Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

FROM

ADD
SUBJECT
TO
Revision R0
DATE 14/09/2020
Unit / Quantity NET UNIT GRAND
SR NO. Description
Area [Approx] RATE TOTAL
1 AIR HANDLING UNIT
MAKE - CITIZEN , ULTRA AIRTECH , ZECO or Approved equivalent
Instalation of AIR Handling Uints of Different Capacitys
BRIEF SPECIFICATIONS Air Handling Units[DX Operated],Doube Decker,Double Skin
1.1 AHU - 01 - 2570 CFM - 12 KW REHEAT - 100 MM STATIC - 07 TR SET 1
1.2 AHU - 02 - 3157 CFM - 14 KW REHEAT - 100 MM STATIC - 08 TR SET 1
1.3 AHU - 03 - 2443 CFM - 04 KW REHEAT - 100 MM STATIC - 08 TR SET 1
1.4 AHU - 04 - 1014 CFM - 02 KW REHEAT - 130 MM STATIC - 03 TR SET 1
FAN
Make:Kruger,Nikotra,Punkar only , Type: Belt Driven
Velocity: Not More Then 10 mt/second. , Canvass Connection-Heavy duty, non partical shreding,Fire Retardent
Selection of fan-Should run comfortably at 45 HZ at rated capecity.
MOTOR
Make:Siemence,B.B,Crompton,ABB , Type:TEFC,IP:55,Foot Mounted, VFD compitable
Poles: 2 or 4 ,RPM:1440/2800 , Volts:3Ø,415 , Mounting:Heavy duty chennels
Safety: Motor should have interlocked with AHU Motor door/excess/Fire Damper
BODY
Type-TWO TIRE, Floor Mounted , Inner const.:0.6mm plain G.I , Outer const.:0.8 mm G.I. Pre coated
M.O.C:Heavy Duty Hollow Extruded Aluminum sections with Thermal break construction and rested on heavy duty MS "C" Chenel
Thickness of Insulation:43 mm,PUF injected having density 40 to 42 kg/m3. ,Colour:As approved by CLIENT
Drain Pan:S.S.-304,18 SWG duly insulated by 13 mm closed cell nitrile 40 mm heavy duty coupling.
Hardware:.S.S or Galvenised,Diecaste Al.S.S Hinges with Nylone locks , Size: Indicte L x W x H with offer
Inspection Window-Yes Require , Inspection Light-Marine Light Fitting Require with micro switch
Cable Entry-Yes with Rubber Grommet , Megnahelic Gauges-Across all Filter with Gauge
Noice Level-NMT 70 db at @ 1 meter. , Internal coving to all surfaces & internal arrengement of components.
Doors- Aluminum die casted hing type , BMS compitible port across fan, coil,filters should be provided
FILTERS WITH FILTER SECTIONS FOR AHU-01
Fresh Air[EU-4]: Box type,Al. const.,Washable HDPE,95% down to 10µ With Mixing box
Pre Air[EU-4-Before Coil]:AHU mounted,Flange type,Al. const.,Washable HDPE, 95% down to 10µ.
Bleed Air filter[EU-4]: AHU mounted,Flange type,AL construction, to remove particles down to 10 Microns with an efficiency of 95 %
FILTERS WITH FILTER SECTIONS FOR AHU-02
Fresh Air[EU-4]: Box type,Al. const.,Washable HDPE,95% down to 10µ With Mixing box
Pre Air[EU-4-Before Coil]:AHU mounted,Flange type,Al. const.,Washable HDPE, 95% down to 10µ.
Bleed Air filter[EU-4]: AHU mounted,Flange type,AL construction, to remove particles down to 10 Microns with an efficiency of 95 %
FILTERS WITH FILTER SECTIONS FOR AHU-03
Fresh Air[EU-4]: Box type,Al. const.,Washable HDPE,95% down to 10µ With Mixing box
Pre Air[EU-4-Before Coil]:AHU mounted,Flange type,Al. const.,Washable HDPE, 95% down to 10µ.
Bleed Air filter[EU-4]: AHU mounted,Flange type,AL construction, to remove particles down to 10 Microns with an efficiency of 95 %
3 micron fine filter [After Coil]: AHU mounted,Flange type,AL construction, to remove particles down to 3 Microns with an efficiency of 99 %
FILTERS WITH FILTER SECTIONS FOR AHU-04
Fresh Air[EU-4]: Box type,Al. const.,Washable HDPE,95% down to 10µ With Mixing box
Pre Air[EU-4-Before Coil]:AHU mounted,Flange type,Al. const.,Washable HDPE, 95% down to 10µ.
Bleed Air filter[EU-4]: AHU mounted,Flange type,AL construction, to remove particles down to 10 Microns with an efficiency of 95 %
3 micron fine filter [After Coil]: AHU mounted,Flange type,AL construction, to remove particles down to 3 Microns with an efficiency of 99 %
COOLING COIL[DX]
Casing:G.I.sheet , Header:M.S. Heavy duty pipe & suitable refrigerent distributor.
MOC Tube:0.4mm thick,12.5mm dia,Copper,Hydraulically tested at 250psi. , Face Velocity:@450FPM
MOC Fins:0.16 mm thick,Aluminum,12 fins/inch proparly bonded with tube ,Raw Deep-Six
Pipe Entry-With Rubber Grommets , Material to be handled- Refrigerent
VOLUME CONTROL DAMPER
Type:Box,Aerofoil profile opposed blade,Gear driven,Low leakage , MOC: 18 swg Extruded Aluminum.
Other:Marked for Open & Closed. Location-AHU supply,Return,Bleed air,Fresh air[All Actuator compitible]
OTHERS
SUBMIT FOLLOWINGS
G.A.Drawing before Manufacturing. , Fan Performance Curve with offer ,Coil Hydro test certificate ,Noice level Testing certificate.
PUF insulation certificate. , Motor Testing certificate. , IQ,DQ,PQ.of total installation. , Inspection:At Manufacturers work.

