Se Inverter Installation Guide Error Codes PDF
Se Inverter Installation Guide Error Codes PDF
This addendum is a supplement to the SolarEdge Installation Guide versions 3.0 and above (P/N MAN-01-00057-3.0 and above;w
http://www.solaredge.com/sites/default/files/se-inverter-installation-guide.pdf). This document describes error codes and how to troubleshoot them.w
Error Codes
The error messages include an error number (in firmware version 3.18xx and before) or a code (in firmware version 3.19xx and later) and a description:
Error Code XXX
(3xD2)
Error Code 3xD2
<Line 1>
<Line 2>
WARNING!
All warnings and cautions in this manual should be adhered to while troubleshooting an error.
1
Troubleshooting MAN-01-00333-1.1
Error Codes
Over temperature
104, 163- Temperature Too
17 2x11 8x47, 8x77-79 o Verify proper inverter clearances.
165 High
o Make sure the heat-sink fins are clean and unobstructed.
Faulty Temp.
24 2x18 120 8x57 Broken or unconnected temperature sensor. Contact SolarEdge Support.
Sensor
2 Troubleshooting MAN-01-00333-1.1
Error # Single Phase Error # Three Phase LCD
Cause and Troubleshooting
Inverter Inverter Message
CPU v3.18xx CPU v3.19xx CPU v3.18xx CPU v3.19xx
and before and later and before and later
o Consult the grid operator.
N/A 71 8x26 VLL Min
o If permitted by local authorities, change the grid protection values.
N/A 78 8x2D Grid Sync Error Check grid voltage and frequency stability.
8x3A/8x3B/
91/92/93, 8x3C AC Over Current
N/A Contact SolarEdge support.
96/97/98 8x3F/ 8x40/ Line 1/2/3
8x41
Communication
N/A 49 8x10 Contact SolarEdge support.
Error
o Verify that the inverter is set to the correct country.
8x42, 8x43, AC Voltage Too
N/A 99-101 o Consult the grid operator.
8x44 High Line 1/2/3
o If permitted by local authorities, change the grid protection values.
Temperature Too Make sure the inverter is installed in a location with ambient temperatures within the
N/A 105 8x48
Low range specified in the datasheet.
o Refer to
www.solaredge.com/files/pdfs/application_note_isolation_fault_
N/A 114 8x51 RCD Current Surge troubleshooting.pdf
o Contact SolarEdge support.
Unbalanced DC
N/A 115 8x52 Contact SolarEdge support.
Voltage
Common Voltage
N/A 116 8x53 Contact SolarEdge support.
Too High
N/A 123 8x5A Measurement Error Contact SolarEdge support.
Ground Current –
N/A 124 8x5B Contact SolarEdge support.
RCD
AC grid voltage malfunction. When AC voltage returns the inverter should restart after
N/A 87 8x36 Islanding - Active the reconnection time.
If the problem persists, consult with the grid operator.
AC grid voltage malfunction. When AC voltage returns the inverter should restart after
144 2x90 89 8x38 Islanding - Passive the reconnection time.
If the problem persists, consult with the grid operator.
145 2x91 102 8x45 UDC Max Contact SolarEdge support.
147, 150,
147, 150, 3x11, 2x96, 3x11, 2x96,
151 Arc Fault Detected
151 2x97 2x97
Refer to http://www.solaredge.com/sites/default/files/arc_fault_
Arc detector self- detection_application_note.pdf
152 2x98 152
test failed
System Warnings
Warnings are displayed in the initial status screen with the format: <Warning X>. For example:
Vac[V] Vdc[V] Pac[W]
1.0 0.5 0.0
P_OK: XXX/YYY <S_OK>
Warning 8 ON
The warning is a status screen. To view the warning description, press the LCD button.
The following is a list of system warnings:
Warning #
CPU v3.18xx and CPU v3.19xx and LCD text Comments and troubleshooting
before later
8x66 - 8x69
1-4, 6-7 Fan # Failure Clean or replace the fan
8x6A - 8x6F
Appears when trying to access the Setup menus during
5 Turn Switch Off to Configure
production
3
Troubleshooting MAN-01-00333-1.1