Solar Boost™ 2000E: 25amp 12Vdc Maximum Power Point Tracking Photovoltaic Charge Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

SOLAR BOOST™ 2000E

25AMP 12VDC MAXIMUM POWER POINT TRACKING


PHOTOVOLTAIC CHARGE CONTROLLER

INSTALLATION AND OPERATION


MANUAL

THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODEL SB2000E


SAVE THESE INSTRUCTIONS.

COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS


6,111,391

© Blue Sky Energy, Inc. 2011 430-0012 H

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

TABLE OF CONTENTS

IMPORTANT SAFETY INSTRUCTIONS ................................................................................................................................ 2

PRODUCT DESCRIPTION...................................................................................................................................................... 3
Part Numbers and Options ..................................................................................................................................... 3

OPERATION ......................................................................................................................................................................... 3
Charge Control ....................................................................................................................................................... 4
Charge Status Indicator.......................................................................................................................................... 3
Battery Level Graphic ............................................................................................................................................. 4
Equalization ............................................................................................................................................................ 4
Current Limit ........................................................................................................................................................... 4
Optional Temperature Compensation .................................................................................................................... 5
Maximum Power Point Tracking (MPPT) ............................................................................................................... 5

INSTALLATION....................................................................................................................................................................... 5
Electrostatic Handling Precautions......................................................................................................................... 5
Selecting PV Modules ............................................................................................................................................ 6
Temperature Compensation ................................................................................................................................... 6
Battery and PV Wiring ............................................................................................................................................ 6
Setting Charge Voltage .......................................................................................................................................... 7
Maximum Power Voltage ....................................................................................................................................... 7
Optimizing MPPT ........................................................................................................................... 7

TROUBLESHOOTING GUIDE ................................................................................................................................................ ..8

SPECIFICATIONS ................................................................................................................................................................... ..9

FIVE YEAR LIMITED WARRANTY......................................................................................................................................... ..9

TABLES AND FIGURES


Table 1 Charge Status Indicator ................................................................................................................. 3
Table 2 Maximum Conductor Length - 3% Voltage Drop............................................................................ 7
Figure 1 Front Panel and Remote Display Indicators................................................................................... 4
Figure 2 Factory Charge Voltage Setpoint -vs.- Battery Temperature ......................................................... 5
Figure 3 Setup and Wiring Diagram ............................................................................................................. 7
Figure 4 Mounting Template ........................................................................................................................ 10

Downloaded from www.Manualslib.com manuals search engine


Installation and Operation Manual

IMPORTANT SAFETY INSTRUCTIONS


This manual contains important instructions for Model SB2000E
SAVE THESE INSTRUCTIONS
1. Refer installation and servicing to qualified service personnel. High voltage is present inside unit. Incorrect installation or use may result in risk of electric shock
or fire. No user serviceable parts in this unit.
2. To reduce the risk of electric shock, fire or personal injury, the following symbols are placed throughout this manual to indicate dangerous conditions, or
important safety or operational instructions.

WARNING CAUTION IMPORTANT

)
Indicates dangerous conditions or electric Indicates items critical to safe installation or Follow these instructions closely for proper
shock potential. Use extreme caution. operation of the unit. operation of the unit

