Overview

The APC by Schneider Electric Metered Rack Power Distribution Unit (PDU) distributes power to
devices in the rack. It has a sensor that measures the current that it and its attached devices use. It can be
monitored through Web, Telnet, SNMP, SSH, or InfraStruXure® Central interfaces.

Outlets. The Rack PDU has thirty-six (36) IEC-320-C13 and six (6) IEC-320-C19 locking outlets .
(The locking feature is compatible with APC locking input cords and APC locking jumper cords.)

Display interface. The liquid crystal display (LCD)  and input buttons  allow you to monitor
current, power, and voltage measurements of the Rack PDU. Local communication can be established
through the serial port , and remote communication through the network port . The USB  and
CAN  ports enable data transfer and communication for future expansion options. The environmental
sensor port  allows for monitoring of the temperature and humidity of the room or enclosure.

Power cord. The 2-m (6.0-ft) power cord terminates with a 16 A, 5-pin IEC-309 connector .

Toolless mounting. The Rack PDU has two toolless mounting pegs  for 0 U mounting capability in
a rack or enclosure.
Menu
Main

Scroll

Mai n
Me nu
Select

S crol l

S el ec t
L ni k - R x/ T x

/ u mid i ty
T emp H
10 0
1 0/
In

Out
Se ria l P ort

US B
Link - Rx/Tx

Temp/Humidity
100
10/
In

Out
Serial Port

USB

pdu0468a

2 Metered Rack PDU — Overview and Specifications


Specifications

Electrical

Acceptable input voltage 380–415 VAC +6%, -10%

Maximum input current (phase) 16 A UL (derated)


16A VDE

Input frequency 50/60 Hz

Input connection 16 A, 5-pin IEC-309

Input power 11.5 kVA UL


11.0 kVA VDE

Output voltage 220–240 VAC

Maximum output current (outlet) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (derated)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Maximum output current (phase) 16 A UL (derated)


16 A VDE

Output connections Thirty-six (36) IEC-320-C13; six (6) IEC-320-C19

Physical

Dimensions (H x W x D)
(depth does not include toolless pegs) 177.8 x 5.6 x 4.4 cm (70.5 x 2.2 x 1.7 in)

Power cord length 2 m (6.0 ft)

Shipping dimensions (H x W x D) 192.4 x 16.2 x 10.7 cm (75.8 x 6.4 x 4.2 in)

Weight/shipping weight 6.2 kg (13.6 lb) / 8.1 kg (17.8 lb)

Environmental

Maximum elevation (above MSL)


Operating/Storage 0–3 000 m (0–10,000 ft) / 0–15 000 m (0–50,000 ft)

Temperature
Operating/Storage –5 to 45°C (23 to 115°F) / –25 to 65°C (–13 to 149°F)

Humidity
Operating/Storage 5–95% RH, non-condensing

Compliance

EMC verification EN 55022 Class A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Part 15 Class A, ICES-003 Class A

Safety verification UL, VDE

Customer support and warranty information is available at the APC Web site, www.apc.com. 990-3440
10/2009
© 2009 APC by Schneider Electric. All trademarks are owned by Schneider Electric Industries
S.A.S., American Power Conversion Corporation, or their affiliated companies.
Metered Rack-Stromverteilerleiste (AP8881)

S eri al P ort In Li n k - Rx/T x

M ai n
Me nu
1 0/
10 0
S c ro l l

S e el ct

US B O ut Te mp /H um di i t y

pdu0467a
Übersicht und technische Daten
Übersicht

Die Metered Rack PDU (überwachte Stromverteilerleiste) von APC by Schneider Electric verteilt Strom
an die im Rack befindlichen Geräte. Sie verfügt über einen Sensor, der den internen und den von
angeschlossenen Geräten verbrauchten Strom misst. Die Einheit kann über eine Web-Schnittstelle sowie
über Telnet, SNMP, SSH oder InfraStruXure® Central überwacht werden.

Steckdosen. Die Rack PDU verfügt über absperrbare Stromausgänge, und zwar sechsunddreißig (36)
vom Typ IEC-320-C13 und sechs (6) vom Typ IEC-320-C19 . (Die Absperrfunktion ist zu
verriegelbaren Eingangsstromkabeln von APC sowie zu verriegelbaren Überbrückungskabeln von APC
kompatibel.)

Anzeige. Die LCD-Anzeige  und die Bedientasten  ermöglichen die Überwachung der gemessenen
Stromstärke, Leistung und Spannung der Rack PDU. Für den lokalen Datenaustausch steht ein serieller
Anschluss  zur Verfügung; der Datenaustausch per Fernzugriff ist über einen Netzwerkanschluss 
möglich. Über den USB-  und den CAN-Anschluss  ist ein Datenaustausch mit späteren
Erweiterungsoptionen möglich. Über den Umgebungssensoranschluss  kann die Temperatur oder die
Luftfeuchtigkeit im Raum oder Gehäuse überwacht werden.

