Configurator]→[IECConf] to the IEC103 Configurator
software.
Note: The instruction manual of IEC103 Configurator can be viewed by clicking
[Help]→[Manual] on IEC103 Configurator.
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of loads, 32 for one protection equipment
1.2 Optical interface
Glass fibre (option)
ST type connector (option)
1.3 Transmission speed
User setting: 9600 or 19200 bit/s
2. Application Layer
COMMON ADDRESS of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
3. List of Information
The following items can be customized with the original software tool “IEC103 configurator”.
(For details, refer to “IEC103 configurator” manual No.6F2S0839.)
- Items for “Time-tagged message”: Type ID(1/2), INF, FUN, Transmission condition(Signal
number), COT
- Items for “Time-tagged measurands”: INF, FUN, Transmission condition(Signal number),
COT, Type of measurand quantities
- Items for “General command”: INF, FUN, Control condition(Signal number)
- Items for “Measurands”: Type ID(3/9), INF, FUN, Number of measurand, Type of
⎯ 126 ⎯
6 F 2 S 0 7 9 0
measurand quantities
- Common setting
• Transmission cycle of Measurand frame
• FUN of System function
• Test mode, etc.
Note: To be effective the setting data written via the RS232C, turn off the DC supply of the relay and
turn on again.
3. 1 IEC60870-5-103 Interface
3.1.1 Spontaneous events
The events created by the relay will be sent using Function type (FUN) / Information numbers
(INF) to the IEC60870-5-103 master station.
3.1.2 General interrogation
The GI request can be used to read the status of the relay, the Function types and Information
numbers that will be returned during the GI cycle are shown in the table below.
For details, refer to the standard IEC60870-5-103 section 7.4.3.
3.1.3 Cyclic measurements
The relay will produce measured values using Type ID=3 or 9 on a cyclical basis, this can be read
from the relay using a Class 2 poll. The rate at which the relay produces new measured values can
be customized.
3.1.4 Commands
The supported commands can be customized. The relay will respond to non-supported commands
with a cause of transmission (COT) of negative acknowledgement of a command.
For details, refer to the standard IEC60870-5-103 section 7.4.4.
3.1.5 Test mode
In test mode, both spontaneous messages and polled measured values, intended for processing in
the control system, are designated by means of the CAUSE OF TRANSMISSION ‘test mode’.
This means that CAUSE OF TRANSMISSION = 7 ‘test mode’ is used for messages normally
transmitted with COT=1 (spontaneous) or COT=2 (cyclic).
For details, refer to the standard IEC60870-5-103 section 7.4.5.
3.1.6 Blocking of monitor direction
If the blocking of the monitor direction is activated in the protection equipment, all indications and
measurands are no longer transmitted.
For details, refer to the standard IEC60870-5-103 section 7.4.6.
⎯ 127 ⎯
6 F 2 S 0 7 9 0
List of Information
IEC103 Configurator Default setting
INF Description Contents GI Type COT FUN DPI
ID Signal No. OFF ON
Standard Information numbers in monitor direction
System Function
0 End of General Interrogation Transmission completion of GI items. -- 8 10 255 -- -- --
0 Time Synchronization Time Synchronization ACK. -- 6 8 255 -- -- --
2 Reset FCB Reset FCB(toggle bit) ACK -- 5 3 217 -- -- --
3 Reset CU Reset CU ACK -- 5 4 217 -- -- --
4 Start/Restart Relay start/restart -- 5 5 217 -- -- --
5 Power On Relay power on. Not supported -- -- --
Status Indications
If it is possible to use auto-recloser, this item is set
16 Auto-recloser active Not supported
active, if impossible, inactive.
If protection using telecommunication is available,
17 Teleprotection active Not supported
this item is set to active. If not, set to inactive.
If the protection is available, this item is set to 1, 7, 9, 12,
18 Protection active GI 1 217 155 1 2
active. If not, set to inactive. 20, 21
1, 7, 11, 12,
19 LED reset Reset of latched LEDs -- 1 217 149 -- 2
20, 21
Block the 103 transmission from a relay to control
20 Monitor direction blocked GI 1 9, 11 217 131 1 2
system. IECBLK: "Blocked" settimg.
Transmission of testmode situation froma relay to
21 Test mode GI 1 9, 11 217 132 1 2
control system. IECTST "ON" setting.
When a setting change has done at the local, the
22 Local parameter Setting Not supported
event is sent to control system.
