Download as pdf or txt
Download as pdf or txt
You are on page 1of 150

MINI VRF System

U-36LE1U6
U-36LE1U6E * Section

U-52LE1U6 1
Section

U-52LE1U6E * 1
2
2
Model No.
Outdoor Unit 3
Class 36 52 3
Model Name U-36LE1U6 U-52LE1U6
U-36LE1U6E* U-52LE1U6E*
Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specifications. 4
Indoor Units
4
Class 7 9 12 15 18 19 24 36 48 54

U1 4-Way Cassette S-12MU1U6 S-18MU1U6 S-24MU1U6 S-36MU1U6


5
Y1 4-Way Cassette 60×60 S-12MY1U6 S-18MY1U6 5
D1 1-Way Cassette S-07MD1U6 S-09MD1U6 S-12MD1U6

F1 Low Silhouette Ducted S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6 S-24MF1U6 S-36MF1U6 S-48MF1U6 S-54MF1U6 6
6
M1 Slim Low Static Ducted S-07MM1U6 S-09MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6
High Static Pressure
E1 S-36ME1U6 S-48ME1U6
Ducted

T1 Ceiling S-12MT1U6 S-18MT1U6 S-24MT1U6 7


7
K1 Wall Mounted S-07MK1U6 S-09MK1U6 S-12MK1U6 S-18MK1U6 S-19MS1U6** S-24MK1U6

P1 Floor Standing S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6

R1
Concealed Floor
Standing
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6 8
** Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U)

85464869256000 REFERENCE NO. TD831156-00

TD831156-00_MINI_VRF_SYS.indb a 2012/01/31 14:39:29


IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and oper- When Installing…
ating standards. As the installer or service person, it is an
important part of your job to install or service the system so Select an installation location which is rigid and strong
it operates safely and efficiently. enough to support or hold the unit, and select a location
for easy maintenance.
For safe installation and trouble-free operation, you must:
…In a Room
Carefully read this instruction booklet before beginning.
Properly insulate any tubing run inside a room to prevent
Follow each installation or repair step exactly as shown.
“sweating” that can cause dripping and water damage to
Observe all local, state, and national electrical codes. walls and floors.
Pay close attention to all warning and caution notices Keep the fire alarm and the air outlet at
given in this manual. CAUTION
least 5 feet away from the unit.
This symbol refers to a hazard or
unsafe practice which can result …In Moist or Uneven Locations
WARNING
in severe personal injury or death. Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
This symbol refers to a hazard or
water damage and abnormal vibration.
unsafe practice which can result
CAUTION in personal injury or product or …In an Area with High Winds
property damage. Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
If Necessary, Get Help
These instructions are all you need for most installation …In a Snowy Area (for Heat Pump-type Systems)
sites and maintenance conditions. If you require help for a Install the outdoor unit on a raised platform that is higher
special problem, contact our sales/service outlet or your than drifting snow. Provide snow vents.
certified dealer for additional instructions.
When Connecting Refrigerant Tubing
In Case of Improper Installation
The manufacturer shall in no way be responsible for • Ventilate the room well, in the event that is refrigerant
improper installation or maintenance service, including fail- gas leaks during the installation. Be careful not to allow
ure to follow the instructions in this document. contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
SPECIAL PRECAUTIONS • Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
WARNING When Wiring
• Apply refrigerant lubricant to the matching surfaces of
ELECTRICAL SHOCK CAN CAUSE the flare and union tubes before connecting them, then
SEVERE PERSONAL INJURY OR DEATH. tighten the nut with a torque wrench for a leak-free con-
ONLY A QUALIFIED, EXPERIENCED nection.
ELECTRICIAN SHOULD ATTEMPT TO • Check carefully for leaks before starting the test run.
WIRE THIS SYSTEM.
• When performing piping work
• Do not supply power to the unit until all wiring and tubing do not mix air except for speci-
are completed or reconnected and checked. fied refrigerant (R410A) in
• Highly dangerous electrical voltages are used in this refrigeration cycle. It causes
system. Carefully refer to the wiring diagram and these capacity down, and risk of
instructions when wiring. Improper connections and inad- explosion and injury due to high
equate grounding can cause accidental injury or death. WARNING tension inside the refrigerant
cycle.
• Ground the unit following local electrical codes. • Refrigerant gas leakage may
• Connect all wiring tightly. Loose wiring may cause over- cause fire.
heating at connection points and a possible fire hazard. • Do not add or replace refrigerant
• To prevent possible hazards from insulation failure, other than specified type.
the unit must be grounded. It may cause product damage,
burst and injury etc.
When Transporting
• Do not leak refrigerant while piping work for an
Be careful when picking up and moving the indoor and installation or re-installation, and while repairing
outdoor units. Get a partner to help, and bend your knees refrigeration parts.
when lifting to reduce strain on your back. Sharp edges or Handle liquid refrigerant carefully as it may cause
thin aluminum fins on the air conditioner can cut your fingers. frostbite.

TD831156-00_MINI_VRF_SYS.indb b 2012/01/31 14:39:29


When Servicing • Do not touch the air inlet or the
CAUTION sharp aluminum fins of the
• Turn the power OFF at the main power box (mains)
outdoor unit. You may get injured.
before opening the unit to check or repair electrical
parts and wiring. • Ventilate any enclosed areas when
installing or testing the refrigeration
• Keep your fingers and clothing away from any moving
system. Escaped refrigerant gas, on
parts.
contact with fire or heat, can produce
• Clean up the site after you finish, remembering to check dangerously toxic gas.
that no metal scraps or bits of wiring have been left
• Confirm after installation that no
inside the unit being serviced.
refrigerant gas is leaking. If the gas
• Do not clean inside the indoor and comes in contact with a burning stove,
WARNING
outdoor units by users. Engage gas water heater, electric room heater
authorized dealer or specialist for or other heat source, it can cause the
cleaning. generation of poisonous gas.
• In case of malfunction of this Others
appliance, do not repair by yourself.
Contact to the sales dealer or service • Do not touch the air inlet or the
CAUTION sharp aluminum fins of the
dealer for a repair.
outdoor unit. You may get injured.
• Do not sit or step on the unit,
you may fall down accidentally.
• Do not stick any object into the
FAN CASE.
You may be injured and the
unit may be damaged.

Check of Density Limit


The room in which the air conditioner is to be ASHRAE and the International Mechanical Code of the
installed requires a design that in the event of refrig- ICC as well as CSA provide guidance and define safe-
erant gas leaking out, its density will not exceed a set guards related to the use of refrigerants, all of which define
limit. a Refrigerant Concentration Level (RCL) of 25 pounds
The refrigerant (R410A), which is used in the air condition- per 1,000 cubic feet for R410A refrigerant.
er, is safe, without the toxicity or combustibility of ammonia, For additional guidance and precautions related to
refrigerant safety, please refer to the following documents:
and is not restricted by laws imposed to protect the ozone
layer. However, since it contains more than air, it poses the
International Mechanical Code 2009 (IMC-2009)
risk of suffocation if its density should rise excessively. Suf- (or more recently revised)
focation from leakage of refrigerant is almost non-existent. ASHRAE 15
With the recent increase in the number of high density ASHRAE 34
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effec-
tive use of floor space, individual control, energy conserva-
tion by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation pro-
cedure so that if the refrigerant accidentally leaks out, its
density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).

ii

TD831156-00_MINI_VRF_SYS.indb c 2012/01/31 14:39:29


Precautions for Installation Using New Refrigerant
1.Care regarding tubing
1-1.Process tubing
Material:Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
Tubing size:Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash.This also applies to distribution joints
(optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.

Use sufficient care in handling the tubing.Seal the tubing ends with
CAUTION caps or tape to prevent dirt,moisture,or other foreign substances
from entering.These substances can result in system malfunction.
Unit: in. (mm)
Material O
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Copper tube
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0) 5/128 (1.0)

1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating
machine oil, the prevention of water and other impurities becomes more important than ever.

2. Be sure to recharge the refrigerant only in liquid form.


2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.

3. Different tools required


3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.

R407C tools Manifold gauge


Item New compatible Remarks
tool? with R410A?

Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and


pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that
react to chlorine do not function because Vacuum pump
R410A contains no chlorine. Leak detector
Outlet
for HFC134a can be used for R410A.
Inlet
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.

* Using tools for R22 and R407C and new tools for R410A together can cause defects.

iii

TD831156-00_MINI_VRF_SYS.indb d 2012/01/31 14:39:29


3-2.Use R410A exclusive cylinder only. Valve

Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid

New refrigerant R410A cannot be used for


earlier models

1.Compressor specifications are different.


If recharging a R22 or R407C compressor with
R410A, durability will significantly decrease since
some of the materials used for compressor parts are
different.

2.Existing tubing cannot be used (especially R22).


Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.

3.Refrigerating machine oil differs (R22).


Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A.Therefore, refrigerating
machine oil discharged from the compressor can
cause compressor damage.

R22 refrigerating machine oil Mineral oil (Suniso oil)


R407C refrigerating machine oil Synthetic fluid (ether oil)
R410A refrigerating machine oil Synthetic fluid (ether oil)

iv

TD831156-00_MINI_VRF_SYS.indb e 2012/01/31 14:39:29


Contents
Section 1: OUTLINE OF MINI VRF SYSTEM .........................................................................1-1
1. Line-up ............................................................................................................ 1-2
2. Salt-Air Damage Resistant Specifications .......................................................1-4
Section 2: DESIGN OF MINI VRF SYSTEM .......................................................................... 2-1
1. Model Selecting and Capacity Calculator ....................................................... 2-2
2. System Design ............................................................................................. 2-13
3. Electrical Wiring ............................................................................................ 2-22
4. Installation Instructions ................................................................................. 2-30
5. HOW TO PROCESS TUBING ...................................................................... 2-38
6. AIR PURGING .............................................................................................. 2-42
7. Optional Parts ............................................................................................... 2-45
Section 3: CONTROL OF MINI VRF SYSTEM ...................................................................... 3-1
1. Main Operating Functions
2. Wireless Remote Controller
3. Timer Remote Controller
4. Simplified Remote Controller
5. System Controller
6. Schedule Timer
7. Intelligent Controller (CZ-256ESMC1U)
8. Communication Adaptor (CZ-CFUNC1U)
9. Remote Sensor
10. LonWorks Interface (CZ-CLNC1U)
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Section 4: MINI VRF SYSTEM UNIT SPECIFICATIONS ....................................................... 4-1
1. Outdoor Unit .................................................................................................. 4-2
2. 4-Way Cassette Type (U1 Type)
3. 4-Way Cassette 60×60 Type (Y1 Type)
4. 1-Way Cassette Type (D1 Type)
5. Low Silhouette Ducted Type (F1 Type)
6. Slim Low Static Ducted Type (M1 Type)
7. High Static Pressure Ducted Type (E1 Type)
8. Ceiling Type (T1 Type)
9. Wall Mounted Type (K1 Type)
10. Floor Standing Type (P1 Type)
11. Concealed Floor Standing Type (R1 Type)
12. Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Section 5: TEST RUN ............................................................................................................. 5-1
1. Preparing for Test Run .................................................................................... 5-2
2. Test Run Procedure ........................................................................................ 5-3
3. Outdoor Unit PCB Setting .............................................................................. 5-4
4. Auto Address Setting ...................................................................................... 5-6
5. Remote Controller Test Run Settings ........................................................... 5-12
6. Caution for Pump Down ................................................................................ 5-13
7. Meaning of Alarm Messages ........................................................................ 5-13
Section 6: ELECTRICAL DATA ..............................................................................................6-1
1. Outdoor Unit ................................................................................................... 6-2
2. Indoor Unit
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Section 7: PCB AND FUNCTIONS ........................................................................................ 7-1
1. Outdoor Unit Control PCB ...............................................................................7-2
2. Indoor Unit Control PCB Switches and Functions
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Section 8: CAPACITY TABLE ................................................................................................ 8-1
1. Capacity Ratio of Outdoor Unit ...................................................................... 8-2
2. Cooling Capacity of Indoor Unit .................................................................... 8-10
v

TD831156-00_MINI_VRF_SYS.indb f 2012/01/31 14:39:29


Outline of Mini VRF SYSTEM
Contents

1. OUTLINE OF MINI VRF SYSTEM


1. Line-up .................................................................................................................................1-2
2. Salt-Air Damage Resistant Specifications.........................................................................1-4

1-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/31 14:39:10


Outline of Mini VRF SYSTEM
1. Line-up

Indoor units
Type 7 9 12 15 18 19 24 36 48 54

4-Way Cassette

(U1 Type)
S-12MU1U6 S-18MU1U6 S-24MU1U6 S-36MU1U6

4-Way Cassette
60 X 60
(Y1 Type) S-12MY1U6 S-18MY1U6

1-Way Cassette

(D1 Type)
S-07MD1U6 S-09MD1U6 S-12MD1U6

Low Silhouette
Ducted
(F1 Type) S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6 S-24MF1U6 S-36MF1U6 S-48MF1U6 S-54MF1U6

Slim Low Static


Ducted

1 (M1 Type) S-07MM1U6 S-09MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6

High Static
Pressure Ducted
(E1 Type) S-36ME1U6 S-48ME1U6
2
Ceiling

(T1 Type)
S-12MT1U6 S-18MT1U6 S-24MT1U6

3 Wall Mounted

(K1 Type) *
S-07MK1U6 S-09MK1U6 S-12MK1U6 S-18MK1U6 S-19MS1U6 S-24MK1U6

4 Floor Standing

(P1 Type)
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6

Concealed Floor
5 Standing
(R1 Type) S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6

* Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).

1-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/31 14:39:11


Outline of Mini VRF SYSTEM
1. Line-up

Indoor units
DC inverter unit
Type
36 52
Capacity:
BTU/h (kW) 38,200 (11.2) 52,900 (15.5)

Cooling /
/ 42,700 (12.5) / 60,000 (17.6)
Heating
U-36LE1U6/U-52LE1U6
U-36LE1U6E*/U-52LE1U6E*

6- 4-
11/16 25-31/32 5/16
2-
3/4 8-5/8 5-29/32

Air intake

25/32
13/32
1/2 1/2

14-31/32

15-15/16
11-21/32
13-3/8

13/32
19/32
1/2 1/2
Air 1
discharge

37

Outdoor
Unit
2
Air Air
discharge intake
3
3-3/16
48-7/16

3-29/32
25/32

4
6-13/16
22-9/16
23-5/8

5-9/16
23/32

7-25/32
5
2-27/32
4-3/4
2-25/32
4-23/32

1-13/32
6-9/16

6-5/8
5-1/2

7-3/4

2-3/8
2-3/8 4-11/32
5-1/8

6
* Outdoor unit model name ended with letters "U6E". Refer to the Section 1 "2. Salt-Air Damage Resistant Specifications".

1-3

TD831156-00_MINI_VRF_SYS.indb 3 2012/01/31 14:39:11


Outline of Mini VRF SYSTEM
2. Salt-Air Damage Resistant Specifications

Specifications
Salt-Air Damage
Relevant Parts Material Standard Specifications Resistant Specifications

Outdoor unit model name ended


with letters "U6E".

Outer box/side plate/ Hot-dip zinc-coated Polyester powder double coating Polyester powder double coating
drain pan steel sheet (both sides) ( 40 m) (both sides) ( 120 m)
between the stud
Hot-dip aluminum-zinc Polyester powder double coating
Base frame No treatment (both sides) ( 120 m)
coated steel sheet
Fan guard Resin (Polypropylene) No treatment No treatment
Fin Aluminum No treatment Zinc rich treatment
Exchanger

Tube Copper No treatment Zinc rich treatment (whole)


Heat

Hot-dip zinc-coated
Tube plate No treatment Zinc rich treatment (whole)
steel sheet
Resin No treatment No treatment
Aluminum No treatment Urethane coating ( 30 m)
Propeller fan
Hot-dip zinc-coated
No treatment Urethane coating ( 30 m)
1 steel sheet
Fan

Motor maker's spec. for salt-air


Motor -- Motor maker's standard spec.
damage resistant (urethane coating)

Hot-dip zinc-coated Polyester powder double coating Polyester powder double coating
Installation frame
2 steel sheet (both sides) ( 120 m) (both sides) ( 120 m)

Hot-dip zinc-coated
Electrical component box No treatment Polyester powder coating ( 120 m)
steel sheet

Hexavalent chromium-free Hexavalent chromium-free coating +


3 Tapping screws SUS410 coating urethane coating

Stud supplementary Hot-dip zinc-coated Polyester powder double coating


bracket steel sheet No treatment ( 120 m)

PC board -- No treatment Dessicant coating ( 30 m)


4 Accumulator
Steel Epoxy coating + alkyd coating
Zinc rich double coating + urethane
Receiver tank coating ( 70 m)
Refrigeration

Welded portion Copper tube No treatment Urethane coating


cycle tube

5
Outer surface Copper tube No treatment Urethane coating

Hot-dip zinc-coated Polyester powder double coating


Fixing bracket No treatment
steel sheet (both sides) ( 80 m)
6
Notes: 1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment.
2 The specifications are subject to change without notice for development.
3 Contact us for the delivery schedule.

1-4

TD831156-00_MINI_VRF_SYS.indb 4 2012/01/31 14:39:11


Design of Mini VRF SYSTEM
Contents

2. DESIGN OF MINI VRF SYSTEM


1. Model Selecting and Capacity Calculator ......................................................................... 2-2
1-1. Operating Range ........................................................................................................... 2-2
1-2. Procedure for Selecting Models and Calculating Capacity ........................................... 2-3
1-3. Calculation of Actual Capacity of Indoor Unit ................................................................ 2-4
1-4. Capacity Correction Graph According to Temperature Condition ................................ 2-9
1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference .... 2-11
2. System Design ................................................................................................................... 2-13
2-1. Tools Required for Installation (not supplied) .............................................................. 2-13
2-2. Accessories Supplied with Outdoor Unit ..................................................................... 2-13
2-3. Type of Copper Tube and Insulation Material .............................................................. 2-13
2-4. Additional Materials Required for Installation............................................................... 2-13
2-5. Tubing Size .................................................................................................................. 2-14
2-6. Straight Equivalent Length of Joints ........................................................................... 2-14
2-7. Additional Refrigerant Charge ..................................................................................... 2-15
2-8. System Limitations....................................................................................................... 2-15
2-9. Tubing Length .............................................................................................................. 2-15
2-10. Check of Limit Density ............................................................................................... 2-16
2-11. System Example ........................................................................................................ 2-17
2-12. Example of Tubing Size Selection and Refrigerant Charge Amount ......................... 2-19 1
2-13. Installing Distribution Joint ......................................................................................... 2-21
3. Electrical Wiring ................................................................................................................. 2-22
3-1. General Precautions on Wiring ................................................................................... 2-22
3-2. Recommended Wire Length and Wire Diameter for Power Supply System ................. 2-22 2
3-3. Wiring System Diagrams ............................................................................................. 2-23
3-4. Important Note When Wiring for Common Type ......................................................... 2-26
3-5. Important Note When Wiring for Y1 Type..................................................................... 2-29
4. Installation Instructions..................................................................................................... 2-30 3
Outdoor Unit ................................................................................................................. 2-30
4-1. Selecting the Installation Site for Outdoor Unit ............................................................ 2-30
4-2. Air Discharge Chamber for Top Discharge .................................................................. 2-31
4-3. Installing the Unit in Heavy Snow Areas ...................................................................... 2-31
4-4. Precautions for Installation in Heavy Snow Areas ....................................................... 2-31
4
4-5. Dimensions of Air-Discharge Chamber........................................................................ 2-32
4-6. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply) .................... 2-32
4-7. Dimensions of Snow Ducting ...................................................................................... 2-34
4-8. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply) .......................... 2-34 5
4-9. Installing the Outdoor Unit .......................................................................................... 2-37
4-10. Drainage Work ........................................................................................................... 2-37
4-11. Routing the Tubing and Wiring ................................................................................... 2-37
Indoor Unit 6
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
5. HOW TO PROCESS TUBING ............................................................................................. 2-38
5-1. Connecting the Refrigerant Tubing ............................................................................ 2-38
5-2. Connecting Tubing Between Indoor and Outdoor Units ............................................. 2-39 7
5-3. Insulating the Refrigerant Tubing ............................................................................... 2-40
5-4. Taping the Tubes ........................................................................................................ 2-41
5-5. Finishing the Installation .............................................................................................. 2-41
6. AIR PURGING .................................................................................................................... 2-42
Air Purging with a Vacuum Pump (for Test Run) Preparation.................................. 2-42
8
7. Optional Parts ..................................................................................................................... 2-45
7-1. Distribution Joint Kits.................................................................................................... 2-45
2-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/31 14:38:40


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

1-1. Operating Range

Cooling Heating
113 77
109

104 68

95 59

Outdoor air intake temp. °F (WB)


86 50
Outdoor air intake temp. °F (DB)

77 41

Operating
68 Operating 32 range
range

59 23

50 14

41 5

1 32
–4
50 59 68 77 86 95

23 Indoor air intake temp. °F (DB)

2 14
57
50 59 68 77 86
Indoor air intake temp. °F (WB)

2-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/31 14:38:40


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

1-2. Procedure for Selecting Models and Calculating Capacity


■ Model Selection Procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
● Calculate the maximum air-conditioning load for each room or zone.
Selection of an air conditioning system
● Select the ideal air conditioning system for air conditioning of each room or zone.
Design of the control system
● Design a suitable control system for the selected air conditioning system.
Preliminary selection of indoor and outdoor units
● Make preliminary selections that are within the allowable range for the system. ................... 2-2
Check of the tubing length and elevation difference
● Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges.................................................................................................................. 2-4, 2-15 – 2-16
Calculation of the corrected outdoor unit capacity
● Capacity correction coefficient for outdoor temperature conditions .......................... 2-4, 2-6 – 2-7
● Capacity correction coefficient for tubing length and elevation difference ........................ 2-4, 2-8
● Heating capacity correction coefficient for frosting/defrosting............................................ 2-4, 2-7
Calculation of the corrected capacity for each indoor unit
● Capacity correction coefficient for indoor temperature conditions ..................................... 2-4, 2-8
1
● Capacity distribution ratio based on the tubing length and elevation difference ... 2-4, 2-15 – 2-16
Calculation of the actual capacity for each indoor unit
● Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit
capacity and the total corrected capacity of all indoor units in the same system. Use the result to 2
calculate the capacity correction coefficient for the indoor units...................................... 2-4 – 2-8
● Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to
calculate the actual capacity for each indoor unit. ................................................................... 2-6
Recheck of the actual capacity for each indoor unit 3
● If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity ........................................................ 2-17 – 2-18
Example 2: Increasing the indoor unit capacity .......................................................... 2-17 – 2-18
Design of tubing
● Create a tubing design which minimizes the amount of additional refrigerant charge as much as
4
possible........................................................................................................................ 2-14 – 2-15
● If tubing extension is expected in the future, create the tubing design with adequate
consideration for this extension.
● Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated 5
cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the
total rated cooling capacity of the connected indoor units.
Calculation of additional refrigerant charge amount
● Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant 6
tubing. Even if the gas tubing diameter was increased, determine the additional refrigerant
charge based only on the liquid tubing size........................................................................... 2-21
● Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the
limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. 2-22 7
Design of electrical wiring capacity
● Select a wiring capacity according to the method of power supply........................................ 2-32

2-3

TD831156-00_MINI_VRF_SYS.indb 3 2012/01/31 14:38:40


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

1-3. Calculation of Actual Capacity of Indoor Unit


■ Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length,
elevation difference and other factors, select the correct model after taking into account the various correction
values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use
the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual
final capacity of each indoor unit.

1. Outdoor unit capacity correction coefficient


Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-6, use the outdoor temperature to find the capacity
correction coefficient.
(2) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-7, use the tubing length and elevation difference
to find the capacity correction coefficient.
The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(3) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-7, find the capacity correction coefficient.
1
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the indoor unit temperature conditions
2 From the graph of capacity characteristics on page 2-8, use the indoor temperature to find the capacity
correction coefficient.
(2) Capacity distribution ratio based on the indoor unit tubing length and elevation difference

3 First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit
to find the correction coefficient from the graph of capacity change characteristics on page 2-8. Then divide the
result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
Capacity distribution ratio for each indoor unit (2) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor unit
4 3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
5 ● Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for
outdoor temperature conditions ((1) Page 2-6) × Correction
coefficient for tubing length and elevation difference ((2) Page 2-8)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
6 capacity [5] is considered to be 100%.
● Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-7) × Distribution ratio based on tubing
length and elevation difference at that indoor unit ((2) Page 2-8)
7 However, the corrected cooling capacity of each indoor unit is found as shown below.
If (1) < 100% and (1) × (2) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit
If (1) ≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit × (1)

2-4

TD831156-00_MINI_VRF_SYS.indb 4 2012/01/31 14:38:41


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

<Heating>
● Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient
for outdoor temperature conditions ((1) Page 2-6) × Correction
coefficient for tubing length and elevation difference ((2) Page 2-8)
× Correction coefficient for frosting/defrosting ((2) Page 2-7)
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
● Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-6) × Distribution ratio based on tubing
length and elevation difference at that indoor unit ((2) Page 2-8).

However, the corrected heating capacity of each indoor unit is found as shown below.
length
If (1) < and
100%elevation difference
and (1) × (2) at that indoor
> 100%: Corrected unit
heating ((3) Page
capacity 2-72)
for that indoor unit (5) = Rated heating capacity for that indoor unit
If (1) ≥ 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit × (1)
* Characteristic graphs are shown on the pages listed above next to each correction item.
Find each correction coefficient from the appropriate conditions.

4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit
capacity and the corrected capacity of each indoor unit.
<Cooling capacity>
1
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in
that system / Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of 2
all indoor units in that system (Ruc ≤ 1), then:
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5)
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is 1.) 3
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units
in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 ×
Ruc + 0.75) / Ruc
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
4
indoor unit, is the underlined part in the formula above.)

<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in 5
that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of
all indoor units in that system (Ruh ≤ 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5) 6
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units
in that system (Ruh > 1), then: 7
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 ×
Ruh + 0.9) / Ruh
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is the underlined part in the formula above.) 8

2-5

TD831156-00_MINI_VRF_SYS.indb 5 2012/01/31 14:38:41


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

Refer to the graph below for the correction coefficients for Ruc and Ruh.

Indoor unit capacity correction coefficient for Ruc (cooling)


Indoor unit capacity correction coefficient for Ruh (heating)
Indoor unit capacity correction coefficient

1.0

0.9

0.8

0.7

0.6

0.5
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Corrected indoor/outdoor capacity ratio (Ruc or Ruh)

Note: When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.

5. Graph of capacity correction coefficients

1 ■ Graph of outdoor unit capacity characteristics (1 – (1))

Outdoor unit cooling capacity characteristics

2
120 (1) U-36LE1U6, U-36LE1U6E
Capacity ratio (%)

71°F WB
104 (1)
100 100 (2)
66°F WB
90 (1)
3 80
60°F WB
80 (2)
(2) U-52LE1U6, U-52LE1U6E

4
14 95 100 109
Outdoor air intake temp. (°F DB)

2-6

TD831156-00_MINI_VRF_SYS.indb 6 2012/01/31 14:38:41


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

Outdoor unit heating capacity characteristics

U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E

130 (°F DB) 130 (°F DB)


120 120

Capacity ratio (%)


Capacity ratio (%)

59 59
110 110
100 68 100 68
90 90
80 77 77
80
70 70
60 60
50 50
0
40 40
0
–4 5 14 23 32 41 50 59 –4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F DB) Outdoor air intake temp. (°F DB)

■ Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2))


Outdoor intake air
temp. (°F WB RH 85%)
–4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42 1
Correction 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
coefficient
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above. 2

2-7

TD831156-00_MINI_VRF_SYS.indb 7 2012/01/31 14:38:42


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

■ Graph of indoor unit capacity characteristics (2 – (1))

Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics

Rate of heating capacity change (%)


Rate of cooling capacity change (%) indicates the rating point. indicates the rating point.
120 110

110 105
100 100

90 95

80 90
57 59 60 62 64 66 68 69 71 73 75 77 59 60 62 64 66 68 69 71 73 75 77 78 80
Indoor air intake temp. (˚F WB) Indoor air intake temp. (˚F DB)

■ Graph of capacity change characteristics resulting from tubing length and elevation difference (1 • 2 – (2))

<Cooling> <Heating>
Base capacity Base capacity
change rate (%) 92 change rate (%)
1 164
131 94
90 88 86 84 82 80 78 76
164
131 98
97 96 95 94 93 92 91
Elevation difference (ft)

Elevation difference (ft)

98 96 98
99
66 98 66
100 100
33 % 33 %
0 0
2 -33
-66
-33
-66
-98 -98
-131 -131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492

3 Equivalent length (ft) Equivalent length (ft)

The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.

2-8

TD831156-00_MINI_VRF_SYS.indb 8 2012/01/31 14:38:43


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

1-4. Capacity Correction Graph According to Temperature Condition


■ Capacity characteristics
(The corrected capacity for specific temperature conditions can be found from the graphs below and next page.)

<COOLING>

120 (1) U-36LE1U6, U-36LE1U6E


Capacity ratio (%)

71°F WB
104 (1)
100 100 (2)
66°F WB
90 (1) (2) U-52LE1U6, U-52LE1U6E
80 80 (2)
60°F WB

14 95 100 109
Outdoor air intake temp. (°F DB)
1

92 104 100 112 2


124 (1)
118 (1)
Capacity ratio (%)

114 (2)
108 (2)
100 100 (2)
(1) U-36LE1U6, U-36LE1U6E 3
71°F WB
66°F WB
63 (2) U-52LE1U6, U-52LE1U6E
50 50

33
60°F WB
4
14 95 100 109
Outdoor air intake temp. (°F DB)
5

2-9

TD831156-00_MINI_VRF_SYS.indb 9 2012/01/31 14:38:43


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

<HEATING>
U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E

130 (°F DB) 130 (°F DB)


120
Capacity ratio (%)

59 120

Capacity ratio (%)


110 59
110
100 68 100 68
90 90
80 77 77
80
70 70
60 60
50 50
40 40
130 130
120 120
Input ratio (%)

110

Input ratio (%)


59 110
100 59
100
90 90
80 68 80 68
70 70
60 77 60 77
50 50
–4 5 14 23 32 41 50 59 –4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F DB)
1 Outdoor air intake temp. (°F DB)

2 - 10

TD831156-00_MINI_VRF_SYS.indb 10 2012/01/31 14:38:43


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

● Inverter model rated performance values

Item Cooling Heating

Cooling Power Heating Power


Model capacity consumption capacity consumption
BTU/h(kW) BTU/h(kW) BTU/h(kW) BTU/h(kW)
U-36LE1U6, U-36LE1U6E 38,200 (11.2) 9,400 (2.76) 42,700 (12.5) 9,800 (2.88)
U-52LE1U6, U-52LE1U6E 52,900 (15.5) 16,600 (4.57) 60,000 (17.6) 15,600 (4.58)

■ Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3))


Outdoor intake air –4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
temp. (°F WB RH 85%)
Correction 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
coefficient
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.

1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference
■ Capacity change characteristics 1
<Cooling>

Base capacity
164
change rate (%) 92 90 88 86 84 82 80 78 76
2
131 94
Elevation difference (ft)

98 96

66 98

33
100
%
*1
3
0

–33

–66

–98 4
–131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492

Equivalent length (ft)

<Heating>
5
Base capacity
change rate (%) 97 96 95 94 93 92 91
164

131 98 6
Elevation difference (ft)

98
99
66 *1
100
33 %

0 7
–33

–66

–98

–131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
8
Equivalent length (ft)

2 - 11

TD831156-00_MINI_VRF_SYS.indb 11 2012/01/31 14:38:43


Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator

For U-36LE1U6(E) units


■ If the maximum tubing length (L1) exceeds 295 ft. (equivalent length), increase the tubing size of the main gas
tube (LM) by one rank.
* The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the
tubing size.
■ Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-1 to increase the tubing size. However, the maximum allowable tubing length must not be
exceeded.
* The size increase is applied to the LM gas tube (main tube with the largest diameter) only, and is limited to the
cases shown in Table 2-1. In addition, the amount of additional refrigerant charge is determined from the liquid
tube size only.
* In case of 6 pieces, increasing the size of the gas tube is not possible.

Table 2-1 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased

Standard tube diameter (gas tube, in. (mm)) ø5/8" (ø15.88)


Tube diameter after change (gas tube, in. (mm)) ø3/4" (ø19.05)
Equivalent length correction coefficient 0.4

* When increasing the size of the gas tubing (LM), multiply by the correction coefficient from Table 2-1 and calculate the
1 equivalent length for section LM.