Netzkabel. Das 2 m (6,0 Fuß) lange Netzkabel verfügt an einem Ende über einen Anschluss vom
Typ IEC-309 (16 A, 5-polig) .

Montage ohne Werkzeuge. Die Rack PDU verfügt über zwei Montagestifte für den werkzeuglosen
Einbau  in ein Rack oder Gehäuse (0 HE).
Menu
Main

Scroll

Mai n
Me nu
S elect

S cr ol l

S el ec t
L ni k - Rx/ T x

/ u mid i ty
T emp H
10 0
1 0/
In

Out
Se r ai l P ort

U SB
Link - Rx/Tx

Temp/Humidity
100
10/
In

Out
Serial Port

USB

pdu0468a

Metered Rack-Stromverteilerleiste — Übersicht und technische Daten 5


Technische Daten

Elektrische Daten

Zulässige Eingangsspannung 380–415 VAC +6%, -10%

Maximaler Eingangsstrom (Phase) 16 A UL (unterbelastet)


16 A VDE

Eingangsfrequenz 50/60 Hz

Eingangsanschluss IEC-309 - 16 A, 5-polig

Stromeingang 11,5 kVA UL


11,0 kVA VDE

Ausgangsspannung 220–240 VAC

Maximaler Ausgangsstrom (Steckdosen) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (unterbelastet)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Maximaler Ausgangsstrom (Phase) 16 A UL (unterbelastet)


16 A VDE

Ausgangsanschlüsse Sechsunddreißig (36) IEC-320-C13; sechs (6) IEC-320-C19

Maße und Gewichte

Abmessungen (H x B x T)
(Tiefe ohne Montagestifte für werkzeuglosen Einbau) 177,8 x 5,6 x 4,4 cm (70,5 x 2,2 x 1,7 Zoll)

Länge des Netzkabels 2 m (6,0 Fuß)

Versandabmessungen (H x B x T) 192,4 x 16,2 x 10,7 cm (75,8 x 6,4 x 4,2 Zoll)

Gewicht / Versandgewicht 6,2 kg (13,6 lb) / 8,1 kg (17,8 lb)

Umgebungsbedingungen

Maximale Höhe (über dem Meeresspiegel)


Betrieb / Lagerung 0–3000 m (0–10.000 Fuß) / 0–15.000 m (0–50.000 Fuß)

Temperatur
Betrieb / Lagerung –5 bis 45 °C (23 bis 115 °F) / –25 bis 65 °C (–13 bis 149 °F)

Luftfeuchtigkeit
Betrieb / Lagerung 5–95% RH, keine Kondensation

Konformität

EMC EN 55022 Class A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Teil 15 Klasse A, ICES-003 Klasse A

Sicherheitsprüfung UL, VDE

Bei Fragen an den Kundendienst oder zur Abwicklung möglicher Garantiefälle informieren Sie sich bitte 990-3440
auf der Website von APC unter www.apc.com. 10/2009

© 2009 APC by Schneider Electric. Alle Marken sind Eigentum von Schneider Electric Industries S.A.S.,
der American Power Conversion Corporation oder ihnen angegliederter Unternehmen.
Metered Rack Power Distribution Unit (Unidad de
distribución de alimentación de rack con
medidor) (AP8881)
Información general y especificaciones

M ai n
Me nu

S c ro l l

S e el ct
Li n k - Rx/ T x

Te mp /Hum di i ty
10 /
10 0
In

O ut
S er i al P or t

US B

pdu0467a
Información general

La Metered Rack Power Distribution Unit (PDU) de APC by Schneider Electric distribuye la
alimentación a los dispositivos del rack. Dispone de un sensor que mide la corriente que usa la unidad y
los dispositivos conectados a ella. La PDU se puede supervisar a través de una interfaz Web, Telnet,
SNMP, SSH or InfraStruXure® Central.

Tomas de corriente. La PDU de rack cuenta con treinta y seis (36) tomas de corriente bloqueables
IEC-320-C13 y seis (6) IEC-320-C19 . (La característica de bloqueo es compatible con los cables de
entrada bloqueables APC y los cables de puente bloqueables APC.)

Interfaz de pantalla. La pantalla de cristal líquido (LCD)  y los botones de entrada  le permiten
supervisar las medidas de corriente, potencia y tensión de la PDU de rack. La comunicación local se
puede establecer a través del puerto serie , y la comunicación remota a través del puerto de red . Los
puertos USB  y CAN  posibilitan la transferencia de datos y la comunicación para futuras opciones
de expansión. El puerto de sensor ambiental  permite la supervisión de la temperatuva y la humedad
de la sala o armario.

Cable de alimentación. El cable de alimentación tiene una longitud de 2 m (6,0 ft) y termina en un
conector IEC-309 de 5 clavijas de 16 A .