3. PERSONAL PRECAUTIONS
a) Working in the vicinity of lead-acid batteries is dangerous. Batteries produce explosive gasses during normal operation.
b) To reduce risk of battery explosion, follow these instructions and those published by battery manufacturer and manufacturer of any equipment you intend
to use in vicinity of battery.
c) Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery.
d) Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing or eyes.
e) Wear complete eye protection and clothing protection. Avoid touching eyes while working near battery.
f) If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at
least 15 minutes and get medical attention immediately.
g) NEVER SMOKE or allow a spark or flame in vicinity of battery.
h) Be extra cautious to reduce risk of dropping metal tool onto battery. It might spark or short circuit battery or other electrical part that may cause explosion.
i) Remove personal metal items such as rings, bracelets and watches when working with a lead-acid battery. A lead-acid battery can produce a short circuit
current high enough to weld a ring or the like to metal, causing a severe burn.
j) Remove all sources of power, photovoltaic and battery before servicing or installing.
4. CHARGER LOCATION & INSTALLATION
a) This unit is designed to charge 12V (6 cell) flooded or sealed type lead-acid chemistry batteries within the range of 10 to 10,000 amp-hours. Follow
battery manufacturers charging recommendations when considering this unit for use with other battery chemistry.
b) This unit employs components that tend to produce arcs or sparks. NEVER install in battery compartment or in the presence of explosive gases.
c) This unit must be installed and wired in accordance with National Electrical Code, ANSI/NFPA 70.
d) Over current protection for the battery must be provided externally. To reduce the risk of fire, connect to a circuit provided with 30 amperes maximum
branch-circuit over current protection in accordance with National Electrical Code, ANSI/NFPA 70.
e) Insure that unit is properly configured for the battery being charged.
f) This unit is not water tight. Do not expose to rain, snow or excessive moisture.
g) Insure all terminating connections are clean and tight. Battery, PV and battery temperature sensor terminals are to be tightened to 9 in-lb (1 nm).
h) Do not connect to a PV array capable of producing greater than 20 amperes of short circuit current (ISC) or 24V of open circuit voltage (VOC) @ STC.
i) This unit is not provided with a GFDI (ground-fault detector/interrupter) device and must be used with an external GFDI device as required by Article 690
of National Electrical Code for the installation location.
5. PREPARING TO CHARGE
a) Never charge a frozen battery.
b) Be sure battery is mounted in a well ventilated compartment.
c) Add distilled water in each cell of a lead-acid battery until battery acid reaches level specified by battery manufacturer.

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

PRODUCT DESCRIPTION
Solar Boost™ 2000E is a 25 amp 12 volt Maximum Power Point Tracking (MPPT) photovoltaic (PV) battery charge controller with built in digital
display. Through the use of patented MPPT technology the 2000E can increase charge current up to 30% or more compared to conventional controllers. The
2000E’s sophisticated charge control system improves battery performance and life while minimizing battery maintenance. The unit is fully protected against
voltage transients, over temperature, over current, reverse battery and reverse PV connections. An automatic current limit feature allows use of the full 25
amp capability without worrying about overload or nuisance fuse blow from excessive current. An environmentally sealed high current high reliability relay is
used to disconnect the PV array at night to prevent unwanted current drain.
PART NUMBERS AND OPTIONS
• SB2000E ............ Solar Boost 2000E charge controller
• 930-0022-20 ....... Optional battery temperature sensor
• 720-0011-01 ....... Optional wall mount box, black powder coated steel

OPERATION
Charge control and MPPT current boost operations are fully automatic. Charge turns on whenever the PV array is capable of producing approximately
0.15 amps at @ 14 volts. Note that there must be a battery in the system with a minimum voltage of 9 volts or greater for the 2000E to operate. Electronic
current limit prevents the possibility of overload by limiting output current to 25 amps regardless of available PV input current or input power.
The highly accurate digital display consumes very little power and is always on and available for use. As shown in Figure 1, the display can be
selected to show Solar Panel Current, Output Charge Current or Battery Voltage. Solar Panel Current displays current in amps flowing from the PV array to
the 2000E, whereas Output Charge Current displays current in amps flowing from the 2000E to the battery. When MPPT current boost is functioning, Output
Charge Current will be greater than Solar Panel Current. If operating conditions are such extra power is not available from the PV array and MPPT current
boost is unable to operate, Output Charge Current may show 0.1 amps less than Solar Panel Current. This is normal as the 2000E consumes approximately
0.090 amps to operate when PV charge is on. When PV charge is off, standby current consumption is quite low at approximately 0.017 amps.
Battery Voltage is measured at the 2000E’s battery terminals. Although the measurement system is highly accurate, displayed voltage may be
somewhat higher than actual battery terminal voltage when high charge current is being delivered to the battery. This is due to voltage drop in the wires
between the 2000E and battery. Error during charge can be minimized by using large low resistance wiring.

) ¾ The 2000E operates on battery power, not PV power. A battery must be connected with a minimum voltage of 9 volts for the unit
to operate.