Tubing equivalent length after size increase = Standard tubing equivalent length × Equivalent length correction coefficient

2 WARNING
The upper limit for tubing size is ø3/4” (ø19.05). Tubing above that size cannot be
used.

2 - 12

TD831156-00_MINI_VRF_SYS.indb 12 2012/01/31 14:38:44


Design of Mini VRF SYSTEM
2. System Design

2-1. Tools Required for Installation (not supplied) 2-3. Type of Copper Tube and Insulation Material
1. Flathead screwdriver
If you wish to purchase these materials separately
2. Phillips head screwdriver
from a local source, you will need:
3. Knife or wire stripper
1. Deoxidized annealed copper tube for refrigerant
4. Tape measure
tubing.
5. Carpenter’s level
6. Sabre saw or key hole saw 2. Foamed polyethylene insulation for copper tubes as
7. Hack saw required to precise length of tubing. Wall thickness
8. Core bits of the insulation should be not less than 5/16".
9. Hammer 3. Use insulated copper wire for field wiring. Wire
10. Drill size varies with the total length of wiring. Refer to
11. Tube cutter 3. Electrical Wiring for details.
12. Tube flaring tool
13. Torque wrench Check local electrical codes
CAUTION
14. Adjustable wrench and regulations before
15. Reamer (for deburring) obtaining wire. Also, check
2-2. Accessories Supplied with Outdoor Unit any specified instructions
or limitations.
Table 2-2 (Outdoor Unit)
2-4. Additional Materials Required for Installation
1
Q'ty
1. Refrigeration (armored) tape
Patr name Figure U-36LE1U6 U-52LE1U6
U-36LE1U6E U-52LE1U6E 2. Insulated staples or clamps for connecting wire
(4 hp) (6 hp) (See your local codes.) 2
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
3
6. Scale for weighing
Tube Discharge
0 1
Assembly

Instruction
manual
paper 1 1 5
hp = horsepower

2 - 13

TD831156-00_MINI_VRF_SYS.indb 13 2012/01/31 14:38:44


Design of Mini VRF SYSTEM
2. System Design

2-5. Tubing Size


Table 2-3 Main Tubing Size (LA)
BTU/h (kW) 38,200 (11.2) 52,900 (15.5)
System horsepower 4 6
Gas tubing ø5/8" (ø15.88) ø 3/4" (ø19.05)
Liquid tubing ø 3/8" (ø9.52) Unit: in. (mm)
Note: If the system consists of only one indoor unit with an outdoor 6HP (Type 52), the main tube of the unit (LA) should be
ø19.05. Convert ø19.05 to ø15.88 using a reducer (field supply) close to the indoor unit and then make the connection.

Table 2-4 Main Tubing Size After Distribution (LB, LC...)


Total capacity Below BTU/h 24,200 (2.5 hp) 38,200 (4 hp) 47,800 (5 hp) 52,900 (6 hp)
after distribution Over BTU/h – 24,200 (2.5 hp)
s tubing ø1/2" (ø12.7) ø5/8" (ø15.88) ø3/4" (ø19.05)
Tubing size Unit: in. (mm)
Liquid tubing ø3/8" (ø9.52) ø3/8" (ø9.52) hp = horsepower

Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main
tubing size for the total capacity of the outdoor units.

1 Table 2-5 Indoor Unit Tubing Connection ( 1, 2... n–1)

Indoor unit type 7 9 12 15 18 19 24 36 48 54


Gas tubing ø1/2" (ø12.7) ø5/8" (ø15.88)
2 Liquid tubing ø1/4" (ø6.35) ø3/8" (ø9.52) Unit: in. (mm)

2-6. Straight Equivalent Length of Joints


3 Design the tubing system by referring to the following table for the straight equivalent length of joints.

Table 2-6 Straight Equivalent Length of Joints Unit: ft.

Gas tubing size (in. (mm)) 1/2" (12.7) 5/8" (15.88) 3/4" (19.05)
4 90° elbow 1 1.1 1.4

45° elbow 0.8 0.9 1

5 U-shape tube bend (R2-3/8" – 4" (60 – 100)) 3 3.4 4.1

Trap bend 7.5 9.2 10.5

Y-branch distribution joint Equivalent length conversion not needed.

6 Ball valve for service Equivalent length conversion not needed.

Table 2-7 Required Copper Tubing Dimensions Unit: in. (mm)


7 Material O
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Copper tube
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0) over 5/128 (1.0)

2 - 14

TD831156-00_MINI_VRF_SYS.indb 14 2012/01/31 14:38:44


Design of Mini VRF SYSTEM
2. System Design

2-7. Additional Refrigerant Charge


Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 2-8 Amount of Refrigerant Charge Per Feet, According to Liquid Tubing Size
Liquid tubing size Amount of refrigerant Required amount of charge = (Amount of refrigerant
(in. (mm)) charge (oz/ft.)
charge per ft. of each size of liquid tube × its tube
ø1/4” (ø6.35) 0.279 length) + (...) + (...)
ø3/8” (ø9.52) 0.602
*Always charge accurately using a scale for weighing.

Table 2-9 Refrigerant Charge Amount at Shipment (for outdoor unit)

Heat pump unit U-36LE1U6 U-52LE1U6


(Single-phase)(oz) U-36LE1U6E U-52LE1U6E
123 123

2-8. System Limitations

Table 2-10 System Limitations


1
Outdoor units U-36LE1U6 U-52LE1U6
U-36LE1U6E U-52LE1U6E
Number of max. connectable indoor units 6 9
Max. allowable indoor/outdoor capacity ratio 50 – 130%
2
2-9. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below. 3

4
L1
LA L2
Main tube of unit LB LC LD n

H1 5
1st branch
L3 1 2 3 n-1 H2
Unit distribution tube
6
Note: Do not use commercially available T-joints for the liquid tubing.
* Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor R410A distribution joint
unit connections and tubing branches. CZ-P160BK1U (for indoor unit)
7

2 - 15

TD831156-00_MINI_VRF_SYS.indb 15 2012/01/31 14:38:45


Design of Mini VRF SYSTEM
2. System Design

Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Items Marks Contents Length (ft.)
Actual length > 492
L1 Max. tubing length
Equivalent length > 574
Difference between max. length and min.
Allowable tubing L (L2 – L3) > 131
length from the No.1 distribution joint
length
LA Max. length of main tubing (at max. diameter) > 262

1 , 2... n Max. length of each distribution tube > 98


Total max. tubing length including length of
1 + 2 +... n-1 +L1 > 656
each distribution tube (only narrow tubing)
When outdoor unit is installed higher than indoor unit > 164
Allowable elevation H1
When outdoor unit is installed lower than indoor unit > 131
difference
H2 Max. difference between indoor units > 49

L = Length, H = Height

Always check the gas den-


WARNING
1 sity limit for the room in
which the unit is installed.

2-10. Check of Limit Density


When installing an air conditioner in a room, it is
2 necessary to ensure that even if the refrigerant gas
accidentally leaks out, its density does not exceed the
limit level for that room.

3
Pay special attention to any
CAUTION location, such as a base-
ment, etc., where leaking
4 refrigerant can accumulate,
since refrigerant gas is
heavier than air.

2 - 16

TD831156-00_MINI_VRF_SYS.indb 16 2012/01/31 14:38:45


Design of Mini VRF SYSTEM
2. System Design

2-11. System Example


(1) Below are the tables created using the “PAC System Diagram Software.”
Details of the calculations are shown in (2).
Outdoor
unit

131 ft.
33 ft. 33 ft. 49 ft.

Elevation 33 ft. 33 ft. 33 ft.


difference: 33 ft.
Indoor Indoor Indoor Indoor
unit 1 unit 2 unit 3 unit 4

Selection conditions
Assumes that installation is in a 60 Hz region.
Room 1 Room 2 Room 3 Room 4
Outdoor unit (indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model U-36LE1U6 (U-36LE1U6E) Type 12 Type 7 Type 7 Type 7
Air condition 91.0 / 72.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0
Cooling (DB/WB)
Max. load (BTU/h) 10,000 7,000 7,000 7,000
Air condition
Heating (DB/WB)
37.0 / 35.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0
1
Max. load (BTU/h) 12,000 8,400 8,400 8,400
Actual tubing length 246 ft. 164 ft. 197 ft. 230 ft. 246 ft.
Equivalent length (with
295 ft. 197 ft. 236 ft. 276 ft. 295 ft.
consideration for curves, etc.)
2
Preliminary selection

Outdoor unit Room 1 Room 2 Room 3 Room 4


(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model
Load (cooling/heating) (BTU/h)
U-36LE1U6 (U-36LE1U6E) Type 12 Type 7 Type 7
10,000 / 12,000 7,000 / 8,400
Type 7
7,000 / 8,400 7,000 / 8,400
3
Rated capacity
38,200 / 42,700 12,000 / 14,000 7,500 / 8,500 7,500 / 8,500 7,500 / 8,500
(cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h)
33,200 / 33,700 11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 6,900 / 8,300
4
(7) Actual capacity 6,900 / 7,300
11,700 / 12,200 7,200 / 7,400 7,000 / 7,300
(cooling/heating) (BTU/h)
Total corrected capacity of indoor units (cooling/heating) = 32,800 / 39,100
Ruc = 32,800 / 33,200 = 0.988 < 1 Ruh = 39,100 / 33,700 = 1,160 > 1
Outdoor unit changes
5
During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units
in the system. As a result, the actual capacity of each indoor unit is less than the maximum load. Therefore
the outdoor unit is increased by one rank.
Outdoor unit
Room 1 Room 2 Room 3 Room 4
(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
6
Selected model U-52LE1U6 (U-52LE1U6E) Type 12 Type 7 Type 7 Type 7
Maximum load
(cooling/heating) (BTU/h) 10,000 / 12,000 7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
Rated capacity
52,900 / 60,000 12,000 / 14,000 7,500 / 8,500 7,500 / 8,500 7,500 / 8,500
7
(cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h) 45,900 / 47,300 11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 6,900 / 8,300
(7) Actual capacity
(cooling/heating) (BTU/h)
11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 6,900 / 8,300 8
Total corrected capacity of all indoor units (cooling/heating) = 32,800 / 39,100
Ruc = 32,800 / 45,900 = 0.715 < 1 Ruh = 39,100 / 47,300 = 0.827 < 1
2 - 17

TD831156-00_MINI_VRF_SYS.indb 17 2012/01/31 14:38:45


Design of Mini VRF SYSTEM
2. System Design

Indoor unit changes


The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is
increased by one rank.
Room 1 Room 2 Room 3 Room 4
Outdoor unit
(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Selected model U-52LE1U6 (U-52LE1U6E) Type 12 Type 7 Type 7 Type 12
Maximum load
10,000 / 12,000 7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
(cooling/heating) (BTU/h)
Rated capacity
52,900 / 60,000 12,000 / 14,000 7,500 / 8,500 7,500 / 8,500 12,000 / 14,000
(cooling/heating) (BTU/h)
(5) Corrected capacity
45,900 / 47,300 11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 11,000 / 13,700
(cooling/heating) (BTU/h)
(7) Actual capacity
11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 11,000 / 13,700
(cooling/heating) (BTU/h)
Total corrected capacity of all indoor units (cooling/heating) = 36,900 / 44,500
Ruc = 36,900 / 45,900 = 0.804 < 1 Ruh = 44,500 / 47,300 = 0.941 < 1
•For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum
load. Selection is completed.

(2) Calculate the final selection results according to the capacity calculation procedure.
[From calculation of the correction coefficient to calculation of actual capacity] (Cooling/heating)
1 Outdoor unit
Room 1 Room 2 Room 3 Room 4
(indoor unit 1) (indoor unit 2) (indoor unit 3) (indoor unit 4)
Rated capacity
(cooling/heating) (BTU/h) 52,900 / 60,000 12,000 / 14,000 7,500 / 8,500 7,500 / 8,500 12,000 / 14,000

2 (1) Model 1.00 / 1.00


coefficient
Correction

(2) Temp. condition 1.020 / 0.937 0.920 / 0.980 0.920 / 0.980 0.920 / 0.980 0.920 / 0.980
(3) Tubing length,
0.851 / 0.946 1.062 / 1.020 1.037 / 1.012 1.012 / 1.004 1.000 / 1.000
elevation difference

3 (4) Frosting • defrosting — / 0.890


Result of (2) × (3) 0.977 / 1.000 0.954 / 0.992 0.992 / 0.984 0.920 / 0.980
Correction coefficient
applied to indoor unit *1 0.977 / 1.000 0.954 / 0.992 0.992 / 0.984 0.920 / 0.980

4 (5) Corrected capacity (BTU/h) *2


(6) Correction coefficient
45,900 / 47,300 11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 11,000 / 13,700

for corrected capacity 1.00 / 1.00


ratio
(7) Actual capacity (BTU/h) 11,700 / 14,000 7,200 / 8,400 7,000 / 8,400 11,000 / 13,700
5 *1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)).
*2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4)

The actual capacity is calculated as shown below.


6 Cooling: Ruc = (11,700 + 7,200 + 7,000 + 11,000) / 45,900 = 0.804 < 1
Therefore,
Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit
(In other words, the correction coefficient [6] for the corrected capacity ratio is 1.)
7 Heating: Ruh = (14,000 + 8,400 + 8,400 + 13,700) / 47,300 = 0.941 < 1
Therefore,
Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit
(In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)
8

2 - 18

TD831156-00_MINI_VRF_SYS.indb 18 2012/01/31 14:38:45


Design of Mini VRF SYSTEM
2. System Design

2-12. Example of Tubing Size Selection and Refrigerant Charge Amount

Additional refrigerant charging


Based on the values in Tables 2-3, 2-4, 2-5 and 2-8, use the liquid tubing size and length, and calculate the amount
of additional refrigerant charge using the formula below.

Required additional = 0.602 × (a) + 0.279 × (b)


refrigerant charge (oz)
(a): Liquid tubing Total length of ø3/8” (ø9.52) (ft.) (b): Liquid tubing Total length of ø1/4” (ø6.35) (ft.)
● Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be
in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging
with refrigerant from the gas tubing side. (This is performed at the time of the test run. For this, all valves
must be in the “fully open” position.)
Charge with R410A refrigerant in liquid form.
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent 1
liquid refrigerant from backing up.
● After charging is completed, turn all valves to the “fully open” position.
● Replace the tubing covers as they were before.
2

Tightening torque for valve stem cap: 160 – 180 lbs · in. 4 1 Tightening torque: 590 – 710 lbs · in.
6
Tightening torque: 300 – 360 lbs · in. 3 2 Tightening torque for valve stem cap: 240 – 280 lbs · in.

1. R410A additional charging absolutely must be done through liquid charging.


CAUTION 2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
7
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon
tube is present. (This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in
installation, it is not possible in some cases to use the same tools for R22 and
8
for R410A.

2 - 19

TD831156-00_MINI_VRF_SYS.indb 19 2012/01/31 14:38:45


Design of Mini VRF SYSTEM
2. System Design

Example:

L1
LA L2
Main tube of unit LB LC LN n

1st branch
1 2 3 n–1
model 18
Unit distribution tube
model 7 model 9 model 12 model 18

● Example of each tubing length


Main tubing Distribution joint tubing
LA = 131 ft. Indoor side
LB = 16 ft. 1 = 16 ft. 4 = 20 ft.
LC = 16 ft. 2 = 16 ft. 5 = 16 ft.
LD = 49 ft. 3 = 7 ft.
1
● Obtain charge amount for each tubing size
Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.
ø3/8" (ø9.52) → LA + LB + LC + LD : 212 ft. × 0.602 oz/ft. = 127 oz
2 ø1/4" (ø6.35) → 1+ 2+ 3+ 4+ 5 : 75 ft. × 0.279 oz/ft. = 20 oz

Total 147 oz
Additional refrigerant charge amount is 147 oz.
3
Be sure to check the limit density
CAUTION for the room in which the indoor
unit is installed.
4

2 - 20

TD831156-00_MINI_VRF_SYS.indb 20 2012/01/31 14:38:46


Design of Mini VRF SYSTEM
2. System Design

2-13. Installing Distribution Joint Tube branching methods (horizontal use)

(1) Refer to “HOW TO ATTACH DISTRIBUTION


JOINT” enclosed with the optional distribution
joint kit (CZ-P160BK1U).
B A
(2) In order to prevent accumulation of refrigerant oil Arrow view D

in stopped units, if the main tubing is horizontal Arrow view C

°
30
then each branch tubing length “B” should be at 15

to
to

15
30
an angle that is greater than horizontal. If the main °

tubing is vertical, provide a raised starting portion B B


for each branch. A
Horizontal A
When only one indoor unit is connected to the side of line View as seen
“A”, install part “A” at a positive angle (15-30°) for the view D view C from arrow
field tubing as shown in the figure.

(3) If there are height differences between indoor units


Types of vertical trap specifications
or if branch tubing that follows a distribution joint
is connected to only 1 unit, a trap or ball valve (When using ball valve)

must be added to that distribution joint. (When Main tubing


adding the ball valve, locate it within 1.3 ft. of the
distribution joint.) 1
Ball valve Indoor unit (more than 2 units)
If a trap or ball valve is not added, do not operate
(BV: purchased (If only 1 unit is connected, a ball
the system before repairs to a malfunctioning separately) valve is also needed on this side.)
unit are completed. (The refrigerant oil sent Indoor unit (1)
through the tubing to the malfunctioning unit will 2
accumulate and may damage the compressor.) (When not using ball valve)

Main tubing
Horizontal
Indoor unit (Each unit is
Branch tubing is connected to tubing
3
directed upward. that is either level or
is directed
More than downward.)
8 in.

Indoor unit is directed downward 4

2 - 21

TD831156-00_MINI_VRF_SYS.indb 21 2012/01/31 14:38:46


Design of Mini VRF SYSTEM
3. Electrical Wiring

3-1. General Precautions on Wiring


(1) Before wiring, confirm the rated voltage of the unit (7) Regulations on wire diameters differ from locality
as shown on its nameplate, then carry out the to locality. For field wiring rules, please refer
wiring closely following the wiring diagram. to your LOCAL ELECTRICAL CODES before
(2) Provide a power outlet to be used exclusively for beginning.
each unit, and a power supply disconnect, circuit You must ensure that installation complies with all
breaker and earth leakage breaker for overcurrent relevant rules and regulations.
protection should be provided in the exclusive line. (8) To prevent malfunction of the air conditioner
(3) To prevent possible hazards from insulation failure, caused by electrical noise, care must be taken
the unit must be grounded. when wiring as follows:
(4) Each wiring connection must be done in The remote control wiring and the inter-unit control
accordance with the wiring system diagram. wiring should be wired apart from the inter-unit
Wrong wiring may cause the unit to misoperate or power wiring.
become damaged.
Use shielded wires for inter-unit control wiring
(5) Do not allow wiring to touch the refrigerant tubing, between units and ground the shield on both sides.
compressor, or any moving parts of the fan.
(9) If the power supply cord of this appliance is
(6) Unauthorized changes in the internal wiring can be damaged, it must be replaced by a repair shop
very dangerous. The manufacturer will accept no
1 responsibility for any damage or misoperation that
appointed by the manufacturer, because special
purpose tools are required.
occurs as a result of such unauthorized changes.

2 3-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
Time delay fuse or
Type
circuit capacity

3 U-36LE1U6
U-36LE1U6E
30 A

U-52LE1U6
50 A
U-52LE1U6E

4 Indoor unit
Time delay fuse or
Type
circuit capacity
K1 15 A
5 D1, U1, Y1, F1, M1, T1, P1, R1 15 A
E1 15 A

6 Control wiring
(A) Inter-unit (between outdoor and
(B) Remote control wiring (C) Control wiring for group control
indoor units) control wiring*

7 AWG #18 (0.75 mm2)


Max. 3,280 ft.
AWG #18 (0.75 mm2)
Max. 1,640 ft.
AWG #18 (0.75 mm2)
Max. 650 ft. (Total)

NOTE
8
* With ring-type wire terminal.

2 - 22

TD831156-00_MINI_VRF_SYS.indb 22 2012/01/31 14:38:46


Design of Mini VRF SYSTEM
3. Electrical Wiring

3-3.Wiring System Diagram


Indoor
* unit (No. 1)
Power supply L1 L1
Outdoor unit
208 / 230V, 60Hz, 1-PH L2 INV unit
L2
A *
L1 L1 Power supply
Ground U1 1
L2
L2 208 / 230V, 60Hz, 1-PH
Remote U2 2
Controller B
Ground
WHT 1 1 R1
BLK 2 2 R2
* Disconnect switch
A
Indoor
(Field Supply)
* unit (No. 2)
Power supply L1 L1 * NOTE:
208 / 230V, 60Hz, 1-PH L2 L2
Disconnect Switch may be needed by the
Ground U1
Remote U2
National/Local code.
Controller B
WHT 1 1 R1
BLK 2 2 R2 ALWAYS COMPLY WITH NATIONAL AND
A
LOCAL CODE REQUIREMENTS.
Group control: Indoor
unit (No. 3)
*
Power supply L1 L1
208 / 230V, 60Hz, 1-PH L2 L2

Ground U1
C U2
Outdoor Unit
R1
R2 5P terminal board 1
A

K1 Type Indoor
* unit (No. n)
Power supply L1
208 / 230V, 60Hz, 1-PH L2
L1
L2
2
Ground U1
U2
Remote BLK
WHT L1 L2 1 2
Controller B
Power
(BLU)

BLK 2 BLK BLK 3


3
RC

supply
WHT 1 WHT WHT 1

CONNECTOR
2P (WHT) Indoor Unit
U1, E1 Types Y1, D1, T1, F1, M1, P1, R1 Types
7P terminal board 6P terminal board
4
NOTE
(1) Refer to Section 3-2.“Recommended Wire
Length and Wire Diameter for Power Supply
System for the explanation of “A,” “B,” and
1(L1) 2(L2) U1 U2 R1 R2
L1 L2 U1 U2 R1 R2 5
“C,” in the above diagram. Power Unit Remote Power Unit Remote
supply control control supply control control
(2) The basic connection diagram of the indoor Line Line
Line Line
unit shows the 6P terminal board, so the
terminal boards in your equipment may differ
K1 Type
Model : S-07MK1U6
K1 Type
Model : S-18MK1U6
6
from the diagram. S-09MK1U6 S-19MS1U6
S-12MK1U6 S-24MK1U6
(3) Refrigerant Circuit (R.C.) address should be
5P terminal board 5P terminal board
set before turning the power on.
(4) Regarding the R.C. address setting, refer to
7
Section 5 "TEST RUN." Address setting can be
executed by remote controller automatically.
1 2 U1 U2 1 2 U1 U2
(L1) (L2)
Power Unit
(L1)(L2)
Power Unit
8
supply control supply control
Line Line

2 - 23

TD831156-00_MINI_VRF_SYS.indb 23 2012/01/31 14:38:46


Design of Mini VRF SYSTEM
3. Electrical Wiring

CAUTION

(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003,
2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one
of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 2-1)

Outdoor unit Outdoor unit Outdoor unit


Prohibited

Prohibited

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Fig. 2-1

(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-
1 address setting.

Outdoor unit Indoor unit Indoor unit


2
NO Indoor unit Indoor unit

Branch point

3 Fig. 2-2

(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 2-3)
4 Outdoor unit Outdoor unit Outdoor unit

5 Indoor unit Indoor unit Indoor unit Indoor unit

more than 3.3 ft


Branch
point
6 16 or fewer
Indoor unit Indoor unit Indoor unit Indoor unit

more than 3.3 ft

Indoor unit
7 less than 3.3 ft

Indoor unit

8
Fig. 2-3

2 - 24

TD831156-00_MINI_VRF_SYS.indb 24 2012/01/31 14:38:47


Design of Mini VRF SYSTEM
3. Electrical Wiring

Loose wiring may cause


WARNING the terminal to overheat or Stranded wire
result in unit malfunction.

Strip 3/8"
A fire hazard may also
Ring
exist. Therefore, ensure pressure
that all wiring is tightly terminal
connected.
When connecting each power wire to the terminal,
follow the instructions on “How to connect wiring to
the terminal” and fasten the wire securely with the Fig. 2-4
fixing screw of the terminal plate.
Special
How to connect wiring to the terminal washer Screw
Ring pressure
For stranded wiring terminal Screw and
Special washer
(1) Cut the wire end with cutting pliers, then strip the Terminal plate
Wire
insulation to expose the stranded wiring approx. Ring
3/8 in. and tightly twist the wire ends. (Fig. 2-4) pressure
terminal
(2) Using a Phillips head screwdriver, remove the
Wire
terminal screw(s) on the terminal plate. 1
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal. Fig. 2-5

(4) Place the ring pressure terminal, and replace 2


and tighten the removed terminal screw using a
screwdriver. (Fig. 2-5)

2 - 25

TD831156-00_MINI_VRF_SYS.indb 25 2012/01/31 14:38:47


Design of Mini VRF SYSTEM
3. Electrical Wiring

3-4. Important Note When Wiring for Common Type


U1 Type
Connect the wires referring to the diagram.
Note that the control wirings (Low voltages) shall be
segregated from the power supply wires (High voltage)
as follows:

1. Connect the Inter-unit control wiring to U1/U2


Earth screw
terminals and the remote control wire to R1/R2.
(excepting K1 type). Power wiring
(field supplied)
2. Connect the power supply wires to “L1, L2” of the
terminal block. Be sure to connect the grounding
Connection for
conductor of the incoming power supply to the earth Solenoid Valve Kit
Clamping
(ground) screw. clip (for 3WAY)
3. Securely affix the power supply wires and remote
control wires by the clamping strap or clamping clip
not to cross each other and not to leave the wirings
loose. When loosening the clamping clip, twist the
strap and it will come undone.

Clamping clip
1 Twist
NOTE
Securely affix the 3-way wiring Remote control wiring
harness with the remote Conduit
and Inter-unit control wiring
2 control wiring (U1 type). (field supplied)

D1 Type F1 Type
3 Remote control wiring
and Inter-unit control wiring Conduit
(field supplied) (field supplied)

4 Earth screw

Power wiring
(field supplied)
5
Conduit
(field supplied)

6
Clamping
clip

Clamping Power wiring


7 clip Earth screw (field supplied)

Remote control wiring Connection for Solenoid


and Inter-unit control wiring
8 (field supplied)
Valve Kit (for 3WAY)

2 - 26

TD831156-00_MINI_VRF_SYS.indb 26 2012/01/31 14:38:47


Design of Mini VRF SYSTEM
3. Electrical Wiring

Important Note When Wiring for Common Type (Continued)

E1 Type T1 Type
Remote control wiring
and Inter-unit control
wiring (field supplied)
Clamping Remote control wiring
clip (field supplied)

Clamping
clip
Conduit
(field supplied)

1
Earth screw Power wiring Conduit
(field supplied) (field supplied)
Power wiring
Earth screw (field supplied)
2

M1 Type P1, R1 Type


3

Clamping clip
5
Connection
for Solenoid
Valve Kit
Power wiring (for 3WAY)
(field supplied)
6
Earth screw

Power wiring Conduit


(field supplied)
Conduit 7
(field supplied)

Remote control wiring


Earth screw Clamping
and Inter-unit control wiring
clip
(field supplied) Optional remote control
wiring (field supplied)
3-way connection wiring
with harness(supplied)
8

2 - 27

TD831156-00_MINI_VRF_SYS.indb 27 2012/01/31 14:38:47


Design of Mini VRF SYSTEM
3. Electrical Wiring

Important Note When Wiring for Common Type (Continued)

K1 Type
Model : S-07MK1U6 Clamping Connection for Solenoid
S-09MK1U6 strap Valve Kit (for 3WAY)
S-12MK1U6

Power wiring
(field supplied)

1
Conduit Remote control wiring
(field supplied) and Inter-unit control
wiring (field supplied)
2

K1 Type
3 Clamping Connection for Solenoid
Valve Kit (for 3WAY)
Model : S-18MK1U6 strap
S-19MS1U6*
S-24MK1U6

4
Power wiring
(field supplied)

6
Earth screw

7
Remote control wiring
Conduit and Inter-unit control
(field supplied) wiring (field supplied)

8
* Necessary to install the External Electronic Expansion Valve Kit (Optional : CZ-P56SVK1U)

2 - 28

TD831156-00_MINI_VRF_SYS.indb 28 2012/01/31 14:38:48


Design of Mini VRF SYSTEM
3. Electrical Wiring

3-5. Important Note When Wiring for Y1 Type


Connect the wires referring to the diagram.
Y1 Type
Note that the control wirings (Low Voltages) shall be
segregated from the power supply wires (High Voltage) Connection for Solenoid
as follows: Valve Kit (for 3WAY)
1. Connect the Inter-unit control wiring to U1/U2 Remote control wiring
terminals and the remote control wire to R1/R2. (field supplied)
Then place and fix the two clasps so that the clasps Clasp
shall cover both the remote control wires, the Inter-
unit control wiring and the 3-way wiring harness as
shown in the magnified drawing.
2. Connect the grounding conductor of the incoming
power supply to the earth (ground) screw before
connecting the power supply conductors to “L1, L2” of
the terminal block.
3. Securely affix the two power supply conductors (L1, Power wiring
L2) in the wiring channel by the clamping strap as (field supplied)
shown.

Conduit
(field supplied)
1
Earth screw
Clamping clip

2
Entirely cover the control
NOTE wirings (Remote / Inter-unit
Take care not to damage the control wirings by the clasp. 3WAY connection)
Do not leave the control wirings loose. Remote control wiring and Inter-unit
control wiring (field supplied) 3

2 - 29

TD831156-00_MINI_VRF_SYS.indb 29 2012/01/31 14:38:48


Design of Mini VRF SYSTEM
4. Installation Instructions

4-1. Selecting the Installation Site for Outdoor Unit


Exhaust fan
AVOID:
heat sources, exhaust fans, etc.(Fig.2-6) Hot air

damp, humid or uneven locations Heat source


Out-
DO: door
unit
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 113°F
constantly.
Fig. 2-6
allow enough room around the unit for air intake/
exhaust and possible maintenance.(Fig.2-7)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.

Installation space
Distance between obstructions and the unit air inlet
and outlet must be as shown below. (Obstruction above unit)
1 *3 Air direction chamber
(field supply)
Inlet side C
More than 25/64" More than 25/64" B
A
2 *2
Outlet side
*4

More than Inlet side


3.3 ft. *1 More than 8 in.
(Obstruction on
*1 inlet side)
3 Fig. 2-7
(Ground)
Fig. 2-8
Concerning inlet-side distance “C” (Fig. 2-7)
4 CAUTION
The minimum for distance “C” is 6 in. if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 8 in.
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
5 tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 2-7), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-7), then the minimum distance for “A” and “B” is 6.6 ft. (Fig. 2-9).
Even if there is no wall on the outlet side, a minimum of 3.3 ft. is required.
6
In case of multiple installations
Anchor bolts
provide a solid base (concrete block, 4 × 16 in. (4 pieces)
beams or equal), a minimum of 6 in. above ground
7 level to reduce humidity and protect the unit against
possible water damage and decreased service life.
(Fig. 2-9)
use lug bolts or equal to bolt down unit, reducing
8 vibration and noise.

Fig. 2-9
2 - 30

TD831156-00_MINI_VRF_SYS.indb 30 2012/01/31 14:38:48


Design of Mini VRF SYSTEM
4. Installation Instructions

4-2. Air Discharge Chamber for Top Discharge


Be sure to install an air discharge chamber (field sup-
Air discharge
ply) in the field when:
it is difficult to keep a space of min.20 in.between
the air discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and
discharged hot air may annoy passers-by.
Refer to Fig.2-10.

4-3. Installing the Unit in Heavy Snow Areas


In locations with strong wind, snow-proof ducting
(field supply) should be fitted and direct exposure to
the wind should be avoided as much as possible.
Fig. 2-10
Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not pro- In regions with significant snowfall, the outdoor unit should
vided with a platform and snow-proof ducting: be provided with a platform and snow-proof ducting.

a) The outdoor fan may not run and damage to the


unit may occur.
1
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2
4-4. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
3
depth. (Fig. 2-11) Without snow- With snow-
proof ducting proof ducting
(2) The 2 anchoring feet of the outdoor unit should be (Low platform) (High platform)
used for the platform, and the platform should be
installed beneath the air intake side of outdoor Fig. 2-11
4
unit.
(3) The platform foundation must be firm and the unit Outdoor
must be secured with anchor bolts. Unit
5
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
Duct
the unit from being blown over.
6

Air
Intake
8
Fig. 2-12
2 - 31

TD831156-00_MINI_VRF_SYS.indb 31 2012/01/31 14:38:48


Design of Mini VRF SYSTEM
4. Installation Instructions

4-5. Dimensions of Air-Discharge Chamber


Reference diagram for air-discharge chamber (field supply)

1 Unit front, air discharge chamber

11-13/16
2 Unit left side, air discharge chamber
2
3 Unit right side, air discharge chamber
4 Reinforcement brackets, 4 locations
3 9-7/16 1-1/8

1-3/8
1-1/8 9-7/16 1 4

1-3/8
9-27/32

12-15/32
Rectangular Rectangular

21-5/32
hole hole

9-27/32

2-3/4
42-29/32
39-1/4
12-7/32
2-3/4

21-5/32
12-15/32

Rectangular Rectangular

9-27/32
1 hole hole

22-13/32
1 21-13/32 1 Unit:in.

2 4-6. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply)


6-11/16 25-31/32 4-5/16
13/32
25/32

Wind direction
1/2 1/2

3
14-31/32
15-15/16

Win
13-3/8

dire d
ctio
n
25/32

19/32

1/2
11-13/16

4
2-11/36 21-13/32 11-13/16
4-1/4

37
Wind direction
5

6 Wind
direction
Wind
direction
Wind direction
39-1/4
48-7/16

7
Wind Wind
direction direction
23/32

8
Unit:in.

2 - 32

TD831156-00_MINI_VRF_SYS.indb 32 2012/01/31 14:38:48


Design of Mini VRF SYSTEM
4. Installation Instructions

Reference for air-discharge chamber (field supply)


Required space around outdoor unit

If an air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

Min. 7-7/8
Min. 39-3/8
Unit:in.

The top and both sides must remain open.


CAUTION
If there are obstacles to the front and rear of the outdoor unit,
the obstacle at either the front or rear must be no taller than the
height of the outdoor unit.

(2) Multiple-unit installation 1


Installation in lateral rows

More than 15-3/4 2

More than 11-13/16 More than 11-13/16 3


More than 7-7/8

The front and top must remain open. 4


CAUTION
The obstacles must be no taller than the height of the outdoor unit.

Installation in front-rear rows 5


Installation with intakes facing Installation with intakes facing outlets
intakes or outlets facing outlets

More than 15-3/4


6
More than 59-1/16 More than 78-3/4

Unit: in. 8
CAUTION The front and both sides must remain open.