Montaje sin herramientas. La PDU de rack tiene dos clavijas de montaje sin herramientas  que
permiten un montaje de 0 U en un rack o un armario.
Menu
Main

Scroll

Mai n
Me nu
Sele ct

S cr ol l

S elec t
L ni k -R x/T x

/ u mid i ty
T emp H
10 0
1 0/
In

O ut
Se ria l P or t

U SB
Link - Rx/Tx

Te mp/Humidity
10 0
1 0/
In

Ou t
Serial Port

USB

pdu0468a

8 PDU de rack con medidor — Información general y especificaciones


Especificaciones

Eléctricas

Tensión de entrada aceptable 380–415 V de CA +6%, -10%

Corriente máxima de entrada (fase) 16 A UL (limitada)


16A VDE

Frecuencia de entrada 50/60 Hz

Conexión de entrada IEC-309 de 5 clavijas de 16 A

Potencia de entrada 11,5 kVA UL


11,0 kVA VDE

Tensión de salida 220–240 V de CA

Corriente máxima de salida (enchufe) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (limitada)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Corriente máxima de salida (fase) 16 A UL (limitada)


16 A VDE

Conexiones de salida Treinta y seis (36) IEC-320-C13; seis (6) IEC-320-C19

Físicas

Dimensiones (Alto x Ancho x Fondo)


(el fondo no incluye las clavijas de montaje sin 177,8 x 5,6 x 4,4 cm (70,5 x 2,2 x 1,7 pulg.)
herramientas)

Longitud del cable de alimentación 2 m (6,0 ft)

Dimensiones de salida de fábrica (Alto x Ancho x 192,4 x 16,2 x 10,7 cm (75,8 x 6,4 x 4,2 pulg.)
Fondo)

Peso/Peso de salida de fábrica 6,2 kg (13,6 lb) / 8,1 kg (17,8 lb)

Ambientales

Altura máxima (sobre el nivel del mar)


Funcionamiento/almacenamiento 0–3 000 m (0–10.000 ft) / 0–15 000 m (0–50.000 ft)

Temperatura
Funcionamiento/almacenamiento –5 a 45 °C (23 a 115 °F) / –25 a 65 °C (–13 a 149 °F)

Humedad
Funcionamiento/almacenamiento 5–95% RH sin condensación

Cumplimiento

Verificación de EMC EN 55022 Clase A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Parte 15 Clase A, ICES-003 Clase A

Verificación de seguridad UL, VDE

La información sobre asistencia al cliente y garantía está disponible en el sitio Web de APC, www.apc.com. 990-3440
10/2009
© 2009 APC de Schneider Electric. Todas las marcas comerciales son propiedad de Schneider Electric
Industries S.A.S., American Power Conversion Corporation o sus empresas asociadas.
S eri al P ort In Li n k - Rx/T x

M ai n
Me nu
1 0/
10 0
S c ro l l

S e el ct

US B O ut Te mp /H um di i t y

pdu0467a
PDU à monter en rack avec compteur (AP8881)
Présentation et caractéristiques techniques
Présentation

L'unité de distribution de l'alimentation (PDU) en rack avec compteur d'APC by Schneider Electric
distribue l'alimentation aux dispositifs du rack. Elle est munie d'un capteur mesurant le courant utilisé
par la PDU et les dispositifs reliés. Elle peut être contrôlée par l'intermédiaire d'interfaces Web, Telnet,
SNMP, SSH ou de l'InfraStruXure® Central.

Prises. La PDU à monter en rack est dotée de trente-six (36) prises à verrouillage CEI-320-C13 et de
six (6) prises à verrouillage CEI-320-C19  (la fonction de verrouillage est compatible avec les cordons
d'entrée à verrouillage d'APC et les cordons d'alimentation à verrouillage d'APC).

Interface d'affichage. L'affichage à cristaux liquides (LCD)  et les boutons d'entrée  permettent de
contrôler les mesures d'intensité, de puissance et de tension de la PDU en rack. La communication locale
peut être établie par l'intermédiaire du port série , la communication à distance par l'intermédiaire du
port réseau . Les ports USB  et CAN  permettent le transfert et la communication de données pour
des options d'extension futures. Le port du capteur environnemental  permet de contrôler la
température et l'humidité de la salle ou de l'armoire.

Cordon d'alimentation. Le cordon d'alimentation de 2 m est muni à son extrémité d'un connecteur
CEI-309 de 16 A à 5 broches .

Montage sans outil. La PDU en rack comprend deux chevilles de montage sans outil  pour une
option de montage 0 U dans un rack ou une armoire.
Men u
Main

Scroll

Mai n
Me nu

S crol l
Select

S el ec t
L ni k - Rx/T x

T emp /H u mid i ty
10 0
1 0/
In

Out
Se ria l P ort

US B
Link - Rx/Tx

Temp/Humidity
10 0
1 0/
In

Ou t
Serial Port

USB

pdu0468a

PDU à monter en rack avec compteur — Présentation et caractéristiques techniques 11


Caractéristiques techniques

Circuit électrique

Tension d'entrée admissible 380-415 V c.a. +6 %, -10 %

Intensité maximale en entrée (phase) 16 A UL (déclassé)


16 A VDE

Fréquence d'entrée 50/60 Hz

Connexion d'entrée CEI-309, 16 A, 5 broches

Puissance d'entrée 11,5 kVA UL


11,0 kVA VDE

Tension de sortie 220–240 V c.a.

