VIC Building
VIC Building
VIC Building
Office Building
Standards Guidelines
2001 Edition
Victorian Government Office Buildings
Standards Guidelines
This document was prepared by Fish Payne Pattenden Viney Pty Ltd, Architects and
Environmental planners for, and in consultation with, the Victorian Government Property
Group, Department of Treasury and Finance. The following personnel contributed to its
preparation:-
Laurie Thomas
WT Partnership
Quantity Surveyors
Table of Contents
Table of Contents................................................................................................ i
Introduction........................................................................................................ 1
Purpose .......................................................................................................... 1
Project Intent ................................................................................................... 1
Specification Intent........................................................................................... 1
Scope ............................................................................................................. 1
Information and Documentation ........................................................................ 2
Government policies and guidelines .................................................................. 2
Element 1 Architectural Design ......................................................................... 3
1.1 Building location...................................................................................... 3
1.2 Building types ......................................................................................... 3
1.3 Building design ....................................................................................... 3
1.4 Planning module ..................................................................................... 4
1.5 Accommodation standards ...................................................................... 4
1.6 Provisions for people with disabilities ....................................................... 5
1.7 Building area efficiency ........................................................................... 6
1.8 Quality assurance................................................................................... 6
1.9 Durability................................................................................................ 6
1.10 Asbestos / hazardous materials ............................................................... 6
Element 2 Architectural Finishes....................................................................... 7
2.1 Scope .................................................................................................... 7
2.2 General standard .................................................................................... 7
2.3 Typical finishes ....................................................................................... 7
2.4 Typical areas ........................................................................................ 14
Element 3 Structural Design............................................................................ 17
3.1 General requirements ........................................................................... 17
3.2 Design loadings .................................................................................... 17
3.3 Deflection limitations ............................................................................. 18
3.4 Constructional tolerances ...................................................................... 18
3.5 Weather-tightness and control of moisture entry...................................... 19
3.6 Vibration............................................................................................... 19
3.7 Non-conforming products & materials..................................................... 19
Element 4 Civil Works...................................................................................... 21
4.1 Stormwater drainage system ................................................................. 21
4.2 Regulations & standards ....................................................................... 21
Element 5 Hydraulic Services.......................................................................... 23
5.1 Water supply ........................................................................................ 23
5.2 Fire hydrant & hose reels....................................................................... 23
5.3 Sanitary plumbing and drainage............................................................. 23
5.4 Regulations and standards .................................................................... 24
5.5 Energy efficiency .................................................................................. 24
Introduction
Purpose
These Guidelines set out fundamental requirements for the design, development
and/or procurement of office accommodation for lease or purchase by the State
Government of Victoria and provide the basis for comparison and assessment of
proposals.
Project Intent
To provide buildings which satisfy the accommodation requirements of the Victorian
Government at the standard outlined in this specification or better at minimum cost.
Specification Intent
The purpose of this specification is to set forth the design and construction
parameters which will ensure that the building and associated facilities are free from
repair work for a minimum period of 25 years, or for the duration of the lease, to limit
ongoing maintenance and to minimise running costs.
Scope
The Guidelines incorporate the following disciplines:
• one set of ‘as-built’ floor and ceiling plans on A3 size white paper at 1:200 scale
without technical notes and dimensions.
• 3.5’ HD diskettes containing the above ‘as-built’ drawings in DXF format with
supporting drawing register and DXF translation logs.
Element 1
Architectural Design
• Type 1a Located in Melbourne capital city precinct and intended for office
use.
• Type 1b Located in metropolitan Melbourne and intended predominantly for
office use.
2
• Type 1c Net rentable floor area greater than 2,000 m and located in other
major urban or rural centres with a population in excess of 50,000.
2
• Type 2 Net rentable floor area less than 2,000 m predominantly for office
use and located in smaller urban and rural centres with a population
less than 50,000.
• Type 3 Special purpose building.
• Public space
– entrance foyer with reception area
– lift lobbies
– waiting areas
– public toilets.
• Office space
– open plan office areas and individual offices
– communications and equipment rooms
– interview, meeting and conference rooms
– areas for compactus storage.
• Ceiling heights
– ceiling height generally over office space 2,700 mm minimum
– ceiling heights in foyer and reception areas 3,000 mm minimum
– ceiling heights in service areas 2,400 mm minimum
– Note bulkheads below 2,400 mm will generally not be accepted.
• Parking
– internal or external secure car parking as set out in the attached table
– sheltered bicycle park with provision for locking points.