CHARGE CONTROL
The 2000E provides a two stage charging process, Bulk and Constant Voltage. A third manually actuated Equalize mode is also available. The 2000E
will be in Bulk charge when battery voltage is below the charge voltage setpoint (factory set to 14.0 volts). During Bulk the 2000E delivers as much charge current
as possible to rapidly recharge the battery and drive battery voltage up to the charge voltage setpoint. Once the battery recovers sufficient charge for battery
voltage to rise to the charge voltage setpoint, both PV current and output charge current are reduced as necessary to control battery voltage at the charge voltage
setpoint.
CHARGE STATUS INDICATOR
A Charge Status indicator LED is provided on the 2000E panel. For small scale solar electric systems an excellent indication of a highly charged battery is
when the 2000E is able to hold the battery at the desired charge voltage setpoint. These systems usually consist of 75 – 400 watts of PV power, and charge a
battery bank in the range of perhaps 100 – 600 amp-hours. With sufficient PV power and the battery under light load so that there is at least 2 amps of net charge
current per 100 amp-hours of battery capacity, the system will show the battery to be charged when the battery is greater than approximately 90 – 95% full. When
the Charge Status LED blinks showing the 2000E to be in the constant voltage mode, the battery is considered charged.
If PV power generation is too low and/or load current is too high for there to be at least 2 amps of net charge current available per 100 amp-hours of battery
capacity the Solar Boost 2000E may be unable to hold battery voltage at the desired charge voltage setpoint. This will cause a discharged condition to be
displayed even though the battery may be highly charged. A charged condition will again be displayed if sufficient net charge current becomes available and the
battery is indeed charged. A smaller battery and/or larger PV array will tend to show a charged condition sooner.
CHARGE STATUS INDICATOR
CHARGE STATUS INDICATOR CHARGE MODE APPROXIMATE CHARGE LEVEL
OFF CHARGE OFF
CONTINUOUSLY ON BULK LESS THAN 90% FULL
BLINKING • 2 SEC ON / 2 SEC OFF CONSTANT VOLTAGE GREATER THAN 90% FULL
RAPID BLINKING • 0.2 SEC ON / 0.2 SEC OFF EQUALIZE
TABLE 1

Downloaded from www.Manualslib.com manuals search engine


Installation and Operation Manual

) ¾ The 2000E front panel serves as a heat sink for power control devices. It is normal for the front panel to be quite warm to the touch
during operation while delivering high charge current.

PANEL LAYOUT

Figure 1
BATTERY LEVEL GRAPHIC
The 2000E also provides a battery level graphic on the front panel which indicates approximate battery level versus battery voltage. The indication covers a
fairly wide range of voltage because at a given state of charge battery voltage can vary significantly depending on whether the battery is being charged, is at rest,
or is being discharged under load. A higher voltage is generally better than a lower voltage.
A battery being charged will typically range in voltage from about 12.5 volts after charge begins to perhaps 14.0 volts or greater when the battery is highly
charged. Once charge stops and the battery is delivering power to a load voltage will drop which is normal and typically ranges between about 12.6 volts when the
battery is full down to about 12.2 volts when the battery is about 50% discharged. Most battery manufacturers recommend not discharging below 50% DOD (depth
of discharge) to promote improved battery performance and life. Battery voltage will continue to fall as the battery is further discharged. Note that the voltage during
discharge will tend to be higher under light load and lower under heavy load. NEVER allow battery voltage to drop below 10.0 volts.
EQUALIZATION
¾ WARNING: Not all batteries can be safely equalized. Equalization should be performed only on vented liquid electrolyte
lead-acid batteries. Always follow battery manufacturers recommendations pertaining to equalization. Equalization applies a
relatively high voltage producing significant battery gassing. Disconnect equipment that cannot tolerate the high equalization
voltage which is temperature compensated. The 2000E equalization function is fully manual and an operator should always
plan and monitor the process.
Equalization is essentially a controlled over charge and should only be performed on vented liquid electrolyte lead-acid batteries. Repeated
charge/discharge cycles can lead to an imbalance in the specific gravity and state of charge of individual battery cells. Equalization brings all battery cells up to the
same specific gravity, and eliminates electrolyte stratification by heavily gassing the battery. Periodic equalization per the battery manufacturers recommendations
will improve battery performance and life.
A minimum net charge current of approximately 3.5 amps per 100 amp-hours of battery capacity is required for the battery reach the equalization voltage.
Battery voltage setpoint during equalization will be the present charge voltage setpoint plus 1.2 volts or 15.2 volts for the factory calibrated charge voltage setpoint
of 14.0 volts. Note that with temperature compensation, the equalization voltage can be quite high at cool temperatures. The operator should disconnect equipment
that may not tolerate the high equalization voltage applied to the battery.
As shown in Figure 1, the blue equalization push-button is located on the 2000E panel. Equalization is enabled when the push-button is in, and the Charge
Status LED blinks rapidly. Always follow the battery manufacturers recommendations pertaining to equalization. Equalization is normally conducted approximately
once per month, with the battery held at the equalization voltage for a period of approximately two hours. It is best to equalize a battery that is already fully charged
so that the desired equalization voltage is reached quickly. Following the desired equalization period, the equalization cycle is terminated and normal charge
operation is resumed by again pressing the equalization push-button. The battery should then be topped off with distilled water per the battery manufacturers
recommendations.
CURRENT LIMIT
If PV input power is high enough to produce more than 25 amps of output current, the 2000E will automatically prevent output current from exceeding
25 amps to prevent overload or nuisance fuse blow.