2 - 33

TD831156-00_MINI_VRF_SYS.indb 33 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
4. Installation Instructions

4-7. Dimensions of Snow Ducting


Reference diagram for snow-proof ducting (field supply)

Fastened by screws at 13 locations


30-3/32
1 Unit top, snow-proof vent
2 Unit left side
3 Unit right side
4
4 Unit reverse side

1 Unit: in.

25-13/32
3 11-7/8
17-15/32 2
3-3/4 19-11/16
3-31/32

5-29/32

9-3/16
9-3/16

25/32

13-5/16
28-13/16

28-13/16
17-23/32

19-11/16
47-19/32

47-19/32
1
19-11/16

ole
Fastened by screws at rh
3 locations (also on reverse side) a n cho hole)
it 2
Un ø9/3
2 (7
– 5/8

1-3/16
Fastened by screw at 1-5/8 28-3/4
15-9/32
1 location (also on reverse side) 30-5/8

3 4-8. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply)


30-3/32 7-1/16
Wind direction Wind direction

4
25/32
13/32
25-13/32

14-31/32
15-15/16

5 Unit: in.
Wind direction Wind direction
19/32
25/32

37 11-29/32
24-7/8

6
28-13/16

7 Wind direction
47-19/32
48-7/16

8 Wind direction

2 - 34

TD831156-00_MINI_VRF_SYS.indb 34 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
4. Installation Instructions

Reference diagram for snow-proof ducting – 1

Space requirements for setting – (1)

[Obstacle to the rear of unit] [Obstacle to the front of unit]


Top is open: Top is open:
(1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation

Min. H
Min. A

Min. D
Min. B
Min. C
(2) Multiple-unit installation (2 or more units)

(3) Multiple-unit installation (2 or more units)


1

Min. J
Min. I Min. I
Min. G

H I J
2
19-11/16 11-13/16 39-3/8
Min. E Min. E Min. E

Min. F

3
A B C D E F G
5-29/32 5-29/32 11-13/16 7-7/8 11-13/16 5-29/32 7-7/8

Note: In cases 2 and 3 the height of the obstacle


must be no taller than the height of the outdoor
Top is blocked by an obstacle: 4
unit.

Top is blocked by an obstacle:


5
Min. N

Min. M

Min. L

6
Min. K

M
39-3/8
N
39-3/8
7
K L
19-11/16 5-29/32

Unit: in.
8

2 - 35

TD831156-00_MINI_VRF_SYS.indb 35 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
4. Installation Instructions

Reference diagram for snow-proof ducting – 2

Space requirements for setting – (2)

[Obstacles to the front and rear of unit]


The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.

(1) Single-unit installation


Min. P
Q Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 19-11/16" or more.
Min. O

O P
39-3/8 5-29/32

1
(2) Obstacles on both sides

2
Min. 7-7/8

Q
Min. 39-3/8

Min. 11-13/16 Min. 11-13/16

3
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle
4 to the rear must be no taller than the height of the outdoor unit.
Min. 11-13/16 Q

Min. 39-3/8 Min. 59-1/16 Min. 78-3/4 Min. 7-7/8

5 Dimension Q
If a snow protection duct is
attached after the unit is
installed, verify that dimension
Q is 19-11/16" or more.
6

Unit:in.
7

2 - 36

TD831156-00_MINI_VRF_SYS.indb 36 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
4. Installation Instructions

4-9. Installing the Outdoor Unit


Use concrete or a similar material to create the base, and
ensure good drainage.
Ordinarily, ensure a base height of 2" or more. If a drain pipe
is used, or for use in cold-weather regions, ensure a height
of 6" or more at the feet on both sides of the unit.
(In this case, leave clearance below the unit for the drain Drain port (2 locations)
pipe, and to prevent freezing of drainage water in 6-47/64 25-63/64 4-3/8

25/64
cold-weather regions.) 8-5/8 5-29/32

25/32
33/64 33/64
Refer to the Fig. 2-13 for the anchor bolt dimensions.

13-13/64

14-61/64
Be sure to anchor the feet with the anchor bolts (M10 or

15-15/16
11-21/32
3/8"). In addition, use anchoring washers on the top side.
(Use large square 1-1/4"×1-1/4" SUS washers with
33/64 33/64

3/4
19/32
diameters of 3/8".) (Field supply)
4-10. Drainage Work
37
Follow the procedure below to ensure adequate draining for
the outdoor unit.
For the drain port dimensions, refer to the figure at right.
Ensure a base height of 6" or more at the feet on both sides
1
of the unit.

4-11. Routing the Tubing and Wiring


The tubing and wiring can be extended out in 4 directions: 2
front, rear, right, and down.
The service valves are housed inside the unit. To access Anchor bolt
(M10 or 3/8")
them, remove the inspection panel. (To remove the
inspection panel, remove the 3 screws, then slide the 3
panel downward and pull it toward you.) Drain port
Unit: in.
(1) If the routing direction is through the front, rear, or right,
Fig. 2-13
use a nipper or similar tool to cut out the knockout holes for
the inter-unit control wiring outlet, power wiring outlet, and 4
Inter-unit control wiring
tubing outlet from the appropriate covers A and B.
(2) If the routing direction is down, use a nipper or similar tool to Inspection panel
cut out the lower flange from cover A. Rear
5
CAUTION Route the tubing so that it does Cover B
Cover A
not contact the compressor,
Front
panel, or other parts inside the
unit. Increased noise will result if
Power supply
Right
6
Down
the tubing contacts these parts.
When routing the tubing, use a Tubing outlet
tube bender to bend the tubes.
Fig. 2-14 7

2 - 37

TD831156-00_MINI_VRF_SYS.indb 37 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
5. HOW TO PROCESS TUBING

5. HOW TO PROCESS TUBING Deburring

5-1. Connecting the Refrigerant Tubing Before After

Use of the Flaring Method


Many of conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units.In this
method, the copper tubes are flared at each end and
connected with flare nuts.

Flaring Procedure with a Flare Tool


(1) Cut the copper tube to the required length with a Fig. 2-15
tube cutter. It is recommended to cut approx. 1 –
2 ft. longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a Copper
tube reamer or file. This process is important and tubing
should be done carefully to make a good flare.
(Fig. 2-15)
1 Reamer

NOTE
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube.(Fig.2-16)
2 Fig. 2-16
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
3 tool. (Fig.2-17)
Flare nut
NOTE
Copper
A good flare should have the following characteristics: tubing
4 inside surface is glossy and smooth
edge is smooth Flare tool
tapered sides are of uniform length
5 Fig. 2-17

2 - 38

TD831156-00_MINI_VRF_SYS.indb 38 2012/01/31 14:38:49


Design of Mini VRF SYSTEM
5. HOW TO PROCESS TUBING

Caution Before Connecting Tubes Tightly


(1) Apply a sealing cap or water-proof tape to prevent dust or
water from entering the tubes before they are used.
Apply refrigerant
(2) Be sure to apply refrigerant lubricant to the matching lubricant
surfaces of the flare and union before connecting them
together. This is effective for reducing gas leaks. (Fig.2-18) Fig. 2-18
(3) For proper connection, align the union tube and flare tube
straight with each other, then screw in the flare nut lightly
at first to obtain a smooth match.(Fig.2-19)
Adjust the shape of the liquid tube using a tube bender at
the installation site and connect it to the liquid tubing side
valve using a flare.
Union Flare nut

Cautions During Brazing Fig. 2-19


Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during the
Torque wrench
brazing process. (Oxygen, carbon dioxide and Freon
are not acceptable.)
Do not allow the tubing to get too hot during brazing. Indoor unit
Spanner 1
The nitrogen gas inside the tubing may overheat,
causing refrigerant system valves to become dam-
aged. Therefore allow the tubing to cool when brazing. Outdoor unit

Use a reducing valve for the nitrogen cylinder. Fig. 2-20


2
Do not use agents intended to prevent the
formation of oxide film. These agents adversely
Tightening torque, Tube thickness
affect the refrigerant and refrigerant oil, and may Tube diameter

cause damage or malfunctions. ø1/4"


approximate
120 – 160 lbs · in. 1/32"
3
(ø6.35 mm) (140 – 180 kgf · cm) (0.8 mm)
5-2. Connecting Tubing Between Indoor and Outdoor ø3/8" 300 – 360 lbs · in. 1/32"
Units (ø9.52 mm) (340 – 420 kgf · cm) (0.8 mm)

(1) Tightly connect the indoor-side refrigerant tubing


ø1/2" 430 – 480 lbs · in. 1/32" 4
(ø12.7 mm) (490 – 550 kgf · cm) (0.8 mm)
extended from the wall with the outdoor-side tubing. ø5/8" 5/128"
590 – 710 lbs · in.
(2) To fasten the flare nuts, apply specified torque as at (ø15.88 mm) (680 – 820 kgf · cm) (1.0 mm)
right: ø3/4"
(ø19.05 mm)
870 – 1040 lbs · in.
(1000 – 1200 kgf · cm)
over 5/128"
(1.0 mm)
5
When removing the flare nuts from the tubing
connections, or when tightening them after connecting
the tubing, be sure to use 2 adjustable wrenches or Because the pressure is approximately 1.6 times
spanners as shown. (Fig. 2-20) higher than conventional refrigerant pressure, the 6
If the flare nuts are over-tightened, the flare may be use of ordinary flare nuts (type 1) or thin-walled
damaged, which could result refrigerant leakage and tubes may result in tube rupture, injury, or
cause in injury or asphyxiation to room occupants. asphyxiation caused by refrigerant leakage.

For the flare nuts at tubing connections, be sure to use In order to prevent damage to the flare caused by
7
the flare nuts that were supplied with the unit, or else over-tightening of the flare nuts, use the table
flare nuts for R410A (type 2). The refrigerant tubing above as a guide when tightening.
that is used must be of the correct wall thickness as
shown in the table at right.
When tightening the flare nut on the liquid tube, 8
use an adjustable wrench with a nominal handle
length of 7-7/8".
2 - 39

TD831156-00_MINI_VRF_SYS.indb 39 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
5. HOW TO PROCESS TUBING

5-3. Insulating the Refrigerant Tubing

Tubing Insulation
Thermal insulation must be applied to all unit tubing, Two tubes arranged together
including distribution joint (purchased separately). Liquid tubing Gas tubing
* For gas tubing, the insulation material must be heat
resistant to 248°F or above. For other tubing, it must
be heat resistant to 176°F or above.
Insulation material thickness must be 25/64" or greater.
If the conditions inside the ceiling exceed DB 86°F and Insulation
RH 70%, increase the thickness of the gas tubing Fig. 2-21
insulation material by 1 step.
Taping the flare nuts

CAUTION If the exterior of the outdoor


unit valves has been finished
with a square duct covering,
make sure you allow sufficient
space to use the valves and to
1 allow the panels to be
attached and removed. Sealer (supplied)
Insulation tape (white)
Wind the white insulation tape around the flare nuts at the (supplied)
Flare insulator (supplied)
2 gas tube connections. Then cover up the tubing
connections with the flare insulator, and fill the gap at the Tube insulator
Unit side (not supplied)
union with the supplied black insulation tape. Finally, insulator Heat resistant
248°F or above
fasten the insulator at both ends with the supplied vinyl
3 clamps. (Fig.2-22) Flare nut
Vinyl clamps (supplied)

Fig. 2-22

2 - 40

TD831156-00_MINI_VRF_SYS.indb 40 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
5. HOW TO PROCESS TUBING

5-4. Taping the Tubes


(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped
together with armoring tape in 1 bundle. To prevent
the condensation from overflowing the drain pan,
keep the drain hose separate from the refrigerant
tubing. Clamp
(2) Wrap the armoring tape from the bottom of the Insulated tubes Drain hose
outdoor unit to the top of the tubing where it enters
the wall. As you wrap the tubing, overlap half of
each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. each ft. (Fig.2-23)

NOTE
Do not wind the armoring tape too tightly since this will Fig. 2-23
decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the
bundle and drips clear of the unit and the tubing.
1
Apply putty here
5-5. Finishing the Installation
After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent
2
rain and draft from entering. (Fig.2-24)
Tubing

Fig. 2-24
3

2 - 41

TD831156-00_MINI_VRF_SYS.indb 41 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
6. AIR PURGING

6. AIR PURGING Manifold gauge

Air and moisture in the refrigerant system may have


undesirable effects as indicated below.
pressure in the system rises
operating current rises
cooling (or heating) efficiency drops
moisture in the refrigerant circuit may freeze and block
capillary tubing
water may lead to corrosion of parts in the refrigerant Fig.2-25
system
Therefore, the indoor unit and tubing between the indoor Vacuum pump
and outdoor unit must be leak tested and evacuated to Outlet
remove any noncondensables and moisture from the Inlet
system.
Air Purging with a Vacuum Pump (for Test Run)
Preparation
Check that each tube (both liquid and gas tubes) between
the indoor and outdoor units has been properly connected
1 and all wiring for the test run has been completed. Remove
Fig.2-26

the valve caps from both the gas tube and liquid tube
service valves on the outdoor unit. Note that both liquid and Manifold valve
gas tube service valves on the outdoor unit are kept closed
2 at this stage. Pressure
gauge Lo Hi

Leak test Charge hose


3 (1) Attach a manifold valve (with pressure gauges) and dry
nitrogen gas cylinder to this service port with charge Cylinder
valve
hoses.
Nitrogen gas cylinder
4 CAUTION Use a manifold valve for air
(In vertical standing
position)
purging. If it is not available, use
a stop valve for this purpose. The
“Hi” knob of the manifold valve
5 must always be kept closed.
Service port ø5/16"

(2) Pressurize the system to no more than


512 psig (36 kgf/cm2G) with dry nitrogen gas and close Open

6 the cylinder valve when the gauge reading reaches Gas


512 psig (36 kgf/cm2G). Then, test for leaks with liquid tube
Close
soap. Outdoor unit

7 CAUTION To avoid nitrogen entering the


refrigerant system in a liquid state,
Open

Liquid
the top of the cylinder must be tube
higher than the bottom when you Close

8 pressurize the system. Usually, the


cylinder is used in a vertical Fig.2-27
standing position. (Refer to the
previous page.)
2 - 42

TD831156-00_MINI_VRF_SYS.indb 42 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
6. AIR PURGING

(3) Do a leak test of all joints of the tubing (both indoor and
outdoor) and both gas tube and liquid tube service
valves. Bubbles indicate a leak. Wipe off the soap with a
Manifold valve
clean cloth after the leak test.
(4) After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose Pressure
gauge Lo Hi
connector at the nitrogen cylinder. When the system
pressure is reduced to normal, disconnect the hose from
the cylinder.

Evacuation
(1) Attach the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit. Confirm that the “Lo” knob of the manifold
valve is open. Then, run the vacuum pump. The
operation time for evacuation varies with the tubing Vacuum pump
length and capacity of the pump. The following table
Service port ø5/16"
shows the amount of time for evacuation:

Open
1
Required time for evacuation
when 30 gal/h vacuum pump is used Gas
tube
If tubing length is If tubing length is
Close
less than 49 ft.
45 min. or more
longer than 49 ft.
90 min. or more
Outdoor unit
2
Open

NOTE Liquid
tube
The required time in the above table is calculated based on Close 3
the assumption that the ideal (or target) vacuum condition is
Fig. 2-28
less than –14.7 psig (–755 mmHg, 5 Torr).

(2) When the desired vacuum is reached, close the “Lo” 4


knob of the manifold valve and turn off the vacuum pump.
Confirm that the gauge pressure is under –14.7 psig
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum
pump operation. 5

2 - 43

TD831156-00_MINI_VRF_SYS.indb 43 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
6. AIR PURGING

CAUTION
Use a cylinder designed for
Manifold valve
use with R410A.

Pressure
Charging additional refrigerant gauge Lo Hi

Charging additional refrigerant (calculated from the


liquid tube length as shown in Section 2-7 Valve
“Additional Refrigerant Charge”) using the liquid
tube service valve. (Fig. 2-29)
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot
be charged at once, charge the remaining
refrigerant in liquid form by using the gas tube Liquid
service valve with the system in cooling operation
mode at the time of test run. (Fig. 2-30)
R410A
Finishing the job
(1) With a hex wrench, turn the liquid tube service Close
1 valve stem counter-clockwise to fully open the
Gas
valve. tube
(2) Turn the gas tube service valve stem Close
Outdoor unit
counter-clockwise to fully open the valve.
2 Open
To avoid gas from leaking when
CAUTION Liquid
removing the charge hose, tube
make sure the stem of the gas Close
3 tube is turned all the way out
(“BACK SEAT” position).
Fig. 2-29
(3) Loosen the charge hose connected to the gas
4 tube service port (for ø5/16" tube) slightly to
release the pressure, then remove the hose.
(4) Replace the service port cap on the gas tube
service port and fasten the cap securely with an
5 adjustable wrench or box wrench. This process is
very important to prevent gas from leaking from Open
the system.
Gas
(5) Replace the valve caps at both gas tube and liquid tube
6 tube service valves and fasten them securely. Open
Outdoor unit
This completes air purging with a vacuum pump.
Theair conditioner is now ready for a test run. Close

7 Liquid
tube
Open

Fig. 2-30
8

2 - 44

TD831156-00_MINI_VRF_SYS.indb 44 2012/01/31 14:38:50


Design of Mini VRF SYSTEM
7. Optional Parts

7-1. Distribution Joint Kits


CZ-P160BK1U (for R410A)
Size of connection point on each part
How to Attach Distribution Joint (Shown are inside diameters of tubing)
1. Accompanying Parts
Size mm Inch
Check the contents of your distribution joint kit.
Part A o19.05 3/4
2. Distribution Joint Kits (with insulation)
Part B o15.88 5/8
Parts Kit 1 Parts Kit 2
4-21/64 4-21/64 Part C o12.7 1/2
3-13/16 3-13/16 Part D o9.52 3/8
C
B Part E o6.35 1/4
B D C C DE
A A
C
B
2-53/64

2-53/64
Distribution Distribution Straight tubing 5-15/16" or larger
Joint Joint

C D
E

Insulation unit : inch Insulation unit : inch

3. Making Branch Connections


For branching tubes, install 5-15/16" or larger (including reducer) Fig. 2-31
straight tubing up to the point where the tube branches Stopper(boss) Cutting point
1
(or after the point where the tubes join together). (Fig. 2-31)
Using a tube cutter, cut the joints at the diameter required to match
the outside diameter of the tubing you are connecting.
(This is usually done at the installation site.)
2
Make space as long as possible.
The tube diameter depends on the total capacity of the indoor unit. Insertion length of the
Note that you do not have to cut the joints if it already matches the connecting tube
tubing end size. For size selection of the tube diameter, refer to the Fig. 2-32
installation instructions provided with the outdoor unit.
3
NOTE Indoor unit
Outdoor unit Side
Avoid forceful cutting that may harm the shape of the joints or tubing. Side
(Inserting the tubing will not be possible if the tube shape is not proper.)
15 to 30
4
Cut off as far away from stopper as possible. (Fig. 2-32) upward slant

After cutting the joints, be sure to remove burrs on the inside of the In case of horizontal position
joints. (If the joints have been squashed or dented badly, reshaped
them using a tube spreader.)
5
Make sure there is no dirt or other foreign substances inside the
distribution joint.
The distribution joint can be either horizontal or vertical. (Fig. 2-33)
In the case of horizontal, the L-shaped tubing must be slanted slightly
6
upward (15 to 30 ).
When brazing a pipe E to the reducer of which middle pipe inner In case of vertical position

dimension is D as shown above chart, cut the middle pipe as long as (directed upward)
7
possible so that the pipe E can be inserted. Fig. 2-33
When brazing, replace air inside the tube with nitrogen gas to prevent copper oxide from forming.
To insulate the distribution joint, use the supplied tubing insulation. (If using insulation other than that supplied,
make sure that its heat resistance is 248 F or higher.) 8
For additional details, refer to the installation instructions provided with the outdoor unit.

2 - 45

TD831156-00_MINI_VRF_SYS.indb 45 2012/01/31 14:38:51


– MEMO –

2 - 46

TD831156-00_MINI_VRF_SYS.indb 46 2012/01/31 14:38:51


Control of Mini VRF SYSTEM
Contents

3. CONTROL OF MINI VRF SYSTEM


1. Main Operating Functions
2. Wireless Remote Controller
3. Timer Remote Controller
4. Simplified Remote Controller
5. System Controller
6. Schedule Timer
7. Intelligent Controller (CZ-256ESMC1U)
8. Communication Adaptor (CZ-CFUNC1U)
9. Remote Sensor
10. LonWorks Interface (CZ-CLNC1U)
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)

3-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/25 14:07:53


– MEMO –

3-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/25 14:07:53


Mini VRF SYSTEM
Contents Unit Specifications

4. MINI VRF SYSTEM UNIT SPECIFICATIONS


1. Outdoor Unit ..................................................................................................................... 4-2
1-1. Specifications ............................................................................................................. 4-2
1-2. AHRI Registration Values .......................................................................................... 4-4
1-3. Dimensional Data ...................................................................................................... 4-5
1-4. Refrigerant Flow Diagram............................................................................................ 4-6
1-5. Sound Data ................................................................................................................. 4-7
2. 4-Way Cassette Type (U1 Type)
3. 4-Way Cassette 60×60 Type (Y1 Type)
4. 1-Way Cassette Type (D1 Type)
5. Low Silhouette Ducted Type (F1 Type)
6. Slim Low Static Ducted Type (M1 Type)
7. High Static Pressure Ducted Type (E1 Type)
8. Ceiling Type (T1 Type)
9. Wall Mounted Type (K1 Type)
10. Floor Standing Type (P1 Type)
11. Concealed Floor Standing Type (R1 Type)
12. Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type 1
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)

4-1

TD831156-00_MINI_VRF_SYS.indb 1 2011/12/12 17:31:22


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

1-1. Specifications
Unit specifications (A)
1
MODEL No. Outdoor Unit U-36LE1U6, U-36LE1U6E*
POWER SOURCE 208 - 230 V / 1ø / 60 Hz
PERFORMANCE Cooling Heating
BTU / h 38,200 42,700
Capacity
kW 11.2 12.5
Air circulation (Hi) CFM 3,530
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 14.6 13.6 14.6 13.6
Max. running amperes * A 23.6 23.6 – –
Power input kW 2.76 2.76 2.88 2.88
Max. power input kW 4.85 4.85 – –
Power factor % 91 88 95 92
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1

1 FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Sensor temp. recall function
Service function
2 Past service warnings recall function
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Power level 67
Operation sound (Hi) dB-A
3 Pressure level 51
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Refrigerant tubing
4 Limit of tubing length ft. (m) 492 (150)
Limit of elevation difference Outdoor unit is higher than indoor unit : 164 (50)
ft. (m)
between the 2 units Outdoor unit is lower than indoor unit : 131 (40)
Refrigerant tube Liquid tube in. (mm) 3/8 (9.52)
5 diameter Gas tube in. (mm) 5/8 (15.88)
Refrigerant tubing kit / Joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions

6 Unit dimensions
Height
Width
in. (mm)
in. (mm)
48-7/16 (1230)
37 (940)
52-13/32 (1331)
40 (1016)
Depth in. (mm) 13-13/32 (340) 16-11/32 (415)
Net weight lbs. (kg) 229 (104)

7 Shipping weight lbs. (kg)


3 3
247 (112)
Shipping volume ft (m ) 19.8 (0.56)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
8 Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
* Outdoor unit model name ended with letter “E”
Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”.
4-2

TD831156-00_MINI_VRF_SYS.indb 2 2011/12/12 17:31:23


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

Unit specifications (B)


1
MODEL No. Outdoor Unit U-52LE1U6, U-52LE1U6E*
POWER SOURCE 208 - 230 V / 1ø / 60 Hz
PERFORMANCE Cooling Heating
BTU / h 52,900 60,000
Capacity
kW 15.5 17.6
Air circulation (Hi) CFM 3,530
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 23.5 21.9 23.5 21.9
Max. running amperes * A 28.0 28.0 – –
Power input kW 4.57 4.57 4.58 4.58
Max. power input kW 5.72 5.72 – –
Power factor % 93 91 94 91
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES 1
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Sensor temp. recall function
Service function
Past service warnings recall function 2
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Power level 68
Operation sound (Hi) dB-A
Pressure level 52 3
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Refrigerant tubing
Limit of tubing length ft. (m) 492 (150) 4
Limit of elevation difference Outdoor unit is higher than indoor unit : 164 (50)
ft. (m)
between the 2 units Outdoor unit is lower than indoor unit : 131 (40)
Refrigerant tube Liquid tube in. (mm) 3/8 (9.52)
diameter Gas tube in. (mm) 3/4 (19.05) 5
Refrigerant tubing kit / Joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions

Unit dimensions
Height
Width
in. (mm)
in. (mm)
48-7/16 (1230)
37 (940)
52-13/32 (1331)
40 (1016)
6
Depth in. (mm) 13-13/32 (340) 16-11/32 (415)
Net weight lbs. (kg) 229 (104)
Shipping weight lbs. (kg)
3 3
247 (112) 7
Shipping volume ft (m ) 19.8 (0.56)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100% 8
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
* Outdoor unit model name ended with letter “E”
Refer to the Section 1 “2. Salt-Air Damage Resistant Specifications”.
4-3

TD831156-00_MINI_VRF_SYS.indb 3 2011/12/12 17:31:24


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

1-2. AHRI Registration Values

Cooling Heating
Outdoor Unit Indoor Unit EER SEER HSPF
Capacity Capacity
Models Types
BTU/h 95°F BTU/h
Ducted 37,000 9.60 13.1 38,500 7.8
U-36LE1U6(E) Non Ducted 39,000 11.50 17.0 43,000 9.8
Mixed Non-Ducted and Duced 38,000 10.55 15.05 40,750 8.8
Ducted 51,500 9.40 14.6 57,500 7.7
U-52LE1U6(E) Non Ducted 52,000 10.20 17.4 58,500 9.6
Mixed Non-Ducted and Duced 51,750 9.80 16.0 58,000 8.65

4-4

TD831156-00_MINI_VRF_SYS.indb 4 2011/12/12 17:31:24


1 Installation anchoring hole (4-R6.5 or R1/4"), anchor bolt: M10 or 13/32''
2 Refrigerant tubing (liquid tube), flared connection ø3/8'' (ø9.52)
3 Refrigerant tubing (gas tube), flared connection ø5/8'' (ø15.88) 2 x ø32 or ø1/4'' holes (holes for drain)
Of the 4 ø32 or ø1/4'' holes, use 1 of the 2 holes specified
4 Refrigerant tubing port

TD831156-00_MINI_VRF_SYS.indb 5
for drain use to install the drain port.
5 Electrical wiring port ø1-3/8'' (ø35)
Use rubber plugs to seal the remaining 3 holes.
6 Electrical wiring port ø1-7/64'' (ø28)
1. Outdoor Unit

7 Electrical wiring port ø55/64'' (ø22)


1-3. Dimensional Data

Electrical wiring port ø33/64'' (ø13)


U-52LE1U6, U-52LE1U6E
U-36LE1U6, U-36LE1U6E

11-11/32
10-25/32
9 Auxiliary connection tube ø5/8'' to ø3/4'' (ø15.88 to ø19.05) 6 hp only

6-11/16 25-31/32 4-5/16


2- 2-7/32
3/4 8-5/8 5-29/32
4-19/32
Air intake
1/2 1/2

25/32
13/32
R1
-3
/1 6
2-3/8

13-3/8
5/16

14-31/32
15-15/16

11-21/32
Air

4-5
1/2 1/2 2-7/16 R
discharge

13/32
19/32
3/
1 4
37

3 7
Air Air
discharge intake
7
9
3-3/16

6 3-7/16
7

48-7/16
3-29/32 8 5 2-1/4
8
25/32 1-13/16
7 4 6
7 5 7
6-13/16

4
23-5/8
5-9/16

22-9/16

23/32
7-25/32

1-13/32
6 5 8 2-3/8
4
4-3/4

5-1/2
7-3/4
2-27/32
8-9/32
7-8/32

6-5/8

6-9/16
8-15/16

2-25/32
4-23/32
6-11/16
5-29/32

Unit: inch 2-3/8 4-11/32


Unit Specifications
Mini VRF SYSTEM

5-1/8
For R410A only

8
7
6
5
4
3
2
1

2011/12/12 17:31:24
Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

1-4. Refrigerant Flow Diagram

U-36LE1U6
U-36LE1U6E
U-52LE1U6
U-52LE1U6E Suction

4-6

TD831156-00_MINI_VRF_SYS.indb 6 2011/12/12 17:31:24


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

1-5. Sound Data

(1) Sound Power Level

U-36LE1U6, U-36LE1U6E

Model U-36LE1U6, U-36LE1U6E


Sound Power 67 dB (A)
Level Cooling
Condition

90

80

NC – 70
1
70
Sound Power Level (dB)

60
NC – 60
2

50
NC – 50 3

40
NC – 40
4
30
NC – 30
5
20
NC – 20

6
10
63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz)
7
NOTE
1. dBA = A – weighted sound power level (A – scale according to IEC)
2. Reference acoustic intensity 0 dB = 10–13 W/ft2
8

4-7

TD831156-00_MINI_VRF_SYS.indb 7 2011/12/12 17:31:25


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

U-52LE1U6, U-52LE1U6E

Model U-52LE1U6, U-52LE1U6E


Sound Power 68 dB (A)
Level Cooling

Condition

90

80

NC – 70
70
Sound Power Level (dB)

1
60
NC – 60

2
50
NC – 50

3 40
NC – 40

4 30
NC – 30

20
5 NC – 20

10
63 125 250 500 1000 2000 4000 8000
6 Frequency at center of sound pressure band (Hz)

NOTE
1. dBA = A – weighted sound power level (A – scale according to IEC)
7 2. Reference acoustic intensity 0 dB =10–13 W/ft2

4-8

TD831156-00_MINI_VRF_SYS.indb 8 2011/12/12 17:31:25


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

(2) Sound Pressure Level

U-36LE1U6, U-36LE1U6E

Model U-36LE1U6, U-36LE1U6E


Sound Pressure Level Front 51 dB (A)
Cooling Quiet Mode 48 dB (A)
Condition 3.3 ft. in front at height of 4.9 ft.

Front

Quiet Mode
90

80 1

70
NC – 70
2
Octave Band Level (dB)*

60 NC – 60
3
50

NC – 50
4
40
NC – 40

5
30
NC – 30

Approximate
minimum audible
6
20 limit for continuous NC – 20
noise

10
7
63 125 250 500 1000 2000 4000 8000
Overall
Frequency at center of sound pressure band (Hz)
* 0 dB = 0.0002 µbar
8

4-9

TD831156-00_MINI_VRF_SYS.indb 9 2011/12/12 17:31:25


Mini VRF SYSTEM
1. Outdoor Unit Unit Specifications

U-52LE1U6, U-52LE1U6E

Model U-52LE1U6, U-52LE1U6E


Sound Pressure Level Front 52 dB (A)
Cooling Quiet Mode 49 dB (A)
Condition 3.3 ft. in front at height of 4.9 ft.

Front
Quiet Mode
90

80

1 NC – 70
70
Octave Band Level (dB)*

2 60 NC – 60

3 50

NC – 50

40
4 NC – 40

30
NC – 30
5
Approximate
minimum audible
20
limit for continuous NC – 20
noise
6
10
63 125 250 500 1000 2000 4000 8000
Overall
Frequency at center of sound pressure band (Hz)
7 * 0 dB = 0.0002 µbar

4 - 10

TD831156-00_MINI_VRF_SYS.indb 10 2011/12/12 17:31:25


Test Run
Contents

5. TEST RUN
1. Preparing for Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
2. Test Run Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
3. Outdoor Unit PCB Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
4. Auto Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5. Remote Controller Test Run Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
6. Caution for Pump Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
7. Meaning of Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13

5-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/31 14:38:20


Test Run
1. Preparing for Test Run

● Before attempting to start the air conditioner,


check the following.
(1) All loose matter is removed from the cabinet,
especially steel filings, bits of wire, and clips. ON

(2) The control wiring is correctly connected and all (Power must be turned ON
electrical connections are tight. at least 5 hours before
attempting test run)
(3) The transportation pads for the indoor fan have
been removed. If not, remove them now.
(4) The power has been connected to the unit for at
Power mains switch
least 5 hours before starting the compressor. The
bottom of the compressor should be warm to the
Fig. 5-1
touch and the crankcase heater around the feet of
the compressor should be hot to the touch.
(Fig. 5-1)
(5) Both the gas and liquid tube service valves are
open. If not, open them now. (Fig. 5-2)
(6) Request that the customer be present for the trial
run.
1 Explain the contents of the instruction manual,
then have the customer actually operate the
system.

2 (7) Be sure to give the instruction manual and


warranty certificate to the customer.
(8) When replacing the control PCB, be sure to make
all the same settings on the new PCB as were in
3 use before replacement.
The existing EEPROM is not changed, and is
connected to the new control PCB.

8 Liquid tube service cap Gas tube service cap

Fig. 5-2
5-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/31 14:38:20


Test Run
2. Test Run Procedure

Items to Check Before the Test Run


1. Turn the remote power switch on at least 5 hours before
the test, in order to energize the crankcase heater.
2. Turn the outdoor service valves
Recheck the items to check before the test run. (2 locations) to the full-open positions.
● Use caution when making the settings. If there are
<Outdoor unit control PCB> duplicated system addresses, or if the settings for
Unit No. setting switch Set the No. of indoor units. the Nos. of the indoor units are not consistent, an
(S004)
alarm will occur and the system will not start.
● These settings are not made on the indoor unit PCB.
Are the inter-unit control NO CASE 1
(Check the link wiring.) wires connected to more than 1
refrigerant system?
<Outdoor unit control PCB> YES
Unit No. setting switch Set the system address.
(S002 and S003)

When multiple outdoor units exist, disconnect the


Refer to Fig. 5-4 terminals extended from the shorted plugs
(CN33) at all outdoor unit PCBs except for 1.‫ޓ‬
Alternatively, move the sockets to the OPEN side.

