Technical Data Type CZ Vacuum On-Load Tap Changer For Dry Type Transformer
Technical Data Type CZ Vacuum On-Load Tap Changer For Dry Type Transformer
General
1. General⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯2
2. Technical specifications ⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯⋯3
1
HM0.154.1102
1. General
Type CZ vacuum on-load tap changer (hereafter refer as CZ or CZ OLTC) is applicable to indoor dry type transformer,
through which the tap changes can be realized for voltage regulation when transformer is energized. CZ OLTC
is designed in single phase structure, If it is applied for three-phase transformer, three units of CZ must be linked
mechanically, and operated by one motor drive unit. CZ can be used for both STAR and DELTA winding connection.
CZ OLTC adopts quick resistance transition switching principle. During tap switching process, the tap selector selects
the tap firstly and then the diverter switch performs switching under the load. The vacuum interrupters work as arcing
contact, and the mechanical contacts carry the main circuit current .Hence, CZ OLTC has good capability for arc
extinguishing and reliable operation for long time.
2
Fig 1 Basic Connection Modes of Regulating Winding
HM0.154.1102
2. Technical specifications
CZ OLTC is designed and manufactured according to IEC60214-1:2003. Please refer to Table 1 for the technical
specifications.
3
HM0.154.1102
3. Model designation
CZ OLTC has various models due to difference of the phase, max. rated through current, highest voltage for
equipment and operation positions. Variations will be described in the CZ model. See below Fig.2 for details:
3 × CZ 500 - 40.5 - 9
Operation positions
4
Fig 3 Basic Connection Diagram of Tap Selector
HM0.154.1102
According to Fig.4 Curve of CZ OLTC Rated Step Capacity., the max. rated through current versus the associated
step voltage of the OLTC can be determined.
We can also provide the supporting frame or cabinet according to the requirements.
5. Special design
The special design of CZ OLTC mainly refers to tap positions location scheme on OLTC and number of operation
positions. Up to date, we can provide the maximum operation positions up to 13 for linear regulation mode.
CZ OLTC can be provided together with supporting frame or cabinet according to customer's requirement. see details
in Appendix.
6
HM0.154.1102
CZ OLTC may be operated by SHM-III or CMA7 motor drive unit according to the requirement, please refer to table 3
for technical data.
SHM-III motor drive unit is proprietary and patented design of Huaming. SHM-III encloses the mechanical actuation
part in the motor drive box and encapsulates the control part in the controller HMK8. It literally separates the mechanic
and electric part.
Table 3 Motor Drive Unit Technical Specifications
Note: Please specify if special voltage required for motor, and control & heater circuit.
7. Operation controllers
HMK8 has BCD code position signal output (contact capacity:AC250V/5A or DC30V/5A) and remote control signal
input (non potential contact), it can also communicate with host computer via RS485 interface to realize remote
supervising of OLTC position.
HMK8 main technical data is as below, refer to HMK8 manual for more details.
Working voltage: 380V, 3AC/N
Power frequency: 50Hz/60Hz
Maximum operation positions: 35
Environment temperature: -10℃ to 40℃ Indoor 7
HM0.154.1102
8. Accessories
The horizontal shaft is made from high strength insulation material, Its length will be determined by the insulation level
required between phases when the tap changer is mounted on the transformer.
The bevel gearbox connects the horizontal shaft of tap changer body and the vertical shaft of motor drive unit, it
transmit the drive torque from motor drive unit to the tap changer. See installation dimension of bevel gearbox in
Appendix 13.
9. Appendixes
8
HM0.154.1102
Unit: mm
9
HM0.154.1102
10 Unit: mm
HM0.154.1102
Unit: mm
11
HM0.154.1102
12 Unit: mm
HM0.154.1102
Unit: mm
13
HM0.154.1102
14 Unit: mm
HM0.154.1102
Unit: mm
15
HM0.154.1102
16 Unit: mm
HM0.154.1102
Unit: mm
17
HM0.154.1102
18 Unit: mm
HM0.154.1102
Unit: mm
19
HM0.154.1102
20 Unit: mm
HM0.154.1102
Unit: mm
21
HM0.154.1102
22 Unit: mm
HM0.154.5701