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

OPTIONAL TEMPERATURE COMPENSATION


The charge voltage required by flooded or sealed (AGM or GEL) lead-acid chemistry batteries changes with battery temperature. Temperature
compensation of charge voltage leads to improved battery performance and life, and decreased battery maintenance. Automatic temperature compensation
can be provided using the optional battery temperature sensor p/n 930-0022-20. Most 12 volt lead-acid chemistry batteries require a compensation
characteristic of –30.0 millivolts/°C (–5.00mV/°C/cell). The graph of Figure 2 shows charge voltage setpoint vs. battery temperature for the factory setting of
14.0 volts @ 80°F and the compensation characteristic of –30.0 millivolts/°C. As described in the installation section the 2000E can also provide a –20.0
millivolts/°C compensation characteristic required for 10 cell NiCd batteries and some GEL or AGM lead-acid chemistry batteries.
FACTORY DEFAULT CHARGE VOLTAGE SETPOINT -VS.- BATTERY TEMPERATURE

FIGURE 2
MAXIMUM POWER POINT TRACKING (MPPT)
Patented MPPT technology can extract more power and increase charge current up to 30% or more compared to conventional charge controllers. The
principal operating conditions which affect current boost performance are PV array temperature and battery voltage. At constant solar intensity, available PV
voltage and power increase as PV temperature decreases but it takes an MPPT controller to access this extra power. When PV voltage is sufficiently high in Bulk
for MPPT to operate, a constant power output is delivered to the battery. Since output power is constant a decrease in battery voltage produces a further increase
in charge current. This means that the 2000E provides the greatest charge current increase when you need it most, in cold weather with a discharged battery. In
cool comfortable temperatures most systems see about 10 – 20% increase. Charge current increase can go to zero in hot temperatures, whereas charge current
increase can easily exceed 30% with a discharged battery in near freezing temperatures. For a more complete MPPT description see www.blueskyenergyinc.com.

INSTALLATION
¾ WARNING: Read, understand and follow the Important Safety Instructions in the beginning of this manual before proceeding.
This unit must be installed and wired in accordance with National Electrical Code, ANSI/NFPA 70. Over current protection must be
provided externally. To reduce the risk of fire, connect to a circuit provided with 30 amp maximum branch-circuit over current
protection in accordance with National Electrical Code, ANSI/NFPA 70. Do not connect a PV array capable of delivering greater
than 20 amps of short circuit current ISC at STC. Do not connect BAT– and PV– together external to the unit or improper operation
or damage will result. Terminal block connections accept #20−10 AWG wire and are to be tightened to 9 in-lb (1 nm). The front
panel serves as a heat sink for power control devices and requires free air circulation for cooling. Do not enclose the front panel
behind a tight fitting door or otherwise substantially restrict air flow. Figure 3 shows generalized connections only and is not intended
to show all wiring, circuit protection and safety requirements for a photovoltaic or DC battery electrical system.