Intensité maximale en sortie (prise) CEI-320-C13 : 12 A ; CEI-320-C19 : 16 A UL (déclassé)


CEI-320-C13 : 10 A ; CEI-320-C19 : 16 A VDE

Intensité maximale en sortie (phase) 16 A UL (déclassé)


16 A VDE

Connexions de sortie Trente-six (36) CEI-320-C13 ; six (6) CEI-320-C19

Caractéristiques physiques

Dimensions (H x l x P)
(la profondeur ne tient pas compte des chevilles 177,8 x 5,6 x 4,4 cm
sans outil)

Longueur du cordon d'alimentation 2m

Dimensions à l'expédition (H x l x P) 192,4 x 16,2 x 10,7 cm

Poids / Poids à l'expédition 6,2 kg / 8,1 kg

Caractéristiques environnementales

Altitude maximale (au-dessus du niveau de la mer)


Fonctionnement / Stockage 0–3000 m / 0 à 15 000 m

Température
Fonctionnement / Stockage –5 à 45°C (23 à 115°F) / –25 à 65°C (–13 à 149°F)

Humidité
Fonctionnement / Stockage 5–95% HR, sans condensation

Conformité

Compatibilité électromagnétique EN 55022 Classe A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC section 15, classe A, ICES-003 classe A

Normes de sécurité UL, VDE

Pour obtenir des informations sur l'assistance et la garantie, les clients peuvent consulter le site 990-3440
Web d'APC à l'adresse www.apc.com. 10/2009

© 2009 APC by Schneider Electric. Toutes les marques déposées sont la propriété de Schneider
Electric Industries S.A.S., American Power Conversion Corporation ou de leurs filiales.
graduato (AP8881)

S er i al P or t In Li n k - Rx/ T x

M ai n
Me nu
10 /
10 0
S c ro l l

S e el ct

US B O ut Te mp /Hum di i ty

pdu0467a
Unità di distribuzione dell'alimentazione in rack

Panoramica e specifiche
Panoramica

L’unità di distribuzione dell'alimentazione in rack graduato APC by Schneider Electric distribuisce


l’alimentazione ai dispositivi nel rack. Dispone di un sensore che misura la corrente utilizzata sia
dall’unità che dai dispositivi collegati. Può essere monitorata tramite interfacce web, Telnet, SNMP,
SSH o InfraStruXure® Central.

Uscite. La PDU in rack dispone di 36 uscite IEC-320-C13 e 6 uscite di fissaggio IEC-320-C19 .


(La funzione di fissaggio è compatibile con i cavi di ingresso di fissaggio APC e con i cavi di
accoppiamento di fissaggio APC.)

Interfaccia del display. Il display LCD  e i pulsanti di ingresso  consentono di monitorare le


misurazioni di corrente, potenza e tensione della PDU in rack. È possibile stabilire la comunicazione a
livello locale tramite la porta seriale  e la comunicazione remota tramite la porta di rete . Le porte
USB  e CAN  consentono il trasferimento di dati e la comunicazione per opzioni di espansione
future. La porta del sensore ambientale  consente di eseguire il monitoraggio di temperatura e umidità
della stanza o dell’armadietto.

Cavo di alimentazione. Il cavo di alimentazione da 2 m (6 piedi) termina con un connettore da 16 A,


IEC-309 a 5 pin .

Installazione senza utensili. La PDU in rack dispone di due pioli di sostegno che non richiedono
l’uso di strumenti  per funzionalità di installazione 0 U in un rack o in un armadietto.
Menu
Main

Scroll

Mai n
Me nu
Sele ct

S cr ol l

S el ec t
L ni k -R x/T x

T emp /H u mid i ty
10 0
1 0/
In

O ut
Se ria l P or t

U SB
Link - Rx/Tx

Te mp/Humidity
10 0
1 0/
In

Ou t
Serial Port

USB

pdu0468a

14 PDU in rack graduato — Panoramica e specifiche


Specifiche

Caratteristiche elettriche

Tensione in ingresso accettabile 380–415 V c.a. +6%, -10%

Corrente massima in ingresso (fase) 16 A UL (a potenza ridotta)


16A VDE

Frequenza in ingresso 50/60 Hz

Collegamento in ingresso 16 A, IEC-309 a 5 pin

Potenza in ingresso 11,5 kVA UL


11 kVA VDE

Tensione di uscita 220–240 V c.a.