1, 7, 9, 11,
23 Characteristic1 Setting group 1 active GI 1 176 133 1 2
12, 20, 21
1, 7, 9, 11,
24 Characteristic2 Setting group 2 active GI 1 176 134 1 2
12, 20, 21
1, 7, 9, 11,
25 Characteristic3 Setting group 3 active GI 1 176 135 1 2
12, 20, 21
1, 7, 9, 11,
26 Characteristic4 Setting group 4 active GI 1 176 136 1 2
12, 20, 21
27 Auxiliary input1 Binary input 1 No set
28 Auxiliary input2 Binary input 2 No set
29 Auxiliary input3 Binary input 3 No set
30 Auxiliary input4 Binary input 4 No set
Supervision Indications
32 Measurand supervision I Zero sequence current supervision Not supported
33 Measurand supervision V Zero sequence voltage supervision Not supported
35 Phase sequence supervision Negative sequence voltage supevision Not supported
36 Trip circuit supervision Output circuit supervision Not supported
37 I>>backup operation Not supported
38 VT fuse failure VT failure Not supported
39 Teleprotection disturbed CF(Communication system Fail) supervision Not supported
46 Group warning Only alarming GI 1 1, 7, 9 176 104 1 2
47 Group alarm Trip blocking and alarming GI 1 1, 7, 9 176 102 1 2
Earth Fault Indications
48 Earth Fault L1 A phase earth fault No
49 Earth Fault L2 B phase earth fault No
50 Earth Fault L3 C phase earth fault No
51 Earth Fault Fwd Earth fault forward Not supported
52 Earth Fault Rev Earth fault reverse Not supported
⎯ 128 ⎯
6 F 2 S 0 7 9 0
⎯ 129 ⎯
6 F 2 S 0 7 9 0
⎯ 130 ⎯
6 F 2 S 0 7 9 0
Default setting
INF Description Contents Control Type
direction
COT FUN
ID
Selection of standard information numbers in control direction
System functions
Initiation of general
0 -- 7 9 217
interrogation
0 Time synchronization -- 6 8 217
General commands
16 Auto-recloser on/off Not supported
17 Teleprotection on/off Not supported
18 Protection on/off (*1) ON/OFF 20 20 217
19 LED reset Reset indication of latched LEDs. ON 20 20 217
23 Activate characteristic 1 Setting Group 1 ON 20 20 217
24 Activate characteristic 2 Setting Group 2 ON 20 20 217
25 Activate characteristic 3 Setting Group 3 ON 20 20 217
26 Activate characteristic 4 Setting Group 4 ON 20 20 217
Generic functions
Read headings of all defined
240 Not supported
groups
Read values or attributes of all
241 Not supported
entries of one group
Read directory of a single
243 Not supported
entry
Read values or attributes of a
244 Not supported
single entry
General Interrogation of
245 Not supported
generic data
248 Write entry Not supported
249 Write entry with confirmation Not supported
250 Write entry with execution Not supported
(∗1) Note: While the relay receives the "Protection off" command, " IN SERVICE LED" is off.
✓: signal reverse
⎯ 131 ⎯
6 F 2 S 0 7 9 0
GRB150
Description Contents Comment
supported
Basic application functions
Test mode Yes
Blocking of monitor direction Yes
Disturbance data No
Generic services No
Private data Yes
Miscellaneous
Max. MVAL = rated
Measurand
value times
Current L1 Ia No
Current L2 Ib No
Current L3 Ic No
Voltage L1-E Vda Configurable
Voltage L2-E Vdb Configurable
Voltage L3-E Vdc Configurable
Active power P P No
Reactive power Q Q No
Frequency f f No
Voltage L1 - L2 Vab Configurable
⎯ 132 ⎯
6 F 2 S 0 7 9 0
[Legend]
GI: General Interrogation (refer to IEC60870-5-103 section 7.4.3)
Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1)
1 : time-tagged message
2 : time-tagged message with relative time
3 : measurands I
4 : time-tagged measurands with relative time
5 : identification
6 : time synchronization
8 : general interrogation termination
9 : measurands II
10: generic data
11: generic identification
20: general command
23: list of recorded disturbances
26: ready for transmission for disturbance data
27: ready for transmission of a channel
28: ready for transmission of tags
29: transmission of tags
30: transmission of disturbance values
31: end of transmission
COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3)
1: spontaneous
2: cyclic
3: reset frame count bit (FCB)
4: reset communication unit (CU)
5: start / restart
6: power on
7: test mode
8: time synchronization
9: general interrogation
10: termination of general interrogation
11: local operation
12: remote operation
20: positive acknowledgement of command
21: negative acknowledgement of command
31: transmission of disturbance data
40: positive acknowledgement of generic write command
41: negative acknowledgement of generic write command
42: valid data response to generic read command
43: invalid data response to generic read command
44: generic write confirmation
FUN: Function type (refer to IEC60870-5-103 section 7.2.5.1)
DPI: Double-point Information (refer to IEC60870-5-103 section 7.2.6.5)
DCO: Double Command (refer to IEC60870-5-103 section 7.2.6.4)
⎯ 133 ⎯
6 F 2 S 0 7 9 0
The file extension of IEC103 setting data is “.csv”. The version name is recommended to be
provided with a revision number in order to be changed in future as follows:
First draft: ∗∗∗∗∗∗_01.csv
Second draft: ∗∗∗∗∗∗_02.csv
Third draft: ∗∗∗∗∗∗_03.csv
Revision number
The name “∗∗∗∗∗∗” is recommended to be able to discriminate the relay type such as GRZ100 or
GRL100, etc. The setting files remark field of IEC103 is able to enter up to 12 one-byte
characters. It is utilized for control of IEC103 setting data.