2 FIRE DAMPER
2.1 To be installed in the return air of AHU, Bi Metalic, Spring Loaded , micro switch to interlock with motor NOS. 4

3 CONDENSING UNIT
Make - Emerson / carrer / voltas / blue star or Approved equivalent
Type-With Three Phase reciprocating Compressor / Scroll Compressor
Accessories-All controls,expansion device,Refrigerent insulated copper pipe & Filters, system with gas charging,
(copper pipe + cabletray + cable + Insulation + gas INCLUDED)
Internal power wiring (panel to motor & controls on suitable GI perforated tray along with insulated copper pipe .)
3.1 FOR AHU - 01 - 07 TR SET 1
3.2 FOR AHU - 02 - 08 TR SET 1
3.3 FOR AHU - 03 - 08 TR SET 1
3.4 FOR AHU - 04 - 03 TR SET 1
3.10 ABOVE 03 MTR RMT

4 ELECTRICAL PANEL FOR AHU


M.O.C.- 16 SWG CRCS Powder coated.
Type-Stand Mounted Component-M.C.B.,Contector, O/L protector, ON-OFF push button with indicating lamps[Siemense/L & T or App. Equi.]
Temp & RH control with sensor
Inter Locking-With Fan door, Fire Damper/ where ever applicable , Earthing-Proparly earth to individual panel
Cable Entry- May be both top or bottom, shall be decided at the time of Drg.approval
CABLE BETWEEN CONDENSOR UNIT & AHU PANEL accessories like bends, tee’s, supports, etc.
GI perforated cable trays for laying power & control cables between HVAC panel & equipment; including hardware,
Earthing: GI double earthing for HVAC equipment & controls.
4.1 FOR AHU - 01 - 2570 CFM - 12 KW REHEAT - 07 TR SET 1
4.2 FOR AHU - 02 - 3157 CFM - 14 KW REHEAT - 08 TR SET 1
4.3 FOR AHU - 03 - 2443 CFM - 04 KW REHEAT - 08 TR SET 1
4.4 FOR AHU - 04 - 1014 CFM - 02 KW REHEAT - 03 TR SET 1

5 DUCTING
Unit / Quantity NET UNIT GRAND
SR NO. Description
Area [Approx] RATE TOTAL
MAKE - ESSAR, Uttam , JINDLE[GI SHEET] or Approved equivalent
Duct Febrication Work in accordance with the approved shop drawing , and as required by the specifications , ducting comprising complete with hot
dip gelvenized MS Angle Frame , nut bolt , gasket, Sealed by food grade RTV selent , hot dip galvenised supports
Smoke test is essential for all classified area ducts (before insulation) must be witnessed by client.
5.1 24 G GI Sheet SQ.FT 5000