Massimo carico di corrente in uscita (uscita) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (a potenza ridotta)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Massimo carico di corrente in uscita (fase) 16 A UL (a potenza ridotta)


16 A VDE

Collegamenti in uscita 36 IEC-320-C13; 6 IEC-320-C19

Caratteristiche fisiche

Dimensioni (A x L x P)
(la profondità non comprende i pioli) 177,8 x 5,6 x 4,4 cm (70,5 x 2,2 x 1,7 pollici)

Lunghezza del cavo di alimentazione 2 m (6 piedi)

Dimensioni con imballaggio (A x L x P) 192,4 x 16,2 x 10,7 cm (75,8 x 6,4 x 4,2 pollici)

Peso/peso con imballaggio 6,2 kg (13,6 libbre) / 8,1 kg (17,8 libbre)

Caratteristiche ambientali

Altezza massima (SLM)


Di esercizio/Di stoccaggio 0–3.000 m (0–10.000 piedi) / 0–15.000 m (0–50.000 piedi)

Temperatura
Di esercizio/Di stoccaggio Da –5 a 45°C (da 23 a 115°F) / da –25 a 65°C (da –13 a 149°F)

Umidità
Di esercizio/Di stoccaggio 5–95% umidità relativa senza condensa

Conformità

Verifiche EMC EN 55022 Classe A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC parte 15 Classe A, ICES-003 Classe A

Verifiche di sicurezza UL, VDE

Le informazioni sull’assistenza clienti e sulla garanzia sono consultabili sul sito web di APC 990-3440
all’indirizzo www.apc.com. 10/2009

© 2009 APC by Schneider Electric. Tutti i marchi commerciali sono di proprietà di Electric
Industries S.A.S., American Power Conversion Corporation o di aziende affiliate.
com medição (AP8881)

S er i al P or t In Li n k - Rx/ T x

M ai n
Me nu
10 /
10 0
S c ro l l

S e el ct

US B O ut Te mp /Hum di i ty
Unidade de distribuição de energia para rack

pdu0467a
Visão geral e especificações
Visão geral

A unidade de distribuição de energia (PDU) para rack com medição da APC by Schneider Electric
distribui energia para dispositivos no rack. Possui um sensor que mede a corrente usada por ela e por
seus dispositivos conectados. Pode ser monitorada através da Web, Telnet, SNMP, SSH ou das interfaces
do InfraStruXure® Central.

Tomadas. A PDU para rack possui 36 (trinta e seis) tomadas com trava IEC-320-C13 e 6 (seis)
IEC-320-C19 . (O recurso de travamento é compatível com os cabos de entrada com trava da APC e
com os cabos jumper com trava da APC.)

Display. O display de cristal líquido (LCD)  e os botões de entrada  permitem monitorar medições
de corrente, potência e tensão da PDU para rack. A comunicação local pode ser estabelecida através da
porta serial  e a comunicação remota através da porta de rede . As portas USB  e CAN 
permitem a comunicação e a transferência de dados para futuras opções de expansão. A porta do sensor
ambiental  permite o monitoramento de temperatura e umidade da sala ou do compartimento.

Cabo de energia. O conector de terminação do cabo de energia de 2 m é um IEC-309 de 16 A e


5 pinos .

Montagem sem ferramentas. A PDU para rack possui dois prendedores para montagem sem
ferramentas  que permitem a montagem 0 U em rack ou gabinete.
Menu
Main

Scroll

Mai n
Me nu
Select

S croll

S el ec t
L ni k - R x/ T x

T emp /H u mid ity


10 0
1 0/
In

O ut
Se ria l P ort

US B
Link - Rx/Tx

Temp/Humidity
100
10 /
In

Out
Seri al Port

USB

pdu0468a

PDU para Rack com Medição — Visão Geral e Especificações 17


Especificações

Elétricas

Tensão de entrada aceitável 380 a 415 VCA +6%, -10%

Corrente máxima de entrada (fase) 16 A UL (reduzida à capacidade nominal)


16 A VDE

Frequência de entrada 50/60 Hz

Conexão de entrada IEC-309 16 A, 5 pinos

Energia de entrada 11,5 kVA UL


11,0 kVA VDE

Tensão de saída 220–240 VCA

Corrente máxima de saída (tomada) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (reduzida à


capacidade nominal)
IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Corrente máxima de saída (fase) 16 A UL (reduzida à capacidade nominal)


16 A VDE

Conexões de saída 36 (trinta e seis) IEC-320-C13; 6 (seis) IEC-320-C19

Físicas

Dimensões (A x L x P)
(a profundidade não inclui os prendedores para 177,8 x 5,6 x 4,4 cm
montagem sem ferramentas)

Comprimento do cabo de energia 2m

Dimensões para transporte (A x L x P) 192,4 x 16,2 x 10,7 cm

Peso/peso para transporte 6,2 kg / 8,1 kg

Ambientais

Altitude máxima (acima do nível médio do mar)