Type 1a By arrangement
Type 1b 3.5 bays / 100 m 2 rentable floor area
Type 1c 3.5 bays / 100 m 2 rentable floor area
Type 2 3.5 bays / 100 m 2 rentable floor area
Type 3 Dependant on the requirements of the architectural
facilities brief
Refer Advisory Notes on Access to Premises (Human Rights and Equal Opportunity
Commission), RD97/01 Provisions for People with Disabilities (Australian Building
Codes Board), Australian Standard (AS) AS 1428 (all parts) and the Building Code of
Australia (as amended).
Type 1a,b & c 75%-80% for total building, 80%-85% for typical floor
1.9 Durability
The Proposer may provide an evaluation of Life Cycle Costing over the projected life
of the building or the lease period. Life cycle costing shall include energy,
maintenance and all other running costs.
Element 2
Architectural Finishes
2.1 Scope
Where a Proposer intends to provide for fitout to a new building or offer the use of an
existing fitout, the finishes and fittings shall generally be as described in this section
of the Guidelines.
• The design of the entire roofing system, including rainwater goods must be such
that the roof remains permanently weatherproof.
• Provide adequate means of dealing with vapour pressure, condensation,
corrosion and thermal movement.
• Support equipment loads, access walkways and roof access without impairment
to performance.
• Provide a minimum thermal resistance of R 3.0. For metal deck roofs use
insulation blanket supported on double sided foil or use foil bonded to an
insulation blanket.
• Metal deck roofing must be a minimum of 0.48 mm base metal thickness.
• Where roof can be overlooked, or where required by any Authority, Colorbond
metal decking is to be used. Elsewhere use Zincalume. Use only one finish on a
building.
Glazing
• Thickness of glass shall be determined by the size of the frame and the exposure
conditions in accordance with AS 1288 – Installation of Glass in Buildings.
• A minimum of 10.38 mm thick laminated safety glass is to be used for internal
partitions, join vertically with silicone rubber compound.
• Selection of external glazing must take into account the requirement for general
energy efficiency and be selected so as to minimise the requirement for air
conditioning.
• Mirrors to be fabricated from 6 mm thick mirror backed float glass, adhered to
12 mm thick moisture resistant medium density fibreboard, edged with 18 x
18 mm aluminium angle on all sides. Aluminium angle to be powder–coated to
selected colour and to have mitred corners. Use concealed fixings to attach to
wall.
Window furnishings
Windows to be fitted with Luxaflex Slimline Shades or approved equivalent as follows:
• Plasterboard
– 13 mm thick gypsum plasterboard to AS 2588
– recessed edges for flush jointing.
• Solid plaster
– multiple coat application to AS C 27
– nominal overall thickness 16 mm.
• Fibre cement sheet
– 6 mm or 9 mm thick Villaboard fibre cement sheet depending on location and
usage
– recessed edges for flush jointing
– use in wet areas and as a substrate for ceramic wall tiles on stud walls.
Tiling
Floor and wall tiling shall be to the following minimum extent.
• Toilets Ceramic wall tiles to 1,200 mm on all walls, ceramic floor tiles
throughout, proprietary cove tiles where floor and wall tiles meet.
• Shower areas Ceramic wall tiles to full height on all walls, ceramic floor tiles
throughout, proprietary cove tiles where floor and wall tiles meet.
• Tea rooms Ceramic wall tiles to 300 mm above sinks etc. where no overhead
cupboards provided and to underside of overhead cupboards where provided,
Ceramic floor tiles or sheet vinyl throughout.
• Foyers Ceramic floor tiles throughout.
• Porches Ceramic or quarry floor tiles with matching step treads where required.
• Ramps Ceramic or quarry floor tiles with matching step treads where required.
• Steps Ceramic or quarry floor tiles with matching step treads where required.
• Ceramic wall tiles generally to be 150 x 150 mm or 100 x 200 mm Johnson tiles
or equivalent approved manufacture.
• Internal floor tiles generally to be 200 x 200 mm Granito F series or equivalent
approved manufacture.
• External floor tiles generally to be 300 x 300 mm Granito QC series or equivalent
approved manufacture.
• Grout colour to match tiles and to be sealed.
• Provide matching colour silicone sealant to vertical jointing at internal corners.
Cabinet making
Where supplied, custom made built in cupboards, benches, shelving units shall
conform to the following standard.
• All materials shall be new and shall be the best of their kind.
• Timber shall be kiln dried reconditioned Victorian Mountain Ash (KDRHW)
dressed on 4 sides.
• Particle board shall be Laminex moisture resistant craftwood. Work surfaces shall
be a minimum of 32 mm thick. Shelving to be a minimum of 25 mm thick. Carcass
to be 18 mm thick with full backs.
