FG Wilson
Service Bulletin
SB 0045 - PCA
02nd March 2010

SUBJECT: CAPTIVE FASTENER INSPECTION


ON CE RADIATOR FAN GUARD ACCESS PLATES
TERMINATION DATE

6 Months after published.

PROBLEM

On sets fitted with new CE type radiator fan guards, the captive acorn nuts need to be adjusted
correctly.
This procedure must be carried out on the below mentioned sets.

AFFECTED SERIAL NUMBERS

CDH00663 F0B04596 PWA01697


CDH00664 F0B04598 PWA01703
CDH00665 F0B04599 PWA01709
CDH00666 F0B04601 PWA01711
CDH00667 F0B04602 PWA01712
F0B04564 F0B04604 PWA01723
F0B04565 F0B04605 PWA01724
F0B04566 F0B04606 PWA01725
F0B04567 F0B04607 PWA01729
F0B04568 F0B04608 PWA01730
F0B04569 F0B04609 PWA01735
F0B04570 F0B04610
F0B04595 LHC00171

Safety

Follow Olympian safety rules and H & S handbook.

Equipment required

Service tool kit

Page 1 of 3
2

Procedure

1. Switch off the generator set.

2. Make sure the genset has been safely isolated from starting

3. Remove access plate from right and left hand side of radiator guard as shown in image 1.1.1
below.

Loosen bolts
securing fan guard
access plate

Image 1.1.1

4. Check all access plate nuts to ensure they all have been torqued up to 6NM as shown in
image 1.1.2 below.

Tighten up acorn nut to


6NM

Page 2 of 3
3
Image 1.1.2

5. Upfit access guard to finish and tighten all bolts securely as shown in image 1.1.3 below.

Image 1.1.3

WARRANTY ALLOWANCE

NOTE: THE SERVICE BULLETIN NUMBER MUST BE QUOTED ON THE WARRANTY CLAIM AS
THE PART NUMBER CAUSING FAILURE.

Claim Allowance Conditions


This is a 0.5-hour job.
Labour Hours
N/A. This inspection must be done before 1st start-up or at
Travel Hours
dealership

MAKE EVERY EFFORT TO COMPLETE THIS PROGRAM AS SOON AS POSSIBLE.

For more information contact [email protected]