Operação/armazenamento 0–3.000 m / 0 a 15.000 m

Temperatura
Operação/armazenamento –5 a 45°C / –25 a 65°C

Umidade
Operação/armazenamento 5–95% Umidade relativa, não condensante

Conformidade

Verificação EMC EN 55022 Classe A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Parte 15 Classe A, ICES-003 Classe A

Verificação de segurança UL, VDE

Informações sobre o Serviço de Atendimento ao Cliente e sobre garantia estão disponíveis no site da Web da 990-3440
APC, www.apc.com. 10/2009

© 2009 APC by Schneider Electric. Todas as marcas comerciais são propriedade da Schneider Electric
Industries S.A.S., American Power Conversion Corporation ou de suas empresas controladas.
szafie (AP8881)

S er i al P or t In Li n k - Rx/ T x

M ai n
Me nu
10 /
10 0
S c ro l l

S e el ct

US B O ut Te mp /Hum di i ty
Monitorowana listwa zasilająca do montażu w

pdu0467a
Przegląd i specyfikacja
Dane ogólne

Monitorowana listwa zasilająca do montażu w szafie firmy APC by Schneider Electric zapewnia
dystrybucję zasilania do urządzeń w szafie. Jest ona wyposażona w czujnik, który mierzy prąd
zużywany przez samą listwę i podłączone do niej urządzenia. Działanie listwy może być monitorowane
za pośrednictwem interfejsu bazującego na sieci Web, usłudze Telnet, protokole SNMP, SSH lub
kontrolerze InfraStruXure® Central.

Gniazda. Listwa zasilająca do montażu w szafie jest wyposażona w trzydzieści sześć (36) gniazd
IEC-320-C13 oraz sześć (6) gniazd IEC-320-C19 z blokadami . (Blokady gniazd są kompatybilne z
wejściowymi przewodami zasilającymi APC z blokadami oraz przewodami połączeniowymi APC z
blokadami.)

Wyświetlacz. Wyświetlacz ciekłokrystaliczny (LCD)  oraz przyciski wejść  umożliwiają


monitorowanie prądu, mocy i napięcia na listwie zasilającej. Możliwe jest nawiązanie komunikacji
lokalnej przez port szeregowy  oraz komunikacji zdalnej przez port sieciowy . Porty USB  i
CAN  umożliwiają komunikację z opcjonalnymi urządzeniami dodatkowymi, jakie mogą zostać
wprowadzone w przyszłości. Port czujnika warunków otoczenia  umożliwia monitorowanie
temperatury i wilgotności w pomieszczeniu lub w obudowie.

Przewód zasilający. Przewód zasilający o długości 2,0 m jest zakończony 5-stykowym złączem
IEC-309 o prądzie znamionowym 16 A .

Montaż bez użycia narzędzi. Listwa zasilająca do montażu w szafie jest wyposażona w dwa kołki do
mocowania bez użycia narzędzi ; umożliwiają one zamontowanie listwy w szafie lub obudowie w taki
sposób, aby nie zajmowała miejsca na sprzęt (0 U).
Men u
Main

Scroll

Mai n
Me nu
Sele ct

S cr ol l

S el ec t
L ni k - R x/ T x

/ u mid i ty
T emp H
10 0
1 0/
In

Out
Se ria l P ort

U SB
Link - Rx/Tx

Te mp/Humidity
10 0
10 /
In

Ou t
Serial Port

USB

pdu0468a

20 Monitorowana listwa zasilająca do montażu w szafie — Przegląd i specyfikacja


Dane techniczne

Parametry elektryczne

Dopuszczalne napięcie wejściowe 380-415 VAC +6%, -10%

Maksymalny prąd wejściowy (faza) 16 A UL (zredukowany znamionowy)


16 A VDE

Częstotliwość na wejściu 50/60 Hz

Połączenie wejściowe 16 A, 5-stykowe IEC-309

Zasilanie na wejściu 11,5 kVA UL


11,0 kVA VDE

Napięcie na wyjściu 220–240 VAC

Maksymalny prąd na wyjściu (gniazda) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (zredukowany


znamionowy)
IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Maksymalny prąd na wyjściu (faza) 16 A UL (zredukowany znamionowy)


16 A VDE

Połączenia wyjściowe Trzydzieści sześć (36) gniazd IEC-320-C13; sześć (6) gniazd
IEC-320-C19

Parametry fizyczne

Wymiary (W x S x G)
(głębokość bez uwzględnienia kołków do mocowania) 177,8 x 5,6 x 4,4 cm (70,5 x 2,2 x 1,7 cala)

Długość przewodu zasilającego 2 m (6,0 stóp)

Wymiary transportowe (W x S x G) 192,4 x 16,2 x 10,7 cm (75,8 x 6,4 x 4,2 cala)

Ciężar/Ciężar transportowy 6,2 kg (13,6 funta) / 8,1 kg (17,8 funta)

Parametry środowiska

Maksymalna wysokość (n.p.m)


Eksploatacja/Przechowywanie 0–3 000 m (0–10 000 st.) / 0–15 000 m (0–50 000 st.)