Is it possible to turn
YES CASE 2
ON the power only for the 1 refrigerant
system where the test run will
be performed?
1
Turn ON the indoor and outdoor unit
NO power for that refrigerant system only.

Make necessary

NO
Will automatic address setting be
performed in Heating mode?
corrections. Short-circuit the automatic address
pin (CN51) on the outdoor unit PCB 2
for 1 second or longer, then release it.
YES Turn OFF the indoor and
CASE 3B CASE 3A outdoor unit power.
Is it OK to start the Is it OK to start the LED 1 and 2 blink alternately
(about 2 or 3 minutes).
compressors? compressors? Check the alarm contents.
3
Turn ON the indoor and Turn ON the indoor and
outdoor unit power. outdoor unit power. NO
Are LEDs 1 and 2 on the
*2 *2 Make necessary
outdoor unit PCB OFF?
Short-circuit the mode change pin corrections Refer to “Table of
Short-circuit the automatic
(CN50) on the outdoor unit PCB.
At the same time, short-circuit the
automatic address pin (CN51) for 1
address pin (CN51) on the
outdoor unit PCB for 1
Self-Diagnostic Functions and
Description of Alarm Displays.” YES 4
second or longer, then Turn OFF the indoor
second or longer, then pull it out. release it. and outdoor unit

*3 *3
Start indoor and outdoor unit Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
heating operation. LED 1
and 2 blink alternately.
Check the alarm
contents. 5
*2 A minimum of 5 hours must have passed
after the power was turned ON to the
outdoor unit.
Are LEDs 1 and 2 on the NO
outdoor unit PCB OFF?
*3 All indoor units operate in all refrigerant
systems where the power is ON. 6
YES

Check that test run preparation is OK.


(Do not allow the short-circuited pins to remain short-circuited.) 7
Set the wired remote controller for test run.

Refer to the remote


controller test-run
settings.
Does system
operate?
NO Check and make corrections according to
“Table of Self Diagnostic Functions.”
8
YES
Return remote control to normal mode Fig. 5-3
End test run.
5-3

TD831156-00_MINI_VRF_SYS.indb 3 2012/01/31 14:38:21


Test Run
3. Outdoor Unit PCB Setting

2
CN33

4
CN51
CN50
5 S003

S002 D043
(LED2)
S004
D042
6 (LED1)

8
Fig. 5-4

5-4

TD831156-00_MINI_VRF_SYS.indb 4 2012/01/31 14:38:21


Test Run
3. Outdoor Unit PCB Setting

Examples of the No. of indoor units settings

Indoor unit setting (S004)


No. of indoor units
(Rotary switch, red)
1
1 unit (factory setting) Set to 1

2
2 units Set to 2

9 units 9 Set to 9

Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)
System address (S003) System address (S002)
System address No. (2P DIP switch, blue) (Rotary switch, black)
10 20 ON
ON 1
System 1 (factory setting) Both OFF Set to 1
1 2 OFF

1
ON ON
1
System 11 1 ON Set to 1
1 2 OFF
ON ON
1
System 21 2 ON Set to 1
1 2 OFF
ON ON
0
System 30 1 & 2 ON Set to 0
1 2 OFF
2

5-5

TD831156-00_MINI_VRF_SYS.indb 5 2012/01/31 14:38:21


Test Run
4. Auto Address Setting

Basic wiring diagram: Example (1)


• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 unit settings

(S004)
System address No. of indoor units
(system 1 setting) (8 units setting)
(S003) (S002) (S004)
ON ON 1
1 2 8
OFF

Unit
Outdoor Unit
No. 1

Inter-unit control wiring

1 Indoor Unit 1-1 1-2 1-3 1-8


Remote control
Remote controller communication wiring

Fig. 5-5
2
(1) Automatic Address Setting from the Outdoor Unit
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the
ON
DIP switch (S003) is set to “0.” ON (These are the settings at the time of factory shipment.)
3 1 2 OFF

2. To set the number of indoor units that are connected to the outdoor unit to 8 on the outdoor unit control PCB, set

4 the No. of indoor units rotary switch (S004) to “8.”

3. Turn ON the power to the indoor and outdoor units.


4. On the outdoor unit control PCB, short-circuit the automatic address pin (CN51) for 1 second or longer, then
5 release it.

(Communication for automatic address setting begins.)
↓ * To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
6 The LED that indicates that automatic address setting is in progress turns OFF and the process is
stopped.

(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
7 ↓
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 3, then use the remote controller and
complete automatic address setting.

8 Refer to “Automatic Address Setting from the Remote Controller.”

5-6

TD831156-00_MINI_VRF_SYS.indb 6 2012/01/31 14:38:22


Test Run
4. Auto Address Setting

Basic wiring diagram: Example (2)

• If link wiring is used * When multiple outdoor units exist, remove the socket that
is used to short-circuit the terminal plug (CN33) from all
outdoor unit PCBs except for 1.
Alternatively, move the sockets to the “OPEN” side .
No. 1 unit settings

System address No. of indoor units


(system 1 setting) (6 units setting)
(S003) (S002) (S004)
ON ON 1

6
1 2
OFF

Leave the socket


Outdoor unit Unit that is used to
system 1 No. 1 short-circuit the
terminal plug.
(CN33)
Inter-unit control wiring

1
Indoor unit 1-1 1-2 1-3 1-6
Remote control
Remote communication wiring
controller

No. 2 unit settings


2
System address No. of indoor units
(system 2 setting) (7 units setting)
3
7
(S002) (S003)
(S004)
ON ON
2

7
1 2
OFF

4
Unit Leave the socket
Outdoor unit that is used to open
system 2 No. 1
circuit the terminal
plug (CN33). 5
Inter-unit control wiring

Indoor unit 2-1 2-2 2-7


To other system
link wiring Remote control
6
Remote communication wiring
controller

Make settings as appropriate for the cases listed below.


(Refer to the instructions on the following pages.) 7
• Indoor and outdoor unit power can be turned ON for each system separately. Case 1
• Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic address setting in Heating mode Case 2

Automatic address setting in Cooling mode Case 3 8


Fig. 5-6
5-7

TD831156-00_MINI_VRF_SYS.indb 7 2012/01/31 14:38:22


Test Run
4. Auto Address Setting

Case 1 Automatic Address Setting (no compressor operation)


● Indoor and outdoor unit power can be turned ON for each system separately.

Indoor unit addresses can be set without operating the compressors.

Automatic Address Setting from Outdoor Unit


1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the
DIP switch (S003) is set to “0.” ON ON (These are the settings at the time of factory shipment.)

1 2 OFF
2. To set the number of indoor units that are connected to the outdoor unit to 6 on the outdoor unit control PCB, set
the No. of indoor units rotary switch (S004) to “6.”

3. At the outdoor unit where all indoor and outdoor unit power has been turned ON, short-circuit the automatic
address pin (CN51) for 1 second or longer, then pull it out.

(Communication for automatic address setting begins.)
↓ * To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.

1 (Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)

4. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 3
in the same way to complete automatic address settings for all systems.
2 ↓
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller
3 complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”

5-8

TD831156-00_MINI_VRF_SYS.indb 8 2012/01/31 14:38:22


Test Run
4. Auto Address Setting

Case 2 Automatic Address Setting in Heating Mode


● Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.

Automatic Address Setting from Outdoor Unit


1. Perform steps 1 and 2 in the same way as for Case 1 .
2. Turn the indoor and outdoor unit power ON at all systems.

3. To perform automatic address setting in Heating mode , on the outdoor unit control PCB in the refrigerant
system where you wish to set the addresses, short-circuit the automatic address pin (CN51) for 1 second or
longer, then pull it out.
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for
more than one system at the same time.)

(Communication for automatic address setting begins, the compressors turn ON, and automatic address
setting in heating mode begins.)
(All indoor units operate.)
↓ * To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. 1
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit
control PCB turn OFF.) 2
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or
longer, then pull it out.

(Repeat the same steps to complete automatic address setting for all units.) 3

5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller 4
complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”

5-9

TD831156-00_MINI_VRF_SYS.indb 9 2012/01/31 14:38:23


Test Run
4. Auto Address Setting

Case 3 Automatic Address Setting in Cooling Mode


● Indoor and outdoor unit power cannot be turned ON for each system separately.
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.

Automatic Address Setting from Outdoor Unit


1. Perform steps 1 and 2 in the same way as for Case 1 .
2. Turn the indoor and outdoor unit power ON at all systems.

3. To perform automatic address setting in Cooling mode , on the outdoor unit control PCB in the refrigerant
system where you wish to set the addresses, short-circuit the mode change 2P pin (CN50). At the same time,
short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. (Be sure to perform this
process for one system at a time. Automatic address settings cannot be performed for more than one system at
the same time.)

(Communication for automatic address setting begins, the compressors turn ON, and automatic address
setting in Cooling mode begins.)
1 (All indoor units operate.)
↓ * To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit
2 control PCB turn OFF.)
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or
longer, then pull it out.

3 (Repeat the same steps to complete automatic address setting for all units.)

5. Operation from the remote controllers is now possible.
4 * Automatic address setting in Cooling mode cannot be done from the remote controller.

Automatic Address Setting from the Remote Controller


Selecting each refrigerant system individually for automatic address setting
5 ---Automatic address setting for each system: Item code “A1”
● Press the remote controller timer time button and button at the
same time. (Press and hold for 4 seconds or longer.)
● Next, press either the temperature setting or button.
6 (Check that the item code is “A1.”)
● Use either the or button to set the system No. to perform
automatic address setting.
● Then press the button.
7 (Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the sys-
tem returns to normal stopped status.) <Approximately 4 – 5 minutes is
required.>
8 (During automatic address setting, “ ” is displayed on the remote controller. This message disappears
when automatic address setting is completed.)
● Repeat the same steps to perform automatic address setting for each successive system.
5 - 10

TD831156-00_MINI_VRF_SYS.indb 10 2012/01/31 14:38:23


Test Run
4. Auto Address Setting

Display during automatic address setting


● On outdoor unit PCB
LED 2 1
* Do not short-circuit the automatic address setting pin (CN51) again while automatic
address setting is in progress. Doing so will cancel the setting operation and will cause
Blink alternately LEDs 1 and 2 to turn OFF.

* When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.
* LED 1 is D042. LED 2 is D043.
* If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then
perform automatic address setting again.

● Display details of LEDs 1 and 2 on the outdoor unit control PCB


( : ON :: Blinking : OFF)
LED 1 LED 2 Display meaning
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor
units in that system is possible.
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are
confirmed in that system; however, the number of indoor units does not match the number that was set.

Alternating
Automatic address setting is in progress.
1
Automatic address setting completed.
At time of automatic address setting, the number of indoor units did not match the number that was set.
Simultaneous (when indoor units are operating) indication appears on the displa y.

Alternating Refer to Table of Self-Diagnostic Functions and Description of Alarm Displays. 2


Note: indicates that the solenoid is fused or that there is a C T (current detection circuit) failure (current is detected when
the compressor is OFF).

● Remote controller display during automatic setting 3


is blinking

5 - 11

TD831156-00_MINI_VRF_SYS.indb 11 2012/01/31 14:38:23


4. Auto Address Setting Test Run
5. Remote Controller Test Run Settings

Request concerning recording the indoor/outdoor unit combination Nos.


After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location
(next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3… (Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.

Checking the indoor unit addresses


Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the button and button for 4 seconds or
longer (simple settings mode).
2. The address is displayed for the indoor unit that is connected to the
remote controller.
(Only the address of the indoor unit that is connected to the remote
controller can be checked.)
3. Press the button again to return to normal remote controller Number changes to indicate which indoor unit is
mode. currently selected.
1 <If multiple indoor units are connected to 1 remote controller
Indoor unit address

(group control)>
1. Press and hold the button and button for 4 seconds or
2 longer (simple settings mode).
2. “ALL” is displayed on the remote controller.
3. Next, press the button.
4. The address is displayed for 1 of the indoor units which is
3 connected to the remote controller. Check that the fan of that indoor
unit starts and that air is discharged.
5. Press the button again and check the address of each
indoor unit in sequence. Number changes to indicate which indoor unit is

4 6. Press the button again to return to normal remote controller


currently selected.

Indoor unit address


mode.

5. Remote Controller Test Run Settings


5 1. Press the remote controller button for 4 seconds or longer. Then press the button.
● “TEST” appears on the LCD display while the test run is in progress.
● The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
6 2. The test run can be performed using the HEAT, COOL, or FAN operation modes.
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after
operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote controller display.
7 (Refer to “2-6. Meaning of Alarm Messages” and correct the problem.)
4. After the test run is completed, press the button again. Check that “TEST” disappears from the remote
controller's display.
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
8 60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type
ceiling panel has not been installed. (“P09” display does not occur.)
5 - 12

TD831156-00_MINI_VRF_SYS.indb 12 2012/01/31 14:38:24


6. Caution for Pump Down Test Run
7. Meaning of Alarm Messages

6. Caution for Pump Down


Pump down means refrigerant gas in the system
is returned to the outdoor unit. Pump down is used
when the unit is to be moved, or before servicing the
refrigerant circuit.

● This outdoor unit cannot collect more than the rated refrigerant amount as shown
CAUTION by the nameplate on the back.
● If the amount of refrigerant is more than that recommended, do not conduct pump
down. In this case use another refrigerant collecting system.

7. Meaning of Alarm Messages


Table of Self-Diagnostics Functions and Description of Alarm Displays
Alarm messages are indicated by the blinking of LED 1 and 2 (D042, D043) on the outdoor unit PCB. They are also displayed
on the wired remote controller.
● Viewing the LED 1 and 2 (D042 and D043) alarm displays

LED 1 LED 2 Alarm contents

Alternating
Alarm display
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
1
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.

( : Blinking)
Alarm is “P17.”
2
Alarm
Possible cause of malfunction message
Serial commu-
nication errors
Remote controller is detecting
error signal from indoor unit.
Error in receiving serial communication signal.
(Signal from main indoor unit in case of group control) <E01>
3
Mis-setting Ex: Auto address is not completed.
Error in transmitting serial communication signal. <E02>
Indoor unit is detecting error signal from remote controller (and system controller).
Indoor unit is detecting error Error in receiving serial communication signal.
<<E03>>
4
signal from outdoor unit. When turning on the power supply, the number of connected E04
indoor units does not correspond to the number set. (Except R.C.
address is “0.”)
Error of the outdoor unit in receiving serial communication signal
from the indoor unit. <E06>
5
Improper setting of indoor unit or Indoor unit address setting is duplicated. E08
remote controller.
Remote controller address connector (RCU. ADR) is duplicated.
<<E09>>
(Duplication of main remote controller)
During auto address setting,
number of connected units does
Starting auto address setting is prohibited.
This alarm message shows that the auto address connector CN100 E12
6
not correspond to number set. is shorted while other RC line is executing auto address operation.
Error in auto address setting. (Number of connected indoor units
E15
is less than the number set)
When turning on the power Error in auto address setting. (Number of connected indoor units
supply, number of connected
units does not correspond to
is more than the number set)
No indoor unit is connected during auto address setting.
E16
7
number set. E20
(Except R.C. address is “0.”) Error of outdoor unit address setting. E25
Indoor unit communication error Error of main indoor unit in receiving serial communication signal
of group control wiring. E18
from sub indoor units.

Continued
8

5 - 13

TD831156-00_MINI_VRF_SYS.indb 13 2012/01/31 14:38:24


Test Run
7. Meaning of Alarm Messages

Alarm
Possible cause of malfunction message
Serial Improper setting. This alarm message shows when the indoor unit for multiple-use
is not connected to the outdoor unit. L02
communication
errors Duplication of main indoor unit address setting in group control. <L03>
Mis-setting
Duplication of outdoor R.C. address setting. L04
There are 2 or more indoor units Priority set remote controller L05
controllers which have operation
mode priority in 1 refrigerant circuit. Non-priority set remote controller L06
Group control wiring is connected to individual control indoor unit. L07
Indoor unit address is not set. L08
Capacity code of indoor unit is not set. <<L09>>
Capacity code of outdoor unit is not set. L10
Mis-matched connection of outdoor units which have different kinds L17
of refrigerant.
4-way valve operation failure L18
Activation of Protective device in indoor unit Thermal protector in indoor unit fan motor is activated. <<P01>>
protective is activated. Improper wiring connections of ceiling panel. <<P09>>
device
Float switch is activated. <<P10>>
Operation of protective function of fan inverter. P12
O2 sensor (detects low oxygen level) activated. P14
1 Protective device in outdoor unit
is activated.
Compressor thermal protector is activated.
Power supply voltage is unusual. (The voltage is more than 260 V P02
or less than 160 V between L1 and L2 phase.)
Incorrect discharge temperature. P03
High pressure switch is activated. P04
2 Detective phase (3-phase outdoor unit only) P05
Compressor running failure resulting from missing phase in the
P16
compressor wiring, etc. (Start failure not caused by IPM or no gas.)
Outdoor unit fan motor is unusual. P22

3 Overcurrent at time of compressor runs more than 80Hz (DCCT


secondary current or ACCT primary current is detected at a time P26
other than when IPM has tripped.)
IPM trip (IPM current or temperature) H31
Inverter for compressor is unusual. (DC compressor does not
P29
operate.)
4 Thermistor Indoor thermistor is either open Indoor coil temp. sensor (E1) <<F01>>
fault or damaged. Indoor coil temp. sensor (E2) <<F02>>
Indoor coil temp. sensor (E3) <<F03>>
Indoor suction air (room) temp. sensor (TA) <<F10>>
5 Indoor discharge air temp. sensor (BL) <<F11>>
Outdoor thermistor is either Compressor discharge sensor (TD) F04
open or damaged. Outdoor No. 1 coil liquid temp. sensor (C1) F07
Outdoor air temp. sensor (TO) F08

6 Compressor suction port temperature sensor (TS) F12


High pressure sensor F16
EEPROM on indoor unit PCB failure F29
Protective Protective device for compressor EEPROM on the outdoor unit PCB is a failure. F31
7 device for
compressor is
No. 1 is activated.
Current is not detected when comp. is ON. H03
activated

5 - 14

TD831156-00_MINI_VRF_SYS.indb 14 2012/01/31 14:38:24


Electrical Data
Contents

6. ELECTRICAL DATA
1. Outdoor Unit ...................................................................................................................... 6-2
(1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E .................................................. 6-2
(2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E .................................................. 6-4
2. Indoor Unit
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)

6-1

TD831156-00_MINI_VRF_SYS.indb 1 2011/11/07 8:59:18


Electrical Data
1. Outdoor Unit

(1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E

6-2

TD831156-00_MINI_VRF_SYS.indb 2 2011/11/07 8:59:18


Electrical Data
1. Outdoor Unit

Schematic Diagram U-36LE1U6, U-36LE1U6E

6-3

TD831156-00_MINI_VRF_SYS.indb 3 2011/11/07 8:59:19


Electrical Data
1. Outdoor Unit

(2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E

6-4

TD831156-00_MINI_VRF_SYS.indb 4 2011/11/07 8:59:19


Electrical Data
1. Outdoor Unit

Schematic Diagram U-52LE1U6, U-52LE1U6E

6-5

TD831156-00_MINI_VRF_SYS.indb 5 2011/11/07 8:59:19


– MEMO –

6-6

TD831156-00_MINI_VRF_SYS.indb 6 2011/11/07 8:59:19


PCB and Functions
Contents

7. PCB AND FUNCTIONS


1. Outdoor Unit Control PCB ................................................................................................ 7-2
1-1. Outdoor Unit Control PCB CR-CHX06052 .................................................................... 7-2
1-2. Outdoor Unit HIC Board HIC-CHDX14053 ....................................................................7-3
1-3. Functions (for CR-CHX06052) ...................................................................................... 7-4
2. Indoor Unit Control PCB Switches and Functions
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)

7-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/31 14:37:54


PCB and Functions
1. Outdoor Unit Control PCB

1-1. Outdoor Unit Control PCB CR-CHX06052

7-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/31 14:37:54


PCB and Functions
1. Outdoor Unit Control PCB

1-2. Outdoor Unit HIC Board HIC-CHDX14053

7-3

TD831156-00_MINI_VRF_SYS.indb 3 2012/01/31 14:37:54


PCB and Functions
1. Outdoor Unit Control PCB

1-3. Functions (for CR-CHX06052)

CN51 2P plug (black): Automatic address setting pin


• If the system address switch (S002: Factory setting is 0) is set to other than 0 (centralized
control), press this switch once to automatically set the address of the indoor unit to the
connected outdoor unit within the same system. While the automatic address setting is in
progress, 2 LEDs (red) on the outdoor unit control PCB blinks alternately. (The automatic
address operation will stop when this switch is pressed again.)
• When other system in centralized control mode is in the progress of automatic address
setting, only the LED1 of the outdoor unit control PCB blinks and indicates that the
automatic address setting for other system is in progress. While other unit is in the progress
of automatic address setting, pressing S001 will disable the automatic address setting.

S002 Rotary switch (10 positions, black): Outdoor system address setting switch
• The factory setting is 0 (1 system control), but it is necessary to set the address to each
system with the multiple system control or centralized control. (Fig.7-1)
• When system address is set to 0, automatic address will start simultaneously with power
activation, and it is not necessary to set the automatic address setting with SW01 switch
when there is only a single or simultaneously running multiple controls in a single system.
• When multiple systems are operated in centralized control, maximum of 30 systems (up
to indoor unit 64 units) can be connected. When operated by group control or centralized
control, set the system address other than 0 (1 or more).
• When the number of systems exceeds 9, you can set up to 30 systems by combining with
1 the dip switch S003. You can set up to 39, however control will be for 30 systems even if you
set more than 30. (For details, refer to Table 7-1.)
• LED1 of the outdoor unit control PCB lights up and the warning “ ” is displayed in remote
control when the system addresses has overlapped (multiple equated addresses exist).

2 S003 DIP switch (2P, blue): Switches for setting system address 10s digit and 20s digit
• If 10 systems or more are set, the setting is made by a combination of this DIP switch and
S002.
• If 10 - 19 systems are set, set switch 1P (10s digit) to ON.
• If 20 - 29 systems are set, set switch 2P (20s digit) to ON, and set switch 1P (10s digit) to
3 OFF.
• If 30 systems are set, set both switch 1P (10s digit) and switch 2P (20s digit) to ON. (For
details, refer to Table 7-1.)

4 CN14 2P plug (white): PCB inspection pin at the factory

7-4

TD831156-00_MINI_VRF_SYS.indb 4 2012/01/31 14:37:55


PCB and Functions
1. Outdoor Unit Control PCB

CN15 The control operations that are shown below are when you short-circuit this cooling inspection
pin located on the outdoor unit control PCB.
1.Thermistor inspection

Detection results
Thermistor
Normal Error
Discharge temperature (TD) LED1 lights up
Outdoor temperature (TO) LED2 lights up
Heat exchanger temperature (C1) LED1 lights up LED1, 2 turns off
Heat exchanger temperature (C2) LED2 lights up
Air inlet temperature (TS) LED1 lights up


2. Turn ON the four-way valve for one second
3. Forced cooling operation

CN50 This pin is used to perform automatic address while operating the compressor. Normally,
automatic address can be performed in Heating mode, short-circuit this pin to perform
automatic address when operation is in Cooling mode.

CN33 3P plug (black): Terminal plug of the communications circuit 1


• A connecting socket (2P, black) for short circuiting is attached to the terminal plug at the
time of shipment from the factory.
• When multiple systems are operated in centralized control, leave the connecting socket in
place at only 1 of the outdoor unit in system address, and then replace the socket 2 to 3
from the outdoor unit (other than 1). If multiple connecting sockets are left in place while
operated in centralized control, communications trouble will occur.
2
• When there is only single (system address 0) connecting socket of 1 system, do not remove
the connecting socket. (It is for the warning “ ”.)

CN028 2P plug (white): Silent mode operation pin 3


• Operates the outdoor fan and compressor frequency with a limitation.
• When relay turns ON, operating noise becomes low.

Relay Power
(field supply) source 4
Silent
CN028 External contact
(Timer input, etc.: field supply)
5
Outdoor unit control PCB
Note 1: Make the length of the wire between the outdoor unit control PCB to Relay within 6.5 ft.
• 2P socket with lead wire (Service parts: Parts code/CV6231612098)
• Relay field supply contact input specification DC5V and 0.5mA
(Recommended relay; The Fuji Electric Co. /HH62SW nano-contact point
6
correspondence)
• Use commercially available timer. (Omron “H5” daily time switch, etc.)

7-5

TD831156-00_MINI_VRF_SYS.indb 5 2012/01/31 14:37:55


PCB and Functions
1. Outdoor Unit Control PCB

Table 7-1. Setting the System Address


[S002: Rotary switch (black), S003: 2P DIP (green or blue)]
S002 setting S003 setting
Outdoor
(System
system 1P 2P
address
address No. (10s digit) (20s digit)
switch)
1
refrigerant
1 0 OFF OFF
system
only
1 1 OFF OFF
2 2 OFF OFF
3 3 OFF OFF
4 4 OFF OFF
5 5 OFF OFF
6 6 OFF OFF
7 7 OFF OFF
8 8 OFF OFF
9 9 OFF OFF
Outdoor Outdoor Outdoor Outdoor
10 0 ON OFF unit unit unit unit
System
11 1 ON OFF
controller
12 2 ON OFF
1 When
13
14
3
4
ON
ON
OFF
OFF Indoor Indoor Indoor Indoor
operated in 15 5 ON OFF unit unit unit unit
centralized 16 6 ON OFF
control 17 7 ON OFF
2 18
19
8
9
ON
ON
OFF
OFF Fig. 7-1
20 0 OFF ON
21 1 OFF ON
22 2 OFF ON
3 23
24
3
4
OFF
OFF
ON
ON
25 5 OFF ON
26 6 OFF ON
27 7 OFF ON
4 28
29
8
9
OFF
OFF
ON
ON
30 0 ON ON

7-6

TD831156-00_MINI_VRF_SYS.indb 6 2012/01/31 14:37:55


Capacity Table
Contents

8. CAPACITY TABLE
1. Capacity Ratio of Outdoor Unit ........................................................................................ 8-2
1-1. U-36LE1U6, U-36LE1U6E (Cooling) ............................................................................ 8-2
1-2. U-36LE1U6, U-36LE1U6E (Heating) ............................................................................8-4
1-3. U-52LE1U6, U-52LE1U6E (Cooling) ............................................................................ 8-6
1-4. U-52LE1U6, U-52LE1U6E (Heating) ............................................................................8-8
2. Cooling Capacity of Indoor Unit ..................................................................................... 8-10
2-1. 4-Way Cassette Type (U1 Type), 4-Way Cassette 60×60 Type (Y1 Type) .................. 8-10
2-2. 1-Way Cassette Type (D1 Type) ................................................................................. 8-16
2-3. Wall Mounted Type (K1 Type) ..................................................................................... 8-19
2-4. Ceiling Type (T1 Type) ................................................................................................ 8-25
2-5. Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type) ....... 8-28
2-6. High Static Pressure Ducted Type (E1 Type) ............................................................. 8-42
2-7. Floor Standing Type (P1 Type) ................................................................................... 8-44
2-8. Concealed Floor Standing Type (R1 Type) ................................................................. 8-50

8-1

TD831156-00_MINI_VRF_SYS.indb 1 2012/01/31 14:37:17


Capacity Table
1. Capacity Ratio of Outdoor Unit
1-1. U-36LE1U6, U-36LE1U6E (Cooling)
MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CWB
Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 10.1 0.99 11.0 1.17 11.8 1.32 12.7 1.50 13.5 1.62 14.3 1.74 15.2 1.86
-5.0 10.1 1.02 11.0 1.20 11.8 1.35 12.7 1.56 13.5 1.68 14.3 1.80 15.2 1.92
0.0 10.1 1.08 11.0 1.26 11.8 1.41 12.7 1.62 13.5 1.77 14.3 1.86 15.2 2.01
5.0 10.1 1.14 11.0 1.32 11.8 1.50 12.7 1.71 13.5 1.83 14.3 1.98 15.2 2.13
10.0 10.1 1.23 11.0 1.41 11.8 1.59 12.7 1.80 13.5 1.95 14.3 2.10 15.2 2.25
15.0 10.1 1.35 11.0 1.55 11.8 1.74 12.7 1.92 13.5 2.10 14.3 2.28 15.2 2.46
130% 20.0 10.1 1.50 11.0 1.70 11.8 1.89 12.7 2.10 13.5 2.28 14.3 2.46 15.2 2.71
25.0 10.1 1.68 11.0 1.89 11.8 2.10 12.7 2.34 13.5 2.52 14.3 2.71 15.2 3.13
30.0 10.1 1.92 11.0 2.13 11.8 2.34 12.7 2.64 13.5 3.01 14.3 3.22 14.8 3.34
35.0 10.1 2.25 11.0 2.49 11.8 2.74 12.7 3.01 13.5 3.25 13.9 3.43 14.3 3.55
40.0 10.1 2.64 11.0 2.89 11.8 3.13 12.3 3.46 12.8 3.55 13.2 3.58 13.4 3.58
43.0 10.1 3.01 11.0 3.25 11.1 3.40 11.6 3.55 12.1 3.58 12.3 3.58 12.8 3.58

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 9.7 0.97 10.6 1.14 11.4 1.29 12.2 1.46 13.0 1.58 13.8 1.70 14.6 1.82
-5.0 9.7 1.00 10.6 1.17 11.4 1.32 12.2 1.52 13.0 1.64 13.8 1.76 14.6 1.87
0.0 9.7 1.05 10.6 1.23 11.4 1.38 12.2 1.58 13.0 1.73 13.8 1.82 14.6 1.96
5.0 9.7 1.11 10.6 1.29 11.4 1.46 12.2 1.67 13.0 1.79 13.8 1.93 14.6 2.08
10.0 9.7 1.20 10.6 1.38 11.4 1.55 12.2 1.76 13.0 1.90 13.8 2.05 14.6 2.20
15.0 9.7 1.32 10.6 1.51 11.4 1.70 12.2 1.87 13.0 2.05 13.8 2.23 14.6 2.40
120% 20.0 9.7 1.46 10.6 1.65 11.4 1.84 12.2 2.05 13.0 2.23 13.8 2.40 14.6 2.64
25.0 9.7 1.64 10.6 1.84 11.4 2.05 12.2 2.28 13.0 2.46 13.8 2.64 14.6 3.05
30.0 9.7 1.87 10.6 2.08 11.4 2.28 12.2 2.58 13.0 2.93 13.8 3.13 14.3 3.25
35.0 9.7 2.20 10.6 2.43 11.4 2.66 12.2 2.93 13.0 3.16 13.4 3.34 13.8 3.46
1 40.0
43.0
9.7
9.7
2.58
2.93
10.6
10.6
2.81
3.16
11.4
10.7
3.05
3.31
11.8
11.2
3.37
3.46
12.3
11.7
3.46
3.57
12.8
12.0
3.54
3.58
13.1
12.4
3.58
3.58

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
2 capacity ratio °CDB
-10.0
kW
9.4
kW
0.94
kW
10.2
kW
1.11
kW
11.0
kW
1.25
kW
11.8
kW
1.42
kW
12.5
kW
1.54
kW
13.3
kW
1.65
kW
14.1
kW
1.76
-5.0 9.4 0.97 10.2 1.14 11.0 1.28 11.8 1.48 12.5 1.59 13.3 1.71 14.1 1.82
0.0 9.4 1.02 10.2 1.19 11.0 1.34 11.8 1.54 12.5 1.68 13.3 1.76 14.1 1.90
5.0 9.4 1.08 10.2 1.25 11.0 1.42 11.8 1.62 12.5 1.73 13.3 1.88 14.1 2.02
10.0 9.4 1.17 10.2 1.34 11.0 1.51 11.8 1.71 12.5 1.85 13.3 1.99 14.1 2.13
15.0 9.4 1.28 10.2 1.46 11.0 1.65 11.8 1.82 12.5 1.99 13.3 2.16 14.1 2.33
3 110% 20.0
25.0
9.4
9.4
1.42
1.59
10.2
10.2
1.61
1.79
11.0
11.0
1.79
1.99
11.8
11.8
1.99
2.22
12.5
12.5
2.16
2.39
13.3
13.3
2.33
2.56
14.1
14.1
2.56
2.96
30.0 9.4 1.82 10.2 2.02 11.0 2.22 11.8 2.50 12.5 2.84 13.3 3.04 13.8 3.16
35.0 9.4 2.13 10.2 2.36 11.0 2.59 11.8 2.84 12.5 3.07 12.9 3.24 13.3 3.35
40.0 9.4 2.50 10.2 2.73 11.0 2.96 11.4 3.27 11.9 3.35 12.3 3.44 12.7 3.53
43.0 9.4 2.84 10.2 3.07 10.3 3.21 10.8 3.35 11.3 3.47 11.8 3.58 12.1 3.58