¾ CAUTION: The unit is protected against reverse battery and PV polarity, and swapped PV and battery connections, but will be
damaged by reverse battery to the PV terminals. Transient voltage protection is provided, but steady state voltage in excess of
30VDC on the battery or PV terminals will damage the unit. The unit is not water tight and must be installed in an area free from
rain, snow or excessive moisture. Damage due to improper installation, corrosion, or adjustments or connections other than those
shown in Figure 3 void the limited warranty.
ELECTROSTATIC HANDLING PRECAUTIONS
All electronic circuits may be damaged by static electricity. To minimize the likelihood of electrostatic damage, discharge yourself by touching a water faucet
or other electrical ground prior to handling the 2000E and avoid touching components on the circuit board. The risk of electrostatic damage is highest when relative
humidity is below 40%.

Downloaded from www.Manualslib.com manuals search engine


Installation and Operation Manual

SELECTING PV MODULES
Voltage, current and power produced by Photovoltaic (PV) modules fluctuate widely with operating conditions. As a result a set of test conditions
referred to as Standard Test Conditions (STC) are used to rate modules in a meaningful manner and accurately predict real world performance. STC
ratings are not maximum or optimal ratings. Conditions can be present where VOC and ISC approach 1.25 times STC ratings which is why National Electrical
Code and our recommendations call for 1.25 derating of both VOC and ISC. Yet in real world conditions IMP is commonly only about 75 – 80% of IMP at STC.
Key PV module specifications;
PMAX Maximum power in watts (PMAX = VMP x IMP)
VOC Voltage with module open circuit (typically ≈20 – 22V for 12V nominal modules)
VMP Voltage where module produces Maximum Power (typically ≈17 – 18V for 12V nominal modules)
IMP Current where module produces Maximum Power
ISC Current with module Short Circuit
The 2000E will provide the best MPPT current boost performance if all PV modules are identical. Dissimilar modules should have VMP values within
≈0.5V or better and be of the same basic cell technology so their VMP will tend to track as operating conditions change. If module types are very different
consider using a separate charge controller for each module type to obtain the best MPPT current boost performance. Select PV modules that do not exceed
the maximum ratings shown below, and preferably produce at least 3.5 amps of IMP per 100 amp-hours of battery capacity. For more detail on PV module
sizing see technical bulletin #100214 at www.blueskyenergyinc.com.

Maximum PV Power @ Maximum PV Maximum PV Recommended range of VMP at STC


STC Isc @ STC VOC @ STC Nominal 12V PV
340W 20A 24.0V 16.5 – 18.5V
TEMPERATURE COMPENSATION
For temperature compensation to operate, battery temperature sensor p/n 930-0022-20 must be installed and temperature compensation enabled via dip
switches 3 & 4. The sensor is electrically isolated and may mount to any battery terminal, but battery negative is preferred. Select a temperature compensation
characteristic that most closely matches the battery manufacturers recommendation. Most 12 volt flooded or GEL lead-acid chemistry batteries require the –
30.0 millivolts/°C (–5.00mV/°C/cell) setting. NiCd and many lead-acid chemistry AGM type batteries require the –20.0 millivolts/°C (–3.33mV/°C/cell) setting.
¾ WARNING: Do not attach a sensor or any connections other than Blue Sky Energy battery temperature sensor p/n 930-0022-20
to the temperature sensor terminals. Be certain to observe proper RED/BLK polarity as shown in Figure 3. The 2000E cannot
properly limit and control battery voltage if temperature compensation is enabled with the sensor installed reverse polarity.
Additionally, output current will be disabled if temperature compensation is enabled without the sensor installed.