Temperatura
Eksploatacja/Przechowywanie Od –5 do 45°C (od 23 do 115°F) /
od –25 do 65°C (od –13 do 149°F)

Wilgotność
Eksploatacja/Przechowywanie 5–95% — wilg. względna, bez kondensacji

Zgodność z normami

Atesty kompatybilności elektromagnetycznej (EMC) EN 55022 Klasa A, EN 55024, EN 61000-3-2


EN 61000-3-3, FCC Part 15 klasa A, ICES-003 klasa A

Atesty bezpieczeństwa UL, VDE

Informacje dotyczące gwarancji oraz pomocy technicznej znajdują się na stronie internetowej 990-3440
firmy APC: www.apc.com. 10/2009

© 2009 APC by Schneider Electric. Wszystkie znaki towarowe są własnością firmy Schneider
Electric Industries S.A.S., American Power Conversion Corporation lub ich firm zależnych.
Устройство распределения питания для
монтажа в стойку с функцией измерения
(AP8881)
Описание и характеристики

M ai n
Me nu

S c ro l l

S e el ct
Li n k - Rx/ T x

Te mp /Hum di i ty
10 /
10 0
In

O ut
S er i al P or t

US B

pdu0467a
Обзор

Устройство распределения питания для монтажа в стойку с функцией измерения APC компании
Schneider Electric предназначено для распределения электропитания между устройствами,
смонтированными в стойке. Оно оснащено датчиком, который измеряет ток, используемый
данным блоком и подключенными к нему устройствами. Мониторинг блока распределения
питания можно осуществлять посредством веб-интерфейса, а также с помощью интерфейсов
Telnet, SNMP, SSH или InfraStruXure® Central.

Разъемы. Устройство Rack PDU имеет тридцать шесть (36) разъемов IEC-320-C13 и шесть (6)
IEC-320-C19 запорных разъемов . (Функция запирания совместима с запорными входными
шнурами APC, а также с запорными соединительными шнурами APC.)

Интерфейс дисплея. Жидкокристаллический дисплей (LCD)  и клавиши ввода  позволяют


отслеживать значения тока, мощности и напряжения в устройстве Rack PDU. Локальное
соединение можно установить через последовательный порт , а удаленное соединение – через
сетевой порт . Порты USB  и CAN  обеспечивают возможность передачи данных в случае
расширения функций. Порт датчиков окружающей среды  позволяет отслеживать температуру
и влажность помещения или монтажного шкафа.

Кабель питания. Кабель питания имеет длину 2 м. На конце кабеля установлен 5-контактный
разъем IEC-309 16 А .

Монтаж без применения инструментов. В устройстве Rack PDU есть два монтажных
ограничителя  для 0 U монтажа в шкаф или стойку.
Menu
Main

Scroll

Mai n
Me nu

S crol l
Select

S el ec t
L ni k - R x/T x

T emp /H u mid i ty
10 0
1 0/
In

Out
Se r ai l P or t

US B
Link - Rx/Tx

Te mp/Humidity
100
10 /
In

Out
Seri al Port

USB

pdu0468a

Устройство распределения питания для монтажа в стойку с функцией измерения — 23


Описание и характеристики
Технические требования

Электрические компоненты

Допустимое входное напряжение 380–415 В переменного тока +6 %, -10 %

Максимальный входной ток (по фазам) 16 A UL (с пониженными характеристиками)


16 А VDE

Частота 50/60 Гц

Входное соединение 16 A, 5-контактный разъем IEC-309

Входная мощность 11,5 кВА UL


11,0 кВА VDE

Выходное напряжение 220–240 В переменного тока

Максимальный выходной ток (разъем) IEC-320-C13: 12 А; IEC-320-C19: 16 A UL


(с пониженными характеристиками)
IEC-320-C13: 10 А; IEC-320-C19: 16 А VDE

Максимальный выходной ток (по фазам) 16 A UL (с пониженными характеристиками)


16 А VDE

Выходные соединения Тридцать шесть (36) IEC-320-C13; шесть (6) IEC-320-C19

Физические параметры

Габариты (В x Ш x Г)
(глубина без учета штифтов для монтажа без 177,8 x 5,6 x 4,4 см
инструментов)

Длина кабеля питания 2м

Габариты при транспортировке (В x Ш x Г) 192,4 x 16,2 x 10,7 см

Вес/ вес в упаковке 6,2 кг / 8,1 кг

Окружающая среда

Максимальная высота (над средним уровнем моря)


При эксплуатации/ При хранении 0–3 000 м / 0–15 000 м

Температура
При эксплуатации/ При хранении –5 – 45 °C / –25 – 65 °C

Влажность
При эксплуатации/ При хранении 5–95 % Относительная влажность, без конденсации

Соответствие стандартам

Подтверждение EMC EN 55022 класс A, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Часть 15, Класс А, ICES-003 Класс А