4 Combination(%): Outdoor
Indoor/outdoor air temp.
16.0 17.0 18.0
Indoor air temp. : °CWB
19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 9.0 0.91 9.7 1.08 10.4 1.21 11.2 1.38 11.9 1.49 12.7 1.60 13.4 1.71
-5.0 9.0 0.94 9.7 1.10 10.4 1.24 11.2 1.44 11.9 1.55 12.7 1.66 13.4 1.77
0.0 9.0 0.99 9.7 1.16 10.4 1.30 11.2 1.49 11.9 1.63 12.7 1.71 13.4 1.85
5 5.0
10.0
9.0
9.0
1.05
1.13
9.7
9.7
1.21
1.30
10.4
10.4
1.38
1.46
11.2
11.2
1.57
1.66
11.9
11.9
1.68
1.79
12.7
12.7
1.82
1.93
13.4
13.4
1.96
2.07
15.0 9.0 1.24 9.7 1.42 10.4 1.60 11.2 1.77 11.9 1.93 12.7 2.10 13.4 2.26
100% 20.0 9.0 1.38 9.7 1.56 10.4 1.74 11.2 1.93 11.9 2.10 12.7 2.26 13.4 2.48
25.0 9.0 1.55 9.7 1.74 10.4 1.93 11.2 2.15 11.9 2.32 12.7 2.48 13.4 2.87
30.0 9.0 1.77 9.7 1.96 10.4 2.15 11.2 2.43 11.9 2.76 12.7 2.95 13.1 3.06
35.0 9.0 2.07 9.7 2.29 10.4 2.51 11.2 2.76 11.9 2.98 12.3 3.15 12.7 3.26
6 40.0
43.0
9.0
9.0
2.43
2.76
9.7
9.7
2.65
2.98
10.4
9.9
2.87
3.12
10.9
10.3
3.17
3.26
11.3
10.8
3.26
3.37
11.8
11.2
3.34
3.48
12.1
11.6
3.42
3.53

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
8.1
8.1
0.77
0.80
8.7
8.7
0.91
0.94
9.4
9.4
1.03
1.06
10.1
10.1
1.17
1.22
10.7
10.7
1.27
1.31
11.4
11.4
1.36
1.41
12.1
12.1
1.45
1.50
0.0 8.1 0.84 8.7 0.99 9.4 1.10 10.1 1.27 10.7 1.38 11.4 1.45 12.1 1.57
5.0 8.1 0.89 8.7 1.03 9.4 1.17 10.1 1.34 10.7 1.43 11.4 1.55 12.1 1.67
10.0 8.1 0.96 8.7 1.10 9.4 1.24 10.1 1.41 10.7 1.52 11.4 1.64 12.1 1.76
15.0 8.1 1.06 8.7 1.21 9.4 1.36 10.1 1.50 10.7 1.64 11.4 1.78 12.1 1.92
90% 20.0 8.1 1.17 8.7 1.33 9.4 1.48 10.1 1.64 10.7 1.78 11.4 1.92 12.1 2.11
8 25.0
30.0
8.1
8.1
1.31
1.50
8.7
8.7
1.48
1.67
9.4
9.4
1.64
1.83
10.1
10.1
1.83
2.06
10.7
10.7
1.97
2.35
11.4
11.4
2.11
2.51
12.1
11.8
2.44
2.60
35.0 8.1 1.76 8.7 1.95 9.4 2.13 10.1 2.35 10.7 2.53 11.1 2.67 11.4 2.77
40.0 8.1 2.06 8.7 2.25 9.4 2.44 9.8 2.70 10.2 2.77 10.6 2.84 10.9 2.91
43.0 8.1 2.35 8.7 2.53 8.9 2.65 9.3 2.77 9.7 2.86 10.1 2.96 10.5 3.00

8-2

TD831156-00_MINI_VRF_SYS.indb 2 2012/01/31 14:37:18


Capacity Table
1. Capacity Ratio of Outdoor Unit

MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CWB
Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 7.2 0.65 7.8 0.76 8.4 0.86 9.0 0.98 9.6 1.06 10.2 1.14 10.8 1.21
-5.0 7.2 0.67 7.8 0.78 8.4 0.88 9.0 1.02 9.6 1.10 10.2 1.18 10.8 1.25
0.0 7.2 0.71 7.8 0.82 8.4 0.92 9.0 1.06 9.6 1.16 10.2 1.21 10.8 1.31
5.0 7.2 0.74 7.8 0.86 8.4 0.98 9.0 1.12 9.6 1.20 10.2 1.29 10.8 1.39
10.0 7.2 0.80 7.8 0.92 8.4 1.04 9.0 1.18 9.6 1.27 10.2 1.37 10.8 1.47
15.0 7.2 0.88 7.8 1.01 8.4 1.14 9.0 1.25 9.6 1.37 10.2 1.49 10.8 1.61
80% 20.0 7.2 0.98 7.8 1.11 8.4 1.23 9.0 1.37 9.6 1.49 10.2 1.61 10.8 1.76
25.0 7.2 1.10 7.8 1.23 8.4 1.37 9.0 1.53 9.6 1.65 10.2 1.76 10.8 2.04
30.0 7.2 1.25 7.8 1.39 8.4 1.53 9.0 1.72 9.6 1.96 10.2 2.10 10.5 2.18
35.0 7.2 1.47 7.8 1.63 8.4 1.78 9.0 1.96 9.6 2.12 9.9 2.23 10.1 2.31
40.0 7.2 1.72 7.8 1.88 8.4 2.04 8.7 2.25 9.0 2.31 9.4 2.37 9.7 2.43
43.0 7.2 1.96 7.8 2.12 7.9 2.21 8.2 2.31 8.6 2.39 9.0 2.47 9.3 2.51

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 6.3 0.53 6.8 0.62 7.3 0.70 7.8 0.80 8.4 0.86 8.9 0.93 9.4 0.99
-5.0 6.3 0.54 6.8 0.64 7.3 0.72 7.8 0.83 8.4 0.90 8.9 0.96 9.4 1.02
0.0 6.3 0.58 6.8 0.67 7.3 0.75 7.8 0.86 8.4 0.94 8.9 0.99 9.4 1.07
5.0 6.3 0.61 6.8 0.70 7.3 0.80 7.8 0.91 8.4 0.98 8.9 1.06 9.4 1.14
10.0 6.3 0.66 6.8 0.75 7.3 0.85 7.8 0.96 8.4 1.04 8.9 1.12 9.4 1.20
15.0 6.3 0.72 6.8 0.82 7.3 0.93 7.8 1.02 8.4 1.12 8.9 1.22 9.4 1.31
70% 20.0 6.3 0.80 6.8 0.90 7.3 1.01 7.8 1.12 8.4 1.22 8.9 1.31 9.4 1.44
25.0 6.3 0.90 6.8 1.01 7.3 1.12 7.8 1.25 8.4 1.34 8.9 1.44 9.4 1.66
30.0 6.3 1.02 6.8 1.14 7.3 1.25 7.8 1.41 8.4 1.60 8.9 1.71 9.2 1.78
35.0 6.3 1.20 6.8 1.33 7.3 1.46 7.8 1.60 8.4 1.73 8.6 1.82 8.9 1.89
40.0
43.0
6.3
6.3
1.41
1.60
6.8
6.8
1.54
1.73
7.3
6.9
1.66
1.81
7.6
7.2
1.84
1.89
7.9
7.5
1.89
1.95
8.2
7.8
1.94
2.02
8.5
8.2
1.98
2.05
1
Indoor air temp. : °CWB
Combination(%): Outdoor 16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
-10.0
kW
5.4
kW
0.43
kW
5.8
kW
0.51
kW
6.3
kW
0.57
kW
6.7
kW
0.65
kW
7.2
kW
0.70
kW
7.6
kW
0.75
kW
8.1
kW
0.80 2
-5.0 5.4 0.44 5.8 0.52 6.3 0.58 6.7 0.67 7.2 0.73 7.6 0.78 8.1 0.83
0.0 5.4 0.47 5.8 0.54 6.3 0.61 6.7 0.70 7.2 0.77 7.6 0.80 8.1 0.87
5.0 5.4 0.49 5.8 0.57 6.3 0.65 6.7 0.74 7.2 0.79 7.6 0.86 8.1 0.92
10.0 5.4 0.53 5.8 0.61 6.3 0.69 6.7 0.78 7.2 0.84 7.6 0.91 8.1 0.97
15.0 5.4 0.58 5.8 0.67 6.3 0.75 6.7 0.83 7.2 0.91 7.6 0.99 8.1 1.06
60% 20.0
25.0
5.4
5.4
0.65
0.73
5.8
5.8
0.73
0.82
6.3
6.3
0.82
0.91
6.7
6.7
0.91
1.01
7.2
7.2
0.99
1.09
7.6
7.6
1.06
1.17
8.1
8.1
1.17
1.35 3
30.0 5.4 0.83 5.8 0.92 6.3 1.01 6.7 1.14 7.2 1.30 7.6 1.39 7.9 1.44
35.0 5.4 0.97 5.8 1.08 6.3 1.18 6.7 1.30 7.2 1.40 7.4 1.48 7.6 1.53
40.0 5.4 1.14 5.8 1.25 6.3 1.35 6.5 1.49 6.8 1.53 7.1 1.57 7.3 1.61
43.0 5.4 1.30 5.8 1.40 5.9 1.47 6.2 1.53 6.5 1.58 6.7 1.63 7.0 1.66

Combination(%): Outdoor
Indoor/outdoor air temp.
16.0 17.0 18.0
Indoor air temp. : °CWB
19.0 20.0 21.0 22.0
4
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 4.5 0.33 4.8 0.39 5.2 0.44 5.6 0.50 6.0 0.54 6.3 0.58 6.7 0.62
-5.0 4.5 0.34 4.8 0.40 5.2 0.45 5.6 0.52 6.0 0.56 6.3 0.60 6.7 0.64
0.0 4.5 0.36 4.8 0.42 5.2 0.47 5.6 0.54 6.0 0.59 6.3 0.62 6.7 0.67
5.0
10.0
4.5
4.5
0.38
0.41
4.8
4.8
0.44
0.47
5.2
5.2
0.50
0.53
5.6
5.6
0.57
0.60
6.0
6.0
0.61
0.65
6.3
6.3
0.66
0.70
6.7
6.7
0.71
0.75
5
15.0 4.5 0.45 4.8 0.51 5.2 0.58 5.6 0.64 6.0 0.70 6.3 0.76 6.7 0.81
50% 20.0 4.5 0.50 4.8 0.56 5.2 0.63 5.6 0.70 6.0 0.76 6.3 0.81 6.7 0.89
25.0 4.5 0.56 4.8 0.63 5.2 0.70 5.6 0.78 6.0 0.83 6.3 0.89 6.7 1.03
30.0 4.5 0.64 4.8 0.71 5.2 0.78 5.6 0.87 6.0 0.99 6.3 1.06 6.6 1.10
35.0 4.5 0.75 4.8 0.82 5.2 0.90 5.6 0.99 6.0 1.07 6.2 1.13 6.3 1.17
40.0
43.0
4.5
4.5
0.87
0.99
4.8
4.8
0.95
1.07
5.2
4.9
1.03
1.12
5.4
5.2
1.14
1.17
5.7
5.4
1.17
1.21
5.9
5.6
1.20
1.25
6.0
5.8
1.23
1.27
6

8-3

TD831156-00_MINI_VRF_SYS.indb 3 2012/01/31 14:37:18


Capacity Table
1. Capacity Ratio of Outdoor Unit
1-2. U-36LE1U6, U-36LE1U6E (Heating)
MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 9.9 3.25 9.6 3.22 9.3 3.19 9.2 3.13 9.0 3.10 8.8 3.04 8.5 2.98
-14.7 -15.0 11.3 3.43 11.0 3.40 10.7 3.34 10.6 3.28 10.5 3.25 10.2 3.22 9.9 3.16
-9.6 -10.0 12.9 3.58 12.6 3.55 12.3 3.52 12.1 3.46 11.9 3.40 11.6 3.37 11.4 3.34
-4.4 -5.0 14.3 3.74 14.1 3.74 13.8 3.68 13.7 3.61 13.6 3.58 12.7 3.40 11.7 3.13
-1.8 -2.5 15.0 3.74 14.7 3.74 14.6 3.68 14.1 3.61 13.6 3.46 12.7 3.22 11.7 2.95
130% 0.8 0.0 15.4 3.74 15.3 3.74 14.6 3.52 14.1 3.46 13.6 3.31 12.7 3.07 11.7 2.77
2.8 2.0 15.7 3.74 15.5 3.74 14.6 3.37 14.1 3.31 13.6 3.19 12.7 2.92 11.7 2.62
6.0 5.0 16.3 3.74 15.5 3.58 14.6 3.16 14.1 3.10 13.6 2.92 12.7 2.71 11.7 2.41
7.0 6.0 16.4 3.74 15.5 3.52 14.6 3.07 14.1 3.01 13.6 2.86 12.7 2.62 11.7 2.32
8.6 7.5 16.5 3.68 15.5 3.40 14.6 2.98 14.1 2.92 13.6 2.80 12.7 2.53 11.7 2.23
11.2 10.0 16.5 3.49 15.5 3.19 14.6 2.80 14.1 2.74 13.6 2.62 12.7 2.35 11.7 2.05
16.4 15.0 16.5 3.16 15.5 2.86 14.6 2.44 14.1 2.38 13.6 2.26 12.7 2.05 11.7 1.69

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 9.5 3.20 9.2 3.17 9.0 3.14 8.8 3.08 8.7 3.05 8.4 2.99 8.2 2.93
-14.7 -15.0 10.9 3.38 10.6 3.35 10.3 3.29 10.2 3.23 10.1 3.20 9.8 3.17 9.5 3.11
-9.6 -10.0 12.4 3.53 12.1 3.50 11.8 3.47 11.7 3.41 11.4 3.35 11.2 3.32 11.0 3.29
-4.4 -5.0 13.9 3.70 13.6 3.67 13.3 3.62 13.2 3.56 13.1 3.53 12.2 3.35 11.3 3.08
-1.8 -2.5 14.4 3.74 14.3 3.70 14.1 3.62 13.6 3.56 13.1 3.41 12.2 3.17 11.3 2.90
120% 0.8 0.0 15.0 3.74 14.8 3.74 14.1 3.47 13.6 3.41 13.1 3.26 12.2 3.02 11.3 2.73
2.8 2.0 15.3 3.74 15.0 3.67 14.1 3.32 13.6 3.26 13.1 3.14 12.2 2.87 11.3 2.58
6.0 5.0 15.8 3.74 15.0 3.53 14.1 3.11 13.6 3.05 13.1 2.87 12.2 2.67 11.3 2.37
7.0 6.0 15.9 3.73 15.0 3.47 14.1 3.02 13.6 2.96 13.1 2.82 12.2 2.58 11.3 2.28
8.6 7.5 15.9 3.62 15.0 3.35 14.1 2.93 13.6 2.87 13.1 2.76 12.2 2.49 11.3 2.19
1 11.2
16.4
10.0
15.0
15.9
15.9
3.44
3.11
15.0
15.0
3.14
2.82
14.1
14.1
2.76
2.40
13.6
13.6
2.70
2.34
13.1
13.1
2.58
2.22
12.2
12.2
2.31
2.02
11.3
11.3
2.02
1.66

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
2 capacity ratio
DB
-19.8
WB
-20.0
kW
9.2
kW
3.16
kW
8.9
kW
3.13
kW
8.7
kW
3.10
kW
8.5
kW
3.04
kW
8.4
kW
3.01
kW
8.1
kW
2.95
kW
7.9
kW
2.89
-14.7 -15.0 10.5 3.33 10.2 3.30 10.0 3.24 9.8 3.19 9.7 3.16 9.5 3.13 9.2 3.07
-9.6 -10.0 11.9 3.48 11.7 3.45 11.4 3.42 11.3 3.36 11.0 3.30 10.8 3.27 10.6 3.24
-4.4 -5.0 13.4 3.65 13.1 3.62 12.9 3.57 12.7 3.51 12.7 3.48 11.8 3.30 10.9 3.04
-1.8 -2.5 14.0 3.71 13.8 3.65 13.6 3.57 13.1 3.51 12.7 3.36 11.8 3.13 10.9 2.86
110% 0.8 0.0 14.6 3.74 14.4 3.74 13.6 3.42 13.1 3.36 12.7 3.22 11.8 2.98 10.9 2.69
3 2.8
6.0
2.0
5.0
14.8
15.4
3.74
3.74
14.4
14.4
3.62
3.48
13.6
13.6
3.27
3.07
13.1
13.1
3.22
3.01
12.7
12.7
3.10
2.84
11.8
11.8
2.84
2.63
10.9
10.9
2.54
2.34
7.0 6.0 15.4 3.68 14.4 3.42 13.6 2.98 13.1 2.92 12.7 2.78 11.8 2.54 10.9 2.25
8.6 7.5 15.4 3.57 14.4 3.30 13.6 2.89 13.1 2.84 12.7 2.72 11.8 2.46 10.9 2.16
11.2 10.0 15.4 3.39 14.4 3.10 13.6 2.72 13.1 2.66 12.7 2.54 11.8 2.28 10.9 1.99
16.4 15.0 15.4 3.07 14.4 2.78 13.6 2.37 13.1 2.31 12.7 2.19 11.8 1.99 10.9 1.64

4 Combination(%):
Indoor/outdoor
Outdoor
air temp.
15.0 17.0 19.0
Indoor air temp. : °CDB
20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 8.8 3.11 8.5 3.08 8.3 3.05 8.1 3.00 8.0 2.97 7.8 2.91 7.5 2.85
-14.7 -15.0 10.0 3.28 9.8 3.25 9.5 3.20 9.4 3.14 9.3 3.11 9.0 3.08 8.8 3.02
-9.6 -10.0 11.4 3.43 11.1 3.40 10.9 3.37 10.8 3.31 10.5 3.25 10.3 3.23 10.1 3.20
5 -4.4
-1.8
-5.0
-2.5
12.8
13.4
3.60
3.66
12.5
13.1
3.57
3.60
12.3
12.9
3.51
3.51
12.1
12.5
3.46
3.46
12.1
12.1
3.43
3.31
11.3
11.3
3.25
3.08
10.4
10.4
3.00
2.82
100% 0.8 0.0 14.0 3.74 13.8 3.69 12.9 3.37 12.5 3.31 12.1 3.17 11.3 2.94 10.4 2.65
2.8 2.0 14.3 3.74 13.8 3.57 12.9 3.23 12.5 3.17 12.1 3.05 11.3 2.79 10.4 2.51
6.0 5.0 14.6 3.69 13.8 3.43 12.9 3.02 12.5 2.97 12.1 2.79 11.3 2.59 10.4 2.30
7.0 6.0 14.6 3.63 13.8 3.37 12.9 2.94 12.5 2.88 12.1 2.74 11.3 2.51 10.4 2.22
8.6 7.5 14.6 3.51 13.8 3.25 12.9 2.85 12.5 2.79 12.1 2.68 11.3 2.42 10.4 2.13
6 11.2
16.4
10.0
15.0
14.6
14.6
3.34
3.02
13.8
13.8
3.05
2.74
12.9
12.9
2.68
2.33
12.5
12.5
2.62
2.28
12.1
12.1
2.51
2.16
11.3
11.3
2.25
1.96
10.4
10.4
1.96
1.61

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
7.9
9.0
2.74
2.89
7.7
8.8
2.71
2.86
7.4
8.6
2.69
2.81
7.3
8.4
2.64
2.76
7.2
8.3
2.61
2.74
7.0
8.1
2.56
2.71
6.8
7.9
2.51
2.66
-9.6 -10.0 10.2 3.02 10.0 2.99 9.8 2.97 9.7 2.91 9.5 2.86 9.2 2.84 9.1 2.81
-4.4 -5.0 11.5 3.17 11.3 3.14 11.0 3.09 10.9 3.04 10.9 3.02 10.1 2.86 9.3 2.64
-1.8 -2.5 12.0 3.22 11.8 3.17 11.6 3.09 11.3 3.04 10.9 2.91 10.1 2.71 9.3 2.48
90% 0.8 0.0 12.6 3.29 12.4 3.24 11.6 2.97 11.3 2.91 10.9 2.79 10.1 2.59 9.3 2.33
2.8 2.0 12.8 3.29 12.4 3.14 11.6 2.84 11.3 2.79 10.9 2.69 10.1 2.46 9.3 2.20
8 6.0
7.0
5.0
6.0
13.2
13.2
3.24
3.19
12.4
12.4
3.02
2.97
11.6
11.6
2.66
2.59
11.3
11.3
2.61
2.53
10.9
10.9
2.46
2.41
10.1
10.1
2.28
2.20
9.3
9.3
2.03
1.95
8.6 7.5 13.2 3.09 12.4 2.86 11.6 2.51 11.3 2.46 10.9 2.36 10.1 2.13 9.3 1.88
11.2 10.0 13.2 2.94 12.4 2.69 11.6 2.36 11.3 2.31 10.9 2.20 10.1 1.98 9.3 1.72
16.4 15.0 13.2 2.66 12.4 2.41 11.6 2.05 11.3 2.00 10.9 1.90 10.1 1.72 9.3 1.42

8-4

TD831156-00_MINI_VRF_SYS.indb 4 2012/01/31 14:37:19


Capacity Table
1. Capacity Ratio of Outdoor Unit

MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 7.0 2.36 6.8 2.34 6.6 2.32 6.5 2.28 6.4 2.25 6.2 2.21 6.0 2.17
-14.7 -15.0 8.0 2.50 7.8 2.47 7.6 2.43 7.5 2.39 7.4 2.36 7.2 2.34 7.0 2.30
-9.6 -10.0 9.1 2.60 8.9 2.58 8.7 2.56 8.6 2.52 8.4 2.47 8.2 2.45 8.1 2.43
-4.4 -5.0 10.2 2.74 10.0 2.71 9.8 2.67 9.7 2.63 9.7 2.60 9.0 2.47 8.3 2.28
-1.8 -2.5 10.7 2.78 10.5 2.74 10.4 2.67 10.0 2.63 9.7 2.52 9.0 2.34 8.3 2.15
80% 0.8 0.0 11.2 2.85 11.0 2.80 10.4 2.56 10.0 2.52 9.7 2.41 9.0 2.23 8.3 2.01
2.8 2.0 11.4 2.85 11.0 2.71 10.4 2.45 10.0 2.41 9.7 2.32 9.0 2.12 8.3 1.90
6.0 5.0 11.7 2.80 11.0 2.60 10.4 2.30 10.0 2.25 9.7 2.12 9.0 1.97 8.3 1.75
7.0 6.0 11.7 2.76 11.0 2.56 10.4 2.23 10.0 2.19 9.7 2.08 9.0 1.90 8.3 1.69
8.6 7.5 11.7 2.67 11.0 2.47 10.4 2.17 10.0 2.12 9.7 2.04 9.0 1.84 8.3 1.62
11.2 10.0 11.7 2.54 11.0 2.32 10.4 2.04 10.0 1.99 9.7 1.90 9.0 1.71 8.3 1.49
16.4 15.0 11.7 2.30 11.0 2.08 10.4 1.77 10.0 1.73 9.7 1.64 9.0 1.49 8.3 1.23

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 6.1 1.99 6.0 1.97 5.8 1.95 5.7 1.92 5.6 1.90 5.4 1.86 5.3 1.82
-14.7 -15.0 7.0 2.10 6.8 2.08 6.7 2.05 6.6 2.01 6.5 1.99 6.3 1.97 6.1 1.94
-9.6 -10.0 8.0 2.19 7.8 2.17 7.6 2.16 7.5 2.12 7.4 2.08 7.2 2.06 7.1 2.05
-4.4 -5.0 8.9 2.30 8.8 2.29 8.6 2.25 8.5 2.21 8.4 2.19 7.9 2.08 7.3 1.92
-1.8 -2.5 9.4 2.34 9.2 2.30 9.1 2.25 8.8 2.21 8.4 2.12 7.9 1.97 7.3 1.81
70% 0.8 0.0 9.8 2.40 9.6 2.36 9.1 2.16 8.8 2.12 8.4 2.03 7.9 1.88 7.3 1.70
2.8 2.0 10.0 2.40 9.6 2.29 9.1 2.06 8.8 2.03 8.4 1.95 7.9 1.79 7.3 1.60
6.0 5.0 10.2 2.36 9.6 2.19 9.1 1.94 8.8 1.90 8.4 1.79 7.9 1.66 7.3 1.47
7.0 6.0 10.2 2.32 9.6 2.16 9.1 1.88 8.8 1.84 8.4 1.75 7.9 1.60 7.3 1.42
8.6 7.5 10.2 2.25 9.6 2.08 9.1 1.82 8.8 1.79 8.4 1.71 7.9 1.55 7.3 1.36
11.2
16.4
10.0
15.0
10.2
10.2
2.14
1.94
9.6
9.6
1.95
1.75
9.1
9.1
1.71
1.49
8.8
8.8
1.68
1.46
8.4
8.4
1.60
1.38
7.9
7.9
1.44
1.25
7.3
7.3
1.25
1.03
1
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB
-19.8
WB
-20.0
kW
5.3
kW
1.68
kW
5.1
kW
1.66
kW
5.0
kW
1.65
kW
4.9
kW
1.62
kW
4.8
kW
1.60
kW
4.7
kW
1.57
kW
4.5
kW
1.54 2
-14.7 -15.0 6.0 1.77 5.9 1.76 5.7 1.73 5.6 1.70 5.6 1.68 5.4 1.66 5.3 1.63
-9.6 -10.0 6.8 1.85 6.7 1.84 6.5 1.82 6.5 1.79 6.3 1.76 6.2 1.74 6.1 1.73
-4.4 -5.0 7.7 1.94 7.5 1.93 7.4 1.90 7.3 1.87 7.2 1.85 6.8 1.76 6.2 1.62
-1.8 -2.5 8.0 1.98 7.9 1.94 7.8 1.90 7.5 1.87 7.2 1.79 6.8 1.66 6.2 1.52
60% 0.8 0.0 8.4 2.02 8.3 1.99 7.8 1.82 7.5 1.79 7.2 1.71 6.8 1.59 6.2 1.43
2.8
6.0
2.0
5.0
8.6
8.8
2.02
1.99
8.3
8.3
1.93
1.85
7.8
7.8
1.74
1.63
7.5
7.5
1.71
1.60
7.2
7.2
1.65
1.51
6.8
6.8
1.51
1.40
6.2
6.2
1.35
1.24 3
7.0 6.0 8.8 1.96 8.3 1.82 7.8 1.59 7.5 1.56 7.2 1.48 6.8 1.35 6.2 1.20
8.6 7.5 8.8 1.90 8.3 1.76 7.8 1.54 7.5 1.51 7.2 1.45 6.8 1.31 6.2 1.15
11.2 10.0 8.8 1.80 8.3 1.65 7.8 1.45 7.5 1.42 7.2 1.35 6.8 1.21 6.2 1.06
16.4 15.0 8.8 1.63 8.3 1.48 7.8 1.26 7.5 1.23 7.2 1.17 6.8 1.06 6.2 0.87

Combination(%):
Indoor/outdoor
Outdoor
air temp.
15.0 17.0 19.0
Indoor air temp. : °CDB
20.0 21.0 23.0 25.0
4
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 4.4 1.37 4.3 1.36 4.1 1.34 4.1 1.32 4.0 1.31 3.9 1.28 3.8 1.25
-14.7 -15.0 5.0 1.44 4.9 1.43 4.8 1.41 4.7 1.38 4.6 1.37 4.5 1.36 4.4 1.33
-9.6 -10.0 5.7 1.51 5.6 1.50 5.4 1.48 5.4 1.46 5.3 1.43 5.1 1.42 5.1 1.41
-4.4
-1.8
-5.0
-2.5
6.4
6.7
1.58
1.61
6.3
6.6
1.57
1.58
6.1
6.5
1.55
1.55
6.1
6.3
1.52
1.52
6.0
6.0
1.51
1.46
5.6
5.6
1.43
1.36
5.2
5.2
1.32
1.24
5
50% 0.8 0.0 7.0 1.65 6.9 1.62 6.5 1.48 6.3 1.46 6.0 1.39 5.6 1.29 5.2 1.17
2.8 2.0 7.1 1.65 6.9 1.57 6.5 1.42 6.3 1.39 6.0 1.34 5.6 1.23 5.2 1.10
6.0 5.0 7.3 1.62 6.9 1.51 6.5 1.33 6.3 1.31 6.0 1.23 5.6 1.14 5.2 1.01
7.0 6.0 7.3 1.60 6.9 1.48 6.5 1.29 6.3 1.27 6.0 1.20 5.6 1.10 5.2 0.98
8.6 7.5 7.3 1.55 6.9 1.43 6.5 1.25 6.3 1.23 6.0 1.18 5.6 1.06 5.2 0.94
11.2
16.4
10.0
15.0
7.3
7.3
1.47
1.33
6.9
6.9
1.34
1.20
6.5
6.5
1.18
1.03
6.3
6.3
1.15
1.00
6.0
6.0
1.10
0.95
5.6
5.6
0.99
0.86
5.2
5.2
0.86
0.71
6

8-5

TD831156-00_MINI_VRF_SYS.indb 5 2012/01/31 14:37:19


Capacity Table
1. Capacity Ratio of Outdoor Unit
1-3. U-52LE1U6, U-52LE1U6E (Cooling)
MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CWB
Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 14.0 1.64 15.2 1.94 16.3 2.19 17.5 2.49 18.7 2.59 19.8 2.89 21.0 3.09
-5.0 14.0 1.69 15.2 1.99 16.3 2.24 17.5 2.59 18.7 2.74 19.8 3.04 21.0 3.19
0.0 14.0 1.79 15.2 2.09 16.3 2.34 17.5 2.69 18.7 2.94 19.8 3.23 21.0 3.33
5.0 14.0 1.89 15.2 2.19 16.3 2.49 17.5 2.84 18.7 3.14 19.8 3.43 21.0 3.53
10.0 14.0 2.04 15.2 2.34 16.3 2.64 17.5 2.99 18.7 3.28 19.8 3.63 21.0 3.73
15.0 14.0 2.24 15.2 2.56 16.3 2.89 17.5 3.19 18.7 3.63 19.8 3.98 21.0 4.08
130% 20.0 14.0 2.49 15.2 2.81 16.3 3.14 17.5 3.48 18.7 3.98 19.8 4.33 21.0 4.48
25.0 14.0 2.79 15.2 3.14 16.3 3.48 17.5 3.88 18.7 4.48 19.8 4.83 20.7 4.78
30.0 14.0 3.19 15.2 3.53 16.3 3.88 17.5 4.38 18.7 4.68 19.6 4.88 20.3 5.08
35.0 14.0 3.73 15.2 4.13 16.3 4.53 17.5 4.98 18.2 5.08 18.9 5.23 19.6 5.37
40.0 14.0 4.38 15.2 4.78 16.3 5.18 15.8 5.33 17.0 5.37 17.9 5.52 18.4 5.72
43.0 14.0 4.98 14.0 5.28 14.0 5.37 14.0 5.47 15.8 5.62 16.8 5.72 17.5 5.87

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 13.5 1.60 14.6 1.89 15.7 2.13 16.9 2.42 18.0 2.52 19.1 2.81 20.2 3.01
-5.0 13.5 1.65 14.6 1.94 15.7 2.18 16.9 2.52 18.0 2.67 19.1 2.96 20.2 3.10
0.0 13.5 1.75 14.6 2.04 15.7 2.28 16.9 2.62 18.0 2.86 19.1 3.15 20.2 3.25
5.0 13.5 1.84 14.6 2.13 15.7 2.42 16.9 2.76 18.0 3.05 19.1 3.35 20.2 3.44
10.0 13.5 1.99 14.6 2.28 15.7 2.57 16.9 2.91 18.0 3.20 19.1 3.54 20.2 3.64
15.0 13.5 2.18 14.6 2.50 15.7 2.81 16.9 3.10 18.0 3.54 19.1 3.88 20.2 3.98
120% 20.0 13.5 2.42 14.6 2.74 15.7 3.05 16.9 3.39 18.0 3.88 19.1 4.22 20.2 4.36
25.0 13.5 2.72 14.6 3.05 15.7 3.39 16.9 3.78 18.0 4.36 19.1 4.70 19.9 4.65
30.0 13.5 3.10 14.6 3.44 15.7 3.78 16.9 4.27 18.0 4.56 18.9 4.75 19.6 4.95
35.0 13.5 3.64 14.6 4.02 15.7 4.41 16.9 4.85 17.5 4.95 18.2 5.09 18.9 5.24
1 40.0
43.0
13.5
13.5
4.27
4.85
14.6
13.5
4.65
5.14
15.7
13.5
5.04
5.24
15.2
13.5
5.19
5.33
16.4
15.2
5.24
5.48
17.2
16.2
5.38
5.58
17.7
16.9
5.58
5.72

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
2 capacity ratio °CDB
-10.0
kW
13.0
kW
1.55
kW
14.1
kW
1.84
kW
15.2
kW
2.07
kW
16.3
kW
2.35
kW
17.3
kW
2.45
kW
18.4
kW
2.73
kW
19.5
kW
2.92
-5.0 13.0 1.60 14.1 1.88 15.2 2.12 16.3 2.45 17.3 2.59 18.4 2.87 19.5 3.01
0.0 13.0 1.69 14.1 1.98 15.2 2.21 16.3 2.54 17.3 2.78 18.4 3.06 19.5 3.15
5.0 13.0 1.79 14.1 2.07 15.2 2.35 16.3 2.68 17.3 2.97 18.4 3.25 19.5 3.34
10.0 13.0 1.93 14.1 2.21 15.2 2.49 16.3 2.82 17.3 3.11 18.4 3.44 19.5 3.53
15.0 13.0 2.12 14.1 2.42 15.2 2.73 16.3 3.01 17.3 3.44 18.4 3.77 19.5 3.86
3 110% 20.0
25.0
13.0
13.0
2.35
2.64
14.1
14.1
2.66
2.97
15.2
15.2
2.97
3.29
16.3
16.3
3.29
3.67
17.3
17.3
3.77
4.24
18.4
18.4
4.10
4.57
19.5
19.2
4.24
4.52
30.0 13.0 3.01 14.1 3.34 15.2 3.67 16.3 4.14 17.3 4.42 18.2 4.61 18.9 4.80
35.0 13.0 3.53 14.1 3.91 15.2 4.28 16.3 4.71 16.9 4.80 17.6 4.94 18.2 5.08
40.0 13.0 4.14 14.1 4.52 15.2 4.90 14.6 5.04 15.8 5.08 16.6 5.22 17.1 5.41
43.0 13.0 4.71 13.0 4.99 13.0 5.08 13.0 5.18 14.6 5.32 15.6 5.41 16.3 5.55