The IEC103 setting data is recommended to be saved in external media such as FD (floppy disk)
or CD-R, not to remain in the folder.
⎯ 134 ⎯
6 F 2 S 0 7 9 0
Troubleshooting
⎯ 135 ⎯
6 F 2 S 0 7 9 0
⎯ 136 ⎯
6 F 2 S 0 7 9 0
Appendix N
Timing Chart of Cold load Condition
Judgment
⎯ 137 ⎯
6 F 2 S 0 7 9 0
(1) Function 1:
Setting: [TCLP]= should be set.
[TCLE],[TCLR]=Not applied.
From CB close command output, the cold load condition is judged for a time.
CB closing CB open
CB closing command
(BI1 COMMAND)
COLD LOAD
(3) Function 2:
Setting: [TCLP]=Not applied.
[TCLE],[TCLR]=should be set.
From CB contact closing, the cold load condition is judged for a time.
CB closing CB open
CB contact CLOSE
COLD LOAD
⎯ 138 ⎯
6 F 2 S 0 7 9 0
Appendix O
Ordering
⎯ 139 ⎯
6 F 2 S 0 7 9 0
Ordering
GRB150 − B− 0− 0−
Type:
High-impedance Differential Relay GRB150
Model:
- Single-phase protection (with EB-101) 101
- Three-phase protection (with EB-102) 201
Ratings:
50Hz, 110V/125Vdc 1
60Hz, 110V/125Vdc 2
50Hz, 220V/250Vdc 5
60Hz, 220V/250Vdc 6
50Hz, 48V/54V/60Vdc A
60Hz, 48V/54V/60Vdc B
Communications:
Dual RS485 3
LED label:
Standard None
Option: User configurable LED label J
Note
EB-101: Varistor unit for single phase
EB-102: Varistor unit for three phase
⎯ 140 ⎯
6 F 2 S 0 7 9 0
Version-up Records
Version Date Revised Section Contents
No.
0.0 Jan. 19, 2004 ---- First issue
0.1 Apr. 28, 2004 6.4, 6.5 Modified Figures 6.4.1, 6.4.2 and 6.5.1
Appendices Modified the Appendix M and added the Appendix N.
0.2 May 20, 2004 Appendix B Changed the name of No.131.
0.3 Aug. 24, 2004 3.2.1 Modified the description of Binary input signals.
4.5 Modified the description.
6.7.2 Modified the description of Note.
Appendices Modified the Appendix J and M.
0.4 Feb. 25, 2005 Appendices Modified the Appendix D and M.
0.5 Jan. 31, 2006 Appendices Appendices Modified the Appendix I, J and N.
0.6 Apr. 06, 2006 3.2.1 Modified the description.
4.1.2 Modified the description.
Appendices Appendix F, J and N.
0.7 Jan. 15. 2007 2.2.3 Modified the description about secondary winding resistance.
4.4, 4.5 Modified the description.
Appendices Added the item ‘LCD and Button operation Instruction’ in Appendix D, and
modified Appendix M.
0.8 Aug.01, 2007 4.2.1 Modified the description.
Appendices Modified Appendix D, M and N
0.9 May. 21, 2009 2.3.1 Added the title ‘High-impedance differential protection’.
2.3.2 Added ‘2.3.2 Cold Load Protection’.
2.4 Modified the setting range table.
3.2.1 Modified Table 3.2.2 and figure 3.2.1.
3.4.2 Modified Table 3.4.1.
3.4.3 Modified the description.
4.2.6.1, 4.2.6.4, Modified the description.
4.2.6.7, 4.2.6.10
Appendices Modified Appendix B, D, F, G and J, and added Appendix N.
Old Appendix N shifted to Appendix O.
1.0 Jun. 11, 2009 2.3.2 Modified the description and Figure 2.3.2.
3.1 Modified Figure 3.1.4.
Appendices Modified Appendix F.
1.1 Oct. 2, 2017 --- Republished under spin-off company
141