• Laminates. Work surfaces shall be 0.8 mm thick postformed to substrate.
Splashbacks shall be 1.2 mm thick hand bonded to substrate. All visible surfaces
shall be Lamiwood with matching PVC edge strip to all sides of drawer fronts and
doors. Internal surfaces shall be white melamine.
• Hardware. Stock pattern brass pintols shall be used for adjustable carcass
shelving. Hinges shall be first quality concealed type cupboard hinges which will
provide a long and trouble free service life. Handles shall be 100 mm wide satin
chrome ‘D’ pulls. Lockwood 600 series lever cupboard locks shall be fitted to all
drawers and doors.
Ceilings
Suspension systems and ceiling linings are to generally comply with the requirements
of AS 2785 and as follows:
• Suspension system
– screw-up metal suspension system for flush jointed plasterboard.
– exposed grid metal suspension system for removable ceiling panels.
– exposed suspension members and trim to be factory painted.
– suspension system should be capable of height adjustment.
• Plasterboard
– 13 mm thick gypsum plasterboard to AS 2588 or 10 mm unispan.
– recessed edges for flush jointing.
• Acoustic tiles
– removable mineral fibre tiles or panels.
– when tested to AS 1530.3 the Fire Hazard Indices to be not greater than
Ignitability = 0, Spread of Flame = 0, Heat Evolved = 0 and Smoke
Developed = 3.
• Special linings
Approved materials to suit locations and user requirements.
• Acoustic insulation
Ceilings over fully enclosed interview, meeting, conference, plant,
communications and equipment rooms to have a 50 mm sound insulation blanket
to entire ceiling and 1,200 mm beyond partition wall.
Broadloom carpet
• Thoroughly prepare the concrete floor. Fill any holes, grind off any lumps and
smooth the surface with Ardur K 15 or Ardit, etc. to ensure a suitable surface.
• Install carpet over Monoslab underlay. Underlay is to be adhered to the prepared
substrate. Carpet is to be adhered to the underlay. Install carpet with bars at
transitions between carpet and other floor finishes.
• Minimum carpet specification to be:
– heavy duty, anti-static broadloom
– pile fibre 100% wool or 80/20 wool/nylon mix
2
– pile weight 1,640 grams/m
– average pile height 6 mm
– when tested to AS 1530.3 the spread of flame index should be not greater
than 0 and the smoke developed index should be not greater than 5.
Carpet tiles
• Thoroughly prepare the concrete floor. Fill any holes, grind off any lumps and
smooth the surface with Ardur K 15 or Ardit, etc. to ensure a suitable surface.
• Minimum carpet tile specification to be Feltex 100% Antron XL rubber backed
carpet tiles.
Vinyl flooring
• Thoroughly prepare the concrete floor. Fill any holes, grind off any lumps and
smooth the surface with Ardur K 15 or Ardit, etc. to ensure a suitable surface.
• Minimum vinyl specification in general use areas to be Armstrong Nylex Contract
Interior range or equivalent approved.
• Minimum vinyl specification in wet areas to be Altro safety flooring D 25 or
equivalent approved.
Painting
Unless otherwise noted all materials must be premium grade paints (not trade paints).
• One brand of paint only may be used for the entire job. (e.g. one of Dulux,
Taubmans, Bristol, Wattyl or British Paints)
• All preparation, type of paint and number of coats of each type is to be in
accordance with the manufacturers recommendation.
• Preparation of surfaces, painting systems. This specification is to be taken as a
minimum statement of requirements
Dulux brand paints have been called-up for the sake of specification convenience.
An alternative brand may be used provided that the painting systems are equivalent to the
Dulux Systems listed.
Work stations
Submit details of proposed proprietary workstations for approval.
Element 3
Structural Design
• stability
• strength
• serviceability
• durability
• fire resistance.
• AS 1170.1 SAA Loading Code, Part 1: Dead and Live Loads and Load
Combinations
• AS 1170.2 SAA Loading Code, Part 2: Wind Loads
• AS 1170.4 SAA Loading Code, Part 4: Earthquake Load.
Live loads
Minimum design live loads shall be as follows:
Dead loads
A minimum dead load allowance of 0.3 kpa for ceiling and services is required for all
office floors.
– shrinkage
– creep
– temperature variations
– moisture variations
– deformations under load
– foundations movements.
Inter-storey lateral drift of the building under loadings must not exceeding 1/500 of the
storey height.
3.6 Vibration
Vibration of the structure due to plant, equipment, vehicular traffic and pedestrian
traffic must be within limits that will not adversely affect the structure, occupant
comfort and operation of equipment.