4 Combination(%): Outdoor
Indoor/outdoor air temp.
16.0 17.0 18.0
Indoor air temp. : °CWB
19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 12.4 1.51 13.4 1.78 14.5 2.01 15.5 2.29 16.5 2.38 17.6 2.65 18.6 2.83
-5.0 12.4 1.55 13.4 1.83 14.5 2.06 15.5 2.38 16.5 2.51 17.6 2.79 18.6 2.92
0.0 12.4 1.65 13.4 1.92 14.5 2.15 15.5 2.47 16.5 2.70 17.6 2.97 18.6 3.06
5 5.0
10.0
12.4
12.4
1.74
1.87
13.4
13.4
2.01
2.15
14.5
14.5
2.29
2.42
15.5
15.5
2.60
2.74
16.5
16.5
2.88
3.02
17.6
17.6
3.15
3.34
18.6
18.6
3.24
3.43
15.0 12.4 2.06 13.4 2.35 14.5 2.65 15.5 2.92 16.5 3.34 17.6 3.66 18.6 3.75
100% 20.0 12.4 2.29 13.4 2.58 14.5 2.88 15.5 3.20 16.5 3.66 17.6 3.98 18.6 4.11
25.0 12.4 2.56 13.4 2.88 14.5 3.20 15.5 3.56 16.5 4.11 17.6 4.43 18.3 4.39
30.0 12.4 2.92 13.4 3.24 14.5 3.56 15.5 4.02 16.5 4.30 17.4 4.48 18.0 4.66
35.0 12.4 3.43 13.4 3.79 14.5 4.16 15.5 4.57 16.1 4.66 16.7 4.80 17.4 4.94
6 40.0
43.0
12.4
12.4
4.02
4.57
13.4
12.4
4.39
4.84
14.5
12.4
4.75
4.94
14.0
12.4
4.89
5.03
15.0
14.0
4.94
5.16
15.8
14.9
5.07
5.26
16.3
15.5
5.26
5.39

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -10.0
-5.0
11.2
11.2
1.27
1.31
12.1
12.1
1.50
1.54
13.0
13.0
1.69
1.73
14.0
14.0
1.92
2.00
14.9
14.9
2.00
2.11
15.8
15.8
2.23
2.34
16.7
16.7
2.38
2.46
0.0 11.2 1.38 12.1 1.61 13.0 1.80 14.0 2.07 14.9 2.26 15.8 2.50 16.7 2.57
5.0 11.2 1.46 12.1 1.69 13.0 1.92 14.0 2.19 14.9 2.42 15.8 2.65 16.7 2.73
10.0 11.2 1.57 12.1 1.80 13.0 2.03 14.0 2.30 14.9 2.53 15.8 2.80 16.7 2.88
15.0 11.2 1.73 12.1 1.98 13.0 2.23 14.0 2.46 14.9 2.80 15.8 3.07 16.7 3.15
90% 20.0 11.2 1.92 12.1 2.17 13.0 2.42 14.0 2.69 14.9 3.07 15.8 3.34 16.7 3.45
8 25.0
30.0
11.2
11.2
2.15
2.46
12.1
12.1
2.42
2.73
13.0
13.0
2.69
2.99
14.0
14.0
2.99
3.38
14.9
14.9
3.45
3.61
15.8
15.6
3.72
3.76
16.5
16.2
3.69
3.92
35.0 11.2 2.88 12.1 3.19 13.0 3.49 14.0 3.84 14.5 3.92 15.1 4.03 15.6 4.15
40.0 11.2 3.38 12.1 3.69 13.0 3.99 12.6 4.11 13.5 4.15 14.2 4.26 14.6 4.41
43.0 11.2 3.84 11.2 4.07 11.2 4.15 11.2 4.22 12.6 4.34 13.4 4.41 14.0 4.53

8-6

TD831156-00_MINI_VRF_SYS.indb 6 2012/01/31 14:37:20


Capacity Table
1. Capacity Ratio of Outdoor Unit

MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CWB
Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 9.9 1.03 10.7 1.21 11.6 1.37 12.4 1.55 13.2 1.62 14.0 1.80 14.9 1.93
-5.0 9.9 1.06 10.7 1.24 11.6 1.40 12.4 1.62 13.2 1.71 14.0 1.90 14.9 1.99
0.0 9.9 1.12 10.7 1.31 11.6 1.46 12.4 1.68 13.2 1.83 14.0 2.02 14.9 2.08
5.0 9.9 1.18 10.7 1.37 11.6 1.55 12.4 1.77 13.2 1.96 14.0 2.14 14.9 2.21
10.0 9.9 1.27 10.7 1.46 11.6 1.65 12.4 1.86 13.2 2.05 14.0 2.27 14.9 2.33
15.0 9.9 1.40 10.7 1.60 11.6 1.80 12.4 1.99 13.2 2.27 14.0 2.49 14.9 2.55
80% 20.0 9.9 1.55 10.7 1.76 11.6 1.96 12.4 2.18 13.2 2.49 14.0 2.70 14.9 2.80
25.0 9.9 1.74 10.7 1.96 11.6 2.18 12.4 2.42 13.2 2.80 14.0 3.01 14.6 2.98
30.0 9.9 1.99 10.7 2.21 11.6 2.42 12.4 2.73 13.2 2.92 13.9 3.05 14.4 3.17
35.0 9.9 2.33 10.7 2.58 11.6 2.83 12.4 3.11 12.9 3.17 13.4 3.26 13.9 3.36
40.0 9.9 2.73 10.7 2.98 11.6 3.23 11.2 3.33 12.0 3.36 12.6 3.45 13.0 3.57
43.0 9.9 3.11 9.9 3.29 9.9 3.36 9.9 3.42 11.2 3.51 11.9 3.57 12.4 3.67

Indoor air temp. : °CWB


Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 8.7 0.83 9.4 0.98 10.1 1.11 10.9 1.26 11.6 1.31 12.3 1.46 13.0 1.56
-5.0 8.7 0.85 9.4 1.01 10.1 1.13 10.9 1.31 11.6 1.38 12.3 1.53 13.0 1.61
0.0 8.7 0.90 9.4 1.06 10.1 1.18 10.9 1.36 11.6 1.48 12.3 1.63 13.0 1.68
5.0 8.7 0.96 9.4 1.11 10.1 1.26 10.9 1.43 11.6 1.58 12.3 1.73 13.0 1.78
10.0 8.7 1.03 9.4 1.18 10.1 1.33 10.9 1.51 11.6 1.66 12.3 1.83 13.0 1.89
15.0 8.7 1.13 9.4 1.29 10.1 1.46 10.9 1.61 11.6 1.83 12.3 2.01 13.0 2.06
70% 20.0 8.7 1.26 9.4 1.42 10.1 1.58 10.9 1.76 11.6 2.01 12.3 2.19 13.0 2.26
25.0 8.7 1.41 9.4 1.58 10.1 1.76 10.9 1.96 11.6 2.26 12.3 2.44 12.8 2.41
30.0 8.7 1.61 9.4 1.78 10.1 1.96 10.9 2.21 11.6 2.36 12.2 2.46 12.6 2.56
35.0 8.7 1.89 9.4 2.09 10.1 2.29 10.9 2.51 11.3 2.56 11.7 2.64 12.2 2.71
40.0
43.0
8.7
8.7
2.21
2.51
9.4
8.7
2.41
2.66
10.1
8.7
2.61
2.71
9.8
8.7
2.69
2.76
10.5
9.8
2.71
2.84
11.1
10.4
2.79
2.89
11.4
10.9
2.89
2.97
1
Indoor air temp. : °CWB
Combination(%): Outdoor
16.0 17.0 18.0 19.0 20.0 21.0 22.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
-10.0
kW
7.4
kW
0.68
kW
8.1
kW
0.80
kW
8.7
kW
0.90
kW
9.3
kW
1.03
kW
9.9
kW
1.07
kW
10.5
kW
1.19
kW
11.2
kW
1.28 2
-5.0 7.4 0.70 8.1 0.82 8.7 0.93 9.3 1.07 9.9 1.13 10.5 1.25 11.2 1.32
0.0 7.4 0.74 8.1 0.86 8.7 0.97 9.3 1.11 9.9 1.21 10.5 1.34 11.2 1.38
5.0 7.4 0.78 8.1 0.90 8.7 1.03 9.3 1.17 9.9 1.30 10.5 1.42 11.2 1.46
10.0 7.4 0.84 8.1 0.97 8.7 1.09 9.3 1.23 9.9 1.36 10.5 1.50 11.2 1.54
15.0 7.4 0.93 8.1 1.06 8.7 1.19 9.3 1.32 9.9 1.50 10.5 1.65 11.2 1.69
60% 20.0
25.0
7.4
7.4
1.03
1.15
8.1
8.1
1.16
1.30
8.7
8.7
1.30
1.44
9.3
9.3
1.44
1.60
9.9
9.9
1.65
1.85
10.5
10.5
1.79
1.99
11.2
11.0
1.85
1.97 3
30.0 7.4 1.32 8.1 1.46 8.7 1.60 9.3 1.81 9.9 1.93 10.4 2.02 10.8 2.10
35.0 7.4 1.54 8.1 1.71 8.7 1.87 9.3 2.06 9.7 2.10 10.0 2.16 10.4 2.22
40.0 7.4 1.81 8.1 1.97 8.7 2.14 8.4 2.20 9.0 2.22 9.5 2.28 9.8 2.36
43.0 7.4 2.06 7.4 2.18 7.4 2.22 7.4 2.26 8.4 2.32 8.9 2.36 9.3 2.43

Combination(%): Outdoor
Indoor/outdoor air temp.
16.0 17.0 18.0
Indoor air temp. : °CWB
19.0 20.0 21.0 22.0
4
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio °CDB
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-10.0 6.2 0.52 6.7 0.62 7.2 0.70 7.8 0.79 8.3 0.82 8.8 0.92 9.3 0.98
-5.0 6.2 0.54 6.7 0.63 7.2 0.71 7.8 0.82 8.3 0.87 8.8 0.96 9.3 1.01
0.0 6.2 0.57 6.7 0.66 7.2 0.74 7.8 0.85 8.3 0.93 8.8 1.03 9.3 1.06
5.0
10.0
6.2
6.2
0.60
0.65
6.7
6.7
0.70
0.74
7.2
7.2
0.79
0.84
7.8
7.8
0.90
0.95
8.3
8.3
1.00
1.04
8.8
8.8
1.09
1.15
9.3
9.3
1.12
1.19
5
15.0 6.2 0.71 6.7 0.81 7.2 0.92 7.8 1.01 8.3 1.15 8.8 1.26 9.3 1.30
50% 20.0 6.2 0.79 6.7 0.89 7.2 1.00 7.8 1.11 8.3 1.26 8.8 1.38 9.3 1.42
25.0 6.2 0.89 6.7 1.00 7.2 1.11 7.8 1.23 8.3 1.42 8.8 1.53 9.1 1.52
30.0 6.2 1.01 6.7 1.12 7.2 1.23 7.8 1.39 8.3 1.49 8.7 1.55 9.0 1.61
35.0 6.2 1.19 6.7 1.31 7.2 1.44 7.8 1.58 8.1 1.61 8.4 1.66 8.7 1.71
40.0
43.0
6.2
6.2
1.39
1.58
6.7
6.2
1.52
1.68
7.2
6.2
1.64
1.71
7.0
6.2
1.69
1.74
7.5
7.0
1.71
1.79
7.9
7.4
1.76
1.82
8.1
7.8
1.82
1.87
6

8-7

TD831156-00_MINI_VRF_SYS.indb 7 2012/01/31 14:37:20


Capacity Table
1. Capacity Ratio of Outdoor Unit
1-4. U-52LE1U6, U-52LE1U6E (Heating)
MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 12.1 4.31 11.7 4.22 11.3 4.12 11.1 4.07 10.7 4.00 10.3 3.88 9.7 3.74
-14.7 -15.0 14.1 4.65 13.7 4.50 13.3 4.41 13.1 4.36 12.9 4.29 12.5 4.17 11.7 4.02
-9.6 -10.0 16.1 4.93 15.7 4.79 15.3 4.69 15.1 4.65 14.9 4.58 14.5 4.46 13.7 4.31
-4.4 -5.0 18.3 5.17 17.9 5.08 17.7 4.98 17.1 4.93 16.9 4.86 16.5 4.74 15.5 4.60
-1.8 -2.5 19.1 5.32 18.7 5.22 18.3 5.13 18.1 5.08 17.9 5.01 17.5 4.84 16.5 4.69
130% 0.8 0.0 20.3 5.46 19.9 5.32 19.3 5.22 19.1 5.17 18.9 5.10 17.9 4.93 16.5 4.41
2.8 2.0 21.1 5.61 20.7 5.46 20.1 5.37 19.9 5.27 19.2 5.20 17.9 4.65 16.5 4.12
6.0 5.0 22.5 5.80 21.9 5.70 20.6 5.27 19.9 4.93 19.2 4.69 17.9 4.31 16.5 3.83
7.0 6.0 22.9 5.84 21.9 5.56 20.6 5.03 19.9 4.79 19.2 4.55 17.9 4.17 16.5 3.69
8.6 7.5 23.3 5.89 21.9 5.37 20.6 4.89 19.9 4.65 19.2 4.41 17.9 4.02 16.5 3.55
11.2 10.0 23.3 5.61 21.9 5.08 20.6 4.60 19.9 4.36 19.2 4.12 17.9 3.74 16.5 3.21
16.4 15.0 23.3 5.03 21.9 4.55 20.6 4.02 19.9 3.78 19.2 3.55 17.9 3.16 16.5 2.68

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 11.7 4.24 11.3 4.15 10.9 4.05 10.7 4.01 10.3 3.94 10.0 3.82 9.4 3.68
-14.7 -15.0 13.6 4.57 13.2 4.43 12.8 4.34 12.6 4.29 12.4 4.22 12.1 4.10 11.3 3.96
-9.6 -10.0 15.5 4.85 15.1 4.71 14.7 4.62 14.6 4.57 14.4 4.50 14.0 4.38 13.2 4.24
-4.4 -5.0 17.6 5.09 17.2 5.00 17.0 4.90 16.5 4.85 16.3 4.78 15.9 4.67 14.9 4.52
-1.8 -2.5 18.4 5.23 18.0 5.14 17.6 5.04 17.4 5.00 17.2 4.92 16.9 4.76 15.9 4.62
120% 0.8 0.0 19.5 5.37 19.1 5.23 18.6 5.14 18.4 5.09 18.2 5.02 17.2 4.85 15.9 4.34
2.8 2.0 20.3 5.51 19.9 5.37 19.3 5.28 19.1 5.18 18.5 5.11 17.2 4.57 15.9 4.05
6.0 5.0 21.6 5.70 21.1 5.61 19.8 5.18 19.1 4.85 18.5 4.62 17.2 4.24 15.9 3.77
7.0 6.0 22.0 5.75 21.1 5.47 19.8 4.95 19.1 4.71 18.5 4.48 17.2 4.10 15.9 3.63
8.6 7.5 22.4 5.80 21.1 5.28 19.8 4.81 19.1 4.57 18.5 4.34 17.2 3.96 15.9 3.49
1 11.2
16.4
10.0
15.0
22.4
22.4
5.51
4.95
21.1
21.1
5.00
4.48
19.8
19.8
4.52
3.96
19.1
19.1
4.29
3.72
18.5
18.5
4.05
3.49
17.2
17.2
3.68
3.11
15.9
15.9
3.16
2.64

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
2 capacity ratio
DB
-19.8
WB
-20.0
kW
11.3
kW
4.18
kW
10.9
kW
4.09
kW
10.5
kW
4.00
kW
10.3
kW
3.95
kW
10.0
kW
3.88
kW
9.6
kW
3.77
kW
9.1
kW
3.63
-14.7 -15.0 13.1 4.51 12.8 4.37 12.4 4.28 12.2 4.23 12.0 4.16 11.6 4.04 10.9 3.90
-9.6 -10.0 15.0 4.79 14.6 4.65 14.2 4.56 14.0 4.51 13.9 4.44 13.5 4.32 12.8 4.18
-4.4 -5.0 17.0 5.02 16.6 4.93 16.4 4.83 15.9 4.79 15.7 4.72 15.3 4.60 14.4 4.46
-1.8 -2.5 17.7 5.16 17.4 5.07 17.0 4.97 16.8 4.93 16.6 4.86 16.3 4.70 15.3 4.56
110% 0.8 0.0 18.8 5.30 18.5 5.16 17.9 5.07 17.7 5.02 17.6 4.95 16.6 4.79 15.3 4.28
3 2.8
6.0
2.0
5.0
19.6
20.9
5.44
5.62
19.2
20.3
5.30
5.53
18.7
19.1
5.21
5.11
18.5
18.5
5.11
4.79
17.8
17.8
5.04
4.56
16.6
16.6
4.51
4.18
15.3
15.3
4.00
3.72
7.0 6.0 21.3 5.67 20.3 5.39 19.1 4.88 18.5 4.65 17.8 4.42 16.6 4.04 15.3 3.58
8.6 7.5 21.6 5.72 20.3 5.21 19.1 4.74 18.5 4.51 17.8 4.28 16.6 3.90 15.3 3.44
11.2 10.0 21.6 5.44 20.3 4.93 19.1 4.46 18.5 4.23 17.8 4.00 16.6 3.63 15.3 3.11
16.4 15.0 21.6 4.88 20.3 4.42 19.1 3.90 18.5 3.67 17.8 3.44 16.6 3.07 15.3 2.60

4 Combination(%):
Indoor/outdoor
Outdoor
air temp.
15.0 17.0 19.0
Indoor air temp. : °CDB
20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 10.7 4.12 10.4 4.03 10.0 3.94 9.9 3.89 9.5 3.82 9.2 3.71 8.6 3.57
-14.7 -15.0 12.5 4.44 12.1 4.31 11.8 4.21 11.6 4.17 11.4 4.10 11.1 3.98 10.4 3.85
-9.6 -10.0 14.3 4.72 13.9 4.58 13.6 4.49 13.4 4.44 13.2 4.37 12.8 4.26 12.1 4.12
5 -4.4
-1.8
-5.0
-2.5
16.2
16.9
4.95
5.08
15.8
16.5
4.85
4.99
15.7
16.2
4.76
4.90
15.1
16.0
4.72
4.85
15.0
15.8
4.65
4.79
14.6
15.5
4.53
4.63
13.7
14.6
4.40
4.49
100% 0.8 0.0 18.0 5.22 17.6 5.08 17.1 4.99 16.9 4.95 16.7 4.88 15.8 4.72 14.6 4.21
2.8 2.0 18.7 5.36 18.3 5.22 17.8 5.13 17.6 5.04 17.0 4.97 15.8 4.44 14.6 3.94
6.0 5.0 19.9 5.54 19.4 5.45 18.2 5.04 17.6 4.72 17.0 4.49 15.8 4.12 14.6 3.66
7.0 6.0 20.2 5.59 19.4 5.31 18.2 4.81 17.6 4.58 17.0 4.35 15.8 3.98 14.6 3.53
8.6 7.5 20.6 5.63 19.4 5.13 18.2 4.67 17.6 4.44 17.0 4.21 15.8 3.85 14.6 3.39
6 11.2
16.4
10.0
15.0
20.6
20.6
5.36
4.81
19.4
19.4
4.85
4.35
18.2
18.2
4.40
3.85
17.6
17.6
4.17
3.62
17.0
17.0
3.94
3.39
15.8
15.8
3.57
3.02
14.6
14.6
3.07
2.56

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
7 -19.8
-14.7
-20.0
-15.0
9.7
11.2
3.59
3.87
9.3
10.9
3.51
3.75
9.0
10.6
3.43
3.67
8.9
10.5
3.39
3.63
8.6
10.3
3.33
3.57
8.2
10.0
3.23
3.47
7.8
9.3
3.11
3.35
-9.6 -10.0 12.8 4.10 12.5 3.98 12.2 3.90 12.0 3.87 11.9 3.81 11.6 3.71 10.9 3.59
-4.4 -5.0 14.6 4.30 14.3 4.22 14.1 4.14 13.6 4.10 13.5 4.04 13.1 3.94 12.4 3.83
-1.8 -2.5 15.2 4.42 14.9 4.34 14.6 4.26 14.4 4.22 14.3 4.16 13.9 4.02 13.1 3.90
90% 0.8 0.0 16.2 4.54 15.8 4.42 15.4 4.34 15.2 4.30 15.0 4.24 14.3 4.10 13.1 3.67
2.8 2.0 16.8 4.66 16.5 4.54 16.0 4.46 15.8 4.38 15.3 4.32 14.3 3.87 13.1 3.43
8 6.0
7.0
5.0
6.0
17.9
18.2
4.82
4.86
17.4
17.4
4.74
4.62
16.4
16.4
4.38
4.18
15.8
15.8
4.10
3.98
15.3
15.3
3.90
3.79
14.3
14.3
3.59
3.47
13.1
13.1
3.19
3.07
8.6 7.5 18.5 4.90 17.4 4.46 16.4 4.06 15.8 3.87 15.3 3.67 14.3 3.35 13.1 2.95
11.2 10.0 18.5 4.66 17.4 4.22 16.4 3.83 15.8 3.63 15.3 3.43 14.3 3.11 13.1 2.67
16.4 15.0 18.5 4.18 17.4 3.79 16.4 3.35 15.8 3.15 15.3 2.95 14.3 2.63 13.1 2.23

8-8

TD831156-00_MINI_VRF_SYS.indb 8 2012/01/31 14:37:21


Capacity Table
1. Capacity Ratio of Outdoor Unit

MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 8.6 3.03 8.3 2.96 8.0 2.90 7.9 2.86 7.6 2.81 7.3 2.73 6.9 2.63
-14.7 -15.0 10.0 3.27 9.7 3.16 9.4 3.10 9.3 3.06 9.2 3.01 8.9 2.93 8.3 2.83
-9.6 -10.0 11.4 3.47 11.1 3.37 10.8 3.30 10.7 3.27 10.6 3.21 10.3 3.13 9.7 3.03
-4.4 -5.0 13.0 3.64 12.7 3.57 12.5 3.50 12.1 3.47 12.0 3.42 11.7 3.33 11.0 3.23
-1.8 -2.5 13.5 3.74 13.2 3.67 13.0 3.60 12.8 3.57 12.7 3.52 12.4 3.40 11.7 3.30
80% 0.8 0.0 14.4 3.84 14.1 3.74 13.7 3.67 13.5 3.64 13.4 3.59 12.7 3.47 11.7 3.10
2.8 2.0 14.9 3.94 14.6 3.84 14.2 3.77 14.1 3.70 13.6 3.65 12.7 3.27 11.7 2.90
6.0 5.0 15.9 4.07 15.5 4.01 14.6 3.70 14.1 3.47 13.6 3.30 12.7 3.03 11.7 2.69
7.0 6.0 16.2 4.11 15.5 3.90 14.6 3.53 14.1 3.37 13.6 3.20 12.7 2.93 11.7 2.59
8.6 7.5 16.5 4.14 15.5 3.77 14.6 3.43 14.1 3.27 13.6 3.10 12.7 2.83 11.7 2.49
11.2 10.0 16.5 3.94 15.5 3.57 14.6 3.23 14.1 3.06 13.6 2.90 12.7 2.63 11.7 2.26
16.4 15.0 16.5 3.53 15.5 3.20 14.6 2.83 14.1 2.66 13.6 2.49 12.7 2.22 11.7 1.89

Indoor air temp. : °CDB


Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 7.5 2.51 7.3 2.46 7.0 2.40 6.9 2.37 6.7 2.33 6.4 2.26 6.0 2.18
-14.7 -15.0 8.7 2.71 8.5 2.63 8.3 2.57 8.1 2.54 8.0 2.50 7.8 2.43 7.3 2.35
-9.6 -10.0 10.0 2.88 9.7 2.79 9.5 2.74 9.4 2.71 9.2 2.67 9.0 2.60 8.5 2.51
-4.4 -5.0 11.3 3.02 11.1 2.96 11.0 2.91 10.6 2.88 10.5 2.84 10.2 2.77 9.6 2.68
-1.8 -2.5 11.8 3.10 11.6 3.05 11.3 2.99 11.2 2.96 11.1 2.92 10.8 2.82 10.2 2.74
70% 0.8 0.0 12.6 3.18 12.3 3.10 12.0 3.05 11.8 3.02 11.7 2.98 11.1 2.88 10.2 2.57
2.8 2.0 13.1 3.27 12.8 3.18 12.4 3.13 12.3 3.07 11.9 3.03 11.1 2.71 10.2 2.40
6.0 5.0 13.9 3.38 13.6 3.32 12.8 3.07 12.3 2.88 11.9 2.74 11.1 2.51 10.2 2.24
7.0 6.0 14.2 3.41 13.6 3.24 12.8 2.93 12.3 2.79 11.9 2.65 11.1 2.43 10.2 2.15
8.6 7.5 14.4 3.44 13.6 3.13 12.8 2.85 12.3 2.71 11.9 2.57 11.1 2.35 10.2 2.07
11.2
16.4
10.0
15.0
14.4
14.4
3.27
2.93
13.6
13.6
2.96
2.65
12.8
12.8
2.68
2.35
12.3
12.3
2.54
2.21
11.9
11.9
2.40
2.07
11.1
11.1
2.18
1.84
10.2
10.2
1.87
1.56
1
Indoor air temp. : °CDB
Combination(%): Outdoor
15.0 17.0 19.0 20.0 21.0 23.0 25.0
Indoor/outdoor air temp.
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB
-19.8
WB
-20.0
kW
6.4
kW
2.12
kW
6.2
kW
2.08
kW
6.0
kW
2.03
kW
5.9
kW
2.00
kW
5.7
kW
1.97
kW
5.5
kW
1.91
kW
5.2
kW
1.84 2
-14.7 -15.0 7.5 2.29 7.3 2.22 7.1 2.17 7.0 2.15 6.9 2.11 6.7 2.05 6.2 1.98
-9.6 -10.0 8.6 2.43 8.3 2.36 8.1 2.31 8.0 2.29 7.9 2.25 7.7 2.19 7.3 2.12
-4.4 -5.0 9.7 2.55 9.5 2.50 9.4 2.45 9.1 2.43 9.0 2.39 8.8 2.34 8.2 2.26
-1.8 -2.5 10.1 2.62 9.9 2.57 9.7 2.52 9.6 2.50 9.5 2.46 9.3 2.38 8.8 2.31
60% 0.8 0.0 10.8 2.69 10.6 2.62 10.2 2.57 10.1 2.55 10.0 2.51 9.5 2.43 8.8 2.17
2.8
6.0
2.0
5.0
11.2
11.9
2.76
2.85
11.0
11.6
2.69
2.81
10.7
10.9
2.64
2.59
10.6
10.6
2.59
2.43
10.2
10.2
2.56
2.31
9.5
9.5
2.29
2.12
8.8
8.8
2.03
1.89 3
7.0 6.0 12.1 2.88 11.6 2.74 10.9 2.48 10.6 2.36 10.2 2.24 9.5 2.05 8.8 1.82
8.6 7.5 12.4 2.90 11.6 2.64 10.9 2.41 10.6 2.29 10.2 2.17 9.5 1.98 8.8 1.75
11.2 10.0 12.4 2.76 11.6 2.50 10.9 2.26 10.6 2.15 10.2 2.03 9.5 1.84 8.8 1.58
16.4 15.0 12.4 2.48 11.6 2.24 10.9 1.98 10.6 1.86 10.2 1.75 9.5 1.56 8.8 1.32

Combination(%):
Indoor/outdoor
Outdoor
air temp.
15.0 17.0 19.0
Indoor air temp. : °CDB
20.0 21.0 23.0 25.0
4
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
capacity ratio
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 5.4 1.73 5.2 1.69 5.0 1.65 4.9 1.64 4.8 1.61 4.6 1.56 4.3 1.50
-14.7 -15.0 6.2 1.87 6.1 1.81 5.9 1.77 5.8 1.75 5.7 1.72 5.5 1.67 5.2 1.62
-9.6 -10.0 7.1 1.98 7.0 1.92 6.8 1.89 6.7 1.87 6.6 1.84 6.4 1.79 6.1 1.73
-4.4
-1.8
-5.0
-2.5
8.1
8.4
2.08
2.14
7.9
8.3
2.04
2.10
7.8
8.1
2.00
2.06
7.6
8.0
1.98
2.04
7.5
7.9
1.95
2.01
7.3
7.7
1.90
1.94
6.9
7.3
1.85
1.89
5
50% 0.8 0.0 9.0 2.19 8.8 2.14 8.5 2.10 8.4 2.08 8.4 2.05 7.9 1.98 7.3 1.77
2.8 2.0 9.3 2.25 9.2 2.19 8.9 2.15 8.8 2.12 8.5 2.09 7.9 1.87 7.3 1.65
6.0 5.0 9.9 2.33 9.7 2.29 9.1 2.12 8.8 1.98 8.5 1.89 7.9 1.73 7.3 1.54
7.0 6.0 10.1 2.35 9.7 2.23 9.1 2.02 8.8 1.92 8.5 1.83 7.9 1.67 7.3 1.48
8.6 7.5 10.3 2.37 9.7 2.15 9.1 1.96 8.8 1.87 8.5 1.77 7.9 1.62 7.3 1.42
11.2
16.4
10.0
15.0
10.3
10.3
2.25
2.02
9.7
9.7
2.04
1.83
9.1
9.1
1.85
1.62
8.8
8.8
1.75
1.52
8.5
8.5
1.65
1.42
7.9
7.9
1.50
1.27
7.3
7.3
1.29
1.08
6

8-9

TD831156-00_MINI_VRF_SYS.indb 9 2012/01/31 14:37:21


Capacity Table
2. Cooling Capacity of Indoor Unit
2-1. 4-Way Cassette Type (U1 Type), 4-Way Cassette 60×60 Type (Y1 Type)
S-12MU1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 15.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
16 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
17 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

1 29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2
18 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
2 27
29
SHC
SHC
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.4
3.2
3.3
3.1
3.2
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.7
2.1
1.6
2.1
1.6
2.0
1.6
2.0
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.3
31 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7
20 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6

5 29
31
SHC
SHC
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.2
3.7
3.2
3.7
3.2
3.6
3.2
3.6
3.1
3.5
3.1
3.4
3.1
3.3
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5
21 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0
6 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.4 3.3 3.3
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
1.9
2.4
1.9
2.4
1.9
2.3
1.9
2.3
1.9
2.3
1.8
2.3
1.8
2.2
1.8
2.2
1.7
2.2
29 SHC 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.5
23 27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0
29 SHC 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9

8 - 10

TD831156-00_MINI_VRF_SYS.indb 10 2012/01/31 14:37:22


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MU1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
15 23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
16 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
29 SHC
TC
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.0
1
21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2
18 25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7
27
29
SHC
SHC
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.3
4.9
4.3
4.8
2
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

21
23
SHC
SHC
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.0
2.4
3.0
2.4
2.9
2.3
2.9
3
19 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2 4
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.6
29
31
SHC
SHC
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.4
5.0
4.4
5.0
4.3
4.9
4.3
4.9
4.2
4.8
4.2
4.7
5
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.3 6
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.6 4.5 4.4
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

22
25
27
SHC
SHC
3.0
3.5
3.0
3.5
3.0
3.5
3.0
3.5
2.9
3.5
2.9
3.4
2.9
3.4
2.8
3.4
2.8
3.3
2.8
3.3
2.7
3.3
2.7
3.2
2.6
3.2
2.6
3.2
2.5
3.1
7
29 SHC 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.7 3.6
31 SHC 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.4 4.4 4.3 4.3 4.2 4.2
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

25 SHC 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 8
23 27 SHC 3.3 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8
29 SHC 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4
31 SHC 4.4 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9

8 - 11

TD831156-00_MINI_VRF_SYS.indb 11 2012/01/31 14:37:22


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MU1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.3 kW AIR FLOW 20.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
15 23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
25 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
16 23 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
17 23 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

1 29 SHC
TC
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.8
6.3
6.7
6.3
6.5

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0
18 25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7
2 27
29
SHC
SHC
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.1
5.4
6.0
5.3
5.9
31 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.5
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 7.0 6.8 6.6

3 21
23
SHC
SHC
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.3
3.9
3.2
3.9
3.1
3.8
3.1
3.7
3.0
3.6
19 25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.3 4.3
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 4.9
29 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.7 5.6 5.5
31 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.3 6.3 6.2
4 TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8

23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.5 3.5 3.4 3.3 3.3
20 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.5

5 29
31
SHC
SHC
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.3
5.6
6.2
5.5
6.2
5.5
6.1
5.4
6.1
5.3
6.0
5.3
5.9
5.2
5.8
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.1 7.9 7.8 7.7 7.5 7.3 7.2 7.0

23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.1 3.1 3.0 2.9
21 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6
6 27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.3 4.3 4.2
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9
31 SHC 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.9 5.9 5.8 5.7 5.7 5.6 5.6 5.5
TC 8.8 8.8 8.8 8.7 8.7 8.6 8.5 8.4 8.2 8.1 8.0 7.8 7.6 7.5 7.3

