FG Wilson Service Bulletin: SB 0045 - PCA
FG Wilson Service Bulletin: SB 0045 - PCA
FG Wilson
Service Bulletin
SB 0045 - PCA
02nd March 2010
PROBLEM
On sets fitted with new CE type radiator fan guards, the captive acorn nuts need to be adjusted
correctly.
This procedure must be carried out on the below mentioned sets.
Safety
Equipment required
Page 1 of 3
2
Procedure
2. Make sure the genset has been safely isolated from starting
3. Remove access plate from right and left hand side of radiator guard as shown in image 1.1.1
below.
Loosen bolts
securing fan guard
access plate
Image 1.1.1
4. Check all access plate nuts to ensure they all have been torqued up to 6NM as shown in
image 1.1.2 below.
Page 2 of 3
3
Image 1.1.2
5. Upfit access guard to finish and tighten all bolts securely as shown in image 1.1.3 below.
Image 1.1.3
WARRANTY ALLOWANCE
NOTE: THE SERVICE BULLETIN NUMBER MUST BE QUOTED ON THE WARRANTY CLAIM AS
THE PART NUMBER CAUSING FAILURE.
Page 3 of 3