Element 4
Civil Works
The roof storm drainage system should provide for the collection of surface runoff
from carparks, access roads, forecourts, ramps and other external areas including
landscaping areas by way of entry pits and/or grated pits. The pipe drain system
should provide for a minimum of 1 in 10 year storm event with overland flow paths
away from buildings for flows in excess of this storm event. Where overland flow
paths cannot be provided the pipe drain should provide for at least a 1 in 50 year
storm event.
Where required, a pumped system be installed to provide for a 1 in 100 year storm
event with connection to a suitable pipe drain system for areas which cannot be
drained by way of a gravity system. If damage to the building could result from failure
of the pump, a dual pump installation should be provided.
Element 5
Hydraulic Services
• mains pressure water supply reticulation to all fixtures plant and equipment
• where mains pressure is inadequate, a duplicate pumping system servicing upper
level storage tanks with gravity feed to upper level fixtures
• capacities of water supplies and water storage and make up systems should be
sufficient to cater for peak period demand
• an allowance of 30% capacity is suggested for additional fixtures in fit out works
• pressure in hot and cold water systems should be similar.
Flexibility should be available in the pipe sizing and layout for the connection of
fixtures in tenancy areas.
Taps over kitchen sinks and have basins to include aerators and showerheads to be
AAA rated for water use.
Toilet groups will have accessible isolation valves on hot and cold water.
Element 6
Mechanical Services
• Access for maintenance and servicing of all systems and equipment including:
– air conditioning and ventilation ductwork and terminal equipment
– cooling and heating piping
– electrical and controls cabling and equipment.
• Incorporate additional space for any future capacity requirements. Masonry shafts
may be used for return air - not supply air
• Access facilities such as:
– fully sealed doorways
– services risers to be accessed from circulation corridors (not from office
areas)
– access through ceilings to service all items of equipment.
• Equipment schedules including:
– cooling, heating, air handling and pumping equipment
– energy performance details and source of supply
– age and condition of each item of equipment and ‘balance of life’ remaining
– maintenance schedules including servicing intervals
– maintenance records and service report forms.
• As installed documentation including:
– as built drawings
– testing and commissioning results including settings of all items of equipment
– operating and maintenance manuals
– descriptions systems and equipment including operating procedures.
• Energy management records including:
– last 12 months billing data for all fuels
– energy management plan and procedures
– energy/service documentation.
6.2 Quality
Installation will be evaluated against specific criteria including:
• design integrity
• reliability
• durability
• flexibility of fit out
• ease of maintenance.
Indicate the quality systems in place to assure the quality of design, maintenance,
and construction – refer Element 1.8 – Quality Assurance.
• cleaning of all equipment and ducted systems. State methods and extent of
cleaning proposed.
• air filters installed to the following minimum criteria:
– Type 1 Buildings Deep bed dry media filters or electrostatic precipitators
and precipitators and pre-filters to the following
minimum efficiencies in accordance with AS 1234
No.1 Dust: Minimum peak efficiency 30%
No.2 Dust: Minimum peak efficiency 98%
No.3 Dust: Minimum average efficiency 81%
– Type 2 Buildings Built up air handling units shall be provided with deep
bed filters as per Type 1 buildings
Packaged air conditioning units shall be provided with
high quality panel filters to the following minimum
efficiencies in accordance with AS 1132
No.2 Dust: Minimum arrestance efficiency 90%
No.4 Dust: Minimum arrestance efficiency 70%
– Type 3 buildings Air filters shall be installed according to the project brief.
• No leakage between filters and filter frames.
• Provision of air filter pressure differential instrumentation.
Separation between outside air intakes and exhaust shall comply with the
requirements of AS 1668. Where cooling towers are used careful consideration shall
be given to location of cooling towers in relation to outside air intakes and adjoining
properties to minimise risks associated with legionella.
A building health audit be carried out in accordance with the procedures set out in the
document Managing Indoor Air Quality by the Property Council of Australia prior to
the conclusion of any contract agreements.
• AS 1132 Air Filters for Use in Air Conditioning and General Ventilation
• AS 1668.1 Fire and Smoke Control
• AS 1668.2 Mechanical Ventilation for Acceptable Indoor Air Quality
• AS 1670 Automatic Fire Detection and Alarm Systems - System Design,
Installation and Commissioning
• AS 3666, Parts 1 & 2 Air Handling and Water Systems of Buildings -
Microbial Control
• AS 3000 Wiring Rule
• AS 3439.1 Low Voltage Switch Gear And Control Gear Assemblies.
• AS 4254: Ductwork for Air Handling Systems in Buildings.