7 22
25
27
SHC
SHC
3.8
4.5
3.8
4.5
3.8
4.5
3.8
4.5
3.8
4.4
3.7
4.4
3.7
4.3
3.7
4.3
3.6
4.3
3.5
4.2
3.5
4.1
3.5
4.1
3.4
4.0
3.3
4.0
3.3
3.9
29 SHC 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.5
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.6 5.5 5.5 5.4 5.4 5.3 5.3 5.2
TC 9.3 9.2 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.0 7.8 7.6

8 25 SHC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.1 3.1 3.0 2.9
23 27 SHC 4.2 4.2 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6
29 SHC 4.8 4.8 4.8 4.8 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.4 4.3 4.2
31 SHC 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9

8 - 12

TD831156-00_MINI_VRF_SYS.indb 12 2012/01/31 14:37:22


Capacity Table
2. Cooling Capacity of Indoor Unit

S-36MU1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 10.6 kW AIR FLOW 28.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

21 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
15 23 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5
25 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

21 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
16 23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

21 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3
17 23 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
29 SHC
TC
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.9
8.6
9.8
8.6
9.5
1
21 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.8
23 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.7
18 25 SHC 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.5
27
29
SHC
SHC
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.5
8.3
7.4
8.3
7.3
8.2
2
31 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.1 9.0
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 10.1 9.9 9.6

21
23
SHC
SHC
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.7
5.6
4.6
5.5
4.6
5.3
4.4
5.2
4.3
5.1
3
19 25 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0
27 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.1 7.0 6.9 6.8
29 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.8 7.7
31 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.8 8.7 8.6 8.4
TC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.2 11.0 10.8 10.6 10.4 10.1 9.8 4
23 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.0 4.9 4.8 4.7
20 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.9 5.8 5.7 5.6 5.5
27 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.8 6.6 6.5 6.4 6.3
29
31
SHC
SHC
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.8
8.6
7.7
8.5
7.5
8.4
7.5
8.3
7.4
8.2
7.3
8.1
7.1
8.0
5
TC 12.0 12.0 12.0 12.0 12.0 12.0 11.9 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1

23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2
21 25 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.7 5.6 5.5 5.5 5.3 5.2 5.2 5.1
27
29
SHC
SHC
6.6
7.5
6.6
7.5
6.6
7.5
6.6
7.5
6.6
7.5
6.6
7.5
6.6
7.4
6.5
7.3
6.4
7.3
6.4
7.2
6.2
7.1
6.2
7.0
6.1
6.9
6.0
6.8
5.9
6.7
6
31 SHC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.2 8.1 8.0 7.9 7.8 7.8 7.7 7.5
TC 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6

22
25
27
SHC
SHC
5.5
6.3
5.5
6.3
5.5
6.3
5.5
6.3
5.4
6.2
5.3
6.2
5.3
6.1
5.2
6.1
5.2
6.0
5.1
5.9
5.0
5.9
5.0
5.7
4.8
5.7
4.7
5.6
4.6
5.5
7
29 SHC 7.1 7.1 7.1 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3
31 SHC 8.0 8.0 8.0 7.9 7.9 7.9 7.8 7.8 7.7 7.6 7.5 7.4 7.3 7.2 7.1
TC 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1

25 SHC 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.4 4.3 4.2 8
23 27 SHC 6.0 6.0 5.9 5.9 5.9 5.8 5.7 5.7 5.6 5.5 5.5 5.3 5.3 5.2 5.1
29 SHC 6.8 6.8 6.8 6.7 6.7 6.6 6.6 6.5 6.4 6.4 6.3 6.2 6.1 6.0 5.9
31 SHC 7.7 7.6 7.6 7.5 7.5 7.4 7.4 7.3 7.3 7.2 7.1 7.0 6.9 6.9 6.8

8 - 13

TD831156-00_MINI_VRF_SYS.indb 13 2012/01/31 14:37:22


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MY1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
17 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1 29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
2 27
29
SHC
SHC
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.8
3.2
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
1.9
1.5
1.9
1.5
1.9
19 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.3
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4

5 29
31
SHC
SHC
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
2.9
3.3
2.9
3.3
2.9
3.3
2.9
3.2
2.8
3.2
2.8
3.2
2.8
3.1
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5
21 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
6 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.2
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.7
2.1
1.7
2.1
1.7
2.0
1.6
2.0
29 SHC 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5
23 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
29 SHC 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
31 SHC 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6

8 - 14

TD831156-00_MINI_VRF_SYS.indb 14 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MY1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 12.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
15 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
29 SHC
TC
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.0
1
21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1
18 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6
27
29
SHC
SHC
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.2
4.7
4.1
4.6
2
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

21
23
SHC
SHC
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.4
2.9
2.4
2.9
2.3
2.8
3
19 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2 4
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.5
29
31
SHC
SHC
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.4
4.9
4.3
4.8
4.3
4.8
4.3
4.8
4.2
4.7
4.2
4.7
4.1
4.6
4.0
4.5
5
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 6
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8
31 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.5 4.5 4.4 4.4 4.3 4.3
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

22
25
27
SHC
SHC
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.8
3.4
2.8
3.3
2.8
3.3
2.7
3.2
2.7
3.2
2.7
3.2
2.6
3.1
2.6
3.1
2.5
3.0
7
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.5
31 SHC 4.5 4.5 4.5 4.4 4.4 4.4 4.4 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

25 SHC 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 8
23 27 SHC 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8
29 SHC 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3
31 SHC 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8

8 - 15

TD831156-00_MINI_VRF_SYS.indb 15 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit
2-2. 1-Way Cassette Type (D1 Type)
S-07MD1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
15 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
16 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
17 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1 29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
18 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
2 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

3 21
23
SHC
SHC
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
0.9
1.2
0.9
1.1
0.9
1.1
19 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0
4 TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.0

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4
5 29
31
SHC
SHC
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.8
2.0
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.6
1.8
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
21 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
6 27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

7 22
25
27
SHC
SHC
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.4
1.1
1.4
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.0
1.3
1.0
1.2
1.0
1.2
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

8 25 SHC 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
23 27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
29 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
31 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5
8 - 16

TD831156-00_MINI_VRF_SYS.indb 16 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MD1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
15 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

21
23
SHC
SHC
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.2
1.5
1.2
1.5
1.2
1.4
1.2
1.4
3
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6 4
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8
29
31
SHC
SHC
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.5
2.2
2.4
2.2
2.4
2.1
2.4
2.1
2.4
2.1
2.3
2.1
2.3
5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 6
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

22
25
27
SHC
SHC
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.6
1.4
1.6
1.3
1.6
1.3
1.6
1.3
1.5
1.3
1.5
7
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8
31 SHC 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

25 SHC 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1 8
23 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
29 SHC 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
31 SHC 2.2 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9
8 - 17

TD831156-00_MINI_VRF_SYS.indb 17 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MD1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
15 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
16 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
17 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
1 29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
18 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
2 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.5
1.8
1.5
1.8
19 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6
20 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2
5 29
31
SHC
SHC
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.7
3.0
2.6
2.9
2.6
2.9
2.6
2.9
2.5
2.8
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8
6 27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1 2.1 2.1
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.7
2.0
1.7
2.0
1.7
2.0
1.6
1.9
1.6
1.9
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4
23 27 SHC 2.1 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8
29 SHC 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1 2.1 2.1
31 SHC 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4
8 - 18

TD831156-00_MINI_VRF_SYS.indb 18 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit
2-3. Wall Mounted Type (K1 Type)
S-07MK1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
16 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
17 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0
1
21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3
18 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

21
23
SHC
SHC
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.3
1.0
1.2
1.0
1.2
0.9
1.2
3
19 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0
TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.0 4
23 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1
20 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6
29
31
SHC
SHC
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.1
1.9
2.1
1.8
2.1
1.8
2.0
5
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9
21 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 6
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

22
25
27
SHC
SHC
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.3
1.1
1.3
1.0
1.3
7
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 8
23 27 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
31 SHC 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
8 - 19

TD831156-00_MINI_VRF_SYS.indb 19 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MK1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
16 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
17 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1 29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
18 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
2 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

3 21
23
SHC
SHC
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.2
1.6
1.2
1.5
1.2
1.5
19 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5
4 TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6

23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.3
20 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0
5 29
31
SHC
SHC
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.4
2.8
2.4
2.8
2.4
2.7
2.4
2.7
2.4
2.7
2.3
2.7
2.3
2.6
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2
21 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
6 27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

7 22
25
27
SHC
SHC
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.4
1.8
1.4
1.8
1.4
1.7
1.4
1.7
1.4
1.7
1.3
1.7
1.3
1.6
29 SHC 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

8 25 SHC 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2
23 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8
31 SHC 2.4 2.4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
8 - 20

TD831156-00_MINI_VRF_SYS.indb 20 2012/01/31 14:37:23


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MK1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
17 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2
1
21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2
29 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

21
23
SHC
SHC
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
1.9
1.5
1.9
1.5
1.9
3
19 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.2
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3
TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3 4
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4
29
31
SHC
SHC
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
2.9
3.3
2.9
3.3
2.9
3.2
2.8
3.2
2.8
3.2
2.8
3.1
5
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5
21 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 6
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 3.0
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

22
25
27
SHC
SHC
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.7
2.1
1.7
2.1
1.7
2.0
1.6
2.0
7
29 SHC 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.8
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 8
23 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
29 SHC 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2
31 SHC 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6
8 - 21

TD831156-00_MINI_VRF_SYS.indb 21 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MK1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.3 kW AIR FLOW 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
15 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
TC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
TC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
1 29 SHC
TC
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
5.0
4.6
4.9
4.6
4.7

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0
18 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
2 27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6
31 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.7
TC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1 4.9 4.8

3 21
23
SHC
SHC
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.4
2.9
2.3
2.9
2.3
2.8
2.3
2.8
2.2
2.7
19 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.3
31 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8
4 TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.5 5.4 5.3 5.2 5.0 4.9

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.4
20 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.5
5 29
31
SHC
SHC
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.3
4.8
4.2
4.8
4.2
4.7
4.1
4.7
4.1
4.6
4.1
4.6
4.0
4.5
TC 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.9 5.8 5.7 5.6 5.5 5.3 5.2 5.1

23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
21 25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.7
6 27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2
TC 6.4 6.4 6.4 6.3 6.3 6.2 6.1 6.1 6.0 5.9 5.8 5.7 5.5 5.4 5.3

7 22
25
27
SHC
SHC
2.8
3.3
2.8
3.3
2.8
3.3
2.8
3.3
2.8
3.3
2.8
3.3
2.7
3.2
2.7
3.2
2.7
3.2
2.6
3.2
2.6
3.1
2.5
3.1
2.5
3.0
2.5
3.0
2.4
2.9
29 SHC 3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.5 3.4
31 SHC 4.4 4.4 4.4 4.4 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.1 4.0 4.0
TC 6.7 6.7 6.6 6.6 6.5 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7 5.5

8 25 SHC 2.6 2.6 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
23 27 SHC 3.1 3.1 3.1 3.1 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.7 2.7
29 SHC 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2
31 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7
8 - 22

TD831156-00_MINI_VRF_SYS.indb 22 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-19MS1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
15 23 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
16 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC
TC
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.0
1
21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
18 25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 2
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

21
23
SHC
SHC
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.0
2.4
3.0
2.4
2.9
2.3
2.9
3
19 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9
29 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.4
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2 4
23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.6 2.5
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.7 3.7 3.6
29
31
SHC
SHC
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.5
5.0
4.4
5.0
4.4
4.9
4.3
4.9
4.3
4.9
4.2
4.8
4.2
4.7
4.1
4.7
5
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.3 6
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9
31 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.6 4.5 4.5 4.4
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

22
25
27
SHC
SHC
3.0
3.5
3.0
3.5
3.0
3.5
3.0
3.5
2.9
3.4
2.9
3.4
2.9
3.4
2.8
3.4
2.8
3.3
2.8
3.3
2.7
3.2
2.7
3.2
2.6
3.2
2.6
3.1
2.5
3.1
7
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.6
31 SHC 4.6 4.6 4.6 4.5 4.5 4.5 4.5 4.4 4.4 4.4 4.3 4.3 4.2 4.2 4.1
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

25 SHC 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 8
23 27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8
29 SHC 3.8 3.8 3.8 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.3
31 SHC 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.9
8 - 23

TD831156-00_MINI_VRF_SYS.indb 23 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MK1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.3 kW AIR FLOW 16.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
15 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
27 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
16 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
17 23 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
1 29 SHC
TC
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.8
5.4
6.7
5.4
6.5

21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8
18 25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.2
2 27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.7
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2
31 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 7.0 6.8 6.6

3 21
23
SHC
SHC
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.2
3.7
3.1
3.6
3.1
3.5
3.0
3.4
19 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 3.9
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.4
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0 5.0 4.9
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.5 5.4 5.3
4 TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8

23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.2 3.2
20 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 3.9 3.8 3.7 3.6
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.3 4.3 4.2 4.1
5 29
31
SHC
SHC
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.5
5.0
5.4
4.9
5.4
4.8
5.3
4.8
5.2
4.7
5.1
4.6
5.0
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.1 7.9 7.8 7.7 7.5 7.3 7.2 7.0

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 2.9
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.7 3.7 3.6 3.5 3.4 3.4
6 27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9
29 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.3
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8
TC 8.8 8.8 8.8 8.7 8.7 8.6 8.5 8.4 8.2 8.1 8.0 7.8 7.6 7.5 7.3

7 22
25
27
SHC
SHC
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.7
4.2
3.7
4.1
3.6
4.1
3.6
4.1
3.5
4.0
3.5
4.0
3.4
3.9
3.3
3.8
3.3
3.8
3.2
3.7
3.1
3.6
29 SHC 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.4 4.3 4.2 4.2 4.1
31 SHC 5.2 5.2 5.2 5.2 5.1 5.1 5.1 5.0 5.0 4.9 4.9 4.8 4.7 4.6 4.6
TC 9.3 9.2 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.0 7.8 7.6

8 25 SHC 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 2.9
23 27 SHC 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4
29 SHC 4.6 4.5 4.5 4.5 4.4 4.4 4.4 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9
31 SHC 5.0 5.0 5.0 5.0 4.9 4.9 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.3
8 - 24

TD831156-00_MINI_VRF_SYS.indb 24 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit
2-4. Ceiling Type (T1 Type)
S-12MT1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
15 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
16 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
29 SHC
TC
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.3
2.9
3.2
1
21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

21
23
SHC
SHC
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.5
1.8
1.5
1.8
1.5
1.7
3
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8
TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3 4
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6 1.6
20 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1
29
31
SHC
SHC
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.9
2.6
2.8
2.5
2.8
2.5
2.8
2.5
2.7
2.4
2.7
2.4
2.7
5
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 2.0 6
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

22
25
27
SHC
SHC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.0
1.8
2.0
1.7
2.0
1.7
2.0
1.7
1.9
1.6
1.9
1.6
1.9
1.6
1.8
7
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1
31 SHC 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

25 SHC 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4 8
23 27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7
29 SHC 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 2.0
31 SHC 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.2
8 - 25

TD831156-00_MINI_VRF_SYS.indb 25 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MT1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 13.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
15 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
16 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
17 23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
1 29 SHC
TC
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.2
4.1
5.0

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8
18 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
2 27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6
29 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

3 21
23
SHC
SHC
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.8
2.4
2.7
2.4
2.7
2.3
2.6
19 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.0 3.0
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.7 3.7
31 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0
4 TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.5 2.5 2.4
20 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.8 2.8
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1
5 29
31
SHC
SHC
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.7
4.1
3.7
4.0
3.6
4.0
3.6
3.9
3.5
3.9
3.4
3.8
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.2
21 25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8 2.8 2.7 2.7 2.6 2.6
6 27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.0 3.0 2.9
29 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.4 3.4 3.3 3.3
31 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

7 22
25
27
SHC
SHC
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.9
3.2
2.8
3.2
2.8
3.1
2.8
3.1
2.7
3.1
2.7
3.0
2.6
3.0
2.6
2.9
2.5
2.9
2.5
2.8
2.4
2.7
29 SHC 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.4
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

8 25 SHC 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.2
23 27 SHC 3.1 3.1 3.1 3.1 3.0 3.0 3.0 3.0 2.9 2.8 2.8 2.8 2.7 2.6 2.6
29 SHC 3.5 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9
31 SHC 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.4 3.4 3.3 3.3
8 - 26

TD831156-00_MINI_VRF_SYS.indb 26 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MT1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.3 kW AIR FLOW 18.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

21 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
15 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
25 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
16 23 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
25 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
27 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
17 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
29 SHC
TC
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.8
5.7
6.7
5.7
6.5
1
21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8
18 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 2
29 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4
31 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 5.9
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 7.0 6.8 6.6

21
23
SHC
SHC
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.2
3.7
3.1
3.6
3.0
3.6
3.0
3.5
3
19 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.0
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8 4.7 4.6 4.5
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.2 5.2 5.1
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.7 5.6
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8 4
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.3 3.2
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.5 4.4 4.3 4.2
29
31
SHC
SHC
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.2
5.7
5.1
5.7
5.1
5.6
5.0
5.5
4.9
5.5
4.8
5.4
4.8
5.3
5
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.1 7.9 7.8 7.7 7.5 7.3 7.2 7.0

23 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.0 3.0 2.9
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.6 3.6 3.5 3.4
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 6
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.6 4.5
31 SHC 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.4 5.3 5.2 5.2 5.1 5.0
TC 8.8 8.8 8.8 8.7 8.7 8.6 8.5 8.4 8.2 8.1 8.0 7.8 7.6 7.5 7.3

22
25
27
SHC
SHC
3.8
4.3
3.8
4.3
3.8
4.3
3.8
4.3
3.7
4.2
3.7
4.2
3.6
4.2
3.6
4.1
3.5
4.1
3.5
4.0
3.4
4.0
3.4
3.9
3.3
3.8
3.2
3.8
3.2
3.7
7
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.6 4.5 4.5 4.4 4.3 4.3 4.2
31 SHC 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.8
TC 9.3 9.2 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.0 7.8 7.6

25 SHC 3.6 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.0 3.0 2.9 8
23 27 SHC 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.6 3.6 3.5 3.5
29 SHC 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1 4.0
31 SHC 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.6 4.5
8 - 27

TD831156-00_MINI_VRF_SYS.indb 27 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit
2-5. Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type)
S-07MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
15 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
16 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
17 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
1 29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2
18 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
2 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

3 21
23
SHC
SHC
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
0.9
1.2
0.9
1.1
0.9
1.1
19 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9
4 TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.0

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4
5 29
31
SHC
SHC
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.6
1.8
1.6
1.8
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
21 25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
6 27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
29 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
31 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

7 22
25
27
SHC
SHC
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.4
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.0
1.3
1.0
1.2
1.0
1.2
1.0
1.2
29 SHC 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

8 25 SHC 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
23 27 SHC 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
29 SHC 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
31 SHC 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5
8 - 28

TD831156-00_MINI_VRF_SYS.indb 28 2012/01/31 14:37:24


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
15 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5
1
21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
18 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

21
23
SHC
SHC
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.2
1.5
1.2
1.5
1.2
1.4
1.1
1.4
3
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6 4
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8
29
31
SHC
SHC
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.1
2.4
2.1
2.4
2.1
2.4
2.1
2.3
2.0
2.3
2.0
2.3
5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1 1.1
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.6 6
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

22
25
27
SHC
SHC
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.6
1.4
1.6
1.3
1.6
1.3
1.6
1.3
1.5
1.3
1.5
1.2
1.5
7
29 SHC 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

25 SHC 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.1 8
23 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
29 SHC 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.6
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9
8 - 29

TD831156-00_MINI_VRF_SYS.indb 29 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 10.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
15 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
16 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
17 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
1 29 SHC
TC
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.4
2.8
3.3
2.8
3.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
18 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
2 27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.9
1.6
1.8
1.5
1.8
1.5
1.8
1.5
1.7
19 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5
31 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6 1.6 1.6
20 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1
5 29
31
SHC
SHC
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.6
2.8
2.5
2.8
2.5
2.8
2.5
2.7
2.4
2.7
2.4
2.7
2.4
2.6
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4
21 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7
6 27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 1.9
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.1
1.8
2.0
1.7
2.0
1.7
2.0
1.7
1.9
1.7
1.9
1.6
1.9
1.6
1.9
1.6
1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.1
31 SHC 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.4
23 27 SHC 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7 1.7
29 SHC 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0
31 SHC 2.6 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2
8 - 30

TD831156-00_MINI_VRF_SYS.indb 30 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-15MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 4.5 kW AIR FLOW 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

21 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
15 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
16 23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
17 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
29 SHC
TC
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.2
3.7
4.1
3.7
4.0
1
21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0
23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4
18 25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 2
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

21
23
SHC
SHC
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.4
2.0
2.3
1.9
2.3
1.9
2.2
1.8
2.2
3
19 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.9
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3
31 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6
TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2 4
23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0
20 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7
29
31
SHC
SHC
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.7
3.3
3.6
3.3
3.6
3.2
3.6
3.2
3.5
3.1
3.5
3.1
3.4
3.0
3.4
5
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.6 4.5 4.4 4.3

23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8 1.8
21 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.5 2.5 6
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.8
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.3 3.2
TC 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.8 4.7 4.6 4.5

22
25
27
SHC
SHC
2.3
2.7
2.3
2.7
2.3
2.7
2.3
2.7
2.3
2.7
2.3
2.6
2.2
2.6
2.2
2.6
2.2
2.6
2.2
2.5
2.1
2.5
2.1
2.4
2.0
2.4
2.0
2.4
2.0
2.3
7
29 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0
TC 5.7 5.7 5.6 5.6 5.6 5.5 5.4 5.4 5.3 5.2 5.1 5.0 4.9 4.8 4.7

25 SHC 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8 1.8 8
23 27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.1
29 SHC 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5
31 SHC 3.3 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.0 3.0 2.9 2.9 2.9
8 - 31

TD831156-00_MINI_VRF_SYS.indb 31 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
15 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
16 23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
17 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
27 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
1 29 SHC
TC
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.2
4.3
5.0

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
23 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9

2 18 25
27
SHC
SHC
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.4
3.8
3.3
3.7
29 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

3 21
23
SHC
SHC
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.9
2.5
2.8
2.4
2.8
2.3
2.7
2.3
2.7
19 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.1 3.0
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.5 3.4
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.8
31 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.3 4.2
4 TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2

23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.5 2.4
20 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2
5 29
31
SHC
SHC
4.0
4.3
4.0
4.3
4.0
4.3
4.0
4.3
4.0
4.3
4.0
4.3
4.0
4.3
4.0
4.3
3.9
4.3
3.9
4.3
3.8
4.2
3.8
4.2
3.7
4.1
3.7
4.1
3.6
4.0
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.3 2.2

6 21 25
27
SHC
SHC
3.0
3.4
3.0
3.4
3.0
3.4
3.0
3.4
3.0
3.4
3.0
3.4
3.0
3.4
3.0
3.4
2.9
3.3
2.9
3.3
2.8
3.2
2.8
3.2
2.7
3.1
2.7
3.1
2.6
3.0
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.4 3.4
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1 4.0 4.0 3.9 3.8 3.8
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

7 22
25
27
SHC
SHC
2.9
3.3
2.9
3.3
2.9
3.3
2.9
3.3
2.8
3.3
2.8
3.2
2.8
3.2
2.7
3.1
2.7
3.1
2.7
3.1
2.6
3.0
2.6
3.0
2.5
2.9
2.5
2.9
2.4
2.8
29 SHC 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2
31 SHC 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

8 25 SHC 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.3 2.2
23 27 SHC 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.7 2.7 2.6
29 SHC 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0
31 SHC 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.5 3.5 3.4
8 - 32

TD831156-00_MINI_VRF_SYS.indb 32 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.3 kW AIR FLOW 19.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
15 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
25 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
TC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

21 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
16 23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
27 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
29 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
TC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

21 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
17 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
25 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8
29 SHC
TC
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.8
5.3
6.7
5.3
6.5
1
21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3
23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.7
18 25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2
27 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 2
29 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1
31 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.6 5.5
TC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.1 7.0 6.8 6.6

21
23
SHC
SHC
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.8
3.3
3.7
3.2
3.7
3.1
3.6
3.0
3.5
3.0
3.4
3
19 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 3.9 3.9
27 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6 4.6 4.5 4.4 4.3
29 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.8 4.8
31 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.5 5.4 5.3 5.2
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8 4
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.3 3.2 3.1
20 25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.2 4.1 4.1
29
31
SHC
SHC
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
5.0
5.4
4.9
5.4
4.8
5.3
4.7
5.2
4.7
5.1
4.6
5.0
4.5
5.0
5
TC 8.3 8.3 8.3 8.3 8.3 8.3 8.2 8.1 7.9 7.8 7.7 7.5 7.3 7.2 7.0

23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.0 3.0 2.9
21 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.4
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1 3.9 3.9 3.8 6
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.3 4.3
31 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.8 4.8 4.7
TC 8.8 8.8 8.8 8.7 8.7 8.6 8.5 8.4 8.2 8.1 8.0 7.8 7.6 7.5 7.3

22
25
27
SHC
SHC
3.8
4.2
3.8
4.2
3.8
4.2
3.8
4.2
3.7
4.2
3.7
4.2
3.7
4.1
3.6
4.1
3.5
4.0
3.5
3.9
3.4
3.9
3.4
3.8
3.3
3.7
3.2
3.7
3.1
3.6
7
29 SHC 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.1 4.0
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5
TC 9.3 9.2 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5 8.3 8.2 8.0 7.8 7.6

25 SHC 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0 2.9 8
23 27 SHC 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.4
29 SHC 4.5 4.5 4.5 4.4 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8
31 SHC 5.0 5.0 4.9 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.6 4.5 4.4 4.3 4.3
8 - 33

TD831156-00_MINI_VRF_SYS.indb 33 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-36MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 10.6 kW AIR FLOW 30.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

21 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
15 23 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4
25 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

21 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
16 23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
25 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
17 23 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
25 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8
27 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7
1 29 SHC
TC
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.9
8.4
9.8
8.4
9.5

21 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8
23 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.6
18 25 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4
2 27 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.2
29 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.0
31 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 8.8
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 10.1 9.9 9.6

3 21
23
SHC
SHC
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.8
5.5
4.6
5.4
4.5
5.3
4.4
5.2
4.3
5.1
19 25 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.1 6.0 5.9
27 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.1 7.1 6.9 6.8 6.7
29 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.8 7.7 7.7 7.5
31 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.6 8.6 8.4 8.3
4 TC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.2 11.0 10.8 10.6 10.4 10.1 9.8

23 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 4.9 4.9 4.8 4.6
20 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.0 6.0 5.8 5.8 5.7 5.5 5.4
27 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.8 6.6 6.6 6.4 6.3 6.2
5 29
31
SHC
SHC
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.5
7.7
8.4
7.5
8.4
7.5
8.3
7.4
8.2
7.2
8.1
7.2
8.0
7.1
7.8
TC 12.0 12.0 12.0 12.0 12.0 12.0 11.9 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1

23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2
21 25 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.7 5.6 5.5 5.4 5.3 5.2 5.1 5.0
6 27 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8
29 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.2 7.2 7.1 7.0 6.9 6.8 6.7 6.6
31 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.1 8.0 7.9 7.8 7.7 7.7 7.5 7.4
TC 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6

7 22
25
27
SHC
SHC
5.5
6.3
5.5
6.3
5.5
6.3
5.4
6.3
5.4
6.2
5.4
6.1
5.3
6.1
5.2
6.0
5.2
6.0
5.1
5.9
5.0
5.8
4.9
5.7
4.8
5.6
4.7
5.5
4.6
5.4
29 SHC 7.1 7.1 7.1 7.1 7.0 6.9 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.2
31 SHC 7.9 7.9 7.9 7.8 7.8 7.8 7.7 7.7 7.6 7.5 7.4 7.3 7.2 7.1 7.0
TC 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1

8 25 SHC 5.1 5.1 5.1 5.1 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.5 4.5 4.3 4.2
23 27 SHC 6.0 5.9 5.9 5.8 5.8 5.8 5.7 5.7 5.5 5.5 5.4 5.3 5.2 5.1 5.1
29 SHC 6.8 6.8 6.7 6.7 6.6 6.6 6.5 6.4 6.4 6.3 6.2 6.1 6.0 6.0 5.8
31 SHC 7.5 7.5 7.5 7.5 7.4 7.4 7.3 7.2 7.2 7.1 7.1 6.9 6.9 6.8 6.6
8 - 34

TD831156-00_MINI_VRF_SYS.indb 34 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-48MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 14.0 kW AIR FLOW 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3

21 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2
15 23 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2
25 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2
27 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

21 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
16 23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
25 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9
29 SHC 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

21 SHC 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8
17 23 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
25 SHC 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8 8.8
27 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7
29 SHC
TC
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
13.1
10.7
12.9
10.7
12.5
1
21 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.3
23 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.4 7.3
18 25 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2
27 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.2 2
29 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.3 10.2
31 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.3 11.1
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.7 13.4 13.1 12.7

21
23
SHC
SHC
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.3
7.2
6.2
7.2
6.1
7.1
6.0
7.0
5.8
6.8
5.6
6.6
3
19 25 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.0 7.8 7.6
27 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.0 8.9 8.8 8.6
29 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.0 9.9 9.7 9.5
31 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.0 10.9 10.7 10.5
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.8 14.6 14.3 14.0 13.7 13.3 13.0 4
23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9 6.8 6.6 6.5 6.4 6.2 6.0
20 25 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.8 7.8 7.6 7.5 7.4 7.2 7.0
27 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.8 8.7 8.6 8.4 8.3 8.2 8.0
29
31
SHC
SHC
9.9
10.8
9.9
10.8
9.9
10.8
9.9
10.8
9.9
10.8
9.9
10.8
9.9
10.8
9.9
10.8
9.8
10.7
9.7
10.7
9.5
10.5
9.4
10.4
9.3
10.3
9.2
10.1
9.0
9.9
5
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.7 15.5 15.2 15.0 14.7 14.4 14.1 13.7 13.4

23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.8 5.7 5.6
21 25 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.4 7.3 7.2 7.1 7.0 6.8 6.6 6.5
27 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.5 8.4 8.3 8.2 8.0 7.9 7.8 7.6 7.5 6
29 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.3 9.2 9.2 9.0 8.9 8.8 8.6 8.5
31 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.4 10.3 10.2 10.1 10.0 9.9 9.7 9.5 9.4
TC 16.8 16.8 16.8 16.7 16.6 16.4 16.2 16.0 15.8 15.5 15.3 15.0 14.6 14.3 13.9

22
25
27
SHC
SHC
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.1
7.0
8.0
7.0
8.0
6.9
7.9
6.8
7.8
6.7
7.6
6.6
7.6
6.4
7.4
6.3
7.3
6.2
7.2
6.0
7.0
7
29 SHC 9.2 9.2 9.2 9.2 9.1 9.0 9.0 8.8 8.8 8.6 8.5 8.4 8.3 8.1 8.0
31 SHC 10.1 10.1 10.1 10.1 10.1 9.9 9.9 9.8 9.7 9.6 9.5 9.3 9.2 9.1 9.0
TC 17.7 17.7 17.6 17.4 17.3 17.1 16.9 16.7 16.5 16.2 15.9 15.6 15.3 15.0 14.6

25 SHC 6.8 6.8 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.8 5.7 5.6 8
23 27 SHC 7.8 7.8 7.8 7.7 7.6 7.6 7.5 7.4 7.3 7.2 7.1 7.0 6.8 6.7 6.6
29 SHC 8.8 8.8 8.7 8.7 8.6 8.6 8.4 8.4 8.3 8.2 8.0 8.0 7.8 7.7 7.6
31 SHC 9.7 9.7 9.7 9.6 9.5 9.5 9.4 9.3 9.2 9.2 9.0 8.9 8.8 8.6 8.5
8 - 35

TD831156-00_MINI_VRF_SYS.indb 35 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-54MF1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 16.0 kW AIR FLOW 33.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7

21 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
15 23 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0
25 SHC 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
27 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
TC 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8 12.8

21 SHC 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9
16 23 SHC 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9
25 SHC 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8
27 SHC 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
29 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8
TC 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

21 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7
17 23 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7
25 SHC 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7
27 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6
1 29 SHC
TC
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.9
11.6
14.7
11.6
14.3

21 SHC 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.4 7.2
23 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.2
18 25 SHC 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.2
2 27 SHC 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.3 10.1
29 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.3 11.1
31 SHC 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.3 12.1
TC 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0 15.7 15.3 14.9 14.5

3 21
23
SHC
SHC
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.2
8.2
7.0
8.0
6.9
7.9
6.7
7.7
6.5
7.5
19 25 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.0 8.8 8.7 8.5
27 SHC 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.1 10.0 9.8 9.7 9.5
29 SHC 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.1 11.0 10.8 10.6 10.5
31 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.0 11.8 11.6 11.4
4 TC 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 16.9 16.6 16.3 16.0 15.6 15.2 14.8

23 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.8 7.6 7.4 7.2 7.1 6.9
20 25 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 8.7 8.6 8.4 8.2 8.1 7.9
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.8 9.7 9.5 9.4 9.2 9.0 8.9
5 29
31
SHC
SHC
10.9
11.9
10.9
11.9
10.9
11.9
10.9
11.9
10.9
11.9
10.9
11.9
10.9
11.9
10.9
11.9
10.8
11.8
10.7
11.7
10.5
11.5
10.4
11.3
10.2
11.2
10.0
11.0
9.8
10.8
TC 18.1 18.1 18.1 18.1 18.1 18.1 17.9 17.7 17.4 17.1 16.8 16.5 16.1 15.7 15.3