SWITCH SWITCH TEMPERATURE COMPENSATION


3 4
OFF OFF DISABLED
ON ON –30.0 millivolts/°C
Flooded Lead-Acid (–5.00mV/°C/cell • 6 cells)
ON OFF –20.0 millivolts/°C
NiCd (–2.00mV/°C/cell • 10 cells) ♦ AGM Lead-Acid (–3.33mV/°C/cell • 6 cells)
BATTERY AND PV WIRING
The 2000E panel should be mounted in a dry location that provides easy routing of large size wires to the PV array and battery, and keeps PV/battery wire
length as short as practical. The location should also provide free air circulation around the front of the panel, and if possible, around the rear. Take great care not
to touch or damage circuit board components as this damage is not covered under the limited warranty. Figure 4 provides a 1:1 template for the panel cut-out.
Wiring and connections used with the 2000E can have a significant effect on current boost performance. The 2000E increases charge current by
transforming previously wasted or unharvested power into useable charge current. The effect wiring has on current boost performance is that power wasted
heating wires or connections is power that becomes unavailable to charge the battery. A desirable installation will produce a total system wiring voltage drop of 3%
or less. The lengths shown in Table 2 are one way from the PV modules to the battery with the 2000E located along the path. Wire length can be increased
inversely proportional to actual current. If current was reduced by ½ (to 10 amps), wire lengths could be doubled and still provide the same 3% voltage drop.
MAXIMUM CONDUCTOR PAIR LENGTH – 3% VOLTAGE DROP
WIRE GAUGE 12 VOLT SYSTEM @20AMPS
AWG FEET / METERS
12 AWG 6.4 / 1.9
10 AWG 10.2 / 3.1
8 AWG 16.2 / 4.9
6 AWG 25.7 / 7.8
4 AWG 40.8 / 12.5
TABLE 2

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

SETUP AND WIRING DIAGRAM

The 2000E cannot limit and


control battery voltage if
temperature compensation
is enabled with sensor
installed reverse polarity.
Output charge current will
be disabled if temperature
compensation is enabled
without sensor installed.

FIGURE 3
SETTING CHARGE VOLTAGE
Charge voltage should be set to the battery manufacturers recommendations. The factory setting of 14.0 volts is suitable for most lead-acid chemistry
batteries and does not typically require adjustment. For a predominately float application a somewhat lower voltage of 13.8 volts may be beneficial in decreasing
water loss. For a heavily cycling application, a somewhat higher voltage of 14.5V may be beneficial in decreasing charge time and increasing amp-hours delivered.
The adjustment potentiometer location is shown in Figure 3. With the Charge Status LED blinking indicating that the battery at or near full charge, adjust the charge
voltage potentiometer to the desired battery charge voltage as displayed on the 2000E digital display. If optional temperature compensation option is installed,
disable temperature compensation, adjust the charge voltage to the desired 80°F value, and then turn temperature compensation back on.
Since charge voltage is calibrated by adjusting actual battery charge voltage as displayed on the 2000E, setting charge voltage therefore requires that the
battery be at or near full charge so that the unit is actually controlling battery voltage at the charge voltage setpoint. This can sometimes be hard to achieve when
battery capacity is large compared to available PV charge current. Charge Voltage Calibration Tool P/N 930-0031-01 as described in technical bulletin #100209
simplifies charge voltage calibration be eliminating the need to have the battery be highly charged. To access this and other technical bulletins, see
www.blueskyenergyinc.com.
MAXIMUM POWER VOLTAGE
The nominal setting for this adjustment is the difference between the PV panel’s open circuit voltage (VOC) and maximum power voltage (VMP). These
voltage values are typically listed on both the PV panel datasheet and on the rating label affixed to each PV panel. This value needs to be set correctly for the
MPPT system to deliver maximum current boost. The factory setting is 4.4 volts which is the appropriate value for many popular 36 cell PV modules. These
modules typically list VOC at ≈21.4 volts and VMP at ≈17.0 volts, which yields; 21.4 volts - 17.0 volts = 4.4 volts.
OPTIMIZING MPPT
The combined effects of manufacturing tolerances in the PV panel and wiring resistance in a particular installation can sometimes shift the optimum
setting. While not required, it is recommended that for maximum MPPT current boost performance this adjustment be fine-tuned following installation. This is
a one-time setup and does not require seasonal adjustment. Fine tuning is also desirable following installation of additional PV panels or other substantial
system change.
Fine tuning is easily accomplished by slowly adjusting the MPPT adjust potentiometer to obtain maximum Output Charge Current. Adjustment is best
done in near full sun with a discharged battery and cool ambient temperatures. The red MPPT Active LED above the potentiometer turns on when MPPT is

Downloaded from www.Manualslib.com manuals search engine


Installation and Operation Manual

functioning and adjustment can be made. Verify that the LED remains on at the maximum current adjustment point, and as you check for a slight drop in
current on either side of the maximum point. If LED does not remain on, MPPT is not operating due to a combination of high PV temperature and/or high
battery voltage. MPPT can usually be made to operate by lowering battery voltage through application of a heavy DC load. If in doubt, leave the adjustment
at the factory default position of midway between 11:00 and 12:00 o’clock as shown in Figure 3. Note that the LED briefly turns off every 10 seconds while
the system recalculates the MPPT operating point.