• Sustainable Energy Authority - Building Energy Brief for Commercial and Public
Buildings
• Building Code of Australia
• Property Council of Australia - Managing Indoor Air Quality
• ASHRAE Guideline 1–1996, HVAC Commissioning Process.
• ASHRAE Standard III–1988, Practices for Measurement, Testing, Adjusting and
Balancing of Building Heating, Ventilation, Air Conditioning and
Refrigeration Systems.
• Victorian Health (Infectious Diseases) Regulations 1990, S.R. No. 85/90.
• Victorian Service and Installation Rules.
• Design of fitouts should comply with the current edition of the Property Council of
Australia’s guidelines.
• Design temperature based on the values tabulated in the Australian Institute of
Refrigeration Air Conditioning and Heating Design Aid Air-Conditioning Systems,
current edition.
• Indoor temperature settings - nominally 22.50C + 1.50C .
Together with other particular facilities as may be required by the particular project
brief.
The requirements of the above documents shall also be applied to other building
services systems, in so far as they are relevant.
6.11 Controls
Automatic controls shall be provided to maintain space temperatures and economical
operation of all systems and equipment and shall be configured as follows:
Integrate the operation of the mechanical services, fire protection systems and
communication facilities.
Mechanical services switchboard shall be type tested to prospective fault levels and
shall be provided with segregations appropriate to the size and capacity of the
installation. Provision for 20% spare capacity should be provided.
All necessary protective and other devises shall be provided. Power and control
wiring shall be run separately and shall be enclosed in conduits, in plant-rooms and
other exposed locations. Elsewhere wiring shall be run on cable trays.
Electric motors below 22.0 kW shall be provided with Type 1 protection in accordance
with AS 3947.4.1. For electric motors larger than 22.0 kW Type II protection shall be
provided in accordance with AS 3947.4.1.
The entire circuitry and motors shall be sized to drive pumps and fans at 100% of
their rated duty and the installed design flow.
All fan motors should be fitted with variable speed drives where applicable.
In addition, procedures for operation and maintenance of these facilities shall be set
down in the manuals provided.
• up to 100% redundancy
• valve connections to each floor
• 24 hour 7 days per week operation.
Indicate flow rates and flow and return temperatures allocated to tenants for such
systems.
External noise levels shall comply with the requirements of the Environmental
Protection Act.
Element 7
Electrical Services
7.1 Scope
The electrical services as applied to building shall include the following:
7.2 Standards
The electrical services installation and facilities shall conform to the requirements of
the latest issues of the following standards and subsequent amendments:
• Electromagnetic interference
Computer equipment, communication facilities, video display units, sensitive
electronic control systems, etc., shall be located away from the immediate vicinity of
high power carrying conductors and plant including:
• Stand–by capacity
Type 1 buildings shall generally have an on-site stand-by electrical power
generation facility having a minimum capacity which is sufficient to maintain in
operation during any period of loss of mains power all essential services, plus
50% lighting, 50% of lifts and all air handling systems.
• Power factor
Power factor connection facilities shall be provided to satisfy the requirements of
the Distributor and the Consumption Tariff.
The proposer shall liaise with the supply authority in order to select the most
economical tariff based upon the expected profile of use and the size of the load.
The proposer shall provide a copy of the analysis of the tariff options, which has
led to the selection of the tariff chosen.
• Metering
Provision shall be made to install separate metering and meter reading and
reporting system to meet anticipated tenancy sub-divisions. The Victorian
Government will advise proposers in the project brief of the particular metering
arrangement it requires.
The metering shall be installed to the requirements of the Metering Code and the
electricity supplier.
7.5 Switchboards
• General
All switchboards shall comply with the following requirements:
– Spare space shall be provided within the switchboard to permit the future
installation of switchgear required to make use of the 50% spare electrical
capacity.
– Spare space shall be provided within the switch-room or cupboard to permit
the future installation of one additional switchboard module of length equal to
the other modules or 20% of total switchboard length, whichever is the
greater.
– Provide discrimination co-ordination for all protection devices.
– Main switchboard and distribution switchboards (DBS) should include pulsing
submeters to facilitate energy management of energy cost divestment.
• Distribution boards
Distribution boards shall be designed in compliance with the following:
7.6 Submains
Separate submains shall be installed for each type of building facility in each plant
area, and shall comprise:
• Other areas
Provide sufficient general purpose outlets to serve all facilities called up within
these Guidelines. In addition outlets shall be in all service areas, toilets, plant-
rooms and the like to ensure that cleaning and maintenance operations can be
carried out safely and efficiently.