23 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.3 7.2 7.0 6.8 6.7 6.5 6.4
21 25 SHC 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.4 8.3 8.2 8.0 7.8 7.7 7.5 7.4
6 27 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.5 9.4 9.3 9.2 9.0 8.8 8.7 8.5 8.3
29 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.5 10.4 10.3 10.1 10.0 9.8 9.7 9.5 9.3
31 SHC 11.6 11.6 11.6 11.6 11.6 11.6 11.5 11.4 11.3 11.1 10.9 10.8 10.7 10.5 10.3
TC 19.2 19.2 19.2 19.1 19.0 18.8 18.6 18.3 18.0 17.7 17.4 17.1 16.7 16.3 15.9

7 22
25
27
SHC
SHC
8.3
9.3
8.3
9.3
8.3
9.3
8.3
9.3
8.2
9.2
8.1
9.1
8.0
9.0
7.9
8.9
7.8
8.8
7.6
8.6
7.5
8.5
7.4
8.4
7.2
8.2
7.0
8.0
6.8
7.8
29 SHC 10.3 10.3 10.3 10.2 10.1 10.1 9.9 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.8
31 SHC 11.3 11.3 11.3 11.2 11.1 11.1 10.9 10.9 10.7 10.6 10.5 10.3 10.1 10.0 9.8
TC 20.3 20.2 20.1 19.9 19.7 19.5 19.3 19.1 18.8 18.5 18.2 17.9 17.5 17.1 16.7

8 25 SHC 8.0 7.9 7.8 7.8 7.7 7.6 7.5 7.4 7.3 7.2 7.0 6.9 6.8 6.6 6.4
23 27 SHC 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.3 8.2 8.0 7.9 7.8 7.6 7.4
29 SHC 9.9 9.9 9.8 9.7 9.7 9.6 9.5 9.4 9.3 9.2 9.0 8.9 8.7 8.6 8.4
31 SHC 10.9 10.9 10.8 10.7 10.7 10.6 10.5 10.4 10.3 10.1 10.0 9.9 9.7 9.5 9.3
8 - 36

TD831156-00_MINI_VRF_SYS.indb 36 2012/01/31 14:37:25


Capacity Table
2. Cooling Capacity of Indoor Unit

S-07MM1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 8.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
15 23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0
1
21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
18 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

21
23
SHC
SHC
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.1
1.4
1.0
1.4
1.0
1.4
1.0
1.3
1.0
1.3
3
19 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0
TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.0 4
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.1
20 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8
29
31
SHC
SHC
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.3
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.1
2.0
2.0
5
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0
21 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 6
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9
31 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

22
25
27
SHC
SHC
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.2
1.6
1.2
1.6
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.2
1.5
1.1
1.5
7
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8
31 SHC 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

25 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 8
23 27 SHC 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 2.0
8 - 37

TD831156-00_MINI_VRF_SYS.indb 37 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MM1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 8.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
15 23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
16 23 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
17 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
1 29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7
18 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0
2 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

3 21
23
SHC
SHC
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.3
1.6
1.2
1.6
1.2
1.6
1.2
1.5
19 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2
29 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5
31 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5
4 TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6

23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.3
20 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0
5 29
31
SHC
SHC
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.5
2.8
2.4
2.8
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.3
2.6
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2
21 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5
6 27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

7 22
25
27
SHC
SHC
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.9
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.5
1.8
1.4
1.8
1.4
1.7
1.4
1.7
1.4
1.7
1.3
1.7
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.3 2.3
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

8 25 SHC 1.4 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2
23 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8
31 SHC 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2
8 - 38

TD831156-00_MINI_VRF_SYS.indb 38 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MM1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
15 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
16 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
17 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2
1
21 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

21
23
SHC
SHC
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
1.9
1.5
1.9
1.5
1.9
3
19 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2
27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0
31 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.3
TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3 4
23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4
29
31
SHC
SHC
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
3.0
3.3
2.9
3.3
2.9
3.3
2.9
3.3
2.9
3.2
2.8
3.2
2.8
3.2
2.8
3.1
5
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5
21 25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 6
29 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

22
25
27
SHC
SHC
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.3
1.9
2.2
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.7
2.1
1.7
2.1
1.7
2.0
1.6
2.0
7
29 SHC 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

25 SHC 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 8
23 27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8
29 SHC 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2
31 SHC 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6
8 - 39

TD831156-00_MINI_VRF_SYS.indb 39 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit

S-15MM1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 4.5 kW AIR FLOW 10.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
15 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
25 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
16 23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
29 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
17 23 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
25 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
27 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
1 29 SHC
TC
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.2
3.4
4.1
3.4
4.0

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0
23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
18 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6
2 27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3
31 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

3 21
23
SHC
SHC
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
1.9
2.2
1.9
2.2
1.8
2.1
19 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.4
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.8 2.8 2.7
29 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1
31 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4
4 TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2

23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0 2.0 1.9
20 25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6
5 29
31
SHC
SHC
3.2
3.5
3.2
3.5
3.2
3.5
3.2
3.5
3.2
3.5
3.2
3.5
3.2
3.5
3.2
3.5
3.1
3.5
3.1
3.4
3.1
3.4
3.0
3.3
3.0
3.3
2.9
3.2
2.9
3.2
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.6 4.5 4.4 4.3

23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.8 1.8

6 21 25
27
SHC
SHC
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.4
2.7
2.3
2.7
2.3
2.6
2.3
2.6
2.2
2.5
2.2
2.5
2.1
2.4
2.1
2.4
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.8 2.7
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0
TC 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.8 4.7 4.6 4.5

7 22
25
27
SHC
SHC
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.3
2.6
2.2
2.6
2.2
2.5
2.2
2.5
2.2
2.4
2.1
2.4
2.1
2.4
2.0
2.3
2.0
2.3
1.9
2.3
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6
31 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9
TC 5.7 5.7 5.6 5.6 5.6 5.5 5.4 5.4 5.3 5.2 5.1 5.0 4.9 4.8 4.7

8 25 SHC 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 1.9 1.9 1.8 1.8
23 27 SHC 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.2 2.2 2.2 2.1
29 SHC 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4
31 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.8 2.7
8 - 40

TD831156-00_MINI_VRF_SYS.indb 40 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MM1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 12.5 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
15 23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
16 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
27 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
17 23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
25 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8
27 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
29 SHC
TC
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.2
4.8
5.0
1
21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6
23 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1
18 25 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 2
29 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5
31 SHC 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

21
23
SHC
SHC
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
3.0
2.5
2.9
2.4
2.9
2.4
2.8
2.3
2.8
3
19 25 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.8 3.8 3.7
29 SHC 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.3 4.2
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8 4.7
TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2 4
23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.5
20 25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0
27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5
29
31
SHC
SHC
4.3
4.7
4.3
4.7
4.3
4.7
4.3
4.7
4.3
4.7
4.3
4.7
4.3
4.7
4.3
4.7
4.2
4.7
4.2
4.7
4.1
4.6
4.1
4.6
4.0
4.5
4.0
4.5
3.9
4.4
5
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.3 2.2
21 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.7
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 6
29 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7
31 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.3 4.2 4.2
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

22
25
27
SHC
SHC
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.4
2.9
3.3
2.8
3.3
2.8
3.3
2.8
3.2
2.7
3.2
2.7
3.2
2.6
3.1
2.6
3.1
2.5
3.0
2.5
3.0
7
29 SHC 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4
31 SHC 4.4 4.4 4.4 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0 3.9
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

25 SHC 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 8
23 27 SHC 3.2 3.2 3.2 3.1 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9 2.8 2.8 2.7
29 SHC 3.7 3.7 3.6 3.6 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2
31 SHC 4.2 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7
8 - 41

TD831156-00_MINI_VRF_SYS.indb 41 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit
2-6. High Static Pressure Ducted Type (E1 Type)
S-36ME1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 10.6 kW AIR FLOW 30.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

21 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3
15 23 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4
25 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
27 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
TC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

21 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0
16 23 SHC 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
25 SHC 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1
27 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
29 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
TC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

21 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
17 23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
25 SHC 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7
27 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7
1 29 SHC
TC
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.9
9.2
9.8
9.2
9.5

21 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1
23 SHC 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.2 6.1
18 25 SHC 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.3 7.2
2 27 SHC 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.3 8.2
29 SHC 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.3
31 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.8 9.5
TC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 10.1 9.9 9.6

3 21
23
SHC
SHC
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.8
5.8
4.7
5.8
4.6
5.7
4.5
5.5
4.4
5.5
19 25 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.8 6.6 6.5
27 SHC 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.8 7.7 7.6
29 SHC 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.9 8.7 8.6
31 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.0 9.9 9.8 9.6
4 TC 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.2 11.0 10.8 10.6 10.4 10.1 9.8

23 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9
20 25 SHC 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.4 6.3 6.2 6.1 6.0 5.9
27 SHC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.5 7.4 7.3 7.2 7.1 7.0
5 29
31
SHC
SHC
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.7
8.6
9.6
8.5
9.6
8.4
9.5
8.4
9.4
8.3
9.3
8.1
9.2
8.1
9.1
TC 12.0 12.0 12.0 12.0 12.0 12.0 11.9 11.7 11.5 11.3 11.1 10.9 10.7 10.4 10.1

23 SHC 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.5 4.4 4.3
21 25 SHC 6.1 6.1 6.1 6.1 6.1 6.1 6.0 6.0 5.9 5.8 5.7 5.7 5.5 5.5 5.4
6 27 SHC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.9 6.9 6.8 6.7 6.6 6.5 6.4
29 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.1 8.1 8.0 8.0 7.8 7.8 7.7 7.6 7.5
31 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.2 9.2 9.1 9.0 8.9 8.9 8.7 8.7 8.6
TC 12.7 12.7 12.7 12.7 12.6 12.4 12.3 12.1 12.0 11.8 11.5 11.3 11.1 10.8 10.6

7 22
25
27
SHC
SHC
5.6
6.7
5.6
6.7
5.6
6.7
5.6
6.7
5.5
6.6
5.5
6.6
5.5
6.5
5.4
6.4
5.4
6.4
5.3
6.3
5.2
6.3
5.1
6.2
5.0
6.1
4.9
6.0
4.8
5.9
29 SHC 7.8 7.8 7.8 7.7 7.7 7.7 7.6 7.5 7.5 7.4 7.3 7.2 7.2 7.1 7.0
31 SHC 8.8 8.8 8.8 8.8 8.7 8.7 8.7 8.6 8.5 8.4 8.4 8.3 8.2 8.1 8.0
TC 13.4 13.4 13.3 13.2 13.1 13.0 12.8 12.6 12.5 12.3 12.1 11.8 11.6 11.3 11.1

8 25 SHC 5.2 5.1 5.1 5.1 5.1 5.0 4.9 4.9 4.8 4.8 4.7 4.6 4.5 4.5 4.3
23 27 SHC 6.2 6.2 6.1 6.1 6.1 6.0 6.0 6.0 5.9 5.8 5.7 5.7 5.6 5.5 5.4
29 SHC 7.3 7.3 7.2 7.2 7.2 7.1 7.1 7.0 6.9 6.9 6.8 6.8 6.6 6.6 6.4
31 SHC 8.4 8.3 8.3 8.3 8.2 8.2 8.1 8.1 8.0 8.0 7.8 7.8 7.7 7.6 7.5
8 - 42

TD831156-00_MINI_VRF_SYS.indb 42 2012/01/31 14:37:26


Capacity Table
2. Cooling Capacity of Indoor Unit

S-48ME1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 14.0 kW AIR FLOW 36.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3

21 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2
15 23 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6
25 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
27 SHC 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
TC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

21 SHC 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8
16 23 SHC 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2
25 SHC 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6
27 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
29 SHC 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
TC 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

21 SHC 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3
17 23 SHC 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7
25 SHC 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1 10.1
27 SHC 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4
29 SHC
TC
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
13.1
12.1
12.9
12.1
12.5
1
21 SHC 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.7
23 SHC 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.0
18 25 SHC 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.5 9.4
27 SHC 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 10.9 10.7 2
29 SHC 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.4 12.3 12.1
31 SHC 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.9 12.5
TC 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.7 13.4 13.1 12.7

21
23
SHC
SHC
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.4
7.7
6.2
7.6
6.1
7.5
5.9
7.3
5.8
7.2
3
19 25 SHC 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.0 9.0 8.8 8.7 8.5
27 SHC 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.4 10.3 10.2 10.1 9.9
29 SHC 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.7 11.6 11.4 11.3
31 SHC 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.1 12.9 12.8 12.7
TC 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.8 14.6 14.3 14.0 13.7 13.3 13.0 4
23 SHC 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.0 6.9 6.8 6.7 6.5 6.4
20 25 SHC 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.3 8.2 8.0 7.9 7.8
27 SHC 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.8 9.8 9.7 9.5 9.4 9.3 9.1
29
31
SHC
SHC
11.3
12.7
11.3
12.7
11.3
12.7
11.3
12.7
11.3
12.7
11.3
12.7
11.3
12.7
11.3
12.7
11.2
12.6
11.1
12.5
11.1
12.4
10.9
12.3
10.8
12.2
10.6
12.0
10.5
11.9
5
TC 15.9 15.9 15.9 15.9 15.9 15.9 15.7 15.5 15.2 15.0 14.7 14.4 14.1 13.7 13.4

23 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4 6.4 6.3 6.1 6.1 5.9 5.8 5.7
21 25 SHC 8.0 8.0 8.0 8.0 8.0 8.0 7.9 7.8 7.7 7.7 7.5 7.5 7.3 7.2 7.1
27 SHC 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.2 9.1 9.0 8.9 8.8 8.7 8.5 8.4 6
29 SHC 10.7 10.7 10.7 10.7 10.7 10.7 10.6 10.6 10.5 10.4 10.3 10.2 10.1 9.9 9.8
31 SHC 12.1 12.1 12.1 12.1 12.1 12.1 12.0 11.9 11.9 11.8 11.6 11.6 11.4 11.3 11.1
TC 16.8 16.8 16.8 16.7 16.6 16.4 16.2 16.0 15.8 15.5 15.3 15.0 14.6 14.3 13.9

22
25
27
SHC
SHC
7.4
8.8
7.4
8.8
7.4
8.8
7.4
8.8
7.3
8.7
7.2
8.6
7.2
8.5
7.1
8.5
7.0
8.4
6.9
8.3
6.9
8.2
6.7
8.1
6.6
8.0
6.5
7.9
6.4
7.7
7
29 SHC 10.1 10.1 10.1 10.1 10.1 10.0 9.9 9.8 9.8 9.7 9.6 9.5 9.3 9.3 9.1
31 SHC 11.5 11.5 11.5 11.5 11.4 11.4 11.3 11.2 11.1 11.1 10.9 10.9 10.7 10.6 10.5
TC 17.7 17.7 17.6 17.4 17.3 17.1 16.9 16.7 16.5 16.2 15.9 15.6 15.3 15.0 14.6

25 SHC 6.8 6.8 6.7 6.7 6.7 6.6 6.5 6.4 6.4 6.3 6.1 6.1 5.9 5.9 5.7 8
23 27 SHC 8.2 8.2 8.1 8.1 8.0 8.0 7.9 7.8 7.7 7.7 7.5 7.5 7.3 7.2 7.1
29 SHC 9.5 9.5 9.5 9.5 9.4 9.3 9.3 9.2 9.1 9.0 8.9 8.8 8.7 8.6 8.5
31 SHC 10.9 10.9 10.9 10.9 10.8 10.7 10.6 10.6 10.5 10.4 10.3 10.2 10.1 10.0 9.8
8 - 43

TD831156-00_MINI_VRF_SYS.indb 43 2012/01/31 14:37:27


Capacity Table
2. Cooling Capacity of Indoor Unit
2-7. Floor Standing Type (P1 Type)
S-07MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
15 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
16 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
17 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
1 29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2

2 18 25
27
SHC
SHC
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.4
1.6
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

3 21
23
SHC
SHC
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
0.9
1.1
0.9
1.1
19 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7

4 31 SHC
TC
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.3
2.0
2.2
2.0
2.2
2.0
2.1
1.9
2.1
1.9
2.0

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
5 29
31
SHC
SHC
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.6
1.8
1.6
1.8
1.6
1.8
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9

6 21 25
27
SHC
SHC
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.3
1.1
1.3
1.1
1.3
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

7 22
25
27
SHC
SHC
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.4
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.0
1.3
1.0
1.2
1.0
1.2
1.0
1.2
29 SHC 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4
31 SHC 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

8 25 SHC 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
23 27 SHC 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
29 SHC 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
31 SHC 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
8 - 44

TD831156-00_MINI_VRF_SYS.indb 44 2012/01/31 14:37:27


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
15 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

21
23
SHC
SHC
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.2
1.5
1.2
1.5
1.2
1.4
1.2
1.4
3
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6 4
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8
29
31
SHC
SHC
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.1
2.4
2.1
2.4
2.1
2.3
2.1
2.3
2.0
2.3
5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 6
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

22
25
27
SHC
SHC
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.6
1.4
1.6
1.4
1.6
1.3
1.6
1.3
1.6
1.3
1.5
1.3
1.5
7
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

25 SHC 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1 8
23 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
29 SHC 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9
8 - 45

TD831156-00_MINI_VRF_SYS.indb 45 2012/01/31 14:37:27


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
16 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
1 29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2 27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
1.9
1.6
1.9
1.5
1.8
1.5
1.8
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 2.0
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3
5 29
31
SHC
SHC
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.7
3.1
2.7
3.1
2.7
3.0
2.7
3.0
2.6
2.9
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8
6 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.8
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.8
2.1
1.7
2.1
1.7
2.0
1.7
2.0
1.6
2.0
1.6
2.0
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3
31 SHC 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
23 27 SHC 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5
8 - 46

TD831156-00_MINI_VRF_SYS.indb 46 2012/01/31 14:37:27


Capacity Table
2. Cooling Capacity of Indoor Unit

S-15MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 4.5 kW AIR FLOW 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
15 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
16 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
17 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
29 SHC
TC
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.1
3.9
4.0
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
18 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 2
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

21
23
SHC
SHC
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.4
2.0
2.4
1.9
2.3
1.9
2.3
3
19 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1
TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2 4
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.0
20 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9
29
31
SHC
SHC
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.0
3.6
4.0
3.5
4.0
3.5
3.9
3.4
3.9
3.4
3.8
3.4
3.8
5
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.6 4.5 4.4 4.3

23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8
21 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 6
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6
TC 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.8 4.7 4.6 4.5

22
25
27
SHC
SHC
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.3
2.8
2.3
2.7
2.3
2.7
2.3
2.7
2.2
2.7
2.2
2.6
2.2
2.6
2.1
2.6
2.1
2.5
2.0
2.5
7
29 SHC 3.3 3.3 3.3 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9
31 SHC 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.4
TC 5.7 5.7 5.6 5.6 5.6 5.5 5.4 5.4 5.3 5.2 5.1 5.0 4.9 4.8 4.7

25 SHC 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8 8
23 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
29 SHC 3.1 3.1 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7
31 SHC 3.5 3.5 3.5 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1
8 - 47

TD831156-00_MINI_VRF_SYS.indb 47 2012/01/31 14:37:27


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
15 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
16 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
1 29 SHC
TC
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.0

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
18 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8
2 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

3 21
23
SHC
SHC
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.0
2.4
3.0
2.4
3.0
2.3
2.9
19 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.5 3.5
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.6
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1
4 TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.1
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7
5 29
31
SHC
SHC
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.1
4.5
5.1
4.5
5.0
4.4
5.0
4.4
4.9
4.3
4.9
4.3
4.8
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.3
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 3.0 2.9 2.8
6 27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.6 4.6
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

7 22
25
27
SHC
SHC
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.5
3.0
3.5
2.9
3.5
2.9
3.5
2.9
3.4
2.8
3.4
2.8
3.3
2.7
3.3
2.7
3.3
2.7
3.2
2.6
3.2
2.6
3.1
29 SHC 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.7
31 SHC 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

8 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3
23 27 SHC 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9
29 SHC 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4
31 SHC 4.4 4.4 4.4 4.4 4.4 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0
8 - 48

TD831156-00_MINI_VRF_SYS.indb 48 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MP1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.1 kW AIR FLOW 17.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
15 23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
16 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
TC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
17 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
29 SHC
TC
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.5
6.2
6.4
1
21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0
18 25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 2
29 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.8 6.6 6.4

21
23
SHC
SHC
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.8
3.1
3.8
3.1
3.7
3.0
3.7
2.9
3.6
3
19 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.7 5.6 5.5
31 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.3 6.1
TC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.4 7.2 7.1 6.9 6.8 6.6 4
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3 3.3 3.2
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 3.9 3.9
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.7 4.7 4.6 4.6 4.5
29
31
SHC
SHC
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.1
5.4
6.0
5.4
6.0
5.3
5.9
5.2
5.9
5.2
5.8
5
TC 8.1 8.1 8.1 8.1 8.1 8.1 8.0 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8

23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.0 3.0 2.9 2.9
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.3 4.3 4.2 4.2 6
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8 5.7 5.6 5.6 5.5 5.5
TC 8.5 8.5 8.5 8.5 8.4 8.3 8.2 8.1 8.0 7.9 7.7 7.6 7.4 7.3 7.1

22
25
27
SHC
SHC
3.7
4.4
3.7
4.4
3.7
4.4
3.7
4.4
3.7
4.3
3.7
4.3
3.6
4.3
3.6
4.2
3.5
4.2
3.5
4.1
3.4
4.1
3.4
4.0
3.3
4.0
3.2
3.9
3.2
3.8
7
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.5 4.5
31 SHC 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.5 5.5 5.4 5.4 5.3 5.3 5.2 5.1
TC 9.0 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.2 8.1 7.9 7.8 7.6 7.4

25 SHC 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.0 3.0 2.9 2.9 8
23 27 SHC 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5
29 SHC 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.2 4.2
31 SHC 5.4 5.4 5.4 5.3 5.3 5.3 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8
8 - 49

TD831156-00_MINI_VRF_SYS.indb 49 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit
2-8. Concealed Floor Standing Type (R1 Type)
S-07MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.2 kW AIR FLOW 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

21 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
15 23 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

21 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
16 23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
TC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
17 23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
1 29 SHC
TC
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.1
1.9
2.0
1.9
2.0

21 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0
23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2
18 25 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4
2 27 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6
29 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.0

3 21
23
SHC
SHC
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
1.0
1.2
0.9
1.1
0.9
1.1
19 25 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5
29 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7
31 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9
4 TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.1 2.1 2.0

23 SHC 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0
20 25 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2
27 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
5 29
31
SHC
SHC
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.7
1.9
1.6
1.8
1.6
1.8
1.6
1.8
TC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.1

23 SHC 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
21 25 SHC 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
6 27 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
29 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5
31 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.2 2.2

7 22
25
27
SHC
SHC
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
1.1
1.4
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.1
1.3
1.0
1.3
1.0
1.2
1.0
1.2
1.0
1.2
29 SHC 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4
31 SHC 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6
TC 2.8 2.8 2.8 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

8 25 SHC 1.1 1.1 1.1 1.1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.9 0.9
23 27 SHC 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1
29 SHC 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
31 SHC 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
8 - 50

TD831156-00_MINI_VRF_SYS.indb 50 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-09MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 2.8 kW AIR FLOW 7.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

21 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
15 23 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
25 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
TC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

21 SHC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
16 23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
TC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
17 23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
27 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
29 SHC
TC
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.6
2.4
2.5
1
21 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3
23 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
18 25 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8
27 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3
31 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
TC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.5

21
23
SHC
SHC
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.3
1.5
1.2
1.5
1.2
1.5
1.2
1.4
1.2
1.4
3
19 25 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7
27 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9
29 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2
31 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4
TC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.7 2.6 4
23 SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.3 1.3
20 25 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5
27 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8
29
31
SHC
SHC
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.2
2.4
2.1
2.4
2.1
2.4
2.1
2.3
2.1
2.3
2.0
2.3
5
TC 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 2.7 2.7

23 SHC 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1
21 25 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
27 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6 6
29 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9
31 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2
TC 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.0 2.9 2.9 2.8

22
25
27
SHC
SHC
1.5
1.7
1.5
1.7
1.5
1.7
1.5
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.7
1.4
1.6
1.4
1.6
1.4
1.6
1.3
1.6
1.3
1.6
1.3
1.5
1.3
1.5
7
29 SHC 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8
31 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0
TC 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 2.9

25 SHC 1.4 1.4 1.4 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.1 8
23 27 SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4
29 SHC 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.6
31 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 1.9 1.9
8 - 51

TD831156-00_MINI_VRF_SYS.indb 51 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-12MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 3.6 kW AIR FLOW 9.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

21 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
15 23 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
TC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

21 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
16 23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
27 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
TC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

21 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
17 23 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2
25 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
27 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
1 29 SHC
TC
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.3
3.1
3.2

21 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0
18 25 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
2 27 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
29 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
31 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3

3 21
23
SHC
SHC
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
2.0
1.6
1.9
1.6
1.9
1.5
1.8
1.5
1.8
19 25 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1
27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5
29 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8
31 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1
4 TC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.5 3.4 3.3

23 SHC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.6
20 25 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 2.0
27 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3
5 29
31
SHC
SHC
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.8
3.1
2.7
3.1
2.7
3.1
2.7
3.0
2.7
3.0
2.6
2.9
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.7 3.6 3.5 3.4

23 SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.4
21 25 SHC 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8
6 27 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
29 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4
31 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.8 2.8 2.8
TC 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.1 4.1 4.0 3.9 3.8 3.8 3.7 3.6

7 22
25
27
SHC
SHC
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.9
2.2
1.8
2.2
1.8
2.2
1.8
2.2
1.8
2.1
1.8
2.1
1.7
2.1
1.7
2.0
1.7
2.0
1.6
2.0
1.6
2.0
29 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3
31 SHC 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6
TC 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 3.9 3.9 3.8

8 25 SHC 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5
23 27 SHC 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8
29 SHC 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1
31 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5
8 - 52

TD831156-00_MINI_VRF_SYS.indb 52 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-15MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 4.5 kW AIR FLOW 12.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

21 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
15 23 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
25 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
27 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
TC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

21 SHC 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
16 23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
27 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
29 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
TC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

21 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
17 23 SHC 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
27 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
29 SHC
TC
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.2
3.9
4.1
3.9
4.0
1
21 SHC 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1
23 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
18 25 SHC 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.0 3.0
27 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 2
29 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

21
23
SHC
SHC
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.4
2.0
2.4
1.9
2.3
1.9
2.3
3
19 25 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7
27 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2
29 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6
31 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.1
TC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.5 4.4 4.3 4.2 4
23 SHC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.0
20 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5
27 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9
29
31
SHC
SHC
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.1
3.6
4.0
3.6
4.0
3.5
4.0
3.5
3.9
3.4
3.9
3.4
3.8
3.4
3.8
5
TC 5.1 5.1 5.1 5.1 5.1 5.1 5.0 5.0 4.9 4.8 4.7 4.6 4.5 4.4 4.3

23 SHC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8
21 25 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
27 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 6
29 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1
31 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6
TC 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1 5.1 5.0 4.9 4.8 4.7 4.6 4.5

22
25
27
SHC
SHC
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.4
2.8
2.3
2.8
2.3
2.7
2.3
2.7
2.3
2.7
2.2
2.7
2.2
2.6
2.2
2.6
2.1
2.6
2.1
2.5
2.0
2.5
7
29 SHC 3.3 3.3 3.3 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 2.9 2.9
31 SHC 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.6 3.6 3.5 3.5 3.5 3.4 3.4 3.4
TC 5.7 5.7 5.6 5.6 5.6 5.5 5.4 5.4 5.3 5.2 5.1 5.0 4.9 4.8 4.7

25 SHC 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.8 8
23 27 SHC 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3
29 SHC 3.1 3.1 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7
31 SHC 3.5 3.5 3.5 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1
8 - 53

TD831156-00_MINI_VRF_SYS.indb 53 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-18MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 5.6 kW AIR FLOW 15.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

21 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
15 23 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
TC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

21 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
16 23 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
25 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
29 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
TC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

21 SHC 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
17 23 SHC 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
25 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6
1 29 SHC
TC
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.2
4.9
5.0

21 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2
18 25 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.8
2 27 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 4.9
31 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.0
TC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.2 5.1

3 21
23
SHC
SHC
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.1
2.5
3.0
2.4
3.0
2.4
3.0
2.3
2.9
19 25 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.6 3.6 3.5 3.5
27 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0
29 SHC 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.7 4.6 4.6
31 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 5.2 5.1
4 TC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9 5.8 5.7 5.6 5.5 5.3 5.2

23 SHC 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.7 2.7 2.6 2.6
20 25 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.1
27 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7
5 29
31
SHC
SHC
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.2
4.6
5.1
4.5
5.1
4.5
5.0
4.4
5.0
4.4
4.9
4.3
4.9
4.3
4.8
TC 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.6 5.5 5.4

23 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.3 2.3
21 25 SHC 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.1 3.1 3.0 3.0 3.0 2.9 2.8
6 27 SHC 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4
29 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0
31 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.6 4.6
TC 6.7 6.7 6.7 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.7 5.6

7 22
25
27
SHC
SHC
3.0
3.6
3.0
3.6
3.0
3.6
3.0
3.5
3.0
3.5
2.9
3.5
2.9
3.5
2.9
3.4
2.8
3.4
2.8
3.3
2.7
3.3
2.7
3.3
2.7
3.2
2.6
3.2
2.6
3.1
29 SHC 4.1 4.1 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.7
31 SHC 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.4 4.4 4.3 4.2
TC 7.1 7.1 7.0 7.0 6.9 6.8 6.8 6.7 6.6 6.5 6.4 6.3 6.1 6.0 5.8

8 25 SHC 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3
23 27 SHC 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 3.0 3.0 3.0 2.9 2.9
29 SHC 3.9 3.9 3.8 3.8 3.8 3.8 3.7 3.7 3.7 3.6 3.6 3.6 3.5 3.5 3.4
31 SHC 4.4 4.4 4.4 4.4 4.4 4.3 4.3 4.3 4.2 4.2 4.2 4.1 4.1 4.0 4.0
8 - 54

TD831156-00_MINI_VRF_SYS.indb 54 2012/01/31 14:37:28


Capacity Table
2. Cooling Capacity of Indoor Unit

S-24MR1U6
Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW)
RATING CAPACITY: 7.1 kW AIR FLOW 17.0 m3/min
EVAPORATOR CONDENSER
AIR INTAKE. TEMP AMBIENT TEMP. (oC)
W.B. D.B. 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43
TC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

21 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
15 23 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
TC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

21 SHC 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
16 23 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
25 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2
27 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
29 SHC 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
TC 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2

21 SHC 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
17 23 SHC 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
25 SHC 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
27 SHC 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
29 SHC
TC
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.6
6.2
6.5
6.2
6.4
1
21 SHC 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3
23 SHC 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 4.0
18 25 SHC 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.6
27 SHC 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 2
29 SHC 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.9
31 SHC 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.5 6.4
TC 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.0 6.8 6.6 6.4

21
23
SHC
SHC
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.9
3.2
3.8
3.1
3.8
3.1
3.7
3.0
3.7
2.9
3.6
3
19 25 SHC 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.4 4.3 4.2
27 SHC 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9
29 SHC 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.7 5.7 5.6 5.5
31 SHC 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.3 6.1
TC 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.5 7.4 7.2 7.1 6.9 6.8 6.6 4
23 SHC 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.4 3.3 3.3 3.2
20 25 SHC 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.1 4.0 3.9 3.9
27 SHC 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.8 4.7 4.7 4.6 4.6 4.5
29
31
SHC
SHC
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.2
5.5
6.1
5.4
6.0
5.4
6.0
5.3
5.9
5.2
5.9
5.2
5.8
5
TC 8.1 8.1 8.1 8.1 8.1 8.1 8.0 7.8 7.7 7.6 7.5 7.3 7.1 7.0 6.8

23 SHC 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.0 3.0 2.9 2.9
21 25 SHC 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5
27 SHC 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.3 4.3 4.2 4.2 6
29 SHC 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8
31 SHC 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8 5.7 5.6 5.6 5.5 5.5
TC 8.5 8.5 8.5 8.5 8.4 8.3 8.2 8.1 8.0 7.9 7.7 7.6 7.4 7.3 7.1

22
25
27
SHC
SHC
3.7
4.4
3.7
4.4
3.7
4.4
3.7
4.4
3.7
4.3
3.7
4.3
3.6
4.3
3.6
4.2
3.5
4.2
3.5
4.1
3.4
4.1
3.4
4.0
3.3
4.0
3.2
3.9
3.2
3.8
7
29 SHC 5.0 5.0 5.0 5.0 5.0 5.0 4.9 4.9 4.8 4.8 4.7 4.7 4.6 4.5 4.5
31 SHC 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.5 5.5 5.4 5.4 5.3 5.3 5.2 5.1
TC 9.0 9.0 8.9 8.8 8.8 8.7 8.6 8.5 8.4 8.2 8.1 7.9 7.8 7.6 7.4

25 SHC 3.4 3.4 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.0 3.0 2.9 2.9 8
23 27 SHC 4.1 4.1 4.1 4.0 4.0 4.0 3.9 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5
29 SHC 4.7 4.7 4.7 4.7 4.6 4.6 4.6 4.5 4.5 4.5 4.4 4.4 4.3 4.2 4.2
31 SHC 5.4 5.4 5.4 5.3 5.3 5.3 5.2 5.2 5.2 5.1 5.1 5.0 5.0 4.9 4.8
8 - 55

TD831156-00_MINI_VRF_SYS.indb 55 2012/01/31 14:37:28


201201