TROUBLESHOOTING GUIDE
SYMPTOM PROBABLE CAUSE ITEMS TO EXAMINE OR CORRECT
Completely dead, no No battery power Battery disconnected, overly discharged, or connected reverse polarity. Battery powers the
display system, not PV. Battery voltage must be present for unit to operate.
Display OK, but PV disconnected Verify PV connection. Requires PV to supply at least 0.15A at ≈14V to begin charge.
system will not turn on
PV reverse polarity Reverse polarity PV will cause front panel to heat, and display to show “negative” PV current
(charge status LED
off) if battery is connected.
PV- connected to BAT- PV- & BAT- must be separate for proper operation. PV- must receive earth ground via shunts
in the 2000E which internally connect PV- to BAT-. External connection prevents proper
operation of the internal current measurement system.
Charge status LED on Dip switches set incorrectly Double check dip switches #1-4.
in Bulk, but no output
Low PV power Correct PV’s.
charge current
Charge status LED on Battery voltage greater than This is normal operation. Output is off due to high battery voltage which may be caused by
& blinking in Constant charge voltage setpoint other charging systems.
Voltage mode but no
Temp comp. enabled without Disable temp compensation, or replace sensor. Proper temp sensor terminal voltage when
output charge current
sensor, or sensor failed open connected is 2.98V at 25°C, changing at +10mV/°C.
Battery voltage too low A minimum battery voltage of ≈9.0V is required for the unit to operate.
Charge status LED on Charge current is very low and If charge current is very low (≈0.1 – 0.2A) because battery voltage is at setpoint, relays may
in Constant Voltage, the system is on the edge of switch on/off. This normal and will cause no harm. The on/off symptom will go away with a
relays click on/off being able to stay on slight increase or decrease in battery voltage, or load current.
PV- connected to BAT- PV- & BAT- must not connect together external to controller for proper operation.
Relays click on/off Dip switch #2 off Double check dip switch #2, must always be on. Used for factory test only.
rapidly
Charge status LED System in equalize mode Disable equalize by pressing the equalize pushbutton.
blinking, charge
Temp sensor failed short, or Replace sensor, or remove sensor and disable temp compensation. Proper temp sensor
voltage high
installed reverse polarity terminal voltage when connected is 2.98V at 25°C, changing at +10mV/°C.
Charge current is Battery is highly charged Normal operation, system will be in Constant Voltage mode and current is reduced to control
lower than expected, battery voltage.
PV current may be low
Worn out PV modules Replace, or use as is.
as well
Low insolation Atmospheric haze, PV’s dirty, sun low on horizon, etc.
PV- connected to BAT- PV- & BAT- must be separate for proper operation. PV- must receive earth ground via shunts
inside the 2000E which internally connect PV- to BAT-. External connection prevents proper
operation of the internal current measurement system.
MPPT improperly setup See Maximum Power Voltage and Optimizing MPPT sections.
MPPT Current boost is PV maximum power voltage May result from PV’s with low VMP. PV’s with higher VMP produce greater power and current
less than expected (VMP) is not much higher than boost potential. PV’s with VMP ≥ 17V work best, PV’s with <36 cells tend to work poorly.
battery voltage, leaving little
extra power to be extracted Excessive PV wiring voltage drop due to undersize wiring, poor connections, etc., consumes
and wastes available power. This simulates having PV’s with low VMP.
Battery is nearly charged and battery voltage is near setpoint. Output during MPPT operation
is “constant power” so higher battery voltage produces less charge current.

PV’s hot VMP and available power decrease with increasing PV cell temperature. Cooler PV’s will
produce greater boost. MPPT LED off indicates that extra power is not available from PV
array. It is normal for boost to decrease as temperature rises.
MPPT improperly setup See Maximum Power Voltage and Optimizing MPPT sections.
At high temperature, System temporarily shuts Improve ventilation or reduce PV power. Providing sufficient ventilation or operating
unit shuts down down due to high temperature conditions which do not cause over temperature shut down will improve reliability.