• Wiring
2
General purpose power circuits shall be wired in not less than 2.5 mm PVC
wiring with not greater than two-thirds circuit utilization.
7.8 Lighting
• General
Low brightness tri-phosphor lamp fluorescent lighting shall be used for all office
and other working areas. The entire installation shall comply with the
requirements of AS 1680. Corridor/circulation space lighting should be at lower
levels than work areas.
In conference and meeting rooms, the lights shall be controlled by the room
switch and sensor control.
2
Lighting circuits shall be wired in not less than 2.5 mm PVC wiring to a maximum
two-thirds capacity.
Ballasts and PFC capacitors shall conform to AS 2643, AS 2644 and AS 3168.
Ballasts shall be selected from a ‘low loss’ or super low loss’ range i.e. 15% or
10% of the nominal lamp rating. Consider usage of electronic ballast.
The wiring network shall be loaded to a maximum of two-thirds capacity and shall
incorporate an un-switched active conductor, carried to each plug base, to
facilitate future luminaire switching.
Where the project brief identifies the possibility that screen based equipment will
be installed, the lighting installation shall comply with the requirements of
AS 1680.2.2.
minimum, work area lighting shall be switched locally in banks having not more
2
than 50 m lit from a single switch. The lighting layout shall be arranged so that
perimeter lighting near windows can be switched separately. Automatic lighting
controls shall switch manually on and automatically off. Occupancy sensors shall
be considered for intermittently used areas, such as conference rooms and
lecture theatres.
• Architectural lighting
Quite often there will be parts of a project where the lighting requirement extends
beyond the purely functional need to provide a specified illuminance.
Dimming systems and/or programmed controls for the integration of natural with
artificial light should be a consideration in all new lighting installations.
Centralised emergency and exit luminate testing facilities shall be provided. This
facility shall comprise test switches at the location of each distribution board in
2
buildings with a floor area of no more than 5,000 m . In larger buildings a
computerised central test facility shall be installed.
Element 8
8.1 Scope
Fire Protection Services as applied to buildings are defined as all fire detection and
fire suppression facilities, together with all required alarms and controls. These
facilities are integral with the smoke control systems contained within the mechanical
services installation, the emergency exit lighting provisions of the electrical
installation, the emergency warning and evacuation system contained within the
Communications installation and the operation of the lifts in fire alarm mode.
– Part 1 Fire
– Part 2 Local Fire
– Part 3 Monitoring network performance
• Sprinkler systems shall generally be of the wet pipe type except as may be
specified otherwise in the project brief.
• Sprinkler system piping networks shall be designed, calculated and sized to
accommodate the installation of up to 30% additional sprinkler heads in office
and work areas. Provide plugged tees in branch piping to facilities such additions.
Provision for one additional module or 20% additional length, whichever is the
greater, shall be made.
All necessary protective and other devices shall be provided. Power control wiring
shall be run separately and shall be enclosed in conduits, in plant-rooms and other
exposed locations. Elsewhere wiring shall be run on cable trays.
• General
Provision shall be made to provide ongoing access for the installation and
servicing of all systems and equipment. Service pathways shall be continuous
and allow access at every floor level, typically form circulation corridors.
Visual and audible alarm/evacuation shall be provided in accordance with the BCA,
associated standards, and manufacturers requirements to suit each
application/installation. Gas cylinder storage shall be in accordance with the BCA,
associated standards and manufacturers requirements.
Element 9
Lift Services
9.1 Scope
Building transportation facilities are defined as all those systems which facilitate the
movement of people, furniture, equipment and other suppliers throughout a building
and, supplementarily, the movement vehicles in situations where spatial limitations
apply. As such they include:
• passenger lifts
• goods lifts
• escalators
together with other particular facilities as may be specified in the particular project
brief.
For two (2) and three (3) storey buildings a lift shall be provided for the vertical
transportation of equipment, furniture, supplies and disabled persons unless direct
compliant access to all floors is possible from ground level as a consequence of, for
example, a sloping site.
Consideration should be given to reducing capacity standby and out of hours energy
use through efficient control systems and lift drive technology.
For small buildings having only one lift this unit shall be designed for combined
passenger/goods services.
For buildings exceeding 4 levels (including ground) having a net useable floor area of
2
less than 20,000 m at least two passenger lifts shall be equipped for combined
passenger/goods service. Passenger/goods lifts shall have a minimum rated capacity
of 1,500 kg.
2
For buildings having a net useable floor area of between 20,000 and 35,000 m a
minimum of one dedicated goods lift having a minimum rated capacity of 2,000 kg
shall be provided.