Подтверждение эксплуатационной безопасности UL, VDE

Техническую поддержку и сведения о гарантийном обслуживании можно получить на веб-сайте


компании APC по адресу www.apc.com. 990-3440
© 2009 APC, компания Schneider Electric. Все товарные знаки являются собственностью компании 10/2009
Schneider Electric Industries S.A.S., American Power Conversion Corporation и их аффилированных
компаний.
S eri al P ort In Li n k - Rx/T x

M ai n
Me nu
1 0/
10 0
S c ro l l

S e el ct

US B O ut Te mp /H um di i t y
Sayaçlı Kabin İçi Güç Dağıtım Birimi (AP8881)

pdu0467a
Genel Bakış ve Teknik Özellikler
Genel Bakış

Schneider Electric'e bağlı APC'nin Sayaçlı Kabin İçi Güç Dağıtım Birimi (PDU) gücü kabin içindeki
cihazlara dağıtır. Kendisinin ve kendine bağlı cihazların kullandığı akımı ölçen bir sensöre sahiptir.
Web, Telnet, SNMP, SSH veya InfraStruXure® Central arabirimlerinden de takip edilebilir.

Çıkışlar. Kabin İçi PDU otuz altı (36) IEC-320-C13 ve altı (6) IEC-320-C19 kilit çıkışı  ile
donatılmıştır. (Kilit özelliği, kilitli APC giriş kabloları ve kilitli APC jumper kablolarıyla uyumludur.)

Görüntü arabirimi. Likit kristal ekran (LCD)  ve giriş butonları  Kabin İçin PDU'nun akım, güç ve
voltaj ölçümlerini takip etmenizi sağlar. Yerel iletişim seri port  ve uzak iletişim ağ portu 
aracılığıyla kurulabilir. USB  ve CAN  portları ileride çıkacak olan ilave seçenekler için veri
transferi yapılmasını ve iletişim kurulmasını sağlar. Ortam sensörü portu  ile odanın veya muhafazanın
sıcaklık ve nem oranı takip edilebilir.

Güç kablosu. 2 metre uzunluğundaki güç kablosunun sonunda bir 16-A, 5 pimli IEC-309 konnektör 
bulunmaktadır.

Aletsiz montaj. Kabin İçi PDU kabinde veya muhafazada 0 U montaj için iki aletsiz montaj çivisi 
ile donatılmıştır.
Menu
Main

Scroll

Mai n
Me nu
Select

S crol l

S el ec t
L ni k - R x/ T x

T emp /H u mid i ty
10 0
1 0/
In

Out
Se ria l P ort

US B
Link - Rx/Tx

Temp/Humidity
100
10/
In

Out
Serial Port

USB

pdu0468a

26 Sayaçlı Kabin İçi PDU — Genel Bakış ve Teknik Özellikler


Teknik Özellikler

Elektriksel

Uygun giriş voltajı 380-415 VAC +%6, -%10

Maksimum giriş akımı (faz) 16 A UL (düşürülmüş)


16 A VDE

Giriş frekansı 50/60 Hz

Giriş bağlantısı 16 A, 5 pim IEC-309

Giriş gücü 11,5 kVA UL


11,0 kVA VDE

Çıkış voltajı 220–240 VAC

Maksimum çıkış akımı (çıkış) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (düşürülmüş)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE

Maksimum çıkış akımı (faz) 16 A UL (düşürülmüş)


16 A VDE

Çıkış bağlantıları Otuz altı (36) IEC-320-C13; altı (6) IEC-320-C19

Fiziksel

Boyutlar (Y x G x D)
(derinlik aletsiz montaj çivilerini içermez) 177,8 x 5,6 x 4,4 cm

Güç kablosu uzunluğu 2m

Nakliye boyutları (Y x G x D) 192,4 x 16,2 x 10,7 cm

Ağırlık / nakliye ağırlığı 6,2 kg / 8,1 kg

Çevresel

Maksimum yükseklik (ortalama deniz seviyesinin üzerinde)


Çalıştırma / Depolama 0–3000 m / 0–15.000 m

Sıcaklık
Çalıştırma / Depolama –5 ila 45°C / –25 ila 65°C

Nem
Çalıştırma / Depolama %5–95 Bağıl Nem, yoğunlaşmayan

Uyum

EMC standardı EN 55022 A Sınıfı, EN 55024, EN 61000-3-2,


EN 61000-3-3, FCC Bölüm 15, A Sınıfı, ICES-003 A Sınıfı

Güvenlik standardı UL, VDE

Müşteri desteği ve garanti bilgisine APC web sitesinden www.apc.com ulaşabilirsiniz. 990-3440
10/2009
© 2009 APC, Schneider Electric tarafından alınmıştır. Bütün ticari markalar Schneider Electric
Industries S.A.S., American Power Conversion Corporation veya onlara bağlı şirketlerin
mülkiyetindedir.

You might also like