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

SPECIFICATIONS

Output current rating ........................................ 25A Temperature compensation coefficient


System voltage ................................................. 12V nominal Lead-acid ....................................... -30.0mV/°C
Max. PV Open circuit voltage........................... 30V NiCd ............................................... -20.0mV/°C
Max. battery voltage ......................................... 30V Current consumption
Output current limit ........................................... 25±1A Standby ......................................... 17mA typical
Volt meter full scale range................................ 19.99V Charge on...................................... 90mA typical
Volt meter accuracy.......................................... ±0.1% full-scale Panel dimensions............................................. 4.6”Hx6.4”Wx1.8”D
Current meter full scale range.......................... ±26A Storage temperature range ............................. -40 to +85°C
Current meter accuracy.................................... ±0.75% full-scale Specified temperature range ........................... 0 to +40°C
Charge voltage adjustment .............................. 13 - 16V typical Extended range ............................. -40 to +50°C
Equalization voltage ......................................... charge set +1.2V (will operate but may not meet specifications,
Power conversion efficiency ............................ 95% typical @ 15A see Technical Bulletin #100206)

As a part of our continuous improvement process


specifications are subject to change without prior notice.

FIVE YEAR LIMITED WARRANTY


Blue Sky Energy, Inc. (hereinafter BSE), hereby warrants to the original consumer purchaser, that the product or any part thereof shall be free from
defects due to defective workmanship or materials for a period of five (5) years subject to the conditions set forth below.
1. This limited warranty is extended to the original consumer purchaser of the product, and is not extended to any other party.
2. The limited warranty period commences on the date the product is sold to the original consumer purchaser. A copy of the original purchase receipt
identifying purchaser and date of purchase, must accompany the product to obtain warranty repairs.
3. This limited warranty does not apply to, and future warranty shall become void, for any product or part thereof damaged by; a) alteration, disassembly
or application of a foreign substance, b) repair or service not rendered by a BSE authorized repair facility, c) accident or abuse, d) corrosion, e) lightning
or other act of God, f) operation or installation contrary to instructions pertaining to the product, or g) cosmetic aging.
4. If BSE’s examination of the product determines that the product is not defective the consumer shall be charged a test and evaluation fee of $20 and be
responsible for all transportation costs and insurance related to returning the product to the consumer. The consumer is ultimately responsible for
proper installation and operation of the product and BSE’s prior troubleshooting assistance shall not serve as a waiver of the test and evaluation fee.
The test and evaluation fee is subject to change without prior notice.
5. If within the coverage of this limited warranty, BSE shall repair or replace the product at BSE’s sole discretion and return the product via standard
ground transportation of BSE’s choosing within the continental US. The consumer shall be responsible for all transportation costs and insurance to
return the product outside the continental US, and for all transportation costs and insurance related to expedited return of the product. BSE’s liability for
any defective product or any part thereof shall be limited to the repair or replacement of the product. BSE shall not be liable for any loss or damage to
person or property, or any other damages, whether incidental, consequential or otherwise, caused by any defect in the product or any part thereof.
6. Any implied warranty for merchantability or fitness for a particular purpose is limited in duration to the length of this warranty.
7. To obtain warranty repairs, contact BSE at 760-597-1642 to obtain a Returned Goods Authorization (RGA) number. Mark the outside of the package
with the RGA number and return the product, postage prepaid and insured to the address below. The consumer is responsible for all transportation
costs and insurance related to returning the product to BSE, and for any shipping damage which may void the warranty or increase the cost of repairs.

Blue Sky Energy, Inc.


2598 Fortune Way, Suite K
Vista, CA 92081 USA

800-493-7877 • 760-597-1642 • Fax 760-597-1731 • www.blueskyenergyinc.com

Downloaded from www.Manualslib.com manuals search engine


Blue Sky Energy - Solar Boost 2000E

MOUNTING TEMPLATE

Figure 4

Downloaded from www.Manualslib.com manuals search engine

You might also like