2
For buildings have a net useable floor area in excess of 35,000 m a minimum of
two (2) dedicated goods lifts having a minimum rated capacity of 2,000kg each shall
be provided.
Where circumstances require additional goods service the relevant requirements will
be defined in the particular project brief.
Protective quilts which clip on to lift interiors shall be provided for combined
goods/passenger lifts. Dedicated goods lifts shall have appropriately braced stainless
steel wall linings or similar robust finish preferably with a 250 mm buffer rail located at
an appropriate height on all walls of the car. Buffer rails shall be manufactured from
an approved impact resistant and absorbing material.
Supplementary systems
Lift systems which serve car-parks or other particular areas shall bed designed to
provide a quality of service which is consistent with the specified quality of the main
lift systems.
Main lift system service shall preferably not be extended to supplementary areas
such as basement car-parks.
Where passenger lifts incorporate goods and/or stretcher carrying provisions the
above width/depth requirements may be varied.
Door safeties shall include full height light ray detection with ray spacing not
exceeding 100 mm. Door nudging audible indicators and displays be included.
For installations with a service speed greater than 1.8 m/s acceleration shall not
2 3
exceed 1.3 m/s and the rate of change of acceleration shall not exceed 1.8 m/s .
9.7 Escalators
Where provided, escalators shall be minimum 1,000 mm width and shall operate at
0.6 m/s.
Liberal provision for queuing shall be made at the top and bottom landings and at
entry and exit points of the escalator itself. In public areas construction shall take
All communication devices within lift cars shall be fully flush mounted and not require
the use of a handset. Ensure all remote connections to telephone/data lines
necessary are made to ensure correct operation of the communication systems.
9.9 Controls
Transportation systems controls shall be microprocessor based and shall incorporate
remote monitoring facilities for both performance and maintenance requirements.
This information shall include complete details of circuitry, software and maintenance
and trouble shooting procedures for all equipment which forms part of the installation.
Element 10
Energy Management
• appropriateness to the size, location, use and internal environment of the building
• passive energy performance of the building facade
• capacity of the building service systems and their performance in relation to
energy consumption
• ability to monitor and report energy consumption of various services and
tenancies for energy management and cost divestment purposes
• potential impact of materials, fuels and refrigerants upon atmospheric ozone layer
depletion and global warming
• flexibility of spatial planning to allow the integration of developing technologies
into business operations
• safety and security and information
• maintainability of systems and equipment.
10.2 Usage
Proposers shall submit evidence of energy performance which is based upon actual
records of consumption and hours of operation. This information shall be
standardised to reflect compliance with the design requirements set out in these
Guidelines and the basic 2,500 hours of annual operation. This is nominally 250 days
(which excluded weekends and public holidays) of 10 hours each. Occupation to
commence at 8.00 am and terminate at 6.00 pm. Allowance shall be made for
morning warm up and cooling down prior to 8.00 am occupancy.
• Energy Guidelines for Building Owners and Managers published by the Property
Council of Australia
• ASHRAE/IES Standard 90.1 Energy Conservation in New Building Design,
Except Low Rise Residential, published by the American Society of Heating,
Refrigeration and Air Conditioning Engineers in collaboration with the Illumination
Engineering Society of North America.
• Building envelope passive energy performance would normally incorporate the
following design factors:
– single glazing, where used shall not exceed 25% of the wall area (reference
shading coefficient 0.95) except for ground floor show rooms, entry lobbies
and the like.
– double glazing, where used shall not exceed 50% of the wall area (reference
shading coefficient 0.4)
• Building energy brief published by the Sustainable Energy Authority.
• Insulation would normally be applied to other building envelope components to
attain thermal resistance values as follows:
– Walls R 1.3
– Roofs R 3.0
– Floors R 1.0
• Infiltration levels shall be minimised by careful consideration of construction
requirements. Design of entry lobbies and other entry and exit doors shall also
reflect this requirement
• Alternative arrangements of building envelope which deviate from the above
requirements will be considered provided that the building as a whole achieves
equal or superior passive energy performance levels to that which would be
attained when adhering to the requirements. In calculating such performance
levels allowance shall not be made for internal shading devices. It is permissible,
however, to incorporate permanent external shading devices in the assessment.
Calculations which demonstrate equivalent performance shall be submitted
where such other arrangements are to be adopted.
10.4 Lighting
Energy efficient lighting shall be adopted throughout the building.
For other areas proposers shall indicate the energy consumption levels attained.
• Air Transport Factor = Space Sensible Heat Removed ÷ Supply & Return Fans
Power Input > 5.5
For general ventilation systems low velocity/low pressure systems shall be provided.