6 INSULATION
MAKE - AROFOAM , K-FLEX , ARMAFLAX [Insulation] or Approved equivalent
6.1 19 mm [Supply duct] polyethylene insulation Fire retardant Class "O" with metalised foil insulation duly sticked with help of adhesive SR-595 SQ.FT 2500
6.2 13 mm [Return duct] polyethylene insulation Fire retardant Class "O" with metalised foil insulation duly sticked with help of adhesive SR-595 SQ.FT 2500

7 Extruded Aluminum Diffuser WITH V.C.D.


MAKE - COSMOS or Approved equivalent
7.1 Supply of aluminium powder coated air diffuser (16/18 SWG) NECK SIZE 300X300 SET 14

8 Megnahelic Gauges (ANALOG TYPE)


MAKE - DWAYER , SENSOCON or Approved equivalent
8.1 Differential Pressure Gauges with sensors & hardware to measure the perssure differential between two adjucent rooms SET 13
Range - 50 0 50 Pascal with calibration certificate 16 SWG CRCS Powder coated Box with frount plet( SS - 304 , 16 SWG)

9 3 MICRON FILTER TERMINAL (ROOM SIDE)


EXTRUDE ALUMINIUM HOUSING (ORIGINAL ONLY) AND WITH SQURE V.C.D. ONLINE HEPA MONITORING AND DOP /POW PORT IS REQUIRED WITH 16
SWG POWDER COATED PERFORRATED CAPSULE SHAPE GRILL
Make : AAF , FREDENBURG , MENCHAMARK or Approved equivalent
9.1 CFM-1000 Bottom loaded filter & housing with v.c.d. operated from bottom SET 8
9.2 CFM-250 Bottom loaded filter & housing with v.c.d. operated from bottom SET 2
MOC
ALUMINIUM ANODIZED EXTRUSION FILTER MEDIA - MICRO GLASS FIBER MEDIA ,GEL MATERIAL - SILICON GEL
EFFICIENCY - 98 % DOWN TO 3 MICRON FILTER , SEALANT - POLYURETHANE
FILTER LOADING - FROM CLEAN ROOM SIDE ONLY ,OPERATION TEMP. - 70 DEGREE C

10 0.3 MICRON HEPA FILTER TERMINAL (ROOM SIDE)


MINI PLEAT HEPA FILTER WITH EXTRUDE ALUMINIUM HOUSING (ORIGINAL ONLY)AND WITH SQURE V.C.D. ONLINE HEPA MONITORING AND DOP /POW
PORT IS REQUIRED WITH 16 SWG POWDER COATED PERFORRATED CAPSULE SHAPE GRILL
Make : AAF , FREDENBURG , MENCHAMARK or Approved equivalent
10.1 CFM-1000 Bottom loaded housing with v.c.d. operated from bottom SET 1
10.2 CFM-500 Bottom loaded housing with v.c.d. operated from bottom SET 1
MOC
ALUMINIUM ANODIZED EXTRUSION FILTER MEDIA - MICRO GLASS FIBER MEDIA ,GEL MATERIAL - SILICON GEL
EFFICIENCY - 99.999 % DOWN TO 0.3 MICRON FILTER GRADE - H 14 , SEALANT - POLYURETHANE
FILTER LOADING - FROM CLEAN ROOM SIDE ONLY ,OPERATION TEMP. - 70 DEGREE C

11 PCC Block for AHUs with RUBBER SHOCK ABSORBER 15MM


11.1 300 (L) X 300 (W) X 300 (H) 06 NOS. TO EACH AHU NOS. 24

12 Commissioning
Commissioning, Documentation & SITC COMPLET AIR HANDLING SYSTEM - DQ,IQ,OQ,PQ JOB 1
12.1 1. CFM
12.2 2. DIFFERIENTAL PRESSURE
12.3 3. TEMP.
12.4 4. HUMIDITY
12.5 5. VELOCITY
12.6 6. ACPH
12.7 7. LIGHT LUMINS
12.8 8. AREA SMOKE VIDIO GRAPHY
TOTAL