Air handling system ducts carrying cooled or heated air shall be fully insulated.
Element 11
Security Systems
11.1 Scope
Security facilities include control and monitoring systems complete with any
necessary interfaces between the various building services.
11.2 Security
Security facilities shall be provided that are appropriate to the needs of the building
user. Where facilities are provided they will be a mix of physical and electronic
measures that must be carefully integrated.
Buildings for Government occupation shall incorporate the following basic security
facilities:
Where CCTV or computer based access control/security system are provided they
shall be selected to enable extension of security on a multi-level basis to all office and
work areas as required.
Element 12
Acoustics
12. Acoustics
The building and its services shall be designed to accord with the recommendations
of Australian Standard (AS) AS 2107 Acoustics – Recommended Design Sound
Levels and Reverberation Times for Building Interiors and of Design Aids Nos. DA2
and DA7, Noise Control in and Around Buildings, Parts 1 and 3 of the Department of
Housing and Construction in association with the Australian Institute of Refrigeration,
Air Conditioning and Heating (Inc.) except that notwithstanding the criteria stated
therein the design noise level for general office accommodation shall be NR 35.
Provide verification from an approved acoustic consultant at the tenancy design stage
to confirm that the maximum noise levels will not be exceeded. Analysis should
include:
Element 13
Information Technology
Element 14
Communication Systems
14.1 Scope
Together with other special facilities as may be specified in the particular project brief.
14.2 Standards
The communication systems installations shall conform to the requirements of the
following standards and other documents:
Where potential users described in the facilities brief are a medium to heavy users of
data equipment, it shall be mandatory for proposers to include a data block cabling
scheme which may be integrated with the telephone block cabling scheme. Cabling
schemes shall conform with the requirements of AS 3080.
• Provision shall be made to provide ongoing access for the installation and
servicing of all systems and equipment. Service pathways shall be continuous
and allow access at every floor level, typically from circulation corridors.
• Separate pathways shall be provided for the installation of:
– electric mains cables
– communication cables
– fire and emergency systems cables
– control cables.
• Cable trays shall be installed in ceiling and other spaces to carry initial cabling in
a future fitout cabling. Trays shall be sized to anticipate the extent of wiring need
to carry the specified design requirements.
• Spatial planning shall incorporate space capacity for future requirements.
The following spatial provisions for both vertical and horizontal spaces are regarded
as being mandatory:
• spare space in MDF and local communications rooms for fibre optics cables
terminations
• space for PABX equipment, data multiplexing equipment, modems and other
such equipment
• space shall be provided on each floor level to accommodate communications
cabling systems distribution facilities.
Element 15
15.1 Objective
Key objectives of the management and synthetic mineral fibre building materials are:
• removal
• enclosure
• encapsulation
• administration controls (labelling and restricting access).
Depending on the nature of the asbestos containing material one or more the above
control methods may be utilised.
Caution is required when handling SMF products in order to minimise airborne SMF
fibre levels.
Essentially, SMF materials should be handled in such a way as to minimise dust and
disturbance of the materials. Where SMF materials are required to be installed or
removed, then suitable controls and appropriate personal attention are to be
provided. Consultation should be sought with regard to appropriate procedures prior
to the handling of such materials.
Element 16
Quantity Surveying
16.1 Introduction
Reference is made to Investment Evaluation - Policy and Guidelines as issued by the
Department of Treasury and Finance and National Public Works Conference (Aust),
Cost Control Manual, 1988.
The Quantity Surveyor shall provide estimating and cost planning services, together
with advice and assistance in value management and Life Cycle Costing.
Estimate Reconciliations
At the issue of new or updated estimates, a full reconciliation with the immediate
previous estimate shall be prepared by the quantity surveyor.
The reconciliation shall include, but not necessarily limited to, changes in scope of
works; changes in specification / quantity; changes in costing levels over time.
Involvement shall include, but not necessarily limited to; attendance at value
management sessions; provision of costing advice for various options; analysis of
impact on capital cost versus operating cost.
• capital cost
• replacement cost
• energy consumption
• design and construction time
• maintenance costs
• staffing costs
• financial costs
Element 17
Building Certification
17.2 Approvals
Confirm with the relevant Municipal Council whether or not a Town Planning permit is
required for the works.
Confirm with the relevant Municipal Council the relevant property information for the
works
All building works and alterations are to be certified and/or be subject to a Building
Permit as required by the Building Act 1993.
• structural
• civil
• hydraulic
• mechanical
• electrical
• fire service
• glazing.
All the above information is to be reviewed and assessed and the necessary approval
granted based on their conformity with their related and respective Government
regulations as stipulated in the above publications.